12. Glossary of display data
12.1 Main menu display functions
Display Description
SET UP Indicates that the SP500 positioner fitted to the valve has not been
NOW programmed or commissioned.
Indicates that you have now entered the SP500 main menu.
Provides access to:
SP500 • View the version of the embedded software.
MENU • Facility to centre the mounting position (CALIB).
• Retain temporary changes to menu values (RETRN).
• Recall previously stored menu values (RTAIN).
• Reset to default values (RESET).
MAN OP Provides access to manual control (MCTL) and current calibration (C-CAL).
Provides access to:
• Autostroke commissioning routine.
AUTOS Note: SET, TUNE and RUN functions can only be accessed after
a successful AUTOSTROKE routine has been completed.
• Selection of percentage travel display % (TRAVL).
Provides access to valve set up functions as follows:
• Valve type (VALVE).
• Actuator type (ACT).
• Control action (CTRLA).
SET • Minimum valve travel (MIN-T).
• Maximum valve travel (MAX-T).
• Displayed % travel (DTRVL).
• Minimum signal range (MIN-R).
• Maximum signal range (MAX-R).
Provides access to additional valve characterisation functions as follows:
• Dead-band sensitivity (dbANd).
• Valve shut-off minimum setting (S-MIN).
• Valve shut-off maximum setting (S-MAX).
TUNE • Valve signal – lift characterisation (CHAR).
• Valve slow opening time (T-UP).
• Valve slow closing time (T-dWN).
• Setting software travel switch 1 (normally open) (TS1).
• Setting software travel switch 2 (normally closed) (TS2).
Provides access to:
• Commencing automatic operation.
• Displaying percentage valve travel (%).
RUN • Visualisation of input mA input signal (mA).
• Total stem strokes (STRVL).
• Total running time (RTIME).
• Return to SP500 menu (RETRN).