Spirax Sarco APT10-2 Installation And Maintenance Instructions Manual

IM-P612-18 ST Issue 3 1
APT10-2
Automatic Pump Trap
Installation and Maintenance Instructions
IM-P612-18
ST Issue 3
6120050/3
1. General safety information
2. Product information
3. Installation
• Closed loop steam systems only
4. Commissioning
5. Operation
6. Maintenance
7. Replacement of spares (1):
• Cover gasket
• Inlet swing check valve
• Spring and actuator arm
• Float
8. Replacement of spares (2):
• Trap and outlet check valve
mechanism
• Steam inlet / exhaust valves
and seats
9. Fault finding guide
IM-P612-18 ST Issue 3
2
IM-P612-18 ST Issue 3 3
1. General safety information
Safe operation of these units can only be guaranteed if they are properly installed, commissioned and maintained by a qualified person in compliance with the operating instructions. All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibilty is safety. Post 'warning notices' if necessary. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with.
Isolation
Consider whether closing isolating valves will put any other part of the system or personnel at risk. Dangers might include: isolation of vents, protective devices or alarms. Ensure isolation valves are turned off in a gradual way to avoid system shocks.
Pressure
Before attempting any maintenance consider what is or may have been in the pipeline. Ensure that any pressure is isolated and safety vented to atmospheric pressure before attempting to maintain the product, this is easily achieved by fitting Spirax Sarco depressurisation valves type DV (see separate literature for details). Do not assume that the system is depressurised even when a pressure gauge indicates zero.
Temperature
Allow time for temperature to normalise after isolation to avoid the danger of burns and consider whether protective clothing (including safety glasses) is required.
Disposal
These products are recyclable. No ecological hazard is anticipated with the disposal of these products providing due care is taken.
IM-P612-18 ST Issue 3
4
2. Product information
Description
The Spirax Sarco automatic pump trap is a displacement receiver pressure rated to PN10. The unit is capable of automatically trapping or pumping, depending on line conditions. The unit is operated by steam and is used to remove condensate from process and heating plant under all pressure conditions including vacuum.
Sizes and pipe connections
Size DN20 x DN20
Fluid connections
Inlet Outlet Motive/Exhaust
DN20 (¾") DN20 (¾") DN15 (½")
BSP - BS 21 parallel BSP
NPT NPT
Limiting conditions
Body design conditions PN10 Maximum motive inlet pressure 2.0 bar g (29 psi g) Maximum operating pressure 2.0 bar g (29 psi g) Maximum back pressure 1.9 bar g (27 psi g) Maximum operating temperature 133°C (271°F) Minimum operating temperature -10°C(14°F) Designed for a maximum cold hydraulic test pressure of: 15.0 bar g (217 psi g) Minimum installation head (from base of pump) 0.2 m (8") Recommended minimum installation head (from base of pump) 0.3 m (12")
Technical specification - Nominal capacities
For full capacity details for a specific application consult Spirax Sarco. To accurately size the pump trap, the following data is required.
1. Installation head available, from the base of the pump trap to the centre line of the heat exchanger/ process condensate outlet (m). If the outlet is mounted vertically, then this should be from the base of the pump to the face of the outlet.
2. Motive steam pressure available to power the pump trap (bar g).
3. Total back pressure in the condensate return system (bar g). See note below.
4. Heat exchanger full load operating pressure (bar g).
5. Heat exchanger maximum steam load (kg/h).
6. Minimum temperature of secondary fluid. (°C).
7. Maximum controlled temperature of secondary fluid (°C).
Size DN20 x DN20
Pump discharge/cycle 2.1 litres
1 metre installation head
Maximum trapping capacity 735 kg/h
At: 2.0 bar g (29 psi g) motive
0.5 bar g (7 psi g) total back pressure
Maximum pumping capacity 405 kg/h
Note: Total lift or back pressure BP (static head plus pressure head in the return system) must be below the motive fluid inlet pressure to allow pump capacity to be achieved. BP (back pressure) = (H x 0.0981) + (P) + (Pf) Height (H) in metres x 0.0981 plus pressure (P) bar g in the return line, plus downstream piping friction pressure drop (Pf) in bar. (Pf can be ignored if the downstream pipework is less than 100 metres to a non-flooded condensate return and has been sized to take into account the effect of flash steam at the heat exchanger's full load operating conditions.)
IM-P612-18 ST Issue 3 5
Fig. 1
Fig. 2
Dimensions / weights (approximate) in mm and kg
Size A B C D E F G H I Weight DN20 x DN20 187 23 223 266 273 194 57 225 171 14
I
B
D
E
H
G
C
Motive steam supply
Exhaust
A
F
OUT
IN
IM-P612-18 ST Issue 3
6
Materials
No. Part Material 1 Cover SG iron DIN 1693 GGG 40.3 / ASTM A395 2 Cover gasket Graphite laminated with stainless steel insert 3 Body SG iron DIN 1693 GGG 40.3 / ASTM A395 4 Cover bolts Stainless steel BS EN ISO 3506 Gr. A2 70 5 Pump trap lever Stainless steel BS 1449 304 S15 6 Float Stainless steel BS 1449 304 S16 7 Pivot shaft Stainless steel BS 970 431 S29 / ASTM A276 431 8 Washer Stainless steel BS 1449 316 9 Trap housing Stainless steel BS 970 431 S29 / ASTM A276 431 10 Ball ASTM A276 440 B 11 Seat (inlet check valve) Stainless steel AISI 420 12 Flap (inlet check valve) Stainless steel BS 3146 ANC 4B
13
Pump mechanism
Stainless steel BS 3146 ANC 4B
bracket
14 Spring (pump) Stainless steel BS 2056 302 S26 Gr. 2 15 Split pin Stainless steel BS 1574 16 Exhaust seat Stainless steel BS 970 431S29 / ASTM A276 431 17 Inlet valve and seat assembly Stainless steel 18 Exhaust valve Stainless steel BS 3146 ANC 2 19 Valve seat gasket Stainless steel BS 1449 409 S19 20 Pump mechanism bolt Stainless steel BS EN ISO 3506 Gr. A2-70 21 Float bolt Stainless steel BS EN ISO 3506 Gr. A2-70 22 Trap 1st stage valve Stainless steel BS 970 431 S29 / ASTM A276 431 23 Trap gasket Stainless steel BS 1449 409 S19 24 Actuator arm Stainless steel BS 3146 ANC 2 25 Name-plate Stainless steel BS 1449 304 S16 26 Drain plug Stainless steel DIN 17440 1.4571
Disposal
There are no hazardous materials used in the construction of this product. Any unwanted material should be recycled or disposed of in an environmentally friendly manner.
IM-P612-18 ST Issue 3 7
Fig. 3
3
12
4
6
21
12
17
13
20
14
11
24
18
5
25
26
16
Trap and
outlet check valve
mechanism
9
8
22
23 10
7
15
19
IM-P612-18 ST Issue 3
8
Important - safety note
Before any installation or maintenance procedure, always ensure that all steam or condensate lines are isolated. Ensure any residual internal pressure in the product or connecting lines is carefully relieved. Also ensure any hot parts have cooled to prevent risk of injury from burns. Always wear appropriate safety clothing before carrying out any installation or maintenance work. Always use suitable lifting gear and ensure the product is safely secured.
3.1 Inlet piping
To prevent condensate backing up into the equipment being drained, it is recommended that the inlet pipework is sufficiently sized to accumulate condensate during the pump’s discharge cycle. Generally a length and diameter of pipe to accommodate 2 litres of condensate will be sufficient. It is recommended this condensate reservoir is situated at least 1 pipe diameter below the process outlet but as high as possible above the APT10-2 inlet. It is essential that a Spirax Sarco Y-type strainer with a maximum 0.8 mm perforation screen size is fitted at the condensate inlet of the APT10-2, as shown in Fig. 5.
3.2 Recommended installation head
An installation head of at least 0.3 m (12 ins) from the base of the unit is recommended. Minimum
0.2 m (8 ins) with reduced capacity. Note: During cold start-up conditions, it is possible for hydraulic
pulsing of the inlet check valve to occur. It is advisable in this case to install a throttling isolation valve to reduce the filling pressure.
3.3 Connections (refer to installation diagram Fig. 4 opposite)
The APT10-2 has four connection ports. The DN20 (¾") port marked (IN) should be connected to the outlet of the equipment being drained. The DN20 (¾") port marked (OUT) should be connected to the condensate return line. A flow arrow indicates the correct direction of flow. The DN15 (½") port marked (S) - steam should be connected to a trapped motive steam supply. * It is important
to ensure this line is drained of condensate at all times using a Spirax Sarco steam trap and filtered using a 100 mesh strainer. The screwed DN15 (½") port marked (E) - exhaust should be
balanced back as close as possible to the condensate outlet of the equipment. This balance line must always be connected to the top of the condensate pipe; as shown in Fig. 5. Note: The APT10-2 can be secured to a level stable surface using the 2 x Ø12 mm holes drilled into the base of the cover.
3.4 Outlet piping
It is important for the outlet piping to be correctly sized to prevent excessive back pressure on the APT10-2. This pipework should be sized to take into account the effects of flash steam at the heat exchangers full load operating conditions. Refer to TR-GCM-05 for Spirax Sarco's method of sizing this pipe.
3. Installation
4. Commissioning
4.1 After ensuring the inlet and outlet pipe connections and steam motive/exhaust connections
are coupled in accordance with Fig.4 / 5, slowly open the motive steam inlet line to supply pressure to the APT10-2. Ensure the exhaust /balance line is open and not restricted in any way.
4.2 Slowly open the isolation valves in the condensate inlet and discharge lines, allowing
condensate to fill the body of the APT10-2.
4.3 The APT10-2 is now ready to operate.
4.4 When the process plant is operational, the APT10-2 will discharge condensate under all
pressure conditions into the return line.
4.4 If any irregularities are observed, recheck the installation according to the recommendations.
If the unit fails to operate, then consult the fault finding guide Section 9.
IM-P612-18 ST Issue 3 9
Steam motive 'S'
Trapped motive
steam supply
line
Removable flanged or union section for ease
of maintenance
Spirax Sarco
APT10-2
Fig. 4 Suggested coupling of motive supply and exhaust lines.
Ensure this steam
line is correctly drained of condensate at all times using a Spirax Sarco steam trap and a 100 mesh strainer is used to prevent debris entering the pump mechanism.
Fig. 5
Minimum installation
head 0.2 m
from base of pump
Spirax Sarco sized length of
pipe to act as a reservoir
Recommended the reservoir is installed at least 1 pipe diameter
below the process outlet, but as high as possible above the APT10-2 inlet.
Balance line
* Trapped motive
steam supply
Exhaust 'E'
Condensate outlet
Condensate inlet
Strainer
Soft sealing flanged or screwedDCV
Strainer
fitted with
100 mesh
screen
IN
OUT
250 mm minimum
withdrawal distance
IM-P612-18 ST Issue 3
10
5. Operation
Step 1 (Fig. 6)
The APT10-2 automatic pump trap operates on a positive displacement principle. Condensate enters the body through the inlet swing check valve causing the float to rise. The float is connected to the trap mechanism via a lever to pivot arrangement. If the upstream system pressure PS is sufficient to overcome the back pressure PB (Fig. 6), the build up of condensate will be discharged through the opening trap mechanism. In this way, the float will automatically modulate according to the rate of condensate entering the APT10-2, controlling the rate of opening and closure of the trap.
Step 3 (Fig. 8)
However, with the APT10-2, the condensate simply fills the main chamber - lifting the float until the changeover linkage is engaged, opening the motive inlet and closing the exhaust valve.
Step 2 (Fig. 7)
With some temperature controlled equipment, it is possible for the system pressure PS to be lower than the back pressure at PB (Fig. 7). If this occurs a standard trap will stall allowing the condensate to flood the equipment being drained.
Fig. 6
Fig. 7
Fig. 8
Condensate
inlet PS
Exhaust
Condensate
outlet PB
Condensate
inlet PS
Exhaust
Condensate
outlet PB
Motive steam inlet
Larger APT14 shown for illustration
IM-P612-18 ST Issue 3 11
Step 4 (Fig. 9)
The snap action mechanism ensures a rapid change from the trapping mode to the active pumping mode. With the motive inlet valve open, the pressure in the APT10-2 increases above the total back pressure and the condensate is forced out through the trap seat into the plant’s return system.
Step 5 (Fig. 10)
As the condensate level falls within the main chamber, the float re-engages the change over linkage, causing the motive inlet to close and the exhaust valve to open.
Step 6 (Fig. 11)
As the pressure inside the APT10-2 equalises with the condensate inlet pressure through the open exhaust valve, condensate re-enters via the inlet swing check valve. At the same time the outlet ball check valve ensures no condensate can drain back into the main chamber and the trapping or pumping cycle begins again.
Return to Step 1.
Fig. 11
Fig. 10
Fig. 9
Motive steam inlet
Condensate
inlet PS
Exhaust
Condensate
outlet PB
Condensate
inlet PS
Exhaust
Condensate
outlet PB
IM-P612-18 ST Issue 3
12
6.1 Mechanisms inspection and repair (Important - safety note)
Before any installation or maintenance procedure, always ensure that all steam or condensate lines are isolated. Ensure any residual internal pressure in the product or connecting lines is carefully relieved. Also ensure any hot parts have cooled to prevent risk of injury from burns. Always wear appropriate safety clothing before carrying out any installation or maintenance work. Always use suitable lifting gear and ensure the product is safely secured. When dismantling this product, care should be taken to prevent injury from the snap action mechanism. Always handle with care.
6.2 Removal and fitting of cover assembly
Please ensure the safety recommendations are observed before commencing with any maintenance of t his product.
Tools required
19 mm A/F socket, Flat blade screw driver, Torque wrench.
6.3 To remove the cover assembly
1. Disconnect all connections to the cover. Remove the cover bolts using a 19 mm A/F socket,
then carefully slide the cover assembly away from the body (225 mm minimum withdrawal distance will be needed). Lift the cover assembly to a bench or other convenient working surface and clamp securely, avoiding contact with the gasket face.
2. Visually inspect the mechanism for obvious damage. Check that it is free of dirt and scale and
operates freely when the float is moved up and down.
3. Inspect the spring assembly for damage. Make sure the valves slide freely and the spring loaded
exhaust valve moves on its guide.
4. Inspect the float to ensure it is undamaged. Check it pivots smoothly on the pump trap lever and
it is not waterlogged.
5. Ensure the inlet swing check valve is free to move and the sealing faces of both the seat and
the flap are clean and undamaged. (If the seat is badly scored or damaged a new cover assembly may be required).
6. Check the integral trap module to ensure the 1st stage valve is free from dirt and debris. Ensure
it slides open and closes smoothly.
7. It is not possible to visually check the outlet check valve without removing the trap module (refer
to Section 8 of this manual for correct removal and fitting of this part).
8. If any of the parts appear damaged or fail to work correctly, then refer to Sections 7 and 8 of
this manual for correct removal and fitting instructions.
6.4 If a new cover assembly is to be fitted
1. Ensure the gasket face in the body is clean and free from debris. Carefully slide the new cover
assembly into the existing body, whilst ensuring the new gasket (item 2) is carefully aligned with the gasket faces and no parts of it are trapped or pinched outside the sealing areas.
2. Refit the cover bolts ensuring they are sequentially tightened in opposing pairs, gradually
increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
Bolt size Socket size Tightening torque
M12 x 40 19 mm A/F 63 ± 5 N m (46.5 ± 4 lbf ft)
3. Carefully reconnect the motive steam supply and the exhaust lines to the connections marked
(S) and (E), and the condensate inlet and outlet to the connections marked (IN) and (OUT), then foll ow t he s ta rt-up procedure in Section 4 'Commissioning' to bring the APT10-2 back into operation.
6. Maintenance
IM-P612-18 ST Issue 3 13
6.5 Spare parts
Available spares
A Cover assembly A - G inclusive B Cover gasket See page 15 C Inlet check valve See page 15 D Spring and actuator arm See page 15 E Floa t See page 15 F Trap and outlet check valve mechanism See page 15 G Inlet/exhaust valves and seat kit See page 15
Note:
Refer to F i g. 3 (page 7) for co m ponent number details. For customer convenience, spares are supplied in kits to ensure all the appropriate replacement parts are available.
Fig. 12 A Cover assembly
B
A
Cover assembly
E
G
C
F D
IM-P612-18 ST Issue 3
14
6.5 Spare parts
Available spares
A Cover assembly A - G inclusive B Cover gasket 2 C Inlet check valve 2, 12 D Spring and actuator arm 2, 14, 24 E Float 2, 5, 6, 21 F Trap and outlet check valve mechanism 2, 7, 8, 9, 10, 22, 23 G Inlet/exhaust valves and seat kit 2, 16, 17, 18, 19
Note:
Refer to Fig. 3 (page 7) for component number details. For customer convenience, spares are supplied in kits to ensure all the appropriate replacement parts are available.
Fig. 13 A Cover assembly
B
A
Cover assembly
E
G
C
F D
IM-P612-18 ST Issue 3 15
F Trap and outlet check valve mechanism G Inlet / exhaust valve and seat kit
E Float
D Spring and actuator arm
C Inlet check valveB Cover gasket
Fig. 14 B - G Spares kits
12
14
24
19
17
18
19
16
10
23
22
8
9
6
5
2
7
21
IM-P612-18 ST Issue 3
16
7. Replacement of spares (1)
7.1 Replacement of cover gasket
Please ensure the safety recommendations are observed before commencing with any maintenance of this product.
Tools required
19 mm A/F socket, Flat blade screw driver, Torque wrench
To fit the new cover gasket
1. Disconnect all connections to the cover. Remove the cover bolts using a 19 mm A/F socket,
then carefully slide the cover assembly away from the body (225 mm minimum withdrawal distance will be needed). Lift the cover assembly to a bench or other convenient working surface and clamp securely, avoiding contact with the gasket face (See Fig. 15).
2. Gently remove used gasket material from the body and cover, being careful not to damage
the gasket sealing faces.
3. Carefully fit a new gasket (item 2) into the existing body (See Fig. 16).
4. Refit the cover assembly to the body, ensuring the gasket faces are carefully aligned and
no parts of the gasket are trapped or pinched outside the sealing areas.
5. Refit the cover bolts ensuring they are sequentially tightened in opposing pairs,
gradually increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
Bolt size Socket size Tightening torque
M12 x 40 19 mm A/F 63 ± 5 N m (46.5 ± 4 lbf ft)
6. Carefully reconnect the motive steam supply and the exhaust lines to the connections
marked (S) and (E), and the condensate inlet and outlet to the connections marked (IN) and (OUT). The APT10-2 is now ready to recommission.
Important - safety note
Before any installation or maintenance procedure, ensure that all steam or condensate lines are isolated. Ensure any residual internal pressure in the product or connecting lines is carefully relieved. Also ensure any hot parts have cooled to prevent risk of injury from burns. Always wear appropriate safety clothing before carrying out any installation or maintenance work. Always use suitable lifting gear and ensure the product is safely secured. When dismantling this product, care should be taken to prevent injury from the snap action mechanism. Always handle with care.
Section 7. covers the replacement of the following spares:­cover gasket, inlet swing check valve, spring and actuator arm and float.
IM-P612-18 ST Issue 3 17
Fig. 15
2
Fig. 16
IM-P612-18 ST Issue 3
18
7.2 Replacement of inlet swing check valve
Please ensure the safety recommendations are observed before commencing with any maintenance of this product.
Tools required
19 mm A/F socket, 13 mm A/F socket, Flat blade screw driver, Torque wrench, Long nose pliers
To replace the inlet swing check valve
1. Remove the cover and old gasket (see cover gasket replacement procedure, Section 7.1).
2. Lift the cover assembly to a bench or other convenient working surface and clamp securely,
avoiding contact with the gasket face.
3. Carefully remove the circlip from the end of the steam inlet valve (item 17).
4. Remove the three M8 bolts that secure the pump mechanism bracket using the 13 mm A/F
socket.
5. Lift away the pump bracket assembly (See Fig. 17). This will allow access to the inlet swing
check valve (item 12).
Note: Do not allow the spring in the pump mechanism to bend back on itself as this may damage the coils and shorten the life of the spring.
6. The swing check valve flap can now easily be withdrawn.
7. Fit a new flap, ensuring the face of the check valve flap and seat are clean and free from
damage.
8. Reassembly is the opposite to removal.
9. Tighten the three M8 bolts using the 13 mm A/F socket to 18 ± 2 N m (13 ± 1.5 lbf ft).
10. It is important to ensure a new circlip is refitted to the steam inlet valve.
11. With the mechanism fully assembled, refit the cover assembly to the body, ensuring the gasket
faces are carefully aligned and no parts of the gasket are trapped or pinched outside the sealing areas.
12. Refit the cover bolts ensuring they are sequentially tightened in opposing pairs, gradually
increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
13. Carefully reconnect the motive steam supply and the exhaust lines to the connections
marked (S) and (E), and the condensate inlet and outlet to the connections marked (IN) and (OUT). The APT10-2 is now ready to recommission.
IM-P612-18 ST Issue 3 19
Fig. 17
17
Circlip
12
IM-P612-18 ST Issue 3
20
7.3 Replacement of spring and actuator arm
Please ensure the safety recommendations are observed before commencing with any maintenance of this product.
Tools required
19 mm A/F socket, Flat blade screw driver, Torque wrench, Long nose pliers
To replace the spring and actuator arm
1. Remove the cover and old gasket (see cover gasket replacement procedure, Section 7.1).
2. Lift the cover assembly to a bench or other convenient working surface and clamp securely,
avoiding contact with the gasket face.
3. Ensure the float is at the bottom of its travel.
4. Remove the split pin and washer, from the spring retaining shaft (Y). (See Fig. 18).
5. Remove the shaft and allow the spring to drop free.
6. Draw the actuator arm downwards within its slots until the whole spring and actuator arm
assembly with the exhaust valve comes free. It may be necessary to slide the exhaust valve (item 18) backwards against its internal spring to free it from the pump bracket guide (item 13).
7. Align the slot in the exhaust valve with the tang of the actuator arm.
8. Gently rotate the exhaust valve away from the tanged spigot of the actuator arm (item 24,
shown in Fig. 18) being careful not to damage or lose the small exhaust valve compression spring.
9. The spring and actuator arm can both be replaced.
Note: There is no need to remove the spring from the actuator arm, as both these items
are supplied fully assembled in the spares kit (See Fig. 19).
10. Fitting the new spring and actuator arm is the opposite to removal. Remember to
compress the small spring within the exhaust valve (item 18) before refitting to the tanged spigot of the new actuator arm.
11. Ensure the actuator is correctly aligned and located within the slots of the pump bracket (item 13).
12. Once this is correctly located, ensure the exhaust valve can slide easily within its guides.
13. Always use new split pins and washers when refitting the spring retaining shaft (Y).
14. With the mechanism fully assembled, reposition the cover assembly with the body, ensuring
the gasket faces are carefully aligned and no parts of the gasket are trapped or pinched outside the sealing areas.
15. Refit the cover bolts ensuring they are sequentially tightened in opposing pairs,
gradually increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
16. Carefully reconnect the motive steam supply and the exhaust lines to the connections
marked (S) and (E) and the condensate inlet and outlet to the connections marked (IN) and (OUT). The APT10-2 is now ready to recommission.
IM-P612-18 ST Issue 3 21
Fig. 18
Fig. 19
13
13
18
Spring retaining shaft (Y)
18
24
IM-P612-18 ST Issue 3
22
Please ensure the safety recommendations are observed before commencing with any maintenance of this product.
Tools required
19 mm A/F socket, 13 mm A/F socket, Flat blade screw driver, Torque wrench, Long nose pliers
To replace the float and lever
1. Remove the cover and old gasket (see cover gasket replacement procedure, Section 7.1).
2. Lift the cover assembly to a bench or other convenient working surface and clamp securely,
avoiding contact with the gasket face.
3. Remove the split pin and washer from one side of the spring retaining shaft (Y) and carefully
remove. (See Fig. 20).
Note: It is extremely important this is done first to prevent over stressing the spring during Step 4.
4. Remove the split pin and washer from one side of trap pivot retaining shaft (Z) and carefully
remove.
5. Carefully slide the shafts out from their respective positions observing the orientation of the
spring and actuator arm (item 14, 24) within the pump bracket (item 13) as these will need to be refitted later.
6. Remove the split pin and washer from one side of pump pivot retaining shaft (X).
7. To remove shaft (X), the whole pump bracket (13) will need to be separated from the cover. This
can be done by unscrewing the three M8 retaining bolts, and removing the circlip from the steam inlet valve (17). Remove the pump pivot retaining shaft (X).
8. The float and lever assembly can now be removed and discarded as the replacement float
and lever is supplied fully assembled in the spares kit.
9. Assembly is the opposite to removal. Always fit new split pins and washers.
10. It is easier to fit the replacement shafts in the following sequence:- (See Fig. 21).
X. Pump pivot (shaft length 52 mm) Refit pump bracket (13) to cover and tighten the three M8 bolts using the 13 mm A/F
socket to 18 ± 2 N m (13 ± 1.5 lbf ft). Refit the new circlip to the steam inlet valve. Z. Trap pivot (shaft length 40 mm)
Y. Spring retainer (shaft length 30 mm)
leaving the spring retaining shaft until after the spring and actuator arm have been correctly aligned and located within the slot of the pump bracket (item 13). Ensure the tanged spigot of the actuator arm is correctly engaged with the exhaust valve.
11. When all the shafts have been secured using new split pins and washers, move the float to its
upper and lower limit to ensure the mechanism operates smoothly and the spring and actuator arm snaps over to operate the motive steam inlet and exhaust valves (items 17, 18). Note: The mechanism has been designed to be adjustment-free, simplifying the fitting of new parts. If after assembly the mechanism does not operate correctly, check all the parts are assembled and aligned as per the diagram.
12. With the mechanism fully assembled, refit the cover assembly to the body, ensuring the gasket
faces are carefully aligned and no parts of the gasket are trapped or pinched outside the sealing areas.
7.4 Replacement of float
IM-P612-18 ST Issue 3 23
Fig. 21
13. Refit the cover bolts ensuring they are sequentially tightened in opposing pairs, gradually
increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
14. Carefully reconnect the motive steam supply and the exhaust lines to the connections
marked (S) and (E) and the condensate inlet and outlet to the connections marked (IN) and (OUT). The APT10-2 is now ready to recommission.
Cover
13
Fig. 20
18
Spring retaining shaft (Y)
13
183 x M8
bolts
14
Pump pivot retaining shaft (X)
24
Trap pivot retaining shaft (Z)
17
IM-P612-18 ST Issue 3
24
8. Replacement of spares (2)
Important - safety note
Before any installation or maintenance procedure, ensure that all steam or condensate lines are isolated. Ensure any residual internal pressure in the product or connecting lines is carefully relieved. Also ensure any hot parts have cooled to prevent risk of injury from burns. Always wear appropriate safety clothing before carrying out any installation or maintenance work. Always use suitable lifting gear and ensure the product is safely secured. When dismantling this product, care should be taken to prevent injury from the snap action mechanism. Always handle with care.
Section 8. covers the replacement of the following spares:­trap and outlet check valve mechanism and steam inlet /exhaust valves and seats.
8.1 Replacement of trap and outlet check valve mechanism
Please ensure the safety recommendations are observed before commencing with any maintenance of this product.
Tools required
19 mm A/F socket, 24 mm A/F socket, Flat blade screw driver, Torque wrench, Long nose pliers.
To fit the new trap and outlet check valve mechanism
1. Disconnect all connections to the cover. Remove the cover bolts using a 19 mm A/F socket,
then carefully slide the cover assembly away from the body (225 mm minimum withdrawal distance will be needed). Lift the cover assembly to a bench or other convenient working surface and clamp securely, avoiding contact with the gasket face.
2. Gently remove used gasket material from the body and cover being careful not to damage
the gasket sealing faces.
3. Carefully fit a new gasket (item 2) into the existing body.
4. Remove split pin, washer and shaft from the trap pivot (Z) (See Fig. 22).
5. Remove trap valve stem (item 22) from the mechanism.
6. The float and lever (items 5, 6) can now be swung up out of the way leaving access to the
trap and check valve assembly.
7. Using the 24 mm A/F socket unscrew the trap and check valve housing (item 9).
8. The whole trap and check valve assembly can now be carefully withdrawn from the cover.
9. There are no serviceable parts within this assembly; the replacement spares kit contains
all new parts.
10. Before fitting a new mechanism, clean the trap housing bore within the cover ensuring any
sludge or scale is carefully removed. Remember to fit a new gasket (item 23).
IM-P612-18 ST Issue 3 25
11. Assembly is the opposite to removal.
12.Tighten the 24 mm A/F trap housing to 125 ± 7 N m (92 ± 5 lbf ft).
13.Refit the trap valve stem and trap pivot shaft (Z) (length 40 mm) remembering to use new
split pins and washers - to the trap lever (item 5).
14.Move the float to its upper and lower limits to ensure the trap mechanism operates smoothly
and the valve stem (item 22) slides smoothly within its guide.
15.With the mechanism fully assembled, refit the cover assembly to the body, ensuring the gasket
faces are carefully aligned and no parts of the gasket are trapped or pinched outside the sealing areas.
16.Refit the cover bolts ensuring they are sequentially tightened in opposing pairs, gradually
increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
Bolt size Socket size Tightening torque
M12 x 45 19 mm A/F 63 ± 5 N m (46.5 ± 4 lbf ft).
17.Carefully reconnect the motive steam supply and the exhaust lines to the connections
marked (S) and (E), and the condensate inlet and outlet to the connections marked (IN) and (OUT). The APT10-2 is now ready to recommission.
Fig. 22
5
6
23
2
9
22
Trap pivot retaining shaft (Z)
IM-P612-18 ST Issue 3
26
8.2 Replacement of steam inlet/exhaust valves and seats
Please ensure the safety recommendations are observed before commencing with any maintenance of this product.
Tools required
13 mm, 19 mm A/F sockets, 24 mm Deep series A/F socket , Flat blade screw driver, Torque wrench, Long nose pliers
To replace the steam inlet and exhaust valve and seats
1. Remove the cover and old gasket (see cover gasket replacement procedure Section 7.1).
2. Lift the cover assembly to a bench or other convenient working surface and clamp securely,
avoiding contact with the gasket face.
3. Carefully remove the circlip from the end of the steam inlet valve (item 17).
4. Remove the three M8 bolts (items 20) using the 13 mm A/F socket.
5. Lift away the whole pump bracket assembly as this will allow access to the valve seats.
Note: Do not allow the spring in the pump mechanism to bend back on itself as this may damage the coils and shorten the life of the spring.
6. Using the 24 mm socket unscrew both the steam inlet and exhaust seats.
7. The seats, metal gaskets and steam inlet valve can now be removed.
8. Carefully clean the threads and gasket faces within the cover assembly ensuring all residues
are removed.
9. Insert the replacement steam valve assembly (item 17) and exhaust valve (item 16) according
to Fig. 23.
10. Place a new metal gasket (item 19) onto the threads of the seat before tightening into the cover.
11. Tighten the seat using the 24 mm socket to 125 ± 7 N m (92 ± 5 lbf ft).
12. The exhaust seat can be replaced in a similar way.
13. Refit the wh ol e pu mp bracket to the cover and tighten the three M8 bolts using the 13 mm
A/F socket to 18 ± 2 N m (13 ± 1.5 lbf ft).
14. It is important to ensure a new circlip is fitted to the steam inlet valve after the bracket has
been bolted in place.
15. To remove the exhaust valve (item 18), remove split pins, washers, and shaft (Y) from the top
spring pivot point. (See Fig. 24).
16. Allow the spring and actuator to drop free.
17. Draw the actuator arm downwards within its slots until the whole spring and actuator arm
assembly with the exhaust valve comes free. It may be necessary to slide the exhaust valve backwards against its internal spring to free it from the pump bracket guide (item 13).
18. Align the slot in the exhaust valve (item 18) with the tang of the actuator arm (item 24)
(See Fig. 24).
19. Gently rotate the exhaust valve away from the tanged spigot of the actuator arm.
20. Fitting the replacement exhaust valve is the opposite to removal, remembering to
compress the small spring within the new valve before refitting to the tanged spigot of the actuator arm.
IM-P612-18 ST Issue 3 27
Fig. 24
1719
Circlip
20
16
Fig. 23
13
18
Spring retaining shaft (Y)
24
(3 x M8 bolts)
IM-P612-18 ST Issue 3
28
19.Ensure the actuator is correctly aligned and located within the slots of the pump bracket (item 13).
20.Once this is correctly located, ensure the exhaust valve can slide easily within its guides.
21.Always use new split pins and washers when refitting the spring retaining shaft (Y) (30 mm long).
22.Check that the mechanism snaps over and opens and closes the valves by moving the float
to its upper and lower limit of travel. Note: The valve gear has been designed to be adjustment-free, simplifying the fitting of new parts. If after assembly the mechanism does not operate correctly, check all the parts are assembled and aligned as per Fig. 25.
23.With the mechanism fully assembled, refit the cover assembly to the body, ensuring the gasket
faces are carefully aligned and no parts of the gasket are trapped or pinched outside the sealing areas.
24.Refit the cover bolts ensuring they are sequentially tightened in opposing pairs, gradually
increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
25.Carefully reconnect the motive steam supply and the exhaust lines to the connections
marked (S) and (E) and the condensate inlet and outlet to the connections marked (IN) and (OUT). The APT10-2 is now ready to recommission.
IM-P612-18 ST Issue 3 29
Fig. 25
13
Spring retaining shaft (Y)
IM-P612-18 ST Issue 3
30
9. Fault finding guide
Caution
Installation and trouble shooting should only be performed by qualified personnel. Before any maintenance is attempted, ensure any residual internal pressure in the product or connecting lines is carefully relieved. Also ensure any hot parts have cooled to prevent risk of injury from burns. Always wear appropriate safety clothing before carrying out any installation or maintenance work.
Always use suitable lifting gear and ensure the product is safely secured. When dismantling this product, care should be taken to prevent injury from the snap action mechanism. Always handle with care.
The APT10-2 has been thoroughly tested before it leaves the factory. This includes a comprehensive functional test. If the unit has failed to operate it is likely that an installation problem could exist. Please check the following before commencing with the trouble-shooting chart.
9.1 Trouble areas to check first:-
• Are all isolating valves open?
• Is the condensate inlet strainer ( as recommended in Fig. 5 page 9) clean and free from debris?
• Does the installation head available exceed 0.2 m from the base of the pump?
• Is the available motive pressure higher than the total back pressure (not exceeding 2.0 bar g (29 psi g)?
• Is the exhaust balance line (E) connected to the outlet of the equipment being drained and is it free from obstruction (refer to installation diagram Fig. 5, page 9)?
• Is the direction of flow though the unit correct, indicated by the flow arrow?
IM-P612-18 ST Issue 3 31
9.2 Quick reference trouble-shooting guide
SYMPTOM APT10-2 fails to operate on start-up
CAUSE 1 No motive presure. CHECK and CURE Motive supply pressure exceeds total back pressure.
CAUSE 2 Inlet isolation valve maybe closed. CHECK and CURE Inlet pipe is free from obstructions and the isolation valve is open.
CAUSE 3 Motive inlet and exhaust lines incorrectly connected. CHECK and CURE Motive = S, Exhaust = E.
CAUSE 4 The rate of condensate produced by the process maybe very low, causing
the APT to cycle slowly.
CHECK and CURE The process being drained is operating correctly.
SYMPTOM Equipment flooded - but APT10-2 appears to cycle normally
CAUSE 1 APT is undersized for the application. CHECK and CURE Check system parameters agree with the custom sizing sheet / graph.
SYMPTOM Equipment flooded and APT10-2 has stopped cycling
CAUSE 1 Blocked exhaust line. CHECK and CURE Balance line is free from obstruction and is not waterlogged. Refer to
installation diagram Fig. 5 page 9.
CAUSE 2 Blocked condensate inlet line. CHECK and CURE Inspect and clean the strainer mesh, check for blockages.
CAUSE 3 Blocked condensate outlet line. CHECK and CURE Inspect line for blockages.
CAUSE 4 Damaged mechanism. CHECK and CURE Mechanism operates as per Section 6. Replace malfunctioning part.
CAUSE 5 No motive steam available. CHECK and CURE Steam supply to APT10-2 is available and at the correct pressure. Motive
pressure must exceed total back pressure.
CAUSE 6 Leaking motive inlet valve. CHECK and CURE If APT10-2 body is hot (observe safety note), this indicates the APT10's
mechanism is stuck on the discharge cycle. Check mechanism for excessive friction as per Section 6. Check motive inlet valve - replace malfunctioning part as per Section 8.
CAUSE 7 Broken spring. CHECK and CURE If APT10- 2 body is cold, this indicates the APT10's mechanism is stuck on
the filling cycle. Check pump mechanism spring - replace malfunctioning part as per Section 7.
CAUSE 8 Blocked condensate inlet line. CHECK and CURE Inspect and clean the filter, check for blockages.
SYMPTOM Chattering or banging of the APT10-2 during cold start-up
CAUSE 1 Hydraulic pulsing of the inlet check valve. CHECK and CURE Reduce installation head to APT - install throttling valve on APT10-2
condensate inlet.
SYMPTOM Chattering/banging in the return line after APT10-2 discharges
CAUSE 1 Live steam entering discharge line. CHECK and CURE Ensure steam traps draining the motive supply line are discharging to a
non-flooded condensate return. Condensate return is adequately sized according to TR-GCM-05.