IM-P612-18 ST Issue 3
12
6.1 Mechanisms inspection and repair (Important - safety note)
Before any installation or maintenance procedure, always ensure that all steam or
condensate lines are isolated.
Ensure any residual internal pressure in the product or connecting lines is carefully
relieved. Also ensure any hot parts have cooled to prevent risk of injury from burns.
Always wear appropriate safety clothing before carrying out any installation or
maintenance work.
Always use suitable lifting gear and ensure the product is safely secured.
When dismantling this product, care should be taken to prevent injury from the snap action
mechanism. Always handle with care.
6.2 Removal and fitting of cover assembly
Please ensure the safety recommendations are observed before commencing with any
maintenance of t his product.
Tools required
19 mm A/F socket, Flat blade screw driver, Torque wrench.
6.3 To remove the cover assembly
1. Disconnect all connections to the cover. Remove the cover bolts using a 19 mm A/F socket,
then carefully slide the cover assembly away from the body (225 mm minimum withdrawal
distance will be needed). Lift the cover assembly to a bench or other convenient working surface
and clamp securely, avoiding contact with the gasket face.
2. Visually inspect the mechanism for obvious damage. Check that it is free of dirt and scale and
operates freely when the float is moved up and down.
3. Inspect the spring assembly for damage. Make sure the valves slide freely and the spring loaded
exhaust valve moves on its guide.
4. Inspect the float to ensure it is undamaged. Check it pivots smoothly on the pump trap lever and
it is not waterlogged.
5. Ensure the inlet swing check valve is free to move and the sealing faces of both the seat and
the flap are clean and undamaged. (If the seat is badly scored or damaged a new cover
assembly may be required).
6. Check the integral trap module to ensure the 1st stage valve is free from dirt and debris. Ensure
it slides open and closes smoothly.
7. It is not possible to visually check the outlet check valve without removing the trap module (refer
to Section 8 of this manual for correct removal and fitting of this part).
8. If any of the parts appear damaged or fail to work correctly, then refer to Sections 7 and 8 of
this manual for correct removal and fitting instructions.
6.4 If a new cover assembly is to be fitted
1. Ensure the gasket face in the body is clean and free from debris. Carefully slide the new cover
assembly into the existing body, whilst ensuring the new gasket (item 2) is carefully aligned with
the gasket faces and no parts of it are trapped or pinched outside the sealing areas.
2. Refit the cover bolts ensuring they are sequentially tightened in opposing pairs, gradually
increasing torque to 63 ± 5 N m (46.5 ± 4 lbf ft).
Bolt size Socket size Tightening torque
M12 x 40 19 mm A/F 63 ± 5 N m (46.5 ± 4 lbf ft)
3. Carefully reconnect the motive steam supply and the exhaust lines to the connections marked
(S) and (E), and the condensate inlet and outlet to the connections marked (IN) and (OUT),
then foll ow t he s ta rt-up procedure in Section 4 'Commissioning' to bring the APT10-2
back into operation.
6. Maintenance