Spirax Sarco 1600V, 1800V User Manual

SOFTWARE VERSION 3.0x code 80086 / Edition 0.5 - 01/2001
ISO 9001
1600V / 1800V
CONTROLLER FOR VALVE
USERS’ MANUAL
1
1 • INSTALLATION
CE MARKING:
EMC conformity (electromagnetic compatibility) with EEC Directive 89/336/CEE with reference to the generic Standard EN50082-2 (immunity in industrial environments) and EN50081-1 (emission in residential environments). BT (low voltage) conformity respecting the Directive 73/23/CEE modified by the Directive 93/68. Limitations: the 1800V model conforms to EN55011 standard for radiated emissions in industrial environment.
MAINTENANCE:
Repairs must be carried out only by trained and specialised personnel. Remove the power to the instrument before accessing the internal parts. DO NOT clean the case with solvent (trichlorethylene, petrol, etc.). The use of such solvents can have adverse effects on the mechanical reliability of the instrument. To clean the plastic case please use a clean cloth with ethilic alcohol or water.
SERVICE:
SPIRAX-SARCO has a service department.The guarantee excludes defects
caused by usage that does not conform to the instructions.
2 • TECHNICAL SPECIFICATIONS
FUNCTION CABLE TYPE LENGTH
Power supply cable 1 mm
2
1 mt
Relais output cable 1 mm
2
3,5 mt
Digital communication wires 0,35 mm
2
3,5 mt
C.T. connection cable 1,5 mm
2
3,5 mt TC input 0,8 mm2compensated 5 mt Pt100 input 1 mm
2
3 mt
The EMC conformity has been tested with the following connections
96
115
108
96
113
10
92
92
115
48
70
115
44,5
92
113
10
108
96
To ensure a correct installation, heed the warnings in the manual
Panel mounting:
To fix the instrument, insert the brackets provided into the seats on either side of the case. To mount two or more instruments side by side, respect the cut-out dimensions shown in the drawing. In order to get the IP65 protection, take the instruments out from its case and apply the supplied gasket of the front edge of the case itself using some adhesive. The replace the instruments inside the case.
!
RTD type (scale configurable within indicated range, with or without decimal point
PTC type (on request)
DIN 43760 (Pt100, JPT100) 990, 25°C
Max line resistance for RTD
20
Safety
detection of short- or open-circuit probe, LBA alarm, HB alarm
°C / °F selection
faceplate configurable
Linear scale ranges
-1999 to 9999 with configurable decimal point position
Thermocouples
IEC 584-1 (J, K, R, S, T, B, E, N, Ni-Ni18Mo, L NiCr-CuNi)
Cold junction error
0,1° / °C
Control terms
PID, Auto-tune, on-off
pb / dt / di
0.0 ... 999.9% / 0.00 ... 99.99min / 0.00 ... 99.99min
Control actions
Heat / Cool
Control outputs
on / off, pwm, Apri / Chiudi
Cycle time
0.1 ... 200 sec
Main output type
Relay, Logic, Continuous (optional)
Softstart
0.0 ... 500.0 min
Maximum power limit heat / cool
0.0 ... 100.0 %
Fault power setting
-100.0 ... 100.0 %
Automatic blanking
Optional exclusion, displays PV value
Configurable alarms
3 configurable alarms of type: high, low, deviation, absolute or relative, LBA, HB
Alarm masking
- exclusion during warm up
- latching reset from faceplate or external contact
Type of relay contact
NO (NC), 5A, 250V, cosϕ = 1
Faceplate protection
IP65
Working / Storage temperature range
0...50°C / -20...70°C
Relative humidity
20 ... 85% Ur non condensing
Installation
Panel, plug-in from the front
Weight
400g (1600V); 600g (1800V) in complete version
Main input
TC, RTD (Pt100 - JPT100), PTC, 60mV, Ri 1M, 10V, Ri 10K, 20mA, Ri = 50
CT scale range
configurable from 0, ... , 100.0A
Transmitter power (optional)
filtered 10 / 24Vdc, max 30mA short-circuit protection, isolation 1500V
Analogue retransmission signal (optional)
10V / 20mA, isolation 1500V
Logic inputs (optional)
24V NPN, 4.5mA; 24V PNP, 3.6mA isolation 1500V
Serial interface (optional)
CL; RS422/485; RS232; isolation 1500V
Baude rate
1200 ... 19200
Protocol
GEFRAN / MODBUS
Logic output for static relay
11Vdc, Rout = 220(6V/20mA)
(option) remote set-point or Ammeter input Feed-back input Valve position from potentiometer
0 ... 10V, 2 ... 10V, Ri 1M 0 ... 20mA, 4 ... 20mA, Ri = 5 Potentiometer > 500, CT 50mAac, 50/60Hz, Ri = 1,5, isolation 1500V
Power supply (switching type)
(std) 100 ... 240Vac/dc ±10%; 50/60Hz, 12VA max (opz.) 20...27Vac/dc ±10%; 50/60Hz, 12VA max
Display
2 x 4 digits green of height 10 and 7mm (1600V), 20 and 13mm (1800V)
Keys
5 mechanical keys (*, Man/Auto, INC, DEC, F)
Accuracy
0.2% full scale a 25°C ambient temperature
SPIRAX SARCO Srl
Via Pasubio, 8
20063 Cernusco sul Naviglio
Tel. +39 02.92119511 - Fax +39 02.9240321
• Linear (V)
3 • FACEPLATE DESCRIPTION
User configurable generic
output
- 5A/250Vac relay, cosϕ=1
- 11Vdc logic, Rout = 220(6V/20mA)
Standard:
100...240Vac/dc ±10% Optional:
20...27Vac/dc ±10% 50/60Hz, 12VA max
Digital input isolated to
1500V
- NPN 24V, 4,5mA
- PNP 24V, 3,6mA (12V, 3,6mA)
• Digital inputs
4 • CONNECTIONS
• Outputs
+
-
User configurable generic
output
- 5A/250Vac relay, cosϕ = 1
- 11Vdc logic, Rout = 220 (6V/20mA))
Available thermocouples:
J, K, R, S, T, B, E, N,
Ni-Ni18Mo, L NiCr-CuNi
- Observe polarity
- For extensions, use the correct compensating cable for the type of TC used
• Inputs
• TC
2
1
Linear input in dc voltage
0...50mV, 10...50mV,
0...10V, 2...10V
Potentiometer 0...10V
2
1
+
-
8
5
7
14
16
15
17
Out3 (AL1)
IN1
IN2
COM
• Power supply
12
13
~
~
Auxiliary input
isolated 1500V
Current transformer
50mAac, 1,5, 50/60Hz
Remote setpoint
0...20, 4...20mA, 5
0...1V, 0...10V, > 1M Potentiometer > 500
• Auxiliary inputs
6
5
~
~
• Outputs
User configurable generic
output
analogue output 1500V (0 ... 10V, 0 ... 20mA, 4 ... 20mA)
11
10
+
-
Out4
(AL2 / HB)
33
31
0V
+W2
Transmitter supply
isolated 1500V
10/24Vdc, max. 30mA short-circuit protection
9
5
+
-
18
20
19
21 22
Out2 (Close) Out1 (Open)
C
32
+W1
• Transmitter supply
GND
+Vt
1800 1600
(-) NC
(-) NC
(-) NC
(+) NO
(+) NO
(+) NO
C
C
!
PWR
2
• Pt100 2-wires or PTC
Use wires of adequate
diameter
(min. 1mm2)
PT100, JPT100, PTC
• Pt100 3-wires
3
1
2
3
1
2
TT
Linear input in dc
current
0...20mA, 4...20mA
• Linear (I)
4
1
2
-
+
9
Pot
+10V
+ Vt
Gnd
Configurable serial
line isolated to 1500V
Passive current loop
(max. 1200 baud)
RS422/485 or RS232
(optional)
• Serial line
27 26 25 24
-
+
-
+
Tx
Rx
A +
B -
RS485 2-wires
GND
RS232
Tx
Rx
*” key:
Function definited defined by but.2 parameter
Auto/Manual selection:
Function definited defined by “butt” parameter
PV Display:
Indication of process variable
Error Indication: LO, HI, Sbr, Err
LO
= the value of process variable is < di LO_S
HI
= the value of process variable is > di HI_S
Sbr
= faulty sensor or input values higher
than max. limits
Err
= PT100 third wire opened, PTC or input values
lower than min. limits
(i.e.: TC wrong connection)
Function key:
Allows access to the various phases of configuration •• Confirms the change of set parameters and browses the next parameter, or the previous (if Auto/Man key is pressed)
Function indicator Indicates modes of operation MAN = OFF (Automatic control) MAN = ON (Manual control) AUX = OFF (IN1 = OFF - Local setpoint 1) AUX = ON (IN1 = ON - Local setpoint 2) REM = OFF (Local setpoint) REM = ON (Remote setpoint)
SV display:
Indication of setpoint
Indication of output states:
OUT 1 (Open); OUT 2 (Close);
OUT 3 (AL 1); OUT 4 (HB)
“Raise” and “Lower” keys:
Used to increment (decrement) any numerical parameter •• The increment (decrement) speed is proportional to the time the key remains depressed •• The operation is not cyclic. Once the maximum (minimum) value of a field is reached, the value will not change further even if the key is held down
Bargraph:
% indication of a variable defined by the
bArG parameter
12 13 14 15 16 17 18 19 20 21 22
33
11
32
10
31
9
30
8
29
7
28
6
27
5
26
4
25
3
24
2 1
3
Instrument layout
CPU Board
S4 S5
S6
S14 (S3) close Configuartion and Calibration enable
Relay state at powerr ON S2 relay Out4
A = OFF B = ON
OutW/ serial Board
Power Supply enable
B A
S3 relay Out3 A = OFF
B = ON
Relay state at power ON S2 relay Out2
S4 close = Calibration enable
B A
A B
sp.i
ts
inp.2
al.1
al.2
al.3
al.xb
0vt.p
212
5 • PROGRAMMING and CONFIGURATION
F
After 30sec, if no keys are pressed, the instrument returns automatically to PV/SV display.
This function is not present in INFO and dAtA menu.
INFO
P.V. / S.V.
Process variable (PV display)
Current setpoint (SV display)
or manual control output
Value of auxiliary input, remote
setpoint or valve position
(with auxiliary input enabled)
Alarm point 1 (scale points)
Alarm point 2 (scale points)
Alarm point 3 (scale points)
Heater break alarm point
(scale points of current transformer
input)
Control output value
(+Heat / -Cool)
Press for
approx. 2sec
Control parameters
dAtA
CFG
SEr
InP
Out
PASS = 99
Prot
Lin
CuSt
Serial communications
Input settings
Output settings
Hardware configuration
Input linearisation
Custom “dAtA” menu
_CAL
Select calibration menu [ 0...12 ]
YES
NO
Keep the F key
pressed to browse
the menus
Release the F key
to enter the
displayed menu
Press the F key to
browse the parameters
Keep the F key
pressed to exit any
menu at any time Keeping pressed
F+Auto/Man keys (whichener is the
selected menu) for
2sec, the display
immediately
changes to level 1
(*)
(*)
S3 = ON
Setpoint value
LEVEL 1 MENU
PASS
NO
YES
Hrd
U.CAL
S4 = ON
YES
NO
Menù custom
Password
User calibration
Protection code
(*) The automatic return
PV/SV
display is disabled for this parameters
1
2
3
4
5
6
7
Information display
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Timer Setpoint
0 ... 9999 sec
N.B.: Once a particular configuration is entered, all unnecessary parameters are no longer displayed
213
214
215
217
SP
-
-
­sp.2
­sp.3
­sp.4
-
--
-
-
-
rst
p.rst
a.rst
ffd
soft
xys.i
xys.2
xys.3
xb t
lba.t
lba.p
Fa(.p
gr.sp
-at-
t lo
t xi
-db-
s.tvn
h pb
h it
h dt
h.p.xi
h.p.lo
(.med
c.sp.o
c pb
c it
c dt
c.p.xi
c.p.lo
(ODE
updt
er.nr
prot
• Info display
4
• CFG
Enabling
selftuning,
autotuning,
softstart
CFG
Control parameters
Proportional band for
heating or hysteresis on
ON-OFF action
Integral time for heating
Derivative time for
heating
Maximum power limit for
heating
Proportional band for
heating or hysteresis on
ON-OFF action
Proportional band for
cooling or hysteresis on
ON-OFF action
Integral time for cooling
Derivative time for
cooling
Maximum power limit for
cooling
Manual reset
Alarm 2 hysteresis
Alarm 3 hysteresis
Waiting time for HB alarm
intervention
Waiting time for LBA alarm intervention
(Enter “0” to disable LBA alarm)
Power limit for LBA alarm condition
Power output in fault condition
(when probe is faulty)
(*)
(*)
15
16
17
18
19
20
21
22
23
24
25
31
33
34
35
36
S.tun Continuous Selftuning Softstart
Autotuning 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 - - ­7 - - ­8 WAIT NO NO 9 GO NO NO
10 WAIT YES NO 11 GO YES NO 12 WAIT NO YES 13 GO NO YES
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
-999 ... 999
scale points
0 ... 999.9%
full scale
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
± 25.0% full scale
0 ... 999.9%
full scale
± 999
scale points
± 999
scale points
0 ... 999 sec
0.0 ... 500.0 min
-100.0 ... 100.0% ON / OFF
-100.0 ... 100.0% ON / OFF
Setpoint gradient
(see notes)
0.0 ... 999.9 digit / min. (digit / sec) see SP.ty
Antireset
Feedforward
27
28
0 ... 9999
scale points
-100.0 ... 100.0%
Reset power
26
-100.0 ... 100.0%
Actuator time
(time required by the valve to move from
completely open to completely closed)
0 ... 2000 sec
Minimum pulse time
(useful to reduce mechanical stress of the valve)
0.0 ... 25.0%
Pulsating control band
(set in percentage of opening
valve time)
0.0 ... 100.0%
Dead Band, symmetrical to Setpoint and
selectable in full scale percentage
(when the process value is within this band,
the valve is locked)
Only for valve control type V0, V1, V2
0.0 ... 25.0% full scale
(*)When the LBA alarm is active, it can be reset by pushing the+ keys together when the display
shows the control output value (OutP), or switching the unit to Manual control.
216
207
208
209
210
INFO
Serial
communication
code
Software
version
Software
protection code
Self diagnostic error code
8
9
10
11
12
Information
display
0 No Error 1 Lo 2 Hi 3 ERR 4 SBR
Alarm 1 hysteresis
30
± 999
scale points
Softstart time
29
0.0 ... 500.0 min
(The value must be higher than the cycle time of the output associated to HB alarm)
Minimum power limit for
heating
(not available for double
heat/cool action)
254
0.0 ... 100.0%
Cooling Medium
97
0 ... 2
Cooling power lower limit
(not available for
heating/cooling
double action)
255
0.0 ... 100.0%
C.MEd Relative Gain (rG)
(see applicative note) 0 Air 1 1 Oil 0,8 2 Water 0,4
Remark:
h_Pb, h_it, h_dt, h.P.Hi, hPLo, c_Pb, c_it, c_dt, c.P.Hi, c.P.Lo parameters are “read only” if the option “control parameter groups” has been selected (showing current values) c_Pb, c_it, c_dt parameters “read only” if the option “relative gain heat/cool control” (Ctrl = 14) has been selected
-
-
-
-
-
-
-
-
-
-
-
-
(ode
ser.p
bavd
sp.ty
type
5
• Ser
Ser
Instrument identification code when
connected in serial line (if enabled)
[see “hrd.1” in Hrd]
Serial communications
Digital
communication
protocol:
CENCAL, MODBUS
Baudrate
38
39
40
0 ... 9999
SEr.P Digital communication protocol
0 CENCAL GEFRAN 1 MODBUS RTU
bAud Baudrate CENCAL Interface MODBUS Interface
0 1200 CL / 485 / 232 485 1 2400 485 / 232 485 2 4800 485 / 232 485 3 9600 485 / 232 485 4 19200 485 / 232 485
Parity
101
PAr Parity
0 No parity 1 Odd 2 Even
Setpoint type:
LOC/REM,
Select type of remote
setpoint [0...3]
Probe type, signal and scale of main input
tYPE Probe type Scale Scale range max. Scale range max.
(C/F) without decimal point with decimal point 0 J (Fe-CuNi) C 0 / 1000 0.0 / 999.9 1 J (Fe-CuNi) F 32 / 1832 32.0 / 999.9 2 K (NiCr-Ni) C 0 / 1300 0.0 / 999.9 3 K (NiCr-Ni) F 32 / 2372 32.0 / 999.9 4 R (Pt13Rh - Pt) C 0 / 1750 not available 5 R (Pt13Rh - Pt) F 32 / 3182 not available 6 S (Pt10Rh - Pt) C 0 / 1750 not available 7 S (Pt10Rh - Pt) F 32 / 3182 not available 8 T (Cu-CuNi) C -200 / 400 -199.9 / 400.0 9 T (Cu-CuNi) F -328 / 752 -199.9 / 752.0 10 B (Pt30Rh - Pt6Rh) C 44 / 1800 not available 11 B (Pt30Rh - Pt6Rh) F 111 / 3272 not available 12 E (NiCr-CuNi) C -100 / 750 -100.0 / 750.0 13 E (NiCr-CuNi) F -148 / 1382 -148.0 / 999.9 14 N (NiCrSi-NiSi) C 0 / 1300 0.0 / 999.9 15 N (NiCrSi-NiSi) F 32 / 2372 32.0 / 999.9 16 (Ni - Ni18Mo) C 0 / 1100 0.0 / 999.9 17 (Ni - Ni18Mo) F 32 / 2012 32.0 / 999.9 18 L - GOST (NiCr-CuNi) C 0 / 600 0.0 / 600.0 19 L - GOST (NiCr-CuNi) F 32 / 1112 32.0 / 999.9 20 TC C custom scale (*) 21 TC F custom scale (*)
tYPE Probe type Scale Scale range max. Scale range max.
(C/F) without decimal point with decimal point 0 PT100 C -200 / 850 -199.9 / 850.0 1 PT100 F -328 / 1562 -199.9 / 999.9 2 JPT100 (JIS C 1609/81) C -200 / 600 -199.9 / 600.0 3 JPT100 (JIS C 1609/81) F -328 / 1112 -199.9 / 999.9 4 RTD C custom scale (*) 5 RTD F custom scale (*)
(*) Linearisation and scale limit settings (whit or without decimal point)
are selectable from PC via serial line
PROBE: 3 wires RTD
(SEnS=1)
PROBE: PTC
(SEnS=2) (on request, alternative to 3-wires RTD)
• InP
InP
Input settings
44
45
SP.tY Type of remote Absolute
setpoint Relative 0 analogue (InP.2) absolute 1 analogue (InP.2) relative to
local setpoint
2 digital absolute
(from serial line)
3 digital relative to
(from serial line) local setpoint
SENSORE: TC
(SEnS=0)
+4 gradient to setpoint (digit/sec)
tYPE Probe type Scale Scale range max. Scale range max.
(C/F) without decimal point with decimal point 0 PTC 990 C -55 ... 120 -55.0 ... 120.0 1 PTC 990 F -67 ... 248 -67.0 ... 248.0 2 PTC 990 C custom scale (*) 3 PTC 990 F custom scale (*)
tYPE Signal type Scale Scale range max. 0 0...50mV linear -1999 / 9999 1 0...50mV custom linearised see table in menu Lin 2 10...50mV linear -1999 / 9999 3 10...50mV custom linearised see table in menu Lin
PROBE: VOLTAGE 50mV
(SEnS=3)
tYPE Signal type Scale Scale range max. 0 0...20mA linear -1999 / 9999 1 0...20mA custom linearised see table in menu Lin 2 4...20mA linear -1999 / 9999 3 4...20mA custom linearised see table in menu Lin
PROBE: CURRENT 20mA or TRANSMITTER
(SEnS=4)
tYPE Signal type Scale Scale range max. 0 0...10V linear -1999 / 9999 1 0...10V custom linearised see table in menu Lin 2 2...10V linear -1999 / 9999 3 2...10V custom linearised see table in menu Lin
PROBE: VOLTAGE 10V or TRANSMITTER
(SEnS=5)
tYPE Signal type Scale Scale range max. 0 Custom 0...10V linear -1999 / 9999
1 Custom 0...10V custom see table
linearised in menu Lin
PROBE: CUSTOM 10V
(SEnS=6)
tYPE Signal type Scale Scale range max. 0 Custom linear -1999 / 9999 1 Custom custom see table
linearised in menu Lin
PROBE: CUSTOM 50mV, 20mA
(SEnS=7)
par
-
6
xi l
lo l
of.52
xi.52
lo.52
flt.2
filt
fild
dp s
lo s
xi s
ofst
typ.2
Digital filter on main input
Digital filter on display
process variable:
acts as hysteresis
Decimal point position for
the main input scale,
alarms and
remote setpoint
(*) not available for
TC, RTD and PTC scales
Minimum limit of the main
input scale
Maximum limit of the
main input scale
Offset correction of the
main input
Digital filter on auxiliary
input (if enabled)
[see “hrd.1” in Hrd]
Function of auxiliary
analogue input
(if enabled)
[see “hrd.1” in HrD]
and custom scale
limitation enable
Minimum limit of the auxiliary input scale
(if enabled)
[see “hrd.1” in Hrd]
Maximum limit of the
auxiliary input scale
(if enabled)
[see “hrd.1” in Hrd]
Offset correction of the
auxiliary input (if enabled)
[see “hrd.1” in Hrd]
Low limit for the local
setpoint and absolute
alarms
High limit for the local setpoint and absolute
alarms
+ 8 to select custom linearisation (see table in menu Lin)
46
47
48
49
50
51
52
53
54
55
56
57
58
0.0 ... 20.0 sec
0 ... 9.9
scale points
dP_S Format
0 xxxx 1 xxx.x 2 xx.xx (*) 3 x.xxx (*)
min...max input range
selected in tyPE
min...max input range
selected in tyPE
-999 ... 999 scale points
tYP.2 Auxiliary input function
0 none 1 remote setpoint 2 remote analogue manual 3 analogue reset power 4 current transformer
input for HB
5 Valve position
0.0 ... 20.0 sec
min...max input range
selected in tyP.2
min...max input range
selected in tyP.2
-999 ... 999 scale points
Lo.S ... Hi.S
Lo.S ... Hi.S
• Out
61
Out
Output settings
Select
reference
signal for
alarm 1
AL.1.r, AL.2.r, AL.3.r
Select
reference
signal for
alarm 2
Select
reference
signal for
alarm 3
60
62
AL.x.r Variable to compare Alarm Setpoint
0 PV (process variable) AL 1 InP.2 (auxiliary input) AL 2 SSP (active setpoint) AL (only absolute) 3 PV (process variable) InP.2
(auxiliary input)
+ 4 for relative allarms only, referring to SP1 only 4available if the “multiset” function has been selected)
64
63
Alarm 1
type
Alarm 2
type
Alarm 3
type
+ 8 to disable on power up until the first interception + 16 to latch the alarm
65
AL.x.t Direct (high limit) Absolute or Normal
Inverse (low limit) Relative Symmetric
to setpoint (window) 0 direct absolute normal 1 reverse absolute normal 2 direct relative normal 3 reverse relative normal 4 direct absolute symmetric 5 reverse absolute symmetric 6 direct relative symmetric 7 reverse relative symmetric
AL.1.t, AL.2.t, AL.3.t
HB alarm
function
66
Hb_F Function description
0 Relay, logic output: alarm active on load
current level lower than setpoint during the ON time of the control outptut
1 Relay, logic output: alarm active on load
current level higher than setpoint during the OFF time of the control output
2 Alarm active if one of the functions 0 and 1
is true (OR logic between 0 and 1) (*) 3 HB alarm for heating analog output 7 HB alarm for cooling analog output
+ 0 associated to output OUT1 (only for Hb_F= 0, 1, 2) + 4 associated to output Out2 (only for Hb_F= 0, 1, 2) + 8 associated to output Out3 (only for Hb_F= 0, 1, 2) + 12 associated to output Out4 (only for Hb_F= 0, 1, 2) + 16 inverse HB alarm
(*) the minimum set is fixed at 12% f.s.
al.1.r
al.2.r
al.3.r
al.1.t
xb f
al.2.t
al.3.t
-
-
-
-
-
-
• Prot
an.o.1
l.an.1
x.an.1
an.o.2
l.an.2
x.an.2
at.ty
rl.o.1
rl.o.2
rl.o.3
rl.o.4
(t.1
(t.2
(t.3
(t.4
rel.
7
Fault action
(sets state in condition of
probe fault)
Alarm outputs AL1, AL2,
AL3; Select intrinsic safety
Minimum limit of the
analogue repetition
signal output 1
Note:
1) In case of broken probe, the logic state of the individual alarm takes up the logic value assigned without taking into account the alarm type (direct or inverse): ON=alarm active; OFF=alarm inactive
2) The assignment of the alarms to the available outputs is made by entering codes in rLo1, rLo2, rLo3, rLo4.
Maximum limit of the
analogue repetition
signal output 1
Minimum limit of the
analogue repetition
signal output 2
Maximum limit of the
analogue repetition
signal output 2
An.o.x Reference value
0 PV - process variable 1 SSP - active setpoint 2 SP - local setpoint 3 InP.2 - auxiliary input 4 Deviation (SSP-PV) 5 HEAT (*) 6 COOL (*) 7 AL1 (alarm point) 8 AL2 (alarm point)
9 AL3 (alarm point) 10 AL.HB - (alarm point) 11 Value acquired from serial line
Out W1
Allocate signal or reference value:
PV, SP, SP-PROG, DEV+, DEV-, IN.AUX, HEAT,
COOL, AL1, AL2, AL3, serial line value
Out W2
Allocate signal or reference value:
PV, SP, SP-PROG, DEV+, DEV-, IN.AUX, HEAT,
COOL, AL1, AL2, AL3, serial line value
Allocation of
reference signal
to the Out1
output:
HEAT, COOL,
AL1, AL2, AL3,
input repetition
signal
Cycle time for AL3
relay or logic
output = HEAT or
COOL
67
68
69
70
74
75
76
77
78
79
80
81
_rEL Alarm Alarm Alarm
1 2 3 0 OFF OFF OFF 1 ON OFF OFF 2 OFF ON OFF 3 ON ON OFF 4 OFF OFF ON 5 ON OFF ON 6 OFF ON ON 7 ON ON ON
-100.0 ... 100.0% for power
-1999 ... 9999 for input and setpoint
An.o.1, An.o.2
1 ... 200 sec
+ 16 for inverted output with respect to the reference value + 32 for output with 2...10V, 4...20mA signal
(*) - Fixed scale limits
- Not available with ON/OFF control action
71
72
73
Cycle time for
Main relay or logic
output = HEAT or
COOL
Cycle time for AL1
relay or logic
output = HEAT or
COOL
Cycle time for AL2
relay or logic
output = HEAT or
COOL
1 ... 200 sec
(0.1 ... 20.0 sec)
1 ... 200 sec
1 ... 200 sec
Allocation of
reference signal
to the Out2
output:
HEAT, COOL,
AL1, AL2, AL3,
input repetition
signal
Allocation of
reference signal
to the Out3
output:
HEAT, COOL,
AL1, AL2, AL3,
input repetition
signal
Allocation of
reference signal
to the Out4
output:
HEAT, COOL,
AL1, AL2, AL3,
input repetition
signal
Valve Control
Type
0 disabled 1 V0, V1 Heating control 2 V2 Heating control 3 V3, V4 Heating control
+ 4 for Cooling control + 8 for Manual control of the valve with “up” and “down” keys.
-100.0 ... 100.0% for power
-1999 ... 9999 for input and setpoint
-100.0 ... 100.0% for power
-1999 ... 9999 for input and setpoint
-100.0 ... 100.0% for power
-1999 ... 9999 for input and setpoint
rL.o.1, rL.o.2, rL.o.3, rL.o.4
+ 32 for inverse logic signal output
rL.o.x Function of main output relay/logic (OUT1)
0 HEAT (control output for heating) 1 COOL (control output for cooling) 2 AL1 - alarm 1 3 AL2 - alarm 2 4 AL3 - alarm 3 5 AL.HB - alarm HB 6 LBA - alarm LBA 7 IN1 - repetition of logic input 1 8 IN2 - repetition of logic input 2
9 Open valve 10 Close valve 11 ­12 Timer status repetition 13 Manual Set / Reset 14 (AL1) OR (AL2) 15 (AL1) OR (AL2) OR (AL3) 16 (AL1) AND (AL2) 17 (AL1) AND (AL2) AND (AL3) 18 (HBAL) OR (AL1) 19 (HBAL) OR (AL1) OR (AL2) 20 (HBAL) AND (AL1) 21 (HBAL) AND (AL1) AND (AL2)
64 Heat (control output with fast
cicle time) (*)
65 Cool (control output with fast
cicle time) (*)
(*) Only for rL.o.1, HB alarm disabled if
associated to Out 1
211
Prot
42
Protection code
Prot Display only Modification
0 SP, InP2, alarms, OutP, INFO, DATA SP, alarms, DATA 1 SP, InP2, alarms, OutP, INFO, DATA SP, alarms 2 SP, InP2, alarms, OutP, INFO SP 3 SP
+ 4 to disable InP, Out + 8 to disable CFG, Ser + 16 to disable SW “power up - power down” +32 to disable manual power latching +64 to disable manual power modification
-
-
-
-
-
sens
sns.2
al.nr
bvtt
bvt.2
d.1.f.1
d.1.f.2
disp
hrd.1
hrd.2
hrd.3
(trl
s.s.t.
r.t.
• Hrd
Hrd
Hardware configuration
Installation of
auxiliary input,
digital input, serial
interface, timer
function, multiset
function
Installation of
relay, logic
outputs
MAIN, AL1,
AL2, AL3,
and analogue
outputs W1, W2
+ 16 to enable analogue output W1 + 32 to enable analogue output W2 + 64 to invert the state of the LEDs with respect to the state of the output
+ 8 to enable HB alarm + 16 to enable LBA alarm
d.i.F.1, d.i.F.2
Function of digital
input 1 (IN1)
+ 16 for inverse logic input + 32 to force “0” logic state (OFF) + 48 to force “1” logic state (ON)
Function of digital
input 2 (IN2)
hrd.1 Auxiliary Logic Logic Serial
analogue input 1 input 2 interface
input (IN1) (IN2) 0 1 x 2 x 3 x x 4 x 5 x x 6 x x 7 x x x 8 x 9 x x
10 x x 11 x x x 12 x x 13 x x x 14 x x x 15 x x x x
hrd.2 MAIN AL1 AL2 AL3
output output output output
(relay, logic) (relay, logic) (relay, logic) (relay, logic) 0 1 x 2 x 3 x x 4 x 5 x x 6 x x 7 x x x 8 x 9 x x
10 x x 11 x x x 12 x x 13 x x x 14 x x x 15 x x x x
SnS.2 Signal
0 0 ... 1V 1 0.2 ... 1V 2 0 ... 10V 3 2 ... 10V 4 0 ... 20mA 5 4 ... 20mA 6 Potentiometer
7 CT 50mA
~
AL.nr Alarm 1 Alarm 2 Alarm 3
0 disabled disabled disabled 1 enabled disabled disabled 2 disabled enabled disabled 3 enabled enabled disabled 4 disabled disabled enabled 5 enabled disabled enabled 6 disabled enabled enabled 7 enabled enabled enabled
0 none (key disabled) 1 MAN / AUTO selection 2 LOC / REM 3 HOLD 4 Start / Stop timer 5 Reset timer 6 Software power on/off 7 Reset alarm memory 8 SP1 ... SP2 selection (2SP)
SP1 ... SP4 selection - bit Lo
9 SP1 ... SP4 selection - bit Hi
Selection of the
input type for the
auxiliary input
Select the number
of enabled alarms
+16 to enable timer function + 32 to enable multiset function (2 setpoints) + 64 to enable multiset function (4 setpoints)
Timer Start / Stop
0 from digital input
1 from AL1 ON
2 from AL2 ON
3 from AL3 ON
4 from ALHb ON
5 from serial line (address 0049H, bit 0
6 from serial line (address 0049H, bit 1)
7 from keys
Timer Reset
(0 ... 15)
+ 8 to enable the main input curve 4 point correction (alternative to custom linearisation). See the “Input Reading Correction Function” section. +16 to disabled the averaging filter on input sampled value (available from software release 3.05)
+8 to disabled the averaging filter on input sampled value (available from software release 3.05)
SEnS Probe type for main input
0 Thermocouple (TC) 1 Resistance Thermometer (RTD) 2 Thermistor (PTC) 3 Voltage 0...50mV / 10...50mV 4 Current 0...20mA / 4...20mA 5 Voltage 0...10V / 2...10V 6 Custom 10V 7 Custom 50mV
Selection of the
input type for the
main input
8
Control type
[0...11]
43
CtrL Control type 0 P heat 1 P cool 2 P heat / cool 3 PI heat 4 PI cool 5 PI heat / cool 6 PID heat 7 PID cool 8 PID heat / cool 9 ON-OFF heat
10 ON-OFF cool 11 ON-OFF heat / cool 12 PID heat + ON-OFF cool 13 ON-OFF heat + PID coll 14 PID heat + cool with relative
gain (see C.MEd parameter)
0 none (key disabled) 1 MAN / AUTO selection 2 LOC / REM 3 HOLD 4 Start / Stop selftuning 5 Start / Stop autotuning 6 Set/Reset outputs OUT 1 ... OUT 4 7 Reset alarm memory 8 SP1 / SP2 selection 9 Integral action reset
10 START / STOP
timer (if enable in S.S.t.)
11 RESET timer
(if enable in _ _ r.t.)
+16 Autoreset enabled (STOP = Program RESET) (for the _S.S.t. parameter)
+8 inverse action
+ 16 disable the function display in the configuration menu
Selection of derivate action sampling time: +0 sample 1 sec. +16 sample 2 sec. +32 sample 8 sec. +64 sample 240 msec.
“*” Key
and bargraph
installation
hrd.3 “*” Key Bargraph
0 1 x 2 x 3 x x
b u t t , b u t .2
Function of M/A
key
Function of “*”
key
Defining SV
display function
diSP Lower display (SP) function (*) 0 SSP - setpoint enabled (*) 1 InP.2 - auxiliary input (*) 2 Control output (*) 3 Deviation (SSP - PV)
8 Display of current time on
PV display and tS time on SV display
(*) + 4 Timer (when active)
Note: scale selected under “tYPE” in “InP”.
In case of ON/OFF control the LBA alarm is
not enabled
-
--
st.00
st.32
xead pa.01
pa.14
bargled.1
led.2
led.3
LEd.x Function
0 None 1 MAN/AUTO (ON in manual, OFF in auto) 2 LOC/REM (ON in remote, OFF in local) 3 Selftuning active 4 Autotuning active 5 IN1 repetition 6 IN2 repetition 7 Serial communications in operation 8 HOLD inserted
9 Error present (error code <> 0) 10 Softstart in operation 11 SP1 ... SP4 indication - Lo bit 12 SP1 ... SP4 indication - Hi bit 13 Start / Stop Timer 14 Reset Timer
Function of the "MAN": M/A, L/R, ATUN LEDs, IN1, IN2 repetition,
event programmer, serial port enabled, errors present
+ 16 for flashing indication
LEd.1 (MAN), LEd.2 (AUX), LEd.3 (REM)
9
Bargraph
function
bArG
0 Heat 1 Cool 2 Heat + Cool 3 PV 4 Aux. input
(V2 valve position) 5 Setpoint 6 V0 or V1 valve position 7 Time (timer) 8 Deviation (PV - setpoint)
-10% ... +10%
• Lin
Lin
Custom linearisation for main or auxiliary
input (*)
Step 0
Step 32
......
Scale limits
Scale limits
• CuSt
Number of parameters in
the custom menu
[ 0 ... 14 ]
CuSt
Custom “dAtA” menu
Identification code for
parameter 1
Identification code for
parameter 14
......
• U.CAL
U.CAL
User
calibration
X X X X
x
The identification code is specified in this position, under the parameter name
(*) Not available for:
input correction function enabled (SEnS + 8) custom TC input (SEnS = 0; tyPE= 20, 21) custom RTD input (SEnS = 1; tyPE= 4, 5) custom PTC input (SEnS = 2; tyPE= 2, 3)
U.CAL Function
1 Analogue output 1 2 Analogue output 2 3 Input 1 - custom probe 10V 4 Input 1 - custom probe 50mV 5 Input 2 - potentiometer
7 • VALVE CONTROL TYPES
10
6 • MOTORIZED VALVE CONTROL
Control valve
Actuator
SetPoint
MM
V0 CONTROL EXAMPLE
VALVE POSITION CONTROL
Control
Engine
Control Valve
Set Position
Process variable
Potentiometer
Feedback
In a control process the control valve has to adjust the liquid fuel flow rate (often corresponding to the thermal energy of the process) depending on the signal coming from the controller. To this purpose , the valve is equipped with an actuator capable to modify its opening value, forcing the resistance produced by the fluid flowing inside it. Control valves change flow rate according to a modulated mode, producing finite variations of the inside flowing path of the fluid, corresponding with finite variations of the actuator input signal, coming from the controller. The servomechanism is made up, for example, by an electic motor, by a reducer unit and of a transmission mechanical system that operates the valve. Various auxiliary components could be present such as electrical and mechanical limit switches for safety, manual override devices, position detectors and indicators. The controller determines the drive output for the valve from the dynamic behaviour of the process in order that the required value of the process variable can be maintained. When position feedback is required, it is usually supplied by a potentiometer fitted to the actuator.
The controller determines the drive output for the valve from the dynamic behaviour of the process in order that the required value of the process variable can be maintained. When position feedback is required, it is usually supplied by a potentiometer fitted to the actuator.
Time
minimum pulse
Deviation
Beginning of
pulsative
command
Valve command
Valve control parameters
- Actuator time (_At_): time required by the valve to move from completely open to completely closed (and viceversa), selectable in seconds; it is a mechanical characteristics of the valve + actuator assembly. NOTE: if the actuator run is mechanically reduced it is necessary to reduce the _At_ parameter value accordingly.
- Minimum pulse time (t_Lo): selectable in % of the actuator time (resolution 0.1%). This parameter sets the minimum value of command below which the actuator does not move; by increasing t_Lo it is possible to lower the mechanical stress on the valve, allowing a higher accuracy in positioning.
- Pulsating command band (t_Hi): selectable in % of the actuator time (resolution 0.1%). Whenever the valve has to move to another position, this parameter defines a band inside which the valve positioning command is pulsating instead of continuos; the length of each pulse is proportional to the deviation and higher or equal to t_Lo. This type of pulsating command allows a very accurate positioning of the valve, with or without feedback, expecially in case of high mechanical inertia. The pulsating command positioning is disabled by setting t_Hi = 0.
- Dead Band (_db_): selectable in display units, defines a band around the Setpoint inside which the controller gives no command to the valve (Open = OFF; Close = OFF). This parameter is useful to save the actuator from mechanical stress when the process has already settled; the dead band function is disabled by setting _db_ = 0.
PULSATING COMMAND VALVE POSITIONING, AVAILABLE ONLY ON V0, V1 AND V2 CONTROL TYPES
V0 - for floating valves without feedback potentiometer; V1 - for floating valves with potentiometer and position indication; V2 - for valves with position feedback potentiometer and position indication.
Models V0 and V1 have a similar behaviour. Every request for change that is greater than the minimum pulse is sent to the actuator via an OPEN/CLOSE relay.
Process
8 • TIMER, TIMER + 2 SETPOINTS FUNCTIONS
The timer function can be enabled in Hrd configuration by setting parameter hrd.1 = +16 (+48 to enable the 2 setpoints selection). The timer operating mode can be defined through parameters _S.S.t. (timer start/stop) and _ _r.t (timer reset). The timer setpoint can be programmed in level 1 configuration (full scale 9999 sec.). The Start/Stop and Reset of the timer can be executed through a digital input or the tripping of an alarm (AL1, AL2, AL3, ALHb). The Reset command (active on state) reset the timer and keeps it zeroed even if the Start Command is active. It is possible to configure the timer for Auto-Reset function (timer Reset at every Stop). It is possible (through diSP parameter) to show the timer count on display SV. When the timer Setpoint (tS) is reached, it is possible to turn ON an output or select SP2 control Setpoint.
9 • MULTISET FUNCTION / SETPOINT GRADIENT
SP1
SP2
SP3
SP4
SP1
(*)
ON
ON
ON
SP
IN1
IN2
t
t
t
(*) If setpoint gradient is enabled
(*)
IN1
IN2
ts
Timer
0
Reset
Start
Stop
t
t
SP1
SP2
ts
t
t
t
Timer
Reset IN1
SP2
SP1
AL1
SP
SV
Start/Stop from AL1 active
(*) if Auto-Reset function is enabled
The ramp between SP1 and SP2 is defined through GrSP parameter (setpoint gradient). GrSP = 0 means immediate change.
The multiset function can be enabled in Hrd configuration by setting parameter hrd.1 = +64. It is possible to use up to 4 local setpoints, selectable through binary combinations of digital inputs (IN1, IN2); the M/A configurable key can be used to select SP1/SP2. The faceplate LEDs can be configured to display the active SP. SETPOINT GRADIENT (parameter Gr.SP): if Gr.SP = 0 the change from one SP to another is immediate; if Gr.SP 0 the instrument goes from one the SP to another with the defined ramp. If Gr.SP 0, at power-on and on AUTO/MAN commutation the SP is assumed equal to PV and then reaches the local or remote SP with the defined ramp.
11
Every action updates the presumed position of a virtual potentiometer calculated on the basis of the declared actuator time. In this way, there is always a presumed position of the valve that is compared with the controller output. Once the valve reaches a fully opened or fully closed position as calculated by the virtual potentiometer, the controller will supply a series of pulses in the same direction in equal intervals of time with the length of the minimum pulse in order to ensure that the actual end stop is reached. The actuators are usually protected against an OPEN command when in the fully open position and a CLOSE command in the fully closed position. The V2 model reads the position of the valve through an auxiliary analogue input, conditioned to give a percentage (0.0 - 100.0%), it compares it with the controller output, and sends the appropriate command to the valve. The auxiliary input of the controller is used to acquire the valve position. Calibration is required to detect the potentiometer readings that correspond to the maximum and minimum valve positions. The potentiometer is normally powered by the same controller.
V3 - for floating valves without position indication, PI control V4 - for floating valves with valve position potentiometer indication, PI control; when the difference between the requested position from the controller and the proportional component is greater than the value that corresponds to the minimum pulse, the controller supplies an OPEN or CLOSE command equal to the minimum pulse. The integral component of the controller is reset to zero, each time the controller change the valve position (integral desaturation). The frequency and the width of the pulses is related to the integral time that has been set. (_ti_).
12
This alarm detects (when current should be flowing) an interruption in the control loop caused by a possible shortcircuit probe, an inverted probe connections or broken heater circuit. If enabled (AL.nr) the alarm is activated if the variable does not increase when the controller should be heating (reduce when cooling) at maximum power within a set time (LbA.t). The value of the variable is enabled only outside the proportional band, when alarm is ON the power is limited at a set value (LbA.P). The alarm condition resets as soon as an increase in temperature is detected (or reduction if on the cooling channel) or by pressing the “ ” and “Raise” keys simultaneously in the Out.P position of level 1 menu. If LbA.t = 0 the LBA function is disabled.
LBA ALARM FUNCTION
The type of alarm requires the current transformer input (CT). It can indicate the variations of load current measured through HB input, in the range (Lo.S2 ... HI.S2). It is enabled by a configuration code (Hrd, AL.nr); in this case the alarm set-point is expressed as HB scale digits. The alarm function and the associated control output are selected through parameter Hb_F (“Out” menu). The setpoints for alarm is AL.Hb. The direct HB alarm intervenes if the current transformer input falls below the entered setpoint for a time set in Hb_t during periods in which the main output is ON. The HB alarm can be activated only if the ON times are greater than 0,4 seconds. The HB alarm provides monitoring of the load current even during the OFF period of the cycle time of the MAIN output: If the measured current exceeds 12% of the CT input scale for a time set in Hb_t during periods in which the main control relay is in the OFF state, the alarm intervenes. The alarm is reset automatically when the alarm conditions have been cleared. If the alarm AL.Hb is entered as = 0, both types of HB alarm are disabled and the associated relay is disenergised. The load current reading is displayed as InP.2 in level 1 menu. NOTE: the ON/OFF times refer to the entered cycle time. The alarm Hb_F = 3 (7), for analog output is ON when the load current is lower than the alarm setpoint; the alarm is disabled if the control output is lower than 2%.
HB ALARM
10 • ALARMS
tempo
AL1 + Hyst1
AL2 + Hyst2
AL2
AL1
alarm 1
alarm 2
(*)
For AL1 = Lo absolute alarm with positive Hysteresis Hyst1, AL1 t = 1 (*) = OFF if disabled on power-up For AL2 = Hi absolute alarm with negative Hysteresis Hyst2, AL2 t = 0
For AL1 = symmetrical Lo absolute alarm with Hysteresis Hyst1, AL1 t = 5 For AL1 = symmetrical Hi absolute alarm with Hysteresis Hyst1, AL1 t = 4
Absolute alarm Symmetrical absolute alarm
reverse
direct
AL1
AL1 + [ Hyst1 ]
AL1 - [ Hyst1 ]
time
For AL1 = Lo deviation alarm with negative Hysteresis Hyst 1, AL1 t = 3 For AL1 = Hi deviation alarm with negative Hysteresis Hyst 1, AL1 t = 2
For AL1 = Symmetrical Lo deviation alarm with Hysteresis Hyst 1, AL1 t = 7 For AL1 = Symmetrical Hi deviation alarm with Hysteresis Hyst 1, AL1 t = 6
time
SP+AL1
SP
inverse
direct
SP+AL1
SP
inverse
direct
tempo
Hyst1
Deviation alarm Symmetrical deviation alarm
SP-AL1
This function, if enabled, partializes the output power and increases it proportionally to the time elapsed since the power-up of the instrument with respect to the preset time 0.0 ... 500.0 min (“ SoFt ” parameter, CFG). The soft-start is mutually exclusive with self-tuning and it is activated each time the instrument is powered up. The soft-start function is reset by switching the unit to Manual control.
11 • SOFT-START
13
Proportional Action:
the term whose contribution to the output is proportional to the deviation of the input (the deviation is the difference between the measured variable and the set-point).
Derivative Action:
the term whose contribution to the output is proportional to the rate of variation of the input signal deviation.
Integral Action:
the term whose contribution to the output is proportional to the integral with time of the input signal deviation.
The influence that the Proportional, Derivative and Integral terms have on the process under control
* An increase in the P.B. reduces the oscillations but increases the deviation. * A reduction of the P.B. reduces the deviation but provokes oscillation of the controlled variable (if the value of the P.B. is too low, the system will tend to be unstable). * An increase in the Derivative Action, which corresponds to an increase of the Derivative Time, reduces the deviation and also prevents oscillation up to a critical value of the Derivative Time, above which the deviation increases and prolonged oscillations will occur. * An increase of the Integral Action, which corresponds to a reduction of the Integral Time, helps to remove the deviation between the controlled variable and the set-point when the system has settled down. If the value of the Integral Time is too long (Weak integral action) it is possible that there will be a persistent deviation between the input and the set-point. Contact SPIRAX-SARCO to receive further information concerning controls action
12 • NOTES ON THE CONTROL ACTIONS
13 • MANUAL TUNING
A) Enter the set-point at its working value. B) Set the proportional band at 0,1% (with a cycle time set at zero to have on-off action with a relay output). C) Switch to automatic and observe the behaviour of the variable.
It will be similar to that in the illustration:
D) The PID parameters are calculated s follows: Proportional band
Peak
P.B.= ---------------------------------------- x 100
(V max - V min)
(V max - V min) is the scale range. Integral time: It = 1,5 x T Derivative time: dt = It/4 E) Switch the instrument in manual, enter the calculated values. Return to PID action by setting the appropriate relay output cycle time, and switch back to Automatic. F) If possible, to evaluate the optimised parameters, change the set-point and observe how the system reacts to the transitory change. If an oscillation persists, increase the proportional band. If the response is too slow, reduce it.
Process Variable
Time
T
Peak
14 • SOFTWARE ON / OFF SWITCHING FUNCTION
How to switch OFF: hold down the “ F ” and “Raise” keys together for 5 seconds to disactivate the instrument, which puts itself in the OFF
state while keeping the line supply connected, keeping the process value displayed, while the SV display is OFF. All the outputs (alarm as well as control) are in the OFF state (logic 0 or relay disenergised) and all the functions of the instrument are disabled except the switch-on function and the digital communication. How to switch ON: hold down the “ F ” key for 5 seconds and the instrument will pass from the OFF state to the ON state. If the power is removed during the OFF state, the next time the power is connected, the instrument will find itself in the same OFF state (the ON or OFF state is memorised). The function is normally enabled. The function can be disabled by setting the parameter Prot = Prot +16. This function can be executed through a digital input (d.i.F.1 or d.i.F.2).
14
The function works very well for single output systems (heating or cooling). The self-tuning action has the scope of calculating the optimum values for the control parameters during the start up of the process. The variable (for example the temperature) must be that assumed at zero power (ambient temperature). The controller supplies maximum output power until a point below the set-point is reached. It then zeros the power again. By measuring the overshoot, and the time needed to arrive at maximum, the PID parameters are calculated. Once the action has finished its calculations, it disables itself automatically and the control proceeds normally to bring the system to set-point.
How to activate selftuning:
A. Activation at turn-on
1. Adjust the setpoint at requested value
2. Enable selftuning setting Stun parameter at value (CFG menu)
3. Switch the instrument off
4. Be sure that the temperature value approximately corresponds to the ambient temperature
5. Switch the instrument on
B. Activation from keyboard
1. Be sure that the M/A key is enabled for Start/Stop selftuning function
(butt code = 4 Hrd menu)
2. Adjust the temperature value next to the ambient temperature one.
3. Set the setpoint at requested value.
4. Press M/A key to activate selftuning. (Attention: if the key is pressed twice, selftuning will be disabled)
The procedure takes place automatically until the the end. When finishing, the new PID parameters are stored: proportional band, integral and integrated times calculated for the active action (heat or cool). In case of double action (heat or cool) the parameters of the opposite action are calculated maintaining the initial ratio between the respective parameters (ex.: CPb = HPb * K; where K = CPb / HPb when starting selftuning). At the end, the Stun code is automatically cancelled.
Remarks:
• Procedure interrupts when the setpoint value is exceeded during the course. In this case the Stun code is not cancelled.
• It is suggested to enable one of the configurable leds for the selftuning status indication. If one of Led1, Led2, Led3 = 3 (or 19) parameters are
set in the Hrd menu, the corresponding led is on (or flashing), during the active selftuning phase.
15 • SELF-TUNING
Peak
T
S.P.
Room Temp.
Time
Process Variable
S.P. - Room Temp.
2
16 • AUTO-TUNING
If this function is enbled, it is not possible to enter the PID parameters manually. It can be one of two types: permanent or one-shot. The first continual examines system oscillations to recalculate the optimum values to reduce these oscillations. It does not intervene if the oscillations are less than 1,0% of the proportional band. It is interrupted if the set-point is changed, and is reinserted when the set-point is stable. The calculated PID parameters are not stored. If power is removed from the instrument, the instrument reverts to the values entered before auto-tuning was enabled. One-shot auto-tuning is useful for calculating the values around set-point. It produces a variation in output of 10% of the current power and it examines the effect of the overshoot over time. The parameters are stored, and replace those perviously entered. After this disturbance, the controller returns to control at the set-point using the new parameters.
time
PV
c_Pb
h_Pb
SP+cSPo
SP
+100%
Control output
0%
-100%
Proportional only control output with heating Proportional band separated from cooling Proportional band
Proportional only control output with heating Proportional band overlapped on cooling Proportional band
time
PV
c_Pb
h_Pb
SP+cSPo
SP
+100%
Control output
0%
-100%
PV = Process Value SP = Heating Set Point SP+cSPo = Cooling Set Point h_Pb = Heating Proportional band c_Pb = Cooling Proportional band
17 • CONTROL OUTPUT
By this control mode (enabled through CtrL = 14 parameter) the type of cooling has to be specified. Cooling PID parameters are thus calculated starting from the heating ones according to the following ratio. (i.e.: c.MEd = 1 (oil), H_Pb = 10, H_dt = 1, H_It = 4 brings to: C_Pb = 12,5, C_dt = 1 , C_It = 4) It is suggested to select the following values when setting output cycle times: Air T Cycle Cool = 10 sec. Oil T Cycle Cool = 4 sec. Water T Cycle Cool = 2 sec. NB.: By this mode cooling parameters cannot be modified.
Relative Gain Heat/Cool Control
15
Hole for 2,9 x 9 screws
• CURRENT TRANSFORMER
19 • ACCESSORIES
These transformers are used for current measurements at 50 ÷ 60Hz from 25A to 600A (nominal primary current). The peculiar characteristic of these transformers is the high number of secondary turns. This means a very low secondary current directly suitable for an electronic circuit of measurement. The secondary current may be detected as a voltage on a resistor.
CODE Ip / Is Ø Secondary n OUTPUTS Ru Vu ACCURACY
Wire
TA/152 025 25 / 0.05A 0.16 mm n
1-2
= 500 1 - 2 40 2 Vac 2.0 %
TA/152 050 50 / 0.05A 0.18 mm n
1-2
= 1000 1 - 2 80 4 Vac 1.0 %
IN = 25Aac OUT = 50mAac
COD. 330200
IN = 50Aac OUT = 50mAac
COD. 330201
• ORDER CODE
• RS232 interface cable for instrument configuration
COD. 1108200
Cable + Floppy
• ORDER CODE
N.B.: RS232 interface for PC configuration is supplied with
configuration software. The digital communication connection must be executed with instrument ON and inputs/outputs not connected.
18 • MAIN INPUT CORRECTION FUNCTION
It allows a custom correction of the main input reading throught the setting of four values: A1, B1, A2, B2. This function can be enabled selecting “Sens” +8 code (menu “Hrd”). Example: Sens = 1+8 = 9 for RTD sensor with input correction. If this function is applied to linear scales (50mv, 10V, 20mA, Pot), it is possible to reverse the scale. The four values are set in menu “Lin” as follows: A1 = St100, B1 = St01, A2 = St02, B2 = St03. Setting limits correspond to the prefixed scale (“LoS” ... “HiS” nel menù “InP”). The offset function (Parameter “oFt” menu “InP”) remains enabled. Limits: B1 always higher than A1; B1-A1 25% Should be at least 25%, of full scale of selected probe.
Example: Sens = 9, TyPE = 0 (Pt100 natural scale -200...+600), dPS = 0
LoS = 0, HiS = 400, oFt = 0 Reference point on the real curve: A1 = St00 = 50, B1 = St01 = 350 (B1-A1 = 300 greater than 25% of 800) Corresponding points on the adjusted curve: A2 = St02 = 120, B2 = St03 = 220
A1=50 200 B1=350 400
With correction
without correction
Indication
Input
400
B2=220
170
A2 =120
5,5 27 5,5
1 2
152050 9640
50 / 0.05 A
44 30
1010
920 19
48
1 2
13
1
8 8
38
2
20
In
Out1 (R) + Out2 (R) + Out3 (R) + Out4 (R)
RRRR
Out1 (R) + Out2 (R) + Out3 (D) + Out4 (R)
RRDR
OUT 5 (W1) 0...10V OUT 6 (W2) 0...10V
VV
OUT 5 (W1) 0/4...20mA OUT 6 (W2) 0...10V
IV
None 00* OUT 5 (W1) 0...10V V0 OUT 5 (W1) 0/4...20mA I0
OUT 5 (W1) 0/4...20mA OUT 6 (W2) 0/4...20mA
II
Out1 (R) + Out2 (R) + Out3 (R) RRR0*
Out1 (R) + Out2 (R) + Out3 (D) RRD0
OUTPUTS 1,2,3,4
(R/D)
OUTPUT 5, 6
MODEL
1600 V 1800 V
1600 V 1800 V
(*) Indicates the standard version (**) Add +15 to obtain Transmitter Supply 24V # Potentiometer input requires 10V transmitter
supply
For a PTC input a specific calibration has to be requested
16
Before installation, please read the following advices:
• follow the indications of the manual scrupulously when making the connections to the instrument
• use a cable that is suitable for the ratings of voltage and current indicated in the technical specifications
• the instrument has no ON/OFF switch for the power, it operates immediately the supply is connected; for safety reasons, the devices permanently connected to power supply require ON/OFF switch with proper warking; the switch must be close to the unit and should be easily reachable by the user. A single switch can be connected to several units.
• if electrically NON-ISOLATED equipment is connected to the instrument (e.g. thermocouples), a ground wire must be connected to avoid that this connection is made through the machine
• if the instrument is used in applications where there is risk of injury to persons and damage to machines or materials, it is essential that it is used with an auxiliary alarm device. It is advisable to verify frequently that the alarm device is functional even during the normal operation of the equipment
• before using the instrument, it is the user's responsibility to ensure the correct instrument settings to avoid injury to persons or damage to objects and materials
• the instrument must NOT be used in environments where there could be the presence of dangerous atmospheres (inflammable or explosive); if the instrument is used with elements that operate in such atmospheres, they must be connected through an appropriate interface or safety barrier that conforms to the local safety regulations in force
• the instrument contains components that are sensitive to static electrical discharges and appropriate precautions must be taken before handling the electronic circuit boards if permanent damage to these components is to be prevented
Installation:
installation category II, pollution degree 2, double isolation
• the power supply wiring must be kept separate from that of inputs and outputs of the instrument; always check that the supply voltage corresponds to that indicated on the instrument label
• install the instrumentation separately from the relays and power switching devices
• in the same cabinet, do not install power contactors,, contactors, relays; thyristor power units “particularly if phase angle”; motors, etc...
• keep away from dust, humidity, corrosive gases and heat sources
• do not close the ventilation holes; the working temperature must be in the range 0...50°C. If the unit has faston terminals they must be of the protected and isolated type; if the unit has screw terminals it is necessary to fix the cable in pairs.
Power supply
: should be taken from an isolator with a fuse for the instrument section; the path of the supply wiring should be as direct as possible from the isolator to the instruments: the same supply should not be used to power relays, contactors, solenoid valves, etc.; if the voltage waveform is strongly distorted by thyristor switching units or by electric motors, it is recommended that an isolation transformer is used only for the instruments, connecting the screen to ground; it is important the electrical plant has a good ground connection, the voltage between neutral and ground must not exceed 1V and the resistance must be less than 6; if the supply suffers large voltage swings, use a voltage stabiliser for the instrument supply; in the vicinity of high frequency generators or arc welders, use line filters; the power supply wiring must be kept separate from the that of the inputs and that of the outputs of the instruments; always check that the supply voltage corresponds to that indicated on the instrument label
Input and output connections:
for connecting analogue signals (TC, RTD) it is necessary to: physically separate the input wiring from that of the power supply wiring, from the wiring to the outputs and from power connections; use twisted and screened cables, with the screen connected to ground at only one point to use RC (resistor and capacitor in series) spark suppression components in parallel with inductive loads that operate in ac (contactors, solenoid valves, motors, fans, etc.) connected to the outputs of the instrument (
Note: all the capacitors must conform to the VDE standard (class x2) and
withstand a voltage of at least 220Vac. The resistor must be at least 2W
); fit a diode 1N4007 in parallel with the coil of inductive loads that operate in dc
SPIRAX-SARCO srl will not be held responsible for injury to persons or damage to objects and materials caused by mishandling, incorrect or erroneous use that is not in conformity with the instrument specifications.
!
WARNING: this symbol indicates danger. You can see it close the power supply circuit and the relay contacts that may be connected to high voltage.
• WARNINGS
36 IN CT (50mAac)
16**
IN1, IN2 PNP IN SPR (0/4...20mA) + Transmitter Supply 10V
17** IN1, IN2 PNP, IN CT (50mAac) + Transm. Sup. 10V
33 IN SPR (0...1V) 34 IN SPR (0...10V) 35 IN SPR (0/4...20mA)
15**
IN1, IN2 PNP IN SPR (0...10V) / IN Potentiometer # + Transmitter Supply 10V
13** IN1, IN2 NPN, IN CT (50mAac) + Transm. Sup.10V
12**
IN1, IN2 NPN IN SPR (0/4...20mA) + Transmitter Supply 10V
11**
IN1, IN2 NPN IN SPR (0...10V) / IN Potentiometer # + Transmitter Supply 10V
POWER SUPPLY
20...27Vac/dc ±10%0
100...240Vac/dc ±10%1*
DIGITAL COMMUNICATIONS
None0* Current Loop1 RS 4852 RS 232C3
05** IN1, IN2 PNP + Transmitter Supply 10V
ORDER CODE
AUXILIARY INPUTS
None IN1, IN2 NPN
00*
01
IN1, IN2 PNP Transmitter Supply 10V
02
03**
IN1, IN2 NPN + Transmitter Supply 10V04**
10** IN1, IN2 NPN, IN SPR (0...1V) + Transm. Sup. 10V
IN SPR (0...1V) + Transmitter Supply 10V IN SPR (0...10V) / IN Potentiometer #
+ Transmitter Supply 10V
06** 07**
IN SPR (0/4...20mA) + Transmitter Supply 10V08** IN CT (50mAac) + Transmitter Supply 10V09**
14** IN1, IN2 PNP, IN SPR (0...1V) + Transm. Sup. 10V
Loading...