Spellman SL2KW SERIES Instruction Manual

Page 1
R
Instruction Manual
SL2KW SERIES
MODEL : SERIAL# : DATE :
SPELLMAN HIGH VOLTAGE ELECTRONICS CORPORATION
One Commerce Park Valhalla, New York, 10595
+1(914) 686-3600* FAX: +1(914) 686-5424* E-mail: sales@spellmanhv.com Website: www.spellmanhv.com
High Voltage Power Supply
SL2KW MANUAL 118087-001 Rev A
Page 2
IMPORTANT SAFETY PRECAUTIONS
SAFETY
THIS POWER SUPPLY GENERATES VOLTAGES THAT ARE DANGEROUS AND MAY BE FATAL.
OBSERVE EXTREME CAUTION WHEN WORKING WITH THIS EQUIPMENT.
High voltage power supplies must always be grounded.
Do not touch connections unless the equipment is off and the
Capacitance of both the load and power supply is discharged.
Allow five minutes for discharge of internal capacitance of the power supply.
Do not ground yourself or work under wet or damp conditions.
SERVICING SAFETY
.
Maintenance may require removing the instrument cover with the power on.
Servicing should be done by qualified personnel aware of the electrical hazards.
WARNING note in the text call attention to hazards in operation of these units
that could lead to possible injury or death.
CAUTION notes in the text indicate procedures to be followed to avoid possible
damage to equipment.
Copyright © 2000, Spellman High Voltage Electronics Corporation. All Rights Reserved.
This information contained in this publication is derived in part from proprietary and patent data. This information has
been prepared for the express purpose of assisting operating and maintenance personnel in the efficient use of the
model described herein, and publication of this information does not convey any right to reproduce it or to use it for
any purpose other than in connection with installation, operation, and maintenance of the equipment described.
118004-001 REV. B
Page 3
WICHTIGE SICHERHEITSHINWEISE
SICHERHEIT
DIESES HOCHSPANNUNGSNETZTEIL ERZEUGT LEBENSGEFÄHRLICHE HOCHSPANNUNG.
SEIN SIE SEHR VORSICHTIG BEI DER ARBEIT MIT DIESEM GERÄT.
Das Hochspannungsnetzteil muß immer geerdet sein.
Berühren Sie die Stecker des Netzteiles nur, wenn das Gerät ausgeschaltet ist und die elektrischen
Kapazitäten des Netzteiles und der angeschlossenen Last entladen sind.
Die internen Kapazitäten des Hochspannungsnetzteiles benötigen ca. 5 Minuten, um sich zu entladen.
Erden Sie sich nicht, und arbeiten Sie nicht in feuchter oder nasser Umgebung.
SERVICESICHERHEIT
Notwendige Reparaturen können es erforderlich machen, den Gehäusedeckel während des Betriebes zu
entfernen.
Reparaturen dürfen nur von qualifiziertem, eingewiesenem Personal ausgeführt werden.
“WARNING” im folgenden Text weist auf gefährliche Operationen hin, die zu Verletzungen oder zum Tod
führen können.
“CAUTION” im folgenden Text weist auf Prozeduren hin, die genauestens befolgt werden müssen, um
eventuelle Beschädigungen des Gerätes zu vermeiden.
118004-001 REV. B
Page 4
PRECAUTIONS IMPORTANTES POUR VOTRE SECURITE
CONSIGNES DE SÉCURITÉ
CETTE ALIMENTATION GÉNÈRE DES TENSIONS QUI SONT DANGEUREUSES ET PEUVENT ÊTRE FATALES.
OYEZ EXTRÊMENT VIGILANTS LORSQUE VOUS UTILISEZ CET ÉQUIPEMENT.
S
Les alimentations haute tension doivent toujours être mises à la masse.
Ne touchez pas les connectiques sans que l’équipement soit éteint et que la capacité à la fois de la charge et de
l’alimentation soient déchargées.
Prévoyez 5 minutes pour la décharge de la capacité interne de l’alimentation.
Ne vous mettez pas à la masse, ou ne travaillez pas sous conditions mouillées ou humides.
CONSIGNES DE SÉCURITÉ EN CAS DE REPARATION
La maintenance peut nécessiter l’enlèvement du couvercle lorsque l’alimentation est encore allumée.
Les réparations doivent être effectuées par une personne qualifiée et connaissant les risques électriques.
Dans le manuel, les notes marquées « WARNING » attire l’attention sur les risques lors de la manipulation de ces
équipements, qui peuvent entrainer de possibles blessures voire la mort.
Dans le manuel, les notes marquées « CAUTION » indiquent les procédures qui doivent être suivies afin d’éviter
d’éventuels dommages sur l’équipement.
118004-001 REV. B
Page 5
IMPORTANTI PRECAUZIONI DI SICUREZZA
SICUREZZA
QUESTO ALIMENTATORE GENERA TENSIONI CHE SONO PERICOLOSE E
POTREBBERO ESSERE MORTALI.
PONI ESTREMA CAUTELA QUANDO OPERI CON QUESO APPARECCHIO.
Gli alimentatori ad alta tensione devono sempre essere collegati ad un impianto di terra.
Non toccare le connessioni a meno che l’apparecchio sia stato spento e la capacità interna
del carico e dell’alimentatore stesso siano scariche.
Attendere cinque minuti per permettere la scarica della capacità interna dell’alimentatore
ad alta tensione.
Non mettere a terra il proprio corpo oppure operare in ambienti bagnati o saturi d’umidità.
SICUREZZA NELLA MANUTENZIONE.
Manutenzione potrebbe essere richiesta, rimuovendo la copertura con apparecchio
acceso.
La manutenzione deve essere svolta da personale qualificato, coscio dei rischi elettrici.
Attenzione alle AVVERTENZE contenute nel manuale, che richiamano all’attenzione ai
rischi quando si opera con tali unità e che potrebbero causare possibili ferite o morte.
Le note di CAUTELA contenute nel manuale, indicano le procedure da seguire per evitare
possibili danni all’apparecchio.
118004-001 REV. B
Page 6
Table of Contents
1. INTRODUCTION
1.1 Description of the SL2KW Series........................................................................1
1.2 Standard Features.................................................................................................2
1.2.1 Remote Operating Features ..................................................................2
1.2.2 System Status and Fault Diagnostic Display........................................2
1.3 Options.................................................................................................................3
1.4 Interpreting the Model Number...........................................................................4
2. INSPECTION & INSTALLATION
2.1 Initial Inspection..................................................................................................5
2.2 Mechanical Installation........................................................................................5
3. OPERATING INSTRUCTIONS
3.1 Operation .............................................................................................................7
3.2 Standard Features.................................................................................................8
PAGE
4. PRINCIPLES OF OPERATION
4.1 Chassis .................................................................................................................17
4.2 Line Rectification and Filtering...........................................................................17
4.3 Inverter.................................................................................................................18
4.4 High Voltage Transformer...................................................................................18
4.5 High Voltage Assembly.......................................................................................18
4.6 Control/Power PWB ............................................................................................19
4.7 Front Panel Assembly..........................................................................................19
4.8 Options.................................................................................................................19
5. OPTIONS
5.1 Adjustable Overload Trip ....................................................................................20
5.2 Adjustable Power Trip.........................................................................................20
5.3 Arc Sense.............................................................................................................20
5.4 Arc Trip................................................................................................................20
5.5 Bipolar Master/Slave ...........................................................................................20
5.6 Current Mode Select............................................................................................20
5.7 Constant Power Control.......................................................................................20
5.8 Digital Panel Meter, 4.5 Digits............................................................................20
SL2KW SERIES MANUAL I 118088-001 REV C
Page 7
5.9 External Fault Relay ............................................................................................21
5.10 Fine Control Voltage ...........................................................................................21
5.11. Instant On.............................................................................................................21
5.12 Lead Length.........................................................................................................21
5.13 No Arc Detect......................................................................................................21
5.14 No Slow Start.......................................................................................................21
5.15 Positive/Negative.................................................................................................21
5.16 Remote Fault Reset..............................................................................................21
5.17 Remote Over Voltage ..........................................................................................22
5.18 Slides....................................................................................................................22
5.19 Slow Start.............................................................................................................22
5.20 Custom Design Models........................................................................................22
6. MAINTENANCE
6.1 Periodic Servicing................................................................................................24
6.2 Performance Test.................................................................................................24
6.3 High Voltage Dividers.........................................................................................24
7. REPLACEMENT PARTS
7.1 Replacement Parts................................................................................................25
7.2 Correspondence and Ordering Spare Parts..........................................................25
8. FACTORY SERVICE
8.1 Warranty Repairs.................................................................................................26
8.2 Factory Service Procedures .................................................................................26
8.3 Ordering Options and Modifications...................................................................26
8.4 Shipping Instructions...........................................................................................26
SL2KW SERIES MANUAL II 118088-001 REV C
Page 8
LIST OF FIGURES
Figure 2.1 SL Series Dimensions.................................................................................6
Figure 3.1 SL Series Typical Operating Set Up...........................................................10
Figure 3.2A Wiring Diagram for Remote Programming via Voltage Source ................12
Figure 3.2B Wiring Diagram for Remote Programming via External Resistance..........12
Figure 3.3 Remote Monitor Test Point Designations...................................................13
Figure 3.4 Remote Control of High Voltage On and Off ............................................13
Figure 3.5 External Inhibit Interface Circuit................................................................14
Figure 3.6 External Interlock Interface Circuit............................................................14
Figure 3.7 Remote High Voltage On and Remote High Voltage off Indicator Circuit.... 15
Figure 3.8 Remote Indicators Interface............................................................................ 16
Figure 5.1 Polarity Reversal Procedures, 1kV to 8kV ..................................................... 22
Figure 5.2 Polarity Reversal Procedures 10kV to 50kV .................................................. 22
Figure 5.3 Instant On Option............................................................................................23
Figure 5.4 Bipolar Master/Slave Option......................................................................23
LIST OF TABLES
Table 1.1 SL2KW Options..........................................................................................3
Table 3.1 Rear Panel Interface 25 pin Mini D............................................................11
Table 4.1 List of Main Assemblies.............................................................................18
APPENDIX
A. Specification Controls (Custom Models Only)
SL2KW SERIES MA NUAL III 118088-001 REV C
Page 9
Chapter 1
INTRODUCTION
1.1 Description Of The SL2KW Series
he SL2KW Series of high voltage power supplies provides very well regulated, low ripple high voltage
T
in a highly efficient, compact design. The improvements in size and performance over traditionally designed high voltage power supplies are due to the resonant topology and unique control circuitry of the SL2KW design. A proprietary control system maintains high frequency over the operating output range. The combination of proprietary control system and proprietary protection circuitry enables the supplies to operate under arcing and extreme transient conditions without damage or interruptions.
The DC output voltage and current are continuously adjustable from zero to the maximum rating via two front panel ten-turn locking potentiometers.
Custom designed units to meet special needs are also available.
SL2KW SERIES MANUAL 1 118088-001 REV C
Page 10
1.2 Standard Features
The SL2KW Series incorporates several standard features designed to optimize user satisfaction and safety.
SLOW START: This feature provides a gradual
increase in high voltage until the preset operating
point is reached. The slow start time is factory set
for 6 seconds. Other slow start times are available as
an option. ARC DETECT / ARC QUENCH / ARC COUNT:
These features allow the user to tailor the power
supply to meet specific needs in dynamic load
applications. If an arc occurs, the output is inhibited
for approximately one second, then the output is
ramped up to the preset level with the slow-start
circuitry. See Chapter 3 for operating details and
information for user customization of these features. INTERNAL FAULT PROTECTION: The SL
Series continually monitors internal circuits critical to
the proper operation of the power supply. In the
event that one of these circuits does not function
correctly, the fault detection circuit latches the
appropriate fault on the front panel display and turns
off the output and reverts the unit to the POWER
DOWN mode. INDICATOR LAMPS: LINE POWER, HIGH
VOLTAGE OFF AND HIGH VOLTAGE ON
indicators. OUTPUT CABLE: All models are provided with a
ten foot shielded high voltage output cable. The
cables are designed with a plug arrangement so that
they can be easily removed from the mating
receptacle located on the rear of the chassis.
1.2.1 Remote Operating Features
EXTERNAL INHIBIT: A control signal that will
inhibit the high voltage output is provided on the external interface. A logic low, ground, will inhibit the high voltage output an d a logic high, open, will restore the high voltage output to the preset level.
NOTE: The External Inhibit circuit should NOT be used
for protection against injury or for safety interlock. See External Interlock for this type of safety control.
EXTERNAL INTERLOCK: Interlock connections
are provided on the external interface on the rear of the chassis for connection to a safety switch. The unit will not operate unless the interlock circuit is closed. During high voltage operation, opening the interlock circuit will cause the High Voltage to shut off. This circuit should be used for safety interlock circuits.
1.2.2 System Status and Fault Diagnostic Display
“Dead Front” type indictors are provided to give the user complete indication of system operation and fault conditions. If a fault occurs, the power supply will revert to the POWER DOWN mode. This is indicated by both the HV ON and HV OFF lamps turning off. To reset, depress the HV OFF switch.
VOLTAGE (CONTROL): Indicates the output
voltage regulator circuit is maintaining voltage regulation.
CURRENT (CONTROL): Indicates the output
current regulator circuit is maintaining current regulation.
HV INHIBIT: Indicates that the high voltage
supply is being inhibited by either the EXTERNAL INHIBIT or internal protection circuitry.
REMOTE PROGRAMMING: Allows remote
adjustment of the output voltage and current via an external voltage source.
REMOTE MONITOR: Allows remote monitoring
of the output voltage and current.
REMOTE HIGH VOLTAGE CONTROL:
Allows remote control of HIGH VOLTAGE ON and HIGH VOLTAGE OFF. Signals are also provided for remote indication of HV ON or HV OFF status.
SL2KW SERIES MANUAL 2 118088-001 REV C
INTLK CLSD: Indicates the EXTERNAL
INTERLOCK connections are in the closed position. This also indicates closure of internal power supply interlocks.
Page 11
INTKL OPEN: Indicates the EXTERNAL
INTERLOCK connections are in the open position. This also indicates opening of internal power supply interlocks.
OVERVOLT: Indicates the overvoltage protection
circuitry has caused the power supply to turn off. Overvoltage protection is internally set to 110% of the rated output voltage.
OVERCURR: Indicates the output current has
exceeded the programmed current trip level when the AOL (Adjustable Overload Trip) or the OL (Overload Trip) options are installed.
ARC: Indicates that an arc has occurred within the
previous one second or that the ARC COUNT/TRIP has shutdown the power supply.
RGLT ERR: Indicates a failure in the voltage,
current or power regulation circuitry. This fault usually occurs when there is a lack of output power to maintain regulation.
The options available are listed in Table 1.1. See Section 5 for more information on these options along with operating and set-up instructions. With few exceptions, these options and modifications can be retrofitted to your power supply at the factory in a short time. For price and retrofit arrangements, contact the Spellman Sales Department.
1.3 Options
AOL Adjustable Overload Trip (0-103%)
APT Adjustable Power Trip
ARC Arc Sense
AT Arc Trip
BPM/BPS Bipolar Master/Slave
CMS Current Mode Select
CPC Constant Power Control
DPM4 Digital Panel Meter
EFR External Fault Relay
FCV Fine Control Voltage
IO Instant On
SL Slides
LL(X) Lead Length
NAD No Arc Detect
NSS No Slow Start
PN Positive/Negative
RFR Remote Fault Reset
ROV Remote Over Voltage
SL Slides
SS(X) Slow Start (X)
Table 1.1 SL2KW Options
SL2KW SERIES MANUAL 3 118088-001 REV C
Page 12
1.4 Interpreting the Model Number
The model number of the power supply describes its capabilities. After the series name is:
1. the maximum voltage (in KV).
2. the polarity of the unit: positive (P), negative (N) or
reversible (PN).
3. the maximum output (in watts).
4. the option codes for all options that are included.
Custom units have an X number after the option codes.
SL2KW 30 P 2000 / AOL / X (#)
Series
Name
Maximum
Voltage
Polarity
Maximum
Power
Option
Custom
“X”
Number
SL2KW SERIES MANUAL 4 118088-001 REV C
Page 13
Chapter 2
INSPECTION & INSTALLATION
nitial inspection and preliminary checkout procedures are recommended. For safe operation, please follow
I
the step-by-step procedures described in Chapter 3,
Operating Systems.
2.1 Initial Inspection
Inspect the package exterior for evidence of damage due to handling in transit. Notify the carrier and Spellman immediately if damage is evident. Do not destroy or remove any of the packing material used in a damaged shipment.
After unpacking, inspect the panel and chassis for visible damage.
Fill out and mail the Warranty Registration card accompanying the unit. Standard Spellman SL Series
high voltage power supplies and components are covered by warranty. Custom and special order models (with an X suffix and the model number) are also covered by warranty.
2.2 Mechanical Installation
Units in the SL2KW Series have front panel holes for standard EIA rack mounting. The rack must allow rear access for cable connections. Units are fully enclosed and are suitable for bench or table top operation. Standard unit dimensions are shown in Figure 2.1. It is strongly recommended to support the chassis by guides or slides. Slides are available for ease of servicing (SL option).
SL2KW SERIES MANUAL 5 118088-001 REV C
Page 14
SL2KW SERIES MANUAL 6 118088-001 REV C
Figure 2.1- SL2KW Dimensions
Page 15
Chapter 3
OPERATING INSTRUCTIONS
3.1 Operation
WARNING
THIS EQUIPMENT GENERATES DANGEROUS
VOLTAGES THAT MAY BE FATAL.
PROPER GROUNDING OF ALL HIGH VOLTAGE
EQUIPMENT IS ESSENTIAL.
WARNING
BEFORE CONNECTING THE POWER SUPPLY
TO THE AC LINE, FOLLOW THIS STEP BY STEP
PROCEDURE.
DO NOT CONNECT THE POWER SUPPLY TO
THE AC LINE UNTIL STEP H IS REACHED.
Failure to follow these procedures may void the warranty. A) Insure that the Circuit Breaker is in the OFF position
(0).
B) Check the input voltage rating on the nameplate of
the supply and make certain that this is the rating of the available power source. Spellman SL2KW Series units operate on 208Vac Three Phase (220Vac Single Phase if 220Vac Single Phase is ordered).
C) PROPER GROUNDING TECHNIQUES: The
chassis of high voltage power supplies must be grounded, preferably to a water system ground using copper pipe or other earth ground using the ground stud B1 at the rear of the unit. See Figure 3.1 for a typical operating set-up.
The return line from the load should be connected to the ground stud, on the rear of the power supply. Using a separate external ground at the load is not recommended.
D) Attach the output cable to the load.
E) Plug the high-voltage output cable provided with the
unit into the rear of the supply and hand tighten the knurled collar.
F) OPTIONS NOTE: See Section 5 for hook-up and
operating instructions for the options on your unit. Custom models may also require set-up changes.
G) For initial turn-on, rotate the KILOVOLT control
fully counter-clockwise to the zero voltage position.
H) The input power cable may now be connected to the
AC power line.
I) Switch the front panel circuit breaker to the ON
position (1). (If the supply is to be turned off for an extensive period of time, the line cord should be disconnected). The unit is now in the HIGH VOLTAGE OFF mode. The HIGH VOLTAGE OFF light should be lit.
J) Depress and hold the HIGH VOLTAGE OFF switch.
The front panel meters will now read the preset value of the KILOVOLT control dial and the MILLIAMPERES control dial. To preset the desired level of current and voltage during operation, hold in the HIGH VOLTAGE OFF switch and rotate the appropriate control dial while noting its corresponding meter reading. Release the HIGH VOLTAGE OFF switch.
NOTE: No actual output is being produced at this stage. K) Depress the HIGH VOLTAGE ON switch. The light
inside the switch should light up and the output will slow start to the preset level output voltage and/or output current.
NOTE: The SL2KW Series is equipped with a slow start
circuit that ramps the output up to its maximum setting in approximately 6 seconds after the HIGH VOLTAGE ON switch is depressed.
L) To terminate the generation of output power, depress
the HIGH VOLTAGE OFF switch. In the HIGH VOLTAGE OFF mode the power supply’s fault and interface circuits are still active.
SL2KW SERIES MANUAL 7 118088-001 REV C
Page 16
M) To turn off the power supply, turn the circuit breaker
to the off position (0).
referenced to the power supplies signal ground on the rear external interface.
NOTE: If a power supply fault, or system monitoring fault occurs, the power supply will revert to the POWER DOWN mode. In this mode the output power will be turned off. The HV OFF lamp will be off. To reset, depress the HV OFF switch.
AFTER TURNOFF, DO NOT HANDLE THE LOAD
UNTIL THE CAPACITANCE HAS BEEN
LOAD CAPACITANCE MAY BE DISCHARGED BY
SHORTING TO GROUND.
THE VOLTMETER ON THE POWER SUPPLY
FRONT PANEL DOES NOT READ THE OUTPUT
VOLTAGE WHEN THE POWER IS TURNED OFF,
EVEN IF A CHARGE STILL
EXISTS ON THE LOAD.
ALWAYS OPERATE THE UNIT WITH THE COVER
A fan maintains safe operating temperature in the power supply by drawing air over the circuit components. The cover must be on in order to direct the air flow over the areas that need cooling. In operation, the unit must be placed so that the air intake and the fan exhaust are clear of obstructions that might impede the flow of air.
WARNING
DISCHARGED!
WARNING
CAUTION
ON.
3.2 Standard Features
A note on remote interface circuitry and remote signal grounding. Whenever possible, electrical isolation should be provided when interfacing with any high voltage power supply. For power control signals such as EXTERNAL INTERLOCK, HIGH VOLTAGE OFF, AND HIGH VOLTAGE ON, isolated relay contacts should be used. For status signals and control signals such as HIGH VOLTAGE ON, HIGH VOLTAGE OFF, and EXTERNAL INHIBIT, etc., opto-isolation should be used. If possible, analog programming and monitoring signals should be isolated via analog isolation amplifiers. Spellman application engineers are available to assist in interface circuitry design. All interface cables should be properly shielded. All power supply signals should be
REMOTE PROGRAMMING: Allows remote
adjustment of the output voltage and current via an external voltage source. In local control (front panel control), jumpers are installed on the external interface J5 in the rear of the chassis between J5-10 and J5-11 for voltage control and between J5-8 and J5-9 for current control.
For remote programming, the jumpers are removed and a positive voltage source, from 0V to 10 V, is applied to the appropriate terminals. Programming signals should be referenced to J5-1, signal ground. By adjusting the voltage source from 0V (zero output) to 10V (full rated output), the desired output can be selected. See Figure
3.2A for the wiring diagram and specifications.
An alternate method of controlling the output remotely is by using external resistance, such as a potentiometer or a resistor network. For remote control the jumpers are removed and the desired register configuration installed. See Figure 3.2B for the wiring diagram.
REMOTE MONITOR: Test points are made
available at the 25 pin D connector on the rear of the chassis for monitoring the voltage and current output. The test points are always positive regardless of the output polarity where 0V to 10V equals 0 to 100% of the output 0.5%. Test points have an output impedance of 5K ohms. See Figure 3.3 for the test point designation.
REMOTE CONTROL: Remote control of the
HIGH VOLTAGE ON and HIGH VOLTAGE OFF can be accomplished via the rear panel interface. HIGH VOLTAGE OFF and HIGH VOLTAGE ON can be controlled by momentary normally closed and normally open contacts respectively. See Figure 3.4 on page 14 for the recommended interface.
EXTERNAL INHIBIT: Allows the user to inhibit
the power supply output without switching HIGH VOLTAGE OFF control. This circuit can be used to generate fast slewing output waveforms or control of high voltage generation as in Laser and Capacitor discharge applications. The maximum inhibit rate should not exceed 5Hz. Consult the factory for higher repetition rates or high pulse load applications. See Figure 3.5 for the recommended interface circuit.
SL2KW SERIES MANUAL 8 118088-001 REV C
Page 17
WARNING
IT IS EXTREMELY DANGEROUS TO USE THIS
INHIBIT CIRCUIT TO INHIBIT HIGH VOLTAGE
GENERATION FOR THE PURPOSE OF
SERVICING OR APPROACHING ANY AREA OR
LOAD CONSIDERED UNSAFE DURING NORMAL
USE.
EXTERNAL INTERLOCK: Interlock connections
are provided on the terminal block J5-3 and J5-4 on the rear of the chassis for connection to a safety switch. The unit will not operate unless the interlock circuit is closed. If the interlock is not being used, the jumper installed on the terminals before shipping must be in place. If the jumper is missing, or there is an opening between the interlock terminals, the unit’s high voltage inverter will be disabled. During high voltage operation, revert to the HIGH VOLTAGE OFF mode. Subsequent closing of the interlock circuit will NOT return the unit to the HIGH VOLTAGE ON mode. This must be accomplished by depressing the HIGH VOLTAGE ON switch. See Figure 3.6 for the recommended interface circuit
ARC DETECT / ARC QUENCH / ARC COUNT:
The ARC DETECT circuit senses dynamic arcing or discharge conditions present at the output load. If an arc occurs, the output is inhibited for .5 seconds. After the .5 second period, the output is ramped up to the previous set level. This ramp is based on the
standard six second slow start feature. The ARC DETECT ramp circuit may be disabled by removing CR32 on the Control/Power Pwb. Caution should be observed if this feature is disabled. Discharge rates of greater then 1Hz may cause excessive power dissipation in the power supply’s output limiting resistors.
The ARC COUNT feature will allow the user to program the ARC fault parameters. The ARC indicator on the front panel will illuminate for approximately one second after each arc has occurred. The power supply can be programmed to trip the POWER DOWN mode if an arc occurs.
The standard feature is programmed to trip the power supply if 8 arcs occur within a twenty second period.
REMOTE HIGH VOLTAGE ON & REMOTE
HIGH VOLTAGE OFF: Signals are provided for
remote monitoring of the HIGH VOLTAGE ON/OFF status. See Figure 3.7 for recommended interface.
REMOTE MODE INDICATORS: Signals are
provided for remote indication of the control mode status, voltage control, current control, and power control. See Figure 3.8 for the recommended interface.
SL2KW SERIES MANUAL 9 118088-001 REV C
Page 18
SPELLMAN
HIGH VOLTAGE ELECTRONICS CORP HAUPPAUGE, NY 11788 MADE IN USA
PART NO.: MODEL:
SERIAL NO.: OUTPUT: INPUT:
High Voltage Output
REAR PANEL
It is recommended to connect the load return directly to the ground stud located on the rear of the high voltage power supply.
High
Voltage
Load
Shielded High Voltage
Figure 3.1- Typical Operating Setup
SL2KW SERIES MANUAL 10 118088-001 REV C
Page 19
J5 SIGNAL SIGNAL PARAMETERS
1 Power Supply Common Signal Ground 2 External Inhibit Ground = Inhibit, Open = HV ON 3 External Interlock +15V at Open, <15mA at Closed 4 External Interlock Return Return For Interlock 5 Current Monitor 0 to 10V = 0 to 100% Rated Output 6 kV Test Point 0 to 10V = 0 to 100% Rated Output 7 +10V Reference +10V, 1mA Max 8 Remote Current Program In 0 to 10V = 0 to 100% Rated Output 9 Local Current Program Out Front Panel Program Voltage 10 Remote Voltage Program In 0 to 10V = 0 to 100% Rated Output 11 Local Voltage Program Out Front Panel Program Voltage 12 EFR (Common) Optional External Fault Relay
13 EFR (Normally Open / Closed) 14 Local HV Off Out +15V at Open, < 25mA at Closed.
Connect to HV OFF For FP Operation
15 HV OFF 16 Remote HV ON +15V, 10mA Max = HV ON 17 Remote HV OFF Indicator 0 = HV ON, +15V, 10mA Max = HV OFF 18 Remote HV ON Indicator 0 = HV OFF, +15V, 10mA Max = HV ON 19 Remote Voltage Mode Open Collector 50V Max, 10mA Max On = Active 20 Remote Current Mode Open Collector 50V Max, 10mA Max On = Active 21 Remote Power Mode Open Collector 50V Max, 10mA Max On = Active 22 Remote PS Fault 0 = Fault, +15V, 0.1 mA Max = No Fault 23 +15V Output +15V, 100mA Max 24 Power Supply Common Signal Ground 25 Shield Return Chassis Ground
Table 3.1 - Rear Panel Interface 25 pin Mini D
SL2KW SERIES MANUAL 11 118088-001 REV C
Page 20
Voltage Source 0-10V = 0-100% of Rated Output
It is recommended that analog signals be isolated via isolation amplifiers.
All cables should be shielded with the shield being returned to the chassis ground of the High Voltage Power Supply.
Remove jumpers for remote programing
Figure 3.2A – Wiring Diagram for Remote Programming via Voltage
J5
1
2
3
4
5
6
7
8
9
10
11
PS Common
-
V
+
Z in = 10M ohm
Z in = 10M ohm
Remote Current Program
V
+
-
Remote Voltage Program
Fully Counterclockwise = Zero Output Fully Clockwise = 100% of Rated Output
All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply. If connections to external potentiometers are excessively long (>10ft), motorized potentiometers are recommended.
Remove jumpers for remote programing
Figure 3.2B – Wiring Diagram for Remote Programming via External
J5
1
2
3
4
5
6
7
8
9
10
11
PS Common
20k ohm
+10.32V
1mA max.
Z in = 10M ohm
Z in = 10M ohm
CW
20k ohm
Remote Current Control
Remote Voltage Control
CW
SL2KW SERIES MANUAL 12 118088-001 REV C
Page 21
J5
It is recommended that analog signals be isolated via isolation amplifiers.
All cables should be shielded with the shield being returned to the chassis ground of the high voltage power supply.
Figure 3.3 – Remote Monitor Test Point Designations
S1 must be closed to enable HIGH VOLTAGE.
Momentary closure of S2 will enable HIGH VOLTAGE ON.
Opening S1 will disable HIGH VOLTAGE ON and switch the unit to the HIGH VOLTAGE OFF mode.
PS Common
1
2
3
4
­M
Current Monitor
M
-
Voltage Monitor
+
5
Z out = 4.99k ohms ±0.1%
6
Z out = 4.99k ohms ±0.1%
7
It is recommended to use relay contacts
for S1 and S2. Relays should be located as close as possible to the high voltage power supply. Coils should be driven from isolated sources. Signals are at 15Vdc, 25mA max., and are only to be used for contact closure.
+
J5
S1
Remove jumpers for remote programing
All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply.
14
15
16
17
S2
Figure 3.4 – Remote Control of High Voltage ON and High Voltage OFF Interface
SL2KW SERIES MANUAL 13 118088-001 REV C
S1 = Remote High Voltage Off
S2 = Remote High Voltage On
Page 22
The transistor should be located as close as possible
to the power supply
All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply.
+15V
2.2k
High Voltage Power Supply Internal inhibit circuitry.
J5
1
2
3
4
PS Common
Transistor ON Inhibits High Voltage
Relay contacts are recommended for S1. The relay should be located as close as possible to the power supply. Signals are at 15Vdc, 25mA max and are only to be used for contact closure.
Remove jumper for remote external interlock
Figure 3.5 – External Inhibit Interface Circuit
J5
1
2
3
S1
4
5
S1 Open= Interlock Open S1 Closed= Interlock Closed
External Safety Interlock Control
All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply.
SL2KW SERIES MANUAL 14 118088-001 REV C
Figure 3.6 – External Interlock Interface
Page 23
12Vdc lamps or relay coils may replace opto-couplers. Opto-couplers, lamps or relays should be located as close as possible to the high voltage power supply. All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply.
J5
PS Common
1
2
3
4
P/O High Voltage Power Supply
1K
1/4 W
1K
1/4 W
10
11
12
13
14
15
16
17
18
5
General Purpose Opto-Coupler
6
7
8
9
To High Voltage OFF Indicator
General Purpose Opto-Coupler
To High Voltage
ON Indicator
R Limit
R Limit
Signals are = 15Vdc, 10mA max. R Limit must be > 500
Figure 3.7 – Remote High Voltage ON and Remote High Voltage OFF Indicator
SL2KW SERIES MANUAL 15 118088-001 REV C
Page 24
R1
R2
R3
J5
23
19
20
21
R limit
10mA max.
R limit
10mA max.
R limit
10mA max.
R Limit must be > 1kW R1-R3=680W 1/4W
Voltage Control
Indicator
Current Control
Indicator
Power Control
Indicator
Figure 3.8 – Remote Mode Indicators Interface
SL2KW SERIES MANUAL 16 118088-001 REV C
Page 25
Chapter 4
PRINCIPLES OF OPERATION
The SL2KW Series of high voltage power supplies utilizes sophisticated power conversion technology. A variety of analog, digital and power conversion techniques are used throughout. The intention of the Principles of Operation is to introduce the basic function blocks that comprise the SL2KW power supply. For details on a specific circuit, consult Spellman’s Engineering Department.
See Table 4.1 for a list of the main assemblies found in a typical SL2KW power supply.
Due to the many variations within the SL2KW
Series, drawing numbers may differ from unit to unit.
The SL2KW power supply is basically an AC to DC power converter. Within the power supply, conversions of AC to DC then to high frequency AC, then to high voltage DC take place. By reviewing further the sub­assemblies, a basic understanding of the process can be gained.
4.1 Chassis
The SL2KW is a compact, high efficiency, high voltage power supply. The power supply can supply up to 2000
watts of DC power. Output voltages of up to 50kV can be generated.
The energy levels used and generated by the power supply can be lethal! Do not attempt to operate the power supply unless the user has a sufficient knowledge of the dangers and hazards of working with high voltage. Do not attempt to approach or touch any internal or external circuits or components that are connected or have been connected to the power supply. Be certain to discharge any stored energy that may be present before and after the power supply is used. Consult IEEE recommended practices for safety in high voltage testing #510-1983.
WARNING
4.2 Line Rectification And Filtering
Basic single phase rectification provides the DC voltage for the high frequency inverter.
SL2KW SERIES MANUAL 17 118088-001 REV C
Page 26
ASSEMBLY TITLE ASSEMBLY DRAWING NO. SCHEMATIC DRAWING NO.
J5 J5 SL Chassis (2000W) 403920-003 Control / Power PWB (2000W) 404581-001 440687-001 High Voltage Assy (2000W) 403931-TAB 440534-001 Front Panel PWB 403895-001 440525-001
Table 4.1-List of Main Assemblies
In general, the following variations can be ordered:
208Vac 10%, 50 to 60Hz, three phase. 220Vac 10%, 50 to 60Hz, single phase.
If the user is unsure of which input voltage option is supplied, check the serial tag on the rear of the power supply or consult Spellman’s Sales Department.
Circuit protection is provided by a front panel circuit breaker. The circuit breaker is a fast acting magnetic trip type circuit breaker. The line input is connected directly to the line side of the circuit breaker whereas the load side is connected to the CONTROL/POWER PWB. The load side of the breaker is also connected to a step-down type line transformer. This transformer provides voltage for housekeeping and control circuit power.
LINE VOLTAGE IS PRESENT WHENEVER THE
POWER SUPPLY IS CONNECTED TO EXTERNAL
LINE VOLTAGES. BE SURE TO DISCONNECT
THE LINE CORD BEFORE OPENING THE UNIT.
ALLOW 5 MINUTES FOR INTERNAL
CAPACITANCE TO DISCHARGE BEFORE
REMOVING ANY COVER.
When the circuit breaker is ON, voltage is applied to an isolated diode rectifier bridge, which contains the rectifier diodes used for line voltage rectification. The output of this bridge rectifier is connected to a capacitor filter. Capacitors are initially charged through resistive inrush limiters.
Approximately 3 seconds after the circuit breaker is turned on, a relay is energized to short the resistor limiters. This DC voltage is supplied to the high frequency inverter.
The DC rails are connected to the high frequency rail capacitors. These capacitors are high frequency, low loss
WARNING
type, which provides the energy storage for the high frequency inverter.
4.3 Inverter
The inverter is a series resonant, series/parallel loaded topology. A proprietary control scheme is used for regulating the power generated from the inverter. The switching devices are IGBT’s. These devices provide high frequency switching to control the resonant current flow. The typical resonant operating period is approximately 10 Seconds. The gate control for the switching devices is provided by the application circuitry located on the CONTROL/POWER PWB. The CONTROL/POWER PWB also provides circuitry for sensing shoot thru and overcurrent conditions in the inverter.
4.4 High Voltage Transformer
The output of the High Frequency Resonant Inverter is connected to the primary of the High Voltage Transformer. The High Voltage Transformer is a set up type. Typical secondary voltages are in the range of 1kV to 4.5kV depending upon the output voltage ratings.
4.5 High Voltage Assembly
The High Voltage Assembly will vary depending upon the model ordered. The circuitry typically consists of a full wave, full bridge, or full wave doubler for voltage outputs in the range of 1kV to 8kV. The higher voltage ranges utilize various parallel, series arrangements of a full wave voltage doubler.
Output filtering is typically provided by an R-C type filter. Voltage feedback for regulation and monitoring is provided by a high bandwidth resistive/cap acitive divid er. Current feedback for regulation and monitoring is provided by a sense resistor connected at the low voltage end of the High Voltage Rectifier/Multiplier Circuit.
SL2KW SERIES MANUAL 18 118088-001 REV C
Page 27
4.6 Control/Power PWB
The majority of control circuits for power supply controls are located on the CONTROL/POWER PWB. +15VDC, ­15VDC, and +10VDC is generated on the CONTROL/POWER PWB. High Voltage On/Off control is accomplished by K3, and its associated circuitry. Interlock control is provided by K4.
Voltage feedback from the high voltage divider is sent to the control board via a mass terminated ribbon cable. Gain adjustment is provided on the HV PWB. The KV feedback signal is sent to the front panel DVM and to the REAR PANEL 25 pin D connector for remote monitoring. K2 provides switching between feedback and program signal for the front panel DVM’s. This allows the user to preset the desired output before energizing high voltage.
Program voltages are typically ramped up to set level by a slow start circuit.
An arc sense circuit provides sensing, quench and indicator of arc conditions. Consult the operation manual for a detailed description of the arc sense control.
Current feedback from the high voltage rectifier is sent to sense resistors located on the High Voltage Assembly. Calibrated feedback is then sent to the applicable circuitry on the Control/Power Board.
U12 circuit provide visual indication of the control mode, which is in operation. These signals are sent to the FRONT PANEL ASSEMBLY for front panel status indication.
The resonant control circuitry consists of a pulse width converter. U17 generates all pulse width control signals.
Power supply inhibit circuits are provided by U22 and K3. System Fault control and Indication is provided by U19, and associated circuitry. Diagnostic signals are latched and then sent to the FRONT PANEL ASSEMBLY for status indication.
4.7 Front Panel Assembly
Front Panel controls, meters and status indications are connected to the FRONT PANEL PWB. The FRONT PANEL PWB interfaces directly to the CONTROL/POWER PWB.
4.8 Options
Due to the many variations of models and options provided in the SL Series, details of actual circuits used may differ slightly from the above descriptions. Consult Spellman’s Engineering Department for questions regarding the principles of operation for the SL Series.
SL2KW SERIES MANUAL 19 118088-001 REV C
Page 28
Chapter 5
OPTIONS
he options available for this power supply are described in this section. Interface diagrams are
T
shown where required. Options are specified by including the option code in the model number as described in Section 1.5.
5.1 AOL - Adjustable Overload
Trip
A control board jumper is moved to make the power supply shut down if it ever operates in current mode. This allows the user to set the current programming level as a trip point that will turn the power supply off with an Over Current fault if it ever tries to operate in Current Mode.
5.2 APT – Adjustable Power Trip
A third control loop is installed in the power supply, a power loop. This power loop uses an analog multiplier chip to multiply the voltage and current feedback signals to create a power feedback signal. Programming and feedback scaling is 0- 10Vdc = 0-100% of rated power. The circuit is configured to trip the power supply off with an Over Power fault if the power loop ever tries to regulate.
5.3 ARC – Arc Sense
A signal is provided on a spare pin (TB1-21) that changes state whenever the power supply detects an arc.
5.4 AT – Arc Trip
A control board jumper is moved such that the first arc sensed will shut the power supply off with an ARC fault.
5.5 BPM/BPS – Bipolar Master/Slave
The Bipolar Master/Slave option allows two supplies of the same voltage rating but opposite polarities to functions as a single tracking bipolar power supply. The positive supply is configured as the Master, the negative supply is configured as the Slave. This is accomplished by connecting the Voltage Test Point of the positive (Master) unit to the Voltage Programming of the negative (Slave) unit. See Figure 5.4. The Master’s voltage programming signal will provide control of both power supplies from zero to rated output voltage. The negative polarity will track the positive polarity within ±1% from 10% to full rated output. Performance specifications are governed by individual unit characteristics. The two units must be connected independently to their respective loads and ground.
5.6 CMS – Current Mode Select
A front panel switch is provided to allow the power supply to either regulate in current mode or create an over current fault when operated in current mode, which will shut down the supply. This is basically a switch selectable AOL option.
5.7 CPC – Constant Power Control
Identical to the APT Option with the exception the power supply will run and regulate when the power loop becomes active.
5.8 DPM4 - Digital Panel Meter, 4.5 Digits
SL2KW SERIES MANUAL 20 118088-001 REV C
The standard 3.5 digit front panel meters are replaced with 4.5 digit panel meters.
Page 29
5.9 EFR - External Fault Relay
The external fault relay option provides a set of customer accessible relay contacts that are controlled by the fault status circuitry of the applicable SL Series power supply. A standard SL power supply will revert to the “Power Down” mode with a visual front panel indication if any of the following fault conditions occur:
Overvoltage: Greater than 110% of maximum output voltage was produced by the power supply.
Overcurrent: Greater than 104% of maximum output current was produced by the power supply or the AOL circuitry was activated.
Overtemperature: Excessive temperature has been sensed within the chassis.
Regulation Error: Lack of required output power to maintain regulation
Arc (Shutdown): Arc sensing circuit has shut down the supply due to excessive arcing. With the installation of the EFR option, if any of th ese faults occur, a relay will be activated to provide a remote indication that the power supply has reverted to the “power down” mode. The common and normally open or normally closed set of contacts are provided (jumper selectable). Relay contacts are rated at 1A at 30Vdc or 0.5A at 48Vac. Connections on the rear panel 25 pin D connector (J5) can be made as follows: J5-12 Relay Common. J5-13 Normally Open/Normally Closed (jumper selectable). Resetting the front panel and EFR relay is accomplished by depressing the green front panel HV OFF push-button switch, which reverts the power supply back to the “Standby” mode. Removal and reapplication of the AC line input voltage will also reset any fault. The circuitry and components required for the EFR option are installed at the factory when this option is ordered.
5.10 FCV – Fine Control Voltage
This option adds a second potentiometer to the front panel of the unit. This allows for a finer local adjustment of the output voltage setting.
5.11 IO – Instant On
When the Instant On Option is ordered, the High Voltage is enabled as soon as line voltage is applied when the circuit breaker is in the ON position. (See Figure 5.3) To enable Instant On, keep the jumper between J5-14 and J5­15 attached. Connect an additional jumper from J5-15 to J5-16 as shown in Figure 5.3.
CAUTION
The Power Supply will generate programmed
High Voltage whenever the circuit breaker is in
the ON position, and line voltage is applied.
5.12 LL(X) – Lead Length
Extra-long high voltage output cable of standard lengths of20, 40, 60 and 100 feet can be provided. Non standard lengths can be custom ordered.
5.13 NAD – No Arc Detect
This option removes the arc intervention circuitry from the power supply. Care must be exercised when using this option as damage to the HV multiplier could occur.
5.14 NSS – No Slow Start
The standard 6 second long linear ramp of output voltage is removed allowing the high voltage to “step” to its set point when enabled.
5.15 PN – Positive/Negative
Reversible polarity option. Units that are not inherently reversible by design (10kV to 50kV) can have their output polarity reversed by the process of exchanging the high voltage multiplier section.
Models from 0.5 kV to 8kV: For units from 0.5 kV to 8kV, the polarity may be reversed in the field via an internal wiring change by following the procedures shown in Figure 5.1.
Models from 10kV to 130kV: When this option is ordered, a second multiplier is provided to permit the user to replace the existing multiplier with another of reverse polarity. See Figure
5.2 for a step by step procedure.
5.16 RFR – Remote Fault Reset
This option provides the ability to reset any power supply faults that might occur via toggling a signal on the rear panel interface.
SL2KW SERIES MANUAL 21 118088-001 REV C
Page 30
5.17 ROV – Remote Over Voltage
The programming signal for the over voltage comparator circuit is made available to the customer remotely, allowing the power supply to be set to trip the OVP circuit anywhere from 0 -110% of rated output voltage.
5.18 SL – Slides
Industry standard rack mounted slides are installed on the power supply.
5.19 SS(X) – Slow Start(X)
The standard slow start is modified to provide a time of (X) seconds. Time frames of 0.1 seconds to 120 seconds can be accommodated.
5.20 Custom Designed Models – X Numbers
Units built to customer specification are assigned an X number by the factory. If this unit is an X model, a specification control sheet is added at the end of the test of this instruction manual.
Spellman welcomes the opportunity to customize units to fit your requirements or to develop new products for your applications. Contact the Spellman Sales Department with your needs.
SL2KW SERIES MANUAL 22 118088-001 REV C
Page 31
TURN UNIT OFF, UNPLUG LINE CORD FROM AC OUTLET AND WAIT FOR 5 MINUTES BEFORE PROCEEDING TO CHANGE THE HIGH VOLTAGE MULTIPLIER.
1
THAT MOUNT COVER TO CHASSIS AND FRONT PANEL.
2
3
2
LINE
A
PARTIAL VIEW A-A
A
2000 Watt
1kV-8kV chassis
2
3
4
5
LOAD
4
POSITIVE CONFIGURATION SHOWN
TO THE HIGH VOLTAGE BOARD, AND REMOVE COVER.
FOR POSITIVE POLARITY: BLACK WIRE ON J4 AND WHITE WIRE ON J5. FOR NEGATIVE POLARITY: WHITE WIRE ON J4 AND BLACK WIRE ON J5.
POSITIVE UNITS.
REINSTALL LEXAN COVER AND RELATED HARDWARE.
TURNING UNIT ON.
Figure 5.1 – Polarity Reversal Procedures
2000W, 1kV to 8kV Chassis
4
2
66
A
5
PARTIAL VIEW A-A
A
3
2000 Watt
10kV-50kV chassis
LINE
LOAD
8
POSITIVE CONFIGURATION SHOWN
TURN UNIT OFF, UNPLUG LINE CORD FROM AC OUTLET AND WAIT FOR 5 MINUTES BEFORE P ROCEEDING TO CHANGE THE HIGH VOLTAGE MULTIPLIER.
REMOVE COVER BY UNSCREWING AND REMOVING 12 SCREWS
1
THAT MOUNT COVER TO CHASSIS AND FRONT PANEL.
2
UNPLUG HIGH VOLTAGE LEADS FROM ASSEMBLY.
UNPLUG CABLE FROM JB1 AND REMOVE CABLE SHIELD
3
FROM FASTON TAB ON BOARD.
UNPLUG CONNECTOR FROM JB2.
4
REMOVE 2 SCREWS THAT HOLD THE POLY ETHYLENE
5
ENCLOSURE AND THE BOARD TO THE CHASSIS
CAREFULLY TILT UP A ND SLIDE OUT MULTIPLIER.
6
INSTALL NEW MULTIPLIER BY FOLLOWING STEPS 6 THRU 2 IN
7
REVERSE.
8
CHANGE POSITION OF JP4 JUMPERS ON FRONT PANEL BOARD TO MATCH POLARITY OF UNIT, i.e 2 JUMPERS MUST BE ON "N" POSITIONS FOR NEGATIVE UNITS AND ON "P" POSITIONS FOR POSITIVE UNITS.
INSTALL COVER AND ALL HARDWARE BACK BEFORE TURNING
9
UNIT ON.
SL2KW SERIES MANUAL 23 118088-001 REV C
Figure 5.2 – Polarity Reversal Procedures
2000W, 10kV to 50kV Chassis
Page 32
Existing jumper
Jumper JB5 15 to 16 for instant ON option
J5
14
15
16
17
P.S. Common
kV Test
Point OUT
Figure 5.3 – Instant ON
POSITIVE (MASTER)
SUPPLY
J5
1
2
3
4
5
6
7
8
POSITIVE (SLAVE)
SUPPLY
J5
1
2
3
4
5
6
7
8
P.S. Common
SL2KW SERIES MANUAL 24 118088-001 REV C
9
10
11
10
11
9
Remote Voltage Program IN
*REMOVE
JUMPER
12
INSTALLATION NOTE
Keep Interconnecting Wires as Short as possible Use of Twisted Pair or Shielded/Coaxial wire is recommended.
12
Figure 5.4 – Bipolar / Slave Option
LINKING
10-11
Page 33
Chapter 6
MAINTENANCE
his section describes periodic servicing and performance testing procedures.
T
WARNING
THIS POWER SUPPLY GENERATES VOLTAGES
THAT ARE DANGEROUS AND MAY BE FATAL .
OBSERVE EXTREME CAUTION WHEN
WORKING WITH HIGH VOLTAGE.
6.1 Periodic Servicing
Approximately once a year (more often in high dust environments), disconnect the power to the unit and remove the top cover. Use compressed air to blow dust out of the inside of the unit. Avoid touching or handling the high voltage assembly. Be sure that the fans are not obstructed and spins freely. The fan has sealed bearings and does not need lubrication. Be sure to replace the top cover before operating for proper cooling.
6.2 Performance Test
WARNING
HIGH VOLTAGE IS DANGEROUS.
ONLY QUALIFIED PERSONNEL SHOULD
PERFORM THESE TESTS.
High voltage test procedures are described in Bulletin STP-783, Standard Test Procedures for High Voltage Power Supplies. Copies can be obtained from the Spellman Customer Service Department. Test equipment, including an oscilloscope, a high impedance voltmeter, and a high voltage divider such as the Spellman HVD­100 or HVD-200, is needed for performance tests. All test components must be rated for operating voltage.
6.3 High Voltage Dividers
High voltage dividers for precise measurements of output voltage with an accuracy up to 0.1% are available. An HVD-100 is used for voltages up to 100KV. An HVD­200 measures up to 200KV. The Spellman divider is designed for use with differential voltmeters or high impedance digital voltmeters. The high input impedance is ideal for measuring high voltage low current sources, which would be overloaded by traditional lower impedance dividers.
SL2KW SERIES MANUAL 25 118088-001 REV C
Page 34
Chapter 7
REPLACEMENT PARTS
7.1 Replacement Parts
Contact the Spellman Customer Service Department for parts lists for specific models.
Parts and subassemblies for Spellman’s high voltage power supplies are available. It is recommended that only qualified personnel perform the repairs. High voltage is dangerous; even minor mistakes in repairs can have serious consequences.
When requesting parts please give the model number and serial number of the power supply.
7.2 Correspondence and Ordering
Spare Parts
Each power supply has an identification label on the rear of the chassis that bears its model and serial number.
When requesting engineering or applications information, please state the model and serial number of the power supply.
When ordering spare parts, please specify the part number, the component function and the model and serial number of the unit.
SL2KW SERIES MANUAL 26 118088-001 REV C
Page 35
Chapter 8
FACTORY SERVICE
8.1 Warranty Repairs
During the Warranty period, Spellman will repair all units free of charge. The Warranty is void if the unit is worked on by other than Spellman personnel. See the Warranty in the rear of this manual for more information. Follow the return procedures described in Section 8.2. The customer shall pay for shipping to and from Spellman.
8.2 Factory Service Procedures
Spellman has a well-equipped factory repair department. If a unit is returned to the factory for calibration or rep air, a detailed description of the specific problem should be attached.
For all units returned for repair, please obtain an authorization to ship from the Customer Service Department, either by phone or mail prior to shipping. When you call, please state the model and serial numbers, which are on the plate on the rear of the power supply, and the purchase order number for the repair. A Return Material Authorization Code Number (RMA Number) is needed for all returns. This RMA Number should be marked clearly on the outside of the shipping container. Packages received without an RMA Number will be returned to the customer. The Customer shall pay for shipping to and from Spellman.
8.3 Ordering Options and Modifications
Many of the options listed in Chapter 5 can be retrofitted into Spellman’s power supplies by our factory. For prices and arrangements, contact the Spellman Sales Department.
8.4 Shipping Instructions
All power supplies returned to Spellman must be sent shipping prepaid. Pack the units carefully and securely in a suitable container, preferably in the original container, if available. The power supply should be surrounded by at least four inches of shock absorbing material. Please return all associated materials, i.e. high voltage output cables, interconnection cables, etc., so that we can examine and test the entire system.
All correspondence and phone calls should be directed to: Spellman High Voltage Electronics Corp.
475 Wireless Boulevard Hauppauge, New York 11788 TEL: (631) 630-3000 FAX: (631) 435-1620
E-Mail: sales@Spellmanhv.co
m
A preliminary estimate for repairs will be given by phone by Customer Service. A purchase order for this amount is requested upon issuance of the RMA Number. A more detailed estimate will be made when the power supply is received at the Spellman Repair Center. In the event that repair work is extensive, Spellman will call to seek additional authorization from your company before completing the repairs.
SL2KW SERIES MANUAL 27 118088-001 REV C
Page 36
To obtain information on Spellman’s product warranty please visit our website at:
http://www.spellmanhv.com/en/About/Warranty.aspx
Loading...