Spellman’s SL150kV rack mount high voltage power supply is designed for scientific and industrial OEM applications requiring 150kV at 1200 watts in a compact cable
connected standard sized rack. Models are available in
positive, negative or reversible polarity. The SL150kV is
fully arc and short circuit protected. Excellent regulation
specifications are provided along with outstanding stability
performance. The vacuum encapsulated high voltage
output section assures reliable corona free operation by
eliminating any concerns due to environmental factors.
Front Panel Controls Power ON/OFF switch, HV ON
Switch, HV OFF Switch with preset feature, 3.5 digit
backlight digital meters for display of output voltage
and output current,10 turn locking potentiometers with
counting dials for adjustment of both output voltage
and output current.
Front Panel Indicators:
HV ONHigh Voltage Inhibit
HV OFFOver Current
Voltage Control Mode Over Voltage
Current Control Mode Arc
Interlock OpenRegulation Error
Interlock ClosedOvertemperature
Input:
220Vac ±10%, 50/60 Hertz
Output Voltage:
0 to 150kV
Output Polarity:
Positive, negative or reversible specify at time of order
Output Current:
8mA
Output Power:
1200W
Voltage Regulation:
Load: 0.01% of rated voltage for a full load change
Line: ±0.01% of rated current over specified input
voltage range
Current Regulation:
Load: 0.01% of rated current ±100µA for full voltage change.
Line: ±0.01% of rated current over specified input
voltage range
Ripple:
0.1% peak to peak of maximum output
Temperature Coefficient:
100ppm/°C.
Stability:
100ppm/hr after a 2 hour warm up, for both voltage and
current regulation
PAGE 1 OF 2
SPELLMAN HIGH VOLTAGE ELECTRONICS CORPORATION
SL150kV
1200W
POWER SUPPLY
www.spellmanhv.com/manuals/SL150KV
Corporate Headquarters
Hauppauge, New York USA
+1-631-630-3000FAX: +1-631-435-1620
e-mail: sales@spellmanhv.com
www.spellmanhv.com
128062-001 REV. F
Spellman High Voltage is an ISO 9001:2008 and ISO 14001:2004 registered company
For locations worldwide
Page 3
SL1200
18.12[460.24]
17.25[438.15]
JB4
J1
17.00 [431.8]
R13TYP
8.72[221.48]
0.44
[11.17]
1.48[37.59]
FRONT VIEW
BACK VIEW
TOP VIEW
19.00 [482.60]
5.75 [146.05]
SL150 ANALOG INTERFACE—
JB4 25 PIN MALE D CONNECTOR
PAGE 2 OF 2
DIMENSIONS: in.[mm]
PINSIGNALPARAMETERS
1Power Supply CommonSignal Ground
2External InhibitGround = Inhibit, Open = HV ON
3External Interlock+15Vdc @ open, ≤ 5mA @ closed
4External Interlock ReturnConnect to pin 3 to enable supply
5Current Monitor0 to 10Vdc = 0 to 100% rated voltage, Zout =10kΩ
6Voltage Monitor0 to 10Vdc = 0 to 100% rated voltage, Zout =10kΩ
7+10Vdc Reference+10Vdc @ 1mA, maximum
8Remote Current Program Input 0 to 10Vdc = 0 to 100% rated voltage, Zout =10kΩ
9Local Current Program Output Multi-turn front panel pot for local control capability
10Remote Voltage Program Input 0 to 10Vdc = 0 to 100% rated voltage, Zout =10kΩ
11Local Voltage Program Output Multi-turn front panel pot for local control capability
12EFR (Common)External Fault Relay (Optional)
13
14Local HV OFF OUT+15Vdc @ open, <25mA @ closed, connect to
HV OFF for front panel operation
15HV OFFConnect to HV OFF OUT for front panel operation
16Remote HV ON+15Vdc @ 10mA maximum = HV OFF
17Remote HV OFF Indicator0 = HV ON, +15Vdc @ 10mA maximum = HV OFF
18Remote HV ON Indicator0 = HV OFF, +15Vdc @ 10mA maximum = HV ON
19Remote Voltage ModeOpen collector 50Vdc @ 10mA maximum, ON = Active
20Remote Current ModeOpen collector 50Vdc @ 10mA maximum, ON = Active
21Remote Power ModeOpen collector 50Vdc @ 10mA maximum, ON = Active
22Power Supply FaultOpen collector, 50Vdc @ 10mA maximum
23+15Vdc Output+15Vdc @ 100mA, maximum
24Power Supply GroundSignal Ground
25Shield ReturnChassis Ground
Operating Temperature:
0 to 40°C operating
Storage Temperature:
-40 to +85°C storage
Humidity:
20% to 85%, non-condensing
Input Line Connector:
3 conductor 12 AWG 6 ft (1.83m) cable, permanently attached
Output Connector:
A detachable 10 ft (3.05m) shielded HV cable is provided
Cooling:
Forced Air
Dimensions:
8.75”H x 19”W x 22”D rack mount.
(22.23cm x 48.26cm x 55.88cm)
Weight:
89 pounds (40.4kg)
Regulatory Approvals:
Compliant to 2004/108/EC, the EMC Directive
and 2006/95/EC, the Low Voltage Directive.
Specify “P” for positive polarity or “N” for negative polarity, and PN = reversible as
illustrated below.
Sample Model Number: SL150P1200/BFP/LL(20)
Where SL = power supply series, 150 = maximum output voltage in kV,
P = positive output polarity, 1200 = maximum output power (watts), BFP = Blank
Front Panel, LL(20) = 20 foot HV cable.
SPELLMAN HIGH VOLTAGE ELECTRONICS CORPORATION
SL150kV
1200W
POWER SUPPLY
Corporate Headquarters
Hauppauge, New York USA
+1-631-630-3000FAX: +1-631-435-1620
e-mail: sales@spellmanhv.com
www.spellmanhv.com
128062-001 REV. F
Spellman High Voltage is an ISO 9001:2008 and ISO 14001:2004 registered company
For locations worldwide
Page 4
IMPORTANT SAFETY PRECAUTIONS
SAFETY
THIS POWER SUPPLY GENERATES VOLTAGES THAT ARE DANGEROUS AND MAY BE FATAL.
OBSERVE EXTREME CAUTION WHEN WORKING WITH THIS EQUIPMENT.
High voltage power supplies must always be grounded.
Do not touch connections unless the equipment is off and the
Capacitance of both the load and power supply is discharged.
Allow five minutes for discharge of internal capacitance of the power supply.
Do not ground yourself or work under wet or damp conditions.
SERVICING SAFETY
.
Maintenance may require removing the instrument cover with the power on.
Servicing should be done by qualified personnel aware of the electrical hazards.
WARNING note in the text call attention to hazards in operation of these units
that could lead to possible injury or death.
CAUTION notes in the text indicate procedures to be followed to avoid possible
Table 3.1 Rear Panel Interface 25 pin Mini D............................................................11
A. Specification Controls (Custom Models Only)
SL150 MANUAL II 118093-001 REV B
APPENDIX
Page 7
Chapter 1
INTRODUCTION
1.1 Description of the SL150
he SL150 voltage power supply provides very well
regulated, low ripple high voltage in a highly
T
efficient, compact design. The improvements in size
and performance over traditionally designed high voltage
power supplies are due to the resonant topology and
unique control circuitry of the SL design. A proprietary
control system maintains high frequency over the
operating output range. High frequency operation allows
a dynamic response time of less than 5 milliseconds, and
one of the lowest ripple specifications in the industry at
this power level. The combination of proprietary control
system and proprietary protection circuitry enables the
supplies to operate under arcing and extreme transient
conditions without damage or interruptions.
The DC output voltage and current are continuously
adjustable from zero to the maximum rating via two front
panel ten-turn locking potentiometers. These high
voltage power supplies have 0.005% load regulation,
0.005% line regulation, and 0.1% p-p ripple.
The supplies operate from either a 200 (option) or 220
Volt, single phase AC line. Other line voltages are
available. Options are listed in Table 1.1 and are
described in Section 5. Custom designed units to meet
special needs are also available.
SL150 MANUAL 1 118093-001 REV B
Page 8
1.2 Standard Features
The SL150 incorporates several standard features
designed to optimize user satisfaction and safety.
SLOW START: This feature provides a gradual
increase in high voltage until the preset operating
point is reached. The slow start time is factory set
for 6 seconds. Other slow start times are available as
an option.
ARC DETECT / ARC QUENCH / ARC COUNT:
These features allow the user to tailor the power
supply to meet specific needs in dynamic load
applications. If an arc occurs, the output is inhibited
for approximately one second, then the output is
ramped up to the preset level with the slow-start
circuitry. See Chapter 3 for operating details and
information for user customization of these features.
INTERNAL FAULT PROTECTION: The SL
Series continually monitors internal circuits critical to
the proper operation of the power supply. In the
event that one of these circuits does not function
correctly, the fault detection circuit latches the
appropriate fault on the front panel display and turns
off the output and reverts the unit to the POWER
DOWN mode.
INDICATOR LAMPS: LINE POWER, HIGH
VOLTAGE OFF AND HIGH VOLTAGE ON
indicators.
OUTPUT CABLE: All models are provided with a
ten foot shielded high voltage output cable. The
cables are designed with a plug arrangement so that
they can be easily removed from the mating
receptacle located on the rear of the chassis.
1.2.1 Remote Operating Features
REMOTE PROGRAMMING: Allows remote
adjustment of the output voltage and current via an
external voltage source. The output power is also
remotely controllable when the CPC or APT option
is ordered, TB1 only.
REMOTE MONITOR: Allows remote monitoring
of the output voltage and current.
REMOTE HIGH VOLTAGE CONTROL:
Allows remote control of HIGH VOLTAGE ON and
HIGH VOLTAGE OFF. Signals are also provided
for remote indication of HV ON or HV OFF status.
EXTERNAL INHIBIT: A control signal that will
inhibit the high voltage output is provided on the
external interface. A logic low, ground, will inhibit
the high voltage output an d a logic high, open, will
restore the high voltage output to the preset level.
NOTE: The External Inhibit circuit should NOT be used
for protection against injury or for safety interlock.
See External Interlock for this type of safety control.
EXTERNAL INTERLOCK: Interlock connections
are provided on the external interface on the rear of
the chassis for connection to a safety switch. The
unit will not operate unless the interlock circuit is
closed. During high voltage operation, opening the
interlock circuit will cause the High Voltage to shut
off. This circuit should be used for safety interlock
circuits.
1.2.2 System Status and Fault
Diagnostic Display
“Dead Front” type indictors are provided to give the user
complete indication of system operation and fault
conditions. If a fault occurs, the power supply will revert
to the POWER DOWN mode. This is indicated by both
the HV ON and HV OFF lamps turning off. To reset,
depress the HV OFF switch.
VOLTAGE (CONTROL): Indicates the output
voltage regulator circuit is maintaining voltage
regulation.
CURRENT (CONTROL): Indicates the output
current regulator circuit is maintaining current
regulation.
POWER (CONTROL): Indicates the output power
regulator circuit is maintaining power regulation
(optional).
HV INHIBIT: Indicates that the high voltage
supply is being inhibited by either the EXTERNAL
INHIBIT or internal protection circuitry.
NOTE: Output power remote monitor is included with
the CPC and APT options, TB1 only.
SL150 MANUAL 2 118093-001 REV B
INTLK CLSD: Indicates the EXTERNAL
INTERLOCK connections are in the closed position.
This also indicates closure of internal power supply
interlocks.
Page 9
INTKL OPEN: Indicates the EXTERNAL
INTERLOCK connections are in the open position.
This also indicates opening of internal power supply
interlocks.
OVERVOLT: Indicates the overvoltage protection
circuitry has caused the power supply to turn off.
Overvoltage protection is internally set to 110% of
the rated output voltage.
OVERCURR: Indicates the output current has
exceeded the programmed current trip level when the
AOL (Adjustable Overload Trip) or the OL
(Overload Trip) options are installed.
OVERPOWER: Indicates the output power has
exceeded the internally set level or the remote
programmed level if the optional circuitry is
installed.
ARC: Indicates that an arc has occurred within the
previous one second or that the ARC COUNT/TRIP
has shutdown the power supply.
RGLT ERR: Indicates a failure in the voltage,
current or power regulation circuitry. This fault
usually occurs when there is a lack of output power
to maintain regulation.
The options available are listed in Table 1.1. See Section
5 for more information on these options along with
operating and set-up instructions. With few exceptions,
these options and modifications can be retrofitted to your
power supply at the factory in a short time. For price and
retrofit arrangements, contact the Spellman Sales
Department.
1.3 Options
AOL Adjustable Overload Trip (0-103%)
APT Adjustable Power Trip
AT Arc Trip
CPC Constant Power Control
SS(x) Non-Standard Slow Start
NSS No Slow Start
LR Low Ripple (0.05% p-p)
DPM4
PN Reversible Polarity
LL (x) Extra Length Output Cable in Feet
EFR External Fault Relay
BFP Blank Front Panel
NAD No ARC Detect
RFR Remote Fault Reset
4 1/2 Digit 1 Least Significant Digit Panel Mtr
Table 1.1 SL150 Options
Note: APT/CPC cannot be combined with EFR
SL150 MANUAL 3 118093-001 REV B
Page 10
1.4 Interpreting the Model Number
The model number of the power supply describes its
capabilities. After the series name is:
1. the maximum voltage (in kV).
2. the p olarity of the unit: positive (P), negative (N) or
reversible (PN).
3. the maximum output (in watts).
4. the option codes for all options that are included.
Custom units have an X number after the option codes.
SL 150 P 1200 / AOL / X (#)
Series
Name
Maximum
Voltage
Polarity
Maximum
Option
Custom
“X”
Number
Power
SL150 MANUAL 4 118093-001 REV B
Page 11
Chapter 2
INSPECTION &INSTALLATION
nitial inspection and preliminary checkout procedures
are recommended. For safe operation, please follow
I
the step-by-step procedures described in Chapter 3,
Operating Systems.
2.1 Initial Inspection
Inspect the package exterior for evidence of damage due
to handling in transit. Notify the carrier and Spellman
immediately if damage is evident. Do not destroy or
remove any of the packing material used in a damaged
shipment.
After unpacking, inspect the panel and chassis for visible
damage.
Fill out and mail the Warranty Registration card
accompanying the unit. Standard Spellman SL Series
high voltage power supplies and components are covered
by warranty. Custom and special order models (with an
X suffix and the model number) are also covered by
warranty.
2.2 Mechanical Installation
Units in the SL Series have front panel holes for standard
EIA rack mounting. The rack must allow rear access for
cable connections. Units are fully enclosed and are
suitable for bench or table top operation. Standard unit
dimensions are shown in Figure 2.1.
SL150 MANUAL 5 118093-001 REV B
Page 12
JB4
I/O INTERFACE
LINE INPUT
J1
REAR VIEW
Figure 2.1 SL150 Dimensions
SL150 MANUAL 6 118093-001 REV B
Page 13
Chapter 3
OPERATING INSTRUCTIONS
3.1 Operation
WARNING
THIS EQUIPMENT GENERATES DANGEROUS
VOLTAGES THAT MAY BE FATAL.
PROPER GROUNDING OF ALL HIGH VOLTAGE
EQUIPMENT IS ESSENTIAL.
WARNING
BEFORE CONNECTING THE POWER SUPPLY
TO THE AC LINE, FOLLOW THIS STEP BY STEP
PROCEDURE.
DO NOT CONNECT THE POWER SUPPLY TO
THE AC LINE UNTIL STEP H IS REACHED.
Failure to follow these procedures may void the warranty.
A) Insure that the Circuit Breaker is in the OFF position
(0).
E) Plug the high-voltage output cable provided with the
unit into the rear of the supply and hand tighten the
knurled collar.
F) OPTIONS NOTE: See Section 5 for hook-up and
operating instructions for the options on your unit.
Custom models may also require set-up changes.
G) For initial turn-on, rotate the KILOVOLT control
fully counter-clockwise to the zero voltage position.
H) The input power cable may now be connected to the
AC power line.
I) Switch the front panel circuit breaker to the ON
position (1). (If the supply is to be turned off for an
extensive period of time, the line cord should be
disconnected). The unit is now in the HIGH
VOLTAGE OFF mode. The HIGH VOLTAGE OFF
light should be lit.
B) Check the input voltage rating on the nameplate of
the supply and make certain that this is the rating of
the available power source.
C) PROPER GROUNDING TECHNIQUES: The
chassis of high voltage power supplies must be
grounded, preferably to a water system ground using
copper pipe or other earth ground using the ground
stud B1 at the rear of the unit. See Figure 3.1 for a
typical operating set-up.
The return line from the load should be connected to
the ground stud on the rear of the power supply.
Using a separate external ground at the load is not
recommended.
D) Attach the output cable to the load.
SL150 MANUAL 7 118093-001 REV B
Page 14
J) Depress and hold the HIGH VOLTAGE OFF switch.
The front panel meters will now read the preset value
of the KILOVOLT control dial and the
MILLIAMPERES control dial. To preset the desired
level of current and voltage during operation, hold in
the HIGH VOLTAGE OFF switch and rotate the
appropriate control dial while noting its
corresponding meter reading. Release the HIGH
VOLTAGE OFF switch.
NOTE: No actual output is being produced at this stage.
K) Depress the HIGH VOLTAGE ON switch. The light
inside the switch should light up and the output will
slow start to the preset level output voltage and/or
output current.
NOTE: The SL Series is equipped with a slow start
circuit that ramps the output up to its maximum
setting in approximately 6 seconds after the HIGH
VOLTAGE ON switch is depressed.
L) To terminate the generation of output power, depress
the HIGH VOLTAGE OFF switch. In the HIGH
VOLTAGE OFF mode the power supply’s fault and
interface circuits are still active.
M) To turn off the power supply, turn the circuit breaker
to the off position (0).
NOTE: If a power supply fault, or system
monitoring fault occurs, the power supply will revert
to the POWER DOWN mode. In this mode the
output power will be turned off. The HV OFF lamp
will be off. To reset, depress the HV OFF switch.
AFTER TURNOFF, DO NOT HANDLE THE LOAD
UNTIL THE CAPACITANCE HAS BEEN
LOAD CAPACITANCE MAY BE DISCHARGED BY
SHORTING TO GROUND.
THE VOLTMETER ON THE POWER SUPPLY
FRONT PANEL DOES NOT READ THE OUTPUT
VOLTAGE WHEN THE POWER IS TURNED OFF,
EVEN IF A CHARGE STILL
EXISTS ON THE LOAD.
WARNING
DISCHARGED!
WARNING
CAUTION
ALWAYS OPERATE THE UNIT WITH THE COVER
A fan maintains safe operating temperature in the power
supplies by drawing air over the circuit components. The
cover must be on in order to direct the air flow over the
areas that need cooling. In operation, the unit must be
placed so that the air intake and the fan exhaust are clear
of obstructions that might impede the flow of air.
ON.
3.2 Standard Features
A note on remote interface circuitry and remote signal
grounding. Whenever possible, electrical isolation should
be provided when interfacing with any high voltage
power supply. For power control signals such as
EXTERNAL INTERLOCK, HIGH VOLTAGE OFF,
AND HIGH VOLTAGE ON, isolated relay contacts
should be used. For status signals and control signals
such as HIGH VOLTAGE ON, HIGH VOLTAGE OFF,
and EXTERNAL INHIBIT, etc., opto-isolation should be
used. If possible, analog programming and monitoring
signals should be isolated via analog isolation amplifiers.
Spellman application engineers are available to assist in
interface circuitry design. All interface cables should be
properly shielded. All power supply signals should be
referenced to the power supplies signal ground on the rear
external interface.
REMOTE PROGRAMMING: Allows remote
adjustment of the output voltage and current via an
external voltage source. (Output power is also
remotely controllable with the CPC and APT
options). In local control (front panel control),
jumpers are installed on the external interface JB4 in
the rear of the chassis between JB4-10 and JB4-11
for voltage control and between JB4-8 and JB4-9 for
current control.
For remote programming, the jumpers are removed and a
positive voltage source, from 0V to 10 V, is applied to the
appropriate terminals. Programming signals should be
referenced to JB4-1, signal ground. By adjusting the
voltage source from 0V (zero output) to 10V (full rated
output), the desired output can be selected. See Figure
3.2A on page 12 for the wiring diagram and
specifications.
An alternate method of controlling the output remotely is
by using external resistance, such as a potentiometer or a
resistor network. For remote control the jumpers are
removed and the desired register configuration installed.
See Figure 3.2B on page 12 for the wiring diagram.
SL150 MANUAL 8 118093-001 REV B
Page 15
REMOTE MONITOR: Test points are made
available at the terminal block on the rear of the
chassis for monitoring the voltage and current output.
(Output power monitor is included with the CPC and
APT option). The test points are always positive
regardless of the output polarity where 0V to 10V
equals 0 to 100% of the output 0.5%. Test points
have an output impedance of 5K ohms. See Figure
3.3 on page 13 for the test point designation.
REMOTE CONTROL: Remote control of the
HIGH VOLTAGE ON and HIGH VOLTAGE OFF
can be accomplished via the rear panel interface.
HIGH VOLTAGE OFF and HIGH VOLTAGE ON
can be controlled by momentary normally closed and
normally open contacts respectively. See Figure 3.4
on page 13 for the recommended interface.
EXTERNAL INHIBIT: Allows the user to inhibit
the power supply output without switching HIGH
VOLTAGE OFF control. This circuit can be used to
generate fast slewing output waveforms or control of
high voltage generation as in Laser and Capacitor
discharge applications. The maximum inhibit rate
should not exceed 5Hz. Consult the factory for
higher repetition rates or high pulse load
applications. See Figure 3.5 on 14 for the
recommended interface circuit.
WARNING
IT IS EXTREMELY DANGEROUS TO USE THIS
INHIBIT CIRCUIT TO INHIBIT HIGH VOLTAGE
GENERATION FOR THE PURPOSE OF
SERVICING OR APPROACHING ANY AREA
OR LOAD CONSIDERED UNSAFE
DURING NORMAL USE.
EXTERNAL INTERLOCK: Interlock connections
are provided on JB4-3 and JB4-4 on the rear of the
chassis for connection to a safety switch. The unit
will not operate unless the interlock circuit is closed.
If the interlock is not being used, the jumper installed
on the terminals before shipping must be in place. If
the jumper is missing, or there is an opening between
the interlock terminals, the unit’s high voltage
inverter will be disabled. During high voltage
operation, revert to the HIGH VOLTAGE OFF
mode. Subsequent closing of the interlock circuit
will NOT return the unit to the HIGH VOLTAGE
ON mode. This must be accomplished by depressing
the HIGH VOLTAGE ON switch. See Figure 3.6 on
page 14 for the recommended interface circuit
ARC DETECT / ARC QUENCH / ARC COUNT:
The ARC DETECT circuit senses dynamic arcing or
discharge conditions present at the output load. If an
arc occurs, the output is inhibited for one second.
After the one second period, the output is ramped up
to the previous set level. This ramp is based on the
standard six second slow start feature. The ARC
DETECT ramp circuit may be disabled by removing
CR32 on the Control/Power Pwb. Caution should be
observed if this feature is disabled. Discharge rates
of greater then 1Hz may cause excessive power
dissipation in the power supply’s output limiting
resistors.
The ARC COUNT feature will allow the user to program
the ARC fault parameters. The ARC indicator on the
front panel will illuminate for approximately one second
after each arc has occurred. The power supply can be
programmed to trip the POWER DOWN mode if an arc
occurs.
The standard feature is programmed to trip the power
supply if 8 arcs occur within a twenty second period.
REMOTE HIGH VOLTAGE ON & REMOTE
HIGH VOLTAGE OFF: Signals are provided for
remote monitoring of the HIGH VOLTAGE
ON/OFF status. See Figure 3.7 on page 15 for
recommended interface.
REMOTE MODE INDICATORS: Signals are
provided for remote indication of the control mode
status, voltage control, current control, and power
control. See Figure 3.8 on page 16 for the
recommended interface.
SL150 MANUAL 9 118093-001 REV B
Page 16
LINE INPUT
JB4
I/O INTERFACE
J1
Figure 3.1 Typical Operating Setup
SL150 MANUAL 10 118093-001 REV B
Page 17
JB4 SIGNAL SIGNAL PARAMETERS
1 Power Supply Common Signal Ground
2 External Inhibit Ground = Inhibit, Open = HV ON
3 External Interlock +15V at Open, <15mA at Closed
4 External Interlock Return Return For Interlock
5 Current Monitor 0 to 10V = 0 to 100% Rated Output
6 kV Test Point 0 to 10V = 0 to 100% Rated Output
7 +10V Reference +10.24V, 1mA Max
8 Remote Current Program In 0 to 10V = 0 to 100% Rated Output
9 Local Current Program Out Front Panel Program Voltage
10 Remote Voltage Program In 0 to 10V = 0 to 100% Rated Output
11 Local Voltage Program Out Front Panel Program Voltage
12 EFR (Common)
Power Monitor
13 EFR (Normally Open)
Optional External Fault Relay
0-10V = 0-100% Rated Power (Optional)
Remote Power Program In – Optional
14 Local HV Off Out +15V at Open, < 25mA at Closed.
Connect to HV OFF For FP Operation
15 HV OFF 16 Remote HV ON +15V, 10mA Max = HV ON
17 Remote HV OFF Indicator 0 = HV ON, +15V, 10mA Max = HV OFF
18 Remote HV ON Indicator 0 = HV OFF, +15V, 10mA Max = HV ON
19 Remote Voltage Mode 20 Remote Current Mode Open Collector 50V Max, 10mA Max On = Active
21 Remote Power Mode 22 Remote PS Fault 0 = Fault, +15V, 0.1 Ma Max = No Fault
23 +15V Output +15V, 100mA Max
24 Power Supply Common Signal Ground
25 Shield Return Chassis Ground
Table 3.1 - Rear Panel Interface 25 pin Mini D
SL150 MANUAL 11 118093-001 REV B
Page 18
Voltage Source 0-10V = 0-100% of Rated Output
It is recommended that analog signals be isolated via
isolation amplifiers.
All cables should be shielded
with the shield being returned to the chassis ground
of the High Voltage Power Supply.
Remove jumpers for
remote programing
JB4
1
2
3
4
5
6
7
8
9
10
11
PS Common
-
V
+
Z in = 10M ohm
Z in = 10M ohm
Remote
Current
Program
V
-
Remote
Voltage
Program
+
Figure 3.2A -- Wiring Diagram For Remote Programming Via Voltage
Fully Counterclockwise = Zero Output
Fully Clockwise = 100% of Rated Output
All cables should be shielded with the shields
being returned to the chassis ground of the
High Voltage Power Supply.
If connections to external potentiometers are
excessively long (>10ft), motorized
potentiometers are recommended.
Remove jumpers for
remote programing
1
2
3
4
5
6
7
8
9
10
11
PS Common
20k ohm
+10.32V
1mA max.
Z in = 10M ohm
Z in = 10M ohm
CW
20k ohm
Remote
Current
Control
Remote
Voltage
Control
CW
Figure 3.2B -- Wiring Diagram For Remote Programming Via External
JB4
SL150 MANUAL 12 118093-001 REV B
Page 19
JB4
r
r
It is recommended that analog signals be isolated via
isolation amplifiers.
All cables should be shielded
with the shield being returned to the chassis ground
of the high voltage power supply.
Figure 3.3 -- Remote Monitor Test Point Designations
S1 must be closed to enable HIGH VOLTAGE.
Momentary closure of S2 will enable HIGH
VOLTAGE ON.
Opening S1 will disable HIGH VOLTAGE ON and
switch the unit to the HIGH VOLTAGE OFF mode.
PS Common
1
2
3
4
M
Current
Monitor
M
-
Voltage
Monitor
+
5
Z out = 4.99k ohms ±0.1%
6
Z out = 4.99k ohms ±0.1%
7
It is recommended to use relay contacts fo
S1 and S2. Relays should be located as
close as possible to the high voltage powe
supply. Coils should be driven from isolated
sources. Signals are at 15Vdc, 25mA max.,
and are only to be used for contact closure.
+
JB4
S1
S1 = Remote High
Voltage Off
Remove jumpers for
remote programing
14
15
S2
S2 = Remote High
Voltage On
All cables should be shielded
with the shields being returned
to the chassis ground of the
High Voltage Power Supply.
16
17
Figure 3.4 -- Remote Control Of High Voltage On and High Voltage Off
SL150 MANUAL 13 118093-001 REV B
Page 20
The transistor should be located as close as possible
to the power supply
All cables should be shielded with the shields
being returned to the chassis ground of the
High Voltage Power Supply.
+15V
JB4
2.2k
High Voltage Power
Supply Internal inhibit circuitry.
Figure 3.5 -- External Inhibit Interface Circuit
Relay contacts are recommended for S1. The relay
should be located as close as possible to the power supply.
Signals are at 15Vdc, 25mA max and are only to be used
for contact closure.
JB4
1
2
PS Common
1
2
3
4
Transistor
ON
Inhibits
High
Voltage
External Safety
Interlock Control
Remove jumper
for remote
external interlock
All cables should be shielded with the shields being returned
to the chassis ground of the High Voltage Power Supply.
SL150 MANUAL 14 118093-001 REV B
3
S1
4
5
S1 Open= Interlock Open
S1 Closed= Interlock Closed
Figure 3.6 -- External Interlock Interface
Page 21
12Vdc lamps or relay coils may replace opto-couplers.
Opto-couplers, lamps or relays should be located as close
as possible to the high voltage power supply.
All cables should be shielded with the shields being returned
to the chassis ground of the High Voltage Power Supply.
JB4
PS Common
1
2
3
4
P/O High Voltage
Power Supply
1K
1/4 W
1K
1/4 W
10
11
12
13
14
15
16
17
18
5
General Purpose
Opto-Coupler
6
7
8
9
To High Voltage
OFF Indicator
General Purpose
Opto-Coupler
To High
Voltage
ON
Indicator
R Limit
R Limit
Signals are = 15Vdc, 10mA max.
R Limit must be > 500
Figure 3.7 -- Remote High Voltage On and
Remote High Voltage Off Indicator
SL150 MANUAL 15 118093-001 REV B
Page 22
R1
R2
R3
JB4
23
R limit
19
R limit
20
R limit
21
Figure 3.8 -- Remote Mode Indicators Interface
10mA max.
10mA max.
10mA max.
R Limit must be > 1kW
R1-R3=680W 1/4W
Voltage Control
Indicator
Current Control
Indicator
Power Control
Indicator
SL150 MANUAL 16 118093-001 REV B
Page 23
Chapter 4
PRINCIPLES OF OPERATION
The SL150 high voltage power supply utilizes
sophisticated power conversion technology. A variety of
analog, digital and power conversion techniques are used
throughout. The intention of the Principles of Operation
is to introduce the basic function blocks that comprise the
SL power supply. For details on a specific circuit,
consult Spellman’s Engineering Department.
Due to the many variations within the SL Series,
drawing numbers may differ from unit to unit.
The SL power supply is basically an AC to DC power
converter. Within the power supply, conversions of AC
to DC then to high frequency AC, then to high voltage
DC take place. By reviewing further the sub-assemblies,
a basic understanding of the process can be gained.
4.1 Chassis
The SL is a compact, high efficiency, high voltage power
supply. The power supply can supply up to 1200 watts of
DC power.
The energy levels used and generated by the
power supply can be lethal! Do not attempt to
operate the power supply unless the user has a
sufficient knowledge of the dangers and hazards
of working with high voltage. Do not attempt to
approach or touch any internal or external
circuits or components that are connected or
have been connected to the power supply. Be
certain to discharge any stored energy that may
be present before and after the power supply is
used. Consult IEEE recommended practices for
safety in high voltage testing #510-1983.
WARNING
SL150 MANUAL 17 118093-001 REV B
Page 24
4.2 High Voltage Transformer
The output of the High Frequency Resonant Inverter is
connected to the primary of the High Voltage
Transformer. The High Voltage Transformer is a set up
type.
4.3 High Voltage Assembly
The High Voltage Assembly typically consists of various
parallel, series arrangements of a full wave voltage
doubler.
Output filtering is typically provided by an R-C type
filter. Voltage feedback for regulation and monitoring is
provided by a high bandwidth resistive/cap acitive divid er.
Current feedback for regulation and monitoring is
provided by a sense resistor connected at the low voltage
end of the High Voltage Rectifier/Multiplier Circuit.
4.4 Control/Power PWB
The majority of control circuits for power supply controls
are located on the CONTROL/POWER PWB. +15VDC, 15VDC, and +10VDC is generated on the
CONTROL/POWER PWB. High Voltage On/Off control
is accomplished by K3, and its associated circuitry.
Interlock control is provided by K4.
Voltage feedback from the high voltage divider is sent to
the control board via a mass terminated ribbon cable.
Gain adjustment is provided on the HV PWB. The kV
feedback signal is sent to the front panel DVM and to the
REAR PANEL D- CONNECTOR for remote monitoring.
K2 provides switching between feedback and program
signal for the front panel DVM’s. This allows the user to
preset the desired output before energizing high voltage.
Program voltages are typically ramped up to set level by a
slow start circuit.
An arc sense circuit provides sensing, quench and
indicator of arc conditions. Consult the operation manual
for a detailed description of the arc sense control.
Current feedback from the high voltage rectifier is sent to
sense resistors located on the High Voltage Assembly.
Calibrated feedback is then sent to the applicable circuitry
on the Control/Power Board.
U12 circuit provides visual indication of the control
mode, which is in operation. These signals are sent to the
FRONT PANEL ASSEMBLY for front panel status
indication.
The resonant control circuitry consists of a pulse width
converter. U17 generates all frequency and pulse width
control signals.
Power supply inhibit circuits are provided by U22 and
K3. System Fault control and Indication is provided by
U19 and associated circuitry. Diagnostic signals are
latched and then sent to the FRONT PANEL
ASSEMBLY for status indication.
4.5 Front Panel Assembly
Front Panel controls, meters and status indications are
connected to the FRONT PANEL PWB. The FRONT
PANEL PWB interfaces directly to the
CONTROL/POWER PWB.
4.6 Options
Due to the many variations of models and options
provided in the SL150, details of actual circuits used may
differ slightly from the above descriptions. Consult
Spellman’s Engineering Department for questions
regarding the principles of operation for the SL Series.
SL150 MANUAL 18 118093-001 REV B
Page 25
Chapter 5
OPTIONS
he options available for this power supply are
described in this section. Interface diagrams are
T
shown where required. Options are specified by
including the option code in the model number as
described in Section 1.5.
5.1 Adjustable
Overload Trip --AOL
The overload trip protection feature rapidly shuts down
the high voltage output when the current exceeds the limit
set by the current control dial on the front panel. A fast
acting circuit inhibits the generation of high voltage and
reverts the unit to POWER DOWN mode, illuminating
the OVER CURRENT indicator. When adjustable
overload trip is provided, it replaces the standard current
regulation feature.
5.2 200Vac Single Phase
Input--200
SL Series power supplies with the 200Vac input option
will operate from an input voltage of 200Vac RMS
10%, 50 to 60Hz, single phase.
5.3 No Slow Start--NSS
The no slow start option causes the output voltage of the
power supply to rise (within 50 msec) to the rated voltage
upon depressing the HIGH VOLTAGE ON switch.
5.4 Non-Standard Slow
Start--SS(x)
The non-standard slow start option allows the gradual rise
time of the output voltage to be different from the
standard of six seconds. To order the option place the
time desired in seconds after the suffix letter, i.e. SS (10)
denotes a 10 second rise time.
5.5 Extra Length Output
Cable--LL(ft)
Standard output cable is 10 feet of shielded high voltage
cable. Other lengths may be specified in multiples of 10
feet.
5.6 Arc Trip Option--AT
When this option is ordered, the Arc Count circuit is set
so the unit trips to Standby after 1 count. One of the
applications for this option is for sensing a material
breakdown under an applied high voltage.
5.7 Reversible
Polarity Option--PN
5.8 Adjustable Power
Trip/Constant Power Control
APT/CPC Option
The power control options allow monitoring and control
of the power supply output power. The APT option
allows the user to remotely adjust the power limit for the
power supply. If the power limit is exceeded, the unit
will shut down with an OVERPOWER fault. The CPC
option allows power regulation via an internal preset
potentiometer, or a remote program source. When the
unit is in power regulation, the POWER CONTROL
status indicator will be illuminated. See Figure 5.1 for
remote interface.
SL150 MANUAL 19 118093-001 REV B
Page 26
5.9 External Fault Relay Option
EFR
The external fault relay option provides a set of customer
accessible relay contacts that are controlled by the fault
status circuitry of the applicable SL Series power supply.
A standard SL power supply will revert to the “power
down” mode with a visual front panel indication if any of
the following fault conditions occur:
Overvoltage: Greater than 110% of maximum
output voltage was produced by the power supply.
Overcurrent: Greater than 104% of maximum
output current was produced by the power supply or
the AOL circuitry was activated.
Overtemperature: Excessive temperature has been
sensed within the chassis.
Regulation Error: Lack of required output power to
maintain regulation
Arc (Shutdown): Arc sensing circuit has shut down
the supply due to excessive arcing.
Overpower: The power supply has exceeded the
internally set power limit level, if such circuitry is
installed.
With the installation of the EFR option, if any of these
faults occur, a relay will be activated to provide a remote
indication that the power supply has reverted to the
“power down” mode. The common, normally open and
normally closed set of contacts are provided. Relay
contacts are rated at 1A at 30Vdc or 0.5A at 48Vac.
Resetting the front panel and EFR relay is accomplished
by depressing the green front panel HV OFF push-button
switch, which reverts the power supply back to the
“standby” mode. Removal and reapplication of the AC
line input voltage will also reset any fault.
The circuitry and components required for the EFR
option are installed at the factory when this option is
ordered.
5.10 No ARC Detect Option NAD
The No ARC Detect option may be utilized by removing
CR32 on the control board. Caution should be observed
if this feature is disabled. Discharge rates of greater than
1Hz may cause excessive power dissipation in the power
supply’s output limiting resistors.
5.11 Remote Fault Reset Option
RFR
Allows the user to remotely reset a fault by momentarily
grounding JB4-12.
5.12 Custom Designed Models-X#
Units built to customer specification are assigned an X
number by the factory. If this unit is an X model, a
specification control sheet is added at the end of the test
of this instruction manual.
Spellman welcomes the opportunity to customize units to
fit your requirements or to develop new products for your
applications. Contact the Spellman Sales Department
with your needs.
Connections on JB4 can be made as follows:
(JB4-12) Relay Common
(JB4-NA) Normally Closed
(JB4-13) Normally Open
SL150 MANUAL 20 118093-001 REV B
Page 27
Remove internal
jumper, JP1 ON
Control/Pwr PWB
for remote
Programing. (Jumper
connects internal,
pot, factory set at
103% of max power).
JB4
1
2
3
4
5
6
12
13
7
M
+
Z in = 10M ohm
Remote
Power
Monitor
0-10V
=0-100%
power
output
Zout=
4.99k ohm 0.1%
V
-
+
Remote
Power
Program
20K ohm
min.
Remote Power
Programming
potentiometer
Figure 5.1 Adjustable Power Remote Interface Option
SL150 MANUAL 21 118093-001 REV B
Page 28
DETAIL A
FILAMENT OUTPUT
LINE INPUT
BB
CB1
A5
A5
A1
A5
5
A
LAN
USB RS232
TB1
JB1
+ -
I/O INTERFACE
J1
A6
A1
A7
DETAIL A
REAR VIEW
A5
Figure 5.2 Reverse Polarity Option
VIEW B-B
SL150 MANUAL 22 118093-001 REV B
Page 29
Chapter 6
MAINTENANCE
his section describes periodic servicing and
performance testing procedures.
T
WARNING
THIS POWER SUPPLY GENERATES VOLTAGES
THAT ARE DANGEROUS AND MAY BE FATAL.
OBSERVE EXTREME CAUTION WHEN
WORKING WITH HIGH VOLTAGE.
6.1 Periodic Servicing
Approximately once a year (more often in high dust
environments), disconnect the power to the unit and
remove the top cover. Use compressed air to blow dust
out of the inside of the unit. Avoid touching or handling
the high voltage assembly. Be sure that the fan is not
obstructed and spins freely. The fan has sealed bearings
and does not need lubrication. Be sure to replace the top
cover before operating for proper cooling.
6.2 Performance Test
WARNING
HIGH VOLTAGE IS DANGEROUS.
ONLY QUALIFIED PERSONNEL SHOULD
PERFORM THESE TESTS.
High voltage test procedures are described in Bulletin
STP-783, Standard Test Procedures for High Voltage
Power Supplies. Copies can be obtained from the
Spellman Customer Service Department. Test equipment,
including an oscilloscope, a high impedance voltmeter,
and a high voltage divider such as the Spellman HVD200 is needed for performance tests. All test components
must be rated for operating voltage.
6.3 High Voltage Dividers
High voltage dividers for precise measurements of output
voltage with an accuracy up to 0.1% are available. An
HVD-200 measures up to 200kV. The Spellman divider
is designed for use with differential voltmeters or high
impedance digital voltmeters. The high input impedance
is ideal for measuring high voltage low current sources,
which would be overloaded by traditional lower
impedance dividers.
SL150 MANUAL 23 118093-001 REV B
Page 30
Chapter 7
REPLACEMENT PARTS
7.1 Replacement Parts
Contact the Spellman Customer Service Department for
parts lists for specific models.
Parts and subassemblies for Spellman’s high voltage
power supplies are available. It is recommended that only
qualified personnel perform the repairs. High voltage is
dangerous; even minor mistakes in repairs can have
serious consequences.
When requesting parts please give the model number and
serial number of the power supply.
7.2 Correspondence and Ordering
Spare Parts
Each power supply has an identification label on the rear
of the chassis that bears its model and serial number.
When requesting engineering or applications information,
please state the model and serial number of the power
supply.
When ordering spare parts, please specify the part
number, the component function and the model and serial
number of the unit.
SL150 MANUAL 24 118093-001 REV B
Page 31
Chapter 8
FACTORY SERVICE
8.1 Warranty Repairs
During the Warranty period, Spellman will repair all units
free of charge. The Warranty is void if the unit is worked
on by other than Spellman personnel. See the Warranty in
the rear of this manual for more information. Follow the
return procedures described in Section 8.2. The customer
shall pay for shipping to and from Spellman.
8.2 Factory Service Procedures
Spellman has a well-equipped factory repair department. If
a unit is returned to the factory for calibration or rep air, a
detailed description of the specific problem should be
attached.
For all units returned for repair, please obtain an
authorization to ship from the Customer Service
Department, either by phone or mail prior to shipping.
When you call, please state the model and serial numbers,
which are on the plate on the rear of the power supply, and
the purchase order number for the repair. A Return
Material Authorization Code Number (RMA Number) is
needed for all returns. This RMA Number should be
marked clearly on the outside of the shipping container.
Packages received without an RMA Number will be
returned to the customer. The Customer shall pay for
shipping to and from Spellman.
8.3 Ordering Options and
Modifications
Many of the options listed in Chapter 5 can be retrofitted
into Spellman’s power supplies by our factory. For prices
and arrangements, contact the Spellman Sales Department.
8.4 Shipping Instructions
All power supplies returned to Spellman must be sent
shipping prepaid. Pack the units carefully and securely in a
suitable container, preferably in the original container, if
available. The power supply should be surrounded by at
least four inches of shock absorbing material. Please return
all associated materials, i.e. high voltage output cables,
interconnection cables, etc., so that we can examine and test
the entire system.
All correspondence and phone calls should be directed to:
Spellman High Voltage Electronics Corp.
475 Wireless Boulevard
Hauppauge, New York 11788
TEL: (631) 630-3000 FAX: (631) 435-1620
E-Mail: sales@Spellmanhv.co
m
A preliminary estimate for repairs will be given by phone
by Customer Service. A purchase order for this amount is
requested upon issuance of the RMA Number. A more
detailed estimate will be made when the power supply is
received at the Spellman Repair Center. In the event that
repair work is extensive, Spellman will call to seek
additional authorization from your company before
completing the repairs.
SL150 MANUAL 25 118093-001 REV B
Page 32
WICHTIGE SICHERHEITSHINWEISE
SICHERHEIT
DIESES HOCHSPANNUNGSNETZTEIL ERZEUGT LEBENSGEFÄHRLICHE HOCHSPANNUNG.
SEIN SIE SEHR VORSICHTIG BEI DER ARBEIT MIT DIESEM GERÄT.
Das Hochspannungsnetzteil muß immer geerdet sein.
Berühren Sie die Stecker des Netzteiles nur, wenn das Gerät ausgeschaltet ist und die elektrischen
Kapazitäten des Netzteiles und der angeschlossenen Last entladen sind.
Die internen Kapazitäten des Hochspannungsnetzteiles benötigen ca. 5 Minuten, um sich zu entladen.
Erden Sie sich nicht, und arbeiten Sie nicht in feuchter oder nasser Umgebung.
SERVICESICHERHEIT
Notwendige Reparaturen können es erforderlich machen, den Gehäusedeckel während des Betriebes zu
entfernen.
Reparaturen dürfen nur von qualifiziertem, eingewiesenem Personal ausgeführt werden.
“WARNING” im folgenden Text weist auf gefährliche Operationen hin, die zu Verletzungen oder zum Tod
führen können.
“CAUTION” im folgenden Text weist auf Prozeduren hin, die genauestens befolgt werden müssen, um
eventuelle Beschädigungen des Gerätes zu vermeiden.
118004-001 REV. B
Page 33
PRECAUTIONS IMPORTANTES POUR VOTRE SECURITE
CONSIGNES DE SÉCURITÉ
CETTE ALIMENTATION GÉNÈRE DES TENSIONS QUI SONT DANGEUREUSES ET PEUVENT ÊTRE FATALES.
OYEZ EXTRÊMENT VIGILANTS LORSQUE VOUS UTILISEZ CET ÉQUIPEMENT.
S
Les alimentations haute tension doivent toujours être mises à la masse.
Ne touchez pas les connectiques sans que l’équipement soit éteint et que la capacité à la fois de la charge et de
l’alimentation soient déchargées.
Prévoyez 5 minutes pour la décharge de la capacité interne de l’alimentation.
Ne vous mettez pas à la masse, ou ne travaillez pas sous conditions mouillées ou humides.
CONSIGNES DE SÉCURITÉ EN CAS DE REPARATION
La maintenance peut nécessiter l’enlèvement du couvercle lorsque l’alimentation est encore allumée.
Les réparations doivent être effectuées par une personne qualifiée et connaissant les risques électriques.
Dans le manuel, les notes marquées « WARNING » attire l’attention sur les risques lors de la manipulation de ces
équipements, qui peuvent entrainer de possibles blessures voire la mort.
Dans le manuel, les notes marquées « CAUTION » indiquent les procédures qui doivent être suivies afin d’éviter
d’éventuels dommages sur l’équipement.
118004-001 REV. B
Page 34
IMPORTANTI PRECAUZIONI DI SICUREZZA
SICUREZZA
QUESTO ALIMENTATORE GENERA TENSIONI CHE SONO PERICOLOSE E
POTREBBERO ESSERE MORTALI.
PONI ESTREMA CAUTELA QUANDO OPERI CON QUESO APPARECCHIO.
Gli alimentatori ad alta tensione devono sempre essere collegati ad un impianto di terra.
Non toccare le connessioni a meno che l’apparecchio sia stato spento e la capacità interna
del carico e dell’alimentatore stesso siano scariche.
Attendere cinque minuti per permettere la scarica della capacità interna dell’alimentatore
ad alta tensione.
Non mettere a terra il proprio corpo oppure operare in ambienti bagnati o saturi d’umidità.
SICUREZZA NELLA MANUTENZIONE.
Manutenzione potrebbe essere richiesta, rimuovendo la copertura con apparecchio
acceso.
La manutenzione deve essere svolta da personale qualificato, coscio dei rischi elettrici.
Attenzione alle AVVERTENZE contenute nel manuale, che richiamano all’attenzione ai
rischi quando si opera con tali unità e che potrebbero causare possibili ferite o morte.
Le note di CAUTELA contenute nel manuale, indicano le procedure da seguire per evitare
possibili danni all’apparecchio.
118004-001 REV. B
Page 35
SPELLMAN HIGH VOLTAGE ELECTRONICS
WARRANTY
Spellman High Voltage Electronics (“Spellman”) warrants that all power supplies it manufactures will be
free from defects in materials and factory workmanship, and agrees to repair or replace, without charge, any
power supply that under normal use, operating conditions and maintenance reveals during the warranty
period a defect in materials or factory workmanship. The warranty period is twelve (12) months from the
date of shipment of the power supply. With respect to standard SL power supplies (not customized) the
warranty period is thirty-six (36) months from the date of shipment of the power supply.
This warranty does not apply to any power supply that has been:
• Disassembled, altered, tampered, repaired or worked on by persons unauthorized by Spellman;
• subjected to misuse, negligent handling, or accident not caused by the power supply;
• installed, connected, adjusted, or used other than in accordance with the original intended application and/or
instructions furnished by Spellman.
THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
THOSE OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
The buyer’s sole remedy for a claimed breach of this warranty, and Spellman’s sole liability is limited, at
Spellman’s discretion, to a refund of the purchase price or the repair or replacement of the power supply at
Spellman’s cost. The buyer will be responsible for shipping charges to and from Spellman’s plant. The
buyer will not be entitled to make claim for, or recover, any anticipatory profits, or incidental, special or
consequential damages resulting from, or in any way relating to, an alleged breach of this warranty.
No modification, amendment, supplement, addition, or other variation of this warranty will be binding unless
it is set forth in a written instrument signed by an authorized officer of Spellman.
For an authorization to ship contact Spellman’s Customer Service Department. Please state the model and
serial numbers, which are on the plate on the rear panel of the power supply and the reason for return. A
Return Material Authorization Code Number (RMA number) is needed from Spellman for all returns. The
RMA number should be marked clearly on the outside of the shipping container. Packages received without
an RMA Number may delay return of the product. The buyer shall pay shipping costs to and from Spellman.
Customer Service will provide the Standard Cost for out-of-warranty repairs. A purchase order for this
amount is requested upon issuance of the RMA Number (in-warranty returns must also be accompanied by
a “zero-value” purchase order). A more detailed estimate may be made when the power supply is received
at Spellman. In the event that the cost of the actual repair exceeds the estimate, Spellman will contact the
customer to authorize the repair.
Spellman will warrant for three (3) months or balance of product warranty, whichever is longer, the repaired
assembly/part/unit. If the same problem shall occur within this warranty period Spellman shall undertake all
the work to rectify the problem with no charge and/or cost to the buyer. Should the cause of the problem be
proven to have a source different from the one that has caused the previous problem and/or negligence of
the buyer, Spellman will be entitled to be paid for the repair.
For a complete listing of Spellman’s Global Service facilities please go to:
http://www.spellmanhv.com/customerservice/service.asp
Factory Service Procedures
Factory Service Warranty
Spellman Worldwide Service Centers
101520-007 REV D
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.