Spectron BM55-2U, BE55-2U, BE56-2U, BM56-2U Operating Manual

Operating Manual
for the
Pressure Control Panels
of the BM55-2U/BM56-2U
BM55-2U with outlet adapter
BM56-2U with outlet adapter and valve
2 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
Contents
Contents ..................................................................................................................... 2
1.Introduction ........................................................................................................... 3
1.1General ............................................................................................................ 3
1.2Description of the pressure control panels of the BM and BE series .............. 3
1.3Intended use .................................................................................................... 4
1.4Personnel requirements .................................................................................. 5
2.For your safety ..................................................................................................... 5
2.1Symbols used .................................................................................................. 5
2.2Essential safety information ............................................................................ 5
2.3Safety features ................................................................................................ 6
3.Description ........................................................................................................... 8
3.1Overview of the pressure control panel ........................................................... 8
3.2Functional description ................................................................................... 10
3.3Technical data ............................................................................................... 11
3.4Connection options ........................................................................................ 11
3.5Changing the supply side .............................................................................. 11
4.Operation ............................................................................................................ 13
4.1Labelling ........................................................................................................ 13
4.2Installing the pressure control panel .............................................................. 13
4.3Putting the pressure control panel into operation .......................................... 13
4.4Changing the cylinder .................................................................................... 14
4.5Ta king the equipment out of operation .......................................................... 15
5.Problems ............................................................................................................ 16
6.Maintenance, cleaning and repairs ..................................................................... 17
6.1Regular maintenance work and visual inspections........................................ 17
6.2Regular cleaning ........................................................................................... 17
6.3Repair information ......................................................................................... 17
6.4Returns .......................................................................................................... 17
GES_BM+BE_55+56-2U_1212.docx 3
Operating Manual of the BM and BE series
1. Introduction
1.1 General
Validity
This operating manual is valid for the following pressure control panels: BM55-2U, BM56-2U, BE55-2U, BE56-2U.
Manufacturer
Spectron Gas Control Systems GmbH Fritz-Klatte-Straße 8
D-65933 Frankfurt Germany
Phone: +49 69 38016-0 Fax: +49 69 38016-200 Email: info@spectron.de Internet: www.spectron.de
Publication date
December 2012
Retention and completeness
This operating manual is a component of the BM55-2U/BM56-2U/BE55-2U/BE56-2U pressure control
panels and must be accessible to those with the relevant authorisation at all times.
Under no circumstances should chapters be removed from this operating manual. If the operating
manual is lost or if any chapters are missing –in particular the "For your safety" chapter – it or they must be replaced without delay.
Copyright
This operating manual contains information that is protected by copyright. It must not be photocopied, reproduced, translated or copied onto data carriers, either in full or in part, without prior authorisation. All rights reserved.
Updates
No update service is provided for this operating manual by Spectron Gas Control Systems GmbH. Changes can be made to this operating manual without the need to notify anyone about them.
1.2 Description of the pressure control panels of the BM and BE series
Spectron pressure control panels are available in BM and BE versions. BM pressure control panels are suitable for combustible gases, non-combustible gases and oxygen up to a purity grade of 6.0. BE pressure control panels are suitable, in addition, for use with corrosive gases. In addition, there is a distinction between pressure control panels with single-stage pressure relief from the inlet pressure to the desired outlet pressure (type code: 55) and two-stage pressure relief (type code: 56). While two-stage pressure relief ensures an extremely constant outlet pressure throughout the entire inlet pressure range (from "full" gas cylinder to almost "empty" gas cylinder), with single-stage pressure relief the outlet pressure can vary within a certain range.
4 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
1. Introduction
In addition, the outlet pressure drops in the single-stage version at switchover from the operational side to the reserve side. This does not happen with two-stage pressure relief. The 2U pressure control panels are two-sided pressure control panels with a switching mechanism (2U).
The switching mechanism switches automatically from the side that is currently in operation to the reserve side when the gas supply situation requires it. The lever position of the switching mechanism indicates which side is the operational side and which the reserve side. All of the above pressure control panels are equipped with a process gas valve and a waste gas valve on each side. With regard to both the outlet to the supply line and the pressure regulator relief valve, you can choose
between two versions: Pressure regulator with outlet adapter: the outlet and relief valve are located parallel to each other at
the top.
Pressure regulator with outlet adapter and valve: the outlet and relief valve are located parallel to each
other at the top, but there is also a shut-off valve in the outlet. Contact pressure gauges, pressure transducers and pneumatically operated valves can also be configured for each of the above versions.
1.3 Intended use
Intended use
The BM55-2U and BM56-2U pressure control panels described are intended for use with non-corrosive gases up to a purity grade of 6.0. The BE55-2U and BE56-2U pressure control panels are suitable, in addition, for corrosive gases up to a purity grade of 6.0. The permissible gases and pressure ranges are specified on the type plate. Pressure control panels reduce a variable inlet pressure to an outlet pressure that is as constant as possible. The pressure is introduced exclusively via the process gas valve. Appropriate measures must be taken to prevent the introduction of pressure to the pressure regulator outlet via the pipe system.
Pressure control panels without electrical components (such as a contact pressure gauge or pressure transducer) may be used in potentially explosive atmospheres, since they do not have a potential ignition source of their own (ignition hazard evaluated in accordance with DIN EN 13463-1).
The danger of ignition has to be taken into account with pressure control panels with electrical components. It is imperative that this is evaluated on the basis of the documentation of the electrical components, taking into consideration how they are incorporated into the system as a whole, in compliance with directive 94/9/EC (ATEX 95). The user can get more detailed information on the Internet at www.spectron.de
or directly from the customer support staff at Spectron Gas Control Systems GmbH.
Foreseeable misuse
The following operating conditions are deemed to constitute misuse:
Operation with gases that are not specified on the type plate Use with gases in their liquid state Operation outside of the permissible technical limit values Failure to heed and comply with any applicable legal regulations and other provisions Failure to follow the instructions in this operating manual Failure to carry out inspection and maintenance work Failure to heed the information on the type plate and in the product data sheet Pressurisation in reverse
GES_BM+BE_55+56-2U_1212.docx 5
Operating Manual of the BM and BE series
1. Introduction
1.4
Personnel requirements
Definition of an authorised person
An authorised person is a person with a technical training who has received technical instruction about the system as a whole and the associated hazards – gas cylinder – gas type – gas cylinder valve – pressure regulator – and has successfully completed training in the supply of pressurised gases.
Tasks of the operating personnel
The operating personnel must identify problems or irregularities and – if possible and permissible – resolve them.
Requirements to be met by the operating personnel
To be able to do their work, the operating personnel must meet the following requirements: The operating personnel must have received instruction in the operation of the pressure control panel
from an authorised person and must have read and understood this operating manual in its entirety.
2.
For your safety
2.1
Symbols used
Danger This symbol indicates danger of death or physical injury.
2.2
Essential safety information
Note
The safety information given below is to be regarded as supplementary information to the relevant national accident prevention regulations and legislation. All relevant accident prevention
regulations and legislation must be observed under all circumstances. Various laws, regulations, rules and directives have to be observed when handling pressurised gases, depending on the type of gas involved. In Germany the following legislation and publications are applicable (although this is not necessarily a complete list):
ProdSG German equipment and product safety law with the applicable regulations BGV A1 German trade association basic accident prevention regulations BGR 104 German trade association rules on explosion protection BGR 132 German trade association rules for the avoidance of ignition hazards resulting from
electrostatic charges
BGR 500 2.26 German trade association rules on welding, cutting and related work procedures BGR 500 2.31 German trade association rules for working on gas lines BGR 500 2.32 German trade association rules for operation of oxygen systems
Note! Important! Warning! Danger!
6 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
2. For your safety
BGR 500 2.33 German trade association rules for the operation of gas handling systems German technical rules for pressurised gases (TRG) German technical rules for pipelines (TRR) German technical rules for pressure vessels (TRB) German technical rules for operational safety (TRBS) German technical rules for high-pressure gas pipelines (TRGL) German technical rules for hazardous substances (TRGS) Directive 94/9/EC (ATEX) Pressure Equipment Directive 97/23/EC Safety data sheets for the gases used
2.3 Safety features
The pressure regulator of the pressure control panel is equipped with an integrated relief valve to protect the fitting.
Note
The relief valve allows gas that has to be released as a result of an impermissible rise in the
outlet pressure to be blown off.
It does not function as the safety valve for the entire gas supply system.
Important
In the event of the failure of the pressure regulator and its relief valve, a safety mechanism
that meets the requirements of the regulations for operators must be incorporated to protect
downstream fittings, pressure vessels and pipes from excess pressure.
Danger
With combustible, toxic, corrosive and other gases that are harmful to health or the environment,
an exhaust pipe must be connected to the relief valve to take the gas away safely.
The factory setting of the relief valve must not be altered.
Possible hazard Hazard-prevention measures
Danger of death
If oxygen comes into contact with oi l or grea se, the re is a risk of fire due to a chemical reaction.
Keep all parts that come into contact with oxygen free of oil and grease.
Danger of death
Gas escaping into the ambient air can ign ite; there is a risk of fire and explosion.
Smoking and naked flames are strictly prohibited near gas supply equipment.
Danger of death
The pressure control panel may be damaged by unauthorised changes or alterations and may no longer work as intended. There is a risk of the sy stem malfunctioning, catching fire or getting damaged.
No changes or alterations may be made without the written approval of the manufacturer's authorised technical personnel.
GES_BM+BE_55+56-2U_1212.docx 7
Operating Manual of the BM and BE series
2. For your safety
Danger of death
If pressure control panels are used that are not suitable for the relevant gas and pressure range, there is a risk of a fire or explosion o ccurring as a result of a chemical reaction.
The pressure control panel must be suitable for the relevant gas and the pressure ranges involved. Only use for the gases indicated on the device.
If there are no gas types specified on the pressure control panel, you have to ask the manufacturer which gases it can be used with.
On no account must the pressure control panel be put into operation without this information.
Danger of death.
If the pressure control panel is operat ed with combustible, toxic or corrosive gases, the gas can be released into the environment when the relief valve opens.
Relief valves of pressure control panels for combustible, toxic or corrosive gases must have a pipe that brings the gases emitted to a safe recycling facility that complies with regulations.
Danger of death
Gas that escapes in an uncontrolled manner indoors can reduce the oxygen content of the air a nd be lif e­threatening.
Make sure that the outlet end of the blow-off pipe of systems operated indoors is outdoors. In the case of toxic or corrosive gases or gases that are harmful to the environment in some other way, dispose of the blown-off gas in accordance with the applicable regulations.
Danger of death
Oxygen that escapes in an uncontrolled manner indoors can result in a dangerous rise in the oxygen content of the air and an increa se in t he tend ency of clothing and other objects to ignite.
Make sure that the outlet end of the blow-off pipe of oxygen systems operated indoors is outdoors, and do not start a fire or ignite a flame.
Read the EIGA document SAG 79/04/E for more information.
If the pressure control panel is used outside the specified ambient temperature ran ge, ther e is a r isk of the system malfunctioning, catching fire or getting damaged.
Do not use in ambient temperatures below -30 °C or over +60 °C.
If dirt particles get into the pressure r egulator of the pressure control panel, this can damage it or cause it to malfunction.
It must be ensured that no dirt part icles of any kind ca n get into the pressure regulator. That is why a filter is incorporated into the process g as in let of the pressu re control panel.
If the device is not handled properly and used as intended, this may be dangerous for the user and others and may damage it.
Use and handle the pressure control panel only as described in this operating manual.
If the connecting surfaces or gaskets of the fittings are damaged or missing, there is a danger of g as escaping in an uncontrolled manner .
Check the connecting surfaces for damage, and do not install if the connecting surfaces are damaged or gaskets are missing.
8 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
3. Description
3.1 Overview of the pressure control panel
Drawing of the pressure control panel
BM/BE56-2U
Elements of the pressure control panel
Item Designation Correct functioning 1 Pressure regulator Regulates the variable inlet pressure to achieve a set outlet
pressure level.
2 Pressure gauge
Optional contact pressure gauge
Indicates the current inlet pressure. Display and electr. monitoring of the pressure
3 Pressure gauge
Optional contact pressure gauge
Indicates the current outlet pressure of the pressure regulator. Display and electr. monitoring of the pressure
4 Waste gas valve or
purge valve Optionally pneumatic
Is opened to remove the waste gases or vent the process gas pipe.
5 Process gas valve
Optionally pneumatic
Separates the pressure control panel from the gas source.
6 Relief valve Protects the pressure control panel from impermissibly high outlet
pressure. Does not function as a safety valve.
7 Switching mechanism The position of the lever determines which side is in operation as
the supply side.
GES_BM+BE_55+56-2U_1212.docx 9
Operating Manual of the BM and BE series
3. Description
Flow chart of gas supply with a pressure control panel
Legend Process gas valve with inlet filter
Waste gas or purge gas valve Pressure regulator - single-stage Pressure regulator - two-stage Inlet pressure gauge Outlet pressure gauge Relief valve Pigtail Gas cylinder connection Valve port – closed Switching mechanism
Waste gas
Waste gas
Process gas
Waste gas
Waste gas
Waste gas
Waste gas
Process gas
10 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
3. Description
3.2 Functional description
The automatic switching pressure control panels of the BM/BE 55/56-2U series reduce any inlet pressure, provided it is within certain limits, to the outlet pressure required. The pressure is reduced by the pressure regulator used. You select which side of the pressure control panel is to be used by operating the switching mechanism:
Lever up: the pressure regulator on the left is in operation Lever down: the pressure regulator on the right is in operation
The switching mechanism links the pressure regulators with each other by their pressure adjusting spindles. If you shift the lever from the upper position to the lower position, for example, this reduces the outlet pressure in the pressure regulator on the left and increases the outlet pressure in the pressure regulator on the right. The right-hand side is thus currently the operational side. The automatic and interruption-free switchover to the reserve side on the left, where the pressure is set lower, takes place as soon as the outlet pressure on the operational side (on the right) drops to below that of the reserve side. This can happen as a result of the constant emptying of the gas cylinders on the right and thus the falling of the inlet pressure on the operational side to under the level of the reserve side or as a result of very large amounts of gas being drawn, thus lowering the outlet pressure on the operational side quickly. Thus, if the reserve side goes into operation with single-stage switching panels (BM/BE 55-2U), the outlet pressure made available by the switching panel is lower than the outlet pressure made available by the operational side beforehand. The manual operation of the switching lever helps here: it increases the outlet pressure of what has been the reserve side, thus converting it into the operational side, and at the same time reduces the outlet pressure of what has been the operational side up to now. As a result, it becomes the reserve side. In the case of two-stage switching panels, the fall in the outlet pressure as a result of the switchover is
barely noticeable. The outlet pressure is kept largely constant by means of the second regulating stage. All single-stage automatic switching panels have an inlet pressure gauge for each pressure regulator to
indicate the current inlet pressure. Since the pressure regulators are linked to each other on the outlet side, only one pressure regulator has the outlet connection. The other one has the outlet pressure gauge. Depending on the variant, up to the version with an outlet pressure of 100 bar there is an outlet adapter in the outlet with an integrated relief valve or an outlet adapter with an integrated relief valve and shut-off valve. The BM/BE56-2U series have a second regulating stage incorporated into the outlet. An outlet pressure gauge and relief valve are connected to this.
Note
The pressure control panels can be equipped with contact pressure gauges. These issue
a switching signal when a specific pressure limit is violated or, in the same way as pressure
transducers, supply a current that varies continuously with the pressure (4-20 mA).
The switching signal or variable electrical current can be processed by means of connected
control units, resulting, for example, in the issue of a gas shortage alarm.
When these contact pressure gauges or pressure transducers are used in areas where there is
a risk of fire or explosion, special measures have to be taken, as described in directive 95/9/EEC
(ATEX 95). You will find more detailed information at www.spectron.de
. Another option is to equip the pressure control panel with pneumatically operated valves. These require a pneumatic control pressure of between a minimum of 5.5 bar and a maximum of 8 bar.
GES_BM+BE_55+56-2U_1212.docx 11
Operating Manual of the BM and BE series
3. Description
3.3 Technical data
Note
The technical data can be taken from the Spectron data sheet for the relevant product. If this is not available, you can view and download it at www.spectron.de
.
The maximum inlet and outlet pressures and the gas type are indicated on the type plate.
3.4 Connection options
Inlet pressure connector: 1/4" NPT female thread, generally equipped with a stainless steel
compression fitting for 6 mm pipes
Outlet pressure connector: 1/4" NPT female thread Relief valve: 1/4" NPT female thread Extension connector: 1/4" NPT female thread
3.5 Changing the supply side
Step Activity 1 The position of the lever indicates which side the gas is drawn from:
Switching lever up – gas is drawn from the gas cylinders on the left-hand side: The outlet pressure of the pressure regulator on the left is set higher than that of the pressure regulator on the right. Switching lever down – gas is drawn from the gas cylinders on the right-hand side: The outlet pressure of the pressure regulator on the right is set higher than that of the pressure regulator on the left. If the handle is positioned horizontally, the two pressure regulators are set to the same outlet pre ssure.
2 The gas cylinder pressure on the preselected side falls below the outlet pressure of the reserve side:
the reserve side takes over the job of supply ing proce ss ga s to th e conne cted co nsumers with out interruption.
With single-stage switching panels, the outlet pressure falls markedly when there is an automatic switch from the preselected operational side to the reserve side. When the switching lever is operated, the reserve side is raised to the normal outlet pressure level and thus becomes the operational side. Two-stage switching panels keep the pressure very largely constant.
4 Move the switching lever to increase the outlet pressure again on the reserve side that has now
become the operational side.
5 Change the gas cylinder on the side that has now become the reserve side.
12 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
3. Description
3.6 How the operating pressure is adjusted
The pressure control panel is set at the factory to a specific nominal operating pressure or average pressure (with the switching lever positioned in the middle). If necessary, this nominal operating pressure can be changed.
Step Activity 1 Position the switching lever (item 1) horizontally and turn it anti-clockwise to unscrew it. 2 Loosen the grub screw (item 2) using an SW3 Allen key. 3 An SW6 Allen key can now be used to adjust the working pressure by turning the hexagon socket
head screw (item 4) below the switching lever.
Turn clockwise to increase the pressure level. Turn anti-clockwise to reduce the pressure level.
4 After adjusting the pressure level, re-tighten the grub screw (item 2), screw the switching lever
back on, and position it to preselect the side from which the gas is to be drawn.
GES_BM+BE_55+56-2U_1212.docx 13
Operating Manual of the BM and BE series
4. Operation
4.1 Labelling
Labelling example
Hydrogen (H
2
) BM55-2U-300-10-M-M-H2 P1: 300 bar
P2: 10 bar
Note
The gas type must be specified on the pressure control panel. If the gas type is not specified on the type plate, it must be done using the attached gas-type adhesive labels before the device is put into operation for the first time.
Warning
Only the gas type for which the pressure control panel was ordered may be specified on it.
4.2 Installing the pressure control panel
Note
You can find instructions on how to install the pressure control panel in the installation manual MA_BM+BE. You can view and download this at www.spectron.de
.
4.3 Putting the pressure control panel into operation
Important
Before putting the equipment into operation for the first time, the entire pressure control panel must be purged via the process gas valve right up to the consumer. It is imperative to adhere to the direction of the gas flow when doing this. You must not purge counter to the usual direction of flow (from the tapping point to the pressure control panel), since this can flush debris resulting from the installation work, for example, back into the pressure regulator.
The connecting thread and connecting surfaces of the gas cylinder valves and the sealing rings of the manual connectors of the pigtails must be checked to ensure they are in perfect condition.
Pigtails with manual connectors are connected to gas cylinder valves without the need for a tool. Pigtails with flat faces for tightening (generally for corrosive or toxic gases) are tightened with a suitable spanner until they are gas-tight.
Always turn shut-off valves as far as the stop when opening or closing them. Step Activity 1 Ensure that:
The gas type is specified on the pressure control panel. All protective caps have been removed. The installation has been carried out properly. The pigtails and other connecting points have been checked for leaks. The waste gas valves are closed (the red marking is visible in the handwheel window). The pressure regulator is released.
14 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
4. Operation
Step Activity 2 Position the switching lever to specify which is the operational side and which is the reserve side. 3 Pressure purge the system:
Slowly open the gas cylinder valves on the left and right. Slowly close the gas cylinder valves on the left and right. Open the waste gas valve on the left and right to relieve the pressure, and then close it again.
Repeat at least three times. If the inlet pressure is low, the process has to be repeated more often.
4 Slowly open the gas cylinder valve(s). 5 Slowly open the process gas valve. 6 Check the entire pressure control panel and all detachable connections for leakage. 7 Gas can now be drawn.
4.4 Changing the cylinder
Important
Once it is put into operation, both sides of the panel must always be connected.
Before replacing a cylinder, always turn the switching lever with the "In operation" display to the
side from which gas is currently being drawn. The arrow indicating the reserve side points to the
side of the pressure control panel on which the gas cylinders are now to be replaced.
It is extremely important to move the switching lever, since otherwise once the empty gas
cylinders have been replaced with full gas cylinders and the process gas valve has been
opened, this side would take over the gas supply function again.
The reserve side would then remain the reserve side, but its gas reservoir would not be
100% full.
Each time you change the cylinder, check that the gasket is in perfect condition and replace it
if necessary.
Note
Each time you change the cylinder, ambient air gets into the con necting part s of the system. To prevent
the gas and the entire system from being contamin ated, the con nection must be purged b efore gas is
drawn from the cylinder again. In the case o f non- toxic, non-cor rosive gase s, this ca n be don e by
means of multiple pressure purges with own gas. In t he case of co rrosive or toxic gases or gases that
are hazardous in some other way, purging must be carried out with foreign gas. The flushin g device
required for this has the designation BE55-SP. It may have to be retrofitted.
GES_BM+BE_55+56-2U_1212.docx 15
Operating Manual of the BM and BE series
4. Operation
The procedure for changing a cylinder is describ ed below, taking the right -hand ga s cylinder by way of example:
Step Activity 1 Acknowledge the change of cylinder.
Position the switching lever with the arrow marking pointing up. "In operation" can be read for the cylinder on the left --> which is now the supply side. "Reserve" can be read for the cylinder on the right --> which is now the reserve side.
2
Close the right-hand gas cylinder valve and process gas valve.
3
Open the waste gas valve on the right. Release the residual pressure in the pigtail. Close the waste gas valve on the right. Loosen the pigtail on the cylinder valve on the right and connect it to the new cylinder.
4 Pressure purge the system:
Slowly open the gas cylinder valve on the right. Close the gas cylinder valve on the right. Open the waste gas valve on the right to relieve the pressure. Close the waste gas valve again.
Repeat at least three times. If the inlet pressure is low, the process has to be repeated more often.
5 Slowly open the gas cylinder valve on the right. 6 Slowly open the process gas valve on the right. 7 Check the gas cylinder connection and all detachable connections for leakage.
4.5 Taking the equipment out of operation
Taking out of operation or interrupting operation for a short period
When interrupting operation for a short period, all you need to do is close the process gas valve. The red marking in the handwheel window indicates immediately that the valve is closed.
Taking out of operation or interrupting operation for a longer period
Step Activity 1 Close all valves.
To do this, turn until you can see the red marking in the handwheel window. 2 Open the waste gas valves. 3 Any gas in the system flows out of the waste gas pipe. 4 Close the waste gas valves. 5 The pressure in the pressure control panel must be released by allowing the gas to flow away via
the consumer. It must be ensured that the indicators of the two pressure gauges are on zero [0] –
visual check.
If it has been used with corrosive or toxic gases, the entire pressure control panel must be purged
with inert gas.
16 GES_BM+BE_55+56-2U_1212.docx
Operating Manual of the BM and BE series
5. Problems
Problem/cause Remedy Gas is released from the relief valve.
Impermissible increase in the outlet pressure.
Close all valves immediately. Have the pressure control panel checked immediately by the manufacturer or an authorised specialist company.
The pressure regulator is making noises. This indicates a defect.
Close all valves immediately. Have the pressure control panel checked immediately by the manufacturer or an authorised specialist company.
The pressure regulator is frozen. This indicates that too much gas is being drawn.
Reduce the amount of gas drawn or – if technically, chemically and physically possible – add a heater to pre-heat the gas.
There is a leak. This indicates a defect in a pressure regulator component.
Close all valves immediately. Have the pressure control panel checked immediately by the manufacturer or an authorised specialist company.
The outlet pressure level is unstable and is not adhering to the usual range of variation. This indicates that too much gas is being drawn.
Reduce the amount of gas drawn. It is also possible that there is dirt in the inlet filter. In this case, the pressure control panel must be checked by the manufacturer or an authorised specialist company.
The inlet pressure or gas cylinder pressure of the side indicated as the reserve side by the position of the lever is falling.
The reserve side is also supplying gas to the down stream pro cess. This could either be because too much gas is being drawn or because the pressure regulator has a defect. Reduce the amount of gas drawn. If this is not possible or if this does not correct the problem, contact the manufacturer or have the pressure control panel checked by the manufacturer or an authorised specialist company.
GES_BM+BE_55+56-2U_1212.docx 17
Operating Manual of the BM and BE series
6. Maintenance, cleaning and repairs
6.1 Regular maintenance work and visual inspections
Regular maintenance work
To ensure the pressure control panel remains in perfect working order and a constantly high level of operational safety and reliability is maintained, the pressure control panel should be checked once a year by a specialist.
Regular visual inspections
Visual inspection of all parts for
Interval
Damage Correct functioning Leaks Integrity/stability Corrosion
Regular inspections at intervals of 12 months and each time the device is put into operation make an important contribution to the cost-effectiveness and preservation of the value of the fittings.
Note
If you find defects during the visual inspection, do not put the pr essure contr ol panel into operatio n. Have the pressure control panel checked immediately by th e manufa cturer or an aut horised spec ialist company.
6.2 Regular cleaning
Warning
Detergents or disinfectants can corrode and ruin gaskets inside the fittings. Do not use detergents or disinfectants.
If the device gets very dirty, this can interfere with operation. If it becomes necessary to clean the pressure control panel, use only a damp, lint-free cloth.
6.3 Repair information
Important
Repairs may only be carried out by specialist personnel in authorised repair workshops. After repairs, the entire pressure control panel must be checked in accordance with the original Spectron inspection instructions.
Safe and reliable operation can only be guaranteed if original spare parts are used.
Note
The manufacturer accepts no liability for damage resulting from unauthorised repairs or modifications carried out by the user or third parties without the express written approval of the manufacturer.
6.4 Returns
If the pressure control panel is returned to the manufacturer for testing, maintenance or repair, and it has been in contact with corrosive and toxic gases, it is imperative that it is purged with inert gas.
Spectron Gas Control Systems GmbH
Fritz-Klatte-Straße 8
D-65933 Frankfurt
Germany Phone: +49 69 38016-0 Fax: +49 69 38016-200
Email: info@spectron.de
Internet: www.spectron.de
Loading...