The SPECIALTY CONCEPTS SYSTEM (SCS) is a versatile, industrial quality charge
controller for the efficient use of photovoltaic energy and the protection of expensive
batteries.
)
The SCS is a series-relay battery charge controller using mercury relays, remote
temperature compensation, adjustable charging set-points, low-voltage load
disconnect, circuit breakers, and digital metering. Lights indicate "CHARGING" and
"LOAD DISCONNECT" conditions and the meter displays battery voltage, charging and
load current, and current from an external shunt.
FEATURES
CHARGE REGULATION
• Available for 12,24,36 or 48 volt systems
• 50 amp charge current: SCS/50
• 90 amp charge current: SCS/90
• Two-step, series charging, 12,24 v
• Single step, series charging, 36,48 v
• Adjustable charging set-points
• Temperature compensation
LOW-VOLTAGE LOAD DISCONNECT
(LVD)
• 30 amp LVD, 12 volt
• 20 amp LVD, 24 volt
• 15 amp LVD, 36 and 48 volt
• Adjustable disconnect set-points
• Manual override switch
MOUNTING
• Indoor wall mount enclosure (standard)
• Outdoor enclosures (optional)
MONITORING
• Digital volt / amp meter
• “CHARGING” light
DESIGN FEATURES
• Mercury Relays
• Array, battery and load circuit breakers
(providing over-current protection and
manual disconnects)
• Maximum array usage
• Reverse polarity protection
• Reverse leakage protection
• Lightning protection
• Input noise suppression
• Remote battery voltage sense
• “LOAD DISCONNECTED” light
Page 2
SPECIFICATIONS
PARAMETERSUNITSNOMINAL VOLTAGES
FULL CHARGE TERMINATION SET-POINTS
DIMENSIONS (SCS/50)
12 v24 v36 v48 v
Charge Current, Continuous(Amps)50505050
Charge Current, Max. (60 seconds)(Amps)65656565
Load Current, Continuous (1)(Amps)30201515
Load Current, Max. (60 seconds) (2)(Amps)39262020
Array Voltage, Max. Voc(Volts)22446688
Operating Voltage @ Battery, Min.(Volts)8.517.025.534.0
Quiescent Current (3)(Milliamps)40404040
Current Consumption, Charging, SCS/50 (4) (Amps).5.3.25.2
Current Consumption, Charging, SCS/90 (4) (Amps)1.5.4.25
Current Consumption, Load Disconnected (5) (Amps)1111
Voltage Drop, Max. (Array to Battery),SCS/50 (Volts @ Max. rating).4.4.4.4
Voltage Drop, Max. (Array to Battery),SCS/90 (Volts @ Max. rating).8.8.8.8
Voltage Drop, Max. (Battery to Load)(Volts @ Max. rating).1.1.1.1
Full Charge Termination (6)(Volts)14.8 + .229.6 + .444.4 + .659.2 + .8
Full Charge Resumption (Volts)12.8 + .225.6 + .4 38.4 + .651.2 + .8
Load Disconnect (7)(Volts)11.5 + . 223.0 + .434.5 + .646.0 + .8
Load Disconnect Adjustment Range (Volts)11.0 to 12.022.0 to 24.033.0 to 36.044.0 to 48.0
Load Reconnect(Volts)13.0 + .326.0 + .639.0 + .952.0 + 1.2
Float Voltage(Volts)14.1 + .228.2 + .4NANA
Float Current, Max.(Amps)31NANA
Low Alarm Set-point (factory set)(Volts)11.8 + .123.6 + .235.4 + .347.2 + .4
High Alarm Set-point (factory set)(Volts)15.5 + .131.0 + .246.5 + .362.0 + .4
Alarm Relay Contact Current, Max.(Amps)3333
Meter Accuracy, Voltage1 %1 %1 %1 %
Meter Accuracy, Current1 %1 %1 %1 %
Temp. Compensation coef.(from 25°C)(Volts/°C)-.03-.06-.09-.12
Operating Temp. Range, Control circuit(°C) -20 to 50-20 to 50-20 to 50-20 to 50
Operating Temp. Range, Metering(°C)0 to 500 to 500 to 500 to 50
Storage Temp. Range(°C)-20 to 70-20 to 70-20 to 70-20 to 70
Notes:
(1) Non-inductive.
(2) Carry only, Non-switching
(3) Both relays unenergized, red LEDs off, typical value.
(4) Charge relay energized, red L.E.D. on, typical value.
(5) LVD relay energized, red L.E.D. on, typical value.
(6) Set-point adjustable. Refer to table.
(7) Decreases by 10 mv for every amp of load current
The SCS is an integral part of a solar electric power system that includes a PV solar
array, a battery and a load. These items should be installed in accordance with the
National Electrical Code (NEC) or other applicable code, and with the instructions
provided by the equipment supplier.
SOLAR ARRAY PANELS: The SCS is compatible with all makes and models of PV
panels, provided the voltage and current specifications of the SCS are not
exceeded. These are the maximum open circuit voltage of the array (Array Voltage,
Max. Voc: see Specifications) and the maximum power current of the array (Charge
Current, continuous: 50 or 90 amps).
HIGHER CHARGING CURRENTS : For arrays exceeding the maximum power
current of the SCS, the array can be divided into smaller parallel sub-arrays. A SCS
can be wired in parallel to each sub-array, provided the sub-arrays do not exceed
the rating of the individual SCS.
BATTERIES: The SCS is factory set for the most common lead-acid batteries. These
are wet cell batteries using pure lead, lead antinomy and/or lead calcium grids. For
sealed, maintenance free batteries, or vented pocket plate nickel-cadmium
batteries, the charging set-points should be adjusted to maximize performance and
battery life. Note: For sealed, maintenance free batteries or nickel cadmium
batteries, consult the battery manufacturer for recommended set-points and refer to
Table 2 for appropriate settings.
LOADS: The load is considered the item or equipment that the PV system is powering.
System loads such as lights, radios, DC/AC inverters, etc. must be rated for the
proper DC input voltage. DC loads not exceeding the rated SCS load current (see
specification section) can be connected to the load terminals of the SCS and they
will automatically be disconnected in the event of a low-voltage condition. Higher
current, or inductive loads such as pumps, motors or inverters should be connected
directly to the battery, using properly rated over-current/disconnect devices (fuses
or circuit breakers).
OTHER CHARGING SOURCES: Do not use the SCS to regulate a power source other
than a photovoltaic array, such as a hydro or wind generator/alternator or an AC
battery charger. This could result in damage to the SCS and/or the generating
equipment. Connect other charging sources with their own regulation devices
directly to the battery, using properly rated over-current protection devices.
The SCS and array can remain connected to a battery being charged by other
sources, (alternator, battery charger, etc.) without damage to the controller or solar
array.
Page 4
INSTALLATION
WARNINGS / CAUTIONS
WARNING: Electricity, even low voltage electricity, can be dangerous. Installation
should be performed by a licensed electrical contractor or other qualified personnel
only. It is recommended that the requirements of the U.S. National Electrical Code
(NEC) or other applicable code should be followed.
WARNING: Follow all safety precautions of the battery manufacturer and the NEC.
Proper ventilation must be provided for vented batteries. Most vented batteries
produce hydrogen gas when charging, which is extremely explosive. DO NOT
expose the battery to open flame, matches, cigarettes or sparks.
WARNING: Install properly DC rated, high interrupt over-current protection between
the SCS and the battery. Refer to the current NEC or other applicable code for
recommendations.
WARNING: On higher voltage units (36, 48 volt), exercise extreme care during
installation. These voltages can be extremely dangerous in that they can create
large arcs, which can burn or cause other injuries.
WARNING: To remove all power from the controller, all three circuit breakers must be
turned off (including the load).
CAUTION: DO NOT subject the controller to voltages greater than the "Array Voltage,
Max. Voc" as stated in the SCS specifications. This is the open circuit voltage (Voc)
of the solar panel, or the sum of the open circuit voltages of all modules connected
in series.
CAUTION: DO NOT exceed the 50 or 90 amp current rating of the SCS. This is the
sum of the max. power currents of all modules in parallel.
Page 5
INSTALLATION INSTRUCTIONS:
1. LOCATION: - A suitable location must be found for mounting the SCS. The unit
features mercury relays that require the unit to be mounted on a vertical surface.
This unit should also be as close as possible to the batteries to avoid errors in
battery voltage reading. The temperature sensor wire is 10 feet long and should
reach the battery bank if possible.
2. PROTECTION REQUIREMENTS: - The unit should not be placed in direct sunlight
or close to any heat generating source to avoid extreme temperature increases. It
must receive adequate protection from rain, dust and insects. The standard SCS is
supplied in an indoor NEMA 1 enclosure, or optional outdoor enclosures are
available.
3. INSPECT UNIT / PREPARE AND MOUNT THE SCS ENCLOSURE: - Remove the
inner panel of the SCS by unscrewing the four acorn nuts in the four corners.
Inspect the circuitry and hardware for connections that may have become loose
during transit. Determine the size and location of holes needed in the enclosure for
conduit hubs or strain relief feed-throughs for the wiring. Proceed with making holes
in the enclosure by punching out the knock-outs in the steel NEMA 1 and 3R
enclosures, or drilling holes in the plastic NEMA 4X enclosure. Return the inner
panel.
4. COMPLETE THE INSTALLATION OF PANEL, BATTERIES AND LOAD: - Follow
the manufacturer's instructions for mounting and wiring the solar panel, batteries
and the load.
5. SELECT WIRE
WIRE TYPE: - It is recommended to follow the NEC requirements for wiring
methods. Use stranded wire rather than solid wire whenever possible, because
stranded wire does not fatigue and cause loose connections over time as easily
as solid wire.
WIRE SIZE: - The SCS/50 terminal block accepts bare wire up to 6 AWG. The
SCS/90 terminal block accepts bare wire up to 1/0 AWG. Wire should be sized
of sufficient gauge to safely handle the rated current of the system and to limit
voltage drop. Consult wire sizing tables and local alternative energy system
suppliers for information on wire type and sizing.
6. REMOVE POWER FROM BATTERY / PANELS: - Disconnect power from the
batteries and panels prior to running the wires to the controller to prevent accidental
damage and/or bodily harm.
7. SET CIRCUIT BREAKERS TO “OFF”: - Make sure all three circuit breakers on the
SCS are “OFF”.
Page 6
INSTALLATION INSTRUCTIONS (continued):
8. RUN SYSTEM WIRING: - After disconnecting the power sources, refer to wiring
diagram (FIGURE 1) and run the system wiring to the location of the SCS. The
wires should reach the location of the SCS with a little extra for strain relief loops.
9. NOTE WIRE POLARITY: - Insure that the polarity of the wires is correctly marked,
using colored wires or tags. Incorrect polarity should not damage the SCS, but
incorrect operation would result.
10. COMPLETE ARRAY AND BATTERY CONNECTIONS: - Connections to the SCS
terminal block should be made with just the bare wire (not crimped spade or ring
lugs unless the lugs are crimped AND soldered).
11. COMPLETE LOAD CONNECTIONS: - Refer to wiring diagram (FIGURE 1). DC
loads not exceeding the rated SCS load current (see specification section “Load
Current, Continuous”) can be connected to the load terminals of the SCS and they
will automatically be disconnected in the event of a low-voltage condition. Higher
current, or inductive loads such as pumps, motors or inverters should be connected
directly to the battery, using properly rated over-current protection devices (fuses or
circuit breakers).
12. BATTERY VOLTAGE SENSE CONNECTIONS: - The factory has installed two
jumpers onto the terminal block. They connect the "VOLTAGE SENSE" (positive
and negative) terminal to their respective "BATTERY" terminals. These jumpers
should remain in place if the SCS is located within 5-10 feet of the batteries and if
large enough wire is used to minimize voltage drops to less than 2%.
If the SCS is at a greater distance from the batteries and/or if the voltage drop in
the battery wires exceeds 2%, then the jumpers should be removed and replaced
with another circuit running directly to the battery terminals. This is a low current,
voltage sensing circuit that can be wired in 16 AWG wire. Proper over-current
protection should be added on the positive side. This connection will allow the SCS
to accurately measure battery voltage.
13. INSTALL FUSING AS NEEDED: - Add circuit protection where needed. A 50
amp fuse (SCS/50) or 90 amp fuse (SCS/90) should be installed on the Battery (+)
run of the SCS. Fusing is also advised for the battery voltage sense connection, if
included. The load is already protected by the built-in circuit breaker of the SCS.
14. ATTACH TEMPERATURE COMPENSATION CABLE: - SEE TEMPERATURE
COMPENSATION section
15. MAKE HIGH / LOW VOLTAGE ALARM CONNECTIONS: - See VOLTAGE
ALARMS section
Page 7
16. AUX CURRENT CONNECTION (using external shunt): - If needed.
The SCS can be modified to allow the user to monitor a current to or from another
source, such as a charger or alternator or for monitoring loads such as a DC source
center or an inverter. This requires an external shunt to be added to the system and
connected to the circuitry behind the plate. Contact a technical representative for
information.
17. MAKE NEEDED ADJUSTMENTS TO SETTINGS: - See Setting/Adjustments
section
18. RECONNECT BATTERY AND ARRAY POWER - With the 3 circuit breakers in the
“OFF” position, reconnect both power sources. Then turn on the ”BATTERY” circuit
breaker first. After, the remaining two circuit breakers can be turned on.
19. OPERATION: - Operation of the charge controller is now fully automatic. If the
battery voltage is below the Full Charge Termination set-point (seeSPECIFICATIONS) and power is available from the array and the power connect
sequence (step #18) was followed, the SCS should start up in the charge mode. If
the battery voltage is above the Load Disconnect voltage, the loads connected to
the LOAD terminals should go on.
20. CHECK FOR VOLTAGE DROP (OPTIONAL): - Once the system is installed and
operational, a check on the battery connection is recommended. A poor battery
connection will result in a voltage loss that will cause the batteries to be undercharged and/or result in excessive heat generated at the location of poor
connection (wire connection or terminal block). A voltage multi-meter is required
and the SCS must be charging with maximum expected charge current.
First, note the voltage at the battery terminals. Select the positive and negative
terminals that are used for the SCS connection. Then note the voltage at the SCS
terminals labeled “BATTERY (+)” and “BATTERY (-)”. Ideally, the difference in
voltage should be no more than ¼ volt. If the voltage drop is more, suspect crimp
connections that have not been soldered or loose terminals. If no location of voltage
drop is found, consider using larger wires or additional wires for your run and/or run
a separate wire for the Battery Sense connection. See “BATTERY VOLTAGE
SENSE CONNECTION” (see #12 above).
Page 8
SCS
BATTERY
++
++
+
+
B
SOLAR
ARRAY #1
++
LOW HIGH
SOLAR
FIGURE 1
SCS Wiring Diagram
TO
ALARMS
Temp.
Comp.
ARRAY #2
A
Jumpers: These
jumpers (2) should
remain as shown
unless a Battery
Voltage Sense
Connection is
needed.
See INSTALLATION
INSTRUCTIONS:
BATTERY
VOLTAGE SENSE
CONNECTIONS
LOAD
Note: A load with low-voltage disconnect
(LVD) should be wired to the SCS. A
load without LVD may be wired to the
SCS or directly to the battery.
See INSTALLATION INSTRUCTIONS:
COMPLETE LOAD CONNECTIONS
DC LOAD CENTER
(OR)
INVERTER / CHARGER
(OR)
GENERATOR / ALTERNATOR
FUSE RATINGS:
A = Rated for 50 or 90
amps
B = Rated for load /
inverter / charger
Page 9
TEMPERATURE COMPENSATION
DESCRIPTION: - The SCS has a small sensor on a ten foot cable that is wired into
the controller to adjust the charging thresholds according to battery temperature.
The rate of compensation is -5mv/°C per battery cell in series from 25° C.
WHEN NEEDED: - Temperature compensation is recommended for stand alone
systems with sealed batteries, or for systems that have no regular charging
source other than PV AND where prolonged temperature extremes will be
experienced during periods of charging. Temperature extremes would be when
the battery will be exposed to average temperatures below 50°F (10°C) or above
90°F (32°C).
CAUTION: SENSOR CABLE: If the sensor is damaged or the cable is cut, the
controller will no longer function.
INSTALLATION INSTRUCTIONS
Provision must be made to attach the sensor unit to the battery. This must be done
properly to insure that accurate temperature readings are made. It is important that
ambient temperature not influence the sensor. To minimize this, attach the sensor to
the battery as follows:
1. RUN SENSOR TO BATTERIES: Run the sensor to the batteries, taking care to
prevent damage to the actual sensor itself. When pulling the sensor through
conduit, do not pull on the plastic-coated sensor, but instead on the gray cable
just behind the sensor. Do not force the sensor. The sensor itself is made of
glass, but it is encased in an aluminum tube, then coated with plastic. If the tube
should pull off of the glass sensor, and if the sensor is not damaged, the tube
can be slipped back over the sensor.
2. ATTACH SENSOR: Use the adhesive sided foam pad (included) to cover the
sensor (the plastic coated unit at the end of the cable) and attach it to the side
of the battery approximately half-way up the side of the battery. Choose a
battery that is shielded from drafts or sunlight by other batteries or by the
battery shelter. DO NOT immerse the sensor directly in the battery's electrolyte,
it will be severely damaged. Temperature compensation of charging voltage is
now automatic.
DAMAGED SENSOR: If the sensor is damaged or lost, the controller will no longer
function. By adding a 4.7 K Ω resistor, the temperature sensor feature can be
removed from the unit and the unit will operate without temperature compensation.
Table 1 : Voltage change in charging set-points by temperature
The controller is factory set at position B. To change the set-point, locate the
adjustment switch on the front panel. Using a slotted screwdriver, turn the switch
until the slot is pointing at the desired position.
If problems develop, refer to the "TROUBLE SHOOTING" section of this book.
LOW-VOLTAGE LOAD DISCONNECT SETTINGS:
NO LVD: - For an override of the load disconnect function, push the switch up.
No load disconnect will occur with the switch in the "NO LVD" position.
AUTO LVD: - When the “Load Disconnect” switch is in the "AUTO" position,
the load control circuit will operate automatically. Refer to the “OPERATION:
LOW-VOLTAGE DISCONNECT” section for a description of this operation. If
a load disconnect occurs, the loads will be automatically reconnected when
the batteries charge up to the Load Reconnect voltage, or they can be
reconnected manually with the “Load Disconnect” switch.
MANUAL RESET: - For a temporary reset, push the switch down. The battery
voltage must remain above the Load Disconnect voltage for the load to stay
connected after reset.
ADJUSTING LVD SET-POINTS (“LOAD DISCONNECT ADJUST”): The Load
Disconnect and Reconnect set-points are factory set as listed in the specifications
section, and are adjustable. To alter the voltage at which the load disconnect and
reconnect occur, turn the adjustment pot on the front of the unit labeled “LOAD
DISCONNECT ADJUST” clockwise to decrease and counter-clockwise to increase
(for the range of adjustment, refer to the specifications section: “Load Disconnect
Adjustment Range”). Both set-points will change, with the span value fixed.
NOTE : When adjusting this controller, it is important to use the proper size
screwdriver. Do not force the adjustment beyond the end stops, it will damage the
controller.
VOLTAGE ALARM CALIBRATION: Refer to VOLTAGE ALARMS section below
Page 11
CIRCUIT BREAKERS
LOAD CIRCUIT BREAKER : - A 15 amp load circuit breaker is included with the SCS. This
provides over-current and short-circuit protection for the load and can be used as an on/off
switch for the load.
ARRAY CIRCUIT BREAKER : - A 50 amp array circuit breaker is included with the SCS. This
provides over-current and short-circuit protection for the SCS from the array and can be
used as an on/off switch for the array in order to stop additional charging.
BATTERY CIRCUIT BREAKER : - A 50 amp battery circuit breaker is included with the SCS.
This provides over-current and short-circuit protection for the SCS from the battery. This
breaker can be used in conjunction with the ARRAY and LOAD breakers to remove the
power sources in the system. To remove all power to the SCS, all three circuit breakersmust be turned off. To provide power to the load only, turn ARRAY and BATTERY
breakers off (LOAD breaker on). The ARRAY breaker should be switched off whenever the
BATTERY breaker is off to stop the internal relay from oscillating. When turning the
breakers back on, be sure to turn on the Battery switch first and then the Array and Load
switches. This will assure the loads will come on immediately.
VOLTAGE ALARMS
ALARM LIGHTS The "HIGH ALARM" and "LOW ALARM" lights will indicate any abnormal
battery voltages. The voltage set-points for these alarms can be adjusted by using the two
access holes labeled "Alarm Adjust”". The alarm relays operate in conjunction with the
alarm lights.
ALARM RELAYS High and low-voltage alarm relays give separate dry contact relay closures
for high and low voltage conditions. The low alarm is a normally closed contact, being
energized at normal operating voltages and closing on low voltage to provide a signal in
the event of a complete battery failure. The high alarm is a normally open contact. Each
relay is rated at 10 amps, and consumes 30 milliamps when energized. Access to the
contacts is via a terminal block on the front plate.
ALARM CONTACTS / INSTALLATION Wire to the terminal strip below the display. Small
gauge wire can be used.
MODIFYING THE ALARM VOLTAGES:
a. Refer to the 3 sets of pins in the ALARM CALIBRATION window on the front plate.
Put the SCS into Program Mode by installing the Programming Jumper across
PROG MODE pins (center two pins).
b. Set the MONITOR FUNCTION SELECT knob to “AUX CURRENT” (position 3).
Note: If the AUX CURRENT position is currently being used to monitor an auxiliary
current using an external shunt, it has to be temporarily disconnected to free up the
display for the alarm calibration. Access the rear of the front plate and disconnect
the two wires from the external shunt where they are connected to the display
circuit board. After the alarm calibration, this connection can be replaced.
c. For Low-Voltage Alarm: Place a Programming Jumper across the LOW ALARM pins
d. With a small screwdriver, turn the LOW ALARM Adjust dial and set the new voltage
set-point as indicated on the display.
e. For High-Voltage Alarm: Repeat the above two steps using the HIGH ALARM pins
and the HIGH ALARM Adjust dial.
f. When finished, place the Programming Jumpers back into their storage positions
(attached to only one pin). Reconnect AUX CURRENT wires, if needed.
Page 12
OPERATION
CHARGE REGULATION (12 and 24 volt units): The two-step control circuit regulates the
charging of storage batteries by monitoring battery and solar panel voltage. STEP 1:CONSTANT CURRENT (FULL) CHARGE MODE: At sunrise, the charging relay energizes
and closes, connecting the solar panel directly to the battery and lighting the "CHARGE
MODE" light. The battery will accept as much current as the solar panel will provide, and
battery voltage will rise. STEP 2: CONSTANT VOLTAGE (FLOAT) CHARGE MODE:
When the battery reaches the full charge termination voltage, the charging relay will open
and the "CHARGE MODE" light will go out. At this point the float controller takes over to
keep the battery below the float voltage and supply limited current (maximum float current).
As the battery approaches the float voltage, the current will taper off, eventually falling to
the battery's maintenance current.
CHARGE REGULATION (36 and 48 volt units): The operation of a 36 and 48 volts unit is
identical with the exception that no float circuit is included.
MAXIMUM SOLAR PANEL USAGE : If a load is applied when the controller is in the float
mode, the controller will supply up to its maximum float current to maintain the battery
charge. If the load is less than the maximum float current the batteries will still be receiving
a net charge from the float controller. If the load current is more, the battery will supply
what the float controller cannot and the battery voltage will fall. When it falls below the full
charge resumption voltage, the charging relay will re-close, re-initiating the full charge
mode. This insures that if a large load is applied during the day, maximum use will be made
of the power available from the solar panel.
LOW-VOLTAGE DISCONNECT : The low-voltage disconnect (LVD) of the SCS prevents
damage from deep discharge of the batteries by automatically disconnecting the loads.
The disconnect threshold is load current compensated by a factor of 10 mv/amp, and a
minimum time of 3 seconds is applied to prevent false disconnect. When a disconnect
occurs, the load relay is energized and opens, and a red "LOAD DISCONNECTED" light,
visible on the front panel, will light to indicate that the loads have been disconnected.
Normal battery charging will continue. When the battery voltage rises to the reconnect
threshold, the loads will automatically be reconnected to the battery and the red light will go
off. The LVD function has a reset/disable switch and user adjustable set-points.
Note: The amount of time required to recharge the battery sufficiently to reconnect the
loads depends upon the battery size, solar panel current and weather conditions. In some
cases, it can take several days or longer. The loads can be manually reset prior to the
reconnect voltage by pressing the "MANUAL RESET" switch.
REVERSE CURRENT PROTECTION : The SCS uses a timing circuit to disconnect the solar
panel from the battery at night, preventing reverse leakage current loses through the solar
panel. About 12 hours after sunrise the charging relay will open. If the battery is below the
reconnect threshold and voltage is still available from the solar panel, the relay will re-close
and continue charging. It will open again about every 2 hours thereafter to determine if
power is still available for charging. The relay will stay open after the 12 hour period if the
battery is above the reconnect threshold or if there is no power available from the solar
panel. This results in the relay being open every night. Note: The relay may be closed
("CHARGING" light on) for a few hours in the evening after the sun has gone down.
Page 13
MONITORING
"CHARGING" LIGHT: The "CHARGING" light will be on when the controller is in the full charge
mode. In this mode, the charging relay is closed, connecting the array directly to the
battery. This light should go on first thing in the morning, and will go off if the battery
reaches the Full Charge Termination voltage set-point. If the light is off after morning, the
batteries have reached the full charge voltage some time that day. The light may go on
again if the battery drops below the reconnect voltage and the controller goes into the full
charge mode again. It is not uncommon for the light to remain on, for several hours after
dark. Refer to the operation section for details on controller operation.
"LOAD DISCONNECTED" LIGHT: When the "LOAD DISCONNECTED" light is on, the low-
voltage disconnect (LVD) circuit is activated and any DC loads connected to the "Load"
terminals will be disconnected. This occurs at the LVD voltage set-point. The light will go
out when the voltage rises above the reconnect voltage and the load is reconnected
automatically, or if the reset switch is pushed to “MANUAL RESET" or “NO LVD". Refer to
the operation section for details on LVD operation.
DIGITAL DISPLAY: The Digital display on the front of the SCS provides metering of four
parameters, selected by a slide switch to the right of the display, labeled: 1, 2, 3, 4.
“SWITCH POSITIONS”
POSITION 1 - "BATTERY VOLTAGE": This displays the system battery voltage. The
battery voltage is a general indication of battery condition, or capacity. Battery
voltage will change when the battery is being charged and discharged, with the
amount of change depending on the amount of charge current or discharge current.
A fully charged battery that is not being charged or discharged will be at about 12.6-
12.8 volts (12 volt battery). The normal range of a 12 volt battery is about 11 to 15
volts. A voltage below 11 volts would indicate a dead battery, and over 15 volts
indicates an overcharging battery. It is best to keep the batteries above 11.5 and
below 14.8 for maximum battery life and performance.
POSITION 2 - "ARRAY CURRENT": This displays the amount of current the solar
panel is generating. Any current generated by the solar panels will be used first to
operate any loads that are on, and any left over will go into the battery for charging.
The array current reading can be used to optimize the array tilt angle by moving the
array (if possible) and noting when current is maximum. Consult the panel supplier
or literature for rated output to see what the output current should be for the total
number of panels in the system under ideal conditions. Ideal conditions would be a
bright sunny day, with the panel aimed right at the sun and no shadows or dirt on
the panel.
POSITION 3 - "AUX CURRENT": This position is used to calibrate the alarm voltages.
See VOLTAGE ALARMS section.
This position can also be used to display the reading from an external shunt. This
reading could be used for a charger or alternator or for monitoring loads such as a
DC source center or an inverter. Refer to INSTALLATION INSTRUCTIONS: ”AUX
CURRENT CONNECTION” (step #16) (above).
POSITION 4 - "LOAD CURRENT": This position displays the current being consumed
by any DC load connected to the load terminals of the SCS. This position will not
monitor current to loads connected directly to the battery, such as an inverter.
Page 14
OPTIONS
OPTION H - GENERATOR START : The generator start option is for systems designed with
a stand-by generator that has an autostart circuit. A voltage-free contact closure is
provided to signal the generator to start and stop charging, based on battery voltage.
Access to the relay contacts is via a terminal block on the face plate. The start and stop
set-points are factory set at 11.5 volts start and 13.5 volts stop (for a 12 volt system) and
are adjustable. Adjustments are made via the pots labeled "SPAN ADJ." and “START
ADJ.” The range of adjustment for the start voltage is from 11.0 to 12.0 volts, and the
range for the stop is from 12.8 to 14.0 volts for a 12 volt system.
RECALIBRATION PROCEDURE FOR GENERATOR START SET-POINTS:
Equipment required : Power supply, variable, with sufficient voltage range for system
voltage (i.e. 0-15 volts for 12 volt system).
1. With battery sense jumpers in place, connect power supply positive to "BATTERY +"
2. Connect power supply negative to "BATTERY -"
3. Turn selector switch on the SCS face plate to "BATTERY VOLTAGE"
4. Vary power supply voltage in the area where the generator start is set, observing when
the red "GEN.START" light goes on and off.
5. Subtract value of desired start voltage from desired stop voltage.This becomes the
"SPAN" value.
6. Turning the "SPAN ADJ." pot clockwise increases the span. Turning it counter-clockwise
decreases the span.
7. Vary power supply voltage once again to determine new span value.
8. Repeat steps 6 and 7 until desired span is achieved. Start voltage set-point will be
incorrect.
9. Turning the "START ADJ." pot clockwise decreases the set-point, and turning it counterclockwise increases it.
10. Vary the power supply voltage to determine the new start value.
11. Repeat steps 9 and 10 until the desired start set-point is set.
12. Repeat step 4 to verify accuracy of new set-points.
OPTION W - POSITIVE GROUND LOAD : The Low-voltage Load Disconnect is in the
negative leg of the load circuit. Array connections should be floating (not grounded).
OPTION 3R - OUTDOOR ENCLOSURE (NEMA 3R) : This enclosure is intended for use
indoors or outdoors for rain proof applications.
OPTION 4X - OUTDOOR ENCLOSURE (NEMA 4X with Clear Door) : This enclosure is
intended for use indoors or outdoors for watertight, dust tight and corrosion-resistant
applications and provides a clear door for viewing metering and status lights without
opening the enclosure.
Page 15
TROUBLE SHOOTING: GENERAL NOTES
IF THE CONTROLLER IS NEWLY INSTALLED, CHECK THESE FIRST:
1) Re-check system wiring to insure proper installation and polarity .
2) Check all system fuses and circuit breakers. A 1 amp AGC fuse is located behind the
front plate on the display circuit board. Before replacing a blown fuse, locate and
correct the cause.
3) Check to be sure that there is a connection (voltage input) to the " VOLTAGE
SENSE" terminals from the battery. This would be either a factory installed jumper
strip on the controller terminal block from the "VOLTAGE SENSE" terminals to the
"BATTERY" terminals, or a connection from the sense terminals directly to the
battery itself.
4) Check to see that modules and batteries are in the correct series-parallel
configuration for proper system voltage and current.
5) Review controller specifications relating to array output, load ratings and system
sizing to insure that ratings are not exceeded.
6) Review the controller specifications relating to operation and set-points, particularly
the charge termination and reconnect voltage set-points. If possible, check this with
the operation of the controller, monitoring the battery voltage.
7) Some types of loads (fluorescent lights, inverters) can generate electronic "noise"
that sometimes interferes with the operation of the controller. Check to see if
strange behavior can be traced to operation of a certain appliance.
8) Inspect the temperature sensor and sensor wire. Check for a broker sensor or a cut
or frayed sensor wire. See TEMPERATURE COMPENSATION section.
9) If possible, perform the "FIELD TEST PROCEDURE" and /or "BENCH TEST
PROCEDURE" that follows.
IF THE CONTROLLER HAS BEEN INSTALLED AND WORKING
PROPERLY FOR AWHILE, CHECK THESE FIRST:
10) Check all system fuses and circuit breakers. A 1 amp AGC fuse is located behind
the front plate on the display circuit board. Before replacing a blown fuse, locate
and correct the cause.
11) Confirm that all connections are clean and tight. Particularly check crimp
connections that have been crimped but not soldered as these connections tend to
deteriorate over time.
12) Some types of loads (fluorescent lights, inverters) can generate electronic "noise"
that sometimes interferes with the operation of the controller. Check to see if
strange behavior can be traced to operation of a certain appliance.
13) If you have an accurate digital volt meter, check for voltage drop between the
controller and the battery by measuring voltage at the battery and at the controller
when maximum charging is occurring. Drops often occur through old fuses, fuse
holders or circuit breaker boxes and at loose or corroded connections.
14) High voltage from nearby lightning strikes or unregulated charging sources can
damage the controller. The built-in lightning protection provides substantial
protection, but it is sometimes overwhelmed.
15) Inspect the temperature sensor and sensor wire. Check for a broker sensor or a cut
or frayed sensor wire. See TEMPERATURE COMPENSATION section.
16) Check output from the array, and that it is not partially shaded or dirty.
17) If possible, perform the "FIELD TEST PROCEDURE" and /or "BENCH TEST
PROCEDURE" that follows.
Page 16
TROUBLE SHOOTING: SCS
PROBLEM DESCRIPTIONS
BATTERY UNDER CHARGED
CONTROLLER NOT CHARGING AT ALL, ALWAYS IN THE FLOAT MODE ("CHARGING"
LIGHT OFF)
Check to see that the circuit breakers are all on, and that the controller is receiving voltage (at
least about nominal system voltage) from the battery and the solar panels. If it is,
momentarily disconnect and reconnect the panels, using the array circuit breaker. The
controller should reset into the full charge mode ("CHARGING" light on). If it does not
reset, the controller may be defective.
See number 8 above. A damaged sensor or wire will cause the controller to malfunction.
CONTROLLER STOPS CHARGING TOO SOON, AT TOO LOW A VOLTAGE
See number 6 above: Try to monitor the voltage at the "VOLTAGE SENSE" terminals when the
controller actually switches. Most often, when a controller is operational, it is switching the
correct voltage. If the battery is not reaching the charge termination set-point voltage
before the controller switches, it is usually an error in the voltage that the controller is
sensing, not a controller failure.
See numbers 11 and 13 above: A poor connection between the battery and the controller
results in a voltage drop during charging periods (larger drop for higher current) that
disappears when charging stops. This voltage drop results in a higher voltage being
sensed at the controller than is actually at the battery.
CONTROLLER CLICKS AND CHATTERS, PARTICULARLY IN THE MORNING AND EVENING
See numbers 11 and 13 above: Check the connection to the battery. A poor connection at the
battery will cause the relay to chatter under low light conditions and the controller to remain
in float mode during full sun.
CONTROLLER NOT CHARGING, "CHARGING" LIGHT DIM, BATTERY VOLTAGE VERY LOW
See LVD trouble shooting section. If the LVD circuit is not operating, the battery can be
discharged to a very low voltage. If the battery is extremely low, there might not be enough
voltage to operate the controller. The charging relay requires a minimum operating voltage
to engage and allow charging. If the battery is down to 9 volts or lower on a 12 volt system,
(17 on a 24 volt) connect the battery directly to the array (or use an auxiliary charging
source) until sufficient charging has occurred to increase the voltage. Note: Battery life
depends on the number, time and the depth of the discharges. Severe battery damage can
result when batteries are deeply discharged and not recharged immediately.
"CHARGING" LIGHT ON AT NIGHT
Review the "REVERSE CURRENT PROTECTION" and "CONNECTION SEQUENCE" sections
of this manual. The reverse leakage timer may cause the "Charging" light to be on for a few
hours each evening. Also, the light will stay on during the night of the first day of
installation or if the array has been manually disconnected that day. If the light stays on all
night every night, the timer may be defective.
Page 17
BATTERY OVERCHARGING
CONTROLLER ALWAYS IN FULL CHARGE ("CHARGING" LIGHT ON)
See number 6 above: The battery may not be reaching the charge termination set-
point.
See number 3 above: No voltage at the battery sense terminals tells the controller that
the battery voltage is low and needs to be charged more. Install a connection from
battery to "BATTERY SENSE" terminals to resolve.
See number 8 above: A damaged temperature sensor or wire will cause the controller
to malfunction and requires immediate replacement.
CONTROLLER NOT IN CHARGE MODE ("CHARGING" LIGHT OFF)
Disconnect array, then reconnect. Listen for relay to click and for “CHARGING" light to
come back on. If the light goes on but you hear no click, the relay or controller may
be defective.
Check for other charging sources that are not properly regulated, causing the battery to
overcharge.
LOAD DISCONNECT CIRCUIT (LVD) NOT OPERATING CORRECTLY
LOADS ALWAYS DISCONNECTED, LVD LIGHT ON, EVEN WHEN BATTERY
VOLTAGE IS HIGH
See number 6 above: No voltage at the battery sense terminals tells the controller that
the battery voltage is low and loads need to be disconnected. Install a connection
from the battery to "VOLTAGE SENSE" terminals to resolve.
LOADS DISCONNECTED TOO SOON OR NOT RECONNECTING
See number 4 above: The battery may not be reaching the reconnect voltage set-point.
See numbers 11 and 13 above: A poor connection between the controller and the
battery results in a voltage drop when heavy loads are turned on that disappears
when the loads are turned off. The heavier the loads are, the larger the voltage drop
will be. This voltage drop results in the controller seeing a lower voltage than what
the battery voltage actually is.
LOADS NOT DISCONNECTING ON LOW VOLTAGE, LVD LIGHT OFF
Check the position of the "LVD" switch. If the switch is in the "NO LVD" position the
load will not be disconnected.
LOADS ALWAYS DISCONNECTED, LVD LIGHT OFF, BATTERY VOLTAGE IS
HIGH
Check the load circuit breaker on the front of the controller. If the breaker is tripped, the
load will not operate.
Page 18
MONITOR DISPLAY NOT READING CORRECTLY
DISPLAY BLANK, ALARMS DO NOT FUNCTION
Check the fuse on the backside of the front plate on the display circuit board. If it is
blown, replace with a new 1 amp type agc fuse. If it continues to blow, this indicates
that the SCS probably needs servicing.
Inspect the wire connections to and from the display circuit board on the back of the
unit and confirm all connections are sound.
ALARMS DO NOT FUNCTION PROPERLY
Check alarm calibration. See Voltage Alarms section.
INCORRECT READINGS FOR AUX CURRENT
Check to be sure that the external shunt is wired in the negative leg of the system
component.
Using a digital multimeter, measure the millivolt reading at the shunt and then at the
terminal block of the display circuit board to which it is connected. Compare this
value with the expected current reading and the displayed value.
RANDOM READINGS
Check the wire connections to the terminals on the display circuit board and make sure
they are sound.
Electronic "noise" from inverters or other loads can sometimes influences the readings.
Some types of loads (fluorescent lights, inverters) can generate electronic "noise"
that sometimes interferes with the monitor reading, particularly when sense wires
from remote shunts run close to wiring to the load. Check to see if strange behavior
can be traced to the operation of a certain appliance.
CURRENT READINGS LESS THAN EXPECTED
Check to see that array modules and batteries are in the correct series-parallel
configuration for proper system voltage and current.
Check for an alternative path to ground around the shunt. .
Check output from the solar panel(s), and that they are not partially shaded or dirty.
INCORRECT VOLTAGE READINGS
With an accurate digital volt meter, check voltage readings at the battery and at the
monitor, to see if they agree. Voltage drops occur between the SCS and the battery
occasionally during maximum charging. Drops often occur through old fuses, fuse
holders or circuit breaker boxes and at loose or corroded connections.
Page 19
TROUBLE SHOOTING: BATTERIES
Refer to this section to help diagnose potential problems based on battery
observations.
CASEBATTERYSEE NOTE(S)
1 →
2 →
Battery Note 1 - BATTERY OVER-CHARGING: If there is evidence that the batteries
have been over-charging, consider these points:
• Normal Battery Condition: The batteries may not be over-charging but only be
• Controller Problem: The SCS could be defective. Refer to the field test
• Battery Type: The batteries may be a type that require a lower full-charge voltage
Seems to be over-chargingSee Battery Note 1
Does not fully charge batteriesSee Battery Note 2
experiencing normal water loss and normal levels of gassing. Check the
“BATTERY VOLTAGE” reading. Normal battery voltage for a wet cell battery can
be up to 14.8 volts (12v system).
procedure.
than what the SCS is set to. Refer to SETTINGS / ADJUSTMENTS Section.
•Other Charging Sources: Another charging source could be the cause. If the
SCS “CHARGING” light is off and the “ARRAY CURRENT” reading is 0, then the
solar system is off and overcharging can be from another source. Some 110 volt
battery chargers are not well regulated and could over-charge batteries if left
unattended.
•• A Hot Battery - Hot temperatures can affect the battery charging, a hot location
for batteries will tend to over-charge the batteries.
Battery Note 2 - BATTERY UNDER-CHARGED: If the battery voltage is low and they
are not able to be charged sufficiently, consider one of the following problems:
•• Solar Panels Problem - Panel may be dirty, not aligned or other problem.
•• Bad Connection to the Solar Panel.
•• SCS Controller Problem. - Refer to the field test procedure
•• A Bad Battery - The batteries may be going bad. TEST: If the battery is going
bad, a little charging or discharging will cause a large change in the battery
voltage.
•• A Cold Battery - Cold temperatures can affect the battery charging. If the battery
is cold much of the time, the battery’s long-term performance and life may suffer.
•• System not sized correctly - For too much usage, try charging the battery with
another charging source (engine alternator, generator or AC battery charger). If
the batteries are OK and hold the charge, an increase in the number batteries
and panels may be needed to support the usage.
Page 20
TROUBLE SHOOTING: SOLAR PANELS
Refer to this section to help diagnose potential problems based on panel performance.
CASEPANELSSEE NOTE(S)
1 →
Panel Note 1 - The panels should generate a charge close to their rated load current
as presented in their specifications. To reach this level assumes that all conditions
are ideal. If the panel performance as measured at the panel inputs on the SCS
controller is much lower, consider the following potential problems.
•• Solar Panels Problem - Panels may be dirty, not aligned or other problem.TEST:
•• Bad Connection to the Solar Panel. TEST: Measure the voltage up at the solar
•• Solar Panels may be defective - TEST: Disconnect the array by switching the
Less charge than expectedSee Panel note 1
Monitor the "ARRAY CURRENT" reading before and after cleaning of the solar
panels and orientation. Locate panel where no shadows will cross it.
panel, and then down at the battery itself during a sunny period of maximum
charging. These voltage readings should not be more than 1 to 1.5 volts
different. More than that would indicate a bad connection or other voltage drop
in the system. Suspect crimp connections that have not been soldered.
array circuit breaker off, and measure the solar array voltage between the
array(+) and the array(-). In sunny conditions, this should be 18-24 volts (in a 12
volt system). A lower value could indicate problems with the solar panel.
Page 21
FIELD TEST PROCEDURE: SCS
Test equipment required: digital multimeter, jumper wires
Conditions: Sunny or bright overcast if possible
Precautions: This procedure assumes that the system panels are installed and operational, or
at least capable of producing at least 15 volts for a 12 volt system (proportionately higher for
higher nominal system voltages). When connecting and disconnecting the batteries and array
as instructed in this procedure, be sure that the circuit breakers are in the “OFF” or down
position, otherwise arcing will occur. On bright days, it may be advisable to partially cover the
array to reduce current produced.
WARNING: Most batteries produce hydrogen gas when charging, which is extremely
explosive. Avoid making sparks in the vicinity of batteries, and provide adequate battery
ventilation.
1) Inspect temperature compensation sensor and cable for damage. If damaged, the
controller will no longer operate. See TEMPERATURE COMPENSATION section.
2) Remove the VOLTAGE SENSE (+) jumper (or disconnect VOLTAGE SENSE (+) wire if
remote sensing is used).
3) Switch Battery, Array and Load circuit breakers off. Disconnect the BATTERY (+) wire, the
LOAD (+) wire and the SOLAR ARRAY (+) wires from the controller. Secure each wire
away from any possible contact with other wires, metal chassis, enclosures etc. Switch
Battery and Array circuit breakers back on.
4) Measure the resistance between the SOLAR ARRAY (+) and BATTERY (+) terminals on
the controller. It should read open (more than 10M Ω).
5) Switch Array circuit breaker off. Reconnect the solar array to the controller. Switch Array
circuit breaker on.
6) Measure the voltage between the SOLAR ARRAY (+) and SOLAR ARRAY (-) terminals to
ensure it is at least 15 volts (30 for 24 volt units, 45 for 36 volt units, 60 for 48 volt units)
7) If the controller is in charge mode, go to step 8. If it is not, briefly connect a jumper wire
between the SOLAR ARRAY (+) and BATTERY (+) terminals on the controller. When the
controller switches to charge mode, remove the jumper.
8) The controller should now be in charge mode. Measure the voltage between the BATTERY
(+) and BATTERY (-) terminals on the controller. It should be about the same as the panel
voltage from step 6.
9) Install a jumper between SOLAR ARRAY (+) and VOLTAGE SENSE (+). The controller
should switch out of charge mode. Remove the jumper.
10) Switch the Battery and Load circuit breakers on. Measure the resistance between the
LOAD (+) and BATTERY (+) terminals on the controller. It should read closed. Switch
Battery and Load circuit breakers off.
11) Connect BATTERY (+) wire. The LOAD DISCONNECTED light should go on, and battery
voltage should be measured at the load terminals. Switch the Battery and Load circuit
breakers off.
12)If the controller fails any of these tests, it is defective. If all tests are passed the problem is
most likely elsewhere in the system.
5 / 1996
Page 22
BENCH TEST PROCEDURE: SCS
This procedure provides a basic bench test to check the operation and calibration for the SCS.
This procedure is designed specifically for experienced electronic technicians.
Equipment required: Digital multimeter: 0-80 volt 500 ma power supply
The SCS printed circuit board is coated with a water resistant coating. Use a sharp pointed
probe and enough pressure to pierce the coating when making measurements.
1) Inspect temperature compensation sensor and cable for damage. If damaged, the
controller will no longer operate. See TEMPERATURE COMPENSATION section.
2) Make sure there is a jumper between VOLTAGE SENSE (+) and BATTERY (+) and one
between VOLTAGE SENSE (-) and BATTERY (-).
3) Measure the resistance between the BATTERY (+) and SOLAR ARRAY (+) terminals. It
should be open.
4) Check the diodes connected to pins 6 and 7 of the MC1723 IC.
5) Set the power supply to the nominal system voltage (12, 24, 36 or 48 volt), current limit to
500 ma.
6) Connect the power supply (-) to the controller BATTERY (-) terminal. Connect the power
supply (+) to the controller BATTERY (+) terminal and to the controller SOLAR ARRAY (+)
terminal.
7) Measure the voltage at pin 11 of the MC1723 IC. It should be about the power supply
voltage. If it is not, suspect the unit defective and return for repair.
8) Measure the voltage at pin 6 of the MC1723 IC. It should be 7.7 +/- 0.2 volts. If it is not,
unsolder and remove one end of the diode on pin 6 and re-measure. If the voltage is now
correct, the controller should be sent in for repair. If the voltage is still wrong, the MC1723
is bad.
9) If the controller is in charge mode, go to step 9. If it is not, switch on and then off the
ARRAY circuit breaker. The controller should go into charge mode.
10)Measure the voltage across the relay coil (smaller wires). It should be between 8.0 and
13.0 volts. If it is not, suspect the 100 ohm power resistor, Xstr TIP 100(or 102).
11)Verify the set-points by changing the power supply voltage up and down and observing the
activation.
12)Change the CHARGE SET-POINT SELECT switch and power supply to verify other setpoints. Repeat steps 10-11. Refer to the specifications for set-point values.
Page 23
LIMITED FIVE YEAR WARRANTY
SPECIALTY CONCEPTS, INC.
1. Specialty Concepts, Inc. warrants all its products for a period of five (5) years from the date of shipment from its factory.
This warranty is valid against defects in materials and workmanship for the five (5) year warranty period. It is not valid
against defects resulting from, but not limited to:
A. Misuse and/or abuse, neglect or accident.
B. Exceeding the unit's design limits.
C. Improper installation, including, but not limited to, improper environmental protection and improper hook-up.
D. Acts of God, including lightning, floods, earthquakes, fire and high winds.
E. Damage in handling, including damage encountered during shipment.
2. This warranty shall be considered void if the warranted product is in anyway opened or altered. The warranty will be void
if any eyelet, rivets, or other fasteners used to seal the unit are removed or altered, or if the unit's serial number is in any
way removed, altered, replaced, defaced or rendered illegible.
3. The five (5) year term of this warranty does not apply to equipment where another manufacturers' warranty is available.
An example of such equipment may be, but is not limited to, an electronic enclosure. The time limit for this warranty may
be for less than the Specialty Concepts limited warranty. Specialty Concepts will assist the claimant in attempts to seek
warranty claims for such equipment, where appropriate.
4. Specialty Concepts cannot assume responsibility for any damages to any system components used in conjunction with
Specialty Concepts products nor for claims for personal injury or property damage resulting from the use of Specialty
Concepts' products or the improper operation thereof or consequential damages arising from the products or use of the
products.
5. Specialty Concepts cannot guaranty compatibility of its products with other components used in conjunction with
Specialty Concepts products, including, but not limited to, solar modules, batteries, and system interconnects, and
such loads as inverters, transmitters, and other loads which produce "noise" or electromagnetic interference, in excess
of the levels to which Specialty Concepts products are compatible.
6. Warranty repair and/or evaluation will be provided only at Chatsworth, California facility of Specialty Concepts. Units for
such repair and/or evaluation must be returned freight prepaid to Specialty Concepts with a written description of any
apparent defects. Specialty Concepts will not be required at any time to visit the installation site wherein Specialty
Concepts' products are subject to warranty repair and/or evaluation.
7. Only Specialty Concepts is authorized to repair any of its products, and they reserve the right to repair or replace any
unit returned for warranty repair. The party returning a unit for repair is responsible for proper packaging and for
shipping and insurance charges, as well as any other charges encountered, in shipping to and from Specialty Concepts.
8. This warranty supersedes all other warranties and may only be modified by statement in writing, signed by Specialty
Concepts.
Warranty terms effective as of April 1, 1993
REPAIR INFORMATION
Directions for returning units needing repair.
1. Write up a note with the following information:
Name / Company Name
Return Address : (For USA/Canada: UPS Deliverable. Avoid PO Boxes)
Daytime Phone
Description the failure
Specify amount of repair charges pre-approved (we will contact you if repair charges
are larger than this amount.)
2. Box up unit with copy of sales receipt (if available).
3. Send by UPS or Parcel Post to :
Specialty Concepts, Inc.
Attn : Repair Dept.
8954 Mason Ave
Chatsworth, CA 91311 USA
If the Repair is not covered under warranty, the repair charges will not exceed 30% of the value of a new
unit. (shipping and handling not included) Domestic charges are collected via UPS-COD.
For non-warranty repairs, repaired portion features an additional one-year warranty.
SPECIALTY CONCEPTS,INC.
8954 MASON AVE., CHATSWORTH, CA 91311 USA PH: (818) 998-5238, FAX: (818) 998-
5253
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.