Specialty Concepts LPU User Manual

LIGHTNING PROTECTION UNIT
LPU
(
Photovoltaic Lightning Protection Device
Installation and Operation Manual
SPECIALTY CONCEPTS, INC.
8954 Mason Ave.
MODELS COVERED: LPU-50, LPU-150, LPU-200 Copyright 6/1996 Specialty Concepts, Inc.
GENERAL DESCRIPTION
The Specialty Concepts Lightning Protection Unit (LPU) provides primary (gas discharge arrester) and secondary (MOVs) protection against induced transients generated from lightning strikes. The primary protection device is a three electrode gas filled surge protector tube. These devices simultaneously ground both sides of a pair when a surge appears on either line of the pair. The tube then restores when the surge dissipates. The secondary protection feature grounds any high voltage peak (spike) which might be passed by the primary protector. A high power inductor placed between the primary and secondary protectors exhibits a high impedance for most lightning induced voltage transients. This high impedance insures that the primary protector will operate first and the secondary protector will not be exposed to the full surge. The LPU is designed to be installed in series between the PV array and a Specialty Concepts designed PV system control electronics. Specialty Concepts designed electronics have additional lightning protection features in the form of MOVs that compliment the action of the LPU.
)
Terminals are provided for connection to "ARRAY IN" and "ARRAY OUT" plus and minus for each sub-array for each sub-array. Each sub-array channel is rated for 50 amps and is suitable for use in DC systems up to 48 volts DC nominal. Provisions are made for earth ground for each channel and for a chassis ground. The standard LPU is provided with a steel, wall mount, gasketed enclosure.
Note: The standard LPU is designed for negative ground systems. DO NOT wire the array with a common positive ground connection to the battery as this will reduce the effectiveness of the LPU.
FEATURES
SYSTEM LIGHTNING PROTECTION
50 amp, up to 48 volt nominal capacity per channel
Two stage protection
- High capacity gas discharge tube
- Fast response MOV
DESIGN FEATURES
4 gauge terminal block connection
Earth and chassis ground connections
Higher capacity available by paralleling
channels
Negative ground
Positive ground available (optional)
Wall mount indoor enclosure
Outdoor enclosure available (optional)
SPECIFICATIONS
PARAMETERS UNITS VALUE
Nominal Voltage (Volts) 12-48 Array Voc., Max. (Volts) 95 Array Current, Continuous / Channel (Amps) 50 Array Current, Max / Channel (60 seconds) (Amps) 65
Primary Stage Single Impulse Discharge Current,
8/20 µ sec waveform, Max. (Amps) 20,000
Impulse Life - 1000A,
10/1000 µ sec waveform, Min. (Surges) 400
Typ. (Surges) 600
DC Breakdown Voltage
Line to Ground (Volts) 150-300
Impulse Breakdown Voltage
Line to Ground
@ 100 V / µ sec, Typ. (Volts) 500 Max. (Volts) 750 @ 10 KV / µ sec, Typ. (Volts) 750 Max. (Volts) 1000
DC Holdover @ 200mA, Min. (Volts) 150
Secondary Stage Peak Surge Capacity
8/20 µ sec, Max. (Amps) 1500
Peak Voltage Clamping
@1mA, Min. (Volts) 85 Max. (Volts) 115
Response Time, Typ. (Nanosec.) 50
PART NUMBERING KEY
EXAMPLE: Model
Nominal Current Options
LPU - 50 - M
NOMINAL
MODEL CURRENT OPTIONS
LPU 50 M - Outdoor enclosure with
150 clear door (NEMA 4X) 200 P - Positive ground
Specifications and product availability subject to change without notice.