Speakman AL-2 Installation, Maintenance And Operation Instructions

Page 1
SPEAKMAN COMPANY
AL-2 Installation, Maintenance & Operation Instructions
ALARM SYSTEM
DESCRIPTION
Electrical alarm for use with emergency safety equipment. Unit is supplied with an electric horn and flashing light that are activated by a vapor proof flow switch when connected to an emergency shower or eyewash.
SPECIFICATIONS
ELECTRICAL DATA:
ELECTRICAL SUPPLY: 120 VAC, 60 Cycle, Single Phase. ELECTRICAL RATING: 7.5 Amps @ 120 VAC. COMPLIANCE: Unit For Use In Non-Hazardous Locations. Suitable for outdoor / wet locations.
*Power supply to be in compliance with (N.E.C.) National Electric Code.
OPTIONS
◊ DPDT (Double Pole, Double Throw Flow Switch For Remote Locations) ◊ BLUE GLOBE ◊ RED GLOBE ◊ CLEAR GLOBE ◊ BELL (97dB @ 10 Ft.)
INSTALLATION
To avoid electric shock make sure power supply is shut off before doing any electrical maintenance to this unit. Power supply requirement is 120 VAC, 60 cycle, single phase. Ground-fault protection should be GFPD with a nominal 30 milliampere trip level to prevent nuisance tripping. Minimum 15 AMP breaker is required. Make sure power supply is in compliance with National Electric Code (N.E.C.).
Use thread sealant on all joints.
OPERATION
Horn sounds and light flashes automatically when emergency equipment is activated and water flow triggers the
flow switch. Horn will sound and light will flash until emergency equipment is deactivated.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
Page 2
MAINTENANCEMAINTENANCE
To avoid electric shock make sure power supply is shut off before doing any electrical maintenance to this unit. Should you need to replace/repair any part of this unit, please reference parts list below for correct part numbers. Be sure water supply is shut off if flow switch is being repaired.
WARNING: Use only genuine Speakman
parts when repairing or replacing components. To order parts call 1-800-537-2107.
AL-2 REPLACEMENT/REPAIR PARTS
ITEM PART/GROUP # DESCRIPTION
1 76-0021 1/2” Condulett Body 2 76-0022 Condulett Cover 3 76-0023 Condulett Gasket
4 76-0031 Green Globe
5 76-0028 Light Guard 6 76-0181 Light Bulb 7 76-0030 Light Socket 8 76-0029 Light Splice Box 9 76-0172 Flow Switch 10 76-0173 3/4” Junc. Box 11 76-0175 Electric Horn 12 24-0253-GAL 1-1/4 X 1-1/4 X ½ Tee
PO Box 191 Wilmington, DE 19899 Phone: 800-537-2107 Fax: 800-977-2747
Visit us on the web at www.speakmancompany.com
SPEAKMAN
®
12/06
92-1549
Rev-4