Electric heat ................................................................................. 16
Qualied installer only —
This product must be installed
only by a qualied service technician. The installation must be
done using recognized industry
practices, and in compliance with
this manual and all applicable
codes. Failure to comply could
result in death, serious injury or
substantial property damage.
Preparing the SCM for shut down ............................................... 23
To restart after shutdown ............................................................ 23
SECTION 12: REPLACEMENT PARTS
SECTION 13: LIMITED WARRANTY
For information not included in this
manual, see the following: This manual
includes only basic information for installation, operation and maintenance of
SpacePak air to water heat pumps. For
more advanced applications and information not shown in this manual, contact
SpacePak Technical Support for assistance and supplemental instructions. Call
413-564-5530 in Westeld, MA or visit our
website at www.spacepak.com to send an
e-mail or review technical literature.
IN UNITED STATES: 260 NORTH ELM ST. WESTFIELD, MA 01085 800-465-8558 / FAX (413) 564-5815
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 1: READ BEFORE PROCEEDING
Hazard denitions
The following terms are used throughout this manual to bring
attention to the presence of potential hazards or to important
information concerning the product.
Indicates an imminently hazardous situation which,
if not avoided, WILL result in death, serious injury or
substantial property damage.
Indicates an imminently hazardous situation which,
if not avoided, COULD result in death, serious
injury or substantial property damage.
Indicates an imminently hazardous situation which,
if not avoided, MAY result in minor injury or property
damage.
Used to notify of special instructions on installation,
operation or maintenance which are important to
equipment, but not related to personal injury hazards.
Model SCM overview
The SpacePak Model SCM heat pump is a self contained
reverse-cycle heat pump that provides a continuous supply
of heated or chilled water for various purposes, such as:
residential or small commercial building heating and cooling;
and specialty applications, such as computer room cooling or
industrial/agricultural conditioning and dehumidication.
Model SCM heat pumps are available in three- and ve-ton
nominal capacities. Both use the same general design and
operating principals.
Each heat pump contains TWO isolated refrigeration systems
of equal size to cool or heat the delivered water supply. The two
systems can operate individually or in tandem to achieve 50%
or 100% capacity. The major components of each system are:
• A hermetically sealed refrigeration compressor & motor.
• An outside coil to reject heat (in cooling) or absorb heat (in
heating) from the surrounding ambient air.
• A fan and motor to force air over the outside coil.
• A shell-and-tube refrigerant-to-water heat exchanger to absorb heat (in cooling) or supply heat (in heating) to the deliv-
ered water ow.
• An electronic expansion valve to throttle the refrigerant ow
in both heating and cooling modes of operation, responding
to varying load on the system.
• A reversing valve (to select between heating and cooling
operation).
• Sensors and safety circuits to monitor and protect the equipment
from potentially damaging or dangerous operating conditions.
A single water circuit connects both internal heat exchangers,
and contains sensors to measure entering and leaving water
temperatures. A mechanical ow switch safety ensures
continuous water ow while either of the two refrigerant
systems is operating. All components are contained within a
supporting structure and enclosure sufcient to allow stand-
alone outdoor installation in all temperate climates.
All operation and protections are managed by a microprocessor
controller which operates the individual systems, determines
all operating parameters, and monitors the condition of each
system. A simple interface communicates with the indoor air
handler, heat exchanger, or other load.
Failure to comply with all of the guidelines
BELOW could result in death, serious injury or
substantial property damage.
Codes and electrical requirements
• This product must be installed in accordance with all
applicable codes. Where instructions in this manual differ
from specic local requirements, defer to the local codes.
• The electrical installation must also comply with the latest
edition of: in the U. S. — National Electrical Code ANSI/
NFPA No. 70; in Canada — CSA C22.1 Canadian Electrical
Code Part 1. Wiring must be N.E.C. Class 1. Use only copper
wire, rated for 120°F and sized for the load listed in this manual.
• Electrical shock hazard — Disconnect all electrical power
before servicing the unit. Also, the unit must be grounded in
accordance with the Electrical Code listed above.
Refrigerant
• The refrigeration system is factory charged with R410A
refrigerant, and requires no additional service during installation.
Any repair, diagnosis or maintenance service to the refrigeration
system must be performed by a qualied technician. No
alternate refrigerants, lubricants or additives are approved for
this unit. Any use of alternate or non-approved materials in the
refrigeration system may result in personal injury or equipment
damage, and will void the manufacturer’s warranty.
Liquid side
The uid in the liquid side of the Model SCM
must be an anti-freeze/water mix.
• The antifreeze percentage must be at least 10%. Follow
guidelines in this manual to nd the required antifreeze mix
for the application. Thoroughly ush the system before lling.
• The system must be supplied with a pump sized to provide
the minimum ow rates specied in this manual. Pump
selection must consider the pressure loss through the system
and its components plus the pressure loss through the SCM’s
heat exchanger and internal components. The pump must be
rated for use with chilled water/glycol mixture.
• Install a y-strainer at the liquid input of the heat pump as
shown in this manual to prevent damage to the heat
exchanger from sediment.
• DO NOT use for potable water heating. The single-wall
heat exchanger is not suitable for the application.
Ambient limits
• See information in this manual for heating and cooling
performance versus ambient temperature.
• For applications requiring cooling at outdoor temperatures
below 55°F, contact SpacePak Technical Support for
assistance.
• DO NOT disconnect power in cold temperatures. Power
must be on to allow the anti-freeze cycle to operate.
SCM controller
• The SCM controller provides adjustability of various operating
parameters to address specic applications. See Section 2
for detailed instructions to adjust these parameters.
– 2 –
Page 3
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Figure 1
Section 2: SCM Field Adjustable Parameters
Keypad
The keypad is used to set the unit operating values (see Parameters/alarms – Keypad combinations).
– 3 –
Page 4
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 2: SCM Field Adjustable Parameters (continued)
Figure 2 Menu Structure
Save in the EEPROM
parameters r*
parameters P*
parameter
values
regulation
alarm
main menù
setting password
parameters F-r*
software
parameters H*
unit setting
And
For 5”
For 5”
Or
parameters /*
probe settings
parameters F*
Or
parameter level
parameters A*
antifreeze
parameters b*
probes
parameters c*
compressor
parameters D*
defrost
fan
1F eulav level1F sretemarap1F seulav retemarap
Programming and Saving the Parameters
(See Figure 1 for Button Locations)
1. Press " " and "sel" for 5 seconds;
Prg
parameters Fn
Or
2. the heating and cooling symbol and the gure "00" are displayed;
3. use " " and " " to set the password and conrm by pressing "sel";
4. use " " and " " to select the parameter menu (S-P) or levels (L-P) and then press "sel";
5. use " " and " " to select the parameter group and then press "sel";
6. use " " and " " to select the parameter and then press "sel";
7. after making the changes to the parameter, press "sel" to conrm or " " to cancel the changes;
8. press " " to return to the previous menu;
Prg
9. to save the modications, press " " repeatedly until reaching the main menu.
Prg
Prg
Note:
a. The parameters that have been modied without being conrmed using the "sel" button return to the previous value.
b. If no operations are performed on the keypad for 60 seconds, the controller exits the parameter modication menu by timeout
and the changes are cancelled.
c. The appropriate passwords refered to in Step 2 can be found in the right-most column of the chart on the following page.
– 4 –
Page 5
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 2: SCM Field Adjustable Parameters (continued)
SCM Controller
The SCM controller allows the adjustment of heating & cooling setpoints, differentials, and defrosting parameters.
The following chart depicts the factory default values for the most commonly adjusted parameters.
Certain read only parameters are available to evaluate performance or troubleshoot faults. These are accessed through the same
parameter menu and are listed below.
DISPLAY DESCRIPTIONMIN MAX UOM DEFAULT MEANINGPASSWORD
A01 Low Temp AlarmA07 A04°F34.0Water temperature below which the Low Temp alarm A1 will activate22
A02 Alarm differential0.3 122.0°F4.0Alarm A1 turns off at A01 + A0222
A04 Aux heater setpointA01 r16°F36.0 Water temperature below which the pump and electric heater, if present, engage.
A05 Differential for aux heater0.3 50.0°F5.0Pump and heater turns off at A04+A0522
A07 Antifreeze alarm set point limit-40.0 176.0°F32.0Minimum temperature that A01 can be set to66
A08 Auxiliary heater set point in heating modeA01 r15°F90.0 Water temperature below which the electric heater, if present, engages in heating mode22
A09 Auxiliary heater differential in heating mode0.3 50.0°F5.0Electric heater turns off at A08 + A09 in heating.22
b00 Default display value010Flag0b00 = 0 Displays return water temperature b00 = 01 displays supply water temperature22
b01 Probe B1 reading--°F-Read only, real time return water temperature00
b02 Probe B2 reading--°F-Read only, real time sys 1 HX leaving water temp00
b03 Probe B3 reading--°F-Read only, real time Sys 1 OS coil surface temperature00
b04 Probe B4 reading--°F-Read only, real time ambient air temperature00
b05 Probe B5 reading°F-Read only, real time supply water temperature00
b06 Probe B6 reading°F-Read only, real time sys 2 HX leaving water temp00
b07 Probe B7 reading--°F-Read only, real time Sys 2 OS coil surface temperature00
c10 Accumulated compressor #1 hours (System 1)-- hrs x 100-Value x 100 is the accumulated compressor run time in hours00
c12 Accumulated compressor #3 hours (System 2)hrs x 100-Value x 100 is the accumulated compressor run time in hours01
C15 Accumulated pump hours-- hrs x 100-Value x 100 is the accumulated pump run time in hours00
d01 Defrost cycle01Flag0Defrost feature currently disabled22
d02 Defrost logic02Flag0Defrost on timed cycle22
d03 Start defrosting temperature0.0 d04Bar3.2Coil temperature below which Defrost initiates22
d04 End defrosting temperature0.0 176.0°F45End defrost temperature22
d06 Min. duration of a defrosting cycle0 150 Second60Minimum defrost duration even if all conditions are satised.22
d07 Duration of a defrosting cycle1 150 Minute5Time duration of a defrost cycle for one system.22
d08 Time between defrost cycle10 150 Minute45Run time between defrost cycle starts in one system22
d09 Delay between two circuits0 150 Minute10Minimum delay between start of defrost of one cuircuit to start of defrost of other circuit22
d11Immersion heaters on during defrost01Flag1Turns on electric immersion heater to offset heat loss during defrost cycle.22
d16 Forced ventilation time at the end of the defrosting 0360 Second45Duration of fan operation at full speed to clear water from coil66
d17 Defrost with compressors OFF0 80.0°F55.0Temperature above which defrost occurs with fans only.66
F02 Fan operating logic02Flag1
F05 Temperature for fans off in cooling-40.0 °F75.0Coil temperature below which fans turn off (if F02=2) (See Fig 1)22
F06 Temperature differential to turn fans back on0.0 50.0°F10.0Fans turn back on at F05+F06 (if F02=2) (See Fig 1)22
r01Cooling set pointr13 r14°F42.0Primary cooling setpoint (See Fig 3)00
r02Cooling differential0.3 50.0°F8.0Cooling differential/hysteresis00
r03Heating set pointr15 r16°F120.0 Primary heating setpoint (See Fig 5)00
r04Heating differential0.3 50.0°F8.0Heating differential/hysteresis00
r13Min. Cooling set point-40.0 r14°F36.0Minimum allowable cooling setpoint22
r14Max. Cooling set pointr13 176.0°F60.0Maximum allowable cooling setpoint22
r15Min. Heating set point-40 -40.0°F55.0Minimum allowable Heating setpoint22
r16Max. Heating set pointr15 176.0°F125.0 Maximum allowable Heating setpoint22
r17Cooling compensation constant-5.0 +5.0°F0.0Slope of Outdoor reset curve, Deg water temp/Deg ambient temp. Cooling mode (See Fig 5)22
r18Maximum distance from the set point0.3 20.0°F8.0Maximum deviation from setpoint that can be achieved by outdoor reset (See Fig 5 & Fig 6)22
r19Start compensation temperature in cooling mode -40.0 176.0°F85.0Ambient air temp above which Outdoor Reset is active in Cooling (See Fig 5)22
r20Start compensation temperature in heating mode -40.0 176.0°F30.0Ambient air temp below which Outdoor Reset is active in Heating (See Fig 6)22
r31Heating compensation constant-5.0 +5.0°F0.0Slope of Outdoor reset curve, Deg water temp/Deg ambient temp. Heating mode (See Fig 6)22
0=Fans on whenever unit is on, 1=both fans on when either compressor is running,
2=both fans on when either compressor is running and coil temp is above threshold
66
– 5 –
Page 6
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
FAN STATUS
SCM LOW AMBIENT COOLING
SOLSTICE OUTDOOR RESET, COOLING
WATER TEMPERATURE SP,
S
O
L
S
T
I
CE
OUTDO
O
R RESET, HEA
T
I
NG
Section 2: SCM Field Adjustable Parameters (continued)
Figure 3 SCM Fan Speed Control, Cooling
If the fan control logic, parameter F02, is set to 02, the fans will
shut off if the outside coil surface temperature (as read by sensors
b03 & b07, whichever is greater) falls to the value established
by parameter F05 (75°F, factory default) and remain off until
the coil surface temperature rises above F05 plus F06 (75°F +
10°F=85°F, factory default) when the fans will turn on again.
r01
r17 (<0 AS SHOWN)
EMPERATURE SP, °F
WATER
OUTDOOR AMBIENT TEMPERATURE, °F
If the cooling compensation constant, parameter r17, is set to a
value other than zero, the water temperature setpoint will be the
value established by parameter r01, (42°F factory default) until
the outdoor ambient temperature rises to the value of parameter
r19 (85°F factory default). Then, as the outdoor temperature
continues to increase, the water temperature setpoint will
change (increase if r17 is greater than zero, decrease if r17
is less than zero) by the ratio of change in water temperature
setpoint to change in ambient temp. For example, if r17 is
set to a value of -.5, the setpoint will decrease by 0.5°F for
every 1.0°F increase in outdoor ambient temperature. This will
continue, until the difference between the new setpoint and the
original setpoints matches the value established by parameter
r18 (8.0°F factory default), So the nal setpoint (42°F - 8°F=34°F
factory default) will remain xed even if the ambient temperature
continues to rise.
If r17 is set to zero, the water temperature setpoint will remain
xed at the value established by parameter r01 through the
entire range of cooling operation.
r19
r18
°F
r31 (<0 AS SHOWN)
r18
r03
r20
OUTDOOR AMBIENT TEMPERATURE, °F
If the heating compensation constant, parameter r31, is set to a
value other than zero, the water temperature setpoint will be the
value established by parameter r03, (120°F factory default) until
the outdoor ambient temperature falls to the value of parameter
r20 (30°F factory default). Then, as the outdoor temperature
continues to fall, the water temperature setpoint will change
(decrease if r31 is greater than zero, increase if r31 is less than
zero) by the ratio of change in water temperature setpoint to
change in ambient temp. For example, if r31 is set to a value of
-.5, the setpoint will increase by 0.5°F for every 1.0°F decrease
in outdoor ambient temperature. This will continue, until the
difference between the new setpoint and the original setpoints
matches the value established by parameter r18 (8.0°F factory
default), So the nal setpoint (120°F + 8°F=128°F factory default)
will remain xed even if the ambient temperature continues to fall.
If r31 is set to zero, the water temperature setpoint will remain
xed at the value established by parameter r03 through the
entire range of heating operation.
– 6 –
Page 7
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 4: Dimensions
Figure 8 Model SCM dimensions (ALL DIMENSIONS IN INCHES)
ABDD1D2EFGHJKWW1W2
Model
SCM-036
SCM-060
Leg
Front to
height
return
11017
11017
Cabinet
depth
3
/
3
/
Mounting
4
4
lug
depth
17
17
3
/
8
3
/
8
Mounting
lug
centers
3
15
/
4
3
15
/
4
Bottom
to
return
1
5
/
2
1
5
/
2
Bottom
to
supply
1
15
/
4
1
15
/
4
– 10 –
Base to
bottom edge
of lower fan
Overall
Height
Return
connec-
25531" NPT 1" NPT 43
25531" NPT 1" NPT 43
tion
Supply
connec-
tion
Overall
width
3
/
3
/
8
8
Mounting
lug
centers
1
27
/
2
1
27
/
2
Lug
center
to edge
15
7
/
15
7
/
16
16
Page 11
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 5: Location & Mounting
Failure to comply with all of the guidelines
IN THE FOLLOWING could result in death,
serious injury or substantial property damage.
The installation must comply with all applicable
local codes.
Prepare the unit
• Inspect the unit for shipping damage. DO NOT use if there is
a risk that the damage could affect unit operation.
• Make sure all required components are available.
• Install optional immersion heater, if used. See instructions
provided with the heater.
Location
• DO NOT locate where the unit could be sprayed by sprinklers.
• DO NOT locate near swimming pools, spas or any location
that could cause chlorine or other contaminant to enter the
unit.
• DO NOT locate where water run-off from adjacent structures
could impinge on the unit.
• Maintain the clearances shown in Figure 10.
• LOW AMBIENT conditions — Contact SpacePak Technical
Support to obtain low ambient adjustment instructions if
cooling operation below 55°F is required.
• CORROSIVE ENVIRONMENTS — Do not install the unit in
an area subject to sea air or other potential corrosive
contaminants.
• INDOOR INSTALLATION — If the unit is installed inside a
building, the building must be equipped with air openings
sufcient to ensure free discharge of heated (or cooled) air
generated by the heat pump. All clearances must be
maintained to ensure free air ow into and out of the
enclosure. Make sure no other equipment located in the
space will be affected by the unit’s air ow.
Handling
• See Figure 9.
• Place padding at pressure points to prevent damage to the
enclosure.
• Use caution when handling. The unit is heavy and could
cause severe injury or damage if dropped or handled
incorrectly.
Figure 9 Handling with cables
Figure 10 Maintain clearances below
Minimum clearances (inches)
STUV
20 594020
Mounting pad
• The SpacePak heat pump must be mounted on a
level, corrosion and weather-resistant mounting surface,
preferably concrete. The structural support must be
suitable for the operating weight of the unit and attached
components, its mounting pad, snow loading and any other
expected loads.
• The mounting pad must not be attached directly to a structure
where noise transmission can occur.
• Vibration isolators supplied with the heat pump may be installed when desired to reduce transmitted vibration.
• The unit must be bolted securely to the pad. Where required
by local jurisdiction, the mounting must also be analyzed for
seismic loading capability.
• The mounting must ensure that there will be no debris
accumulation which might block air ow through the
enclosure openings. The lower edge of the lower fan
opening must be above the typical snow line, including
allowance for drifting.
• There must be no accumulation of water that could reach the
bottom of the unit’s enclosure.
– 11 –
Page 12
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 6: Recommended Piping Diagram
BACKFLOW-PREVENTION
Figure 11 SpacePak heat pump with single air handler (See Section 7 for instructions)
RETURN FROM TERMINAL UNIT(S)
SUPPLY TO TERMINAL UNIT(S)
BUFFER
TANK
DRAIN VALVE SHOULD BE
LOCATED AT LOWEST
POINT IN PIPING SYSTEM
AUTOFILL LOCATION IS SUGGESTED,
BUT THE FINAL LOCATION TO BE
MADE BY FIELD CONTRACTOR
SCM HEAT PUMP
SPL-WG0994-01_A
CIRCULATOR
DRAIN VALVE
BALL VALVE
STRAINER
EXPANSION TANK
AUTOMATIC AIR VENT
VALVE
PRESSURE RELIEF VALVE
PRESSURE GAGE
PRESSURE REDUCING
DEVICE
VALVE
– 12 –
Page 13
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Ethylene Glycol %1020304050
Min. Ambient Temp for Operation23°F/-5°C14°F/-10°C2°F/-17°C -13°F/-25°C -36°F/-38°C
SpacePak Capacity Multiplier0.980.960.930.910.89
Pressure Drop Multiplier (Cooling)1.061.121.161.251.36
Pressure Drop Multiplier (Heating)1.061.121.161.221.28
Minimum Expansion Volume / System Volume
Heating and Cooling (Gallons)1 gallon expansion per 15 gallons system volume
Heating only, HP only (Gallons)1 gallon expansion per 20 gallons system volume
Heating Only, with Boiler (Gallons)1 gallon expansion per 15 gallons system volume
Propylene Glycol %1020304050
Min. Ambient Temp for Operation26°F/-3°C18°F/-8°C8°F/-13°C -7°F/-22°C -29°F/-34°C
SpacePak Capacity Multiplier0.990.980.960.930.88
Pressure Drop Multiplier (Cooling)1.101.201.341.51.65
Pressure Drop Multiplier (Heating)1.101.201.341.461.5
Minimum Expansion Volume / System Volume
Heating and Cooling1 gallon expansion per 15 gallons system volume
Heating only, HP only1 gallon expansion per 20 gallons system volume
Heating only, with Boiler1 gallon expansion per 15 gallons system volume
*Remember to check the CV rating of your ttings and valves to make
sure your getting the correct ow through the equipment.
Glycol/Water System Design
Each SCM Heat Pump has a recommended ow that should be
maintained during all times of operation. For the SCM-036, the
recommended ow is 10 GPM, at which the head loss through the
heat exchanger is 15.8 ft. WC, 6.8 PSI or 47 kPa. For the SCM-
060, the recommended ow is 12 GPM, at which the head loss
is 24.2 ft. WC, 10.4 PSI or 72 kPa. These head loss values are
based upon pure water, see Figure 12 for multipliers to correct for
various concentrations of anti-freeze solution.
Note: these are the recommended ow values. Should the ow
drop signicantly below this value, the heat pump will shut down
and display the code FL on the display. This is not an indication
of a fault in the heat pump, but rather points to insufcient pump
or plumbing capacity, or air trapped within the system.
System Volume and Expansion Volume
To ensure smooth temperature control and minimize cycling of
refrigeration system, all installations must have total circulating
volumes equal to or greater than 7-1/2 gallons per nominal ton
of the unit performance (The greater of either heating or cooling
produced). In other words, in the case of a four ton heat pump the
minimum total system volume is 4x7-1/2=30 gallons. Multiple heat
pump installations that are operating in a staged conguration follow
the same rule, so that only a single heat pump tonnage needs to be
considered. Additionally, the system requires an expansion volume
(air) to compensate for the change in volume of the glycol mixture
as it heats and cools, see Figure 12 for expansion volume.
A typical multiple heat pump installation may actually have a
volume far greater than the minimum required, and it is this entire
volume that must be considered when sizing the expansion tank.
Note that the nominal expansion tank volume is not the same as
the expansion volume. If the actual air volume is not published,
consider it to be no more than half the nominal volume.
As an example, a four ton nominal heat pump, used for both
heating and cooling, requires a minimum of thirty gallons of
circulated system volume. A 40 gallon buffer tank is selected for
best operation. When the system installation is complete, the
total liquid volume of plumbing, air handlers, and heat pump is
45 gallons. (Note the expansion tank, no matter how large, is
not considered circulated volume) This requires an acceptance
volume of 3 gallons. If the acceptance volume is not specied,
assume it is 50% of the total volume. Therefore, this system
would require an expansion tank of 3 gallons acceptance
volume, or six gallons nominal full volume.
Air Separator
Locate at least one high efciency air separator as shown in the
piping to remove any air from the system.
Glycol / Water Mixture
The water system must contain a mixture of
inhibited glycol and water with thermal protection
sufcient for the coldest expected temperature for
the installation. The inhibitor level can degrade over
time, and may need to be adjusted periodically.
The inhibitor is essential to prevent the glycol from
accelerating corrosion of metal components in the
system. The glycol and inhibitor levels must be
checked regularly (no less than once annually).
The minimum allowable concentration of glycol is
10% by volume in all installations.
Automotive glycol is not suitable for use in the LAHP
system. Over time it may leave deposits which will
degrade the performance and damage pumps or
other devices in the system. Use only ethylene
glycol or propylene glycol mixtures specically
labeled for boiler or HVAC use.
– 13 –
Page 14
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 7: Glycol/Water System (continued)
Glycol/Water System Installation
Obtain all components specied in Figure 11. Make sure all
components and piping comply with applicable local codes.
DO NOT use galvanized pipe anywhere in the system.
Galvanizing will react with the glycol and can cause glycol
degradation and sludge in the system.
• Conrm charge of expansion tank is 12-15 PSIG (with no
water or pressure in the system).
• Install the system piping. DO NOT connect the SpacePak
unit to the system piping until the system has been cleaned
as required below.
The SCM must NOT be connected to the system during this
process.
1. Connect a hose from a fresh water supply to the system ll
hose bib. Note the drain port can be used for this purpose.
The hose bib purge/drain valve should be located low in the
system and close to the SCM return connection.
2. Open the high point purge valve, (not shown in illustration, as
it may be inside the air handler) while slowly lling the system.
Close the valve when air is removed from the system and
water begins to ow out of the valve.
3. Fill the system with fresh water and run water until the system
has been thoroughly ushed clean.
Automatic Fill – When an automatic ll system is installed, the
cooling uid (Glycol/water) must be inspected at least every 3
months, or whenever a leak is detected to ensure the proper
glycol concentration is maintained.
Pressure Test The System
1. Add water to the system as needed to raise the pressure to
25 PSIG (verify that all system components are suitable for
this pressure). Verify that the pressure remains constant for
at least one hour. Locate and correct any leaks.
2. After successfully testing, drain the system and remove the
fresh water hose.
Insulate The Piping
1. After testing and draining the system, apply pipe insulation. Fill
system with glycol/water mixture. Calculate the system volume.
2. See Figure 12, for required glycol concentration for the minimum expected outside temperature.
3. Obtain the required volume inhibited glycol/water solution
premixed or mix in a clean container. (The glycol must contain
an inhibitor to prevent metal corrosion.)
4. Pump the glycol/water solution into the system, allowing air
to escape through the purge valve(s).
5. After lling the system, sample the system uid and verify
glycol and inhibitor percentages, following instructions
provided with the glycol.
The electrical loads given in Figure 1, allow for a pump load of no
more than 5 amps at 110 VAC (2.5 amps at 230 VAC). If the pump
load exceeds this, provide a separate power source to the pump. DO
NOT feed power to the pump from the SpacePak air handler panel.
• Provide a separate power source and overcurrent protection
for the immersion heater. Refer to the Figures 18 and 19 of
this manual for detailed wiring.
SCM Control Wiring Connection
The SpacePak SCM requires a dry contact (relay) signal to
enable and select between heating and cooling modes. They
will not operate on the 24V signals from typical thermostats or air
handlers. Connecting 24V to either of these points will result in
erratic operation and may cause signicant component damage.
• Connect single zone systems to heat pump as shown in
Figure 16.
• Connect multiple zone system to heat pump using SpacePak
SSIC Control Module and instructions included with it.
to manual supplied with SSIC Control Module for connection
and operational details.
• See Figure 19, for heat pump electrical ladder diagram.
Section 9: Electrical Diagrams.
Refer
Low Ambient Temperature Cooling Operation
If cooling operation is desired in a year-round application, or
any time outdoor temperatures are expected to be consistently
below 55˚F, the fan operation should be modied in order to
ensure proper operating conditions within the refrigeration
system. Refer to Section 2, Fig. 3, for instructions.
Note once implemented, this will cause the fans to start and stop
periodically during operation. This is normal behavior during
cooler outdoor temperatures and should not be a concern.
– 14 –
Page 15
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
DRAIN VALVE
Section 8: Start-up and Test
Figure 14
PURGE VALVE
(MANUAL)
A
B
See the above illustration; note this is not intended to include all
components in the system, just the minimum to properly purge
air from the heat pump.
1. With the heat pump isolated and dry, valves A & B closed,
charge the “system”(that is, all the plumbing not shown), and
remove as much air as possible through the air separator.
2. Apply a static pressure to the system, with all pumps off, of
15-25 PSI.
3. Very gradually open the lower ball valve, B, to allow water un-
der pressure to begin to ll the heat pump from the bottom.
4. Crack the manual vent valve until you hear air escaping.
5. Allow the water to continue to ll the heat pump, displacing air.
This should go very slowly, and could take a minute or more.
6. When all the air has been displaced and a steady stream of
water is owing out of the vent valve, fully open ball valve B.
7. Open ball valve A, a small amount of air might escape the
vent valve from the heat pump supply line.
8. When all the air has escaped, close the vent valve.
Note, this procedure lls the heat pumps in the opposite direction
of normal ow, so it must be done when all pumps are off.
BEFORE starting the unit
Electrical shock hazard — Disconnect all electrical
power before proceeding with the following.
1. Verify that the system and all components have been installed in accordance with this manual and all applicable
codes and instructions.
2. Inspect the SpacePak heat pump and all other system components. All components should be in good condition and
operational.
3. Inspect the water piping for any signs of leakage.
Repair all system leaks. Leakage will cause pressure
to drop, preventing the heat pump from operating.
Leaks also allow introduction of excess make-up
water, whether lled automatically or manually.
4. Check system pressure. The pressure should be at least
15 PSIG with heat pump not in operation.
5. Check all wiring connections to ensure terminal connections
are tight and all wiring is in place.
Start the SpacePak heat pump
Start in cooling mode.
1. Apply power to the unit
2. The display (Figure 1) should show the start sequence —
uC2, then 2.0, then the current water temperature. No other
symbol should appear.
3. When the display shows only temperature, lower the
thermostat setpoint below the current room temperature.
4. This begins a call for cooling, and the pump symbol will begin
to ash.
5. After 1 to 2 minutes, the pump symbol will change to constant
display, and the pump will begin circulating.
6. Assuming the water is outside of the cooling temperature
range (above 42°) the refrigeration system will initiate and
the 1, or 3, or both numerals will begin ashing.
7. After 1 to 2 minutes, the 1, or 3, or both numerals will change
to constant, the compressor symbol will turn on and one or
both compressors will start.
8. Observe for any alarms, errors, or faulty operation (noises,
vibration, etc)
9. When operation is deemed satisfactory, raise the thermostat
set-point or turn it off.
10. The pump will run for approximately two minutes after the
compressor shutdown.
Start in heating mode.
1. When the pump has stopped, change the thermostat to Heat-
ing (if applicable) and raise the set point above current room
temperature.
2. This initiates a call in Heating mode. The pump symbol will
begin ashing.
3. After 1 to 2 minutes, the pump symbol will change to constant
display, and the pump will begin circulating.
4. Assuming the water is outside of the heating temperature
range (below 120°) the refrigeration system will initiate and
the 1, or 3, or both numerals will begin ashing.
5. After 1 to 2 minutes, the 1, or 3, or both numerals will change
to constant, the compressor symbol will turn on and one or
both compressors will start.
6. Observe for any alarms, errors, or faulty operation (noises,
vibration, etc).
– 15 –
Page 16
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 8: Start-up and Test (continued)
Anti-freeze cycle
1. Should the water temperature drop to 34°F during periods
of non-use, the pump will start and the antifreeze heater (if
connected) will energize and continue to operate until the
temperature reaches 38°F.
2. If the water temperature continues to fall and reaches 33°F,
the Alarm symbol and Fault Code AL will be displayed,
and the unit will automatically start in heating mode. It will
continue to run until the water temperature reaches 38°F.
3. NOTE: This provides the maximum level of protection in all
cases, but may use energy unnecessarily when a suitable
concentration of glycol anti-freeze is installed. When freeze
protection is sufcient, these value can be adjusted to
lower temperatures. Contact technical support for guidance
in re-conguring these parameters, however it must be
understood that the installer is responsible for ensuring
sufcient freeze protection to the lowest temperature allowed.
24-Hour follow-up
Approximately 24 hours after start-up and testing, return to the
installation to verify proper operation. Perform the following
checks.
1. Check system pressure. Add additional glycol/water mixture
if needed to restore pressure. (Pressure can drop as air is
removed from the system by the air vents.)
2. Sample the glycol/water mixture in the system. Verify inhibitor
and glycol levels.
3. Inspect the piping and components to ensure there are no
leaks. Repair any leaks immediately.
4. Close the isolation valves on either side of the y-strainer at
the SpacePak heat pump return connection. Remove the
screen and inspect for sediment. Clean if necessary.
• If the strainer has become clogged with sediment, determine
whether the system needs to be drained, cleaned and re-
lled. Excessive sediment accumulation in the strainer will
reduce ow and cause the unit to shut down.
5. Cycle the system on heating and cooling. Verify that all
components operate correctly.
B. Heat boost: When the heat pump is operating in heating
mode, the Carel controller will call for the heater to be
energized when the water temperature falls below the value
of parameter A08, again controlled by the TDR. Parameter
A09 is a differential value, such that the heaters will shut off
when the temperature reaches A08 + A09.
C. Defrost operation: When enabled, via parameter d11 being set
to a value of 01, the controller will call for the heater to energize,
after the TDR duration, whenever the defrost cycle is active.
Time Delay Relay
In all instances, the heaters receive power only after a time
interval, controlled by the TDR. See Figure 15. The TDR can be
adjusted to provide a delay from .01 second, to 100 hours. This
is accomplished by two dials on the face of the components. The
lowed dial establishes the range, in increments of 0.1 second, 1
second, 6 seconds, 60 seconds, 0.1 hour, 1 hour, and 10 hours.
The upper dial is the multiplier, and increased the range from 1 to
10 times. The factory default is 10 minutes as shown in the gure;
the range is 60 seconds, and the multiplier is 10. This may be
excessively long for most applications, and may be adjusted to a
shorter interval, especially if it is primarily used for defrost operation.
When the TDR receives a signal from the controller, the Coil
LED will begin to ash, and continue for the duration of the time
delay. Once the delay has expired, the Coil LED will change to
solid, and the Contact LED will illuminate also. When the signal
is removed from the TDR, the contact will open immediately.
Protection
The heater circuit must rst prove water ow before energizing
the heaters, and maintain a circuit through an overtemp
protection device (located within the heater element) which
opens at 201°F. Should either of these conditions fail, the heaters
will immediately de-energize.
Heater Capacity
The internal circuit and switching is sufciently robust to carry the
load of the 3kW internal heater, or the (2) 3kW heaters within the
available BT-H series buffer tanks, but it cannot power all three
heaters. Therefore, the internal heater must be disconnected
from power when connecting buffer tank heaters.
Electric Heat
The SCM series heat pumps are equipped with integral 3 kW
electric heater elements contained within the water circuit. These
are powered by a 230VAC input (separate from the heat pump
power) and must have individual protection, (minimum 15A)
The heater function is managed by the Carel μC2 controller, and
it provides three different functions, all of which are adjustable
via the Display Keypad.
A. Freeze protection: When the heat pump is in standby,
it monitors the temperature of the water circuit. If the
temperature falls below the value of parameter A04, the
controller will start the circulator, and send a call for the
heaters to energize. The heaters are powered through a Time
Delay Relay (TDR), to ensure ow is established before the
heaters come on. Parameter A05 is a differential value, such
that the heaters will shut off when the temperature reaches
A04 + A05.
Figure 15
– 16 –
Page 17
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 9: Electrical Connections
The electrical installation must comply with
the latest edition of: in the U.S. — National
Electrical Code ANSI/NFPA No. 70; in
Canada — CSA C22.1 Canadian Electrical
Code Part 1. Wiring must be N.E.C. Class 1.
Use only copper wire, rated for 120°F and
sized for the load listed in this manual.
Electrical shock hazard — Disconnect
all electrical power before servicing the
unit. Also, the unit must be grounded in
accordance with the Electrical Code listed
above.
Overcurrent protection & wire
sizing
• Protect each circuit with a breaker or fuse rated for
the load given in Figure 1.
The electrical loads given in Figure 1,
page 3 allow for a pump load of no more
than 5 amps at 110 VAC (2.5 amps at
230 VAC). If the pump load exceeds this,
provide a separate power source to the
pump. DO NOT feed power to the pump
from the SpacePak air handler panel.
• Provide a separate power source and overcurrent
protection for the immersion heater. Refer to the
Figures 18 and 19 of this manual for detailed wiring.
Figure 16 SpacePak Heat Pump eld wiring — SINGLE air handler
(See Figure 19 for ladder wiring diagram)
(SCC-1)
SpacePak heat pump wiring
The SpacePak SCM heat pumps require
a dry contact (relay) signal to enable
and select between heating and cooling
modes. They will not operate on the 24V
signals from typical thermostats or air
handlers. Connecting 24V to either of
these points will result in erratic operation
and may cause signicant component
damage.
• Connect single air handler to heat pump as shown
in Figure 16.
• Connect multiple air handlers to heat pump via
SpacePak heat pump Interface Module as shown
in Figure 17.
• See Figure 19, for heat pump electrical ladder diagram.
– 17 –
Page 18
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 9: Electrical Connections (continued)
Multiple air handler applications
•
For multiple air handler applications, provide a zone
valve or pump to control water the ow to the air
handler.
• When the zone thermostat activates the SCM,
the valve will be activated by the SpacePak air
handler.
• The total zone control load must not exceed
20 VA at 24 VAC. If a larger valve or zone pump
is used, it must be switched by a power relay
controlled from the 24 VAC output of the air
handler.
• Refer to manual supplied with SSIC module for
connection and operational details.
Figure 17 SpacePak Heat Pump eld wiring — Multiple air
handlers (see Figure 19 for ladder wiring diagram)
(SSIC)
– 18 –
Page 19
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 11: Annual Maintenance
Perform Annual Inspection
Glycol/water mixture
The water system must contain a mixture of
inhibited glycol and water with thermal protection
sufcient for the coldest expected temperature for
the installation. The inhibitor level can degrade over
time, and may need to be adjusted periodically. The
inhibitor is essential to prevent the glycol from
accelerating corrosion of metal components in the
system. The glycol and inhibitor levels must be
checked regularly (no less than once annually).
The minimum allowable concentration of glycol is
10% by volume in all installations.
Automotive glycol is not suitable for use in the heat
pump system. Over time it may leave deposits
which will degrade heat pump performance and
damage pumps or other devices in the system.
Use only ethylene glycol or propylene clycol
mixtures specically labeled for boiler or hvac use.
1. At least once annually, sample the system uid to verify that
the glycol concentrations meets the minimum value given in
Figure 12. Also test the inhibitor concentration. Add glycol
and inhibitor as needed to return the system to the correct
concentrations.
2. Perform any and all other tests as recommended by the
anti-freeze manufacturer’s instructions in order to ensure
optimal performance and maintain warranty protection on all
installed components.
Check operating pressure
1. Check the glycol/water system pressure. Operating pressure
should be between 15 and 25 PSIG. Adjust uid volume if
needed to restore pressure.
2. If pressure is low, check system for evidence of leaks. Repair
all leaks immediately.
4. Close the isolation valves on either side of the y-strainer at
the SpacePak heat pump return connection. Remove the
screen and inspect for sediment. Clean if necessary.
• If the strainer has become clogged with sediment,
determine whether the system needs to be drained,
cleaned and re-lled. Excessive sediment accumulation
in the strainer will reduce ow and cause the unit to shut
down.
5. Inspect all wiring and wiring connections. Tighten connections if needed. Correct any problems found.
6. Check the fuses or breakers to ensure they are correctly
sized and properly installed.
7. Clean the SCM heat exchangers and air openings.
8. Cycle the system on heating and cooling. Verify that all components operate correctly.
Preparing the SCM for shut down
DO NOT turn off power to the SCM heat pump in
the winter or any time when there is a possibility of
freezing. Power must be ON for the automatic antifreeze operation to occur. See information below for
preparing the unit for shut down.
1. When the water temperature drops below 34°F during
periods of non-use, the pump will start and the antifreeze
heater (optional, when installed) will energize and continue
to operate until the temperature reaches 38°F.
2. If SCM must be turned off or left idle during periods when
freezing is possible, one of the following must be done:
a. Verify that sufcient glycol solution is present to protect
against most extreme anticipate conditions
b. — OR — Drain heat pump and external piping completely
To restart after shutdown
1. If unit was drained, rell.
2. Follow start up procedure from Section 8.
Perform annual inspection
Electrical shock hazard — Disconnect all electrical
power before proceeding with the following.
1. At least once annually, perform a complete inspection of the
system, including at least the following.
2. Inspect the SCM for signs of dirt or debris accumulation. Remove any debris and notify the building owner that the unit
must be kept clean and unobstructed.
3. Inspect glycol/water system piping and components. Repair
or replace any defective components. Repair all leaks immediately.
– 23 –
Page 24
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Figure 23 Replacement parts
PART NUMBERDESCRIPTIONVENDOR PART NUMBER
SCM036SCM060
45R20000-320009Carel Temperature Sensor, 10KNTC015WP00 (IP68,-55F to 212F, 5 Ft., 10K Ohm)
45R20000-360006Compressor ContactorHCC -1NU04A A
45R2000-3136Fan Motor ControllerCONVON/OFF
45R2000-3137Carel Expansion BoardMCH2000020
45R2000-3138Carel ControllerMCH2000010
45R2000-3157Soft Start PCB2000-3157
45R2000-3501Fan Motor CapacitorCBB61 (35μF/450VAC)
After powering up the unit, the following steps must be followed:
START UP IN COOLING MODE
____ Display start sequence will read uC2, then 2.0, then the current water temperature
If only temperature is displayed, lower the thermostat setpoint below the current
room temperature
____ Pump symbol will begin to flash as a call for cooling is made
____ After 1-2 minutes pump symbol will remain constant
____
____ After 1-2 minutes the 1, 3, or both numerals will remain constant, the compressor
____ Observe for any alarms, errors, or faulty operation (noise, vibration etc)
____ When operating sufficiently, raise thermostat set-point or turn it off
____ Pump will run for approximately 2 minutes after compressor shutdown
Once water is outside the cooling temperature range (above 42°F) the refrigeration
system initiates and the 1, 3, or both numerals will begin flashing
symbol will come on and one or both compressors will start
– 25 –
Page 26
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
START UP IN HEATING MODE
____ Once pump has stopped, change the thermostat to Heating (if applicable) and raise the
set point above the current room temperature.
____ Pump symbol will being to flash as a call for heat is made
____ After 1-2 minutes pump symbol will remain constant
____
Once water is outside the cooling temperature range (below 120°F) the refrigeration
system initiates and the 1, 3, or both numerals will begin flashing
____ After 1-2 minutes the 1, 3, or both numerals will remain constant, the compressor
symbol will come on and one or both compressors will start
____ Observe for any alarms, errors, or faulty operation (noise, vibration etc)
24 HOUR FOLLOW UP
24 Hours after start up the following checks should be performed:
____ Check System Pressure (add glycol/water mixture if needed to restore pressure)
____ Sample and verify glycol/water mixture
____ Inspect all piping and components for leaks
____ Close isolation valves on either side of the y-strainer at the heat pump return
connection
____ Remove the screen and inspect for sediment, clean if necessary
If the strainer is clogged determine if system needs to be drained and re-filled.
Excessive sediment buildup will cause reduced flow and the system will shut down
____ Cycle the system in both heating and cooling
____ Verify that all components operate correctly
– 26 –
Page 27
Model SCMAir to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 13: LIMITED WARRANTY
Air to Water Reverse Cycle Heat Pump
The “Manufacturer” warrants to the original owner at the original installation site that the Air to Water
Reverse Cycle Heat Pump (the “Product”) will be free from defects in material or workmanship for
a period not to exceed one (1) year (parts) or two (2) years (compressor) from the startup. If upon
examination by the Manufacturer the Product is shown to have a defect in material or workmanship
during the warranty period, the Manufacturer will repair or replace, at its option, that part of the
Product which is shown to be defective.
This limited warranty does not apply:
a) if the Product has been subjected to misuse or neglect, has been accidentally or
intentionally damaged, has not been installed, maintained or operated in accordance
with the furnished written instructions, or has been altered or modied in any way.
b) to any expenses, including labor or material, incurred during removal or reinstallation of
the defective Product or parts thereof.
c) to any workmanship of the installer of the Product.
This limited warranty is conditional upon:
a) shipment, to the Manufacturer, of that part of the Product thought to be defective. Goods
can only be returned with prior written approval from the Manufacturer. All returns must
be freight prepaid.
b) determination, in the reasonable opinion of the Manufacturer, that there exists a defect
in material or workmanship.
Repair or replacement of any part under this Limited Warranty shall not extend the duration of the
warranty with respect to such repaired or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESS OR
IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE
HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT
SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL,
OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN
EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO
BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT
SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY EACH
JURISDICTION.
– 27 –
Page 28
IN UNITED STATES: 260 NORTH ELM ST. WESTFIELD, MA 01085 800-465-8558 / FAX (413) 564-5815