Pull the cables from the square access hole of the mounting plate C.
3
A.
A.
4
B.
B.
5
A.
C.
B.
A.
6
8
D.
g.
7
d.
Use a screwdriver to screw the metal plate C to the wall.
Take off the plastic mounting plate B from the body A, and pull the cables
C.
through the access hole of C and B, then connect to the body A.
Assemble plate B with the body A, and embed the water proof strip D
onto the plastic side frame.
Assemble the body A onto the mounting plate C with the Allen key and
screws (accessories supplied).
Turn on the power and LED will light and beep will sound.
E.
F.
A1.
F.
3
2
Use a screwdriver to screw the base F onto the wall.
Attach the water proof gasket to the body A1, and pull the cables
from the square hole of the base F, and connect to the body A1.
Assemble the body A1 with the base F.
4
e.
f.
5
Screw A1 and F tight with the Allen key and screws (accessories
supplied).
Turn on the power and LED will light and beep will sound.
Put on G, and attach A1 onto the plastic plate A3, and screw it with
the Allen key and screws (accessories supplied).
Put the ring O on the metal frame, and put them together onto the
reader A1+A3, and screw them and buckle up the 4 buckles on the
back.
Embed the water proof strip D onto the frame side of the base.
Following by the install process of AR-725E-M.
A3.
A2.
H.
A1.+A3.
2
b.
e.
3
f.
D.
4
a.
5
3 Door Controller
Illuminated Touch-panel
Notice
1. Tubing: The communication wires and power line should NOT be bound in the same conduit or tubing.
2. Cable selection: Use AWG 22-24 Shielded Twist Pair to avoid star wiring. Use CAT5 for TCP/IP connection.
3. Power supply: Don’t equip reader and lock with the same power supply. The power for reader may be unstable when the lock is activating, that may make the
reader malfunction. The standard installation: Door relay and lock use the same power supply, and reader use independent power supply.
4. Keypad lock: If 725E does not link [TCP / IP connection], the 725E keypad locks about 5 seconds after power transmission.Setting will work after