These instructions should be read thoroughly before attempting installation.
Set up, installation and Performance Check should be performed by a
qualified service technician. The Manufacturer, Southbend (1100 Old
Honeycutt Rd., Fuquay-Varina, North Carolina 27526), informs you that
unless the installation instructions for the above described Southbend product
are followed and performed by a qualified service technician, (a person
experienced in and knowledgeable concerning the installation of commercial
gas and/or electrical cooking equipment) then the terms and conditions of the
Manufacturer's Limited Warranty will be rendered void and no warranty of any
kind shall apply.
If the equipment has been changed, altered, modified or repaired by other
than a qualified service technician during or after the 12-month limited
warranty period, then the manufacturer shall not be liable for any incidental or
consequential damages to any person or to any property which may result
from the use of the equipment thereafter. Some States do not allow the
exclusion or 'imitation of incidental or consequential damages, so the above
limitation or exclusion thereto may not apply to you.
In the event you have any question concerning the installation, use, care, or
service of the product, write Customer Service Department, Southbend
Corporation, 1100 Old Honeycutt Rd., Fuquay-Varina, North Carolina 27526.
Congratulations! You have just purchased one of the finest pieces of heavy-duty, commercial cooking equipment on
the market today.
You will find that your new equipment, like all Southbend equipment, has been designed and manufactured to some of
the toughest standards in the industry- those of Southbend Corporation. Each piece of Southbend equipment has
been carefully engineered and designs have been verified through laboratory tests and field installations in some of the
more strenuous commercial cooking applications. With proper care and field maintenance, you will experience years of
reliable, trouble-free operation from your Southbend equipment. To get the best results, it's important that you read this
manual carefully.
TABLE OF CONTENTS:
SECTION ONE— INSTALLATION
SECTION TWO— STEAM FUNCTION
SECTION THREE— COOKING CHART
SECTION FOUR— MAINTENANCE
SECTION FIVE — OPERATION
SECTION SEVEN — PARTS
SECTION EIGHT — WIRING
CAUTION: WATER QUALITY IS THE MAJOR FACTOR AFFECTING THE PERFORMANCE OF YOUR
APPLIANCE. INCOMING WATER HARDNESS SHOULD NOT EXCEED 2.0 PPM GRAINS AND
THE pH SHOULD NOT EXCEED 7.5. IF YOU ARE UNSURE OF WATER CONDITIONS, HAVE
IT ANALYZED. CONSULT YOUR LOCAL WATER DEPARTMENT OR A COMPETENT WATER
CONDITIONER AGENCY. FAILURE OR MALFUNCTION OF THIS APPLIANCE DUE TO POOR
QUALITY OF WATER IS NOT COVERED UNDER THE WARRANTY.
Retain this manual for future reference.
Service Connections ........................................……...............3
Southbend warrants that the equipment, as supplied by the factory to the original purchasers, is free from defects in materials
and workmanship. Should any part thereof become defective as a result of normal use within the period and limits defined
below, then at the option of Southbend such parts will be repaired or replaced by Southbend or its Authorized Service Agency.
This warranty is subject to the following conditions:
If upon inspection by Southbend or its Authorized Service Agency it is determined that this equipment has not been used in an
appropriate manner, has been modified, has not been properly maintained, or has been subject to misuse or misapplication,
neglect, abuse, accident, damage during transit or delivery, fire, "flood, riot or Act of God, then this warranty shall be void.
Specifically excluded under this warranty are claims relating to installation; examples are improper utility connections and
improper utilities supply. Claims relating to normal care and maintenance are also excluded; examples are calibration of
controls, and adjustments to pilots and burners.
Equipment failure caused by inadequate water quality is not covered under warranty. WATER QUALITY must not exceed the
following limits: Total Dissolved Solids (TDS) - 60 PPM (Parts Per Million). Hardness - 2 Grains or 35 PPM, PH Factor
- 7.0 to 7.5. Water pressure 30 PSI minimum, 60 PSI maximum. Boiler maintenance is the responsibility of the owner and is not
covered by warranty.
This equipment is intended for commercial use only. Warranty is void if equipment is installed in other than commercial
application.
Repairs under this warranty are to be performed only by a Southbend Authorized Service Agency. Southbend can not be
responsible for charges incurred from other than Authorized Southbend Agencies. THIS WARRANTY MUST BE SHOWN TO AN
AUTHORIZED SERVICE AGENCY WHEN REQUESTING IN-WARRANTY SERVICE WORK. THE AUTHORIZED SERVICE
AGENCY MAY AT HIS OPTION REQUIRE PROOF OF PURCHASE. This warranty does not cover services performed at
overtime or premium labor rates nor does Southbend assume any liability for extended delays in replacing or repairing any items
in the equipment beyond the control of Southbend. "Southbend shall not be liable for consequential or special damages of any
nature that may arise in connection with such product or part." Should service be required at times which normally involve
overtime or premium labor rates, the owner shall be charged for the difference between normal service rates and such premium
rates. In all circumstances, a maximum of one hundred miles in travel and two and one half hours (25) travel time shall be
allowable. In all cases the closest Southbend Authorized Agency must be used. The actual warranty time periods and exceptions
are as follows:
This warranty only covers product shipped into the 48 contiguous United States and Hawaii, one year labor, one year parts
effective from the date of original purchase. There will be no labor coverage for equipment located on any island not connected
by roadway to the mainland. Exceptions to standard warranty, effective within above limitations:
Glass Windows, Door Gaskets, Rubber Seals, Light Bulbs, Ceramic Bricks,
Sight Glasses, Cathodic Descalers or Anodes ..…......………………………………………...................... 90 days material and labor
Stainless Steel Fry Pot.....................…………….…………………... .4 years extended material warranty on fry pot only — no labor
Stainless Steel Open Top Burners..………….………………...........4 years extended material warranty on burners only — no labor
Pressure Steam Boiler Shell .......…………………………........ Prorated 4 years extended warranty on boiler shell only — no labor
Boiler shells which have not been properly maintained will not be covered by warranty.
In all cases parts covered by a five year warranty will be shipped FOB the factory after the first year. Our warranty on all
replacement parts which are replaced in the field by our Authorized Service Agencies will be limited to three months on labor, six
months on materials (parts) effective from the date of installation. See LIMITED WARRANTY
- REPLACEMENT PARTS for conditions and limitations.
If the equipment has been changed, altered, modified or repaired by other than a qualified service technician during
or after the one year limited warranty period, then the manufacturer shall not be liable for any damages to any person
or to any property which may result from the use of the equipment thereafter.
"THE FOREGOING WARRANTY IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED OR IMPLIED
INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS, AND CONSTITUTES THE ENTIRE
LIABILITY OF SOUTHBEND. IN NO EVENT DOES THE LIMITED WARRANTY EXTEND BEYOND THE DURATION
OF ONE YEAR FROM THE EFFECTIVE DATE OF SAID WARRANTY."
SOUTHBEND – Effective February 1, 1990
INSTALLATION & SERVICE CONNECTIONS
SECTION 1: MODELS: GC-2 & GC-3
FIG. 1
Inches5 ½96216 ½ 4 ½ 18310 ½ 3 ½ 7
mm1382281555331631134577626789178
ABCDEFGHJKL
LEGEND
GC Supply gas through 3/4" pipe with pressure of approx. 7" W.C. For propane use IT'
W.C. pressure. A gas shut off valve must be installed in supply piping convenient
and adjacent to appliance.
EC Unless otherwise specified. Field Wire Electrical Connection to be 120 Volts, 60
Hertz single phase with grounding wire.
DR Appliance drain is 2" pipe size. Provide open air gap type drain.
CW Cold Water supply to Boiler. Provide 3/8" copper tube. A Backflow Prevention Device
acceptable to BOCA Code or equivalent must be installed in this line.
ST Steam take-off locations to supply steam to adjacent units if desired.
2
INSTALLATION
&
SERVICE CONNECTIONS
SECTION 1: MODELS: GC-2 & GC-3
INSTALLATION INSTRUCTIONS
Cooker location should have an exhaust system provided directly above the appliance to exhaust
combustion gases generated by the Gas Boiler.
APPLIANCE IS INTENDED FOR USE ON NONCOMBUSTIBLE FLOORS. MINIMUM CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION, 3" ON SIDES AND2" FROM BACK.
Ascertain that adequate clearance of left side of appliance is available for servicing components
contained in Cooker Control Enclosure.
Set Cooker in place and "level appliance using spirit level. Mark hole locations on floor through anchoring
holes provided in flanged adjustable feet.
Remove appliance and drill holes into locations marked on floor and insert proper anchoring devices. Set
Cooker back in proper position.
Re-level the appliance, leveling the unit left to right and front to back. Appliance should be elevated on
the right 1/16" to 1/8" to assure proper compartment drainage.
Bolt and anchor appliance securely to the floor. Seal bolts and flanged feet with Silastic or equivalent
compound.
SERVICE CONNECTIONS
Make service connections as indicated in LEGEND (Fig. 1).
GAS INSTALLATION TO CONFORM TO LOCAL CODES OR IN THE ABSENCE OF LOCAL CODES TO NATIONAL FUEL
GAS CODE - ANSI Z223.1 - 1980. FURTHER NOTE THAT:
1. THE APPLIANCE AND ITS INDIVIDUAL- SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY
PIPING SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG
(3.45kPa).
2. THE APPLIANCE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL
MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST
PRESSURES EQUAL TO OR LESS THAT 1/2 PSIG (3.45kPa).
ELECTRICAL GROUNDING MUST BE PROVIDED IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF
LOCAL CODES, WITH THE NATIONAL ELECTRIC CODE, ANS1/NFPA 70 - 1981.
3
INSTALLATION & SERVICE CONNECTIONS
SECTION 1: MODELS: GC-2& GC-3
START UP TEST RUN
Open manual gas shut off supply valve and if the appliance has a manual Blow Down Valve, close
it. Open left cabinet door and turn ON power switch. Pilot light will come on (green) and water will
begin to enter Boiler and required water level will be reached in about 3 minutes. Observe water
gauge glass to verify.
The Dial on the gas combination control valve has 3 positions (ON-PILOT-OFF) for manual gas
control of main burners and pilot. Turn Dial on gas combination valve to PILOT. Depress Dial and
light Pilot Burner located on centre main burner of Boiler. Maintain Dial in depressed position for
about 30 seconds and release. Observe that Pilot Burner flame stays on. If at any time the flame
should become extinguished, a 5 minute period for complete shut off of Gas Supply is required
before relighting.
Turn Dial to ON and burners will ignite. Steam generation will now commence and be completed in
about 15 minutes. Observe that Boiler Pressure Gauge indicates steam pressure in range of 9 - 12
psi. The Pressure Gauge on the face of the Cooker Control Panel should indicate pressure of 5 to 6
psi.
Open Cooker compartment door. Dial Timer to 5 minutes and pull out Operating Handle and
observe that steam enters compartment.
With Operating Handle pulled out, dial Timer back to "O". The buzzer will now be audible and must
be silenced by releasing Operating handle. Check each compartment in a similar manner.
Close compartment door and turn Handwheel clockwise sufficiently to provide a good seal on door
gasket. Dial Timer to 5 minutes. Pull out Operating Handle and set in position. Steam entry into
compartment will be audible and Compartment Vent, located at rear left side of Cooker
compartment, will exhaust air (hissing noise) trapped in the compartment until replaced by steam.
Observe that door gasket seals properly and no leaks are evident.
After 5 minutes the Timer will read "0", Buzzer will come on, steam will cease to enter
compartment and drain valve will open to exhaust steam and condensate from compartment.
Release Operating Handle to silence Buzzer.
Observe Appliance Drain that live steam from compartment is being cooled by cold water from Cold
Water Solenoid Valve (thermostatically controlled). Turn Handwheel fully counter-clockwise to
avoid pressure on door gasket when not in use. Check each compartment in a similar manner.
During simulation of the cooking cycle, the Burners will cycle on and off to maintain steam
pressure in Boiler between 9 to 12 psi range.
Turn OFF power switch. Observe that Burners go off and if the appliance is equipped with
Automatic Blow Down Solenoid Valve, the Boiler contents water and steam, will be blown out and
exhausted through the appliance Drain. The Cold Water Solenoid Valve will now be activated as
well. If the appliance is equipped with a manual Blow Down Valve, open it.
4
INSTALLATION & SERVICE CONNECTIONS
SECTION 2: MODELS: GC-2& GC-3
Steamers are made of two sections, the Cooker and the Cabinet. These Steamers are
intended for use in commercial establishments. They are floor supported, are steam
heated and incorporate steel enclosures to contain live electrical parts.
Gas, Power, hot and cold water, must be supplied to these Steamers. Refer to Section 1,
Service Connections.
The Cooker consists of two or three compartments and is the upper portion of the Steamer. Each
compartment is provided with its own Solenoids, Interlock Switches, Timer, Pilot Light, Operating
Handle and Door. When a compartment is off, or de-energized, the Exhaust Solenoid Valve is
open and the inlet Steam Solenoid Valve is closed. Pans, containing food properly portioned, are
placed into guided racks or unto wire shelves provided in each compartment. When the door is
closed, the Timer dialed and the Operating Handle is pulled out to the locked position, (which also
locks the door and engages the Interlock Switches), the valves are energized. Steam reduced to
maximum 6 psi pressure by the Pressure Regulating Valve will then be permitted to enter the
compartment but not exit. Air, captured in the sealed compartment is allowed to exhaust through
the Compartment Vent which will close at approximately 180°F, whence the compartment becomes
an entirely sealed chamber. The duration of the cooking cycle is controlled by the Timer and when
desired time has elapsed. Timer will read '0' and will set off an audible Buzzer and de-energize
valves. Buzzer must be silenced by releasing the Operating Handle and presumably door opened
to remove cooked food. -
The Cabinet is the lower portion of the Steamer and contains components which control the
functioning of the Gas Boiler. A switch located on the front face of the Generator Control Box, when
turned ON will provide power for the appliance and also initiate the Gas Burners to maintain steam
generation in the boiler which in turn supplies steam to the compartment.
The Gas Boiler is designed to ASME Code and approved as a steam heating boiler restricted
to operate at pressures not to exceed 15 psi and the burner system is UL tested and Certified.
Refer to Periodic Maintenance, Section 4, for detailed version of components and controls.
5
PAN SELECTION& TIME SCHEDULES
SECTION 3: MODELS: GC-2& GC-3
COMPARTMENT CAPACITIES
The Cooker compartments are provided with either removable shelf supports with slide out shelves OR
universal pan supports. The following capacities for each compartment are based on full size, 12" x 20",
pans and depths indicated.
Shelf supports with shelving can accommodate:
6 - 2-1/2" deep full size pans or
4 - 4" deep full size pans or
2 - 6" deep and 2 - 2-1/2" deep full size pans.
Universal pan supports can accommodate:
8 - 2-1/2" deep full size pans or
4 - 4" deep full size pans or
2 - 6" deep and 2 - 2-1/2" deep full size pans.
Food placed in pans must, where possible, be evenly spread out and not protrude above pans since
steam circulation between pans in the compartment will be impeded.
Always preheat compartments for satisfactory results.
When a11 compartments are to be used at the same time, allow one compartment to recover steam
pressure (approx. 4-1/2 p.s.i.) before commencing cooking operation on next compartment.
When time does not allow for defrosting of frozen vegetables such as loose pack peas. corn, diced
carrots, etc., they may be cooked at once provided half suggested portions in Cooking Chart are used.
Fig. 2: The Cabinet is the lower section of the Steamer providing not only a base for the Cooker to be positioned at a
proper working height but also the enclosure for the Gas Boiler and Controls.
THE APPLIANCE AREA MUST BE KEPT FREE AND CLEAR FROMCOMBUSTIBLES. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR.
FRONT VIEW
Item A: Gas Boiler weldment assembly.
Item B: Safety Sensor, enclosed by the Sensor Cover Box, is a Boiler protective device which will shut off the Main
Burners when excessive heat occurs should the water level in the Boiler drop below a level sufficient to immerse and
protect the Boiler tubes, heads and shell that come in contact with direct heat from the Burners.
Item C: Handhole Cover Assembly when unbolted and removed allows internal examination and cleaning of Boiler if
required.
AT LEAST TWICE A YEAR REMOVE HANDHOLE COVER ASSEMBLY.
INSPECT BOILER INTERIOR FOR SCALANT AND LIME BUILD UP.
Item D: The Pressure Gauge is directly above and threaded to the Water Level Control. It should read '0' during shut
down and function in a range of approximately 9 to 13 p.s.i. during operation of the appliance.
Item E: The Water Level Control is a mechanical switch intended to maintain proper water level in the Boiler. A Float is
contained within the chamber of the Water Level Control and when it drops, it will trip the switch in the control and
demand sufficient water to replenish it to the proper level.
A MANUAL VALVE LOCATED DIRECTLY BELOW THE WATER LEVEL
CONTROL CHAMBER MUST BE OPENED BRIEFLY AT LEAST ONCE A WEEK
TO BLOWDOWN SEDIMENT AND SCALANT THAT MAY BE LODGED IN THE
CHAMBER. FAILURE TO DO SO MAY CAUSE EXCESSIVE
ACCUMULATION, SEIZURE OF THE FLOAT AND EVENTUAL MALFUNCTION
OF THE WATER LEVEL CONTROL.
Item F: The Water Gauge assembly has a glass tube for visual verification that water level is being maintained in the
Boiler during operation. The manual valves at the top and the bottom of this assembly must be fully open and only
closed if damage should occur to the glass tube.
OBSERVE THAT THE WATER IS CLEAN AND CLEAR IN THE GLASS TUBE.
THE APPEARANCE OF EXTREME MURKINESS IN THE WATER
INDICATES INADEQUATE WATER QUALITY AND WILL CAUSE FAILURE
OF CONTROLS AND THE APPLIANCE. WARRANTY DOES NOT COVER
MALFUNCTION DUE TO POOR WATER CONDITIONS.
9
PERIODIC MAINTENANCE
SECTION 4: MODELS: GC-2& GC-3
Item G: Pilot Burner should remain lit at all times unless appliance will not be in use for an
extended period of time.
IF AT ANY TIKE THE FLAME SHOULD BECOMEEXTINGUISHED. A 5 MINUTE PERIOD FOR COMPLETE SHUTOFF OF GAS SUPPLY IS REQUIRED BEFORE RELIGHTING.
Item H: Main Burners of aluminized steel tube.
FLOOR AREA BENEATH BURNERS MUST BE KEPT FREE AND CLEAR TO PROVIDE AIR FOR COMBUSTION ANDVENTILATION.
Item I: Gas Combination Control Valve regulates flow of natural gas (or propane) to Burners.
Operation is dependent on other controls. Refer to START UP TEST RUN - SECTION 1.
Item J: Cold Water Solenoid Valve fastened to the right rear bottom of Generator Control Box
supplies cold water to condense live steam before it exhausts into the drain and is controlled by the
Thermostat (Item P).
Item K: Hot Water Solenoid Valve fastened to the bottom of Generator Control Box immediately in
Front of Item J feeds hot water to the Boiler but its functioning is entirely dependent on the Water
Level Control (Item E).
Item L: Operating Pressure Switch fastened to the inside bottom front of the Generator Control
Box is plumbed to sense the pressure in the Boiler and thence control the operating cycle of the
Gas Combination Control Valve (Item I). This switch is factory set to energize the Gas Combination
Control Valve and ignite the Main Burners at 9 psi but to de-energize the Valve and turn off
Burners at 11 ½ psi thus maintaining a pressure range in the Boiler between 9 psi to
approximately 13 psi (override considered).
Item M: Override Pressure Switch similar to and located directly behind the above switch senses
steam pressure in excess of the normal operating range which occurs only at initial Start-Up of the
Boiler at approximately 13 psi and thence energizes Solenoid Valve (Item V) to open briefly to
allow for discharge of said excess pressurized steam thence the Boiler becomes stabilized.
Item N: Power Switch fastened to the front fact of the Generator Control Box when switched ON
will automatically begin the steam generating process in the Boiler.
Item O: Pilot Light is located directly above the Power Switch and when lit (green) indicates power
is ON.
Item P: A Thermostat mounted on the back wait of the Generator Control Box has its heat
sensing capillary bulb fastened to the appliance Drain. When excessive heat (i.e. steam) comes in
contact with the bulb, the Thermostat will energize the Cold Water Solenoid Valve (Item J).
10
PERIODIC MAINTENANCE
SECTION 4:MODELS: GC-2 &GC-3
Item Q: Safety Valve is a protective device set at 15 psi. Malfunction or improper setting of controls may allow the
pressure to exceed 15 psi in the Boiler and will consequently set off this valve.
ONCE A WEEK THIS VALVE SHOULD BE TRIPPED DURING OPERATION TO ASSURE THAT IT FUNCTIONS PROPERLY.
LEFT SIDE VIEW
Item R: Pressure Regulator reduces the pressure of the steam supplied from the Boiler to the Steam Header and the
Cooker compartments.
TWICE A YEAR UNSCREW THE LARGE HEX HEAD PLUG LOCATED AT THE BOTTOM OF THE REGULATOR AND REMOVE AND CLEAN THE STRAINER.
Item S: A Thermostatic Steam Trap is plumbed to the steam supply piping from the Boiler and is a mechanical device
that closes on high temperatures and opens when the temperature drops. This Trap allows water formed from
condensed steam to exhaust into the appliance Drain but will retain steam being of a higher temperature.
Item T: Drain for compartments and Boiler approximately 2" pipe size. Must be provided with open air gap type floor
drain.
Item U: Thermostat Capillary Bulb fastened to appliance Drain. Refer to Item P.
Item V: Override Solenoid Valve functions only briefly at initial Start-Up of Boiler and is controlled by override Pressure
Switch (Item M).
Item W: Boiler Blowdown Valve is plumbed to the drain pipe of the Boiler and when specified as automatic will be a
solenoid (electrically operated) valve which will close when energized in order to facilitate maintenance of proper water
level in the Boiler.
HOWEVER. THE STEAMER SHOULD BE SWITCHED OFF AT LEAST ONCE
DAILY WHICH WILL DE-ENERGIZE AND OPEN THE VALVE IN ORDER FOR
THE BLOKDOWN PROCEDURE TO OCCUR AND REMOVE SEDIMENTS.
SCALANTS AND LIME BUILD-UP IN THE BOILER. IF THE APPLIANCE IS
SUPPLIED WITH A MANUAL VALVE. IT SHOULD BE OPENED DAILY WHEN
THE APPLIANCE IS SHUT DOWN.
11
PERIODIC MAINTENANCE
SECTION 4:MODELS: 6C-2 &GC-3
FIG. 3
STEAM
EXHAUST
IN
TO DRAIN
12
Loading...
+ 31 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.