BP 078, 090, 102, 120 and 150
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS
9.3-10.7 EER
®
036-21046-007-A-0405
®
DESCRIPTION
ASHRAE 90.1 COMPLIANT
®
YORK
ages with a common footprint cabinet and common roof curb for
all 6-1/2 through 12-1/2 ton models. The units were designed for
light commercial applications and can be easily installed on a roof
curb, slab, or frame.
All Predator
on rigid full perimeter base rails allowing for 3-way forklift access
and overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
Predator® heat pump units are convertible single pack-
®
heat pump units are self-contained and assembled
All units are convertible between side and down airflow. Independent economizer designs are used on side and down discharge
applications, as well as all tonnage sizes.
Tested in Accordance With:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5COOLING CAPACITY 6-1/2 TON UNIT . . . . . . . . . . .14
6COOLING CAPACITY 7-1/2 TON UNIT . . . . . . . . . . .15
7COOLING CAPACITY 8-1/2 TON UNIT . . . . . . . . . . .16
8COOLING CAPACITY 10 TON UNIT . . . . . . . . . . . . .17
9COOLING CAPACITY 12-1/2 TON UNIT . . . . . . . . . .18
10 HEATING APPLICATION DATA 6-1/2 TON UNIT . . . 19
11 HEATING APPLICATION DATA 7-1/2 TON UNIT . . . 20
12 HEATING APPLICATION DATA 8-1/2 TON UNIT . . . 21
13 HEATING APPLICATION DATA 10 TON UNIT . . . . .22
14 HEATING APPLICATION DATA 12-1/2 TON UNIT . . 23
Dual stage cooling for maximum
comfort (7-1/2 12-1/2 Only)
Compressor #2
Access (High-Eff
Compressor)
Base Rails w/ Forklift Slots (3 Sides)
& Lifting Holes
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
Sunline™ footprint to the
BP series footprint are also
available (field installed
accessory)
network connection
TM
Control
Toolless
Door Latch
Disconnect location
(optional disconnect switch)
Side entry power
and control wiring
knockouts
Filter access
(2” throw-away)
Compressor #1 Access
(High-Eff Compressor)
Filter drier (solid core)
Condenser
section
Slide-out motor and
blower assembly for
easy adjustment and
service.
Belt-drive
blower
motor
Slide-out drain pain
with steel 3/4” NPT,
Female Connection
FIGURE 1 - PREDATOR® COMPONENT LOCATION
FEATURES
•High Efficiency – High efficiency units reach as high as
10.7 EER.
•Service Friendly – The Predator
ber of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilit ates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unauthorized persons. It is recommended that the panels be
secured with screws once service is complete.
Unitary Products Group3
®
incorporates a num-
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
The unit control board utilizes flash codes to aid in diagnosis of unit malfunctions. Unique flash codes quickly
identify the source of the unit alarm.
All units use the same standard filter size. This standardization removes any confusion on which filter sizes
are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing the drain pan cover plate on the rear of the unit.
Once the plate is removed, the drain pan slides out
through the rear of the unit.
®
All Predator
units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
036-21046-007-A-0405
•Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively throughout the units.
•Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
•System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil
frosting when the economizer operates at low outdoor air
temperatures while the compressors are running. Every
unit has solid-core liquid line filter-driers and high and
low-pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors do not require crankcase heaters. Phase Monitors
are standard on units with scroll compressors. This
accessory monitors the incoming power to the unit and
protects the unit from phase loss and reversed phase
rotation.
•Advanced Controls - Simplicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
•Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one ano ther. All
units are programmed with default values based
upon their configuration of cooling and heating.
•Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats and
the temperature limit switch on electric heat units.
The unit control board will alarm on compressor
lockouts and repeated limit switch trips.
•Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
•On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
•Reliable – From the beginning – All units undergo computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. All Predator
®
units
are painted with a long lasting, powder paint that stands
up over the life of the unit. The paint used has been
proven by a 750 hour salt spray test.
•Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size after the internal loads have
been determined.
To further simplify planning and installation, Predator
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
•Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit
and protect the unit during shipment. The rails offer forklift access from 3 sides, and rigging holes are available
so that an overhead crane can be used to place the units
on a roof.
•Easy Installation – Electric utility knockouts are supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a fie ld
supplied electrical disconnect switch. Utility connections
can be made quickly and with a minimum amount of field
labor.
All units are shipped with 2” throw-away filters installed.
•Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle most airflow requirements. For high static applications, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units can
supply nominal airflow at up to 1.5” ESP.
®
4Unitary Products Group
036-21046-007-A-0405
•Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty.
FACTORY INSTALLED OPTIONS
YORK® offers several equipment options factory installed, for
the Predator
•Downflow Economizer - (W ith barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to assemble
and mount the outdoor air hood (Provided). The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air.
As the outdoor air intake dampers open, the return air
dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input
dual dry bulb available. To meet regulated air standards,
the economizer control accepts an optional CO
demand ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit
provides a second input used to monitor the return air.
With a dual input kit installed, the economizer control
compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maximum efficiency possible.
•Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
•BAS Ready Economizer -(With barometric relief) The economizer is provided with a Belimo actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” pleated filters.
•Slab Economizer for Energy Recovery Ventilators- (With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the standard single enthalpy
input. There is an optional input dual dry bulb available.
To meet regulated air stand a r d s , th e economizer control
accepts an optional CO
With single enthalpy input, the economizer control moni-
®
line.
input for
2
input fordemand ventilation.
2
tors outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
•Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
•Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
•Electric Heaters - The electric heaters range from 9kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
•Disconnect Switch - For heat pumps with electric heat,
an HACR breaker sized to the unit is provide d. For heat
pump only units, a switch sized to the largest electric
heat available for the particular unit is provided. Factory
installed option only.
•Convenience Outlet - (Non-Powered /Powered) - This
option locates a 120V single-phase GFCI outlet with
cover, on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source
and wiring. The “Powered” option is powered by a stepdown transformer in the unit. Factory installed option
only.
•Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Avail abl e
for both the supply and/or return air.
•Phase Monitors - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of
phase condition. (Standard on units with Scrol l Com-
pressors.)
•Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
•Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
Unitary Products Group5
036-21046-007-A-0405
•Stainless Steel Drain Pan - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
•T echni coat C ondense r Coil s - The condenser coils are
coated with a phenolic coating for protection against corrosion due to harsh environments.
•Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against corrosion due to harsh environments.
•BAS - Building Automation System Controls Simplic-
ity™ INTELLI-Comfort™ Control - The York® Simplic-
ity™ INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field
installed dirty filter indicator switch, an air-proving switch,
an Outside Air Humidity sensor, a Return Air Humidity
sensor, an Inside IAQ sensor, and an Outside Air IAQ
sensor. Construction mode operation, 365-day real time
clock with 7 day programming plus holiday scheduling is
built-in. Two different modes of demand ventilation are
achieved through the INTELLI-Comfort™ using CO
sensors. It uses an inside CO2 sensor to perform
Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a
Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when
harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection
for hot gas re-heat system. It uses the INTELLI-Start™
algorithm to maximize energy savings by recovering the
building from the Unoccupied Setpoints to the Occupied
Setpoints just in time for the Occupied Time Period to
begin. The Simplicity™ INTELLI-Comfort™ balances
space temperature, ventilation air temperature, CO
and
2
humidity for ultimate comfort.
•Simplicity™ INTELLI-Comfort™ with Mod LinkControl - The York® Simplicity™ INTELLI-Comfort™
with Mod Link control is factory installed. It includes all
the features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
•Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch and air proving switch.
•CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch and air proving switch.
FIELD INSTALLED ACCESSORIES
YORK® offers several equipment accessories for field installation, for the Predator
•Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. T he
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the econo-
2
mizer control accepts an optional CO
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With
a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maximum efficiency possible.
•Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
•Slab Economizer for Energy Recovery Ventilator(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. T he
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer control accepts an optional CO
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With
a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood
for field installations without an ERV.
®
line.
input for demand
2
input for demand
2
6Unitary Products Group
036-21046-007-A-0405
•Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
•Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
•Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief/power exhaust hood when
applying to a horizontal flow application.
•Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
•Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when th e
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
•CO
Sensor - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the
preset limits.
•Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters.
•Coil Guard - Field installed decorative wire coil guard.
•Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
•Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
•Metal Frame Filter Kit - Metal frame with polyester filter
medium.
•Permanent Filters - Permanent filters are available.
•Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8” and 14” heights. For applications with security concerns, burglar bars are available for the duct openings of
the roof curbs.
•Roof Curb Transition - Single Piece Adapter (10” High)
- Roof curbs for transitioning from Sunline™ units to
Predator
®
units. Fits 7.5 to 12.5 Sunline™ roof curbs
only.
•Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
•Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.
Unitary Products Group7
036-21046-007-A-0405
TABLE 1: ACCESSORIES
Part NumberDescriptionWeight
1RC0470Roof Curb, 8" Height1RC0471Roof Curb, 14" Height1RC0472Roof Curb, Transition (7.5 T through 12.5 T) 1BD0408Burglar Bars, Downflow2TP04520925Electric Heat 9kW 230V2TP04521825Electric Heat 18kW 230V2TP04522425Electric Heat 24kW 230V2TP04523625Electric Heat 36kW 230V2TP04525425Electric Heat 54kW 230V2TP04520946Electric Heat 9kW 460V2TP04521846Electric Heat 18kW 460V2TP04522446Electric Heat 24kW 460V2TP04523646Electric Heat 36kW 460V2TP04525446Electric Heat 54kW 460V2TP04520958Electric Heat 9kW 575V2TP04521858Electric Heat 18kW 575V2TP04522458Electric Heat 24kW 575V2TP04523658Electric Heat 36kW 575V2TP04525458Electric Heat 54kW 575V2TP04540925Electric Heat 9kW 230V, 42" Tall Cabinet2TP04541825Electric Heat 18kW 230V, 42" Tall Cabinet2TP04542425Electric Heat 24kW 230V, 42" Tall Cabinet2TP04543625Electric Heat 36kW 230V, 42" Tall Cabinet2TP04540946Electric Heat 9kW 460V, 42" Tall Cabinet2TP04541846Electric Heat 18kW 460V, 42" Tall Cabinet2TP04542446Electric Heat 24kW 460V, 42" Tall Cabinet2TP04543646Electric Heat 36kW 460V, 42" Tall Cabinet2TP04540958Electric Heat 9kW 575V, 42" Tall Cabinet2TP04541858Electric Heat 18kW 575V, 42" Tall Cabinet2TP04542458Electric Heat 24kW 575V, 42" Tall Cabinet2TP04543658Electric Heat 36kW 575V, 42" Tall Cabinet1FA0411Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)1FA0412Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)2MD04702724Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)2MD04703324Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
2EE04705424Economizer, Downflow (Incl. Barometric Relief & All Hoods)124 lbs.
2EE04705524Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)97 lbs.
2EE04705224Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
2EE04705624"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet2PE04703225Power Exhaust, Downflow, 230V (For Units with Economizer only)2PE04703246Power Exhaust, Downflow, 460V(For Units with Economizer only)2PE04703258Power Exhaust, Downflow, 580V (For Units with Economizer only)2EC04700924Dual Enthalpy Control (Use with Single Enthalpy Economizer)1EH0407Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
1RD0411Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
1EH0408Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)25 lbs.
1EH0409Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)2AQ04700424CO2 Detector Unit Mount2AQ04700324CO2 Detector Space Mount2SD04700424Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)1CG0419Coil Guard (Electric / Electric & HP models)1CG0427Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet1HG0411Hail Guard Kit1HG0415Hail Guard Kit, 42" Tall Cabinet1FL0402Permanent Filter (Includes (4) Four Filters)1FL0423Permanent Filter (Includes (4) Four Filters), 42" Tall Cabinet2DF0401Dirty Filter Switch1FF0410Filter Fra me Kit, Metal1FF0411Metal Filter Frame Kit, 42" Tall Cabinet