HIGH EFFICIENCY SINGLE PACKAGE HEAT PUMPS
9.3-10.7 EER
®
036-21046-007-A-0405
®
DESCRIPTION
ASHRAE 90.1 COMPLIANT
®
YORK ages with a common footprint cabinet and common roof curb for all 6-1/2 through 12-1/2 ton models. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame.
All Predator on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
Predator® heat pump units are convertible single pack-
®
heat pump units are self-contained and assembled
All units are convertible between side and down airflow. Indepen­dent economizer designs are used on side and down discharge applications, as well as all tonnage sizes.
Tested in Accordance With:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
TABLE OF CONTENTS
036-21046-007-A-0405
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . 6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . 9
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 50
LIST OF FIGURES
Fig. # Pg.#
1 PREDATOR® COMPONENT LOCATION . . . . . . . . . .3
2 POWER EXHAUST ACCESSORY DOWNFLOW
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
3 POWER EXHAUST ACCESSORY HORIZONTAL
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
4 UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . .42
5 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . .42
6 UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . .42
7 UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . .43
8 HORIZONTAL ECONOMIZER DETAIL . . . . . . . . . . .44
9 DOWNFLOW ECONOMIZER HOOD DETAIL . . . . . . 45
10 PREDATOR® ROOF CURB DIMENSIONS . . . . . . . .45
11 SUNLINE™ TO PREDATOR® TRANSITION ROOF
CURBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
12 BOTTOM DUCT OPENINGS (FROM ABOVE) . . . . . 46
13 REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . . .47
14 6-1/2 TON HEAT PUMP WITH OR WITHOUT
ELECTRIC HEAT WIRING DIAGRAM . . . . . . . . . . . .48
15 7-1/2 - 12-1/2 TON HEAT PUMP WITH OR WITHOUT
ELECTRIC HEAT WIRING DIAGRAM . . . . . . . . . . . .49
LIST OF TABLES
Tbl. # Pg.#
1 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3 BP CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . . .13
4 UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . .13
5 COOLING CAPACITY 6-1/2 TON UNIT . . . . . . . . . . .14
6 COOLING CAPACITY 7-1/2 TON UNIT . . . . . . . . . . .15
7 COOLING CAPACITY 8-1/2 TON UNIT . . . . . . . . . . .16
8 COOLING CAPACITY 10 TON UNIT . . . . . . . . . . . . .17
9 COOLING CAPACITY 12-1/2 TON UNIT . . . . . . . . . .18
10 HEATING APPLICATION DATA 6-1/2 TON UNIT . . . 19 11 HEATING APPLICATION DATA 7-1/2 TON UNIT . . . 20 12 HEATING APPLICATION DATA 8-1/2 TON UNIT . . . 21
13 HEATING APPLICATION DATA 10 TON UNIT . . . . .22
14 HEATING APPLICATION DATA 12-1/2 TON UNIT . . 23
15 ELECTRICAL DATA BP078 (6-1/2 TON) HP W/O
PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 24
16 ELECTRICAL DATA BP078 (6-1/2 TON) HP WITH
PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 24
17 ELECTRICAL DATA BP090 (7-1/2 TON) HP W/O
PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 25
18 ELECTRICAL DATA BP090 (7-1/2 TON) HP WITH
PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 25
19 ELECTRICAL DATA BP102 (8-1/2 TON) HP W/O
PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 26
20 ELECTRICAL DATA BP102 (8-1/2 TON) HP WITH
PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 26
21 ELECTRICAL DATA BP120 (10 TON) HP W/O
POWERED CONVENIENCE OUTLET . . . . . . . . . . . 27
22 ELECTRICAL DATA BP120 (10 TON) HP WITH
POWERED CONVENIENCE OUTLET . . . . . . . . . . . 27
23 ELECTRICAL DATA BP150 (12-1/2 TON) HP W/O
POWERED CONVENIENCE OUTLET . . . . . . . . . . . 28
24 ELECTRICAL DATA BP150 (12-1/2 TON) HP WITH
POWERED CONVENIENCE OUTLET . . . . . . . . . . . 28
25 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . 28
26 6-1/2 TON SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
27 BP090 (7-1/2 TON) SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
28 8-1/2 TON SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
29 10 TON SIDE SHOT BLOWER PERFORMANCE . . . 32 30 12-1/2 TON SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
31 6-1/2 TON DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
32 BP090 (7-1/2 TON) DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
33 8-1/2 TON DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
34 10 TON DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
35 12-1/2 TON DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
36 ADDITIONAL STATIC RESISTANCE 50-3/4"
CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
37 ADDITIONAL STATIC RESISTANCE 42" CABINET . 39
38 ELECTRIC HEAT MINIMUM SUPPLY AIR . . . . . . . . 40
39 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . 40
40 POWER EXHAUST SPECIFICATIONS . . . . . . . . . . . 40
41 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 42
42 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 43
43 UNIT WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
44 UNIT HEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
45 UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . 43
2 Unitary Products Group
036-21046-007-A-0405
Simplicity
board w/screw connec­tors for T-stat wiring and
Terminal block for hi-voltage connection
Second Model Nameplate Inside Control Door
Dual stage cool­ing for maximum comfort (7-1/2 ­12-1/2 Only)
Compressor #2 Access (High-Eff Compressor)
Base Rails w/ Fork­lift Slots (3 Sides) & Lifting Holes
Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from Sunline™ footprint to the BP series footprint are also available (field installed accessory)
network connection
TM
Control
Toolless Door Latch
Disconnect location (optional disconnect switch)
Side entry power and control wiring knockouts
Filter access (2” throw-away)
Compressor #1 Access (High-Eff Compressor)
Filter drier (solid core)
Condenser section
Slide-out motor and blower assembly for easy adjustment and service.
Belt-drive blower motor
Slide-out drain pain with steel 3/4” NPT, Female Connection
FIGURE 1 - PREDATOR® COMPONENT LOCATION
FEATURES
High Efficiency – High efficiency units reach as high as
10.7 EER.
Service Friendly – The Predator ber of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common assembly. This facilit ates greater access to all the indoor airflow components, thus simplifying maintenance and adjustment.
Service time is reduced through the use of hinged, tool­less panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unautho­rized persons. It is recommended that the panels be secured with screws once service is complete.
Unitary Products Group 3
®
incorporates a num-
Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.
The unit control board utilizes flash codes to aid in diag­nosis of unit malfunctions. Unique flash codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This stan­dardization removes any confusion on which filter sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to per­mit easy cleaning. The drain pan is accessed by remov­ing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.
®
All Predator
units have a second model nameplate located inside the control access door. This is to prevent deterioration of the nameplate through weathering.
036-21046-007-A-0405
Environmentally Aware – For improved Indoor Air Quality, foil faced insulation is used exclusively through­out the units.
Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side sup­ply/return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.
System Protection - Suction line freezestats are sup­plied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low-pressure switches. Internal compressor protection is standard on all compressors. Crankcase heaters are standard on reciprocating compressors. Scroll compres­sors do not require crankcase heaters. Phase Monitors are standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.
Advanced Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to 0°F outdoor ambient without additional assis­tance. Optionally, the control board can be pro­grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling fan delay times are independent of one ano ther. All units are programmed with default values based upon their configuration of cooling and heating.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats and the temperature limit switch on electric heat units. The unit control board will alarm on compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip
three times within two hours before the unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
Reliable – From the beginning – All units undergo com­puter automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. All Predator
®
units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 750 hour salt spray test.
Flexible Placement – All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the correct tonnage size after the internal loads have been determined.
To further simplify planning and installation, Predator cabinets are designed to fit your roof. With the optional roof curb, the unit ductwork is designed to fit around 24” on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or the rear of the unit. Additionally, the drain pan can be fitted to drain through the roof curb. As it is sometimes difficult to have a level installation, the drain pan features a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer fork­lift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.
Easy Installation – Electric utility knockouts are sup­plied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a fie ld supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
Wide Range of Indoor Airflows – All indoor fan motors are belt-drive type providing maximum flexibility to han­dle most airflow requirements. For high static applica­tions, factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at up to 1.5” ESP.
®
4 Unitary Products Group
036-21046-007-A-0405
Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty.
FACTORY INSTALLED OPTIONS
YORK® offers several equipment options factory installed, for the Predator
Downflow Economizer - (W ith barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Provided). The econo­mizer has spring return, fully modulating damper actua­tors and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrig­eration to economizer operation is regulated by the stan­dard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional CO demand ventilation. With single enthalpy input, the econ­omizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maxi­mum efficiency possible.
Horizontal Economizer - (Without barometric relief) ­All features of the downflow economizer exist except you must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.
BAS Ready Economizer -(With barometric relief) ­The economizer is provided with a Belimo actuator that requires a 0-10V DC input from an external source (i.e., field installed building automation system controller). Power exhaust options are available. The economizer is 2% low leakage type with spring return and fully modu­lating dampers capable of introducing up to 100% out­side air. Also include 2” pleated filters.
Slab Economizer for Energy Recovery Ventilators- (With barometric relief and Fresh Air Hood) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air stand a r d s , th e economizer control accepts an optional CO With single enthalpy input, the economizer control moni-
®
line.
input for
2
input for demand ventilation.
2
tors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.
Electric Heaters - The electric heaters range from 9kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.
Disconnect Switch - For heat pumps with electric heat, an HACR breaker sized to the unit is provide d. For heat pump only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Convenience Outlet - (Non-Powered /Powered) - This option locates a 120V single-phase GFCI outlet with cover, on the corner of the unit housing adjacent to the compressors. The “Non-powered” option requires the installer to provide the 120V single-phase power source and wiring. The “Powered” option is powered by a step­down transformer in the unit. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. Avail abl e for both the supply and/or return air.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on units with Scrol l Com-
pressors.)
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
Unitary Products Group 5
036-21046-007-A-0405
Stainless Steel Drain Pan - An optional rust-proof stain­less steel drain pan is available to provide years of trou­ble-free operation in corrosive environments.
T echni coat C ondense r Coil s - The condenser coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
BAS - Building Automation System Controls Simplic-
ity™ INTELLI-Comfort™ Control - The York® Simplic- ity™ INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sen­sor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide com­fortable ventilation air temperature. The patented econo­mizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occu­pied space or return duct can be monitored and con­trolled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO
and
2
humidity for ultimate comfort.
Simplicity™ INTELLI-Comfort™ with Mod Link Control - The York® Simplicity™ INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch and air proving switch.
FIELD INSTALLED ACCESSORIES
YORK® offers several equipment accessories for field instal­lation, for the Predator
Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. T he economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the econo-
2
mizer control accepts an optional CO ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit pro­vides a second input used to monitor the return air. With a dual input kit installed, the economizer control com­pares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maxi­mum efficiency possible.
Horizontal Economizer - (Without barometric relief) ­All features of the downflow economizer exist except you must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.
Slab Economizer for Energy Recovery Ventilator­(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. T he economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the econo­mizer control accepts an optional CO ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit pro­vides a second input used to monitor the return air. With a dual input kit installed, the economizer control com­pares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maxi­mum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for field installations without an ERV.
®
line.
input for demand
2
input for demand
2
6 Unitary Products Group
036-21046-007-A-0405
Dual Enthalpy Control, Accessory - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase
1EH0408 barometric relief/power exhaust hood when applying to a horizontal flow application.
Manual Outdoor Air Damper - Like the motorized out- door air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when th e indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
CO
Sensor - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the preset limits.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.
Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. Cooling units include an adapter panel for easy installation of the elec­tric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.
Metal Frame Filter Kit - Metal frame with polyester filter medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security con­cerns, burglar bars are available for the duct openings of the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High)
- Roof curbs for transitioning from Sunline™ units to Predator
®
units. Fits 7.5 to 12.5 Sunline™ roof curbs
only.
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24­volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two­stage heat/two-stage cool or two-stage cooling only ther­mostats, depending upon unit configuration.
Unitary Products Group 7
036-21046-007-A-0405
TABLE 1: ACCESSORIES
Part Number Description Weight
1RC0470 Roof Curb, 8" Height ­1RC0471 Roof Curb, 14" Height ­1RC0472 Roof Curb, Transition (7.5 T through 12.5 T) ­1BD0408 Burglar Bars, Downflow ­2TP04520925 Electric Heat 9kW 230V ­2TP04521825 Electric Heat 18kW 230V ­2TP04522425 Electric Heat 24kW 230V ­2TP04523625 Electric Heat 36kW 230V ­2TP04525425 Electric Heat 54kW 230V ­2TP04520946 Electric Heat 9kW 460V ­2TP04521846 Electric Heat 18kW 460V ­2TP04522446 Electric Heat 24kW 460V ­2TP04523646 Electric Heat 36kW 460V ­2TP04525446 Electric Heat 54kW 460V ­2TP04520958 Electric Heat 9kW 575V ­2TP04521858 Electric Heat 18kW 575V ­2TP04522458 Electric Heat 24kW 575V ­2TP04523658 Electric Heat 36kW 575V ­2TP04525458 Electric Heat 54kW 575V ­2TP04540925 Electric Heat 9kW 230V, 42" Tall Cabinet ­2TP04541825 Electric Heat 18kW 230V, 42" Tall Cabinet ­2TP04542425 Electric Heat 24kW 230V, 42" Tall Cabinet ­2TP04543625 Electric Heat 36kW 230V, 42" Tall Cabinet ­2TP04540946 Electric Heat 9kW 460V, 42" Tall Cabinet ­2TP04541846 Electric Heat 18kW 460V, 42" Tall Cabinet ­2TP04542446 Electric Heat 24kW 460V, 42" Tall Cabinet ­2TP04543646 Electric Heat 36kW 460V, 42" Tall Cabinet ­2TP04540958 Electric Heat 9kW 575V, 42" Tall Cabinet ­2TP04541858 Electric Heat 18kW 575V, 42" Tall Cabinet ­2TP04542458 Electric Heat 24kW 575V, 42" Tall Cabinet ­2TP04543658 Electric Heat 36kW 575V, 42" Tall Cabinet ­1FA0411 Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) ­1FA0412 Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) ­2MD04702724 Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief) ­2MD04703324 Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief) 2EE04705424 Economizer, Downflow (Incl. Barometric Relief & All Hoods) 124 lbs. 2EE04705524 Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief) 97 lbs. 2EE04705224 Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief) 2EE04705624 "Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet ­2PE04703225 Power Exhaust, Downflow, 230V (For Units with Economizer only) ­2PE04703246 Power Exhaust, Downflow, 460V(For Units with Economizer only) ­2PE04703258 Power Exhaust, Downflow, 580V (For Units with Economizer only) ­2EC04700924 Dual Enthalpy Control (Use with Single Enthalpy Economizer) ­1EH0407 Hood Kit, Downflow Economizer (Included with all Downflow Economizers) 1RD0411 Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood) 1EH0408 Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood) 25 lbs. 1EH0409 Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood) ­2AQ04700424 CO2 Detector Unit Mount ­2AQ04700324 CO2 Detector Space Mount ­2SD04700424 Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer) ­1CG0419 Coil Guard (Electric / Electric & HP models) ­1CG0427 Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet ­1HG0411 Hail Guard Kit ­1HG0415 Hail Guard Kit, 42" Tall Cabinet ­1FL0402 Permanent Filter (Includes (4) Four Filters) ­1FL0423 Permanent Filter (Includes (4) Four Filters), 42" Tall Cabinet ­2DF0401 Dirty Filter Switch ­1FF0410 Filter Fra me Kit, Metal ­1FF0411 Metal Filter Frame Kit, 42" Tall Cabinet
-
8 Unitary Products Group
036-21046-007-A-0405
NOMENCLATURE
òò7RQ3UHGDWRU+HDW3XPS0RGHO1XPEHU1RPHQFODWXUH
% 3 &
3URGXFW &DWHJRU\
% +HDW3XPS 6LQJOH3DFNDJH
3URGXFW,GHQWLILHU
3 5+LJK (IILFLHQF\
1RPLQDO&RROLQJ&DSDFLW\0%+
 ò7RQ  ò7RQ  ò7RQ  7RQ  ò7RQ
+HDW7\SH1RPLQDO+HDW&DSDFLW\
& &RROLQJ 2QO\ 6XLWDEOH IRUILHOGLQVWDOOHGHOHFWULF KHDW
( N:(OHFWULF+HDW ( N:(OHFWULF +HDW ( N:(OHFWULF +HDW ( N:(OHFWULF +HDW ( N:(OHFWULF +HDW
%LECTRIC (EAT /P TIO NS
$$
9ROWDJH
     
$$ 
,QVWDOODWLRQ2SWLRQV
$ 1R2SWLRQV ,QVWDOOHG % 2SWLRQ & 2SWLRQ ' 2SWLRQV ( 2SWLRQ ) 2SWLRQ * 2SWLRQV + 2SWLRQV
- 2SWLRQV . 2SWLRQV / 2SWLRQV 0 2SWLRQV  1 2SWLRQV 3 2SWLRQV 4 2SWLRQV 5 2SWLRQV 6 2SWLRQ 7 2SWLRQV 8 2SWLRQV 9 2SWLRQV : 2SWLRQV  ; 2SWLRQV < 2SWLRQV = 2SWLRQV
 'LVFRQQHFW  1RQ3ZU¶G &RQY2XWOHW  6PRNH'HWHFWRU 6$  6PRNH'HWHFWRU 5$  3ZU¶G&RQY2XWOHW
2SWLRQV
3URGXFW*HQHUDWLRQ
 UG*HQHUDWLRQ  WK*HQHUDWLRQ
$GGLWLRQDO2SWLRQV
6HH1H[W3DJH
$LUIORZ
$ 6WDQGDUG 0RWRU % 6WDQGDUG 0RWRU(FRQRPL]HU%DURPHWULF5HOLHI 'RZQIORZRQO\ & 6WDQGDUG 0RWRU(FRQRPL]HU3RZHU([KDXVW'RZQIORZ RQO\ ' 6WDQGDUG0RWRU0RWRUL]HG'DPSHU'RZQIORZRQO\ ( 6WDQGDUG 0RWRU+RUL]RQWDO(FRQRPL]HU1R%DURPHWULF5HOLHI ) 6WDQGDUG0RWRU6ODE(FRQRPL]HU3RZHU([KDXVW 'RZQIORZRQO\ * 6WDQGDUG0RWRU6ODE(FRQRPL]HU%DURPHWULF5HOLHI 'RZQIORZRQO\ / 6WDQGDUG 0RWRU%$65HDG\(FRQ1R%$6&RQWUROOHU%DURPHWULF5HOLHIZ3OHDWHG)LOWHUV'RZQIORZRQO\ 0 6WDQGDUG0RWRU%$6 5HDG\(FRQ1R%$6&RQWUROOHU3RZHU([KDXVWZ3OHDWHG)LOWHUV'RZQIORZRQO\ 1 +LJK6WDWLF0RWRU 3 +LJK6WDWLF0RWRU(FRQRPL]HU%DURPHWULF5HOLHI'RZQIORZRQO\ 4 +LJK 6WDWLF0RWRU(FRQRPL]HU3RZHU([KDXVW'RZQIORZ RQO\ 5 +LJK6WDWLF0RWRU0RWRUL]HG'DPSHU 'RZQIORZRQO\ 6 +LJK6WDWLF0RWRU+RUL]RQWDO(FRQRPL]HU 1R%DURPHWULF 5HOLHI 7 +LJK6WDWLF0RWRU6ODE(FRQRPL]HU3RZHU([KDXVW'RZQIORZRQO\ 8 +LJK6WDWLF0RWRU6ODE(FRQRPL]HU%DURPHWULF5HOLHI'RZQIORZRQO\ < +LJK6WDWLF0RWRU%$6 5HDG\ (FRQ1R%$6&RQWUROOHU%DURPHWULF 5HOLHIZ3OHDWHG)LOWHUV'RZQIORZ RQO\ = +LJK6WDWLF0RWRU%$65HDG\(FRQ 1R%$6&RQWUROOHU3RZHU([KDXVW Z3OHDWHG)LOWHUV'RZQIORZ RQO\
Unitary Products Group 9
036-21046-007-A-0405
NOMENCLA TURE ADDITIONAL OPTIONS
Additional Options
AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor & Coil Guard AF Phase Monitor & Dirty Filter Switch AG Coil Guard & Dirty Filter Switch AH Phase Monitor, Coil Guard, & Dirty Filter Switch AJ SS Drain Pan AK SS Drain Pan & Phase Monitor AL SS Drain Pan & Coil Guard AM SS Drain Pan & Dirty Filter Switch AN SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch CA CPC Controller with Dirty Filter Switch & Air Proving Switch CB CPC Controller, DFS, APS & Phase Monitor CC CPC Controller, DFS, APS & Coil Guard CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard CE CPC Controller, DFS, APS & Technicoat Cond. Coil CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard CJ CPC Controller, DFS, APS & Technicoat Evap. Coil CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard CS CPC Controller, DFS, APS, SS Drain Pan CT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard CU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils CV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil CW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils CX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch JB Johnson UNT Controller, DFS, APS & Phase Monitor JC Johnson UNT Controller, DFS, APS & Coil Guard JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard JS Johnson UNT Controller, DFS, APS, SS Drain Pan JT Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard JU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils JV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil JW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils JX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
10 Unitary Products Group
036-21046-007-A-0405
Additional Options
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard HS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan HT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard HU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils HV Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil HW Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils HX Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils WA Intelli-Comfort w/Mod Link Controller WB Intelli-Comfort w/Mod Link Controller, & Phase Monitor WC Intelli-Comfort w/Mod Link Controller, & Coil Guard WD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard WE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil WF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor WG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard WH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard WJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil WK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor WL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard WM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard WN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils WP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor WQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard WR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard WS Intelli-Comfort w/Mod Link Controller, SS Drain Pan WT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard WU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils WV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil WW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils WX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch NB Novar ETC-3 Controller, DFS, APS & Phase Monitor NC Novar ETC-3 Controller, DFS, APS & Coil Guard ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Unitary Products Group 11
036-21046-007-A-0405
Additional Options
NS Novar ETC-3 Controller, DFS, APS, SS Drain Pan NT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard NU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils NV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil NW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils NX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils LA Simplicity Intelli-Comfort Controller LB Simplicity Intelli-Comfort Controller, & Phase Monitor LC Simplicity Intelli-Comfort Controller, & Coil Guard LD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard LE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil LF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor LG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard LH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard LJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil LK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor LL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard LM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard LN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils LP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor LQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard LR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard LS Simplicity Intelli-Comfort Controller, SS Drain Pan LT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard LU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils LV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil LW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils LX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils TA Technicoat Condenser Coil TB Technicoat Condenser Coil & Phase Monitor TC Technicoat Condenser Coil & Coil Guard TD Technicoat Condenser Coil & Dirty Filter Switch TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch TJ Technicoat Evaporator Coil TK Technicoat Evaporator Coil & Phase Monitor TL Technicoat Evaporator Coil & Coil Guard TM Technicoat Evaporator Coil & Dirty Filter Switch TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch TS Technicoat Evaporator & Condenser Coils TT Technicoat Evaporator & Condenser Coils & Phase Monitor TU Technicoat Evaporator & Condenser Coils & Coil Guard TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch T1 Technicoat Condenser & SS Drain Pan T3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch T4 Technicoat Evaporator & SS Drain Pan T6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch T7 Technicoat Evaporator & Condenser Coils & SS Drain Pan T9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
12 Unitary Products Group
036-21046-007-A-0405
TABLE 2: PHYSICAL DATA
Evaporator Blower
Evaporator Coil
Condenser Fan
(2 per Unit)
Condenser Coil
(2 per unit)
Refrigerant Charge
Compressors
Air Filters
Component
Model
078 090 102 120 150
Blower, Centrifugal (Dia. X Wd. in.) 15x15 12 x 12 15x15 15 x 15 15 x 15
Motor, Standard (HP) 1-1/2 2 2 2 3
Motor, Optional (HP) 2 3 3 3 5
Rows 3 3 3 4 4
Fins per Inch 15 15 15 15 15
Height (in.) 40 32 40 40 40
2
Face Area (ft.
Propeller Dia. (in., each) 24 24 24 24 24
Motor (HP, each) 1/3 1/3 3/4 3/4 3/4
CFM, Nominal (each) 1700 1700 2200 2200 2200
Rows (each) 1 2 2 2 2 Fins per Inch 20 20 20 20 20
Height (in., each) 44 36 44 44 44
Face Area (ft.
System 1 (lb./oz.) 18/0 12/0 13/8 15/4 12/12 System 2 (lb./oz.) N/A 12/0 13/8 15/4 12/12
Size (Wd. x Ht. x Thickness in.) 25x20x2 25x16x2 25x20x2 25x20x2 25x20x2
Number Per Unit 4 4 4 4 4
each)
2
each)
Quantity 1 2 2 2 2
Type Scroll Recip Recip Recip Scroll
13.2 10.6 13.2 13.2 13.2
14.5 11.9 14.5 14.5 14.5
TABLE 3: BP CAPACITY RATINGS
Size
(Tons)
078
(6-1/2)
090
(7-1/2)
102
(8-1/2)
120 (10)
150
(12-1/2)
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb. † Rated in accordance with ARI 270 standard. ‡ See Table 25.
Cooling Capacity ARI Ratings
MBH EER IPLV
78 10.2 N/A 2600 69 3.2 43 2.2 84 9, 18, 24 34
89 10.6 11.08 2635 85 3.2 46 2.2 90 9, 18, 24 34
102 10.3 10.3 3400 100 3.2 56 2.2 90 9, 18, 24 34
120 10.3 10.0 3750 113 3.2 60 2.2 90 18, 24, 34 54
144 9.3 9.7 4750 142 3.1 91 2.1 90 18, 24, 34 54
*
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60
460-3-60 575-3-60
187 252 432 504 540 630
CFM
MBH @
47° F
Heating Capacity
COP @
47°F
MBH @
17°F
COP @
17°F
Sound Rating
(dB)
Nom Elec
Heat Cap
(kW)
Unitary Products Group 13
TABLE 5: COOLING CAPACITY 6-1/2 TON UNIT
Air On
Evap. Coil
WB
CFM
(°F)
72 76.1 6.05 63.7 58.1 52.6 47.0 41.5 - - 73.5 6.65 61.4 55.8 50.3 44.7 39.2 - ­67 70.6 5.87 70.6 70.6 70.0 64.4 58.9 53.3 47.8 67.3 6.47 67.3 67.3 66.6 61.0 55.5 49.9 44.3
1950
62 66.1 5.68 66.1 66.1 66.1 60.6 55.0 49.4 43.9 63.6 6.26 63.6 63.6 63.6 58.0 52.5 46.9 41.4 57 64.6 5.68 64.6 64.6 64.6 59.1 53.5 48.0 42.4 62.2 6.28 62.2 62.2 62.2 56.6 51.0 45.5 39.9 72 84.1 6.26 63.0 56.4 49.8 43.3 36.7 - - 81.2 6.88 61.2 54.6 48.0 41.5 34.9 - ­67 78.0 6.07 74.2 70.4 66.3 59.8 53.2 46.6 40.0 74.4 6.69 71.6 67.8 63.6 57.1 50.5 43.9 37.3
2275
62 73.1 5.87 73.1 73.1 71.7 65.1 58.6 52.0 45.4 70.3 6.47 70.3 70.3 69.4 62.9 56.3 49.7 43.2 57 71.4 5.87 71.4 71.4 71.1 64.5 58.0 51.4 44.8 68.7 6.49 68.7 68.7 67.9 61.3 54.7 48.2 41.6 72 92.1 6.46 62.2 54.7 47.1 39.5 31.9 - - 88.9 7.11 61.0 53.4 45.8 38.2 30.6 - ­67 85.4 6.27 77.8 70.2 62.7 55.1 47.5 39.9 32.3 81.4 6.91 75.8 68.2 60.7 53.1 45.5 37.9 30.3
2600
62 80.0 6.07 80.0 80.0 77.3 69.7 62.1 54.5 46.9 76.9 6.69 76.9 76.9 75.3 67.7 60.1 52.5 45.0 57 78.2 6.06 78.2 78.2 77.6 70.0 62.4 54.8 47.2 75.2 6.71 75.2 75.2 73.6 66.0 58.4 50.8 43.3 72 93.7 6.48 67.6 59.0 50.4 41.7 33.1 - - 91.4 7.13 66.8 58.2 49.5 40.9 32.3 - ­67 86.9 6.28 83.1 75.7 67.1 58.4 49.8 41.2 32.5 83.6 6.93 80.8 74.3 65.6 57.0 48.3 39.7 31.1
2925
62 81.4 6.08 81.4 81.4 80.0 71.4 62.8 54.1 45.5 79.0 6.71 79.0 79.0 78.2 69.6 60.9 52.3 43.7 57 79.6 6.08 79.6 79.6 79.2 70.6 62.0 53.3 44.7 77.2 6.73 77.2 77.2 76.4 67.8 59.2 50.5 41.9 72 95.3 6.49 73.1 63.4 53.7 44.0 34.3 - - 93.8 7.15 72.7 63.0 53.3 43.6 33.9 - ­67 88.3 6.30 88.3 81.2 71.5 61.8 52.1 42.4 32.7 85.9 6.95 85.9 80.3 70.6 60.9 51.2 41.5 31.8
3250
62 82.8 6.09 82.8 82.8 82.8 73.1 63.4 53.7 44.0 81.1 6.72 81.1 81.1 81.1 71.4 61.7 52.0 42.4 57 80.9 6.09 80.9 80.9 80.9 71.2 61.5 51.9 42.2 79.3 6.74 79.3 79.3 79.3 69.6 59.9 50.2 40.5
72 70.4 7.38 58.4 52.8 47.3 41.7 36.2 - - 67.2 8.10 55.4 49.8 44.3 38.7 33.2 - ­67 63.9 7.12 63.9 63.9 63.0 57.5 51.9 46.4 40.8 60.4 7.78 60.4 60.4 59.5 54.0 48.4 42.8 37.3
1950
62 60.9 6.93 60.9 60.9 60.9 55.3 49.8 44.2 38.6 58.2 7.59 58.2 58.2 58.2 52.6 47.1 41.5 35.9 57 59.5 6.95 59.5 59.5 59.5 54.0 48.4 42.8 37.3 56.9 7.63 56.9 56.9 56.9 51.3 45.7 40.2 34.6 72 77.3 7.63 58.8 52.3 45.7 39.1 32.5 - - 73.3 8.37 56.5 49.9 43.3 36.8 30.2 - ­67 70.1 7.36 68.7 65.1 60.9 54.4 47.8 41.2 34.6 65.9 8.04 65.9 62.5 58.2 51.7 45.1 38.5 32.0
2275
62 66.9 7.16 66.9 66.9 65.8 59.3 52.7 46.1 39.6 63.5 7.85 63.5 63.5 62.3 55.7 49.1 42.5 36.0 57 65.3 7.19 65.3 65.3 64.7 58.1 51.5 45.0 38.4 62.0 7.88 62.0 62.0 61.5 54.9 48.3 41.8 35.2 72 84.1 7.87 59.3 51.7 44.1 36.5 28.9 - - 79.4 8.64 57.6 50.0 42.4 34.8 27.2 - ­67 76.4 7.61 73.6 66.4 58.8 51.2 43.6 36.1 28.5 71.4 8.30 71.4 64.5 57.0 49.4 41.8 34.2 26.6
2600
62 72.8 7.39 72.8 72.8 70.8 63.2 55.6 48.1 40.5 68.7 8.10 68.7 68.7 66.3 58.8 51.2 43.6 36.0 57 71.2 7.42 71.2 71.2 69.9 62.3 54.7 47.1 39.5 67.2 8.14 67.2 67.2 66.1 58.5 50.9 43.4 35.8 72 86.3 7.91 64.9 56.3 47.7 39.0 30.4 - - 81.3 8.70 63.0 54.4 45.8 37.1 28.5 - ­67 78.4 7.64 77.0 72.0 63.6 54.9 46.3 37.7 29.0 73.1 8.36 73.1 69.7 61.5 52.9 44.2 35.6 27.0
2925
62 74.7 7.43 74.7 74.7 73.7 65.1 56.4 47.8 39.1 70.4 8.16 70.4 70.4 69.2 60.5 51.9 43.3 34.6 57 73.0 7.46 73.0 73.0 72.3 63.7 55.1 46.4 37.8 68.8 8.19 68.8 68.8 68.3 59.6 51.0 42.3 33.7 72 88.5 7.95 70.6 60.9 51.2 41.5 31.8 - - 83.2 8.76 68.5 58.8 49.1 39.5 29.8 - ­67 80.3 7.68 80.3 77.5 68.3 58.6 48.9 39.2 29.6 74.8 8.42 74.8 74.8 66.0 56.4 46.7 37.0 27.3
3250
62 76.6 7.47 76.6 76.6 76.6 66.9 57.2 47.5 37.8 72.0 8.21 72.0 72.0 72.0 62.3 52.6 43.0 33.3 57 74.8 7.50 74.8 74.8 74.8 65.1 55.5 45.8 36.1 70.4 8.25 70.4 70.4 70.4 60.7 51.0 41.3 31.6
72 64.0 8.82 52.4 46.8 41.3 35.7 30.2 - ­67 57.0 8.44 57.0 57.0 56.0 50.4 44.9 39.3 33.7
1950
62 55.5 8.26 55.5 55.5 55.5 49.9 44.3 38.8 33.2 57 54.2 8.30 54.2 54.2 54.2 48.6 43.1 37.5 32.0 72 69.3 9.12 54.1 47.6 41.0 34.4 27.8 - ­67 61.7 8.72 61.7 59.8 55.5 49.0 42.4 35.8 29.3
2275
62 60.1 8.53 60.1 60.1 58.7 52.1 45.5 38.9 32.4 57 58.7 8.58 58.7 58.7 58.3 51.7 45.1 38.6 32.0 72 74.6 9.41 55.8 48.3 40.7 33.1 25.5 - ­67 66.4 9.00 66.4 62.7 55.1 47.5 40.0 32.4 24.8
2600
62 64.7 8.81 64.7 64.7 61.9 54.3 46.7 39.1 31.5 57 63.2 8.86 63.2 63.2 62.4 54.8 47.2 39.6 32.0 72 76.2 9.49 61.1 52.5 43.9 35.2 26.6 - ­67 67.8 9.08 67.8 67.4 59.5 50.8 42.2 33.5 24.9
2925
62 66.1 8.88 66.1 66.1 64.7 56.0 47.4 38.8 30.1 57 64.6 8.93 64.6 64.6 64.2 55.5 46.9 38.3 29.6 72 77.9 9.56 66.4 56.8 47.1 37.4 27.7 - ­67 69.3 9.15 69.3 69.3 63.8 54.1 44.4 34.7 25.0
3250
62 67.5 8.95 67.5 67.5 67.5 57.8 48.1 38.4 28.7 57 65.9 9.00 65.9 65.9 65.9 56.3 46.6 36.9 27.2
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
Tot.
Cap.
(MBH)
Tot.
*
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
036-21046-007-A-0405
*
Tot.
Cap.
(MBH)
Tot.
*
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
* These capacities are gross ratings. For net
capacity, deduct air blower motor , MBH = 3.415 x kW. Refer to the appropriate Blower Perfor­mance Table for the kW of the supply air blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply air blower motor.
*
14 Unitary Products Group
036-21046-007-A-0405
TABLE 6: COOLING CAPACITY 7-1/2 TON UNIT
Air on Evap-
orator Coil
WB
CFM
(°F)
Total Cap.
(MBH)
Total
*
Input
(kW)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
75°F 85°F
Sensible Capacity (MBH)
Return Dry Bulb (°F)
72 103.7 6.2 58.7 52.3 45.9 39.4 33.0 - - 99.8 6.9 58.4 52.0 45.6 39.2 32.8 - ­67 100.5 6.2 77.4 71.0 64.6 58.2 51.8 45.4 38.9 96.1 6.9 75.6 69.2 62.8 56.4 49.9 43.5 37.1
2550
62 98.1 6.2 98.1 89.7 83.3 76.9 70.5 64.1 57.7 92.3 6.8 92.3 86.8 80.4 74.0 67.6 61.1 54.7 57 95.6 6.2 95.6 94.8 88.3 81.9 75.5 69.1 62.7 90.7 6.8 90.7 89.6 83.2 76.7 70.3 63.9 57.5 72 104.1 6.2 63.0 55.5 47.9 40.3 32.7 - - 100.8 6.9 63.2 55.6 48.1 40.5 32.9 - ­67 100.9 6.2 82.6 75.0 67.5 59.9 52.3 44.7 37.1 97.1 6.9 81.3 73.7 66.2 58.6 51.0 43.4 35.8
2625
62 98.6 6.2 98.6 94.4 87.0 79.5 71.9 64.3 56.7 93.2 6.8 93.2 90.5 84.7 77.2 69.6 62.0 54.4 57 96.0 6.2 96.0 95.6 92.3 84.8 77.2 69.6 62.0 91.6 6.8 91.6 91.1 87.7 80.1 72.5 64.9 57.3 72 104.6 6.2 67.4 58.6 49.9 41.1 32.4 - - 101.9 7.0 68.0 59.3 50.5 41.8 33.0 - ­67 101.3 6.2 87.8 79.1 70.3 61.6 52.8 44.1 35.3 98.1 6.9 87.1 78.3 69.6 60.8 52.1 43.3 34.6
3000
62 99.0 6.2 99.0 99.0 90.7 82.0 73.3 64.5 55.8 94.2 6.9 94.2 94.2 89.1 80.3 71.6 62.8 54.1 57 96.4 6.2 96.4 96.4 96.3 87.6 78.8 70.1 61.3 92.5 6.8 92.5 92.5 92.2 83.4 74.7 65.9 57.2 72 107.0 6.3 71.9 62.0 52.0 42.0 32.1 - - 103.7 7.0 73.0 63.1 53.1 43.1 33.2 - ­67 103.7 6.3 94.3 83.3 73.3 63.4 53.4 43.5 33.5 99.9 6.9 93.0 83.1 73.1 63.1 53.2 43.2 33.2
3375
62 101.3 6.3 101.3 101.3 97.2 87.2 77.2 67.3 57.3 95.9 6.9 95.9 95.9 93.3 83.4 73.4 63.4 53.5 57 98.7 6.3 98.7 98.7 98.6 88.6 78.7 68.7 58.7 94.2 6.9 94.2 94.2 94.0 84.0 74.1 64.1 54.1 72 109.4 6.4 76.5 65.3 54.1 42.9 31.8 - - 105.5 7.0 78.0 66.8 55.7 44.5 33.3 - ­67 106.0 6.4 100.7 87.5 76.3 65.2 54.0 42.8 31.6 101.6 6.9 99.0 87.8 76.6 65.4 54.3 43.1 31.9
3750
62 103.6 6.4 103.6 103.6 103.6 92.4 81.2 70.0 58.9 97.5 6.9 97.5 97.5 97.5 86.4 75.2 64.0 52.8 57 100.9 6.4 100.9 100.9 100.9 89.7 78.5 67.3 56.2 95.8 6.9 95.8 95.8 95.8 84.7 73.5 62.3 51.1
95°F 105°F
72 95.9 7.6 58.2 51.7 45.3 38.9 32.5 - - 89.9 8.1 55.4 48.9 42.5 36.1 29.7 - ­67 91.8 7.5 73.8 67.4 60.9 54.5 48.1 41.7 35.3 83.6 8.1 70.3 63.9 57.4 51.0 44.6 38.2 31.8
2550
62 86.4 7.4 86.4 83.9 77.5 71.0 64.6 58.2 51.8 78.4 8.0 78.4 76.1 69.7 63.3 56.9 50.4 44.0 57 85.7 7.4 85.7 84.4 78.0 71.6 65.1 58.7 52.3 77.5 8.0 77.5 76.3 69.9 63.5 57.0 50.6 44.2 72 97.5 7.6 63.4 55.8 48.2 40.7 33.1 - - 91.9 8.3 61.0 53.4 45.8 38.3 30.7 - ­67 93.3 7.6 80.0 72.4 64.9 57.3 49.7 42.1 34.5 85.5 8.2 76.7 69.5 61.9 54.3 46.7 39.2 31.6
2625
62 87.9 7.4 87.9 86.6 82.4 74.9 67.3 59.7 52.1 80.1 8.2 80.1 79.0 75.1 67.5 59.9 52.3 44.7 57 87.2 7.4 87.2 86.5 83.0 75.4 67.8 60.2 52.7 79.3 8.2 79.3 78.6 75.3 67.7 60.1 52.5 44.9 72 99.2 7.7 68.7 59.9 51.2 42.4 33.7 - - 94.0 8.4 66.6 57.9 49.1 40.4 31.6 - ­67 94.9 7.6 86.3 77.5 68.8 60.0 51.3 42.5 33.8 87.4 8.3 83.1 75.1 66.4 57.6 48.9 40.1 31.4
3000
62 89.3 7.5 89.3 89.3 87.4 78.7 69.9 61.2 52.4 81.9 8.3 81.9 81.9 80.4 71.7 62.9 54.2 45.4 57 88.6 7.5 88.6 88.6 88.0 79.3 70.5 61.8 53.0 81.0 8.3 81.0 81.0 80.6 71.9 63.1 54.4 45.7 72 100.4 7.6 74.1 64.1 54.2 44.2 34.3 - - 95.1 8.4 72.4 62.4 52.4 42.5 32.5 - ­67 96.1 7.6 91.8 82.8 72.8 62.9 52.9 43.0 33.0 88.5 8.3 86.3 80.1 70.8 60.9 50.9 40.9 31.0
3375
62 90.4 7.4 90.4 90.4 89.5 79.5 69.5 59.6 49.6 82.9 8.3 82.9 82.9 82.2 72.2 62.3 52.3 42.3 57 89.7 7.4 89.7 89.7 89.4 79.4 69.5 59.5 49.6 82.0 8.3 82.0 82.0 81.8 71.9 61.9 51.9 42.0 72 101.6 7.6 79.6 68.4 57.2 46.0 34.8 - - 96.3 8.3 78.1 66.9 55.7 44.5 33.4 - ­67 97.2 7.5 97.2 88.1 76.9 65.7 54.5 43.4 32.2 89.6 8.3 89.6 85.0 75.3 64.1 52.9 41.7 30.6
3750
62 91.5 7.4 91.5 91.5 91.5 80.3 69.2 58.0 46.8 83.9 8.2 83.9 83.9 83.9 72.8 61.6 50.4 39.2 57 90.8 7.4 90.8 90.8 90.8 79.6 68.5 57.3 46.1 83.0 8.2 83.0 83.0 83.0 71.8 60.7 49.5 38.3
115°F 125°F
72 83.8 8.7 52.6 46.2 39.7 33.3 26.9 - - 77.8 9.2 49.8 43.4 36.9 30.5 24.1 - ­67 75.5 8.7 66.8 60.4 53.9 47.5 41.1 34.7 28.3 67.3 9.3 63.3 56.9 50.5 44.0 37.6 31.2 24.8
2550
62 70.3 8.7 70.3 68.3 61.9 55.5 49.1 42.7 36.3 62.3 9.3 62.3 60.6 54.1 47.7 41.3 34.9 28.5 57 69.3 8.7 69.3 68.2 61.8 55.4 49.0 42.5 36.1 61.1 9.3 61.1 60.1 53.7 47.3 40.9 34.5 28.0 72 86.3 8.9 58.6 51.0 43.4 35.9 28.3 - - 80.7 9.5 56.2 48.6 41.0 33.4 25.9 - ­67 77.7 8.9 73.3 66.5 59.0 51.4 43.8 36.2 28.6 69.8 9.5 69.8 63.6 56.0 48.4 40.8 33.3 25.7
2625
62 72.4 8.9 72.4 71.4 67.7 60.1 52.5 44.9 37.3 64.7 9.6 64.7 63.8 60.3 52.7 45.1 37.5 29.9 57 71.3 8.9 71.3 70.8 67.5 60.0 52.4 44.8 37.2 63.4 9.6 63.4 62.9 59.8 52.2 44.6 37.1 29.5 72 88.7 9.1 64.6 55.9 47.1 38.4 29.6 - - 83.5 9.8 62.6 53.9 45.1 36.4 27.6 - ­67 79.9 9.1 79.9 72.7 64.0 55.2 46.5 37.7 29.0 72.3 9.8 72.3 70.3 61.6 52.8 44.1 35.3 26.6
3000
62 74.5 9.1 74.5 74.5 73.4 64.7 55.9 47.2 38.4 67.0 9.9 67.0 67.0 66.4 57.7 48.9 40.2 31.4 57 73.3 9.1 73.3 73.3 73.3 64.5 55.8 47.0 38.3 65.7 9.9 65.7 65.7 65.7 57.2 48.4 39.7 30.9 72 89.9 9.1 70.6 60.6 50.7 40.7 30.8 - - 84.6 9.8 68.9 58.9 48.9 39.0 29.0 - ­67 80.9 9.1 80.9 77.3 68.8 58.8 48.9 38.9 29.0 73.3 9.8 73.3 73.3 66.8 56.8 46.9 36.9 26.9
3375
62 75.4 9.1 75.4 75.4 74.9 64.9 55.0 45.0 35.0 67.9 9.9 67.9 67.9 67.6 57.6 47.7 37.7 27.8 57 74.3 9.1 74.3 74.3 74.3 64.3 54.3 44.4 34.4 66.6 9.9 66.6 66.6 66.6 56.7 46.7 36.8 26.8 72 91.0 9.1 76.6 65.4 54.2 43.1 31.9 - - 85.7 9.8 75.1 64.0 52.8 41.6 30.4 - ­67 81.9 9.1 81.9 81.9 73.6 62.5 51.3 40.1 28.9 74.3 9.9 74.3 74.3 72.0 60.8 49.7 38.5 27.3
3750
62 76.4 9.1 76.4 76.4 76.4 65.2 54.0 42.8 31.7 68.8 9.9 68.8 68.8 68.8 57.6 46.4 35.3 24.1 57 75.2 9.1 75.2 75.2 75.2 64.1 52.9 41.7 30.5 67.4 9.9 67.4 67.4 67.4 56.3 45.1 33.9 22.7
* The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blo w er motor.
† These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
*
Total
Cap.
(MBH)
Total
*
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
*
Unitary Products Group 15
TABLE 7: COOLING CAPACITY 8-1/2 TON UNIT
Air On
Evap. Coil
WB
CFM
(°F)
72 109.7 8.06 66.4 59.1 51.8 44.5 37.3 - - 108.8 8.75 65.1 57.9 50.6 43.3 36.1 - ­67 104.5 7.96 83.8 76.6 69.3 62.0 54.7 47.5 40.2 100.8 8.61 82.6 75.3 68.0 60.8 53.5 46.2 39.0
2550
62 105.0 7.97 84.3 77.1 69.8 62.5 55.2 48.0 40.7 93.4 8.40 93.4 90.2 82.9 75.6 68.4 61.1 53.8 57 95.9 7.86 95.9 95.9 89.2 81.9 74.6 67.4 60.1 93.6 8.44 93.6 92.3 85.0 77.7 70.4 63.2 55.9 72 112.6 8.10 72.4 63.8 55.2 46.6 38.1 - - 112.1 8.83 71.7 63.1 54.5 45.9 37.4 - -A 67 107.3 8.00 91.0 82.5 73.9 65.3 56.7 48.1 39.5 103.8 8.68 90.5 81.9 73.3 64.7 56.1 47.6 39.0
2975
62 107.7 8.01 91.6 83.0 74.4 65.8 57.2 48.6 40.0 96.2 8.47 96.2 94.6 89.3 80.8 72.2 63.6 55.0 57 98.4 7.90 98.4 98.4 95.1 86.5 77.9 69.3 60.7 96.4 8.51 96.4 95.7 91.6 83.0 74.4 65.8 57.2 72 115.5 8.14 78.5 68.6 58.7 48.7 38.8 - - 115.3 8.90 78.3 68.4 58.5 48.6 38.6 - ­67 110.0 8.04 98.3 88.4 78.4 68.5 58.6 48.7 38.8 106.8 8.76 98.5 88.5 78.6 68.7 58.8 48.9 39.0
3400
62 110.5 8.05 98.8 88.9 79.0 69.1 59.2 49.3 39.3 99.0 8.55 99.0 99.0 95.8 85.9 76.0 66.1 56.1 57 100.9 7.94 100.9 100.9 100.9 91.0 81.1 71.2 61.3 99.2 8.58 99.2 99.2 98.2 88.3 78.4 68.5 58.5 72 118.2 8.16 84.6 73.4 62.1 50.8 39.5 - - 118.2 8.97 84.4 73.1 61.8 50.5 39.2 - ­67 112.6 8.06 105.6 94.3 83.0 71.7 60.4 49.1 37.8 109.5 8.83 105.3 94.4 83.1 71.8 60.5 49.2 37.9
3825
62 113.1 8.07 106.2 94.9 83.6 72.3 61.0 49.7 38.4 101.4 8.61 101.4 101.4 99.8 88.5 77.2 65.9 54.7 57 103.3 7.96 103.3 103.3 103.3 92.0 80.7 69.4 58.1 101.6 8.65 101.6 101.6 101.2 89.9 78.6 67.3 56.0 72 120.9 8.18 90.8 78.1 65.5 52.8 40.1 - - 121.0 9.05 90.5 77.8 65.1 52.4 39.8 - ­67 115.2 8.09 112.9 100.2 87.5 74.9 62.2 49.5 36.9 112.1 8.90 112.1 100.2 87.5 74.9 62.2 49.5 36.9
4250
62 115.7 8.09 113.5 100.8 88.2 75.5 62.8 50.2 37.5 103.8 8.68 103.8 103.8 103.8 91.2 78.5 65.8 53.2 57 105.7 7.98 105.7 105.7 105.7 93.0 80.3 67.7 55.0 104.1 8.72 104.1 104.1 104.1 91.4 78.8 66.1 53.4
72 103.1 9.45 63.0 55.7 48.5 41.2 33.9 - - 97.4 10.15 60.9 53.6 46.3 39.1 31.8 - ­67 93.5 9.21 79.6 72.3 65.1 57.8 50.5 43.3 36.0 86.1 9.81 76.6 69.4 62.1 54.8 47.6 40.3 33.0
2550
62 86.8 9.00 86.8 84.4 77.1 69.8 62.6 55.3 48.0 80.1 9.61 80.1 78.6 71.3 64.0 56.8 49.5 42.2 57 85.3 9.04 85.3 84.4 77.1 69.8 62.6 55.3 48.0 77.0 9.64 77.0 76.5 69.2 62.0 54.7 47.4 40.2 72 106.6 9.53 69.9 61.3 52.7 44.1 35.5 - - 101.1 10.23 68.0 59.5 50.9 42.3 33.7 - ­67 96.6 9.28 87.6 79.4 70.8 62.2 53.6 45.0 36.4 89.4 9.89 84.6 76.8 68.2 59.6 51.0 42.4 33.8
2975
62 89.7 9.08 89.7 88.5 83.8 75.2 66.6 58.0 49.5 83.1 9.68 83.1 82.4 78.3 69.7 61.1 52.5 43.9 57 88.2 9.11 88.2 87.7 83.8 75.2 66.6 58.0 49.4 79.9 9.72 79.9 79.7 76.0 67.4 58.8 50.2 41.6 72 110.0 9.61 76.8 66.9 56.9 47.0 37.1 - - 104.7 10.31 75.2 65.3 55.4 45.5 35.6 - ­67 99.7 9.36 95.5 86.4 76.5 66.5 56.6 46.7 36.8 92.6 9.96 92.6 84.2 74.3 64.4 54.5 44.5 34.6
3400
62 92.6 9.15 92.6 92.6 90.5 80.6 70.7 60.8 50.9 86.2 9.76 86.2 86.2 85.3 75.4 65.5 55.6 45.6 57 91.0 9.19 91.0 91.0 90.5 80.6 70.7 60.8 50.8 82.8 9.80 82.8 82.8 82.8 72.9 63.0 53.1 43.1 72 112.8 9.67 83.2 71.9 60.6 49.3 38.0 - - 107.4 10.37 81.9 70.6 59.3 48.1 36.8 - ­67 102.2 9.43 100.1 92.6 81.3 70.0 58.7 47.5 36.2 95.0 10.03 95.0 90.8 79.6 68.3 57.0 45.7 34.4
3825
62 94.9 9.22 94.9 94.9 93.9 82.6 71.3 60.0 48.7 88.4 9.82 88.4 88.4 88.0 76.7 65.4 54.1 42.8 57 93.3 9.25 93.3 93.3 93.1 81.8 70.5 59.2 47.9 85.0 9.86 85.0 85.0 85.0 73.7 62.4 51.1 39.8 72 115.6 9.74 89.5 76.9 64.2 51.5 38.9 - - 110.2 10.44 88.6 76.0 63.3 50.6 38.0 - ­67 104.8 9.49 104.8 98.8 86.2 73.5 60.9 48.2 35.5 97.4 10.09 97.4 97.4 84.9 72.2 59.5 46.8 34.2
4250
62 97.2 9.28 97.2 97.2 97.2 84.6 71.9 59.2 46.6 90.6 9.88 90.6 90.6 90.6 78.0 65.3 52.6 39.9 57 95.6 9.32 95.6 95.6 95.6 82.9 70.3 57.6 44.9 87.1 9.92 87.1 87.1 87.1 74.4 61.8 49.1 36.4
72 91.7 10.85 58.7 51.5 44.2 36.9 29.6 - ­67 78.8 10.41 73.7 66.4 59.1 51.9 44.6 37.3 30.1
2550
62 73.5 10.21 73.5 72.8 65.5 58.3 51.0 43.7 36.4 57 68.7 10.24 68.7 68.6 61.4 54.1 46.8 39.5 32.3 72 95.6 10.93 66.2 57.6 49.0 40.4 31.8 - ­67 82.2 10.49 81.7 74.2 65.6 57.0 48.4 39.8 31.3
2975
62 76.6 10.29 76.6 76.3 72.8 64.2 55.6 47.0 38.4 57 71.7 10.32 71.7 71.6 68.2 59.6 51.0 42.5 33.9 72 99.4 11.01 73.7 63.8 53.9 44.0 34.0 - ­67 85.5 10.57 85.5 82.0 72.1 62.2 52.3 42.4 32.5
3400
62 79.8 10.37 79.8 79.8 79.8 70.1 60.2 50.3 40.4 57 74.6 10.40 74.6 74.6 74.6 65.2 55.3 45.4 35.4 72 102.1 11.07 80.7 69.4 58.1 46.8 35.5 - ­67 87.8 10.62 87.8 87.8 77.8 66.5 55.2 43.9 32.6
3825
62 81.9 10.42 81.9 81.9 81.9 70.7 59.4 48.2 36.9 57 76.6 10.46 76.6 76.6 76.6 65.6 54.3 43.0 31.7 72 104.7 11.13 87.7 75.0 62.4 49.7 37.0 - ­67 90.1 10.68 90.1 90.1 83.5 70.8 58.2 45.5 32.8
4250
62 84.0 10.48 84.0 84.0 84.0 71.3 58.7 46.0 33.3 57 78.6 10.51 78.6 78.6 78.6 65.9 53.3 40.6 27.9
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
Tot.
Tot.
Cap.
(MBH)
*
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
036-21046-007-A-0405
*
Tot.
Cap.
(MBH)
*
Tot.
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
* These capacities are gross ratings. For net
capacity, deduct air blower motor , MBH = 3.415 x kW. Refer to the appropriate Blower Perfor­mance Table for the kW of the supply air blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply air blower motor.
*
16 Unitary Products Group