8
HARDWIRE INSTALLATION
The alarm base plate is designed to be permanently mounted, using its own built-in terminal block to
connect it to the mains. The base plate can be screwed directly to the ceiling.
• IMPORTANT: The circuit used to power the alarm must be a 24 hour voltage circuit that cannot
be turned off by a switch. BS 5839: Part 6 states that: For mains powered alarms, each with an
integral standby supply (Grade D), the mains electricity supply should take the form of either
a) an independent circuit at the dwelling’s main circuit board, in which case no other electrical
equipment should be connected to this circuit (other than a dedicated monitoring device installed
to indicate failure of the mains electricity supply to the alarms); or b) a separately electrically
protected, regularly used local lighting circuit.
• Ensure a permanent connection to the xed wiring of the building is made in a suitable
junction box.
• Remove the terminal block cover.
• If trunking is required, snap the break-out tab away from the base plate prior to connection.
• The wiring must be connected to the terminal block as follows:
Live (L) - Connect to the Live in the house wiring.
Neutral (N) - Connect to the Neutral in the house wiring.
Interconnect (I) - If desired, join the Interconnect wire between the alarms.
• Use the
terminal to safely terminate any copper Earth or green / yellow cable.
×
DO NOT:
• Install the alarms within 1500 mm (1.5 m) of a uorescent light tting and keep wiring at least
1000 mm (1 m) from these ttings.
• Install alarms on circuits containing uorescent light ttings or dimmer switches.
• Install alarms within 300 mm (12”) of light ttings or room corners.
• Install smoke alarms in wall positions that are less than 100 mm (4”) or more than 300 mm (12”)
away from the ceiling.
• Locate the Thermoptek smoke alarm close to bathrooms or showers as it can be susceptible to
nuisance alarms from steam.
• Install heat alarms on a wall.