SOLUTIONS FOR COMMERCIAL BUILDINGS
installation guide
Power Supply 320 mA
animeo Solo animeo IB+ animeo KNX animeo LON
KNX Power Supply with integrated choke. Worldwide usable due to
wide range input 100 - 240 V AC. LED indicator for Power, Overload
and Reset. Push button for automatic reset on the KNX line. Additional auxiliary voltage output with 30 V DC. Nominal current on
the short circuit protected outputs is 320 mA.
Technical features:
• Wide range input 100 to 240 V AC / 50-60 Hz
• Integrated KNX choke
• Integrated KNX reset function for choked output
• Short circuit protection
• Status LEDs for Power, Overload and Reset
35
45
62
91
71
Power
Overload
Reset
KNX
30 V DC
L N PE
+
_
+
_
62
Ref. 9018244
© 2013, SOMFY SAS . ALL RIGHTS RESERVED . REF. 5115194A – 2013/10/31
SOMFY, 50 avenue du Nouveau Monde, 74300 Cluses Cedex, France - www.somfy-architecture.com
CHaRaC teRistiCs
Supply voltage
100-240 V AC / 50/60 Hz
Output voltage
30 V DC (28-31 V DC according to KNX specification)
Output voltage not choked
30 V DC
Nominal current
320 mA
Terminals
Screw terminal KNX bus terminal/auxilary voltage terminal
max. 2,5 mm
2
cross section ∅ 0,6 - 0,8 mm
Ambient temperature
- 5
° C to + 50 ° C
Protection class
IP 20
Mounting
DIN rail
Dimensions
71 x 91 x 62 mm (w x h x d), 4 modules
Conformity
www.somfy.com/ce

SOLUTIONS FOR COMMERCIAL BUILDINGS
• The device may only be installed and connected by trained electricians, in accordance with the current KNX guidelines and the
country-specific regulations.
• At the planning and construction of electrical plants, the relevant standards, guidelines, rules and regulations of each country
must be observed.
• After installing the device and turning on the power supply, voltage is present at the outputs.
• Device should not be operated outside of the specific technical data.
• During transport, storage and operating the device must be protected from moisture, dirt and damage.
• Only operate in closed case. Don’t impede cooling.
• Device only ground at the dedicated terminals.
Only suitable for fixed installation on DIN-rail distribution boards or in small housings. Installation only in dry rooms.
1. Attach power supply on a DIN-rail
2. Connect power supply on the KNX bus
3. Connect power supply to the supply voltage
4. Switch on the supply voltage
5. After connecting the power supply, the device is ready for operation
LED display Power (green) Operable
LED display Overload (orange) Overload on KNX bus
LED display Reset (red) Reset of KNX bus is running
Button Reset Set up Reset of KNX bus
Power
Overload
Reset
KNX
30 V DC
L N PE
+
_
+
_
N
L1
L2
L3
KNX Bus
+
_
30 V DC
+
_
ConneC tion and install ation
safe t y guidelines
© 2013, SOMFY SAS . ALL RIGHTS RESERVED . REF. 5115194A – 2013/10/31
SOMFY, 50 avenue du Nouveau Monde, 74300 Cluses Cedex, France - www.somfy-architecture.com
Power Supply 320 mA
animeo Solo animeo IB+ animeo KNX animeo LON