Green Power Function
Ultima UPS is equipped with green power function. For saving power and protecting
battery, this method of deep discharging protection is adopted on inverter mode.
Free power monitoring software on CD
• Choose the operation system you need and follow the instructions described on the
CD to install the sof tware.
Note: If you nd the communication unsuccessful after monitoring software installation,
you have to switch the Auto Search on and you can only do that if you go into 'Act as
Administrator'. Once selec ted, the software will hunt for and nd the UPS.
Note: The power switch must be kept in the ‘ON’ position, otherwise, the UPS will be
disabled and your equipment will not be protected during a power failure.
Note: If you change your UPS model, please ensure you uninstall and reinstall the Software.
Troubleshooting guide:
©Sollatek (UK) Limited 1996 All Rights Reserved. SOLLATEK and the SOLLATEK device are the trade marks of the Sollatek group of companies.
Sollatek (UK) Ltd.
Unit 10, Poyle 14 Industrial Estate, Newlands Drive, Horton Road, Poyle, Slough, Berkshire SL3 0DX, UK
Tel: +44 (0) 1753 688300
Fax: +44 (0) 1753 685306
Technical support: support@sollatek.com
Sales: sales@sollatek.com
www.sollatek.com
Rev. no. 1.0 April 07.
Problem Possible Cause Solution
No LED display on the front panel. 1. Battery weak. 1. Re-charge battery up to 8 hours.
2. Battery defect. 2. Replace with the same type of battery.
3. Power switch is not pressed. 3. Press the power switch again.
Alarm buzzer beeps continuously when AC supply is normal. UPS overload. Verify that the load matches the UPS capability specied in the
specs.
When power failure, back-up time is shortened. 1. Overload of the UPS. 1. Remove some noncritical load.
2. Battery voltage is too low. 2. Charge battery 8 hours or more.
3. Battery defect due to high temperature
operation environment, or improper
operation to battery. 3. Replace with the same type of battery.
Communication lost between UPS and computer 1. Software is not properly installed. 1. Check the setting of the software.
2. Interface cable is not properly connected. 2. Check the interface cable is properly connected to the COM1/COM2 of
the computer and conrm the setting again.
Mains normal bottom but UPS is not working. 1. Fuse is blown. 1. Replace with the same type of fuse.
2. Power cord is loose. 2. Reconnect the power cord properly.
Proper care of batteries
• Do not subject the battery to heavy vibration or mechanical shock.
• When you receive a new battery, charge fully before use.
• Full capacity will be reached after 2 or 3 full charge/discharge cycles.
• To obtain maximum life, always store batteries in a charged state.
• When storing batteries, re-charge every 6 months to prevent damage through self
discharge. This should be done more often if storage temperature exceeds 25ºC.
• Try to store / use in a cool, dry place. Do not expose to excessive hot
or cold (i.e. outside the range 10-35°C ambient temp).
• To prolong battery life, try to avoid the complete discharge
of your battery before recovery charge.
• Do not discharge a battery deeper than you have to.
• Do not attempt to dismantle a battery. They do not require topping up.
• Do not incinerate batteries. Always recycle old batteries.
• To avoid the risk of shock, do not touch the terminals.
• Keep terminals free from dirt and corrosion.
• Do not short the connections.
• Always charge in a ventilated area.
• Always use a suitable charging device. If unsure, contact your distributor.
• Replace only with Sollatek recommended replacement batteries.
If unsure, contact your distributor.
MODEL Ultima 400 Ultima 600 Ultima 800
CAPACITY VA/W 400VA/240W 600VA/360W 800VA/480W
INPUT Voltage 120VAC or 220/230/240VAC
Voltage range 85-140VAC or 162-290VAC
Frequency 45-65 Hz (auto sensing)
OUTPUT Voltage 120/220/230/240VAC
Voltage regulation
(batt. mode) +/-10%
Frequency 50Hz or 60Hz
Frequency regulation
(batt. mode) +/-1 Hz
Output waveform modified sinewave
BATTERY Battery type 12V 4.5Ah x 1 12V7Ah x 1 12V9Ah x 1
Recharge time 8 hours to 90% after complete discharge
TRANSFER TIME Typical 2-6 ms
INDICATOR AC mode green lighting
Backup mode green flashing
AUDIBLE ALARM Backup mode sounding every 10 seconds
Low battery sounding every second
Overload sounding every 0.5 second
Battery replacement sounding every 2 seconds
Fault continuously sounding
PROTECTION Full protection discharge, overcharge, and overload protection
PHYSICAL Dimension (mm),
D x W x H 330 x 100 x 140
WEIGHT Net weight 5kgs 6kgs 6.5kgs
ENVIRONMENT Operating
environment 0- 40°C, 0-90 % relative humidity
(non-condensing)
Noise level Less than 40dB
INTERFACE RS-232 Windows, Sun Solaris, IBM Aix, Compaq True64, UnixWare, FreeBSD, HP-UX, Linux, MAC
USB Windows 98/2000/ME/XP
Specifications
CHARGE THE UPS AT LEAST 8 HOURS BEFORE USE, ENSURING
THE BATTERY LEVEL INDICATOR IS FULL
Battery replacement
WARNING: Disconnect all sources of supply before replacing battery.
1. TURN UPS UNIT UPSIDE
DOWN
Locate 4 screws on underside
of UPS unit, and remove.
2. RETURN UPS UNIT TO ITS CORRECT POSITION.
The top half of the casework will now lift off.
The front fascia will now hinge down, revealing battery.
Gently pull out the battery. Disconnect the two wires
that are connected to the UPS. To reassemble the fascia ,
ensure the 2 lugs are located correctly.
Replacement battery installation is the reversal of this
procedure.
Ensure the wires on the battery are connected back
exactly the way they were connected originally.
Caution! UPS may get damaged if these wires are
connected incorrectly - if in doubt, contact Sollatek.
• Replace only with Sollatek recommended replacement batteries.
If unsure, contact your distributor.
2 lugs
Ultima battery back-up times (in minutes)
200VA 300VA 400VA 600VA 800VA 1000VA 1200VA 1400VA 1600VA 1800VA
Ultima 400 8 <3 <1
Ultima 600 15 8 <5 <1
Ultima 800 22 12 8 <3 <1
TM
t he po we r t o pr o te c t