Sollatek ULTIMA 1000, ULTIMA 2000, ULTIMA 1400 User Instructions

Sollatek ULTIMA 1000, 1400, 2000 Uninterruptible Power Supply
USER INSTRUCTIONS
Important safety instructions
WARNING!
IMPORTANT: UPON RECEIPT THE UPS SHOULD BE CONNECTED TO THE MAINS AND ALLOWED TO CHARGE ITS BATTERY FOR AT LEAST EIGHT HOURS BEFORE IT CAN BE EFFECTIVELY USED AS A BACKUP SYSTEM.
• This UPS utilises voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user ser viceable parts. Only factory service personnel may perform repairs.
• Internal battery voltage is 12Vdc. Sealed, lead-acid, 6 cells battery.
• Connection to any other type of receptacle other than a two-pole, three-wire grounded receptacle may result in shock hazard as well as violate local electrical codes.
• In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.
• Do not allow liquids or any foreign objects to enter the UPS. Do not place beverages or any other liquid- containing vessels on or near the unit.
• This unit is intended for installation in a controlled environment (temperature controlled, indoor area free of conductive contaminants). Avoid installing the UPS in locations where there is standing or running water, or excessive humidity.
• Do not plug the UPS input into its own output.
• Do not attach a power strip or surge suppressor to the UPS.
• Do not attach non-computer-related items, such as medical equipment, laser printers, life-support equipment, microwave ovens, or vacuum cleaners to the UPS.
• To reduce the risk of overheating the UPS, do not cover the UPS’ cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.
• Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
• Do not dispose of batteries in a re as they may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
• A battery can present a risk of electrical shock and high short circuit current. The following precautions should be obser ved when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal par ts on top of batteries.
5) Disconnec t charging source prior to connecting or disconnecting batteries terminals.
• Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorised personnel away from batteries.
• When replacing batteries, replace with the same number and type of sealed lead-acid battery. The maximum ambient temperature rating is 40˚.
• This pluggable type A equipment with battery already installed by the supplier is operator installable and may be operated by laymen.
• During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connec ted loads does not exceed 3.5mA.
• Attention: hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage may still be accessible through supply from battery. The battery supply should therefore be disconnected in the plus and minus pole of the battery when maintenance or service work inside the UPS is necessary.
• The mains socket outlet that supplies the UPS should be installed near the UPS and should be easily accessible.
• Electrical Energy Hazard: The battery pack contains HIGH ENERGY. To reduce the risk of electric shock, use caution when you handle and interconnect the units.
• If operating the UPS while it is unplugged from the source of electrical power, DO NOT make contact with the line cord input pins. Electrical shock hazard exists.
• To reduce the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants.
• DO NOT plug laser printers into a UPS. The high surge currents they produce can disrupt any
manufac turer’s UPS.
Introduction
The Ultima is a multi-functional UPS and specially designed for a personal computer. Its light weight and compact design perfectly ts within a limited working environment. The Ultima UPS is equipped with boost and buck AVR to stabilise the input voltage range. It is also has built-in DC start function to enable the UPS to be started up without AC power supplied. Despite its compact dimensions, the UPS is equipped with Smart RS-232 and USB communication ports to oer users more exibility of connection. The power monitoring software helps users monitor the status of the UPS.
The main features of Ultima UPS are listed below:
Features
• Microprocessor controlled line interactive UPS.
• Automatic Voltage Stabiliser with two boost and one buck taps.
• RS232 and USB communication ports with software for controlling the PC for safe shutdown and
UPS parameter reporting via user friendly interface.
• Unique system for charging battery even during a brown out (If the load is off).
• Short circuit and overload protection.
• Cold start feature for load shedding environments.
• Bad battery detection and advance replacement notification (3 months ahead).
• Free power monitoring and PC shutdown software included.
• Green power function for energy saving.
• DC start function.
• Auto restart while AC recovery.
• Compact size and light weight.
• Provides modem/phoneline surge protection.
Installation
Safety precautions
Please read this manual fully before installing and operating the UPS. Keep the manual in a safe place as it includes important information about installation, maintenance and troubleshooting. Under no circumstances should the cover be removed as dangerous voltages can be produced even when the UPS is not connected to mains.
Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.
Placement
Install the UPS unit in any protected environment that provides adequate airow around the unit, and is free from excessive dust, corrosive fumes and conductive contaminants. Do not operate your UPS in an environment where the ambient temperature or humidity is high. Place the UPS away from the monitor at least 20cm to avoid interference.
Charging
This unit is shipped from the factory with its internal battery fully charged. However, some charge may be lost during shipping and the battery should be recharged prior to use. Plug the unit into an appropriate power supply and allow the UPS to charge fully by leaving it plugged in for at least 8 hours with no load (no electrical devices such as computers, monitors, etc.) connected.
Load connection
Connect the loads (PC etc.) to the sockets on the rear panel of the UPS before connecting the UPS to the mains. The UPS can be used as a master on/off switch for all the connected loads. If this is desired, the loads should be left switched on. Never connect a laser printer to the UPS as damage may result.
Connect to mains
Connect the UPS to the mains using the mains cable supplied with your PC or monitor. A mains IEC cable is not provided with the UPS but can be ordered separately.
Turn on/off
To turn on the UPS unit, press the power switch lightly. To turn off the UPS unit, press the power switch again.
Data line surge suppression (optional)
Connect the incoming telephone cable from the wall socket to the Comms Surge Protection IN socket. Using a telephone cable, connect Comms Surge Protection OUT socket to your PC modem.
DC Start
All Ultima Series are equipped with DC Start. To start the UPS when AC utility power is not available, simply press the power switch. Continued overleaf
Functional Description
RS232
Comm Port
Modem/
phone line surge protection
Four IEC-320 Receptacles
Telecom
inlet
VDU
CPU
Mains
inlet
Modem
AC Input
Circuit
breaker
Cooling fan
1400/2000va
Fault LED
In AC Mode: Present Load Level In Backup Mode: Present Battery Capacity
In AC Mode: Green Light on Backup Mode: Green Flashing
Power “ON/OFF” Switch
20cm
USB port
CHARGE THE UPS AT LEAST 8 HOURS BEFORE USE, ENSURING THE BATTERY LEVEL INDICATOR IS FULL
Surge protected.
Not backed up
Green Power Function
Ultima UPS is equipped with green power function. For saving power and protecting battery, this method of deep discharging protection is adopted on inverter mode.
Free power monitoring software on CD
• Choose the operation system you need and follow the instructions described on the CD to install the sof tware.
Note: If you nd the communication unsuccessful after monitoring software installation, you have to switch the Auto Search on and you can only do that if you go into 'Act as Administrator'. Once selec ted, the software will hunt for and nd the UPS.
Note: The power switch must be kept in the ‘ON’ position, otherwise, the UPS will be disabled and your equipment will not be protected during a power failure.
Note: If you change your UPS model, please ensure you uninstall and reinstall the Software.
Troubleshooting guide:
©Sollatek (UK) Limited 1996 All Rights Reserved. SOLLATEK and the SOLLATEK device are the trade marks of the Sollatek group of companies.
Sollatek (UK) Ltd. Unit 10, Poyle 14 Industrial Estate, Newlands Drive, Horton Road, Poyle, Slough, Berkshire SL3 0DX, UK
Tel: +44 (0) 1753 688300 Fax: +44 (0) 1753 685306
Technical support: support@sollatek.com Sales: sales@sollatek.com www.sollatek.com
Rev. no. 1.0 April 07.
Problem Possible Cause Solution
No LED display on the front panel. 1. Battery weak. 1. Re-charge battery up to 8 hours.
2. Battery defect. 2. Replace with the same type of battery.
3. Power switch is not pressed. 3. Press the power switch again.
Alarm buzzer beeps continuously when AC supply is normal. UPS overload. Verify that the load matches the UPS capability specied in the specs.
When power failure, back-up time is shortened. 1. Overload of the UPS. 1. Remove some noncritical load.
2. Battery voltage is too low. 2. Charge battery 8 hours or more.
3. Battery defect due to high temperature operation environment, or improper operation to battery. 3. Replace with the same type of battery.
Communication lost between UPS and computer 1. Software is not properly installed 1. Check the setting of the software
2. Interface cable is not properly connected 2. Check the interface cable is properly connected to the COM1/COM2 of the computer and conrm the setting again
Mains normal but UPS is not working. 1. Circuit breaker has tripped. 1. Reset the circuit breaker.
2. Power cord is loose. 2. Reconnect the power cord properly.
Proper care of batteries
• Do not subject the battery to heavy vibration or mechanical shock.
• When you receive a new battery, charge fully before use.
• Full capacity will be reached after 2 or 3 full charge/discharge cycles.
• To obtain maximum life, always store batteries in a charged state.
• When storing batteries, re-charge every 6 months to prevent damage through self discharge. This should be done more often if storage temperature exceeds 25ºC.
• Try to store / use in a cool, dry place. Do not expose to excessive hot or cold (i.e. outside the range 10-35°C ambient temp).
• To prolong battery life, try to avoid the complete discharge of your battery before recovery charge.
• Do not discharge a battery deeper than you have to.
• Do not attempt to dismantle a battery. They do not require topping up.
• Do not incinerate batteries. Always recycle old batteries.
• To avoid the risk of shock, do not touch the terminals.
• Keep terminals free from dirt and corrosion.
• Do not short the connections.
• Always charge in a ventilated area.
• Always use a suitable charging device. If unsure, contact your distributor.
• Replace only with Sollatek recommended replacement batteries.
If unsure, contact your distributor.
MODEL Ultima 1000 Ultima 1400 Ultima 2000
CAPACITY VA/W 1000VA/600W 1400VA/840W 2000VA/1080W
INPUT Voltage 220/230/240VAC 220/230/240VAC 220/230/240VAC
Voltage range 89-145VAC/160-290VAC 166-280VAC 166-280VAC
Frequency 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz
OUTPUT Voltage 220/230/240VAC 220/230/240VAC 220/230/240VAC
Voltage regulation (batt. mode) +/-10% at load <50% +/-10% at load <50% +/-10% at load <50%
Frequency 50Hz or 60Hz 50Hz or 60Hz 50Hz or 60Hz
Frequency regulation (batt. mode) +/-1 Hz +/-1 Hz +/-1 Hz
Output waveform modified sinewave modified sinewave modified sinewave
BATTERY Battery type and number 12V/7AH x 2pcs 12V/9Ah x 2pcs 12V/9Ah x 2pcs
Recharge time 10 hours 6 hours (to 90% after complete discharge) 6 hours
TRANSFER TIME Typical 4-6 ms 4-8 ms 4-8 ms
INDICATOR AC mode The first green LED lighting The second to fifth green LEDs gradually lighting, indicating load level
Battery mode The first green LED flashing The second to fifth green LEDs gradually lighting, indicating battery capacity
FAULT Red LED lighting
AUDIBLE ALARM Battery mode sounding every 10 seconds
Low battery sounding every second
Overload sounding every 0.5 second
Battery replacement sounding every 2 seconds
Fault continuously sounding
PROTECTION Full protection overcharge overcharge overcharge and overload protection and overload protection and overload protection
PHYSICAL Dimension (mm) D x W x H 405 x 145 x 205 405 x 145 x 205 405 x 145 x 205
WEIGHT Net weight 9.6kgs 9.7kgs 9.8kgs
ENVIRONMENT Operating environment 0- 40°C, 0-90 % relative humidity (non-condensing)
Noise level Less than 50dB
INTERFACE RS-232 Windows family, Sun Solaris, IBM Aix, Compaq True64, UnixWare, FreeBSD, HP-UX, Linux, MAC USB Windows 98/2000/ME/XP
Specifications
Battery replacement
WARNING: Disconnect all sources of supply before replacing battery.
1. REMOVE THE FRONT PANEL
Locate screw on under­side of front fascia, and remove. The front fascia will now lift upwards.
2. REMOVE THE METAL BAT TERY COVER PLATE
Slide it upwards and outwards. Put it to one side.
3. REMOVE THE BATTERY
After removing battery cover plate, gently pull out the battery. Disconnect the two wires that are connected to the UPS.
Replacement battery installation is the reversal of this procedure.
Ensure the wires on the battery are connected back exactly the way they were connected originally. Caution! UPS may get damaged if these wires are connected incorrectly - if in doubt, contact Sollatek.
• Replace only with Sollatek recommended replacement batteries.
If unsure, contact your distributor.
CHARGE THE UPS AT LEAST 8 HOURS BEFORE USE, ENSURING THE BATTERY LEVEL INDICATOR IS FULL
TM
t he p o we r t o pr o te ct
Ultima battery back-up times (in minutes)
200VA 300VA 400VA 600VA 800VA 1000VA 1200VA 1400VA 1600VA 1800VA Ultima1000 45 25 15 8 <5 3 Ultima 1400 58.5 37.3 25 13.5 8.25 4.7 3 1.5 Ultima 2000 58.5 37.3 25 13.5 8.25 4.7 3 1.5 0.5 <0.5
Loading...