Soleus Air KFTHP-12-OD, KFTHP-18-ID, KFTHP-24-ID, 3119233, KFTHP-12-ID User Manual

...
Page 1
13 SEER Mini Split Air Conditioner
with Heat Pump and Back up Electric Heat Strip
KFTHP-12-ID/KFTHP-12-OD KFTHP-18-ID/KFTHP-18-OD KFTHP-24-ID/KFTHP-24-OD
R
T
E
E
T
K
N
I
CM
C
L
I
S
31 19233
US
D
E
Page 2
CAUTION
All units must be installed by a licensed contractor or technician.
Installation must be in accordance with this manual,NEC,State and Local Codes. Otherwise unit warranty will be void and serious damage to person and/or property may occur.
Read all instruction manuals thoroughly before attempting installation.
The Manufacturer shall NOT be liable for any damages or loss due to improper
installation or operation or natural disasters.
Do not power the unit until all wiring,refrigerant tubing and refrigerant charging has been checked and tested.
Units must be grounded per current NEC,State and Local Codes.
Wiring connections must be tightly secured to all terminals.Loose connections can result in electrical arcing,overheating and potential fire hazards.
CONTENTS
Safety Precautions........................................................................1
Identification of Parts...................................................................2
Remote Controller........................................................................4
Operation Instructions..................................................................7
Maintenance.... ............................................................................9
Protection...................................................................................10
Troubleshooting..........................................................................11
Installation Instructions...............................................................12
Preparation Before Use
Before using the air conditioner, be sure to check and pre-set the following.
Remote Controller Pre-setting
The remote controller is NOT preset .and should be set by owner
Each time after the remote Control or is energized, Cool and HEAT alternatively User can preset the remote control type depending on the air conditioner type you have purchased as follows :
Press any button when the flashes . Press any button when the cooling symbol flashes ,then Cooling Only is set. If you dont press any button within 10 seconds, the remote controller is pre-set as Heat Pump automatically.
Note: If the air conditioner you purchased is a Cooling Only one, but you pre-set the remote controller as Heat Pump,
will operate properly in cooling.
controller as Cooling Only, then you CAN NOT preset the Heating operation with the remote controller.
Auto-restart Pre-setting(optional):
the is preset as Auto-restart function by manufacturer.If Auto-restart function is not needed, follow the steps below to cancel this function:
1) Make sure the power is .
2) Keep pressing the Emergency button for more than 10 seconds until four short beeps are heard. Then Auto-restart function is disabled. To activate the Auto-restart function, repeat above procedure until three short beeps are heard.
--This is not intended for use by young children or persons unless they have been adequately supervised by a responsible person to ensure that they can use the safely
--Young children should be supervised to ensure that they do not play with the .
'
air conditioner
air conditioner turned off at remote control
air conditioner handicapped
batteries are replaced, the symbol will flash from
.
heating symbol ,then Heat Pump is set
it
. But if the air conditioner you purchased is a Heat Pump one, and you preset the remote
air conditioner
air conditioner
Page 3
11
Safety Precautions
Symbols in this Use and Care Manual are interpreted as shown below.
WARNING! DANGER!
CAREFUL! Pay Attention.
Grounding is essential.
Be sure to follow this instruction.
Remove the power source plug from a socket.
Warning: Incorrect handling could cause a serious hazard, such as death, serious injury, etc.
Use correct power supply in accordance with the rating plate requirement. Otherwise, serious faults or hazard t.such as a fire could occur
If the supply cord is damaged,it must be replaced by the manufacturer,its service agent or similarly qualified persons in order to avoid a hazard.
Do not tangle, pull or press the power supply cord, as this cord will be damaged and an electric shock or fire
could occur.
SLEEP
TIMER ON
OFF
AUTO
it can
FEEL
HI
COOL
MED
DRY
LO FAN HEAT
SWING
SLEEP
FAN
TIMER
SWING
ON/OFFMODE
If malfunction occurs turn off at remote control first before turning off main power.
Do not touch the operation buttons when your hands are wet.
Do not use extension cords and do not connect the air conditioner to a socket to which other electric appliances are connected.
Make sure to use a fuse of proper electric rating.
Use of steel or copper wire instead of a fuse is strictly prohibited
and will void the warranty.
Do not put anything on the unit, especially vases which contain water inside.
If water gets into the unit,
cause an electrical short and
this could cause electric shocks.
Keep the power supply circuit breaker or plug from dirt. Connect the power supply cord to it firmly and correctly,
Never insert a stick or similar obstacle to the unit. When the fan rotates at high speed, this may cause an injury.
Do not repair the appliance by yourself. If this is done incorrectly, it may cause an electric shock, etc.
Do not put any objects on the outdoor unit.
Check that the plug is not covered with dust and make sure to insert it firmly so that it does not get loosened.
If the plug is coverd with dust or improperly inserted, thes may cause electric shock or fire.
Do not wash the air conditioner with water.
It could cause electric shocks.
OFF
.or hazard could occur
Fully insert the plug firmly.
ON
the system is operating
When simultaneously with a combustion apparatus,you should air the room frequently.
Insufficient ventilation could cause an oxygen deficiency accident.
Do not use the power supply circuit breaker or pull off the plug to turn it off during operation. This may cause a fire due to spark, etc.
Do not stand in front of indoor
I
unit for extended periods of time due to health hazard
.
Prevent the air flow from reaching the gas burners and stoves.
It is the user's responsibility to ground the appliance according to local codes or ordinances by a licenced technician.
When not using the system for a long time, remove the plug from the socket to ensure safety.
If the plug is covered with dust,it could cause
a fire.
If abnormal conditions occur,such as smell of burning,immediately stop the system' operation,remove the power plug and consult your Dealer.
Operating the system under abnormal conditions could result in malfunctions,eletric shocks,fire,etc.
Before cleaning the system,stop the operation and remove the power plug.
Cleaning should never be carried out while the inside fans are running.
ON
OFF
Notes:For the purpose of innovation and improvement,above products are subject to change without prior notice. The air conditioner is not a toy , please keep away from children.
the laundry area.
The appliance shall not be installed in
1
Page 4
11
Identification of Parts
Indoor Unit
Air Intake
Front Panel
Emergency Panel
Display Panel
Air Outlet
Vertical Adjustment
Louver
Horizontal Adjustment
Louver
Charcoal Filter (optional)
Electrostatic Filter (optional)
Air Filter
Outdoor Unit
Note: Condensate water drains at COOLING or DRY operation.
The figures in this manual are based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner you have selected.
Remote Control
Air Intake
Pipes and Power Connection Cord
Drain Hose
Air Outlet
2
Page 5
11
Identification of Parts
Operating and Display
Run Indicator
It is on during operation.
Temperature display
Display of environm­ental temperature or setting temperature
Timer Indicator
It lights up during the set time.
Power Indicator
It lights up when power supply is on.
Sleep Indicator
It lights up during the set sleep function
The above operating sketch map is suitable for Z BG series.
Signal Receives
Receive signal from the remote control.
Sleep Indicator
It lights up during the set sleep function
Power Indicator
It lights up when power supply is on.
POWER
SLEEP
TIMER RUN
Temperature display(optional)
Display of environmental tem­perature or setting temperature
Timer Indicator
It lights up during the set time.
Run Indicator
It is on during operation.
The above operating sketch map is suitable for C D E F G H J K M N V Z BD BE BF BH and BJ series.
Temperature display
Display of environm­ental temperature or setting temperature
Power Indicator
It lights up when power supply is on.
Sleep Indicator
It lights up during the set sleep function
The above operating sketch map is suitable for L R and Y series.
Used to control the unit when the remote control is out of work.
way of operation
This is suitable for C D N R L M Y and Z series.
ON/OFF
Used to control the unit when the remote controller is out of work. This is suitable for
way of operation
EFGHJ K QZBD BE BF BG BH and BJ series.
Signal Receives
Receive signal from the remote control.
Run Indicator
It is on during operation.
Timer Indicator
It lights up during the set time.
Emergency Button
Emergency Button
The above operating sketch map is suitable for Q series.
Temperature display
Display of environm­ental temperature or setting temperature
Sleep Indicator
It lights up during the set sleep function
Power Indicator
It lights up when power supply is on.
ON/OFF
Remarks:When remote control is ,open the panel and you can see emergency button there, .The emergency button for 15K 16K 18K 22K 24K
(see above picture)
not working properly,
28K and 30K series is at the top right,see ON/OFF button there.
The shape and position of the switches and indicators may vary from different models,but their function are simiar.
3
Page 6
11
Remote Control
Remote Control
The remote control transmits signals to the system.
ON/OFF button
Used to start and stop operation .
TIMER button
Used to select TIMER operation.
Setting Display
UP button (TOO COOL button)
Used to increase the set room temperature (60 f f) ~87 and time(0.5~24h or 1~12h ).
DOWN button (TOO WARM button)
Used to decrease the set room temperature and time.
SLEEP button
Used to set or cancel sleep operation.It includes normal-SLEEP( )and ­SLEEP( ),but is optional.
Comfortable-SLEEP
SWING control button
Used to adjust airflow direction.
FAN SPEED control button
Used to select the indoor fan motor speed: Auto( or ), High( or or ), Mid( or or ) and Low( or or ).
MODE button
Used to select the type of operation mode: FEEL( ), COOLING( ), DRY( ), FAN( ) AND HEATING ( Only for Heat Pump). mode such as COOL,DRY,FAN,HEAT automatically depending on the room temperature,and the feel mode is default setting at starting.
3D button(optional)
9
Used to start and stop 3D operation .
direction in different mode( .
ECO. button(optional)
10
(This function does not apply to the Units of KFTHP-12, KFTHP-18, and KFTHP-24. )
Used to start and stop ECONOMY operation .This function is invalid in SUPER mode.
DISPLAY button(optional)
11
Used to start and stop DISPLAY screen operation .
ANTI-MILDEW button(optional)
12
Used to start and stop ANTI-MILDEW operation .
SUPER button(optional)
13
(This function does not apply to the Units of KFTHP-12, KFTHP-18, and KFTHP-24. )
Used to start and stop SUPER operation .
HEALTHY button(optional)
14
Used to start and stop HEALTHY operation .
RESET button(optional)
15
Used to restart.
Note:The position and figure of buttons are
QUIET
QUIET
FEEL mode can select the operation
optional)
Comfortable
This function is invalid in sleep mode.
Two-direction Airflow,the horizontal louver is opened different
11
14
7
5
4
10
1
EC
POWERFUL
subject to the ;the relevant function
is not activated even if press the optional button which is invalid for some models;
Each mode and relevant function will be further specified in following pages.
Signal Transmitting Window
Transmits signals to the system.
RESET
actual unit,
9
12
3
6
2
8
13
15
4
Page 7
11
Remote Control
Remote Control
Some remote control s display:
SLEEP
TIMER ON
TMIER OFF
FEEL COOL DRY FAN HEAT
AUTO HIGH MID LOW
SWING
h
C
Feel Cool Dry Fan Heat
C
h
Auto Low Mid High Sleep Swing
Timer off Timer on
Style.3
FEEL
COOL
DRY
FAN
HEAT
Style.1
HEALTHY
C
ON
AUTOQUIET POWERFUL
AUTO
hr
DELAY
OFF
ON
TIMER
Style.2.
FAN SPEED
AIR SWING
Style.5
Style.4
Note:The above remote control is only for reference, subject to the .actual unit
inserting
When the batteries for the first time or each time the batteries are replaced
as they are discharged, the remote control mades a short Auto-Test :all the symbols can be displayed are shown on the screen and keep 2 seconds,then the symbol will flash from .For cooling only air con, please press any button when the cooling symbol is flashing,the the remote controller has been set as cooling only.For cooling and heating ,please press any button when the heating symbol is flashing,then the remote control has been set as cooling and heating.If none of the button is pressed within 10 seconds,the remote controller will be set as cooling and heating automatically.Cooling only can use the remote control which has cooling and heating function,but do not have the function of heating. Although the is not running,remote still have some display.heating control will
Cool to HEAT alternatively
The light of the remote control will be turned on by pressing any button for
1.5~3 seconds,and it will be turned off automatically if no button is pressed within 10 seconds.
5
Page 8
11
Remote Control
Remote Control
How to Insert the Batteries
Remove the battery cover according to the arrow direction.
Insert new batteries making sure that the (+) and (-) of
battery are matched correctly.
Re-attach the cover by sliding it back into position.
Note: Use 2 LR03 AAA(1.5volt) batteries. Do not use rechargeable batteries.Replace batteries with new ones of the same type when the display becomes dim.
Storage and Tips for Using the Remote Control
The remote control may be mounted on a wall with a holder.
Note: The remote control holder is an optional part.
Remote control holder
F E
S L
E
E
L
E P
C
T I M
O
E
O
R
L
O N
D
T M
R
I E
R
Y
O F
F
F A
N H E
A
A
T
U T O
H
I G H
M
E D
L
O W
S
W I N G
S L
E E
P
T I M
E
R
F A N
M
O
S
D
W
E
I N
G
O
N
/ OF
F
Please slide and remove the cover.
1
Exchange the batteries.
2
Install the cover.
3
F
S L
E
E
E
E P
L
T I M E
C
R
OO
O N
L
T M
I E R
D
O
F
R
F
Y F A
N
A U
H
T
E
O A T
H I G
H
M E
D
L O
W
S W
I
N
G
S L
E E
P
TI M
FA
E
R
N
S
M
W
O
I
N D
G
E
O
N / O
F
F
Slide the cover upwardly in the direction of the arrow.
Attention to the and + marks.
How to Use
To operate the room air conditioner, aim the remote control to the signal receptor. The remote control will operate the air conditioner at a distance of up to 10 feet when pointing at signal receptor of indoor unit.
Signal receptor
F E E
C
L
S
O
L
O
EE
DRY L
P
F
T I M
A
E
N H
R ON
E A T
T M I E R O F F
AU
T
H
O
S
I G
L
M H
E
E
E
L D OW
P
S W
I
T
N
I
G
M E R
M
O
D
F
E
A
N S W I N G
O N
/ O F F
6
Page 9
Operation Instructions
11
FEEL mode operation procedure
Operates by selecting automatically the operation mode(HEAT,DRY,FAN,COOL)depending on the room temperature during staring.
With the remote control pointing toward the air conditioner.
Turning on
ON/OFF
Press button, when the appliance receives the signal, the RUN indicator of the indoor unit lights up.
When the unit is not at FEEL mode.
1
SLEEP
TIMER ON
TMIER OFF
FEEL COOL DRY FAN HEAT
AUTO HIGH MID LOW SWING
Selecting FEEL mode
Press the MODE select button.
Move the MODE to the FEEL position.
Operation mode and temperature are determined by indoor temperature
Indoor temperature
Less than 68 f
68 f - 7 9 f
Over 79 f
Operation mode
HEATING ( FOR HEAT PUMP TYPE)
FAN (FOR COOL ONLY TYPE)
DRY
COOL
Target temperature
73 f
64 f
73 f
2
2
2
SLEEP
TIMER
3
FAN
SWING
ON/OFFMODE
3
1
Air temperature adjustment is possible even during FEEL operation. There are 4 levels of adjustment possible with the button or the button.
Setting temperature
Press the button or the button. When the button is pushed,the temperature will increase .1 f
After temperature will increase 2 ,the indicator will not change. f
When the button is pushed,the temperature will reduce .1 f
After temperature reduce 2 ,the indicator will not change. f
NOTENOTE
There will be a delay when changing mode
is made during the operation.
As there might not be air blown out.
7
The operation of the AUTO
mode can be performed by
only pressing the ON/OFF
button from the next time.
If you don't like the content of FEEL mode operation, change to HEATING,DRY or COOLING than FEEL.
Page 10
Operation Instructions
11
TIMER mode
It is convenient to set the timer on with TIMER button when you go out in the morning to achieve a comfortable room temperature when you get home. You can also set timer off at night to enjoy a good sleep.
When the Remote Control is OFF,press the TIMER button to set a switch-on timer,press again,the setting will be cancel.
Press UP and DOWN button to set time. Time setting is 30-minutes.
Note: After setting the timer,check that TIMER INDICATOR lamp of the indoor unit lights.
When the Remote Control is ON,press the TIMER button to set a switch-on timer, press again,the setting will be cancel.
SLEEP mode
Normal-SLEEP& -SLEEP(Comfortable optional)
1.
press the SLEEP button for 3 seconds, SLEEP operation is
Having
switched from Normal-SLEEP to -SLEEP alternatively. Used to set or cancel sleep operation.
and dehumidify mode,This function is invalid in SUPER mode too. Switches OFF the appliance automatically after 10 hours in Normal­SLEEP mode.
Normal-SLEEP only
2.
While the unit is running,
SLEEP button:the indoor fan speed operates at low speed.
OFF the appliance automatically after 8 hours.
Comfortable
In this model,the temperature will automatically be adjusted with the body temperature, like the english letter V at the first stage of sleep, the body temperature will decrease when our air-conditioner s set-temperature decrease together; and at the last stage of sleep, the body temperature will increase when our air-conditioner s set-temperature increase together. It will help you sleep more comfortably.
-SLEEP note:
. Select the operating mode and then press
'
Comfortable
This function is invalid in fan
Switches
'
8
Page 11
11
Maintenance
Front panel maintenance
Turn off the appliance
Cut off the power supply
Grasp position "a" and pull outward to remove the front panel.
Wipe with a soft and dry cloth.
Use lukewarm water(below
) to clean if the
104 f
appliance is very dirty.
Never use volatile substance such as gasoline or polishing powder to clean the appliance.
Never sprinkle water onto the indoor unit
Reinstall and shut the front panel.
Reinstall and shut the front panel by pressing position "b" downward.
first before disconnecting from power supply.
a
b
Use a dry and
soft cloth to clean it.
Dangero
E
le
ctr
s
ho
Air filter maintenance
It is necessary to clean the air filter after using it for about 100 hours. Clean it as follows:
Stop the appliance and remove the
a
us
!
ic c
k!
b
air filter.
1.Open the front panel.
2.Press the handle of the filter gently from the front.
3. Grasp the handle and slide out the filter.
Clean and re-install the air filter.
If the dirt is conspicuous, wash it with a solution of detergent in lukewarm water. After cleaning, dry well in shade.
Close the front panel again.
Clean the air filter every two weeks if the air conditioner operates in an extremely dusty environment.
At the end of the season
Set temperature to for about half a day and perform the Cooling operation to dry well the Unit
Stop the unit operation and then turn off the power switch for afety
and for saving electric energy.
Clean and reinstall the air filters.
Clean both Indoor and Outdoor Units.
Remove batteries from the remote control .
9
86 f
's inside.
Dry the inside of the unit.
s
OFF
At the beginning of the season
Make sure there are no obstacles blocking the airflow around the air intake and air outlet openings of the Indoor and Outdoor Units
ON
Check the installation base for corrosion or rust.
Make sure the earth wire is not broken or disconnected
Make sure the air filters are cleaned.
Turn on the power switch.
Insert batteries into the remote controller.
Page 12
11
Protection
Operating condition
The protective device maybe trip and stop the appliance in the cases listed below.
HEATING
COOLING
DRY
* For Tropical (T3) Climate condition models, the temperature point is 96 f 96 f instead of .
If the air conditioner runs in COOLING or DRY mode with door or window opened for a long time when relative humidity is above 80%,dew may drip down from the outlet.
Outdoor air temperature is over 75 f
Outdoor air temperature is below -
5 f
(- for inverter models,it's optional)
Room temperature is over 80 f
Outdoor air temperature is over * (or below 32 f for inverter models)
Room temperature is below 69 f
Room temperature is below 64 f
Features of protector Inspection
19 f
110 f
Noise pollution
Install the air conditioner at a place that can bear its weight in order to operate more quietly.
Install the outdoor unit at a place where the air discharged and the operation noise would not annoy your neighbors.
Do not place any obstacles in front of the air outlet of the outdoor unit as it will increase
the noise level and possible malfunction of fan motor.
The protective device will work as follows.
Restarting the unit at once after operation stops or changing mode during operation, you need to wait 3 minutes.
Connect to power supply and turn on the unit at once, it may start 20 seconds later.
If all operation has stopped, press ON/OFF button again to restart. Timer should be set again if it has been canceled.
Features of HEATING mode
After using for long time, the air conditioner should be inspected on the following items.
Overheat of the power supply cord and plug or even a burned smell. Abnormal operating sound or vibration. Water leakage from indoor unit. Metal cabinet electrified.
Stop the air conditioner if above trouble occurs. It is advisable to have a detail inspection after using it for 5 years even if none above occurs.
Preheat
At the beginning of HEATING operation, the airflow from indoor unit is discharged 2-5 minutes later.
Afterheat
After the finishing of HEATING operation, the airflow from indoor unit is discharged 2-5 minutes.
Defrost
In HEATING operation the appliance will defrost (de-ice) automatically to raise efficiency. This procedure usually lasts 2-10 minutes. During defrosting, fans stop operation. After defrosting completes, it returns to HEATING mode automatically.
Note: Heating is NOT available for cooling only air conditioner models.
10
Page 13
11
Troubleshooting
The following cases may not always be a malfunction, please check it before asking for service.
Analysis
Does not run
No cooling or heating air
Ineffective control
Trouble
If the plug is not properly plugged.
If batteries in the remote controller exhausted. If the protective device works to protect the appliance.
If the protector trip or fuse is blown.
Are the intakes and outlets of the air conditioner blocked
Is the temperature set properly
Is the air filter dirty?
If strong interference(from excessive static electricity discharge, power supply voltage abnormality)presents, operation will be abnormal. At this time, disconnect from the power supply and connect back 2-3 seconds later.
Does not operate immediately
Peculiar odor
A sound of flowing water
Cracking sound is heard
Spray mist from the outlet
The compressor indicator(red) lights on constantly,and indoor fan stops.
Air will not immediately blow out at the start of HEAT mode
Stop discharging airflow for 5~10minutes during HEATING operation
The remote control does not function correctly
don't run
Dont
'
discharge
11
Changing mode during operation, 3 minutes will delay.
This odor may come from another source such as furniture, cigarette etc, which is sucked in the unit and blows out with the air.
Caused by the flow of refrigerant in the air conditioner, not a problem.
Defrosting sound in heating mode.
The sound may be generated by the expansion or contraction of the front panel due to change of temperature.
Mist appears when the room air becomes very cold because of cool air discharged from indoor unit during COOLING or DRY operation mode.
The unit is shifting from heating mode to defrost. The indicator will lights go off within ten minutes and returns to heating mode.
The air is ready to blow out enough warm
conditioner
air please wait(2~5 minutes )
The appliance will defrost automatically ,and mist appears from outdoor.After defrosting ,it continues to
run automatically.
check the distance between the remote controller
and the unit. Are the batteries exhausted? Replace them with new ones,and repeat the operation again.
Page 14
11
Installation Instructions
Installation Diagram
Distance from ceiling
Distance from wall
should be over 6””
Distance from floor
should be over 6 feet
should be over 6”
Distance from the wall
should be over 6”
over 20
Air intake distance from the wall should be over 12”
air
o
sh
ut
le
ou
t
d
ld
is
be
t
an
ov
ce
e
fr
r
om
6
f
ee
the w
t
all
NOTENOTE
Above figure is only a simple presentation of the unit, it may not match the external appearance of the unit you purchased. Installation must be performed in accordance with the national wiring standards by authorized personnel only.
Very Important-Installation must done by a registered qualified installer.(Refer warranty section at the back of this manual)
Air intake distance from the wall
Should be over 12”
over 12”
12
Page 15
Installation Instructions
11
C
onn
e
ct
ing
o
f
th
e
C
a
bble
Wiring between the indoor and outdoor units:
1) Remove the PCB cover from the indoor unit;
2) Refer to the wiring diagram attached to indoor unit when connecting cords to indoor unit terminals;
3) Reinstall the PCB cover. Be sure that side B is facing outside.
S
e
le
c
t
th
e
be
s
t
l
o
c
a
tio
n
Location for Installing Indoor Unit
Where there is no obstacle near the air outlet and air can be easily blown to every corner. Where piping and wall hole can be easily arranged. Keep the required space from the unit to the ceiling and wall according to the wiring diagram. Where the air filter can be easily removed. Keep the unit and remote control or more apart from
3 feet
television, radio etc. Keep as far as possible away from fluorescent lamps. Do not put anything near the air inlet to obstruct it from air absorption. Where there is
vibration and noise
bearing wall to handle weight and decrease
.
COVER
A side (before connect)
Installation Diagram
Indoor unit
t
fee 6
d
l u
n 1
o
tha
sh
t h
less
g
i e
be
H
B side (after connect)
Pipe length is
Front panel
Terminal (inside)
COVER
Cabinet
Max.49 feet
Outdoor unit
Location for Installing Outdoor Unit
Where it is convenient to install and well ventilated; avoid installing it where flammable gas could leak. Keep the required distance apart from the wall. Keep the outdoor unit away from a place of greasy dirt, vulcanization gas exit or high salty seashore. Avoid installing it at the roadside where there is a risk of muddy water. A fixed base so as not to increasing operation noise. Where there is no blockage for air outlet.
13
Pipe length is
Indoor unit
Max.49feet
Outdoor unit
t ee
f
d
6 1
oul
an th
sh
t
s s
gh
le
Hei
be
Page 16
11
Installation Instructions
Indoor Unit Installation
1. Installing the Mounting Plate
Decide an installing location for the mounting plate according to the indoor unit location and piping direction.
. Keep the mounting plate horizontally with a horizontal ruler or dropping line.
Drill holes of in depth on the wall for fixing the plate.1" Insert the plastic plugs to the hole, fix the mounting plate with tapping screws.
Inspect if the mounting plate is well fixed. Then drill a hole for piping.
Mounting plate
Dropping line
2
Line drops from here
r
o o d n
I
4
3
Note: When installing the pipe at the directions 1,2 or 4, saw the corresponding unloading piece off the indoor unit base.
r
Wall hole sleeve ( hard polythene tube
tdoo u
prepared by user)
O
(tilt downward)
1/4 "
Hook the line here
holes for fixing
Note: The shape of your mounting plate may be different from the one above, but installation method is similar.
2. Drill a Hole for Piping
Decide the position of hole for piping according to the location of mounting plate.
Drill a hole on the wall. The hole should tilt a little downward toward outside.
Install a sleeve through the wall hole to keep the wall tidy and clean.
3. Indoor Unit Piping Installation
Put the piping (liquid and pipe) and cables through the wall hole from outside or put them through from inside after indoor piping and cables connection complete so as to connect to outdoor unit. Decide whether saw the unloading piece off in accordance with the piping direction.(as shown below)
Piping direction
Saw the unloading piece off along the trough
After connecting piping as required, install the drain hose. Then connect the power cords. After connecting, wrap the piping, cords and drain hose together with thermal insulation materials.
suction
trough
Unloading piece
1
14
Page 17
11
Installation Instructions
NOTENOTE
Piping Joints Thermal Insulation:
Wrap the piping joints with thermal insulation materials and then wrap with a vinyl tape.
The temperature of refrigerant circuit will be high, please keep the
Thermal insulation
interconnection able away from the copper tube.c
Piping Thermal Insulation:
a. Place the drain hose under the piping. b. Insulation material uses polythene foam over in thickness.
Note: Drain hose is prepared by user.
Drain pipe should point downward for easy drain flow. Do not arrange the drain pipe twisted, sticking out or wave around, do not immerse the end of it in water.
3/8"
If an extension drain hose is connected to the drain pipe, make sure to thermal insulated when passing along the indoor unit.
When the piping is directed to the right, piping, power Cord and drain pipe should be thermal insulated and fixed onto the back of the unit with a piping .connector
wrapped with vinyl type
Large pipe
Power cord
Power cord 1 (for heat-pump)
Defrost cable(for heat-pump)
Insert here
Thermal insulation tube
Small pipe
Drain hose (prepared by user)
drain hose
Base
Piping connector
A. Insert the pipe to the slot.connector
Base
B. Press to hook the pipe onto the base.connector
Connecting the refrigerant lines between the indoor& outdoor units
Note that since the refrigerant metering device is located in the outdoor unit,both refrigerant lines must be insulated with a minimum of 3/8 foam along the entire length.
Gently bend the line set stubs from the indoor unit to the desired location and the using 2 box end or adjustable wrenches,remove the flare nuts from the indoor unit line stubs.The indoor unit is charged with a dry gas.If you do not hear the release of pressure when removing the flare nuts,it is possible that the evaporator section(indoor unit)has developed a leak and you should contact your dealer for a replacement indoor unit.Note:Using a small amount of vacuum pump oil on the male flare threads will ease installation.Snug the line set to the stubs using the 2 wrenches-one wrench on the male fitting and one wrench on the female fitting.
Tighten flares to below torques:
Refrigerant Line Connection Torque Table
Flare Nut
1/4-3/8 "
1/4-1/2 "
1/2-3/4 "
7/8-1
1/8"
"
Tightening Torque
25 Ft.LBs(350 Kg.Cm)
40 Ft.LBs(560 Kg.Cm)
60 Ft.LBs(840 Kg.Cm)
110 Ft.LBs(1540 Kg.Cm)
15
small pipe
large pipe
Piping fixer
Base
drain hose
small pipe
large pipe
Hook here
Page 18
11
Installation Instructions
4. Connecting of the Cable
Indoor Unit
Connect the power connecting cord to the indoor unit
Front panel
Terminal (inside)
by connecting the wires to the terminals on the control board individually in accordance with the outdoor unit connection.
Note: For some models, it is necessary to remove the cabinet to connect to indoor unit terminal.
Outdoor Unit
Indoor unit
Cabinet
Chassis
1). Remove the access door from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following.
2). Secure the power connecting cord onto the control board with cable clamp.
3). Reinstall the access door to the original position with the screw.
4) Use a recognized circuit breaker for 24K.30K model between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Outdoor unit
The figures in this manual are based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner you have selected.
Access door Terminal(inside)
Caution:
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, refer to the circuit diagram posted on the inside of the access door .
2.Comfirm that the cable thickness is as specified in the power source specification. (See the cable specification table below)
3.Check the wires and make sure that they are all tightly fastened after cable connection.
4. Be sure to install an earth leakage circuit breaker in wet or moist area.
Wire Gauge Requirements
Circuit
Amp 200ft
15 20 25 30 35 40 45
50
(Nec,105c/221 F Type Copper Conductors)
6 4 4 4 3 3
2
2
Wire Gauge at Different Wire Lengths
150ft
8 6 6 4 4 4 3
3
100ft
10
8 8
6 6 6 4
4
50ft
14 12 10
10
8 8 6
6
16
Page 19
Installation Instructions
11
Outdoor Unit Installation
1.Install Drain Port and Drain Hose (for heat-pump model only)
The condensate drains from the outdoor unit when the unit operates in heating mode. In order to protect the environment, install a drain
port and a drain hose to direct the condensate water. Just install the drain port and rubber washer to the chassis of the outdoor unit, then connect a drain hose to the port as the right figure shown.
2. Install and Fix Outdoor Unit
Drain port
Fix with bolts and nuts tightly on a flat and strong floor.
If installed on the wall or roof, make sure to fix the supporter well to prevent it
from shaking due to serious vibration or strong wind.
3. Outdoor Unit Piping Connection
Remove the valve caps from the 2-way and 3-way valve.
Connect the pipes to the 2-way and 3-way valves separately according to the required torque.
4. Outdoor Unit Cable Connection (see previous page)
Drain hose (prepare by user)
Air Purging
The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor. After connecting the indoor and outdoor units, evacuate air and moisture from refrigerant cycle using a vacuum pump, as shown below.
Washer
Vacuum pump
Indoor unit
Refrigerant flow direction
3-way valve
(7) Turn to fully open the
Service port
(2) Turn (8) Tighten
valve
(1) Turn
Valve cap
Note: To protect the environment, be sure not to discharge the refrigerant to the air directly.
17
2-way valve
(8) Tighten
(6) Open 1/4 turn
(7) Turn to fully open the valve
valve cap
(1) Turn
(8) Tighten
Connect to outdoor unit
3-way valve diagram
Valve core
connect to indoor unit
open position
spindle
needle
service port cap
Page 20
Installation Instructions
11
Interconnection Cable
(1)Take off the cover for Interconnection cable of outdoor unit. (2)Take off the block for Interconnection cable, then put the core of the power wire to the terminal and
fix it according to the diagrams pasted to indoor and outdoor unit separately.
(3)Fix the accessory cable with the Interconnection cable block. (4) Confirm the fixing of the accessory cable is ok. (5)Fix the cover for Interconnection cable on.
Diagram for installation of Interconnection cable
( please see the pasted diagram instruction on the body first)
Circuit Diagram
12K 18K 24K indoor and outdoor interconnection cable sketch map
Indoor Unit
W
L
Connetting outdoor unit
Outdoor Unit
W
Connetting indoor unit
L
L
Connetting power
W
Cooling & Heating
Note: Some models are designed without the conneting terminal in indoor unit,please subject to the connetion diagram of the product.
18
Page 21
11
Installation Instructions
How to Purge Air Tubes
(1). Unscrew and remove caps from 2 and 3-way valves.
(2). Unscrew and remove cap from service valve.
(3). Connect vacuum pump flexible hose to the service valve. (4). Start vacuum pump for 10-15 minutes until reaching a vacuum of Hg absolutes.30" (5). With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop
vacuum pump. (6). Open 2-way valve 1/4 turn then close it after 10 seconds. Check tightness of all joints using liquid
soap or an electronic leak detector.
(7). Turn 2 and 3-way valves stem to fully the valves. Disconnect vacuum pump flexible hose. (8). Replace and tighten all valve caps.
Test Running
Connect to the power source, check if the function selection keys on the remote controller are working
properly. Check if the room temperature adjustments and timer settings are working properly. Check if the drain is open. Check if there is any abnormal noise or vibration during operation. Check if there is leakage of refrigerant.
ATTENTION:
If there is no power plug along with the air conditioner,The power cord should be connected to an air switch ,whose current carrying capacity should be more than 20A and the minimum open-circuit distance among the live polar pole,the neutral polar pole and the ground polar pole should be more than 1".If any malfuctions,please cut off the supply by the air switch and contact the manufacturer or its service agent.
The appliance shall be installed in accordance with national wiring regulations.
If the supply cord is damaged. It is better to be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
NOTENOTE
Please read this manual before installing and using it.
Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.
Test run the air conditioner after finishing installation, and record details of operation. Type of fuse used on indoor unit controller for 7K,9K,12K with rating 3.15 A,250V; rating 15 A,250V,for 18K,22K,24K is 65TS with rating 25A,250V.
The fuse for the whole unit is to be provided by the user according to the current at maximum power
input or use other over-current protective device instead. Accessibility to the plug must be guaranteed even after the installation of the appliance to disconnect it in case of need. If not possible, connect appliance to a double-pole switching device with contact separation of at least placed in an accessible position even after installation.1 "
Please make replacing with the special assembly purchasing from our factory or our service center if something wrong with Interconnection cable. The security out static air pressure for our products is 0.8-1.05 * standard pressure. The biggest length for our connection pipe can be 49 feet. More refrigerant is necessary for per foot if the length is over 21 feet.
Please do not place valuable things under the unit after installation.
Type of fuse used on inverter outdoor unit controller for 7K,9K,12K is 61T with
15K,16K,18K, 22K,24K,30K is 50T
19
Page 22
Model:KFTHP-12-ID
Model:KFTHP-12-OD
Page 23
Model:KFTHP-18-ID
Model:KFTHP-18-OD
Page 24
Model:KFTHP-24-ID
Model:KFTHP-24-OD
Page 25
Page 26
Loading...