-2-
OPERATING INSTRUCTIONS
This unit has many fe
ce the unit .
atures which are different from those
found on conventional units. The servicer must be familiar
with these features in order to properly servi
• LCDI Cords-Underwriters Laboratories and the
National Electric Code (NEC) now require power
cords rent leakage and open
the electrical circuit to the unit on units rated at
250 volts or less. In the event that unit does not
operate, check the reset button located on or near
the head of the power cord as part of the normal
troubleshooting procedure.
that can sense cur
Check the data specification plate and ensure the
proper voltage and current rating for the type of plug
on the unit is available. DO NOT REMOVE THE
GROUNDING PRONG FROM THE POWER CORD.
See Fig 1 for the types of ac ceptable plugs. Do not
use an extension cord for the inst allation of this
product. to the data specification plate for
electrical requirements.
Refer
Fig 1
240V
18 Amp
120V
15 Amp
240V
15 Amp
LCDI Power Cord
VOLTAGE MEASUREMENTS
Before connecting the unit, measure the supply
voltage. Voltage must within the voltage
utilization range given in Table1.
Operating Voltage
Voltage Utilization Range
MinimumMaximum
Unit Voltage
Rating
230/208
115
187
253
103
126
Table 1
IMPORTANT
considered as supplemental information.
T NOTES TO HE SERVICER
Read this manual and familiarize yourself with the specific
items which must be adhered to before attempting to
service this unit. The precautions listed in this manual
should not supersede existed practices but should be
IMPORTAHE OWNER
This equipment is to be serviced b
trained personnel only. If this equipment is improperly
installed, adjusted or altered by an unqualified person, a
safety hazard may result.
NT NOTES TO T
y professional and
All units are securely packed in shipping containers
approved by the National Safe Transit Association. The
carton
should be checked upon arrival for external
damage. If damage is found, make a written request for
inspection immediately by the carrier’s agent.
In the event of damage:
UNPACKING THE UNIT
1. Cut the carton banding and op en the carton.
2. Remove the literature, hardware pack, upper
styrofoam shipping blocks, and styrofoam corner
posts.
3. Remove the front assembly.
4. Lift the u nit from the rema ining carton.
5. Dispose of the cardboard and st yrofoam at an
approved Recycle Center . Check all contents for
damaged or missing parts.
TRANSPORTATION DAMAGE
1. Note on the
2. Notify carrier promptly and request an inspection.
3. File the claim with the following supporting documents
within
the six month statute of limitations.
delivery receipt about any visible damage
to shipment or container.
The carrier is responsible for making prompt inspection
of damage and for a thorough investig
claim. The distributor or manufacturer will not accept
claims from dealers for transportation damage.
ation of each
a. Original Bill of Lading, certified copy, or indemnity
bond.
b. Original paid freight bill or indemnity.
c. Original invoice or certified copy, showing trade
and other discounts or reductions.
d. Copy of the inspection report issued by carrier’s
representative at the time damage is reported to the
carrier.
In case of co ncealed damage, notify the carrier as
soon as possible-preferably within 5 days. Refer to
step 3 of the Transportation Damage section if
damage or missing parts are noted.