Saw the cut-out access off
along the side of the casing
3. Indoor unit
refrigeration line installation
o
The refrigeration
lines
and
wiring
can be
routed
to the outdoor unit
in a number of ways
(left
or right from the back of the
unit), by using the cut-out access
pieces
on the casing of
the
unit.
r
Bend the refrigeration
lines
carefully to the
required
position
in
order
to
be aligned
with the
drilled
hole.
When installing the refngeration lines
at
the directions 1
,2
or 4,
saw the corresponding cut-out
piece
off the indoor unit casing.
e
Afterconnecting refrigeraton lines
(see
directions below), install the condensate drain line
(see page
21+24for detailed
instructions on connecting condensate drain line). Then connect all wiring
(see
pages
25-27
for
detailed
instructions
on
wiring).After all connections are
made,
bundle the
refrigeration lines, wiring,
and
condensate drain line together using a
thermal insulation and vinyl/duct tape
Refrigeration lines insulation:
o
lt is important that
both
the liquid
and suction
refrigeration lines are individuallv insulated to ensure
that they do no sweat and also to maintain
proper
unit
capacities. This is necessary since the refrigeration is
metered from
the outdoor unit and
will
produce
condensation on both
refrigeration
lines if not
proper
insulated.
power
Refrigeration lines/Condensate drain line/wiring bundle thermal insulation:
o
Place
the condensate drain
line
under the refrigeration
lines.
r
lnsulation material should be a
polythene
foam that is approximately a 114
inch wall thickness.
r
Condensate drain
line
should have a downward slooe at all times to ensure
proper
drainage. Do not allow the drain line to
be
twisted, horizontal or the
defrost cable(for heat-pump)
end of the
line
be
immersed in water. lf
an extension is added to the drain
line, make
sure that it is also
properly
insulated.
Connection of
refrigeration
lines:
o
Do not
use contaminated or damaged copper tubing
for refrigeration lines.
lf any of the tubing,
evaporator or condenser coils have been exposed to the air for more that 15 seconds, it is
@@-
important
that
they
are
vacuumed
and
purged
with
field-supplied refrigerant.
Do
not removeimportant
that
they
are
vacuumed
and
purged
with
field-supplied refrigerant.
Do
not remove
...+fq-
plastic
or
rubber
plugs
and brass
nuts
from the valves,
fittings,
tubing, or coils until they are
-itA
t-
ready to
be connected.
\$\ \
Jse
proper
tubing cutters to cut the refrigeration lines, advancing the blade of the tubing cutters
slowly. Extra force or improper cutting will
cause
tubing
distortion
and
also extra burrinq.
\
oncerefrigerationtubesarecut,remoVeburrsfromcutedgeswitharemover.Thiswi||avoid_b.
unevenness on
the flare faces, which
could cause a
gas
lelk. Hold the ends of the
pipes
+A
downward to
prevent
metal from
going
into the tubes.
-r
l(
lnsert the flare nuts, mounted
on the connection ends of both the indoor and outdoor units onto
./_€l
l
the ends of the copper tubing.
/o
/
,A
The length of the
pipe protruding
from the face
of
the flare
die
is determined
by
the
particular
flaring tool that will be
plastic
or
rubber
plugs
and brass
nuts
from the valves,
fittings,
tubing, or coils until they are
readv
to be connected
.
Use
proper
tubing cutters to cut the refrigeration lines, advancing the blade of the tubing cutters
slowly. Extra force or improper cutting will
cause
tubing
distortion
and
also extra burring
o
Once
refrigeration
tubes are cut,
remove
burrs from cut edqes with a remover. This will avoid
used.
r
Fix
the
pipe
firmly
on the flare die. Match the centers of both the flare die and the flaring
punch,
and then tighten the
flaring
punch
fully.
Once flaring is
complete, connection of the tubing is
ready. Align
the center of the tubing and tighten the flare nuts
using a torque wrench.
wrapped with
vinyl
or duct type
Thermal insulation
thermal insulation
-18-