Sole Digital Liftlog XL, LL300 Installation And User Manual

Liftlog™XL
Advanced Crane Data Logger
Model LL300, Version 2.0
Installation and User Manual
© CASWA Pty Ltd – 2013
© CASWA Pty Ltd – 2013 2 | Page
CONTENTS
1 OVERVIEW .......................................................................................................................... 4
1.1 Liftlog™XL Versions ............................................................................................................................... 4
2 SPECIFICATIONS .................................................................................................................... 5
2.1 Operational Specifications .................................................................................................................... 5
2.2 Physical Specifications ........................................................................................................................... 5
2.3 Electrical Specifications ......................................................................................................................... 6
2.4 Communication Specifications .............................................................................................................. 6
3 INSTALLATION DETAILS ......................................................................................................... 7
3.1 Prior to Installation ............................................................................................................................... 7
3.2 Inserting/Changing Your SIM Card ........................................................................................................ 7
3.3 Wiring Details ........................................................................................................................................ 7
3.3.1 Terminals .............................................................................................................................. 8
3.3.2 Connecting the Power Supply ............................................................................................. 11
3.3.3 Connecting Motion Inputs ............................................................................................... 13
3.3.4 Connecting Limit Inputs ................................................................................................... 14
3.3.5 Connecting Load Sensor Inputs ....................................................................................... 15
3.3.6 Connecting the Fault Output .............................................................................................. 17
4 COMMISSIONING DETAILS .................................................................................................. 18
4.1 Installing and Launching the FSU Application ..................................................................................... 18
4.1.1 FSU Program Installation .................................................................................................... 18
4.1.2 Installing the FSU application ............................................................................................. 18
4.1.3 Launching the application ................................................................................................... 18
4.2 Connecting to the Device .................................................................................................................... 19
4.3 Checking for Firmware ........................................................................................................................ 19
4.4 Checking the Date/Time ...................................................................................................................... 20
4.5 General Tab ......................................................................................................................................... 21
4.5.1 Setting Equipment Name .................................................................................................... 21
4.5.2 Upload Data to the Computer ............................................................................................ 21
4.6 Main and Aux Hoist Configuration ...................................................................................................... 21
4.6.1 Input Selection .................................................................................................................... 22
4.6.2 Using/Removing a HoistNet Input ...................................................................................... 22
4.6.3 Using the LiftlogXL with a ControlPro ................................................................................. 23
4.6.4 Checking the Gain ............................................................................................................... 24
4.6.5 Calibrating the Logger ......................................................................................................... 24
© CASWA Pty Ltd – 2013 3 | Page
4.6.6 Resetting the Calibration .................................................................................................... 25
4.7 Comms Tab .......................................................................................................................................... 25
4.7.1 3G configuration ................................................................................................................. 25
4.7.2 Link Status ........................................................................................................................... 25
4.8 Inputs and Limits ................................................................................................................................. 26
4.8.1 Using XL devices with a HVDC IO Expander ........................................................................ 26
4.8.2 Tuning Sensitivity and Noise Immunity............................................................................... 27
4.9 Overloads ............................................................................................................................................ 27
4.9.1 Main, Aux and Combined.................................................................................................... 27
4.9.2 Overload Sensitivity ............................................................................................................ 27
4.9.3 Lockout ............................................................................................................................... 27
4.10 SD Card Management ......................................................................................................................... 28
4.10.1 Test SD Card ........................................................................................................................ 28
4.10.2 Reformat SD Card ............................................................................................................... 29
4.11 Running CheckIt Diagnostics ............................................................................................................... 29
4.12 Recording a Service ............................................................................................................................. 30
5 ROUTINE MAINTENANCE .................................................................................................... 31
6 OPERATING LIFTLOG™XL ..................................................................................................... 32
6.1 Operating Status ................................................................................................................................. 32
6.2 Accessing Your Data ............................................................................................................................ 32
6.2.1 Downloading Data .............................................................................................................. 33
8 TROUBLESHOOTING ............................................................................................................ 34
Appendix A: COMMUNICATION PROTOCOL ......................................................................... 35
Appendix B: COMMUNICATION OPTIONS ............................................................................ 37
B.1 How Much Data? ................................................................................................................................. 37
B.2 Australian Carriers ............................................................................................................................... 37
Appendix C: FSU SYSTEM REQUIREMENTS ........................................................................... 38
Appendix D: DATA FILE FORMAT .......................................................................................... 39
© CASWA Pty Ltd – 2013 4 | Page
1 OVERVIEW
Liftlog™XL is an advanced remaining life and load limiting data-logger for cranes. It can simultaneously monitor two hoists and in addition to logging vertical lifting motions, also supervises long and cross travel. Overloads and dangerous usage will trigger immediate email or SMS alerts. Data is automatically downloaded in real time using GSM/3G/GPRS or WIFI connectivity.
Liftlog™XL is particularly well suited to users seeking an integrated enterprise solution for crane monitoring and management, high risk applications requiring increased oversight of crane operation and dual hoist or process cranes.
1.1 Liftlog™XL Versions
Liftlog™XL V2 devices are marked with a serial number that begins with a 2 (e.g. 2-001, 2-974).
If you have a Liftlog™XL with a two or 3 digit serial number that is smaller than 200 (e.g. 72, 196), you have a V1 device and you should refer to the Liftlog™XL V1 Installation and User Manual.
© CASWA Pty Ltd – 2013 5 | Page
2 SPECIFICATIONS
2.1 Operational Specifications
Parameter
Description
Min
Typ
Max
Units
L
count
Maximum number of logged events
10,000,000
F
log
Frequency of logged events
4
Hz
T
log
Duration of a logged event
1 30000
Sec
2.2 Physical Specifications
Overall length (mm):
157
Overall width (mm):
86
Overall height (mm):
58
Weight (kg):
0.3
Mounting:
Screwed or 30mm DIN rail
Electrical connections:
56 x screwed terminals
Detailed dimensions of the Liftlog™XL case are provided in the following diagram (where all dimensions are shown in mm):
Figure 1: Case Dimensions
© CASWA Pty Ltd – 2013 6 | Page
2.3 Electrical Specifications
Parameter
Description
Min
Typ
Max
Units
Vin
Supply voltage
24
12
250
48
VAC
VDC
Iin
Supply current
40
100
mA
V
limit
Overload relay voltage
60
VAC
I
limit
Overload relay current
0.5 2
V
V
limit
Limit Switch input voltage
60
VAC
L
sense
mv load sensor sensitivity
0.5 10
mV/V
Rin
Input impedance of 0-10V input
1500 Ohms
I24
24V output current
100
mA
Operating temperature
-40 85
Note 2
°C
Notes:
1. Power supply –ve and GND pins are at chassis GND (0V) potential
2. Extended operation at maximum temperature will reduce the life the device.
2.4 Communication Specifications
Communications between the device and a host is usually via a Bluetooth radio link. The Bluetooth device name will be set to the Crane ID, the PIN is 0000.
For more details on the communication protocol used to communicate with the Liftlog™XL, see Appendix A.
© CASWA Pty Ltd – 2013 7 | Page
3 INSTALLATION DETAILS
3.1 Prior to Installation
Before installing your Liftlog™XL device visually inspect the unit and check that:
(a) the case is not damaged and fits together securely; (b) terminals are secure; (c) terminal numbering is as per section 3.3.1 (i.e. stickers have been correctly placed).
If you have chosen to install your own SIM card, then this should be inserted now. Details are provided in the following section.
The antenna can also be screwed into the front terminal now.
3.2 Inserting/Changing Your SIM Card
Remove the lid from the unit by releasing the clips at each end to reveal the internal circuit boards.
Locate the SIM card socket on the upper circuit board and insert a data SIM card into the socket shown. Push the card in fully so that it engages.
For details on what SIM cards are compatible with LiftlogXL see Appendix B: Communication Options.
Replace the cover.
3.3 Wiring Details
For the Liftlog™XL to operate the following must be connected as a minimum:
a. Power supply; plus b. 1 or more inputs (motion, limit or load cell).
The following additional types or inputs are optional:
Up to 15 motion inputs; and/or Up to 9 limit inputs; and/or Up to 2 load cells (of any type); and/or 2 Fault outputs.
© CASWA Pty Ltd – 2013 8 | Page
3.3.1 Terminals
Please note that the terminals of Liftlog™XL have changed slightly for different versions of the product. Label descriptions have also been altered slightly.
Sticker orientations showing terminals, for Liftlog™XL devices with serial numbers that start with a ‘2-’ (i.e. numbers greater than 199) are as follows:
Figure 2: Version 2 Sticker Orientations
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52
© CASWA Pty Ltd 2013 9 | Page
The following table describes each terminal on Liftlog™XL units that have serial numbers starting with a ‘2-’ (i.e. greater than 199).
Terminal Number
Description
Label
1.
Negative reference for mV, mA and V sensors (black wire on RC-3 or RC-5 rope clamps)
GND
2.
-ve sense input for MAIN Hook strain gauge (mV) load cell/pin (white wire on RC-3 or RC-5 rope clamps)
-
MAIN
3.
+ve sense input for MAIN Hook strain gauge (mV) load cell/pin (green wire on RC-3 or RC-5 rope clamps)
+
4.
Excitation voltage (3.3V) for MAIN hook strain gauge (mv) load cell/pin (red wire on RC-3 or RC-5 rope clamps)
XCite
5.
Return connection for MAIN Hook 4-20mA strain gauge (mA) load cell/pin, or output from load display
4-20mA
6.
0-10V input for MAIN hook from loadcell/pin amplifier or Konecranes Control­Pro
0-10V
7.
Connection for MAIN hook to terminal Q, F1, or F2, on an ABUS LIS
Q-Link +
8.
Connection for MAIN hook to Ground on an ABUS LIS
Q-Link -
9.
Drive voltage for 4-20mA sensor
24V
10.
Auxiliary inputs 1-3 can be used for any function (e.g. magnets, twist locks etc.) All are AC inputs across the range 48-240VAC Aux1
11.
Aux2
12.
Aux3
13.
AC input indicating East-West motion is fast
E-W Fast
14.
AC input indicating West Travel
West
15.
AC input indicating East Travel
East
16.
AC input indicating North-South travel is fast
N-S Fast
17.
AC input indicating South Travel
South
18.
AC input indicating North Travel
North
19.
AC input indicating AUX Hook up/down is fast
Fast
AUX
20.
AC input indicating AUX hook lowering
Down
21.
AC input indicating AUX hook raising
Up
22.
AC input indicating MAIN Hook up/down is fast
Fast
MAIN
23.
AC input indicating MAIN hook lowering
Down
24.
AC input indicating MAIN hook raising
Up
25.
Neutral (0VAC) power connection
0V AC
26.
Live (48-240VAC) power connection
24-240V AC
27.
Shield/0V
GND
© CASWA Pty Ltd – 2013 10 | Page
28.
0-10V input for AUX hook from loadcell/pin amplifier or Konecranes Control­pro
0-10V
AUX
29.
Return connection for AUX hook 4-20mA strain gauge (mA) load cell/pin, or output from load display
4-20mA
30.
Excitation voltage (3.3V) for AUX hook strain gauge (mv) load cell/pin (red wire on RC-3 or RC-5 rope clamps)
XCite
31.
+ve sense input for AUX Hook strain gauge (mV) load cell/pin (green wire on RC-3 or RC-5 rope clamps)
+
32.
-ve sense input for AUX Hook strain gauge (mV) load cell/pin (white wire on RC-3 or RC-5 rope clamps)
-
33.
GND negative reference for mV, mA, and V sensors (black wire on RC-3 or RC­5 rope clamps)
GND
34.
Connection for AUX hook to gnd on an ABUS LIS
- Q-Link
35.
Connection for AUX hook to terminal Q, F1, or F2, on an ABUS LIS.
+Q-Link
36.
Drive voltage for 4-20mA sensor
24V
37.
Opto-isolated limit input, can be used for any limit function AUX2
38.
AUX2
39.
Opto-isolated limit input, can be used for any limit function AUX1
40.
AUX1
41.
Opto-isolated side pull input for AUX Hook. Connect across up inputs on SideWise signal processor.
SidePull
AUX Limits
42.
SidePull
43.
Opto-isolated ultimate limit input for AUX Hook. Top
44.
Top
45.
Opto-isolated side pull input for MAIN Hook. Connect across up inputs on SideWise signal processor.
SidePull
MAIN Limits
46.
SidePull
47.
Opto-isolated ultimate limit input for MAIN Hook. Top
48.
Top
49.
AUX hook load limit output 48-240VAC 4A NO/NC Fault2
50.
Fault2
51.
MAIN hook load limit output 48-240VAC 4A NO/NC Fault1
52.
Fault1
© CASWA Pty Ltd – 2013 11 | Page
3.3.2 Connecting the Power Supply
Series 2 Liftlog™XL is designed to operate from 24-240VAC grounded neutral. (Note: Series 1 units could only operate from 48-240VAC.)
It can also operate from 12-48VDC, however this is not preferred as load limits cannot be used in this configuration. For more information on driving the Liftlog™XL from a DC power source, contact
tech@caswa.com.
Liftlog™XL requires constant power so that it can maintain a connection to the 3G/GPRS network.
Do not connect the unit after the K1 or E-Stop relay. Doing so will cause erratic behaviour and
premature failure of the Liftlog™XL electronics.
3.3.2.1 Using an AC Power Source
To connect an AC source from 24-240VAC wire active and neutral as follows.
LiftlogXL
25: 0VAC
#
26: 24-240VAC
24-240VAC (Active)
24-240VAC
Power Supply
0V (Neutral)
Notes:
#
All pins marked as ‘GND’ are connected
internally to pin 25, 0VAC.
Figure 3: Connecting an AC Power Source
© CASWA Pty Ltd – 2013 12 | Page
3.3.2.2 Using a DC Power Source
To connect a DC source from 12-24VDC wire active and neutral as follows.
It is important to remember that when powering the Liftlog™XL from a DC source, that it may not be
possible to use the load limiting functions of the Liftlog™XL as the outputs only switch AC.
LiftlogXL
25,27: 0VAC
#
9,36: 24V
12-24VDC
0V (Neutral)
Notes:
#
All pins marked as ‘GND’ are connected
internally to pin 25, 0VAC.
12-24V DC
Power Supply
Figure 4: Connecting a DC Power Source
© CASWA Pty Ltd – 2013 13 | Page
3.3.3 Connecting Motion Inputs
Motion input pins (Aux1, Aux2, Aux3, E-W Fast, West, East, N-S Fast, South and North) must be connected to GND or 0VAC (pins 1, 25, 27, 33) by a set of voltage independent contacts. Where spare or auxiliary contacts are not available on the MAIN contactors, small relays must be employed.
For example, the DOWN and UP inputs on the Auxiliary hoist would be connected as follows:
LiftlogXL
25, 1, 27, 33: GND
21: Aux UP
20: Aux DOWN
D U
To existing control
circuitry
0V
Figure 5: Connecting Motion Inputs
© CASWA Pty Ltd – 2013 14 | Page
3.3.4 Connecting Limit Inputs
There are two input pins for each limit input (e.g. Pins 45 and 46 for the Main hoist SidePull limit). Each input pair should be connected across the limit switch, or chain of limit switches, to be monitored. All limit inputs are voltage independent and typically configured to be normally closed (i.e. any voltage across these terminals keep the limit from activating).
For example, the Main Hoist SidePull limit would be connected as follows:
LiftlogXL
45: MAIN SidePull
MAIN hoist
SidePull Sensor
46: MAIN SidePull
Figure 6: Connecting Limit Inputs
© CASWA Pty Ltd – 2013 15 | Page
3.3.5 Connecting Load Sensor Inputs
The Liftlog™XL supports two load sensor inputs (marked MAIN and AUX) of various types:
a) Strain gauge input (e.g. CASWA rope clamp load cell); b) 4-20mA input; c) 0-10V input; d) ABUS LIS Q, F1 or F2 inputs.
The load sensor for the MAIN hoist is connected to pins 1-7, the load sensor for the auxiliary hoist connects to pins 28-34.
It can also accept wireless inputs for both the MAIN and AUX hooks via HoistNet.
3.3.5.1 Strain gauge input
When using a strain gauge load cell to measure the load on either the MAIN or the AUX hooks, all four wires from the strain gauge need to be connected. For the MAIN hook, these should be connected as follows:
The AUX hook can be connected in the same way using pins 30 to 33.
LiftlogXL
3: +
2: -
1: GND
4: +XCite
Green
Black
Red
White
Notes: Colour codes are for CASWA supplied rope clamp load cells.
Figure 7: Connecting a Strain Gauge Input
© CASWA Pty Ltd – 2013 16 | Page
3.3.5.2 4-20mA load sensor input
When using a 4-20mA signal to monitor the load, connect the load sensor between pins 5 and 9 for the MAIN hoist and pins 29 and 36 for the AUX hoist.
3.3.5.3 0-10V Load Sensor
When using a 0-10V signal to monitor the load (e.g. from a Konecranes ControlPro), connect the load sensor between pins 1 (or any other pin marked GND) and 6 for the MAIN hoist and pins 33 and 28 for the AUX hoist.
4-20mA
Load Sensor
on MAIN hook
LiftlogXL
5: 4-20mA
9: 24V
0-10V Signal
for MAIN hook
(External device, Amp etc)
LiftlogXL
1: GND
6: 0-10V
Figure 8: Connecting a 4-20mA Input
Figure 9: Connecting a 0-10V Load Input
© CASWA Pty Ltd – 2013 17 | Page
3.3.5.4 ABUS LIS Q or Frequency Input
Liftlog™XL will also accept a load signal from either the Q, F1 or F2 terminals of an ABUS LIS. This has
the advantage of not requiring a separate calibration of the load signal.
In this scenario the load signal from the ABUS LIS (marked as Q, F1 or F2) is connected into the ‘Q-
Link +’ terminal on the LiflogXL (pin marked 7 or 35 for the MAIN and AUX hoists respectively), whilst the ABUS LIS ground is connected into the ‘Q-Link-’ terminal (pin marked 8 or 34 for the MAIN and
AUX hoists respectively).
Connecting a signal for the MAIN hoist is depicted as follows:
3.3.6 Connecting the Fault Output
The two fault outputs (marked Fault1 and Fault2) are normally closed relays which open when an overload is detected. They are typically wired in series with the UP contactor coil. On a dual hoist crane an interposing relay may be required if both hoists are to be inhibited.
For example, connecting up the Fault2 output:
LiftlogXL
8: Q-Link -
7: Q-Link +
ABUS LIS
GND
Q, F1, F2
Figure 10: Connecting a Q-Link Input
LiftlogXL
49: Fault2 50: Fault2
Kx UP
Figure 11: Connecting the Fault Output
© CASWA Pty Ltd – 2013 18 | Page
4 COMMISSIONING DETAILS
Liftlog™XL is designed to be commissioned using a laptop computer. You will need a CASWA LINK-2 Bluetooth Modem and the Field Service Utility (FSU) software application loaded on a laptop.
4.1 Installing and Launching the FSU Application
4.1.1 FSU Program Installation
Ensure that your computer is switched on, connected to the internet and that the minimum required software versions are installed (see Appendix B: for minimum system requirements). Ensure that the LINK-2 modem is installed and that the drivers have loaded.
4.1.2 Installing the FSU application
The latest LINK-2 FSU software (Link-2_FSU) can be downloaded from
http://www.soledigital.com.au/Link2.html.
You should check this location regularly for updates.
4.1.3 Launching the application
Double click on the FSU program icon: .
© CASWA Pty Ltd – 2013 19 | Page
4.2 Connecting to the Device
The FSU will scan for Bluetooth enabled devices. This process takes approximately 10 seconds; when complete a list of all CASWA devices within range will be displayed.
If a particular Liftlog™XL unit is not found, ensure it is powered up and press <Look again> to repeat the search.
Version 2 Liftlog™XL devices are differentiated from version 1 devices by a 'II' superimposed over
the device icons.
NB: The Bluetooth link between the Laptop using a Link-2 and a Liftlog™XL has a range of approximately 200m.
Double-Click on the Liftlog™XL you wish to configure.
4.3 Checking for Firmware
After you have selected your desired Liftlog™XL, a connection will be made and the software will
check if the device has the current firmware. If a new firmware version is available the following window will pop up:
© CASWA Pty Ltd 2013 20 | Page
Press <Update> to update the Liftlog™XL to the latest available firmware version (recommended).
The new firmware will be installed on the device. DO NOT switch off the computer or remove the
LINK2 modem until this is complete – doing so may leave the Liftlog™XL in an unrecoverable state.
Alternatively, press <Not now> to update firmware at a later time.
NB: If you did not see this window, then your device already has the most current firmware.
4.4 Checking the Date/Time
After checking for firmware the FSU application verifies whether the Liftlog™XL has the same date/time as your computer.
If the times are not the same, the following pop up window will display on the screen:
Press <Yes> to update the devices date/time or press <No> to leave the date/time on the device as it is.
NB: If you did not see this window, then your device has the same date/time as your computer.
© CASWA Pty Ltd – 2013 21 | Page
4.5 General Tab
4.5.1 Setting Equipment Name
The only configurable item on the General page is the Equipment ID. This text can be up to 18 characters long and it is used to identify the crane in the reporting system. Whilst any name may be used, it is highly recommended that the XL be named according to the registration details provided at the time of purchase.
4.5.2 Upload Data to the Computer
Clicking the <Upload> button brings up a dialog asking where to save the data.
Enter the required file name (usually the crane name or serial number). Make sure the Location entry is set to “Storage card” and press <Save>.
Progress is indicated on the MAIN screen. Time to download depends on the number of lifts and can be up to 20 minutes.
4.6 Main and Aux Hoist Configuration
If your Liftlog™XL device has been preconfigured (only available with Abus inputs) or you are using a HoistNet load signal (which must be calibrated) then you will not need to calibrate the Liftlog™XL.
All other types of LiftlogXL inputs must be calibrated. Unless you are connecting the device to a Konecranes ControlPro (and elect to use the already calibrated ControlPro settings), this process will require test weights.
The process to configure the Main and Aux hoists is identical, as are the configuration screens.
Click on the Main or Aux tabs to bring up the load settings screens.
© CASWA Pty Ltd – 2013 22 | Page
4.6.1 Input Selection
Select the button that corresponds to the input you have connected to the Liftlog™XL . For connection details see section 3.3.5.
Hint: If the Auxiliary input is not used, it is strongly recommended that its input selection be set to 4­20mA as this input is relatively insensitive to electrical noise. If this is not done, motion data for this crane will often appear to be erroneous (as the sum of both hoists is displayed).
By default the input type for the Main Hoist is set to mV, whilst the Aux is set to 4-20mA.
4.6.2 Using/Removing a HoistNet Input
Liftlog™XL devices are now compatible with CASWA HoistNet. This means that they can obtain their load signal wirelessly from any other HoistNet enabled device, eliminating the need for long cable runs between the load cell and data logger.
NB: HoistNet was first enabled in FSU version 10.7. If you do not see the HoistNet option, then you are running an old FSU version. Download and reinstall the lastest version of CASWA FSU. You may also need to update the firmware on your Liftlog™XL.
To receive a load signal via HoistNet, select the HoistNet input and then press the <Bind> button:
A box will appear asking you which HoistNet enabled device you want to connect to:
Select the device that has the load signal to be used and press <OK>. The popup box will close.
© CASWA Pty Ltd – 2013 23 | Page
The name of the bound HoistNet device will be shown on the Main/Aux screen. The connection status will also be shown:
NB: You will need to ensure that the originating HoistNet device's load signal has been calibrated correctly.
To unbind a Liftlog™XL from a HoistNet device, or to change the bound device, press the <Bind> button on the Load screen and then select <Unbind> on the popup box.
4.6.3 Using the LiftlogXL with a ControlPro
If your LiftlogXL device is connected to a Konecranes ControlPro and you want to use the calibration settings stored on the ControlPro (rather than calibrating with test weights) press the <Control Pro> button.
A dialog box will appear asking you to confirm this action:
Press <OK> to confirm.
Another dialog box will appear.
© CASWA Pty Ltd – 2013 24 | Page
Enter the capacity of the hoist in tonnes and press <OK>. Your device is now calibrated and you will not need to zero or calibrate this hoist in order to use this Liftlog.
NB: You need to have selected the <0-10V> input type on the LiftlogXL and also check that the ControlPRO is set to output load on its analog output pins.
4.6.4 Checking the Gain
Irrespective of the indicated load (which is determined from the calibration), the signal indicator (bar below the load display) shows the absolute magnitude of the input signal.
Before undertaking a calibration, check the magnitude of the signal at near full load. It should be approximately 70-80% of the full scale reading.
If the signal is too large, the signal indicator will turn red and you should reduce the amplification applied to the signal by moving the gain slider to the left.
If the signal is less than half of full scale, then increase the amplification by moving the gain slider to the right.
4.6.5 Calibrating the Logger
With no load on the hook, press the <Zero> button.
After a brief pause the indicated load will show zero. Do not be concerned if the indicated load changes or is slightly higher than zero; in this state the indicated load is very sensitive to both electrical noise and very small changes in applied load.
Next, lift a known load with the crane. Ideally this load should be >80% of the crane’s lifting capacity.
Note: In practice, it is often not possible to arrange test weights for every install. Provided the input amplification has been set correctly (5.2.2), then an acceptable calibration may be performed with 30-50% of the cranes capacity. However, if this is done, the Liftlog™XL should then be recalibrated when the crane is next subject to a full load test.
With this known load lifted, press the <Cal> button. The FSU application will prompt you to enter the load. Do so and press <OK>.
After a brief pause the indicated load will match the load on the hook.
© CASWA Pty Ltd – 2013 25 | Page
4.6.6 Resetting the Calibration
Under some circumstances, it may be necessary to erase the calibration of a hoist.
Warning: IF YOU ERASE THE CALIBRATION THEN YOU WILL NEED A TEST WEIGHT TO SET IT AGAIN!
To reset the calibration for a hoist, tap the <!> button.
NB: Resetting the calibration of one hoist (MAIN or aux) does not affect the calibration of the other.
4.7 Comms Tab
4.7.1 3G configuration
This tab allows the configuration of the 3G connection used to send data.
The values for APN UserID and Password are usually provided by the company supplying the SIM card.
If the SIM card is provided by CASWA, then the settings are:
APN: telstra.m2m UserID: <blank> Password: <blank>
4.7.2 Link Status
Text at the bottom of the window will read either
“Powering Up”,“Searching”,”Logging in”, “Connected”, or “Sending Data” depending on the
state of the 3G connection. After power on, the Liftlog™XL will take up to two minutes to establish a connection to the 3G network. Once connected, any motion of the crane will cause the status to change to Sending Data”.
On the right of the window is a signal strength meter. NB: This meter is only updated when the Liftlog™XL status is “Connected”.
© CASWA Pty Ltd – 2013 26 | Page
4.8 Inputs and Limits
These two tabs show the status of each of the
Liftlog™XL’s input signals. They are intended to be used
to confirm the correct wiring of the unit.
When a signal is detected, the respective box will be checked.
4.8.1 Using XL devices with a HVDC IO Expander
If you have been supplied a Sole Digital HVDC10 module for installing a LiftlogXL on your 80-270VDC crane, check the <Use HVDC IO Expander> box. Otherwise leave it blank (default).
For more information on this option, contact CASWA for a detailed application note.
© CASWA Pty Ltd – 2013 27 | Page
4.8.2 Tuning Sensitivity and Noise Immunity
Very short duration events are often caused by noise; these may appear as very short duration input events. To remove these from the logged data set, adjust the value in the <Ignore inputs shorter than> dropdown box. The default output is 200mS (shortest option). Selecting a longer time period, will reduce the likelihood of recording spurious noise events, but also increases the risk that legitimate inputs will be erroneously ignored. Therefore it is recommended that this value only be increased when the current value is known to be insufficient at removing known noise events.
4.9 Overloads
The Overloads tab contains configuration settings for the behaviour of both Main, Aux and Combined overloads.
4.9.1 Main, Aux and Combined
In each of these boxes, enter the required overload in tonnes.
If only one load input is connected, it is recommended that the Aux and Combined overload be left at their default values.
4.9.2 Overload Sensitivity
Moving this slider changes the period of time that the hoist must be in an overload state before an overload event is triggered. It should always be set as far to the left as practical. Where electrical noise (K1 contactor closures are important to test), a rough runway or high vibrations are triggering false overload events, move the slider to the right to decrease the sensitivity.
4.9.3 Lockout
When an overload occurs, the fault output of the Liftlog™XL opens. When the load is reduced to a safe level, there is a delay of 3 seconds after which the fault output closes and allows lifting to continue.
© CASWA Pty Ltd – 2013 28 | Page
If the Lockout control is set to a non-zero value, when the indicated load exceeds <Overload>+Lockout% a special alert will be sent and the fault output will not close. This effectively disables the crane until it can be inspected and put back into service.
NB: The locked state can only be cleared by unchecking the “Locked” checkbox.
An Example:
Crane capacity: 10t Overload set to: 11t Lockout set to: 20%
Indicated load
Liftlog™XL behaviour
>=11t and < 13.3t
An overload alert is sent, and lifting is disabled until the indicated load drops below 11t
>=13.3t
An additional locked out alert is sent and lifting is disabled until a technician re-enables it by clearing the “Locked” checkbox.
4.10 SD Card Management
Select the SD Card tab to bring up the following screen:
4.10.1 Test SD Card
To test the card and verify that the LiftlogXL device it is correctly writing data to, and reading data from, its internal SD card, press the <Test Card> button.
A popup box will appear informing you of whether the Test Passed or Failed.
If the test fails, it is recommended that the SD card be removed and replaced to ensure it is seated securely. The test process should then be repeated. If the card fails again, then a reformat may be necessary.
© CASWA Pty Ltd – 2013 29 | Page
4.10.2 Reformat SD Card
If necessary, it is possible to delete all loading history from the LiftlogXL device by formatting the SD card. A typical example of where this is useful is when the test process has not been successful, or if the data logger is moved from one crane to another and prior data on the device is no longer applicable.
Configuration and load calibration settings are not affected by reformatting the card. To delete/change these settings, go to sections 4.5 through 0 of this manual.
Hint: Prior to reformatting, it is recommended that data be downloaded from the device as detailed in section 4.5.2.
To erase the onboard memory card, press the <Reformat Card> button. You will be asked to confirm the action.
4.11 Running CheckIt Diagnostics
To confirm whether critical settings and parameters have been set sensibly, after completing the
setup and commissioning of the Liftlog™XL device, it is strongly recommended that you run CheckIt
diagnostics (first introduced in version 11.9 of the FSU application).
To initiate CheckIt Diagnostics, go to the General Tab and click on the check box in the lower left corner of the tab:
A new window will appear and CheckIt Diagnostics will be initiated.
During this process you may be asked to enter parameters (e.g. rated capacity of the hoist) to verify that critical settings have been entered and have saved correctly.
Any potential issues or irregularities will be described in the CheckIt Diagnostics window. A summary of these will also be sent to the server for future reference.
Press <Close> to return to the main FSU screen.
© CASWA Pty Ltd – 2013 30 | Page
4.12 Recording a Service
Liftlog™XL data logs can now incorporate a history of maintenance performed on the crane.
To record that a service has been conducted, select the Service tab on the FSU Application. (Hint: You may need to scroll through the tabs to see it.)
Enter the relevant reference number for the work (e.g. from your maintenance management system or job sheet) in the Reference/Job No field.
Press the <Record Service> button to record the date/time that this particular work was conducted. This maintenance history is then accessed via the online interface.
© CASWA Pty Ltd – 2013 31 | Page
5 ROUTINE MAINTENANCE
There is no routine maintenance required for this device.
© CASWA Pty Ltd – 2013 32 | Page
6 OPERATING LIFTLOG™XL
6.1 Operating Status
The LiftlogXL is fitted with 3 LEDs labelled Power, Connected and Overload. These are visible from the front of the unit.
Power LED : Illuminates whenever power is applied to the unit.
Connected LED: Flashes quickly while a GPRS/3G connection is being established.
Flashes every 3 seconds once connected.
Overload LED: Illuminates for a couple of seconds on start-up.
Flashes briefly once a second at other times to indicate normal operation. Illuminates continuously when either hoist exceeds it overload limit.
6.2 Accessing Your Data
Open a web browser (e.g. Internet Explorer) and type in the URL you have been given into the address box. If you have not received a URL (web address) that can be used to connect to your data, please contact tech@caswa.com.
A screen similar to the following will appear, that reflects all cranes with Liftlog™XL devices installed,
for which you have access rights. If the individual pieces of equipment are not visible, click on the icons on the left hand side to show the equipment belonging to that group (site, equipment class etc).
© CASWA Pty Ltd – 2013 33 | Page
Select the name of the crane/hook you wish to interrogate.
A variety of information is available via this screen to extract data, present data via charts/graphs and further configure the device’s reporting features.
Events data: This shows the date/time (mm/dd/yyyy format), type of event and if an AccessPack is also installed on the equipment, the name of the responsible person using the crane at the time of the event.
Logs: This shows the full list of all logged events recorded by this LiftlogXL. Data includes date/time, hook (1 or 2), tons lifted, sec (duration of event), direction of motion and if an AccessPack is also installed on the equipment, the name of the responsible person using the crane at the time of the event.
Settings: This allows the user to set what type of events will trigger an automatic email. These settings do not affect what data is recorded.
Service History: This shows a list of all service date/times and their respective job numbers that have been logged via Liftlog™XL devices using the CASWA FSU interface.
Graphs: A number of automated summary graphs are accessible via this interface, including graphs showing Load Spectrum, Remaining Life, Moves Per Month and Average Move Duration. To request a new graph, please contact tech@caswa.com or your local Liftlog™XL supplier.
6.2.1 Downloading Data
To download any data, select the desired token (e.g. Logs, Events, Service History etc).
Press the Excel icon that is located just under the table on the right hand side.
Another window will then pop-up for you to select desired date range for your data. Select the start and end dates using the calendars.
Press the <Save> button. You will be asked for a location to save the data.
The format of the downloaded Log data is provided in Appendix D.
© CASWA Pty Ltd – 2013 34 | Page
8 TROUBLESHOOTING
Fault
Cause
Fix
Intermittent connection between XL and Link2 during commissioning
Intermittent power supply
Ensure power has not been supplied after the K1 or E-Stop relay. If so, rewire to supply constant power. Failure to do so will cause the electronics to fail very quickly.
Blue LED not flashing / No data being sent
Incorrect APN
Connect with FSU and verify the information contained under the ‘Comms’ tab
No GPS signal
Check if mobile phone coverage is available at specific location (inside cabinet). Check antenna is connected securely but not over­tightened. If antenna has been over-tightened, the internal wiring may need to resoldered. Open case to check.
SIM Card expired
Check account
Erratic load readings
Noise on input signals
Check shielding on load cell and VSD cabling
Noise on unused channels
Set Aux load type as 4-20mA
Inputs on all the time
Active and neutral reversed
Check the power wiring
Inputs flickering
Ground on LiftlogXL not at 0V
Measure between the chassis and one for the LiftlogXL GND terminals, correct active and neutral wiring , ground control voltage transformer secondary, or ground LiftlogXL
Noise on cables (typically when the cable runs are long or there is a noisy VSD)
Fit 1Kohm, 1W termination resistors between the input terminal and GND.
No load indicated
Wrong input selected
Refer to section 4.6.5 to calibrate the input
Load input wired wrong
Refer to section 4.6.5 to calibrate the input
Insufficient gain
Refer to section 4.6.5 to calibrate the input
No Bluetooth connection between XL and Link2
XL is not powered up
Check that the Green Power LED is illuminated. If not, check power is connected correctly as per section 3.3.2.
Insufficient range
Move laptop closer to the LiftlogXL.
XL in confused state
Power cycle the LiftlogXL.
Faulty Link2 (very rare)
Check if possible to connect to another CASWA device. If not, then replace Link2.
Connection between XL and Link2 lost when E-Stop is pressed
Incorrectly connected power supply (after E-Stop relay)
Ensure power has not been supplied after the K1 or E-Stop relay. If so, rewire to supply constant power. Failure to do so will cause the electronics to fail very quickly.
Red LED not flickering during service but Green Power LED is on
System failure probably due to stopping a firmware update mid­stream (Very rare)
Return to manufacturer for repair.
No data visible on website but all LEDs indicating correct operation
Incorrect name or serial number on Liftlog™XL or in database
Check that Serial Number matches that on the outer case. If problem persists, contact
tech@caswa.com and supply details of device’s
Equipment name and Serial Number.
No email notifications of crane events
No events set to trigger an email
Check settings on website (settings tab) Incorrect email settings
Check settings on website (settings tab)
© CASWA Pty Ltd – 2012 35 | Page
Appendix A: COMMUNICATION PROTOCOL
The host sends single character commands to the device to write or query parameters.
Each command must be followed by a carriage return <CR>(ASCII 13).
Where the command is a query command, no arguments are sent and the device will respond with a
single line (except for the “u” and “E” commands) the requested value in ASCI text followed by a
<CR>. Where the command is a set command, an argument may be included between the command and the <CR> .
Where numbers are sent or received, they are sent as clear text; eg “1234”
Where a number represents a load (eg the “o” and “O” commands, and the logged data returned by the “u” command), it is expressed in 100Kg units. Eg 3.5mt would be sent and received as 35.
Where a number represents an elapsed time (eg in the logged data returned by the “u” command) it
is expressed in 0.1second units. Eg. 35.4 seconds would be sent as 354.
Where dates-time values are sent or received, they are sent in the format dd/mm/yy hh:mm . Hours are in 24 hour clock format. Leading zeros must be used. Eg 3/8/07 13:30 is an invalid datetime and should be sent as 03/08/07 13:30
© CASWA Pty Ltd – 2012 36 | Page
Communication commands:
Command
R/W
Description
Example
v
Read
Query the firmware version number.
Send:v<CR> Rcv:1.02b<CR>
?
Read
Display a summary of all settings
h
Read
Query the input mode: 0=Analog 1=Q-Link 2=Frequency
Send:h<CR> Rcv:2<CR>
H
Write
Set the input mode
Send:H0<CR>
r
Read
Query the raw loadpin reading. The lifted load may be computed from this value as (Raw­Zero)/Cal. See the ”C” command.
Send:r<CR> Rcv: 354<CR>
i
Read
Query the device ID.
Send: i<CR> Rcv: crane34<CR>
I
Write
Set the device ID. Device ID’s are limited to 18 characters
Send: Icrane45<CR>
z
Read
Query the zero parameter The zero value is used to calculate the actual load. See the “C”, and “r” commands/
Send: z<CR> Rcv: 34<CR>
Z
Write
Set the zero parameter.
Send: Z23<CR>
c
Read
Query the cal parameter. The cal parameter is used to calculate the actual load. See the “C” and “r” commands
Send: c<CR> Rcv: 11<CR>
C
Write
Set the cal parameter. In normal operation, the cal parameter would be set as follows:
Send the “r” command to get the raw
reading from the load pin in it’s unloaded state.
Send the “Z” command to set the zero
parameter
Apply a known load to the pin. Send the “r” command to get the raw
reading from the load pin.
Sent the “C” command to set the
calibration value to (Rawunloaded­zero)*Known_Load (in 100Kg units)
Send: C9<CR>
on
Read
Query the overload (setpoint) parameter. This parameter is stored in 100Kg units, eg 3.5mt is expressed as 35. It is used by the device to determine when an overload occurs.
Send: o1<CR> Rcv: 35<CR>
On
Write
Set the overload parameter.
Send: O140<CR>
wn
Read
Query the inverted status of a setpoint output. A return value of 1 means the output is normally open.
Send: w2<CR> Rcv: 1<CR>
Wn
Write
Set the inverted status of a setpoint output.
Send: W20<CR>
*
Write
Reboot the device. This command is usually only used to load new firmware onto the device
Send: *<CR>
© CASWA Pty Ltd – 2012 37 | Page
Appendix B: COMMUNICATION OPTIONS
When purchasing a SIM card for use with the Liftlog™XL system please ensure:
1. The pre or postpaid plan includes data access. Voice only SIM cards will not work with the
Liftlog XL.
2. That you obtain the network name, User ID, and Password required for connection to the
carriers network.
Many carriers do not require a User ID or Password. However, at a minimum, most require that you
configure the Liftlog™XL with the network name. Details on how to do this are provided in this User
Guide.
B.1 How Much Data?
When choosing a mobile service plan for use with LiftlogXL, select the one with the lowest available monthly data limit. A VERY busy crane will generate around 1 megabyte of data per month. Some carriers offer low cost options for telemetry applications. It is worth investigating these.
B.2 Australian Carriers
A list of Australian mobile network service providers and some suggested network name, user ID and Password combinations are provided below. Blank entries in the table mean that the entry should be left blank.
Carrier
APN
USERNAME
PASSWORD
Telstra prepaid
telstra.internet
Optus Business
yesbusiness
Telstra 3G (as supplied by CASWA)
telstra.m2m
© CASWA Pty Ltd – 2012 38 | Page
Appendix C: FSU SYSTEM REQUIREMENTS
The minimum requirements for operating CASWA’s Field Service Utility (FSU) and Link-2 Bluetooth modem are:
Laptop computer running Windows XP SP3 or later; One Spare USB port; Microsoft .NET framework 3.5.
© CASWA Pty Ltd – 2012 39 | Page
Appendix D: DATA FILE FORMAT
Data is recorded each time a motion is detected (a contactor closes). Each datum set contains:
1. Date/Time (based on the logger’s internal clock – when a user connects to the logger via
Bluetooth using the FSU software, the time is compared to the time on the laptop and can be reset)
2. Operator (only used if a logger is bound to an AccessPack)
3. Hook (1 = main, 2 = Aux, 3 = Both hooks)
4. Load from load cell/other input in tenths of a tonne
5. Duration of motion in tenths of a second
6. Motion code – type of motion as shown in the following table.
Motion Code
Motion
0
No move
1
Move Up
2
Move Down
4
Move Fast
8
Move East
16
Move West
32
Move North
64
Move South
128
Move Up Fast
256
Move Aux1 / Aux
512
Move Aux2 / Magnet
1024
Move Aux3/Override
2048
Move Aux1 Off
4096
Move Aux2/Magnet Off
8192
Move Aux3/Override Off
Note: If a combined motion is detected, then the sum of the individual motions is recorded (e.g. Move Up and Move Fast = 1+4=5).