Solcon RVS-DX 8, RVS-DX 85, RVS-DX 17, RVS-DX 58, RVS-DX 72 Instruction Manual

...
R
R
V
V
S
S--
D
D
X
X
DDiiggiittaallSSooffttSSttaarrtteerrwwiitthhiinntteerrnnaallBByyPPaasss
s
88--11110000AA,,222200--669900V
V
IInnssttrruuccttiioonnMMaannuuaal
l
1B
Ver. 26/12/2012
2 • Table of content
__________________________________________________________________________________
RVS-DX Instruction Manual
1. TABLE OF CONTENT
1. Table of content ........................................................................................................................ 2
2. Safety & Warnings .................................................................................................................... 4
2.1 Safety .......................................................................................................................................... 4
2.2 Attention ...................................................................................................................................... 4
2.3 Warnings ..................................................................................................................................... 4
3. Technical Data .......................................................................................................................... 5
3.1 Introduction ................................................................................................................................. 5
3.2 Rating and frames sizes ............................................................................................................. 5
3.3 Starter Selection ......................................................................................................................... 5
3.3.1 Motor current & Starting Conditions ................................................................................ 5
3.3.2 Mains Voltage (line to line) .............................................................................................. 6
3.3.3 Control Voltage ............................................................................................................... 6
3.3.4 Other Options .................................................................................................................. 6
3.3.5 Starter selection tables for various voltage ratings. ........................................................ 6
3.3.5.1 Starter selection for 230V, 400V, 480V, 600V ......................................................... 6
3.3.6 Ordering Information ....................................................................................................... 7
4. Recommended Wiring Scheme ............................................................................................... 8
4.1 Typical wiring diagram ................................................................................................................ 8
4.2 Power wiring scheme for Inside-DeltaConnection .................................................................. 9
4.3 Wiring Notes ............................................................................................................................... 9
4.3.1 Short Circuit Protection ................................................................................................. 10
4.3.2 Transient Protection ...................................................................................................... 10
4.3.3 Control Supply (Terminals A1, A2) ................................................................................
10
4.3.4 S
tart/Stop (or
4.3.4momentary start) Input (terminal B1) .............................................. 10
4.3.5 Aux. Input (terminal C1) ................................................................................................ 11
4.3.6 Auxiliary output relay (terminals 13, 14) ........................................................................ 11
4.3.7 Fault Contact (terminals 23, 24) .................................................................................... 11
4.3.8 Options description ....................................................................................................... 11
4.3.8.1 Analogue I/O (option # 5) (terminals T1, T2, Gnd, Out (-), Out (+)) ...................... 11
4.3.8.2 RS-485 Communication (option # 3M) (terminals out(-),Out(+)) ........................... 12
4.3.9 “Inside-Delta” mode ....................................................................................................... 12
4.3.9.1 General information ................................................................................................ 12
4.3.9.2 Notes on “Inside Delta” connection ........................................................................ 13
5. Dimensions ............................................................................................................................. 14
6. Installation ............................................................................................................................... 18
6.1 Prior to Installation .................................................................................................................... 18
6.2 Mounting ................................................................................................................................... 18
6.3 Temperature range & heat dissipation ...................................................................................... 18
6.3.1 Calculating the enclosure size, for non-ventilated metallic enclosure ........................... 18
6.3.2 Additional Ventilation ..................................................................................................... 19
6.3.3 UL, cUL Installation Instructions .................................................................................... 19
7. Control Keypad ....................................................................................................................... 20
7.1 LCD Arrangement ..................................................................................................................... 20
7.2 Push-buttons .............................................................................................................................
20
7.3 S
tatus LEDs. ............................................................................................................................. 21
7.4 Reviewing and Modifying Parameters ...................................................................................... 21
7.5 Special Actions Performed in TEST/MAINTENANCE Mode ....................................................
21
7.5.1 R
un Self Test ................................................................................................................ 21
7.5.2 View Software Version .................................................................................................. 21
3 • Table of content
__________________________________________________________________________________________
2551B7.5.3 Obtain Default Parameters ............................................................................................ 22
2552B7.5.4 Reset Statistical Data .................................................................................................... 22
2553B7.5.5 Calibrate Voltage, Current and (Factory Use Only!) ................................................... 23
2524B7.6 Mode Pages .............................................................................................................................. 23
2554B7.6.1 Overview of All Mode Pages and Factory Defaults ....................................................... 24
2555B7.6.2 Display Mode – page 0 ................................................................................................. 26
2556B7.6.3 Main Parameters – page 1 ............................................................................................ 27
2582B7.6.3.1 Tripping Curves of the Integrated Overload Protection .......................................... 30
2557B7.6.4 Start Parameters – page 2 ............................................................................................ 31
2583B7.6.4.1 Soft start parameters .............................................................................................. 34
2558B7.6.5 Stop Parameters – page 3 ............................................................................................ 35
2584B7.6.5.1 Soft stop parameters .............................................................................................. 35
2559B7.6.6 Dual Adjustment Parameters – page 4 ......................................................................... 37
2560B7.6.7 Special features Parameters – page 5 .......................................................................... 38
2585B7.6.7.1 WIDER SETTINGS Parameters: ............................................................................ 39
2561B7.6.8 Fault Parameters – page 6 ............................................................................................ 40
2562B7.6.9 I/O Programming Parameters – page 7 ........................................................................ 42
2586B7.6.9.1 PROG. INPUT C1 .................................................................................................. 43
2563B7.6.10 Comm. Parameters – page 8- Applicable with Optional Modbus & DeviceNet Comm. 44
2564B7.6.11 Comm. Parameters – page 8 - Applicable with Optional Profibus Comm. .................... 45
2565B7.6.12 Statistical Data – page 9 ............................................................................................... 46
2525B7.7 Non adjustable protection anf fault Resetting ........................................................................... 46
2566B7.7.1 Phase loss (and Under / Over Frequency) .................................................................... 46
2567B7.7.2 Phase Sequence ........................................................................................................... 47
2568B7.7.3 Shorted SCR or Wrong Connections ............................................................................ 47
2569B7.7.4 Heat-sink Over Temperature ......................................................................................... 47
2570B7.7.5 External Fault ................................................................................................................ 47
2571B7.7.6 Fault and Reset ............................................................................................................. 47
2572B7.7.7 Auto Reset .................................................................................................................... 47
2526B7.8 Timing Occurrence Table ......................................................................................................... 48
2504B8. STARTING PROCEDURE ....................................................................................................... 49
2527B8.1 Setting control voltage on-site RVS-DX8A-310A ...................................................................... 49
2528B8.2 Standard starting procedure ..................................................................................................... 50
2529B8.3 Examples of starting curves ...................................................................................................... 51
2573B8.3.1 Light Loads-Pumps, Fans, etc. ..................................................................................... 51
2574B8.3.2 High Inertia Loads – Fans, Centrifuges, etc .................................................................. 51
2575B8.3.3 Special starting – Using Dual Adjustment ..................................................................... 52
2587B8.3.3.1 Special starting – Using Dual Adjustment – wiring scheme ................................... 53
2576B8.3.4 Choosing a suitable Pump Curve (centrifugal Pumps) ................................................. 53
2588B8.3.4.1 Starting Curve ........................................................................................................ 53
2589B8.3.4.2 Stopping Curve ...................................................................................................... 54
2590B8.3.4.3 Final torque during soft-stopping a pump motor .................................................... 54
2505B9. TROUBLE SHOOTING ............................................................................................................ 55
2530B9.1 Blank RMA Form ...................................................................................................................... 58
2506B10. TECHNICAL SPECIFICATIONS: ............................................................................................ 59
4 Safety & Warnings
__________________________________________________________________________________
2. SAFETY & WARNINGS
2.1 Safety
1
Read this manual carefully before operating the equipment and follow its instructions.
2
Installation, operation and maintenance should be in strict accordance
with this manual, national codes and good practice.
3
Installation or operation not performed in strict accordance with these instructions will void manufacturer’s warranty.
4
Disconnect all power inputs before servicing the soft-starter and/or the motor.
5
After installation, check and verify that no parts (bolts, washers, etc) have fallen into the starter.
6
During shipping, the soft-starter might have been roughly handled,
therefore, it is recommended to initialize the soft-starter by connecting
supply voltage prior to operating the soft-starter with a motor
2.2 Attention
1
This product was designed for compliance with IEC 947-4-2 for class A equipment.
2
RVS-DX 8 - 170 are UL and cUL approved. RVS-DX 210 - 1100 are designed to meet UL and cUL requirements.
3
Use of the product in domestic environments may cause radio interference, in which case, the user may be required to employ
additional mitigation methods.
4
Utilization category is AC-53a or AC53b, Form 1. For further information,
see Technical Specification
2.3 Warnings
1
Internal components and PCBs are at mains potential when the RVS-DX
is connected to mains. This voltage is extremely dangerous and will
cause death or severe injury if contacted.
2
When RVS-DX is connected to mains, even if control voltage is
disconnected and motor is stopped, full voltage may appear on starter’s
output and motor’s terminals.
3
The starter must be grounded to ensure correct operation, safety and to prevent damage.
4
Check that Power Factor capacitors and overvoltage devices are not
connected to the output side of the soft starter. If PF capacitors are used, they must be connected on the line side of the RVS-DX . If a main contactor is used in combination with RVS-DX, the capacitors
must be disconnected from RVS-DX when contactor is open.
5
Do not interchange line and load connections
The company reserves the right to make any improvements or modifications to its products without prior notice.
5 • Technica l Da ta
___________________________________________________________________________________________
3. TECHNICAL DATA
3.1 Introduction
The RVS-DX is a third generation, highly sophisticated and reliable starter designed for use with standard three-phase, three-wire, squirrel cage, induction motors. It provides the best method of reducing current and torque during motor starting. The RVS-DX starts the motor by supplying a slowly increasing voltage, providing soft start and smooth acceleration, while drawing the minimum current necessary to start the motor. The RVS-DX is equipped with internal by-pass controlled by its micro-controller. The by-pass closes after the end of the starting process, thus reducing heating and saving power.
3.2 Rating and frames sizes
Starter type
Starter
FLC
[A]
Frame
Size
Dimensions
WxHxD
[mm]
Weight
[Kg]
RVS-DX 8
8
D1
120x232x122
3.0
RVS-DX 17
17
D1
120x232x122
3.0
RVS-DX 31
31
D1
120x232x122
3.0
RVS-DX 44
44
D1
120x232x122
3.0
RVS-DX 58
58
D2
129x275x182
5.2
RVS-DX 72
72
D2
129x275x182
5.2
RVS-DX 85
85
D3
129x380x182
8.5
RVS-DX 105
105
D3
129x380x182
8.5
RVS-DX 145
145
D4
172x380x192
12.5
RVS-DX 170
170
D4
172x380x192
12.5
RVS-DX 210
210
D5
380x455x295
30.2
RVS-DX 310
310
D5
380x455x295
30.2
RVS-DX 390
390
D6
350x550x310
55
RVS-DX 460
460
D7
460x600x319
65
RVS-DX 580
580
D8
460x643x319
75
RVS-DX 650
650
D8
460x643x318
80
RVS-DX 820
820
D8
460x643x318
90
RVS-DX 950
950
D9
560x833x334
100
RVS-DX 1100
1100
D9
560x833x334
100
3.3 Starter Selection The starter should be selected in accordance with the following criteria:
3.3.1 Motor current & Starting Conditions
Select the starter according to motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if the motor will not be fully loaded). The RVS-DX is designed to operate under the following maximum conditions:
Ambient
Temperature
[0C]
Starting Current
[A]
Acceleration Time
[sec]
40
300%xIn
30
350%xIn
20
400%xIn
5
Max. Starts per Hour: four (4) starts per hour at maximum ratings and up to 10 starts per hour at light load applications (consult factory). Note: For very frequent starts (inching applications) the inching current should be considered as the Full Load Current (FLC) (consult factory).
Notes:
Refer to section 5 on page 14 for detailed dimensions.
6 • Technica l Da ta
________________________________________________________________________________________
3.3.2 Mains Voltage (line to line)
Four Main Voltage levels are available: 400V, 480V, 600V and 690V (690V only available for RVS-DX 390A and up).
Note:
400V applies for 230 to 400V.
3.3.3 Control Voltage
The Control Voltage (terminals A1(~) – A2 (N) operates the electronic circuitry and the bypass. Two voltage levels are available, selectable by internal jumper: 230VAC + 10%-15%, 50/60 Hz (standard) 115VAC+ 10%-15%, 50/60 Hz Refer to section
8.1 on page 49 for instructions on setting control voltages on site.
3.3.4 Other Options
More options are available for the RVS-DX. (Refer to section
3.3.6 on page 7.):
Communication, Analog card, harsh environment treatment, , Remote panel,UL & cUL approval .
3.3.5 Starter selection tables for various voltage ratings.
1
The starter selection table below concern standard, 1500r.p.m. 50Hz, three-phase motors.
2
These values are given for guidance and may vary according to motor manufacturer and depending on the number of poles.
3
It is the user’s responsibility to make sure that motor’s FLA will never exceed Starter’s FLC.
3.3.5.1 Starter selection for 230V, 400V, 480V, 600V
Note: C – Consult factory
Starter type
Starter
FLC
[A]
Motor
kW
@230V,
starter
“In-Line”
[kW]
Motor
kW
@230V,
starter
“Inside
Delta”
[kW]
Motor
kW
@400V,
starter
“In-Line”
[kW]
Motor
kW
@400V,
starter
“Inside
Delta”
[kW]
Motor
kW
@480V,
starter
“In-Line”
[kW]
Motor
kW
@480V,
starter
“Inside
Delta”
[kW]
Motor
kW
@600V,
starter
“In-Line”
[kW]
Motor
kW
@600V,
starter
“Inside
Delta”
[kW]
RVS-DX 8
8
1.5 3 3
6.5 4 8
5.5
9
RVS-DX 17
17 4 8 8 12.5 9 15
12.5
22
RVS-DX 31
31 8 15
15
25
18.5
30
25
40
RVS-DX 44
44
12.5
22
22
37
25
45
30
59
RVS-DX 58
58
15
30
25
51
37
59
45
80
RVS-DX 72
72
20
37
37
59
45
80
59
100
RVS-DX 85
85
25
40
45
80
55
90
59
110
RVS-DX 105
105
30
55
55
90
59
110
80
147
RVS-DX 145
145
40
75
75
132
90
160
110
200
RVS-DX 170
170
51
90
90
160
110
200
140
250
RVS-DX 210
210
59
110
110
184
140
220
160
295
RVS-DX 310
310
90
160
160
257
200
355
257
450
RVS-DX 390
390
110
200
200
355
257
475
315
560
RVS-DX 460
460
140
220
250
400
295
560
400
670
RVS-DX 580
580
180
315
315
560
400
670
500
RVS-DX 650
650 c c c c c c c c
RVS-DX 820
820
250
450
450
670
560 670
RVS-DX 950
950
295
500
500 670 -
RVS-DX 1100
1100
355
560
600 -
7 • Technica l Da ta
___________________________________________________________________________________________
3.3.6 Ordering Information
RVS-DX
31-
400-
230-
0-
S
Full load
Current
Mains Voltage
Control Voltage
Options
Front Panel
Full load Current
Specify
Description
Starter’s FLC [A]
8, 17, 31, 44, 58, 72, 85, 105, 145, 170, 210, 310, 390, 460, 580, 650, 820, 950, 1100
Mains Voltage
Specify
Description
400
230-400VAC + 10%-15%, 50/60 Hz
480
480VAC + 10%-15%, 50/60 Hz
600
600VAC + 10%-15%, 50/60 Hz
690
690VAC + 10%-15%, 50/60 Hz (690V only available for RVS-DX 390A and up)
Control Voltage
Specify
Description
115
115VAC + 10%-15%, 50/60 Hz
230
230VAC + 10%-15%, 50/60 Hz
Note:
Control voltage can be changed on site for RVS-DX up to 310A.
For RVS-DX 390A and up control voltage must be ordered from factory.
Options
Specify
Description
0
No options
3M
Communication RS-485 (MODBUS)
(1)
3P
Communication Profibus PCB (RVS-DX210-1100A)
(2)
3D
Communication RS-485 (MODBUS) and external DevieNet to Modbus Gateway
(1) (4)
5
Analog card – Thermistor in and Analog out
(1) (2)
8
Harsh environment treatment
D
Remote panel mounting replacing the original panel.( supplied with 1.5 m cable)
(3)
U
UL & cUL approval (RVS-DX8-170A mains voltage up to 600V)
Notes:
For more than one option indicate, for example: 8+5 (Harsh environment and
analog out)
Options must be factory installed.
(1)
From RVSDX-8A and up to RVS-DX44A - One option can be installed ­either Modbus communication (3M) or analog (5). From RVS-DX58A and up - both options 3M & 5 can be installed. Both options must be ordered as one package.
(2)
From RVS-DX210A and up - both options 3P & 5 can be installed. Both options must be ordered as one package.
(3)
Remote keypad option available for RVS-DX 58A and up.
Mains voltage of 690V only available for RVS-DX 390A and up.
(4)
External DeviceNet to Modbus Gateway is supplied when DeviceNet
communication link is ordered.
Front Panel
Specify
Description
S
Standard
Example: RVS-DX rated 820A, mains voltage- 230V, control voltage- 115V, Modbus communication card, Analog card, Harsh environment treatment and standard front panel:
RVS-DX 820 - 400 - 115 - 3M+5+8 – S
8 • Recommended Wiring Scheme
________________________________________________________________________________________
4. RECOMMENDED WIRING SCHEME
4.1 Typical wiring diagram
Notes:
(1) - Use fuses for type 2 coordination. Refer to section 4.3.1 on page 10
(2) - For Aux. input programming refer to section 7.6.9 on page 42 The use of solid state relays to control the digital inputs B1 and C1 is prohibited
(3) - For Aux. output programming refer to section 7.6.9 on page 42
(4) - Fault relay can function as a “Fault” relay or as a “Fail-Safe” relay. For Fault relay programming refer to section 7.6.9 on page 42
(5) - When emergency Stop switch is required it is recommended to trip a series contactor or the feeding circuit breaker. (Not shown)
(6) – Mains voltage of 230-600V available to all models. (need to be specified) Mains voltage of 690V only available for RVS-DX390A and up.
9 • Recommended Wiring Scheme
___________________________________________________________________________________________
4.2 Power wiring scheme for “Inside-Delta” Connection (Refer to section
4.3.9 on page 12)
Connecting RVS-DX INSIDE DELTA
Reverse speed with RVS-DX connected INSIDE DELTA.
Notes:
When installing the RVS-DX INSIDE DELTA. it is highly recommended to
use a line contactor (C1) or INSIDE DELTA. contactor (C2) in order to avoid
a destruction of the motor in case of a shorted SCR in the RVS-DX.
If a contactor is connected Inside the Delta (C2) only, motor terminals are “live” (full voltage) even when contactor is open.
4.3 88BWiring Notes
WARNINGS!
When mains voltage is connected to the RVS-DX, even if control voltage is
disconnected, full voltage may appear on the starter load terminals. Therefore, for isolation purposes, it is necessary to connect an isolating device
before the starter.
10 • Recommended Wiring Scheme
________________________________________________________________________________________
Power factor correction capacitors and overvoltage devices must not be
installed on starters load side. When required, install capacitors or overvoltage
devices on starter’s line side.
4.3.1 Short Circuit Protection
For “class 2 coordination”, protect the starter against a short circuit by thyristor Protection Fuses for I²t and fuses as in dictated in the following table:
Notes:
1. The above table is for maximum starting current of 400% of FLC, maximum starting time of 5 sec and rated voltage up to 690V V.
2. Rating may change with different external conditions such as ambient temperature, forced cooling etc. Refer to fuse manufacturer catalogs to confirm correct values.
4.3.2 Transient Protection
Line transient voltages can cause a malfunction of the starter and damage to the thyristors. All RVS-DX starters incorporate Metal Oxide Varistors (MOV) to protect from normal line voltage spikes.
When higher transients are expected, additional external protection should be used (consult factory).
4.3.3 Control Supply (Terminals A1, A2)
220-240V or 110-120V, 50/60Hz is required to power the electronic circuitry and the bypass. Factory set value is indicated on the starter’s side label. This voltage can be from a grounded or ungrounded mains system. In models up to 310A, voltage level 110V /220V can be changed in the field. (Refer to section
8.1 on
page 49)
4.3.4 Start/Stop (or
4.3.4momentary start) Input (terminal B1)
Input from a maintained contact. Close contact between A2 and B1 to soft start the motor. To stop the motor open the contact. If Deceleration time is set to a value other then 0 seconds the motor will soft stop. If Deceleration time is set to 0 seconds the motor will stop immediately. (Refer to section
7.6.5 on page
35) If Aux Input is set as Start / Stop, then terminal B1 is used as momentary N.O. Start input and input C1 is used as maintained N.C Stop input. (Refer to section
7.6.9 on page 42)
For emergency stop of the motor disconnect control voltage from A1, A2 terminals.
RVS-DX
Max.
thyristor
I2t [A2Sec]
BUSSMAN GEC ALSTOM SIBA
FERRAZ – SHAWMUT
(IEC Style 690/700V)
Rate
[A]
P/N
Rate
[A]
P/N
Rate
[A]
P/N
Rate
[A]
P/N
RVS – DX 8
400
30
FWP 30B
32
B210612
32
URD 000-32
RVS – DX 17
5,000
50
FWP 50B
63
B210615
63
6.6URD30D11A0063
RVS – DX 31
10,000
90
FWP 90B
100
V320063
100
6.6URD30D11A0100
RVS – DX 44
12,000
125
FWP 125A
100
X320063
100
6.6URD30D11A0100
RVS – DX 58
15,000
150
FWP 150A
125
X320065
125
6.6URD30D11A0125
RVS – DX 72
18,000
175
FWP 175A
160
B320069
200
SQB1-200
200
6.6URD30D11A0200
RVS – DX 85
40,000
200
FWP 200A
200
E320371
200
SQB1-200
200
6.6URD30D11A0200
RVS – DX 105
60,000
250
FWP 250A.
250
J320375
250
SQB1-250
250
6.6URD30D11A0250
RVS – DX 145
100,000
300
FWP 300A
315
M320079
315
SQB1-315
315
6.6URD30D11A0315
RVS – DX 170
140,000
400
FWP 400A
350
Y320480
350
SQB1-350
350
6.6URD30D11A0350
RVS – DX 210
200,000
500
FWP 500A
450
D320485
450
SQB1-450
450
6.6URD30D11A0450
RVS – DX 310
600,000
700
FWP 700A
630
H320489
630
SQB1-630
630
6.6URD31D11A0630
RVS – DX 390
700,000
700
FWP 700A
800
T320591
800
SQB1-800
800
6.6URD31D11A0800
RVS – DX 460
800,000
800
FWP 800A
900
V320592
900
SQB1-900
900
6.6URD32D11A0900
RVS – DX 580
1,200,000
1000
FWP 1000A
1000
W320593
900
SQB2-900
1000
6.6URD32D11A1000
RVS – DX 650 2,000,000 1200 FWP 1200A
2X 700
2X S320590
1100 SQB2-1100 1250
6.6URD33D11A1250
RVS – DX 820 2,000,000 1200 FWP 1200A
2X 700
2X S320590
1100 SQB2-1100 1250
6.6URD33D11A1250
RVS – DX 950 4,500,000
2X 1000
2X FWP 1000A
2X 900A
2X V320592
SQB2-1250 1600
6.6URD33D11A1600
RVS – DX 1100 4,500,000
2X 1000
2X FWP 1000A
2X 900A
2X V320592
SQB2-1250 1600
6.6URD33D11A1600
11 • Recommended Wiring Scheme
___________________________________________________________________________________________
4.3.5 Aux. Input (terminal C1)
Input from a maintained contact, connected between terminals A2 and C1 to operate as programmed input. Aux. Input can be programmed as one of six options:
(1) Dual Adjust (2) Generator Function (3) Slow Speed / Reverse (4) External fault (5) Remote reset after fault has been removed. (6) Start / Stop (terminal C1 can be used as a maintained N.C Stop input and terminal B1 as
momentary N.O. Start input – refer also to section
4.3.4 above.
For Aux. Input programming refer to section
7.6.9 on page 42.
4.3.6 Auxiliary output relay (terminals 13, 14)
Voltage free, N.O , 8A, 250VAC, 1800VA max. The contact incorporates 0-60 seconds On & Off delays. The auxiliary output relay can be programmed to operate in two modes:
1. IMMEDIATE - Close its contact at start signal (after programmed “on delay” time has elapsed) and open its contact at the end of deceleration time (if any) (after programmed “off delay” time has elapsed).
2. END OF ACCEL. - Close its contact at end of soft start (after programmed “on delay” time has elapsed) and open its contact at the beginning of soft stop (if any) (after programmed “off delay” time has elapsed). The relay contact will open also in case of a fault or upon control supply outage. This output is generally used to:
(1) Release the brake of a brake motor. (2) Interlocking with other systems. (3) Signalling.
For Aux. output programming refer to section
7.6.9 on page 42.
4.3.7 Fault Contact (terminals 23, 24)
Voltage free, N.O , 8A, 250VAC, 1800VA max. The contact changes its position upon fault and returns to its original position after fault has been removed and starter was reset. When disconnection of Control Supply the contacts will be closed. Fault relay can function as a “Fault” relay or as a “Fail-Safe” relay. For Fault relay programming refer to section
7.6.9 on page 42.
4.3.8 Options description
4.3.8.1 Analogue I/O (option # 5) (terminals T1, T2, Gnd, Out (-), Out (+))
The Analogue option incorporates two functions:
Thermistor input
Analogue output
Analogue P.C.B. layout
Thermistor input (terminals T1, T2)
Programmable as PTC or NTC type thermistor. Trip value is adjustable between 1-10K, preset delay of 2 Sec.
12 • Recommended Wiring Scheme
________________________________________________________________________________________
For thermistor input programming refer to section 7.6.8 on page 40.
Ground Terminal (terminal Gnd)
Connect thermistor and / or Analogue output shield to this ground terminal.
Analogue Output ( terminals Out (+), Out (-))
Dip switches allow selection between: 0-10VDC, 0-20mA, 4-20mA
Analogue value can be programmed via the key pad in I/O PROGRAMMING PARAMETERS page to one of the values as follows: (refer to section
7.6.9 on page 42.)
A. 0….200% of FLA (Default setting) B. 0….200% of Pn C. Power factor (POWER FACTOR & POWER measurement only available in RVS-DX58A and up)
Dip No.
4-20 mA*
0-20 mA
0-10VDC
Dip-Sw. S1 # 1
On
On
Off
Dip-Sw. S1 # 2
On
On
Off
Dip-Sw. S1 # 3
Off
Off
On
Dip-Sw. S1 # 4
Off
Off
On
Dip-Sw. S2 # 1
On
Off
Off
Dip-Sw. S2 # 2
No use
No use
No use
* Default
Notes:
It is important that the RVS-DX is properly grounded, and control module is tightly fastened to the power section.
Use twisted shielded cable for thermistor connection.
4.3.8.2 RS-485 Communication (option # 3M) (terminals out(-),Out(+))
Standard RS485, Half Duplex with MODBUS Protocol, baud rate 1200, 2400, 4800, 9600 BPS. Twisted shielded pair should be used, connect shield to ground a PLC/Computer side.Terminals (-) & (+)
must be wired to control supply for operation in communication mode. Leave terminal NC not connected. Note: When DeviceNet option is required an external device will be provided with the option. This gateway is connected via 2 wires to the optional Modbus terminals.
Refer to section 7.6.10 on page 44.
4.3.9 “Inside-Delta” mode
4.3.9.1 General information
When the RVS-DX is installed “Inside Delta”, the individual phases of the Starter are connected in series with the individual motor windings (6 conductor connections as with the star-delta starter). The soft starter must only conduct about 67 % (=1\1.5) of the rated motor current. This ensures the use of a significantly smaller device.
For example:
For a motor with a rated current of 155A motor, a 170A starter will be selected to operate “In-Line”. For “Inside Delta” starter, we calculate (155 x 67% = 104A) and select a 105A starter. Less heat dissipates in the cabinet vs. the standard “In-Line” connection.
13 • Recommended Wiring Scheme
___________________________________________________________________________________________
4.3.9.2 Notes on “Inside Delta” connection
“Inside Delta” requires 6-wire to the motor.
Wrong motor connection will cause serious damage to the motor windings.
When installing the RVS-DX “inside delta” it is highly recommended to use a contactor in
series to the RVS-DX or upstream (after motor protection) in order to avoid a destruction of the motor in case of a shorted SCR in the RVS-DX.
The sinusoidal shape of the current is imperfect (since each phase is separately fired and not influenced by other phase firing). As a result, higher harmonic content is incurred (THD), which can be as high as twice the THD value as in the standard “In-Line”.
Higher motor heating is expected for the same motor size (due to the higher THD).
Phase sequence must be correct; otherwise, “Phase Sequence fault” will trip the starter
immediately (without any damage).
Higher torques can not be obtained
Factory preset - features and functions when “Inside Delta” mode is configured:
o No Pulse Start. o No curve selection (Curve 0 !! only). o No Slow Speed o No Phase sequence “Off” mode
Note :
For a high starting torque process, it is recommended to use the starter in the “In Line” connection.
WARNINGS!
Beware!
Wrong connection of the starter or the Motor, will seriously damage the motor.
When using “Inside delta” connection:
1. It is highly recommended to use a contactor in series to the RVS-DX or upstream (after motor protection) in order to avoid a destruction of the motor in case of a shorted SCR in the RVS-DX.
2. If Contactor is connected Inside the Delta, motor terminals are “live” (full
voltage) even when contactor is open.
RVS-DX connected INSIDE DELTA
Speed reverse with RVS-DX connected INSIDE
DELTA
(1) C1 is a line contactor.
(2) C2 is an “Inside Delta” contactor. (3) U1-U2, V1-V2, W1-W2 are motor’s windings. (4) L1-U, L2-V, L3-W are RVS-DX controlled phases.
Refer also to section 4.2 page 9.
14 • Dimensions
________________________________________________________________________________________
5. DIMENSIONS
RVS-DX 8, 17, 31, 44 Note: Mains voltage terminals: 16mm
2
RVS-DX 58, 72
RVS-DX 85, 105
RVS-DX 145, 170
RVS-DX 210
15 • Dimensions
___________________________________________________________________________________________
RVS-DX 310
RVS-DX 390
16 • Dimensions
________________________________________________________________________________________
RVS-DX 460
RVS-DX 580
17 • Dimensions
___________________________________________________________________________________________
RVS-DX 650-820
RVS-DX 950-1100
18 • Ins tallation
________________________________________________________________________________________
Area (m2) =
6. INSTALLATION
WARNING!
Do not interchange line and load connections
6.1
89BPrior to Installation
Check that Motor’s Full Load Ampere (FLA) is lower than, or equal, to the starter’s Full Load Current (FLC) and that Mains and Control voltages are as indicated on the starter’s side label.
Make sure Starter’s FLCMotor FLA! Make sure Mains voltage is right! Make sure Control voltage is right!
RVS-DX label - example
6.2
90BMounting
The starter must be mounted vertically. Allow sufficient space (at least 100mm) above and below the starter for suitable airflow. It is recommended to mount the starter directly on the rear metal plate for better heat dissipation.
Note:
Do not mount the RVS-DX directly on the rear metal plate in case a ventilation fan or ventilation opening is on the back side of the RVS-DX.
Do not mount the starter near heat sources. Surrounding air temperature in the cabinet should not exceed 40ºC Protect the starter from dust and corrosive atmospheres.
Note: For harsh environments (sewage treatment plants, etc.), it is recommended to order the starter with printed circuit board coating. Refer to section 3.3.6 on page 7 for ordering information.
6.3
91BTemperature range & heat dissipation
The starter is rated to operate over a temperature range of -10ºC (14ºF) to + 40ºC (104ºF). Relative non-condensed humidity inside the enclosure should not exceed 95%.
ATTENTION!
Operating at surrounding air temp. (Inside the cabinet) higher than 40ºC may cause damage to the starter.
Starter’s heat dissipation while motor is running and the internal bypass relays are closed is typically less than 0.4 x In (in watts). During soft start and soft stop, heating is approximately three times the actual starting current (In watts).
Example: For a 100A motor, heat dissipation is less than 40 watts while running and during starting (for example at 350A), heat dissipation is approximately 1050 watts.
Important note: If motor is frequently started, cabinet should be designed for the higher heat dissipation. Internal enclosure heating can be reduced through the use of additional ventilation.
6.3.1
119BCalculating the enclosure size, for non-ventilated metallic enclosure
Where: Area [m
2]
] - Surface area that can dissipate heat (front, sides, top).
0.12 x Total heat dissipation [Watts] 60 – External ambient temp. [ºC]
19 • Ins tallation
___________________________________________________________________________________________
Total heat dissipation [Watt] – The total heat dissipation of the starter and other control devices
in the enclosure. If starter is frequently started, average power should be used.
6.3.2 Additional Ventilation
Use the following arrangement for forced ventilation of the RVS-DX’s enclosure:
6.3.3 UL, cUL Installation Instructions
Input power and output motor field wiring shall be copper conductors, rated 75ºC. Use UL listed closed-loop connectors sized for the selected wire gauge.
Install connectors using the correct crimp tool recommended by the connector manufacturer. Applies only to units bus bars.
Table showing corresponding wire size, terminal screw and closed-loop connector size.
Torque ratings for attachment of connector to bus bar (refer to table below).
Branch circuit protection, shall be provided per the NEC. For units with UL cUL approval, refer to section Error! Reference source not found. on
page Error! Bookmark not defined..
Max. Mot.
FLA
[A]
Min. dimensions for copper
cables
[mm2]
Term
Screw
Mechanical
Torque
[Kg.cm]
8
4 x 1.5 N2XY
17
4 x 2.5 N2XY
31
4 x 4 N2XY
44
4 x 10 N2XY
58
4 x 16 N2XY
72
4 x 16 N2XY
85
4 x 25 N2XY
105
4 x 25 N2XY
M8
180
145
3 x 50 + 25 N2XY
M8
180
170
3 x 70 + 35 N2XY
M8
180
210
3 x 95 + 50 N2XY
M10
220
310
3 x 150 + 70 N2XY
M10
220
390
3 x 185 + 95 N2XY
M10
220
460
3 x 240 + 120 N2XY
M10
220
580
2 x (3x 150 + 70)N2XY
M10
220
820
3 x (3x 185+ 95) N2XY
M10
220
950
1100
Air
Outlet
Air
Inlet
Air
Fan
RVS-DX
20 • Control Keypad
________________________________________________________________________________________
7. CONTROL KEYPAD The control keypad is the link between the Soft Starter and the user.
The RVS-DX control keypad features:
(1) Two lines of 16 alphanumeric characters each (with five selectable languages – English,
French, German, Spanish and Turkish) (2) Six push-buttons (Mode, Reset, Select, Store, Up () and down () keys). (3) Four indication LEDs (On, Ramp, Run and Fault)
Close view
7.1 92BLCD Arrangement
CURRENT LIMIT 390%
Upper line displays function. Lower line displays setting and\or measured values.
7.2
93BPush-buttons
Mode
Scrolls through the display and programming menus of the RVS-DX.
50BNote: Pressing Mode continuously increases the speed at which the parameters change.
Select
When a mode name is displayed, pressing this button drills down to the parameters for that
mode. When a parameter is displayed, pressing this button scrolls to the next parameter.
Allows the operator to increment adjusted values shown in the display. Operator should press
this button once to increment one value, or continuously to rapidly increment values up to the
maximum value.
Allows the operator to decrement adjusted values shown in the display. Operator should press
this button once to decrement one value, or continuously to rapidly decrement values up to the minimum value.
Store
Stores modified parameters only when you have scrolled through all parameters and STORE
ENABLE XXXXXX PARAMETERS is displayed. After you store a parameter successfully DATA SAVED OK will display.
Note: Pressing this button at any other time has no effect.
Reset
Resets the RVS-DX after a fault has been dealt with and the start command has been removed.
This cancels the fault displayed and allows you to restart the motor.
(2)
(3)
(1)
21 • Control Ke ypad
___________________________________________________________________________________________
7.3 Status LEDs.
Green
On
Lights when Control Supply voltage is connected to the RVS-DX.
Yellow
Ramp
Lights during soft start and soft stop process, indicating that motor supply voltage is ramping up or down.
Green
Run
Lights after completion of starting process, indicating that motor is receiving full voltage.
Red
Fault
Lights upon operation of any of the built-in protection.
7.4 Reviewing and Modifying Parameters Press the Mode key several times until you reach the required mode page.
Press the Select key to review parameters for this mode. Once you reach the required parameter, use the ▼ or ▲ keys to modify its value.
To store the new parameters, press the Select key until the STORE ENABLE message displays and then press the Store key. The DATA SAVED OK message will display for 2 seconds.
7.5 Special Actions Performed in TEST/MAINTENANCE Mode
7.5.1 Run Self Test
Press the Mode and keys simultaneously. The LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key. The LCD will display:
RUN SELF TEST? PUSH UP ARROW
Press the key. The LCD will display:
SELF TEST PASSED
And after a few seconds the LCD will display:
% OF MOTOR FLA I<0.1 FLC
7.5.2 View Software Version
Press the Mode and keys simultaneously. The LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key twice. The LCD will display:
BTL-R-17/05/2009 STRT.DX-310111
Press the Mode and keys simultaneously to exit the TEST/MAINTENANCE mode. The LCD will display:
% OF MOTOR FLA I<0.1 FLC
22 • Control Ke ypad
________________________________________________________________________________________
7.5.3 Obtain Default Parameters
Press the Mode and keys simultaneously. The LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key three times. The LCD will display:
STORE ENABLE DEFAULT PARAMET.
Press the Store + Mode keys simultaneously. The LCD will display:
DATA SAVED OK
And after a few seconds the LCD will display:
% OF MOTOR FLA I<0.1 FLC
CAUTION!
Obtaining DEFAULT PARAMETERS erases all previously modified settings
and requires the operator to reprogram all parameters that differ from the factory default. Note: It is especially important to reprogram the FLC (as shown on the label of
the RVS-DX), FLA and RATED LINE VOLT. value again.
7.5.4 Reset Statistical Data
Press the Mode and keys simultaneously. The LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key four times. The LCD will display:
RESET STATISTICS
Press the Reset + Store keys simultaneously. The LCD will display:
DATA SAVED OK
And after a few seconds the LCD will display:
STATISTICAL DATA
- **** -
Press the Mode and go back to:
% OF MOTOR FLA I<0.1 FLC
23 • Control Ke ypad
___________________________________________________________________________________________
7.5.5 Calibrate Voltage, Current and (Factory Use Only!)
Press the Mode and keys simultaneously. the LCD will display:
TEST/MAINTENANCE
***OPTIONS***.
Press the Select key five times. The LCD will display:
VOLTAGE ADJUST. X VOLT
Press the Select key. The LCD will display:
CURRENT ADJUST. 5% OF FLC
Press the Select key. The LCD will display (POWER FACTOR & POWER measurement only available in RVS-DX58A and up):
POWER FACTOR
0.71
Press the Mode and keys simultaneously to exit the TEST/MAINTENANCE mode.
7.6 Mode Pages Upon initiation of the starter, the LCD displays motor’s operating current:
% OF MOTOR FLA 0%
By pressing the Mode key all mode pages can be reviewed:
MAIN PARAMETERS
- **** -
START PARAMETERS
- **** -
STOP PARAMETERS
- **** -
DUAL ADJUSTMENT PARAMETERS
These pages are skipped if RVS-DX is programmed to
“MINIMIZED MODE” and are shown only in “MAXIMIZED MODE” (Refer to section
7.6.3 on page 27 for information on changing
from “MINIMIZED MODE” to “MAXIMIZED MODE”)
SPECIAL FEATURES PARAMETERS
FAULT PARAMETERS
- **** -
I/O PROGRAMMING PARAMETERS
COMM PARAMETERS
- **** -
STATISTICAL DATA
- **** -
24 • Control Ke ypad
________________________________________________________________________________________
7.6.1 Overview of All Mode Pages and Factory Defaults
Appears only in
MAXIMIZED MODE
(1)
% OF MOTOR FLA XX%
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
Refer page 26
Refer page 27
Refer page 31
Refer page 35
Refer page 37
AMP. VOLT 0 0
LANGUAGE: ENGLISH
SOFT START CURVE 0(STANDARD)
SOFT STOP CURVE 0(STANDARD)
DA: INIT. VOLT. 30%
OPTION CARD Not Installed
STARTER FLC 58 AMP.
PULSE TIME 0 SEC.
DEC. TIME 0 SEC.
DA: CUR. LIMIT 400% OF FLA
POWER
(2)
MOTOR FLA 58 AMP.
INITIAL VOLTAGE 30 %
FINAL TORQUE 0 (MIN.)
DA: ACC. TIME 10 SEC.
POWER FACTOR
(2)
RATED POWER 30KW
CURRENT LIMIT 400% OF FLA
STORE ENABLE STOP PARAMETERS
DA: DEC. TIME 0 SEC.
CONNECTION TYPE LINE
ACC. TIME 10 SEC.
DA: MOTOR FLA 31 AMP.
RATED LINE VOLT. 400 VOLT
MAX. START TIME 30 SEC.
STORE ENABLE D. ADJ PARAMETERS
UNDERCURR. TRIP 0% OF FLA
NUMBER OF STARTS 10
UNDERCURR. DELAY 10 SEC.
STARTS PERIOD 30 MIN.
O/C – SHEAR PIN 200% OF FLA
START INHIBIT 15 MIN.
O/C DELAY
0.5 SEC.
STORE ENABLE START PARAMETERS
OVERLOAD CLASS IEC CLASS 10
OVERLOAD PROTECT ENABLE WHILE RUN
UNDERVOLT. TRIP 75%
UNDERVOLT. DELAY 5 SEC.
OVERVOLT. TRIP 120 %
OVERVOLT. DELAY 2 SEC.
DISPLAY MODE MINIMIZED
PARAMETERS LOCK NOT LOCKED
STORE ENABLE MAIN PARAMETERS
(1) - Refer to section
7.6.3 on page 27 for information on changing from “MINIMIZED MODE” (Factory
default) to “MAXIMIZED MODE”. (2) POWER and POWER FACTOR readings available in RVS-DX 58A and up.
25 • Control Ke ypad
___________________________________________________________________________________________
Appears only in
MAXIMIZED MODE
(1)
Appears only in
MAXIMIZED MODE
(1)
Appears only in
MAXIMIZED MODE
(1)
Appears only in
MAXIMIZED MODE
(1)
SPECIAL FEATURES PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
Refer page 38
Refer page 40
Refer page 42
Refer page 44
Refer page 46
SLOW SPEED TORQ. 8
PHASE LOSS Y/N YES
PROG. INPUT C1 REMOTE RESET
COMM. PROTOCOL MODBUS
TOTAL ENERGY
(3)
0 KWH
MAX SLOW SP TIME 30 SEC.
PHASE SEQ. Y/N NO
FAULT RELAY TYPE FAULT
BAUD RATE 9600 (MODBUS)
LAST STRT PERIOD NO DATA
WIDER SETTINGS DISABLE
INSULATION ALARM OFF
PROG. AUX. RELAY IMMEDIATE
PARITY CHECK EVEN
LAST START MAX I NO DATA
STORE ENABLE SPECIAL FEATURES
INSULATION TRIP OFF
RELAY ON DELAY 0 SEC.
SERIAL LINK NO. OFF
TOTAL RUN TIME 0 HOURS
AUTO RESET NO
RELAY OFF DELAY 0 SEC.
S. LINK PAR. SAVE DISABLE
TOTAL # OF START 0
THERMISTOR TYPE PTC
AN. OUT. PARAMETER I, 0...200% OF FLA
SER. LINK CONTROL DISABLE
LAST TRIP NO DATA
THERMISTOR TRIP OFF
STORE ENABLE I/O PROG. PARAM.
MODBUS TIMEOUT OFF
TRIP CURRENT 0 % OF FLA
UNDER CUR. RESET OFF
FRONT COM ADDRES OFF
TOTAL # OF TRIPS 0
STORE ENABLE FAULT PARAMETERS
STORE ENABLE COMM. PARAMETERS
PREVIOUS TRIP -2 NO DATA
Applicable when
Optional Modbus or DeviceNet
is ordered.
.
. .
Applicable when
Optional Profibus Is ordered.
COMM. PROTOCOL PROFIBUS
PREVIOUS TRIP -9 NO DATA
BAUD RATE AUTO (PROFIBUS)
Appears when in
TEST/MAINTENANCE
(2)
PARITY CHECK AUTO (PROFIBUS)
TEST/MAINTENANCE
***OPTIONS***
Display and default
values
PROFI.NETWORK ID OFF
RUN SELF TEST? PUSH UP ARROW
S. LINK PAR. SAVE DISABLE
BTL-R-29/05/2008 STRT.DX-250608
SER. LINK CONTROL DISABLE
STORE ENABLE DEFAULT PARAMETERS
MODBUS TIMEOUT OFF
RESET STATISTICS
FRONT COM ADDRES OFF
VOLTAGE ADJUST X VOLT
STORE ENABLE COMM. PARAMETERS
CURRENT ADJUST 5% OF FLC
POWER FACTOR
(3)
0.71
(1)
- Refer to section 7.6.3 on page 27 for information on changing from “MINIMIZED MODE” (Factory default)
to “MAXIMIZED MODE”.
(2)
- Refer to section 7.5 on page 21 for entering TEST/MAINTENANCE mode.
(3)
– TOTAL ENERGY and POWER FACTOR readings available in RVS-DX 58A and up.
26 • Control Ke ypad
________________________________________________________________________________________
7.6.2 Display Mode – page 0
% OF MOTOR FLA XX%
Displays in MINIMIZED MODE and MAXIMIZED MODE
(Refer to section 7.6.3 page 27)
Display and default
values
Range
Description
% OF MOTOR FLA I<0.1 FLC
Displays operating current as a percentage of motor FLA (Full
Load Ampere). Starter’s Default Display. After pressing Mode or Select keys, a time delay is initiated. Following the delay, the LCD returns to display “% OF MOTOR FLA”.
AMP. VOLT 0 0
Displays Motors current and mains voltage. OPTION CARD Not Installed
NOT
INSTALLED/
INSTALLED
Displays whether option cards are installed in the RVS-DX. POWER 30kw
When power metering option is installed, displays active POWER
drawn by the motor.
Note:
Reading available in RVS-DX58A and up.
POWER FACTOR
0.9
When power metering option is installed, displays POWER
FACTOR of motors power.
Note:
Reading available in RVS-DX58A and up.
Note:
In this page parameters cannot be programmed.
27 • Control Ke ypad
___________________________________________________________________________________________
7.6.3 Main Parameters – page 1
MAIN PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(Refer below for changing modes)
Display and default
values
Range
Description
Remarks
LANGUAGE: ENGLISH
SPANISH
GERMAN FRENCH ENGLISH TURKCE RUSSIAN
(Optional)
Sets Starter’s
language
STARTER FLC 58 AMP.
8–1100A
Sets starter’s
FLC (Full load
current)
Starter’s FLC should be as shown on starter’s
Name plate. (Refer to section 6.1 on page 18)
MOTOR FLA 58 AMP.
50-100% of
STARTER FLC
Sets motor’s
FLA (Full load Ampere)
Should be programmed as shown on motor’s
name plate. Note: When the RVS-DX is installed Inside Delta set
MOTOR FLA = <rated motor current>/1.73.
RATED POWER 30KW
1-3000KW
Sets motor’s
POWER
Rated motor power is used for analog output
reference. When analog card is installed, full scale of the readings (20mA or 10V as per dip­switches settings on the analog card) are related to 200%FLA. (2x rated motor current) or 200% of rated power or POWER FACTOR. Refer to section
7.6.9 on page 42 for analog
output programming. Note: POWER FACTOR & POWER measurement only
available in RVS-DX58A and up.
CONNECTION TYPE LINE
LINE,
INSIDE DELTA
Sets Starter’s
connection type.
Factory preset – features and functions when
“INSIDE DELTA” mode is configured: No Pulse Start. No Curve selection (CURVE 0!!). No slow speed. No phase sequence “off” mode. Refer to section
4.3.9 on page 12 for further
information
RATED LINE VOLT. 400 VOLT
220-690V
Sets rated
LINE
VOLTAGE.
UNDERCURR. TRIP 0% OF FLA
0%=off;
20-90% of FLA
Sets UNDER
CURRENT TRIP
protection.
Trips the starter when motor current drops blow
set level for a time longer than UNDER CURRENT DELAY
UNDERCURR. DELAY 10 SEC.
1-40sec.
Sets the time
delay for the
28 • Control Ke ypad
________________________________________________________________________________________
MAIN PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(Refer below for changing modes)
Display and default
values
Range
Description
Remarks
UNDER
CURRENT TRIP protection
O/C – SHEAR PIN 200% OF FLA
100-300% of
motor’s FLA setting
Sets OVER
CURRENT SHEAR PIN
protection
becomes operational when starter is energized
and has three trip functions: At all time - IF I > 850% of FLC - trips the starter within 1 cycle. (Overrides the value of O/C – SHEAR PIN setting) At starting process - IF I > 850% of FLA - trips the starter after O/C DELAY (see here after) At run time - IF I > O/C – SHEAR PIN setting of FLA - trips the starter after O/C DELAY Important Note: The O/C SHEAR PIN is not intended to replace the fast acting fuses, required to protect the thyristors (Refer to fuse
table in section 4.3.1 on page 10)
O/C DELAY
0.5 SEC.
0.0 –5sec.
Sets O/C –
SHEAR PIN delay time
OVERLOAD CLASS IEC CLASS 10
IEC CLASS 10/
IEC CLASS 20/ NEMA CLASS 10/ NEMA CLASS 20/ NEMA CLASS 30/
Sets
OVERLOAD curve.
Sets OVERLOAD CLASS characteristics
Sets OVERLOAD PROTECT functionality. The HRVS-DN allows motor protection according to IEC class 5 or 10 or according to NEMA class 10 ,20 or 30. Tripping curves are shown on section
7.6.3.1
page 30. The OVERLOAD protection incorporates a THERMAL CAPACITY register that calculates heating minus dissipation of the motor. The RVS-DX trips when the register fills up. (THERMAL CAPACITY=100%) The time constant, in seconds, for cool down after overload trip is:
Class
10
20
30
IEC
320
640
-
NEMA
280
560
840
OVERLOAD PROTECT ENABLE WHILE RUN
DISABLE/
ENABLE WHILE RUN/ ENABLE
The overload protection can be set to protect the
motor as set in the OVERLOAD PROTECT parameter: ENABLE – motor is protected at all time. ENABLE WHILE RUN – motor is protected only when in Run. DISABLE – motor is not overload protected by the soft starter.
Note:
In order to restart after OVERLOAD trip, the
thermal register should be 50% or less.
UNDERVOLT. TRIP 75%
50-90% of
RATED
LINE VOLT.
Sets UNDER
VOLTAGE
TRIP.
Trips the starter when mains voltage drops
below the set level for a time longer than
UNDERVOLT DELAY.
29 • Control Ke ypad
___________________________________________________________________________________________
MAIN PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(Refer below for changing modes)
Display and default
values
Range
Description
Remarks
UNDERVOLT. DELAY 5 SEC.
1–10sec.
Sets
UNDERVOLT TRIP DELAY.
Note:
Becomes operational only after Start signal. When voltage drops to zero (voltage outage) the
starter will trip immediately, overriding the delay.
OVERVOLT. TRIP 120 %
110-125% of
RATED
LINE VOLT.
Sets OVER
VOLTAGE
TRIP.
Trips the starter when mains voltage increases
above the set level for a time longer than OVEERVOLT DELAY.
OVERVOLT. DELAY 2 SEC.
1–10sec.
Sets
OVERVOLT TRIP DELAY.
DISPLAY MODE MINIMIZED
MINIMIZED/
MAXIMIZED
Sets Display
Mode
For operation convenience, there are two display
modes: MINIMIZED – Display of pre-selected parameters for standard applications. MAXIMIZED – Display of all possible parameters. Setting Display Mode to MINIMIZED will minimize the LCD displays. (Refer to section
7.4 7.6 on page 21 for more details)
PARAMETERS LOCK NOT LOCKED
NOT
LOCKED/ LOCKED
Locks or
unlocks parameter modifications.
The software lock prevents undesired parameter
modification. When locked, upon pressing Store , or keys, the LCD displays:
UNAUTHORIZED ACCESS
STORE ENABLE MAIN PARAMETERS
Storing
modified parameters
To store selected parameters, press Store key.
Note: Storing selected parameters is possible only when RAMP LED does not lit. Storing cannot be done when Soft Starting or Soft Stopping. When parameters have been correctly stored, the LCD will read:
DATA SAVED OK
This concludes MAIN PARAMETER settings.
Pressing Select key after “DATA SAVED OK” returns to the first display in this mode. Note: In case of a failure in parameter storing, the LCD displays:
STORAGE ERROR
In this case Refer to section 9 – “TROUBLE
SHOOTING” on page 55.
30 Control Keypad
________________________________________________________________________________________
7.6.3.1 Tripping Curves of the Integrated Overload Protection
The RVS-DX allows motor protection according to IEC class 10 or 20 OR according to NEMA class 10, 20, or
30.
NEMA & IEC Class OVERLOAD curves
NEMA Class 10
1
10
100
1000
10000
0 1 2 3 4 5 6 7 8
Current [I/FLA]
Time [sec.]
IEC Class 10
1
10
100
1000
10000
0 1 2 3 4 5 6 7 8
Current [I/FLA]
Time [sec.]
NEMA Class 20
1
10
100
1000
10000
100000
0 1 2 3 4 5 6 7 8
Current [I/FLA]
Time [sec.]
IEC Class 20
1
10
100
1000
10000
100000
0 1 2 3 4 5 6 7 8
Current [I/FLA]
Time [sec.]
NEMA Class 30
1
10
100
1000
10000
100000
0 1 2 3 4 5 6 7 8
Current [I/FLA]
Time [sec.]
Cold
Hot
Cold
Hot
Cold
Hot
Cold
Hot
Cold
Hot
31 • Control Ke ypad
___________________________________________________________________________________________
7.6.4 130BStart Parameters – page 2
START PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
Remarks
SOFT START CURVE 0(STANDARD)
4 (TORQUE)
3 !! 2 !! 1 !!
0 (STANDARD)
Sets starter’s
SOFT START CURVE.
Refer to section 7.6.4.1 on page 34.
Note:
When RVS-DX is connected “Inside-
Delta”, only CURVE 0 is applied.
PULSE TIME 0 SEC.
0 – 1.0 SEC.
Sets starter’s
PULSE START TIME. PULSE START level is 80% Un.
Intended to start high friction loads,
requiring high starting torque for a short time. A pulse of 80% Un, without Current Limit, is initiated to break the load free. Pulse duration is adjustable, 0.1 – 1sec. After this pulse, the voltage is ramped down to INITIAL VOLTAGE setting, before ramping up again to full voltage according to START PARAMETERS settings.
Note:
When RVS-DX is connected “Inside­Delta”, PULSE START can not be
activated.
INITIAL VOLTAGE 30 %
10-50%
After reaching 50% display changes to: INITIAL CURRENT 100-400%
Note:
The range of the INITIAL VOLTAGE can be extended to 5-80% by using the WIDER
Sets motor’s
INITIAL STARTING VOLTAGE. (Motor’s torque is directly proportional to the square of the voltage)
This adjustment also determines the
inrush current and mechanical shock. A setting that is too high may cause high initial mechanical shock and high inrush current (even if CURRENT LIMIT is set low, as the INITIAL VOLTAGE setting overrides CURRENT LIMIT setting). A setting that is too low may result in prolonged time until motor begins to turn. In general, this setting should ensure that the motor begins turning immediately after start signal.
INITIAL CURRENT 100 %
32 • Control Ke ypad
________________________________________________________________________________________
START PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section 7.6.3 on page 27 for changing mode)
SETTING as
described in section
7.6.7
page 38.
Note:
When INITIAL VOLTAGE is set above 50% (it’s maximum value), display changes to INITIAL CURRENT. When INITIAL CURRENT is set, starter causes current ramp instead of voltage ramp.
CURRENT LIMIT 400% OF FLA
100-400%
Note:
Range can be extended to 100-500% by using the WIDER SETTING as described in section
7.6.7
page 38.
Sets motor’s
highest current during starting.
A too high setting will cause greater
current drawn from mains and faster acceleration. A setting that is too low may prevent motor from completing acceleration process and reaching full speed. In general, this setting should be set to a high enough value in order to prevent stalling.
Note: CURRENT LIMIT is not operating during Run and Soft stop.
ACC. TIME 10 SEC.
1-30sec.
Note:
Range can be
Sets
ACCELERATION
TIME of the
Determines motor’s voltage ramp-up
time, from initial to full voltage.
33 • Control Ke ypad
___________________________________________________________________________________________
START PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section 7.6.3 on page 27 for changing mode)
extended to 1-
90sec. by using the WIDER SETTING as described in section
7.6.7
page 38.
motor.
It is recommended to set
ACCELERATION TIME to the minimum acceptable value (approx. 5 sec).
Notes:
Since CURRENT LIMIT overrides ACC. TIME, when CURRENT LIMIT is set low, starting time will be longer than the preset ACC. TIME. When motor reaches full speed before voltage reaches nominal, ACC. TIME setting is overridden, causing voltage to quickly ramp-up to nominal. Using starting curves 1, 2, 3 prevents
quick ramp up.
MAX. START TIME 30 SEC.
1-30sec.
Note:
Range can be extended to 1­250sec.by using the WIDER SETTING as described in section
7.6.7
page 38.
Sets MAXIMUM
START TIME
The maximum allowable start time, from
Start signal to end of acceleration process. If voltage does not reach full voltage/speed during this time (e.g. because of too low CURRENT LIMIT setting), the starter will trip the motor. LCD displays “LONG START TIME” message.
NUMBER OF STARTS 10
OFF, 1-10
Sets NUMBER
OF STARTS permitted During STARTS PERIOD (see
below).
Limits the NUMBER OF STARTS
during the period of time defined by STARTS PERIOD. If you try to start even one more time within that period the START INHIBIT
period will take effect.
STARTS PERIOD 30 MIN.
1–60min.
Sets STARTS
PERIOD during which NUMBER OF STARTS is being
counted.
During the START INHIBIT period the
WAIT BEFORE RST XX MIN message will be displayed.
START INHIBIT 15 MIN.
1–60min.
Sets START
INHIBIT time which, before elapsed, motor can not be
restarted.
STORE ENABLE START PARAMETERS
Same as STORE ENABLE MAIN
PARAMETERS on page 29.
34 • Control Ke ypad
________________________________________________________________________________________
7.6.4.1 Soft start parameters
The RVS-DX incorporates 4 “Starting Curves”, enabling selection the suitable torque curve: Start Curve 0 – Standard curve (Default). The most stable and suitable curve for the motor, preventing
prolonged starting and motor overheating.
Note:
When RVS-DX is connected “Inside-Delta”, only CURVE 0 is applied. Start curves 1-3 - “Pump Control” - Induction motors produce peak torque of up to 3 times the rated torque
towards the end of starting process. In some pump applications, this peak may cause high pressure in the pipes. Start Curves 1, 2, 3 – During acceleration, before reaching peak torque, the Pump Control Program automatically controls the voltage ramp-up, reducing peak torque.
Choice of three pump control acceleration curves: 0!, 1!, 2!, 3!
Start Curve 4 (Torque) – Torque Controlled acceleration, provides a smooth time controlled torque ramp for the motor and the pump.
Note:
Always start with Start Curve 0. If towards end of acceleration, peak torque is too high (pressure is too high), proceed to Curve 1, 2, 3 or 4 if necessary.
35 • Control Ke ypad
___________________________________________________________________________________________
7.6.5 Stop Parameters – page 3
STOP PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
Remarks
SOFT STOP CURVE 0(STANDARD)
4 (TORQUE)
3 !! 2 !! 1 !!
0 (STANDARD)
Sets starter’s
SOFT STOP CURVE.
Refer to section 7.6.5.1 on page 35
DEC. TIME 0 SEC.
0 – 30sec.
Note:
Range can be extended to 90sec. by using the WIDER SETTING as described in section
7.6.7
page 38.
Sets
DECELERATION TIME of the motor.
Used for controlled deceleration of high
friction loads. Determines motor’s voltage ramp down time.
FINAL TORQUE 0 (MIN.)
0 (min.) – 10
(max.)
Sets FINAL
TORQUE during Soft Stop.
Determines torque towards end of SOFT
STOP. If current is still flowing after speed is softly reduced to zero, increase FINAL TORQUE setting.
STORE ENABLE STOP PARAMETERS
Same as STORE ENABLE MAIN
PARAMETERS on page 29.
7.6.5.1 Soft stop parameters
The RVS-DX incorporates 4 “Starting Curves”, enabling selection the suitable torque curve: Stop Curve 0 – Standard curve (Default) – voltage is linearly reduced from nominal to zero.
The most stable and suitable curve for the motor, preventing prolonged stopping and motor overheating. Stop curves 1, 2, 3 Pump Control – In some pump applications, when pumping to a higher level, a
considerable part of the torque is constant and does not decrease with speed. It may happen that during deceleration process, when voltage is decreasing, motor torque quickly falls below load torque abruptly (instead of smoothly decreasing speed to zero) closing the valve and causing Water Hammer. Curves 1, 2 and 3 are intended to prevent Water Hammer phenomenon. In pump applications, load torque decreases in square relation to the speed, thus correct control of voltage reduction reduces torque adequately to smoothly decelerate to a stop. Note:
36 • Control Ke ypad
________________________________________________________________________________________
It is recommended that for all standard applications (not pumps), Stop Curve 0 will be used. To reduce Water Hammer select STOP CURVE 1, than 2 or 3, if necessary.
Curve 4 - Torque Curve - Provides linear deceleration of the torque. In certain loads, linear torque deceleration can result in close to linear speed deceleration. The RVS-DX Torque Control does not require any external torque or speed sensor (tacho-gen. etc.).
37 • Control Ke ypad
___________________________________________________________________________________________
7.6.6 Dual Adjustment Parameters – page 4
DUAL ADJUSTMENT PARAMETERS
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Description
Remarks
When selecting GEN. START/STOP in mode I/O
PROGRAMMING PARAMETERS on page PROG. INPUT C1 DUAL ADJUST (refer to section
7.6.9.1on
page 43) the following display appears:
D. ADJ: GENERATOR PARAMETERS
DA: INIT. VOLT. 30%
Sets motor’s INITIAL
STARTING VOLTAGE in DA
mode. (Motor’s torque is directly
proportional to the square of the voltage)
Refer to section 7.6.4 on page 31 parameter:
INITIAL VOLTAGE.
DA: INIT. CURRENT 100%
DA: CUR. LIMIT 400% OF FLA
Sets motor’s highest
current during starting in DA mode.
Refer to section 7.6.4 on page 31 parameter:
CURRENT LIMIT.
DA: ACC. TIME 10 SEC.
Sets
ACCELERATION TIME of the motor in
DA mode.
Refer to section 7.6.4 on page 31 parameter:
ACC. TIME.
DA: DEC. TIME 0 SEC.
Sets
DECELERATION TIME of the motor in
DA mode.
Refer to section 7.6.5 on page 35 parameter:
DEC. TIME.
DA: MOTOR FLA 31 AMP.
Sets motor’s FLA
(Full load Ampere) in
DA mode.
Refer to section 7.6.3 on page 26 parameter:
MOTOR FLA.
STORE ENABLE D. ADJ PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS on
page 29.
38 • Control Ke ypad
________________________________________________________________________________________
7.6.7 Special features Parameters – page 5
SPECIAL FEATURES PARAMETERS
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
Remarks
SLOW SPEED TORQ. 8
1(MIN.) –
10(MAX.)
Sets SLOW
SPEED
TORQUE.
Note:
When RVS-DX is connected “Inside-Delta” SLOW SPEED TORQUE is not available.
MAX SLOW SP TIME 30 SEC.
1–30sec.
Note:
Range can be extended to 250sec. by using the WIDER SETTING as described in section
7.6.7
page 38.
Sets
maximum time for SLOW SPEED TORQUE operation.
WIDER SETTINGS DISABLE
DISABLE/
ENABLE
Enables wider
range of parameter
settings.
For use in very special occurrences.
Do not set to ENABLE unless starter is significantly larger then motor!
See detailed explanation next page.
STORE ENABLE SPECIAL FEATURES
Same as STORE ENABLE MAIN
PARAMETERS on page 29.
39 • Control Ke ypad
___________________________________________________________________________________________
7.6.7.1 WIDER SETTINGS Parameters:
Parameter
WIDER SETTINGS Disabled
WIDER SETTINGS Enabled
INITIAL VOLTAGE
10-50%
5
(1)
-80%
CURRENT LIMIT
100-400%
100-500%
ACCELERATION TIME
1-30 seconds
1-90 seconds
DECELERATION TIME
0-30 seconds
0-90 seconds
MAX. START TIME
1-30 seconds
1-250 seconds
PHASE LOSS Y/N
Yes
(2)
Yes/No
(2)
MAX SLOW SP TIME
1-30 seconds
1-250 seconds
O/C or WRONG CON protection
in Inside Delta mode.
Protection active in normal set
(3)
Protection active in high set
(3)
OVERLOAD TRIP protection.
OVERLOAD TRIP will be active
after Run LED is Lit.
(Motor is at full voltage)
(4)
OVERLOAD TRIP will be active
after MAX. START TIME has
elapsed.
(4)
Notes:
(1) Setting the INITIAL VOLTAGE to lower than 10% is not practical for loaded motors. (2) Refer to section 7.6.8 page 40. See PHASE LOSS protection and refer to the warning below. (3) Refer to section 9 page 55. See O/C or WRONG CON protection. (4) In order to avoid OVERLOAD TRIP in special cases (very high inertia loads), where at the end of the acceleration process, although motor is at full voltage (Run LED is Lit) and the current does not reduce to nominal, set WIDER SETTINGS to ENABLE causing the OVERLOAD TRIP to be active only after MAX. START TIME has elapsed.
WARNING! Operator’s responsibility!
1. WIDER SETTINGS are for use in very special applications only!
Do not set WIDER SETTINGS to ENABLE unless RVS-DX is significantly larger than the motor! When using WIDER SETTINGS for the RVS-DX you must be extremely careful to avoid damaging the motor or RVS-DX.
2. Only cancel PHASE LOSS protection when the operator is sure that no real phase loss exists and PHASE LOSS protection is activated. This situation can occur in rare cases when there is no real fault but the RVS-DX recognizes unusual behaviour like when THDV (Total Harmonic Distortion in Voltage) in the network is high. If this is a true case of PHASE LOSS then after cancelling PHASE LOSS protection the motor will single phase and most likely be tripped by the over load
protection mechanism.
40 • Control Ke ypad
________________________________________________________________________________________
7.6.8 Fault Parameters – page 6
FAULT PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
Remarks
PHASE LOSS Y/N YES
YES
Note:
Range can be extended to YES/NO by using the WIDER SETTING as described in section
7.6.7
page 38.
Sets PHASE
LOSS trip
PHASE LOSS protection trips the RVS-DX
when 1 or 2 phases are missing.
Notes:
If RVS-DX trips on PHASE LOSS do the following: (1) Verify that phase voltages are within the required range of the voltages. (2) If you are sure that no real phase loss exists, you can set PHASE LOSS Y/N protection to NO. This situation can occur in rare cases when there is no real fault but the RVS-DX recognizes unusual behaviour like when Total Harmonic Distortion in Voltage (THDV) in the network is high. (3) If this is a true case of PHASE LOSS then after setting PHASE LOSS Y/N protection to NO the motor will single phase and most likely be tripped by the over load protection mechanism. (4) Phase loss might not be detected in
motor operating under a light load.
PHASE SEQ. Y/N NO
NO/YES
Sets PHASE
SEQUANCE
trip
When RVS-DX is connected “Inside-Delta”,
PHASE SEQUANCE protection is always
activated.
INSULATION ALARM OFF
OFF,
0.2–5Mohm
Sets
INSULATION
ALARM level.
Consult factory for availability. INSULATION TRIP OFF
OFF,
0.2–5Mohm
Activates
INSULATION
ALARM trip.
Consult factory for availability. AUTO RESET NO
NO/YES
Sets starter’s
AUTO RESET mode of operation.
Starter can be automatically reset for UNDER
VOLTAGE and PHASE LOSS faults. (Refer to section
7.6.3 on page 27 for details
on adjusting UNDER VOLTAGE and PHASE LOSS faults) To start the motor after UNDER VOLTAGE and PHASE LOSS faults have disappeared, stop the START signal to terminal B1 and recommence the signal to terminal B1. AUTO RESET function has a non-
programmed time delay of 60 seconds.
THERMISTOR TYPE PTC
PTC/NTC
Sets input
THERMISTOR
TYPE
Available only when analog card is installed.
THERMISTOR TRIP OFF
OFF,
0.1–10Kohm
Sets starter’s
THERMISTOR TRIP mode of
operation.
UNDER CUR. RESET OFF
10–120min., OFF.
Sets starter’s UNDER
Starter can be automatically reset for UNDER CURRENT fault. (Refer to section 7.6.3 on
41 • Control Ke ypad
___________________________________________________________________________________________
FAULT PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
Remarks
CURRENT
RESET time delay.
page 27 for details on adjusting UNDER
CURRENT TRIP) To start the motor after UNDER CURRENT fault has disappeared, stop the START signal to terminal B1 and recommence the signal to terminal B1. A time delay (After START signal is stopped) can be programmed to activate the UNDER CURRENT RESET time.
STORE ENABLE FAULT PARAMETERS
Same as STORE ENABLE MAIN
PARAMETERS on page 29.
42 • Control Ke ypad
________________________________________________________________________________________
7.6.9 135BI/O Programming Parameters – page 7
I/O PROGRAMMING PARAMETERS
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
Remarks
PROG. INPUT C1 REMOTE RESET
START/STOP;
REMOTE RESET; EXTERNAL FAULT; SLOW SPD/REVERSE; GEN. START/STOP;
DUAL ADJUSTMENT;
Sets
TERMINAL C1 function
Refer to section 7.6.9.1 on page
43.
FAULT RELAY TYPE FAULT
FAULT,
FAULT – FAIL SAFE
Sets FAULT
RELAY mode of operation.
When configured to FAULT the
internal relay is energized upon fault.
When configured to FAULT-FAIL SAFE the relay is de-energized upon fault. In this mode, while normal operation, the fault relay is energized. Relay will also de-energize upon
control power outage.
PROG. AUX. RELAY IMMEDIATE
IMMEDIATE/
END OF ACCEL.
Sets starter’s
AUX. RELAY mode of
operation.
When configured to IMMEDIATE
– the AUX. RELAY closes its contact at start signal (after programmed “on delay” time has elapsed) and open its contact at the end of deceleration time (if any) (after programmed “off delay” time has elapsed). When configured to END OF ACCEL. -the AUX. RELAY closes its contact at end of soft start (after programmed “on delay” time has elapsed) and open its contact at the beginning of soft stop (if any) (after programmed “off delay”
time has elapsed).
RELAY ON DELAY 0 SEC.
0–60sec.
Sets starter’s
AUX. RELAY on delay
time.
RELAY OFF DELAY 0 SEC.
0–60sec.
Sets starter’s
AUX. RELAY off delay time
AN. OUT PARAMETER I, 0...200% OF FLA
I, 0...200% OF FLA
P, 0...200% OF Pn POWER FACTOR
Sets
ANALOG OUTPUT mode of operation.
Available only when analog card
is installed. When analog card is installed, full scale of the readings (20mA or 10V as per dip-switches settings) are related to 200%FLA. (2x rated motor current) or 200% of rated power or POWER FACTOR.
Note:
POWER FACTOR & POWER measurement only available in
RVS-DX58A and up.
STORE ENABLE I/O PROG. PARAM.
Same as STORE ENABLE MAIN
PARAMETERS on page 29.
43 • Control Ke ypad
___________________________________________________________________________________________
7.6.9.1 PROG. INPUT C1
Terminal C1 can be programmed to operate in various modes:
TERMINAL C1
programmed function
Description
START/STOP
C1 is a maintained stop input to the RVS-DX, while B1 is a momentary start input to the RVS-DX.
REMOTE RESET
C1 is used as REMOTE RESET to reset all RVS-DX faults.
The RESET command will take affect only if START command is
stopped.
EXTERNAL FAULT
C1 is used as an input to the RVS-DX enabling the user to stop the
motor in case of an external fault. When C1 is closed motor will stop
and Fault LED will lit.
SLOW SPD/REVERSE
While C1 is in "ON", the motor will start slow speed forward.
If C1 is moved to "OFF" (while RVS-DX still in "ON"), the motor will slow speed reverse. For adjusting the SLOW SPEED TORQUE and MAX. SLOW SPEED TIME refer to section
7.6.7 on page 38.
Note:
It is not possible to start the motor in “SLOW SPEED“ REVERSE”.
GEN. START/STOP
C1 is used to load start & stop parameters from the D. ADJ:
GENERATOR PARAMETERS Page. In this mode of operation the RVS-DX will start the motor even though “WRONG CONNECTION” failure occurs.
Refer to section 7.6.6 on page 37.
DUAL ADJUSTMENT
C1 is used to load start & stop parameters from the DUAL
ADJUSTMENT PARAMETERS Page.
Refer to section 7.6.6 on page 37.
44 • Control Ke ypad
________________________________________________________________________________________
7.6.10 136BComm. Parameters – page 8- Applicable with Optional Modbus & DeviceNet Comm.
53BNote: When DeviceNet option is required an external unit, DeviceNet to Modbus Gateway is required. This
gateway is connected via 2 wires to the optional Modbus terminals.
COMM.PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
COMM. PROTOCOL MODBUS
MODBUS
Sets RVS-DX communication PROTOCOL.
Applicable when the optional communication card is installed.
BAUD RATE 9600 (MODBUS)
1200, 2400,
4800, 9600
Sets RVS-DX BAUD RATE. PARITY CHECK EVEN
EVEN,
ODD,
NO
Sets RVS- DX communication PARITY CHECK. SERIAL LINK NO.
OFF
OFF,1 – 247
Sets RVS- DX communication SERIAL LINK NO.
Note: If optional, external DeviceNet to Modbus Gateway is supplied set this parameter to 1.
S. LINK PAR. SAVE DISABLE
ENABLE/
DISABLE
Enables parameters modification via serial communication
Note: If optional, external DeviceNet to Modbus Gateway is supplied set this parameter to ENABLE/DISABLE as
required.
SER. LINK CONTROL DISABLE
ENABLE/
DISABLE
Enables start, stop, reset etc… via serial communication.
Note: If optional, external DeviceNet to Modbus Gateway is supplied set this parameter to ENABLE/DISABLE as
required.
MODBUS TIME OUT OFF
0.1-60
SEC., OFF
Sets MODBUS TIME OUT. If no valid Modbus
communication during MODBUS TIME OUT, the HRVS-DN will trip. Trip occurs only if the following conditions exist:
SER. LINK CONTROL is set to ENABLE
SERIAL LINK NO. is not set to OFF
If MODBUS TIME OUT is set to OFF protection is disabled.
FRONT COM ADDRES OFF
OFF,1 – 247
Future enhancement STORE ENABLE COMM. PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS on page
29.
Note:
After changing communication parameters and storing them, control power must be switched off and on to load new
communication parameters.
45 • Control Ke ypad
___________________________________________________________________________________________
7.6.11 Comm. Parameters – page 8 - Applicable with Optional Profibus Comm.
COMM.PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
COMM. PROTOCOL PROFIBUS
PROFIBUS
Sets RVS-DX communication PROTOCOL.
Applicable when the optional communication card is installed.
BAUD RATE AUTO (PROFIBUS)
User can not change BAUD RATE value.
Max. rate is 12 mega bit per second (MBPS).
PARITY CHECK AUTO (PROFIBUS)
User can not change PARITY CHECK settings. PROFI. NETWORK ID OFF
OFF,1 – 126
Sets the Profibus network ID.
When set to OFF the Profibus card will not function.
S. LINK PAR. SAVE DISABLE
ENABLE/
DISABLE
Enables parameter modification via serial communication SER. LINK CONTROL DISABLE
ENABLE/
DISABLE
Enables start, stop, reset etc… via serial communication MODBUS TIME OUT OFF
OFF
Do not change this parameter! Must be set to OFF. FRONT COM ADDRES OFF
OFF,1 – 247
Future enhancement STORE ENABLE COMM. PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS on page
29.
Note:
After changing communication parameters and storing them, control power must be switched off and on to load new
communication parameters.
46 • Control Ke ypad
________________________________________________________________________________________
7.6.12 138BStatistical Data – page 9
STATISTICAL DATA
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Range
Description
TOTAL ENERGY 0 KWH
Displays total energy drawn by the motor in KWH.
Note:
Reading available in RVS-DX58A and up.
LAST STRT PERIOD NO DATA
Displays last starting time in seconds.
Starting time is the duration until motor’s current reaches
nominal.
LAST STRT MAX I NO DATA
Displays last starting maximum starting current. TOTAL RUN TIME 0 HOURS
Displays Motor’s total run time. TOTAL # OF START 0
Displays total number of starts. LAST TRIP NO DATA
Displays motor’s last trip cause. TRIP CURRENT 0 % OF FLA
Displays motor’s current when motor was tripped by the RVS-
DX.
TOTAL # OF TRIPS 0
Displays total number of trips. PREVIOUS TRIP -2 NO DATA
Displays the motor’s trip history.
PREVIOUS TRIP -3 NO DATA
PREVIOUS TRIP -4 NO DATA
PREVIOUS TRIP -5 NO DATA
PREVIOUS TRIP -6 NO DATA
PREVIOUS TRIP -7 NO DATA
PREVIOUS TRIP -8 NO DATA
PREVIOUS TRIP -9
NO DATA
7.7
98BNon adjustable protection anf fault Resetting
7.7.1
139BPhase loss (and Under / Over Frequency)
Becomes operational when starter is energized and protects motor from single phasing. Trips the starter when 1 or 2 phases are missing for more than 1 sec. Starter will also trip when frequency is less than 45 or greater than 65Hz.
Note:
Phase loss might not be detected in lightly loaded motors.
47 • Control Ke ypad
___________________________________________________________________________________________
7.7.2 Phase Sequence
Becomes operational when starter is energized, provided this protection has been activated, trips the starter when phase sequence is wrong. Refer to section 7.6.8 on page 40 parameter PHASE SEQ. Y/N.
7.7.3 Shorted SCR or Wrong Connections
Becomes operational after start signal. Trips if motor is not properly connected to starter’s Load terminals, when Internal disconnection in the motor winding is detected, or when one or more SCRs have been shorted.
7.7.4 Heat-sink Over Temperature
Thermal sensors are mounted on the Heat-sink and trip the starter when temperature rises above 85ºC.
WARNING!
The over temperature protection is designed to operate under normal
conditions e.g. in the event of extended low overload, insufficient ventilation – fan stoppage or air flow blockage. Incorrect starter selection, frequent starting at max. conditions, or repeated starting under fault conditions can cause SCR’s overheating and failure before
the heat-sink reaches 85°C to trip the thermal sensors.
7.7.5 External Fault
If Aux. Input contact - C1 is programmed as an External Fault (Refer to section
7.6.9.1 on page 43 for details
on programming Input C1), the RVS-DX will trip if contact closes for more than 2 sec. External Fault becomes operational when starter is energized.
7.7.6 Fault and Reset
When any of the protections operate, the starter locks in a fault condition, disabling thyristors firing. Fault LED lights up, fault description is displayed on the LCD and Fault Relay operates. For local resetting, after fault has been removed, press Reset key. Remote resetting can be done through Aux. Input, if programmed as REMOTE RESET. (Refer to section
7.6.9.1 on page 43 for details on programming Input C1)
When Fault occurs, followed by a voltage outage, fault condition is latched and reappears upon voltage restoration. Note: Resetting (Local, Remote, Serial Link or Auto Reset) is not possible as long as Start signal exists.
7.7.7 Auto Reset
UNDER VOLTAGE and PHASE LOSS, faults can be set to Auto-Reset (Refer to section
7.6.8 on page 40).
The starter will reset itself 60 seconds after voltage was fully restored provided no start signal exists. UNDER CURRENT fault can be set to Auto-Reset (Refer to section
7.6.8 on page 40).
The starter will reset itself when a programmed time delay has elapsed provided no start signal exists.
48 • Control Ke ypad
________________________________________________________________________________________
7.8 Timing Occurrence Table
Timing And Occurrence
Active During Start Run Stop
Soft Stop
Too many starts with Start Inhibit period
Electronic Overload with Curve selection
O/C Shear Pin (Jam)
Starter Protection – trip immediately at 850% FLC
Motor Protection – trip function During Start – factory set at 850% FLA in less than 1 cy cle (*).
During Run – adjust. 200 – 850% FLA within 1 cycle (*).
Under current adjustable time delay
Phase Loss
Phase sequence
Under voltage with adjustable time delay. Time delay is override in case of “No-Volt”.
√ √
Over voltage with adjustable time delay
√ √
Long start time (Stall protection)
Shorted SCR or Wrong connection
External fault – input from a N.O. contact
√ √ √
SCR protection by Metal Oxide Varistors (MOV)
√ √ √
Starter over-temperature
√ √ √
Starter internal test, when “On” LED is lit.
√ √ √
Motor Insulation test - Not Available (Consult Factory)
Motor Thermistor – Not Available (Consult Factory)
√ √ √
49 STARTING PROCEDURE
___________________________________________________________________________________________
8. STARTING PROCEDURE
Note:
It is necessary to connect a motor to load terminals otherwise S.SCR or WRONG CONNECTION Protection is activated. Other loads such as light bulbs, resistors, etc. may also cause WRONG CONNECTION Fault.
1
When mains voltage is connected to the RVS-DX, even if control voltage is disconnected, full voltage may appear on the starter load terminals. Therefore, for isolation purposes, it is necessary to connect an isolating device before (upstream) the starter.
2
Power factor correction capacitors or overvoltage protection devices must
not be installed on starters load side. When required, install it on starter’s
line side.
3
When using “Inside delta” connection, wrong connection of the starter or
the motor, will seriously damage the motor; therefore make sure motor is
connected properly!
4
Do not interchange line and load connections
5
Before starting the motor verify its rotation direction. If needed, disconnect the rotor from the mechanical load and verify the right rotation
direction.
6
Prior to Start up procedure make sure that line voltage and control
voltage match the ones shown on the starter’s name plate.
7
When start signal is initiated and a motor is not connected to load
terminals, the SHORT SCR or WRONG CONNECTION protection will be
activated.
8.1 Setting control voltage on-site RVS-DX8A-310A
Control voltage can be modified on-site for models 8A to 310A. See drawings below for jumper arrangement for 115/230V control voltages.
RVS-DX 8-44A
RVS-DX 58-72A
Note:
Pictures show RVS-DX8-44A & RVS-DX 58-72A. However, location of the jumper arrangement is very much the same for bigger units as well.
50 • STARTING P RO CEDURE
________________________________________________________________________________________
8.2 Standard starting procedure
Connect Control Supply. On LED will lit .
Review all parameters with Mode and Select keys Set parameters as required. If necessary, return to Default Par am eters (see “Service Mode”). Connect mains voltage to starter’s line terminals. Set LCD to show “MOTOR FLA” (% of motor FLA).
Motor starts to turn
shortly after Start
Initial inrush current or
mechanical shock is
Increase “Initial Voltage” and start again
Decrease “Initial Voltage” and start again
Speed accelerates
smoothly to nominal?
Apply Stop command and wait until motor stops.
Slightly increase Initial Voltage and Current Limit settings to allow for load changes.
Current during
acceleration is too
high?
Decrease “Current Limit”
Motor speed
accelerate to nominal?
Increase “Current Limit”
Yes
No
Yes
No
No
Yes
Yes
No
No
Yes
A
51 • STARTING P RO CEDURE
___________________________________________________________________________________________
8.3 102BExamples of starting curves
8.3.1 146BLight Loads-Pumps, Fans, etc.
INITIAL VOLTAGE – set to 30% (Factory Default) CURRENT LIMIT – set 300% ACCELERATION TIME – set 5 sec
Voltage quickly increases to the INITIAL VOLTAGE value and then gradually ramps-up to nominal. Current simultaneously and smoothly increases to reach CURRENT LIMIT setting or less, before smoothly decreasing to the operating current. Motor speed will accelerate to full speed quickly and smoothly.
8.3.2
147BHigh Inertia Loads – Fans, Centrifuges, etc
INITIAL VOLTAGE – set 50% CURRENT LIMIT – set 400% ACCELERATION TIME – set 20 sec
Voltage and current increase until current reaches CURRENT LIMIT. The voltage is held at this value until motor is close to nominal speed, then current will begin to decrease. The RVS-DX continues to ramp-up the voltage until reaching nominal. Motor speed smoothly accelerates to full speed.
Check total starting time and set Max. Start Time to approx. 5
seconds longer than the maximum time required to complete the
Motor acceleration time
to full speed is as
required?
No
Yes
Apply Start command
If acceleration time is too short, increase ACC.
TIME setting and/or decrease CURRENT LIMIT. (when decreasing CURRENT LIMIT, m ake sure motor increases speed gradually and does not stall).
A
52 • STARTING P RO CEDURE
________________________________________________________________________________________
8.3.3 Special starting – Using Dual Adjustment
For using DUAL ADJUSTMENT automatically, connect AUX. RELAY in series to Aux. Input as shown in section 8.3.3.1 on page 53. Program PROG. AUX. RELAY to IMMEDIATE and program RELAY ON DELAY to tx. Program PROG. INPUT C1 to DUAL ADJUSTMENT. Program Standard parameters and DUAL ADJUSTMENT parameters as shown in the table below. Using t o starting characteristics, the starter will accelerate to reach 200% current limit. After tx (PROG. AUX. RELAY DELAY) voltage to PROG. INPUT C1 is switched on, using the DUAL ADJUSTMENT characteristic to complete acceleration. Useful to prevent initial high acceleration. (Applications: Submersible pumps, Drum fans with resonating frequency, etc).
Standard Parameter
Dual Adjustment Parameter
INITIAL VOLTAGE
10%
25%
ACCELERATION TIME
t1 = 2-30 sec
t2 = 2-30 sec
CURRENT LIMIT
200%
300-400%
PROG. AUX. RELAY DELAY
tx = 1-60 sec.
-----
53 • STARTING P RO CEDURE
___________________________________________________________________________________________
8.3.3.1 Special starting – Using Dual Adjustment – wiring scheme
Notes:
(1) - Program PROG. INPUT C1 to DUAL ADJUST
(2) - Program PROG. AUX. RELAY to IMMEDIATE and program RELAY ON DELAY to tx.
Refer to section 7.6.9 on page 42 for details on I/O programming.
8.3.4 Choosing a suitable Pump Curve (centrifugal Pumps)
8.3.4.1 Starting Curve
Adjust MAIN PARAMETERS as necessary (FLA, FLC, etc..) Set STARTING CURVE, ACCELERATION TIME, CURRENT LIMIT, and INITIAL VOLTAGE to
their default values (curve 0, 10 sec., 400% and 30% respectively). Start the pump while watching the pressure gauge as the pump starts and look for overshooting
(“Pressure Surge”) of the gauge needle above the target pressure. In case of over pressure,
choose a peak torque reduction curve (Pump Control curve 1!). Set START CURVE 1!, increase ACCELERATION TIME to 15 seconds and reduce CURRENT
LIMIT to 350%. Start the pump and watch the pressure gauge while the pump starts. In most cases, overshooting is reduced. If the overshoot persists, increase ACCELERATION
TIME to 25 seconds (confirm with motor manufacturer) and try again. If the overpressure persists, increase START CURVE setting to 2!, or 3!, if necessary. Each
increase in START CURVE setting will reduce the Peak Torque, thus, reducing the
overpressure and preventing the “Pressure Surge” during start. To increase starting time above these maximums, employ “Special Starting” for these
techniques (Consult factory).
54 • STARTING P RO CEDURE
________________________________________________________________________________________
8.3.4.2 Stopping Curve
Adjust MAIN PARAMETERS as necessary (FLA, FLC, etc..) Set STOP CURVE and DECELERATION TIME, to their default values (curve 0, 10 sec.,
respectively). Stop the pump, watching the pressure gauge and check valve as the pump stops. Look for
overshooting (“Water Hammer”) of the gauge (abruptly stops the pump and the motor). Select STOP CURVE 1, increase DECELERATION TIME to 15 seconds. Stop the pump and
watch the pressure gauge and the rate of closing of the check valve as the pump stops. Abrupt
stopping of the pump and motor will cause a loud audible noise emitted from the check valve. In most cases, “Water Hammer” is reduced. If the “Water Hammer” persists, increase the time
to 25 seconds (confirm with motor manufacturer) and try again. If the “Water Hammer” persists, increase STOP CURVE setting to 2!, or 3!. Each increase in
STOP CURVE will reduce the abrupt stop of the pump, thus, preventing the “Water Hammer”
phenomenon.
8.3.4.3 Final torque during soft-stopping a pump motor
While decelerating, the check valve may close before DECELERATION TIME has elapsed, thus, allowing current to flow through stator winding causing unnecessary heat. Select FINAL TORQUE sensitivity to 1, and stop the pump, confirm that current stopped flowing through the motor shortly after the check valve closed. If current still flows more than 3-5 seconds after check valve closure, increase FINAL TORQUE up to 10 if necessary, to stop current flow earlier
55 • TROUBLE SHOOTING
___________________________________________________________________________________________
9. TROUBLE SHOOTING Upon fault – motor stops, Fault LED lights and Fault Relay operates. The LCD shows TRIP: and fault
description. (for example: TRIP: UNDER CURRENT).
Fault Massage
Cause and trouble shooting
TOO MANY
STARTS
Trips the starter if number of starts, during START PERIOD exceeds the preset
number.
Wait until motor and starter cool down – according to START INHIBIT setting. For more information on adjusting START PERIOD and START INHIBIT refer to section
7.6.4 on page 31.
LONG START
TIME
Trips the starter if output voltage does not reach nominal at the present MAX. START
TIME.
Check FLA, FLC, and MAX START TIME settings. Increase INITIAL VOLTAGE, CURRENT LIMIT & MAX. START TIME or decrease ACCELERATION TIME as necessary. For more information on FLC & FLA refer to section
7.6.3 on page 27 (MAIN
PARAMETERS). For more information on adjusting START PARAMATERS refer to section
7.6.4 on
page 31.
O/C – SHEAR
PIN
Trips the starter when:
Instantaneously when current exceeds 8.5 x Starter FLC. (not programmable) During starting when current exceed 8.5 x Motor FLA. (not programmable) During running when current exceeds 100-300%.(programmable value) O/C Shear-Pin has a programmable delay of 0-5 seconds where the starter detects the fault and does not trip before time delay has elapsed (delay is override when
current reaches 8.5 x Starter FLC).
Check that motor is not installed or Jammed.
Check FLA, FLC settings. Check motor and cable connections. Perform a “Megger” test to verify motor and cable’s condition. For more information on FLC,FLA & O/C – SHEAR PIN refer to section
7.6.3 on page 27
(MAIN PARAMETERS).
CAUTION
Check that “Meger” maximum voltage is no more than 500V !!
O/C or WRONG
CON.
Trips the soft RVS-DX when connected Inside Delta and Wrong connection or if over
current is detected by the RVS-DX.
Verify that the motor is not stalled or shorted and check cables and wiring. Verify that motor and RVS-DX are connected exactly as shown in section
4.3.9.2
page 13. If circuitry is 100% confirmed it is possible to start when WIDER SETTINGS are ENABLED. Refer to section
7.6.7 page 38. If a fault occurs again consult the factory.
The operator is advised to try operating one time only. Note that it is useless to try starting in this mode more than once.
OVERLOAD
Trips the starter when current exceed the OVERLOAD TRIP level and thermal
register has filled up.
Check FLA, FLC and Overload settings, check motor current, wait 15 minutes to let motor and starter cool down before restarting. For more information on FLC, FLA & OVERLOAD settings refer to section
7.6.3 on
page 27 (MAIN PARAMETERS).
56 • TROUBLE SHOOTING
________________________________________________________________________________________
Fault Massage
Cause and trouble shooting
UNDER
CURRENT
Trips the starter when line current drops below the preset level for the preset time.
Check UNDER CURRENT TRIP and TIME DELAY settings, check line currents through L1, L2, L3. For more information on UNDER CURRENT settings refer to section
7.6.3 on page
27 (MAIN PARAMETERS).
UNDER/NO
VOLTAGE
Trips the starter when line voltage drops below the preset level for the preset time.
Check UNDER VOLTAGE TRIP and TIME DELAY settings, check line voltages on L1, L2, L3. When voltage drops to zero, the starter trips immediately with no delay.
For more information on UNDER VOLTAGE settings refer to section
7.6.3 on page
27 (MAIN PARAMETERS).
OVER
VOLTAGE
Trips the starter when line voltage increases above a preset level for a preset time.
Check OVER VOLTAGE TRIP and TIME DELAY settings, check line voltage on L1, L2, L3. For more information on OVER VOLTAGE settings refer to section
7.6.3 on page 27
(MAIN PARAMETERS).
PHASE LOSS
Trips the starter if 1 or 2 phases are missing.
Check voltages are within the required range voltages and frequency is within the range of 45-65Hz.
If all previous actions are do not solve the problem and the you are sure that no real phase loss exists, you can set PHASE LOSS Y/N protection to NO. This situation can occur in rare cases when there is no real fault but the RVS­DX recognizes unusual behaviour like when Total Harmonic Distortion in Voltage (THDV) in the network is high.
If this is a true case of PHASE LOSS then after setting PHASE LOSS Y/N protection to NO the motor will single phase and most likely be tripped by the over load protection mechanism.
Phase loss might not be detected in motor operating under a light load.
For PHASE LOSS protection setting refer to section
7.6.8 page 40.
PHASE
SEQUENCE
Trips the starter if line phase sequence is wrong.
Check line phase sequence, and if wrong, swap two wires on line side. If motor now
rotates in the wrong direction, swap two wires on load side.
S. SCR OR WR.
CONNECTION
Trips the starter when one or more motor phases are not properly connected to
starter’s load terminals, in case of internal disconnection in motor winding or if any SCR is short-circuited or when motor windings are shorted.
Check with an ohmmeter between L1-U, L2-V, L3-W; resistance > 20 KΩ. Check for no voltage on terminals U, V, W (from parallel system or an independent by-pass). SCRs may fail due to:
High short current not protected by proper fuses High voltage spikes not protected by proper external Varistors. Frequent starting at maximum conditions or fault conditions.
If required, may be eliminated by using generator mode (programming AUX. IN PROG INPUT parameters accordingly) For more information on programming AUX. IN PROG INPUT refer to section
7.6.9 on
page 42(I/O PROGRAMMING PARAMETERS). Note:
Shorted SCR and Wrong Connection faults are not active in Generator mode.
57 • TROUBLE SHOOTING
___________________________________________________________________________________________
Fault Massage
Cause and trouble shooting
OVER
TEMPERATURE
Heat-sink over-temperature. Trips the starter when heat-sink temp. rises above 85˚C.
Check that motor starting is not too frequent.
EXTERNAL
FAULT In MAXIMIZED display Mode
Trips the starter when a N.O contact between Aux. input terminals 13, 14 closes for
over two seconds.
Check contact position and cause of closure. For more information on programming AUX. IN PROG INPUT refer to section
7.6.9 on
page 42(I/O PROGRAMMING PARAMETERS).
SLOW SPEED
TIME
Slow speed time is exceeded.
Check the settings of MAX SLOW SP TIME. For more information on programming MAX SLOW SP TIME refer to section
7.6.7 on
page 38 (SPECIAL FEATURES PARAMETERS).
Note:
Motor and RVS-DX may be overheated when operating at slow speed for an
extended period.
WRONG
PARAMETERS
Parameters not transferred from RAM to EEPROM or vice versa. After replacing the
EPROM with a new software version or after power up.
Press MODE and ▼ simultaneously, than press STORE and MODE simultaneously. By doing that, you are loading factory defaults to the RVS-DX. Now program all parameters into the RVS-DX like in a first start-up procedure.
(If Fault LED is on, press Reset after WRONG PARAMETERS).
MODBUS TIME
OUT
If no valid Modbus communication during MODBUS TIME OUT, the HRVS-DN will
trip. Trip occurs only if the following conditions exist:
SER. LINK CONTROL is set to ENABLE
SERIAL LINK NO. is not set to OFF
For MODBUS TIME OUT settings refer to section
7.6.10 page 44.
COMM. PORT
FAILED
Trips the RVS-DX if, when controlled via Profibus communication link, the
communication cable is torn or the communication from the PLC is lost. Note that the occurrence of this fault depends on then “Watch Dog” function of the Profibus controller.
You must reconnect the wiring and/or the communication with the PLC and wait for a start command initiated by the PLC.
FREQUENCY
Trips the soft starter when mains voltage frequency is not within the limits of 45-65Hz.
Check mains frequency.
58 • TROUBLE SHOOTING
________________________________________________________________________________________
9.1
Blank RMA Form
Return Material Authorization Form-“RMA” - Fault Report – Non/ Warranty Claim
After Sales Service Department E-mail: tech.support@solcon.com Tel. + 972 – 77-7711130, 972-77-7711123 Fax. + 972 – 77-7711140
To be completed By Solcon Service Dept.:
Return Material Authorization Number
Date
Authorized by
Equipment Model:
Equipment Serial no.:
Report date Date of equipment sale Date of installation Representing Firm
Contact person
Telephone number Fax number Email address
Application
Starter Rating
Motor current rating (motor Label)
Number of starts per hour
Special installation / ambient factors (°C)
Type of Fault Reported & time of occurrence (during start, after start, during soft stop, end of soft stop, ON B.P. closing, when …
Last Start Period
Total Number Of Trips
Last Start Max. I
Starter FLC
Total Run Time Motor FLC
Total Number Of Starts
Initial Voltage
Last Trip
Acceleration Time
Trip Current
Current Limit
Remarks
By Distributor: We declare that product has been correctly
applied, installed and operated, in accordance with Solcon’s written instructions, appropriate codes, regulations and good practice, within the limits of rated capacity and normal usage.
Warranted repair/replacement
59 • TECHNICAL SPECIFICATIONS:
___________________________________________________________________________________________
10. TECHNICAL S P E CIFICATIONS:
Supply Voltage Line to Line 230-600V (to be specified) + 10%-15% for all models Line to Line 690V (to be specified) + 10%-15% for RVS-DX 390A and up Frequency 45 – 65 Hz (Fixed or variable frequency source) Control Supply 115V or 230V (to be specified) +10% - 15% Load Three phases, three wires, squirrel cage induction motor.
Start-Stop Parameters:
Starter FLC Starter’s Full Load Current, according to Selector Guide Motor FLA Motor Full Load Ampere 50-100% of Starter FLC (Full Load Current). Pump and Torque Control Curves Field selectable curves preventing Over-pressure during start and Water
Hammer during stop. Pulse Start Duration A pulse of 80% Un, adjustable range 0.1-1 Sec, for st art i ng hi gh friction loads. Initial Voltage, 5-80% Un Initial Current 100-400% of Motor FLA Current Limit 100-500% of Motor FLA Acceleration Time 1-90 Sec Deceleration Time 1-90 Sec
Motor Protection:
Too Many Starts Maximum number of starts, range: Off or 1-10, during a time period 1-60 min. Starts inhibit Period of 1-60 min, during which starting is prevented, after Too Many Start
fault. Long Start Time (Stall protection) Maximum allowable starting time 1-30 sec. (1-250sec. in WIDER SETTINGS) Over Current (Shear-pin) Two operation functions: during starting t rips the starter at 850% and during
running at 100-850% In, both within 1 Cycle (after internal delay). Electronic Overload (I
2
t) Adjustable IEC and MEMA curves. Under Current Trips when current drops below 20-90% In, time delay 1-40 sec. Under Voltage* Trips when main voltage drops below 50-90%, time delay 1-10 Sec Over Voltage Trips when main voltage increase above 110-125%, time delay 1-10 sec. Phase Loss, Under/Over Frequency* Trips when one or two phases are missing and frequency i s 45H z. or 65Hz. Phase Sequence Trips when phase sequence is wrong Shorted SCR or Wrong connection Prevents starting, trips if motor is not connected / incorrectly connected to the
starter, or in case one or more SCRs have been shorted Heat Sink Over temp Trips when heat-sink temperature rises above 85˚C. External fault Trips when an External Contact closes for 2 sec.
* With optional Auto Reset. Control:
Displays LCD in 4 – Field selectable languages and 4 LEDs. Keypad 6 keys for easy setting Fault Contact 2 Contacts, 8A, 250VAC, 2000VA Aux. Contact – Imm. or End Of Acc. 2 Contacts, 8A, 250VAC, 2000VA
Temperatures: Operating -10˚ to 40˚C
Storage -20˚ to 70˚C
Standards:
Dielectric Test 2500VAC Degree of Protection IP 20 for frame size D1, IP 00 for frame sizes D2-D5 EMC Emissions EN 55011 CISPR 11 Class A Immunity EN 55082-2 ESD 8KV air, IEC 801-2 Electric RF field 10 V/m, 20-1000MHz, IEC 801-3 Fast transients 2KV, IEC 801-4 Safety EN 600947-1 Related to safety requirements. Designed and assembled to conform with UL508C
60 TECHNICAL S P ECIFICATIO NS :
________________________________________________________________________________________
Normal Service Conditions:
Altitude Up to 1000m. For equipment to be used at higher altitudes consult Factory. Humidity 95% at 50˚C or 98% at 45˚C.
Control Power Consumption
The approx. consumption of RVS-DX soft starters is as follows:
Model
Before bypass
Closed
Inrush During
bypass closing
After bypass
closed
8
20VA
20VA
20VA1720VA
20VA
20VA3120VA
20VA
20VA4420VA
20VA
20VA5820VA
20VA
20VA7220VA
20VA
20VA8520VA
20VA
20VA
105
20VA
20VA
20VA
145
20VA
20VA
20VA
170
20VA
20VA
20VA
210
20VA
30VA
30VA
310
20VA
30VA
30VA
390
20VA
600VA
40VA
460
20VA
800VA
40VA
580
20VA
1700VA
40VA
820
20VA
1700VA
40VA
950
20VA
2400VA
60VA
1100
20VA
2400VA
60VA
Notes:
Solcon Industries Ltd.
www.solcon.com; Technical support: office@solcon.com
Loading...