
X3 Series
4.0kW - 10.0kW
User Manual
Solax Power Network Technology(Zhe jiang) Co,. Ltd.
614.00235.05
Copyright Declaration
The copyright of this manual belongs to Solax Power Network Technology(Zhe jiang) Co,. Ltd.. Any
corporation or individual should not plagiarize, par titially or fully copy (including software,etc.),
and no reproduction or distribution of it in any form or by any means. All rights reserved. SolaX
Power Network Technology (Zhe jiang) Co.,Ltd.. reser ves the right of final interpretation.

Contents
Contents
1 Note on this Manual
1.1 Scope of Validity
1.2 Target Group
1.3 Symbols Used
2 Safety
2.1 Appropriate Usage
2.2 Important Safety Instructions
2.3 Explanation of Symbols
2.4 EC Directives
3 Introduction
3.1 Basic Features
3.2 Terminals of Inverter
3.3 Dimension
4 Technical Data
4.1 DC Input
4.2 AC Output
4.3 Efficiency, Safety and Protection
4.4 General Data
03
03
03
03
04
04
06
08
09
11
11
11
12
13
13
13
14
14
5 Installation
5.1 Check for Transport Damage
5.2 Packing List
5.3 Installation Precaution
5.4 Installation Steps
5.5 Connection of the Inverter
5.6 Run the Inverter
6 Operation Method
6.1 Control Panel
6.2 LCD Function
6.3 LCD Operation
15
15
15
16
17
18
28
29
29
30
31
01

Notes on this Ma nualContents
7 Troubleshooting
7.1 Trouble Shooting
7.2 Routine Maintenance
8 Decommissioning
8.1 Dismantling the Inverter
8.2 Packaging
8.3 Storage and Transportation
40
40
43
44
44
44
44
1 Notes on this Manual
1.1 Scope of Validity
This manual is an integral part of X3 Series, It describes the assembly,
installation, commissioning, maintenance and failure of the product. Please
read it carefully before operating.
X3-4.0-T-D X3-5.0-T-D
X3-4.0-T-N X3-5.0-T-N
X3-4.0-S-D X3-5.0-S-D
X3-4.0-S-N X3-5.0-S-N
X3-6.0-T-D X3-7.0-T-D X3-8.0-T-D X3-9.0-T-D X3-10.0-T-D
X3-6.0-T-N X3-7.0-T-N X3-8.0-T-N X3-9.0-T-N X3-10.0-T-N
Note: “4.0” means 4.0kW. ”T” means “dual” MPPT strings. ”S” means “single
MPPT. “D” means with “DC Switch”, ”N” means without “DC Switch”.
Keep this manual at where is accessible all the time.
1.2 Target Group
This manual is for qualified electricians. The tasks described in this manual
only can be performed by qualified electricians.
1.3 Symbols Used
The following types of safety instructions and general information appear in
this document as described below:
Danger!
“Danger” indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
Warning!
“Warning” indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
Caution!
“Caution” indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
Note!
“Note” provides tips that are valuable for the optimal
operation of your product.
0302

SafetySafet y
2 Safety
2.1 Appropriate Usage
The X3 Series are PV inverters which can convert the DC current of the PV
generator into AC current and feed it into the public grid.
Inverter
Distribution
Box
gure1
Surge protection devices (SPDs) for PV installation
►
WARNING !
Over-voltage protection with surge arresters should be provided
when the PV power system is installed.
The grid connected inverter is fitted with SPDs in both PV
input side and MAINS side.
Lightning will cause a damage either from a direct strike or from surges due to a
nearby strike.
Induced surges are the most likely cause of lightning damage in majority or installations,
especially in rural areas where electricity is usually provided by long overhead lines.
Surge may be included on both the PV array conduction and the AC cables
leading to the building.
Specialists in lightning protection should be consulted during the end use application.
Using appropriate external lightning protection, the effect of a direct lightning
strike into a building can be mitigated in a controlled way, and the lightning
current can be discharged into the ground.
Installation of SPDs to protect the inverter against mechanical damage and
excessive stress include a surge arrester in case of a building with external
lightning protection system (LPS) when separation distance is kept.
To protect the DC system, surge suppression device (SPD type2) should be fitted
at the inverter end of the DC cabling and at the array located between the
inverter and the PV generator, if the voltage protection level (VP) of the surge
arresters is greater than 1100V, an additional SPD type 3 required for surge protection
for electrical devices.
Distribution
Box
A
To protect the AC system, surge suppression devices (SPD type2) should be
fitted at the main incoming point of AC supply (at the consumer’s cutout),
located between the inverter and the meter/distribution system; SPD (test
impulse D1) for signal line according to EN 61632-1.
All DC cables should be installed to provide as short a run as possible, and positive
and negative cables of the string or main DC supply should be bundled
together. Avoiding the creation of loops in the system. This requirement for
short runs and bundling includes any associated earth bundling conductors.
Spark gap devices are not suitable to be used in DC circuits once conducting,
they won’t stop conducting until the voltage across their terminals is typically
below 30 volts.
Anti-Islanding Effect
►
1
Islanding effect is a special phenomenon that grid-connected PV
system still supply power to the nearby grid when the voltage loss is
happened in the power system. It is dangerous for maintenance
personnel and the public.
X3 series provide Active Frequency Drift(AFD) to prevent islanding
effect.
04
05

SafetySafety
2.2 Important Safety Instructions
Danger!
Danger to life due to high voltages in the inverter!
All work must be carried out by qualified electrician.
The appliance is not to be used by children or persons with
reduced physical sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given
supervision or instruction.
Children should be supervised to ensure that they do not play
with the appliance.
Caution!
Danger of burn injuries due to hot enclosure parts!
During operation, the upper lid of the enclosure and the
enclosure body may become hot.
Only touch the lower enclosure lid during operation.
Caution!
Possible damage to health as a result of the effects of radiation!
Do not stay closer than 20 cm to inverter for any length of time.
Note!
Grounding the PV generator.
Comply with the local requirements for grounding the PV
modules and the PV generator. SolaX recommends connecting
the generator frame and other electrically conductive surfaces
in a manner which ensures continuous conduction and ground
these in order to have optimal protection of system and persons.
Warning!
Ensure input DC voltage ≤Max. DC voltage .Over voltage
may cause permanent damage to inverter or other losses,
which will not be included in warranty!
Warning!
Authorized service personnel must disconnect both AC and
DC power from X3 series before attempting any maintenance
or cleaning or working on any circuits connected to the X3
series.
WARNING !
Do not operate the inverter when the device is running.
WARNING !
Risk of electric shock!
Prior to the application, please read this section carefully to ensure correct
and safe application. Please keep the user manual properly.
Use only attachments recommended or sold by SolaX. Otherwise may
result in a risk of fire, electric shock, or injury to person.
Make sure that existing wiring is in good condition and that wire is not
undersized.
Do not disassemble any parts of inverter which are not mentioned in
installation guide. It contains no user-serviceable parts. See Warranty for
instructions on obtaining service. Attempting to service the X3 Series
inverter yourself may result in a risk of electric shock or fire and will void
your warranty.
Keep away from flammable, explosive materials to avoid fire disaster.
The installation place should be away from humid or corrosive substance.
Authorized service personnel must use insulated tools when installing or
working with this equipment.
PV modules shall have an IEC 61730 class A rating.
Never touch either the positive or negative pole of PV connecting device.
Strictly prohibit touching both of them at the same time.
The unit contains capacitors that remain charged to a potentially lethal voltage
after the MAINS and PV supply has been disconnected.
Hazardous voltage will present for up to 5 minutes after disconnection from
power supply.
CAUTION-RISK of electric shock from energy stored in capacitor,. Never operate
on the solar inverter couplers, The MAINS cables, PV cables or the PV generator
when power is applied. After switching off the PV and Mains, always wait for
5minutes to let the intermediate circuit capacitors discharge before you unplug
DC and MAINS couplers.
When accessing the internal circuit of solar inverter, it is very important to wait
5minutes before operating the power circuit or demounting the electrolyte
capacitors inside the device. Do not open the device before hand since the
capacitorstime to sufficiently discharge! require
Measure the voltage between terminals UDC+ and UDC- with a multi-meter
(impedance at least 1Mohm) to ensure that the device is discharged before
beginning work (35VDC) inside the device.
0706

SafetySafety
PE Connection and Leakage Current
• The end-use application shall monitor the protective conductor by residual
current operated protective device (RCD) with rated fault current Ifn≤240mA
which automatically disconnects the device in case of a fault.
• DC differential currents are created (caused by insulation resistance and through
capacities of the PV generator). In order to prevent unwanted triggering during
operation, the rated residual current of the RCD has to be min 240mA.
The device is intended to connect to a PV generator with a capacitance limit of
approx 700nf.
WARNING !
High leakage current!
Earth connection essential before connecting supply.
• Incorrect grounding can cause physical injury, death or equipment malfunction
and increase electromagnetic.
• Make sure that grounding conductor is adequately sized as required by safety
regulations.
• Do not connect the ground terminals of the unit in series in case of a multiple
installation. This product can cause current with a d.c component, Where a residual
current operated protective (RCD) or monitoring (RCM) device is used for protection
in case of direct or indirect contact, only an RCD or RCM of type B is allowed
on the supply side of this product.
For United Kingdom
• The installation that connects the equipment to the supply terminals shall
comply with the requirements of BS 7671.
• Electrical installation of PV system shall comply with requirements of BS 7671
and IEC 60364-7-712.
• No protection settings can be altered.
• User shall ensure that equipment is so installed, designed and operated to
maintain at all times compliance with the requirements of ESQCR22(1)(a).
For Australia and New Zealand
• Electrical installation and maintenance shall be conducted by licensed
electrician and shall comply with Australia National Wiring Rules.
Symbols on the Inverter
SymbolExplanation
Operating Display.
Communication is active.
An error has occurred, please inform your installer immediately.
Symbols on the Type Label
SymbolExplanation
CE mark.
The inverter complies with the requirements of the applicable
CE guildlines.
RCM remark.
SAA certification.
Beware of hot surface.
The inverter can become hot during operation. Avoid contact
during operation.
Danger of high voltages.
Danger to life due to high voltages in the inverter!
Danger.
Risk of electric shock!
Observe enclosed documentation.
2.3 Explanation of Symbols
This section gives an explanation of all the symbols shown on the inverter and
on the type label.
The inverter can not be disposed together with the household waste.
Disposal information can be found in the enclosed documentation.
Do not operate this inverter until it is isolated from mains
and on-site PV generation suppliers.
Danger to life due to high voltage.
There is residual voltage in the inverter which needs 5 min to
discharge.
• Wait 5 min before you open the upper lid or the DC lid.
RoHS certificate
The inverter complies with the requirements of Restriction of
Hazardous Substances.
0908

SafetyIntroduction
2.4 CE Directives
This chapter follows the requirements of the European low voltage directives,
which contains the safety instructions and conditions of acceptability for the
endues system, which you must follow when installing, operating and
servicing the unit. If ignored, physical injury or death may follow, or damage
may occur to the unit. Read this instructions before you work on the unit. If
you are unable to understand the dangers, warnings, cautions or instructions,
please contact an authorized service dealer before installing. Operating and
servicing the unit.
The Grid connected inverter meets the requirement stipulated in Low
Voltage Directive (LVD) 2014/35/EU and Electromagnetic Compatibility (EMC)
Directive 2014/30/EU. The unit is based on:
EN 62109-1:2010 ; EN 62109-2:2011 ; IEC 62109-1(ed.1) ; IEC62109-2(ed.1)
EN 61000-6-3:2007+A:2011 ; EN 61000-6-1:2007 ; EN 61000-6-2:2005
In case of installation in PV system, startup of the unit (i.e. start of designated
operation) is prohibited until it is determined that the full system meets the
requirements stipulated in EC Directive (2014/35/EU,2014/30/EU, etc.)
The grid connected inverter leave the factory completely connecting device
and ready for connection to the mains and PV supply ,the unit shall be
installed in accordance with national wiring regulations. Compliance with
safety regulations depends upon installing and configuring system correctly,
including using the specified wires. The system must be installed only by
professional assemblers who are familiar with requirements for safety and
EMC. The assembler is responsible for ensuring that the end system complies
with all the relevant laws in the country where it is to be used.
The individual subassembly of the system shall be interconnected by means
of the wiring methods outlined in national/international such as the national
electric code (NFPA) No.70 or VDE regulation 0107.
3. Introduction
3.1 Basic features
Thanks for your purchasing with SolaX X3 Serial inverter. The X3 Series
inverter is one of the finest inverters on the market today, incorporating
state-of-the-art technology, high reliability, and convenient control
features.
Advanced DSP control technology.
Utilize the latest high-efficiency power component.
Optimal MPPT technology.
- Two independent MPP Tracking.
- Wide MPPT input range.
Advanced anti-islanding solutions.
IP65 protection level.
Max. efficiency up to 98.5%.EU efficiency up to 98%.
THD<2%.
Safety &Reliability: transformerless design with software and hardware
protection.
Export control.
Power factor regulation.
Friendly HMI.
- LED status indications.
- LCD display technical data, Human-machine interaction through press
key.
- PC remote control.
- Upgrade through USB interface.
- Pocket Wi-Fi/Lan monitoring.
- Control loads’ switch intelligently by RF.
- Energy conservation.
3.2 Terminals of inverter
FGHIJ
B
A
1011
D
C
E

Introduction Technic al Data
Object
ADC Switch (optional)
B
C
D
E
F
G
H
I
J
Warning!
Only authorized personnel is allowed to set the connection.
3.3 Dimension
Dimension
Ø
534mm
Description
DRM
Smart plug (optional)
USB for Upgrade
AC Connector
Waterproof plug
Pocket WiFi/Lan/GPRS (all optional)
RS 485/ Meter(optional)
PV Connector
Ground screw
201mm
419mm
4. Technical Data
4.1 DC input
X3-4.0-T-D/
Model
Max. recommended DC power [W]
Max. DC voltage[V]
Norminal DC operating voltage[V]
Operating voltage range [V]
MPPT voltage range@full load [V ]
Max. input current [A]
Max. short circuit current [A]
Start input voltage [V]
Start output voltage [V]
No. of MPP trackers
Strings per MPP tracker
DC disconnection swtich
4.2 AC output
Model
Rated output power [W]
Max.apparent AC power [VA]
Rated grid voltage and range [V]
Rated AC frequency and range [Hz]
Max AC current [A]
Max. output fault current [A]
Max. output overcurrent protection(A)
Max. inverter backfeed current to
the array(mA)
Inrush current(A)
THD
Displacement power factor
Feed in phase
Over voltage category
X3-5.0-T-D/
X3-4.0-T-NX3-5.0-T-N
5200
800
600
160-780
160-780
174-750
220-750
12/12
12/12
14/14
14/14
140
180
2
1
X3-4.0-T-D/
X3-5.0-T-D/
X3-4.0-T-N X3-5.0-T-N
5000
4000
5500
4400
8.0
6.4
9.0
7.4
X3-7.0-T-D/
X3-6.0-T-D/
X3-7.0-T-N
X3-6.0-T-N
6500
7800
800
800
600
600
160-780
261-750
12/12
14/14
140
140
180
180
2
2
1
1
X3-7.0-T-D/
X3-6.0-T-D/
X3-7.0-T-N
X3-6.0-T-N
6000
7000
6600
7700
3/N/PE,230/400 (310-480)
50(45-55)/60(55-65)
9.6
10.6
0.8 leading-0.8lagging
(electric supply side), ( side)IIIIIPV
8400
1000
600
160-950
302-800
12/12
14/14
140
180
2
1
optional
11.2
12
three-phase
X3-8.0-T-D
X3-8.0-T-N
9600
1000
600
160-950
348-800
12/12
14/14
140
180
2
1
X3-8.0-T-D/
X3-8.0-T-N
8000
8800
12.8
13.8
20
0
27
<2%
X3-9.0-T-D/
X3-9.0-T-N
10800
1000
600
160-950
390-800
12/12
14/14
140
180
2
1
X3-9.0-T-D/
X3-9.0-T-N
9000
9900
14.3
15.4
X3-10.0-T-D/
X3-10.0-T-N
12000
1000
600
160-950
430-800
12/12
14/14
140
180
2
1
X3-10.0-T-D/
X3-10.0-T-N
10000
11000
15.9
17.0
X3-4.0-S-D/
X3-5.0-S-D/
X3-4.0-S-NX3-5.0-S-N
4800
6000
1000
1000
600
600
160-950
160-950
348-800
430-800
12
12
14
14
140
140
180
180
1
1
1
1
X3-4.0-S-D/
X3-5.0-S-D/
X3-4.0-S-NX3-5.0-S-N
4000
5000
4400
5500
6.4
8.0
7.4
9.0
1213

Technic al DataInstallation
4.3 Efficiency, Safety and Protection
X3-4.0-T-D/
Model
MPPT efficiency
Euro efficiency
Max. efficiency
Safety & Protection
Over/under voltage protection
DC isolation protection
Monitoring ground fault protection
Grid protection
DC injection monitoring
Back feed current monitoring
Residual current detection
Anti-islanding protection
Over load protection
Over heat protection
X3-5.0-T-D/
X3-4.0-T-NX3-5.0-T-N
99.90%
99.90%
97.80%
97.80%
98.30%
98.30%
4.4 General Data
X3-4.0-T-D/
Model
Dimension [W/H/D](mm)
Dimension of packing [W/H/D](mm)
Net weight [kg]
Gross weight [kg]
Installation
Operating temperature range[℃]
Storage temperature [℃]
Storage/Operation relative humidity
Altitude [m]
Ingress Protection
Isolation type
Protective Class
Night-time consumption
Over Voltage Category
Pollution Degree
cooling
Noise level
Inverter Topology
Communication interface
Standard warranty [year]
14
X3-5.0-T-D/
X3-4.0-T-N X3-5.0-T-N
30303030
35
35
RS485/ WIFI/LAN/GPRS /Meter(optional)/ USB/ DRM
X3-7.0-T-D/
X3-6.0-T-D/
X3-7.0-T-N
X3-6.0-T-N
Inverter+BMU
99.90%
99.90%
97.80%
98.00%
98.30%
98.40%
X3-7.0-T-D/
X3-6.0-T-D/
X3-7.0-T-N
X3-6.0-T-N
Inverter+BMU
30
35
35
-25~+60 (derating at 45)
0%~100%, condensation
IP65(for outdoor use)
Ⅲ(MAINS),Ⅱ(PV)
X3-8.0-T-D/
X3-8.0-T-N
99.90%
98.00%
98.40%
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
X3-8.0-T-D/
X3-8.0-T-N
534*419*201
600*540*300
35
Wall-mounted
-25~+60
<2000
Transformerless
Ⅰ
<2w
Ⅱ
Natural Cooling
<35dB
non-isolated
5 (10 optional)
X3-9.0-T-D/
X3-9.0-T-N
99.90%
98.00%
98.50%
X3-9.0-T-D/
X3-9.0-T-N
30
35
X3-10.0-T-D/
X3-10.0-T-N
99.90%
98.00%
98.50%
X3-10.0-T-D/
X3-10.0-T-N
30
35
X3-4.0-S-D/
X3-5.0-S-D/
X3-4.0-S-NX3-5.0-S-N
99.90%
99.90%
97.80%
97.80%
98.30%
98.30%
X3-4.0-S-D/
X3-5.0-S-D/
X3-4.0-S-NX3-5.0-S-N
2828
33
33
5. Installation
5.1 Check for Transport Damage
Make sure the inverter is intact during transportation. If there are some
visible damages, such as cracks, please contact your dealer immediately.
5.2 Packing List
Open the package and fetch out the product, check the accessories at
first. The packing list shows as below.
AB
F
G
X3 Series 4.0KW-10.0KW
K
Object
B
C
D
E
F
G
H
I
J
K
L
M
N
H
L
Quantity
1
4
1
4
4
1
2(For AU)
1(For EN)
1
1
1
1
1
1
1
C
D
I
M
Description
X3 series inverter1A
Bracket
DC connector
AC connector/Inner hexagon spanner
Expansion bolt
DC pin contact(2*positive, 2*negative)
Earth terminal
Waterproof connector with RJ45
Product manual
Warranty card
Quick installation guide
Pocket LAN( Optional )
Pocket WiFi( Optional )
Meter( Optional )
E
J
N
15

Installation Installation
5.3 Installation Precaution
X3 Series inverter is designed for outdoor installation (IP 65).
Make sure the installation site meets the following conditions:
Not in direct sunlight.
Not in areas where highly flammable materials are stored.
Not in potential explosive areas.
Not in the cool air directly.
Not near the television antenna or antenna cable.
Not higher than altitude of about 2000m above sea level.
Not in environment of precipitation or humidity
Be sure the ventilation is good enough.
The ambient temperature in the range of -25℃ to +60℃.
The slope of the wall should be within ±5°.
The wall hanging the inverter should meet conditions below:
1.solid brick/concrete, or strength equivalent mounting surface;
2.Inverter must be supported or strengthened if the wall’s strength isn’t
enough(such as wooden wall, the wall covered by thick layer of decoration)
Please avoide direct sunlight, rain exposure, snow laying up during installing and
operating.
Available Space Size
Ø
5.4 Installation Steps
Preparation
Ø
Below tools are needed before installation.
Installation tools : crimping pliers for binding post and RJ 45, screwdriver,
manual wrench and φ10 driller.
Step 1: Screw the wall bracket on the wall
Ø
a) Use the wall bracket as a template to mark the position of the 4
holes on the wall.
b) Drill holes with driller, make sure the holes are deep enough (at
least 60mm) for installation, and then tighten the expansion tubes.
c) Install the expansion tubes in the holes, and tighten them. Then
install the wall bracket by using the expansion tubes.
Step 2: Match the inverter with wall bracket
Ø
d) Hang the inverter over the bracket, move the inverter close to it,
slightly lay down the inverter, and make sure the 4 mounting bars on the
back are fixed well with the 4 grooves on the bracket.
30cm
Table Available Space Size
30cm30cm
30cm
1617
PositionMin.size
Left
Right
Top
Bottom
Front
30cm
30cm
30cm
30cm
30cm
a)
b)
c)d)

Installation Installation
5.5 Connection of the Inverter
5.5.1 The Main Steps to Connect to the Inverter
PV String Connection
Ø
X3 series inverter have a couple of PV connectors which can be connected in
series into 2-strings PV modules. Please select PV modules with excellent function
and reliable quality. Open circuit voltage of module array connected should be <
Max.DC (table as follow) input voltage, and operating voltage should be within
the MPPT voltage range.
Model
Max.DC Voltage
Note!
Please choose a suitable external DC switch if the model (X3-4.0-
T-N, X3-5.0-T-N,X3-6.0-T-N,X3-7.0-T-N,X3-8.0-T-N,X3-9.0-T-
N,X3-10.0-T-N, X3-4.0-S-N, X3-5.0-S-N) is purchased.
Warning!
PV module voltage is very high which belongs to dangerous
voltage range, please comply with the electric safety rules when
connecting.
Warning!
Please do not make PV positive or negative ground!
Table 3 Max. DC Voltage Limitation
X3-4.0-T-D/
X3-5.0-T-D/
X3-4.0-T-NX3-5.0-T-N
800V
X3-6.0-T-D/
X3-6.0-T-N
X3-7.0-T-D/
X3-7.0-T-N
Inverter+BMU
X3-8.0-T-D/
X3-8.0-T-N
1000V
X3-9.0-T-D/
X3-9.0-T-N
X3-10.0-T-D/
X3-10.0-T-N
X3-4.0-S-D/
X3-5.0-S-D/
X3-4.0-S-NX3-5.0-S-N
Connection Steps
Below tools are needed before connection.
Wire crimper recommended model :
H4TC0001
Strpping pliers
Wire crimper
manufacturer:Amphenol
a) Turn off the DC switch, then Choose 12 AWG wire to connect the PV module.
b) Trip 6mm of insulation from the wire end by using the strpping pliers.
trip length
6.0 mm
12AWG
c) Insert striped wire into pin contact and ensure all conductor strand are captured
in the pin contact.
pin contact
d) Crimp pin contact by using the wire crimper.
Wire crimper
( recommended model: H4TC0001, manufacturer: Amphenol)
Crimp these parts
Note!
Please follow the requirements of PV modules as below:
Same type; Same quantity; Identical alignment; Identical tilt.
e) Separate the DC connector as two parts: the plug and the cable nut.
Then insert the wire with pin contact through the cable nut.
In order to save cable and reduce the DC loss, we suggest
installing the inverter near PV modules.
plug
cable nut
Danger!
Danger to life due to high voltage on DC conductors.
when exposed to sunlight,the pv array generates dangerous DC
voltage which is present in the DC conductors.Touching the DC
conductors can lead to lethal electric shocks.
f) Insert the wire into plug forcibly, when a "click” is heard or felt the pin contact
assembly is seated correctly. Then tighten the cable nut.
Cover the PV modules. Do not touch the DC conductors.
1819

Installation Installation
Grid Connection
Ø
X3 series inverter are designed for three phase grid. Rated grid voltage is 230V,
frequency is 50/60Hz. Other technical requests should comply with the
requirement of the local public grid.
Table 4 Cable and Micro-breaker recommended
X3-4.0-T-D/
Model
R,S,T,N Cable
PE Cable
Micro-breaker
*The parameters have some differences because of different environment and material. Please
according to the local conditions to choose appropriate cable and micro-breaker.
2.5-5mm²2.5-5mm²2.5-5mm²2.5-6mm²2.5-6mm²2.5-6mm²2.5-6mm²2.5-6mm²2.5-6mm²
X3-5.0-T-D/
X3-4.0-T-NX3-5.0-T-N
4-5mm²
4-5mm²4-5mm²5-6mm²
16A16A16A20A20A25A
X3-6.0-T-D/
X3-6.0-T-N
X3-7.0-T-D/
X3-8.0-T-D/
X3-7.0-T-N
X3-8.0-T-N
Inverter+BMU
5-6mm² 5-6mm²5-6mm²
X3-9.0-T-D/
X3-9.0-T-N
20A
X3-10.0-T-D/
X3-10.0-T-N
X3-4.0-S-D/
X3-5.0-S-D/
X3-4.0-S-NX3-5.0-S-N
4-5mm²4-5mm²
16A16A
Micro-breaker should be installed between inverter and grid, any loads
should not be connected with inverter directly.
Incorrect Connection between Load and Inverter
Connection Steps
d) Separate the AC plug into three parts as below.
- Hold the middle part of the male insert, rotate the back shell to
loose it, and datach it from male inset.
- Remove the cable nut (with rubber insert) from the back shell.
e) Slide the cable nut and then back shell onto the cable.
f) Insert the tripped end of each five wires into the appropriate hole in the
male insert, and then tight each screw (to tight each wire in place).(Use
the accompanying inner hexagon spanner)
g) Tighten the screw of the back shell and the male insert.
h) Tighten the screw of the back shell and the cable nut.
a) Check the grid voltage and compare with the permissive voltage range (refer to
technical data).
b) Disconnect the circuit-breaker from all the phases and secure against re-
connection.
c) Trip the wires:
- Trip all the wires to 52.5mm and the PE wire to 55mm.
- Use the crimping pliers to trip 12mm of insulation from wire ends as below.
R
S
T
20
I) Align the groove of male terminal with the convex of female terminal ,
then tighten the bush in male terminal.
21

Installation Installation
Selection of Fuses and Cables
Main cable(AC line cable)shall be short circuit protected and thermal overload
protected.
Always fit the input cable with fuse. Normal gG(US:CC or T)fuses will protect the
input cable in short circuit situation. They will also prevent damage to adjoining
equipment.
Dimension the fuses according to local safety regulations, appropriate input
voltage and the related current of the solar inverter.
AC output protected by external fuse(gG rated current 16A/600VAC for 4.0KW
/5.0KW/6.0KW; 20A/600VAC for 7.0KW/8.0KW/9.0KW;25A/600VAC for
10.0KW)provides in all live connections to the AC supply.
The rated short circuit breaking capacity of the above protective device shall be
at least equal to the prospective fault current at the point of installation. See
section technical data of this manual details.
AC output cable: Cu; R,S,T, N+PE: 3*4.0mm +4.0mm for 4.0KW/5.0KW/6.0KW and
2*5.3mm +5.3mm for 7.0KW/8.0KW/9.0KW; 3*5.3mm +5.3mm for 10.0KW @40℃
2222
22
ambient temperature with a max length of 5m, with operating time of the fuses is
less than 5 seconds, installation method B2 according to EN60204-1:2006, annex
D: cable in conduit cable trunking system, number of loaded circuit only one. Use
H07RNF(cord designation 60245 IEC66) for an ambient temperature of 40℃ or
less and use 90℃ wire for ambient temperature between 40℃ and 60℃.
Note 1: For condition differing form those mentioned above, dimension the
cables according to local safety regulations, appropriate input voltage and the
load and the load current of the unit.(You can choose a thicker cable but the
fuses must rated according to the cable.)
Note 2: Fuses must be approved by Notified Body.
Earth Connection
Ø
Screw the ground screw with screwdriver shown as follow.
5.5.2 Communication interface
This product has a series of communication interfaces: such as WIFI, RF,
RS485/Meter, DRM and USB for upgrading for human and machine
communication. Operating information like output voltage, current,
frequency, faulty information, etc., can be delivered to PC or other
monitoring equipment via these interfaces.
WiFi/Lan (Optional)
This inverter provides a WiFi/Lan port which can collect information from
inverter including status, performance and updating information to
monitoring website via connecting Pocket WiFi/Pocket Lan( purchase the
product from supplier if needed)
Connection steps:
Please check the Pocket WiFi user manual for more details.
Therefore the current-carrying capacity of the components and sub-assemblies
provided in the end-use system(connectors, cables, junction box, switch ger, etc.)
and the reverse current PV modules shall be considered based on the feedback
current and reverse current. The direct current(DC) circuit breaker or fuse
between each solar generator and inverter shall be provided based on solar
inverter input ratings.
Select DC cables based in the above inverter back-feed current and ISC PV rating
and Vmax ratings.
RF(Optional)
The inverter provides a RF(radio frequency) interface which can make a
load be switched or operated in a specied duration via connecting an
external Smart plug(purchase the product from supplier if needed.) so that
the load mostly consumes PV energy and incurs the lowest-possible
energy costs during operation.
Please check the Smart Plug user manual for the detail of connection steps.
2223

Installation Installation
RS 485/Meter
a. RS 485
This is a communication interface provided for engineer to adjust the inverter.
b. Meter(optional)
A meter can communicate with the X3 series inverter through this interface,
then you can:
X3 series inverter
Electrical
grid
Electric meter,
bidirectional
three-phase
meter
Load
The PIN denitions of RS 485/Meter interface are as below.
RS 485 Connection Steps:
1. Prepare RJ45 connector and a communication cable.
2. Trip the insulation from the communication cable.
3. Let the communication cable pass though the waterproof connector with
RJ45, then insert it into the RJ45 connector following the PIN definition rule.
Han d tight en.t orque :1.2±0.1N mHan d tight en.t orque :1.5±0.1N m
4. Crimp the RJ45 connector with the crimping plier.
5. Insert the cable into the RS 485/Meter port of the inverter, and tighten the
waterproof connector.
Meter Connection Steps:
Please see the Quick Guide for three-Phase Meter Installation for details.
4
DRM
DRM is provided to support several demand response modes by giving control
signals as below.
1
8
1.Monitor the energy to grid and from grid throughout the whole day.
2.Achieve the export control function with a higher accuracy.
1
Pin
Definition
1
2
34
DRM1/5DRM2/6DRM3/7DRM4/8
5
RefGen
6
Com/DRM0
78
V+
V-
8
PIN
Definition
1 2 3 4 5 6 7 8
XXXX
X
485_A
485_B
METER 485_A
METER 485_B
Connection Steps:
1.Prepare RJ45 connector and a communication cable.
2.Trip the insulation from the communication cable.
Note!
It is necessary to connect meter to inverter otherwise inverter will
shutdown with a “Meter fault” alert.
The smart meter must be authorized by Solax, any third party or
non-authorized meter may not match with the inverter.
3.Let the communication cable pass though the waterproof plug, then insert
it into the RJ45 connector following the PIN definition rule.
4. Crimp the RJ45 connector with the crimping plier.
5.Insert the cable into the DRM port of the inverter, and tighten the
waterproof plug.
Solax will not take the responsibility if the meter is unavailable.
24
25

Installation Installation
Upgrade
5
User can update the inverter system through an U-disk.
3) then insert U-disk into the USB port on the bottom of the inverter.
Then turn on DC switch or connect the PV connector, the LCD will show
picture as below.
Make sure the input voltage is more than 140V (in good
illumination condition), or it may result in failing during updating.
Upgrade Steps:
1) Please contact our service support to get the update file, and extract
it into your U-disk as the following file path:
“update\\618.00105.00_MIC__Vx.xx_xxxxxxxx.usb”;ARMARM
“update\DSP\618.00103.00_MIC_DSP_Vx.xx_xxxxxxxx.hex”.
Note: Vx.xx is version number, xxxxxxxx is file completion dates.
Make sure the directory is in accordance with above form
strictly! Do not modify the program file name ! Or it may cause
the inverter not work anymore !
2) Make sure the DC switch is off and the AC is disconnected with grid.
Unscrew the waterproof lid of Upgrade port by straight screwdriver as
below.
Straight screwdriver
U-disk
Update
ARM
DSP
4) Press up and down to select the one that you want to update and
press “OK” to confirm to update.
5) After the upgrade is complete, please remember to turn off the DC
switch or disconnect the PV connector, then pull off the U-disk, screw
the waterproof lid.
During updating, don’t turn off the DC switch or
disconnect the PV connector, if the updating is stopped
due to PV power failure,do not unplug the U-disk until the
PV power comes,update will continue. .if the updating is
stopped due to other reasons,reinsert the usb drive to
continue the update.
26
5
m
Waterproof lid
m
torque:1.5±0.2Nm
27

Installation Ope ration Method
5.6 Run the inverter
Start inverter after checking all below steps:
a) Check that device is xed well on the wall.
b) Make sure all the DC breakers and AC breakers are disconnected.
c) AC cable is connected to grid correctly.
d) All PV panels are connected to inverter correctly, DC connectors which
are not used should be sealed by cover.
e) Turn on the external AC and DC connectors.
f) Turn on the DC switch to the “ON”position.
Start inverter
Inverter will start automatically when PV panels generate enough energy.
Check the status of LED indication and LCD screen, the LED indication should be
blue and the LCD screen should display the main interface.
If the LED indication is not blue, please check the below:
- All the connections are right.
- All the external disconnect switches are closed.
- The DC switch of the inverter is in the “ON” position.
Below is the three different states when operating, which means inverter starting
up successfully.
Waiting: Inverter is waiting to checking when DC input voltage from panels is
greater than 100V(lowest start-up voltage) but less than 140V(lowest operating
voltage).
Checking: Inverter will check DC input environment automatically when DC
input voltage from the PV panels exceeds 140V and PV panels have enough
energy to start inverter.
Normal: Inverter begins to operate normally with blue light on. Meanwhile
feedback energy to grid, LCD displays present output power.
Enter the setting interface to follow the instructions when it is rst time to start
up.
Warning!
Power to the unit must be turned on only after installation
work has been completed. All electrical connections must
be carried out by qualied personnel in accordance with
legislation in force in the country concerned.
6. Operation Method
6.1 Control panel
A
B
E
F
Object Name Description
Display the information of the inverter.
Blue:The inverter is in normal state.
Yellow:The inverter is in communication.
Red:The inverter is faulty.
ESC button: Return from current interface or function.
Up button: Move cursor to upside or increase value.
Down button: Move cursor to downside or decrease value.
OK button: Conrm the selection.
B
A
E
H
C
D
F
G
LCD Screen
Indicator
LED
Function
Button
C
D
H
G
Note!
Please set the inverter if it is the first time to start up.
Above steps are for the regular start of the inverter. If it is the first
time to start up the inverter, you need to setup the inverter.
282829

Ope ration MethodOpe ration Method
6.2 LCD Function
Menu structure
Grid
Status
Setting
Main
menu
History
About
Note: ” ”Can be set by the end user.
Others can only be set by the technical or the installer with the installer password.
Solar
Load
Password
Inverter Yield
Load Consume
Meter
Error Logs
Produt SN
Register SN
Machine Type
Master
Slave
Manager
Safety
Date Time
New Password
PV Connection
Export Control
RF Control
DRM Function
LineImpedance
Grid Services
Grid Protection
Energy Reset
Load Reset
Meter Reset
Errorlogs Reset
Start Guide
P(freq)
Soft Start
ConditionConn
Reactive Power
P(u) Function
Power Limits
Neutral Line
6.3 LCD Operation
● LCD Digital Display
The main interface is the default interface, the inverter will automatically
jump to this interface when the system started up successfully or not
operated for a period of time.
The information of the interface is as below. “Power” means the timely
output power; “Pgrid” means the power export to or import from the
grid.“Today” means the power generated within the day.“Normal”shows
the status of the inverter.
Power
Pgrid
Today
Normal
00.0KWh
0W
0W
● Menu interface
The menu interface is a transfer interface for user to get into other interface
to finish the setting or getting the information.
-User can get into this interface by pressing “OK” button when LCD displays
the main interface.
-User can select interface by moving the cursor with function button,and
press “OK” to confirm.
﹦﹦﹦﹦
● Status
The status function contains three aspects of the inverter, grid, solar and
load.
Press up and down to select and press “OK” to confirm the selection, press
“ESC” to return to Menu.
﹦﹦﹦﹦ Status ﹦﹦﹦﹦
a) Grid
This status shows the current grid condition such as voltage, current,
output power and grid power. Pout measures the output of the inverter,
Pgrid measures power export to or import from grid. Positive value means
the power feeds into grid, negative value means the power used from the
grid.
Press up and down button to review the parameter, press “ESC” to return to
Status .
Menu
Status
Settings
History
Grid
Solar
Load
﹦﹦﹦﹦
3031

﹦﹦﹦﹦ Grid ﹦﹦﹦﹦
Ua
Ia 0.0A
Fa
0
.0 V
00.00Hz
Ope ration MethodOpe ration Method
Password
The default password is “0000”for end user, which only allows the user to
review the current setting and some easy setting. If professional change is
needed, please contact with the distributor or factory for installer password.
We need to increase or decrease the word by pressing up or down button.
Press OK to confirm an alternate to the next word. After word is confirmed,
,press “OK” to enter password.
b) Solar
This status shows the real time PV condition of the system,
such as input voltage, current and power situation of each PV input.
Press up and down button to review parameter, Press “ESC” to return to Status.
c) Load
If the inverter is plugged in a smart plug, this status shows the real time
load power, include load1 power and load 2 power.
Press up and down button to review parameter, Press “ESC” to return to
Status.
﹦﹦﹦﹦ Solar ﹦﹦﹦﹦
U1 0.0V
I 1 0.0A
P1 0.0W
﹦﹦﹦﹦ Load ﹦﹦﹦﹦
L1 Power
0W
●Settings
Setting function is used for setting the inverter for time, connection, Grid
and so on.
Since this function will change the inverter's parameter, the end user with
the user password as”0000” has the limited authority to change the setting.
We need installer password to do most of the professional setting.
﹦﹦﹦﹦Password ﹦﹦﹦﹦
0 0 0 0
Setting
If inputting the installer password, the information of the LCD interface is
as below.
﹦﹦﹦﹦Setting ﹦﹦﹦﹦
Safety
Language
a) Safety
The user can set the safety standard here. According to different countries
and grid tied standards. There is several standards for choice (May change
without notice.)
﹦﹦﹦﹦Safety ﹦﹦﹦﹦
country
VDE4105
Item
Standard
AS/N2S 4777.2:2015
1
2
EN50549_NL
Country
Australia
Netherland
Item
3
4
Standard
IEC 61727
VDE 4105
Country
India
German
3233

b) Date time
This interface is for user to set the system date and time. Increase or decrease
the word by pressing up or down button. Press OK to confirm and alternate
to next word. After all the words are confirmed. Press “OK” to enter the date
and time.
c) New Password
Installer can set the new password here. We need to increase or decrease the
word by pressing up or down button. Press OK to confirm and alternate to
next word. After word is confirmed., press “OK” to reset the password.
﹦﹦﹦﹦Date time ﹦﹦﹦﹦
2016 >06 <06
10 19
﹦﹦﹦New Password ﹦﹦﹦
1 2 3 4
Ope ration MethodOpe ration Method
>Enable/Disable
f) RF Control
RF Control is an optional function which can control designated load
intelligently by consuming the surplus energy when feed in power reaches
certain value.
For specific operation, please refer to “ Load remote control installation guide”.
RF Control
>Load1 setting
>Load2 setting
g) DRM Function
User can choose whether using the DRM function or not.
d) PV Connection
This function can set the mode of PV input. There are two modes for choice:
Comm and Multi. The “Comm” mode mean single MPP tracking, 2 MPPT
working together; “Multi” means multi-MPP tracking, 2 MPPT work
independently.
Press up or down button to select and press “OK” to confirm.
﹦﹦﹦PV Connection﹦﹦﹦
PV Connection
Multi
e) Export control
With this function the inverter can control energy exported to the grid.
Whether having this function is based on user’s wishes.
Choose ”Enable” in ”Enable/Disable” means user must install a meter to
monitor energy exported to the grid. There are user value and factory value.
The factory value is default which can not be charged by user. The user value
setting by installer must be less than the factory value and within the range of
0KW to 20KW.
Choose”Disable” means the function will be shut off.
Press up and down button to select and press”OK” to confirm.
3435
h) Line Impedance
If able is choosen, the inverter will identify actively the imdepance between
the inverter and grid, and reduce the effect on input port of the inverter. This
function is disable by default.
i) Grid Services
Usually end user do not need to set the grid parameters. All default value have
been set before leaving factory according to safety rules.
If need to reset, any changes should according to the requirement of local
grid.
WARNING !
Please enter setting and enable “netural line” if there is no netural
cable in the wiring.
﹦﹦﹦DR M Function
>Enable/Disable
Disable
﹦﹦﹦﹦
>Enable/Disable
Disable
Line Impedance
﹦﹦﹦﹦
﹦﹦﹦﹦

Ope ration MethodOpe ration Method
1.
﹦﹦﹦﹦P(freq) ﹦﹦﹦﹦
Enable/Disable
>Disable <
2.
﹦﹦﹦﹦Soft start ﹦﹦﹦﹦
Enable/Disable
>Disable <
If need to reset, any changes
should according to the
requirement of local grid.
If need to reset, any changes
shou ld accord ing t o t he
requirement of local grid.
3.
ConditionConn
﹦﹦﹦﹦
Enable/Disable
>Disable <
﹦﹦﹦﹦
If need to reset, any changes
shou ld accord ing t o t he
requirement of local grid.
4-1.
Reactive Power
﹦﹦﹦﹦
Mode Selection
>Off <
﹦﹦﹦﹦
If need to reset, any changes
shou ld accord ing t o t he
requirement of local grid.
4-2.
Reactive power control, Reactive standard curve cos φ = f(P)
For VDE ARN 4105, curve cos φ = f(P) should refer to curve A. default values of setting are
as shown in curve A.
For E 8001, curve cos φ = f(P) should refer to curve B. default values of setting are as
shown in curve B.
Upper limit
0.9
curve B
V
Power Upper
0.8
0.7
inductive
0.2
0.3
Power Lower
capactive
0.9
Qmax
Lower limit
V2s=1.10Vn
V1s=1.08Vn=QuVlowRate
V2i=0.90Vn
V2i=0.92Vn=QuVlowRate
V2sV1s
curve A
Reactive power control, Reactive standard curve Q= f(V)
Q
V1iV2i
-Qmax
f (P)
36
ModeComment
Off
Under-ExcitedPF value
Over-ExcitedPF value
PF(P)
Q( u )
Fix Q PowerQ Power
-
Upper limit
Lower limit
Power Upper
Power Lower
Q(u) Range V1 (AS_4777.2)
Q(u) Range V4 (AS_4777.2)
Q(u) V Up Rate (EN50549_NL)
Q(u) V Low Rate (EN50549_NL)
5.
6.
7.
P(u) Function
﹦﹦﹦
Enable/Disable
Power Limits
﹦﹦﹦﹦
>Proportion
1.00
Neutral line
﹦﹦﹦
YES/NO
YES
>Enable<
﹦﹦﹦﹦
﹦﹦﹦
﹦﹦﹦
The device is suitable for Australia if
the “Enable” is chosen.
User can set the power limit
here, the setting value is from
0.00-1.00.
User can set the Neutral line
connection here.
37

Ope ration MethodOpe ration Method
j) Grid Protection
Usually end user do not need to set the grid Protection. All default value have
been set before leaving factory according to safety rules.
If need to reset, any changes should according to the requirement of local grid.
Grid Protection
﹦﹦﹦﹦
>O/V Stage1
295.0
﹦﹦﹦﹦
k) Energy Reset
User can reset the energy record here. Press up or down button to select and
press “OK” to confirm.
l) Load Reset
Reset consume is to reset load, user can reset the load if the inverter is plugged
in a smart plug. Press up or down button to select and press “ok” to conrm.
m) Meter Reset
User can reset the meter. Press up or down button to select and press “ok” to
conrm. (User can Select “Yes” to reset meter if user purchase SolaX meter)
﹦﹦﹦Energy Reset ﹦﹦﹦﹦
Reset
No
﹦﹦﹦
Load Reset
Load 1 Reset
﹦﹦﹦Meter Reset﹦﹦﹦﹦
Reset
>No<
﹦﹦﹦﹦
>No<
o) Start guide
This interface makes user set initial setting of the inverter again possible.
● History
The history function contains four aspects of the information: Inverter yield, load
consume, Meter and error logs.
Press up and down to select ,and press “OK” to confirm the selection, press
“ESC” to return to Menu.
a) Inverter Yield
The inverter yield function contains energy generated by today, yesterday ,this
month ,last month and total.
Press up and down button to review the parameter, Press “ESC” to return to
history.
b) Load consume
User can check the load consumption if the device is plugged in a smart plug.
﹦﹦﹦
﹦﹦﹦﹦
﹦﹦﹦﹦
Start guide
>Start
﹦﹦﹦﹦ History ﹦﹦﹦﹦
>Inverter Yield
Load consume
Meter
Inverter Yield
>Today:
﹦﹦﹦
﹦﹦﹦﹦
0.0KWh
Load consume
>Load 1 consume
Load 2 consume
﹦﹦﹦﹦
n) Errorlogs Reset
User can reset the error log here. Press up or down button to select and
press “OK” to confirm.
3839
﹦﹦﹦
Errorlogs Reset﹦﹦﹦
Reset
No
c) Meter
This function is made user check meter energy possible. (Meter energy
will show if user use SolaX meter)
﹦﹦﹦﹦
>Today Export:
Meter
﹦﹦﹦﹦
00.0KWh

d) Error logs
The Error log contains error information happened, It can record for six
items.
Press up and down button to review parameter, Press“ESC” to return to
History.
﹦﹦﹦﹦Error log ﹦﹦﹦﹦
>
No error
●About
This interface shows information of the inverter, include serial number,
product SN, machine type, master, slave and manager.
TroubleshootingTroubleshooting
﹦﹦﹦﹦About ﹦﹦﹦﹦
>Product S N:
XX XXXXXX XXXXX X
7. Troubleshooting
7.1 Trouble shooting
This section contains information and procedures for solving possible
problems with X3 series inverters, and provides you with troubleshooting
tips to identify and solve most problems that could occur with the X3 series
inverters.
This section will help you narrow down the source of any problems you may
encounter. Please read the following troubleshooting steps.
Check warnings or fault messages on System Control Panel or Fault codes
on the inverter information panel. If a message is displayed, record it before
doing anything further.
Attempt the solution indicated in below table.
4041

TroubleshootingTroubleshooting
● If your inverter's information panel is not displaying a Fault light, check the
following list to make sure that the present state of the installation allows
proper operation of the unit.
— Is the inverter located in a clean, dry, adequately ventilated place?
— Have the DC input breakers been opened?
— Are the cables adequately sized and short enough?
— Are the input and output connections and wiring in good condition?
— Are the configurations settings correct for your particular installation?
— Are the display panel and the communications cable properly
connected and undamaged?
Contact SolaX Customer Service for further assistance. Please be prepared to
describe details of your system installation and provide model and serial number
of the unit.
7.2 Routine maintenance
Inverters do not need any maintenance or correction in most condition, but if
the inverter often loses power due to overheating, this can be the following
reason:
● The cooling fins on the rear of house are coverd by dirts.
Clean the cooling fins with a soft dry cloth or brush if necessary.
Only trained and authorized professional personnel who are familiar with the
requirements of safety was allowed to perform servicing and maintenance
work.
42
Meter Fault
AC10M Volt Fault
Meter Fault
Check if the meter is connected properly.
Check if the meter set normally.
Or seek help from us.
AC10Minute overvoltage Fault
System will reconnect if the utility is back to normal.
Or seek help from us.
► Safety checks
Safety checks should be performed at least every 12 months by manufacturer's
qualified person who has adequate training, kownledge, and practical experience
to perform these tests. The data should be recorded in an equipment log. If the
device is not functioning properly or fails any of test, the device has to be
repaired. For safety check details, refer to this manual, section 2 Safety instruction
and EC Directives.
►Maintain periodically
Only qualified person may perform the following works.
During the process of using the inverter, the manage person shall examine
and maintain the machine regularly. The concrete operations are follow.
1: Check that if the cooling fins on the rear of house are covered by dirts,
and the machine should be cleaned and absorbed dust when necessary.
This work shall be check time to time.
2: Check that if the indicators of the inverter are in normal state, check if the
keys of the inverter are in normal state, check if the display of the inverter is
normal. This check should be performed at least every 6 months.
3: Check that if the input and output wires are damaged or aged. This check
should be performed at least every 6 months.
4: You should get the inverter panels cleaned and their security checked at
least every 6 months.
43

Decommissioning
8. Decommissioning
8.1 Dismantling the Inverter
Disconnect the inverter from DC Input and AC output.
Wait for 5 minutes for de-energizing.
Disconnect communication and optional connection wirings.
Remove the inverter from the bracket.
Remove the bracket if necessary.
8.2 Packaging
If possible, please pack the inverter with the original packaging.
If it is no longer available, you can also use an equivalent carton that meets
the following requirements.
Suitable for loads more than 30 kg.
With handle.
Can be fully closed.
8.3 Storage and Transportation
Store the inverter in dry place where ambient temperatures are always
between -25°C - +60°C. Take care of the inverter during the storage and
transportation,keep less than 4 cartons in one stack.
When the inverter or other related components need to be disposed. Have
it carried out according to local waste handling regulations. Please be sure
to deliver wasted inverters and packing materials to certain site, where can
assist relevant department to dispose and recycle.
44