Solas-Nua SL-16N, SL-16P Installation & Operation Manual

Installation & Operation Manual
This manual specifies the installation and opera­tion requirements for the Fireplace
This appliance may be installed in an aftermar­ket, permanently located manufactured home (USA only) or in a mobile home, where not pro­hibited by local codes.
This appliance is for use only with the type of gas indicated on the rating plate. This appli­ance is not convertible for use with other gases, unless a certified conversion kit is used.
Ce manual est disponsible en Français sur demande.
Report # 361-F-02-5
(Copreci) Model Nos. SL-16N, SL-16P.
WARNING: If the information in these in­structions is not followed exactly, a fire or explosion may result causing property dam­age, personal injury or loss of life.
- Do not store or use gasoline or other flam­mable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
 Do not try to light any appliance.  Do not touch any electrical switch; do not
use any phone in your building.
 Immediately call your gas supplier from a
neighbor’s phone. Follow the gas sup­plier’s instructions.
 If you cannot reach your gas supplier, call
the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
AVERTISSEMENT: Assurez-vous de bien suivre
les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d’essence ni
d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
 Ne pas tenter d’allumer d’appareil.
 Ne touchez à aucan interrupteur. Ne pas
vous servir des téléphones se trouvant dans le bâtiment où vous trouvez.
 Appelez immédiatement votre
fournisseur de gaz depuis un voisin. Suivezles instructions du fournisseur.
 Si vous ne pouvez rejoindre le fournisseur
de gaz, appelez le service des incindie.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Cet appareil peut être installé dans une maison préfabriquée (mobile) déjà installée à demeure si kes règlements locaux le permettent.
Cet appareil doit être uniquement avec las type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
Ne pas utiliser cet appareils’il a été plongé, meme partiellement, dans l’eau. Appeler un technician qualifié pour inspecter l’appareail et remplacer toute partie du système de commande et toute commande qui a été plongée dans /’eau.
Attention. Au moment de l’entretien des com­mandes, étiquetez tous les fils avant de les dé­brancher. Des erreurs de la câblage peuvent en­traîner un fonctionnement inadequate et dan­gereux.
S’assurer que l’appareil fonctionne adéquate­ment une fois l’entretien terminé.
AVERTISSEMENT. Ne pas utiliser l’appareil si le panneau frontal en verre n’est pas en place, est craqué ou brisé. Confiez le remplacement du panneau à un technician agree.
INSTALLATEUR: Laissez cette notice avec l’appareil.
COMSOMMATEUR: Conservez cette notice pour consultation ultérieur.
2
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION 4
SPECIFICATIONS 5
INSTALLATION REQUIREMENTS 6
MASSACHUSETTS REQUIREMENTS 7
VENTING 8
ASSEMBLY & INSTALLATION 16
GAS CONNECTION 20 & 26
LIGHTING AND OPERATION 32
COPRECI CONTROL SYSTEM 34
TROUBLESHOOTING 42
MAINTENANCE 43
MAINTENANCE LOG FORMS 45
REPLACEMENT PARTS LIST 46
CONTROL SCHEMATIC 47
INSTALLATION RECORD FORM 48
WARRANTY INFORMATION 49
WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BE­GININNG THE INSTALLATION OF THE SOLAS DIRECT VENT GAS FIREPLACE. AL­THOUGH THE BASIC REQUIREMENTS FOR THE INSTALLATION OF ALL DIRECT VENT GAS FIREPLACES ARE SIMILAR, EACH SPECIFIC PRODUCT HAS ITS OWN UNIQUE SET­UP AND INSTALLATION REQUIREMENTS THAT MUST BE FOLLOWED EXACTLY. PLAN YOUR INSTALLATION IN ADVANCE BY CAREFULLY REVIEWING ALL THE INFORMA­TION CONTAINED IN THIS MANUAL.
3
IMPORTANT SAFETY INFORMATION
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 or the Canadian Installation Code, CAN/CGA B149.
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 or when such a standard is not applica- ble, the Standard for Manufactured Home Installations, ANSI/BCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
The installation must provide for adequate ventilation air to the appliance. This gas appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance. The appliance, when installed, must be electrically grounded in accordance with local codes, or, in the
absence of local codes, with the National Electrical Code ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22. 1.
The appliance area must be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
The flow of combustion and ventilation air must not be obstructed. Do not use this appliance if any part has been under water. Immediately call a qualifed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance. Clothing or other flammable material should not be placed on or near the appliance. Any screen or guard removed for servicing an appliance must be replaced prior to operating the appliance. Installation and repair should be done by a qualified service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartments, burners and circulating air passageways of the appliance be kept clean.
WARNING: Do not operate the appliance with the glass door assembly removed, or if the glass is
cracked or broken. Replacement of the glass should be done by a qualified service person.
WARNING: Use only glass assembly, P/N 16-510 which includes the glass panel, frame and gasket.
Do not use substitute materials. Do not strike or slam the glass front. Do not use abrasive cleaners. Do not clean when hot.
4
SPECIFICATIONS
INPUT Natural Gas Propane (LP) Input Rating-Btu/hr 13,500 13,500
Min. Input-Btu/hr 7,500 7,500 Orifice-DMS #53 #58 GAS SUPPLY Manifold Pressure 4.8”w.c. / 1.2kPa 10.0”w.c. / 2.5kPa Min. Supply Pressure 5.5”w.c. / 1.4kPa 11.0”w.c. / 2.8kPa Max. Supply Pressure 10.0”w.c. / 2.5kPa 13.0”w.c. / 3.3kPa EFFICIENCY Maximum Observed Steady State Efficiency - % 79.0 77.8 Steady State Efficiency - % 62.6 56.4 Annual Fuel Utilization Efficiency (AFUE) - % 50.9 45.0 Canadian p.4 Efficiency - % 56.2 47.8 NOTE: The maximum achievable steady state efficiency can vary depending on how the fireplace is installed and operated.
It is recommended that the pilot flame be turned off if the appliance will not be in use for an extended period of time. This appliance is equipped for use with the fuel type indicated on the rating plate.
This appliance has been certified by OMNI-Test Laboratories, Inc. to ANSI Z21.88a-2007 • CSA 2.33a­2007 Vented Gas Fireplace Heaters and CAN/CGA-2.17-M91, Gas-Fired Appliances for Use At High Altitudes.
The is approved for installation at elevations up to 2000 feet in the U.S. and 1370 meters (4500 feet) in Canada without change. If your installation is at an elevation greater than these, consult with the local authority having jurisdiction for gas product installations to determine their specific requirements for high altitude installations.
5
INSTALLATION REQUIREMENTS
Several issues must be addressed when selecting a suitable location for your fireplace. The mini­mum clearances to combustible construction are listed below. In addition, access to the gas supply must be considered. The location of the fireplace will also affect the venting requirements and you must be certain the location will allow compliance with the venting requirements shown on page 8. You must also insure that your installation provides adequate accessibility clearance for servicing and proper operation.
Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passageways of the appliance be kept clean.
MINIMUM CLEARANCES TO COMBUSTIBLE CONSTRUCTION
Fireplace to L. Side Wall 6” (152mm) Fireplace to Ceiling 8” (203mm) Fireplace to R. Side Wall 6” (152mm) Fireplace to Rear Wall 0” (0mm)* Fireplace to Corner Wall 6” (152mm) Fireplace to Floor 3” (76mm)** Vent Pipe to Adjacent Materials 1.5” (38mm) *Mounting plate bosses contact the wall **The minimum required clearance to be maintained from the fireplace to combustible flooring is meas­ured from the top surface of carpeting, tile, etc.
A = 6” (152mm)
B = 6” (152mm)
A A
WALLS
CEILING
C = 8” (203mm) D = 3” (76mm)
FLOOR
E = 5/16” (8mm)
C
D
WALL
E
B B
CORNER (SHOWN USING OPTIONAL CORNER KIT)
AIR SPACE BEHIND MOUNTING PLATE
6
INSTALLATION REQUIREMENTS
The gas fireplace is shipped with a plugged 3/8” NPT connection. The gas supply piping should have a separate gas shutoff valve and a 1/8” NPT plugged tapping upstream of the valve. The stove and its main control valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The stove must be isolated from the gas supply pip­ing system by closing the main control valve during any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi (3.5 kPa). After the gas supply has been connected, use a commercial gas leak detector or apply a soapy water solution to all the fittings to check for gas leaks. Never use a flame to test for leaks.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
This product must be installed by a licensed plumber or gas fitter when installed within the Com­monwealth of Massachusetts. If this appliance is installed in a dwelling, building or structure used in whole or in part for residential purposes and the installation includes a horizontal vent termination that is less than seven (7) feet above the finished grade in the area of the venting, including but not limited to decks and porches, a hard-wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level of the dwelling, building or structure where the appli­ance is to be installed.
Additionally, a hard-wired or battery operated carbon monoxide detector with an alarm must be in­stalled on each additional level of the dwelling, building or structure served by the appliance. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard-wired carbon monoxide detectors.
In the event that the horizontally vented appliance is installed in a crawl space or attic, the hard­wired carbon monoxide detector with alarm and battery back-up may be installed on the next adja­cent floor level.
In the event that this requirement cannot be met at the time of completion of the installation of the appliance, the owner shall have a period of thirty (30) days to comply with the requirement. How­ever, during said thirty (30) day period, a battery operated carbon monoxide detector with alarm must be installed.
Each carbon monoxide detector as required in accordance with the above provisions must comply with NFPA 720 and be ANSI/UL 2034 and IAS certified.
In addition when the vent termination is less than seven (7) feet above finished grade a metal or plas­tic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
A COPY OF THESE INSTRUCTIONS PLUS ALL VENTING INSTRUCTIONS WHICH IN­CLUDE PARTS LISTS, AND/OR ALL VENTING DESIGN INSTRUCTIONS MUST REMAIN WITH THE STOVE AT THE COMPLETION OF THE INSTALLATION.
ATTENTION INSTALLERS: Mark below which venting system was used in the installation. These instructions must remain with the Installation & Operation Manual.
Simpson DuraVent GS/PRO® Selkirk Direct-Temp®
AmeriVent Direct™ Metal Fab Direct Vent
7
Security Secure Vent™
ICC Direct Vent
VENTING
The Direct Vent Gas Fireplace has been tested and listed for installation with 4” X 6 5/8” Simpson DuraVent GS/Pro®, Selkirk Direct-Temp
and ICC EXCELDirect venting components. Although you may use the pipe components (straight pipe, el-
bows, etc.) from any of the listed manufacturers, you may only use the vent terminations (caps) listed in the chart on page 9. For installations where a snorkel is needed, please note that only three snorkels are ap­proved for use. Please plan your installation accordingly.
For all specific venting installation requirements, follow the installation instructions included by the venting manufacturer with the venting system components you have chosen.
Please note:
 For venting configurations that include no vertical rise, a total horizontal vent run of up to 30 inches
(and including one 45° elbow) is allowed. However, if your installation has room to add a vertical pipe section, we suggest adding at least one foot of vertical rise to the system.
 For venting configurations that include vertical rise, it is assumed that the installation will include at
least one 90° elbow. Up to three additional 90° elbows (or equivalent 45° elbows) may also be used. The total venting may not exceed 20 feet of vertical rise and/or 10 feet horizontal run. Refer to the venting charts starting on pages 10 & 11 for specific details while you plan your installation. Note: The number of elbows impacts the maximum allowable horizontal vent run.
 Many installations will involve venting directly through standard 2 X 4 or 2 X 6 construction exterior
wall to a horizontal vent termination (cap). The vent starter pipe has been designed to accommodate those two common installations without the use of any additional venting components other than a stan­dard horizontal cap. See the chart on page 9 for a list of approved vent caps.
 A special corner installation kit (Part Number CK-16-1) is also available that will allow the
fireplace to be mounted in a corner without constructing a 45° partition wall. This kit is available from your dealer and has its own installation instructions. Please refer to those instructions for spe­cific details regarding the installation using the kit.
 If the fireplace will be installed on an interior wall or other location that precludes venting directly
through an outside wall to a horizontal vent cap, or if the distance to the outside wall exceeds 30”, one or more elbows will be required to allow addition of the required vertical venting to the installation. When vertical venting is required, the fireplace venting may be terminated with either a vertical or hori­zontal vent cap depending on the specifics of the installation. Refer to the venting charts starting on pages 10 & 11 for specific venting requirements and see the chart on page 9 for a list of approved vent caps before you plan your installation.
 A minimum clear space of 1 1/2” must be maintained around the vent pipe where it penetrates the first
combustible wall adjacent to the fireplace (either the outside wall for the direct-through-the-wall instal­lation or the partition wall for the 45° or other interior wall installations). The special vent pipe heat shields that are provided with the must also be installed in the first wall adjacent to the fire­place. A minimum clear space of 1 1/2” must also be maintained where the vent pipe penetrates any other interior wall, exterior wall, ceiling or roof.
 The may also be installed in front of an exiting fireplace opening utilizing special co-linear
venting components available from the venting manufacturers. These systems split and then recombine the co-axial air and exhaust and allow the use of flexible venting. This makes it easier to run the vent­ing through the narrow fireplace damper opening to the top of the chimney. Refer to the vent manufac­turers’ instructions. Use the vertical venting column (0 feet Horizontal Run) in the venting charts to determine the required restrictor settings depending on the height of chimney.
®
, Security Secure Vent™, AmeriVent Direct™, Metal Fab Direct Vent
8
USING THE VENTING CHARTS
 The location of the vent termination must meet the requirements of the current edition of ANSI Z223.1/
NFPA 54, National Fuel Gas Code or CAN B419.1, Natural Gas and Propane Installation Code and the requirements shown on page 15 of this manual.
Just as with any other vented device, vertical vent rise creates draft (negative pressure) in the firebox as the exhaust gases heat up. If this draft becomes excessive, it can affect the performance or appearance of the fire. The fireplace includes air and exhaust restrictors that are used to balance the draft in the fire­place to the optimal level for installations where excessive draft might occur. The venting charts on pages 10 and 11 provide an easy means for determining whether your specific installation requires inlet air or ex­haust restrictors or both. To make the determination about whether air or exhaust restrictors are needed, a venting chart worksheet is provided on page 12. Follow the instructions and fill in the worksheet for your particular installation. This will allow you to determine the recommended restrictor settings for your exact installation. Although this might appear to be a complicated process at first glance, it is really quite straight-forward and the result will be a fire that looks and performs as intended. Several examples of worksheet calculations are shown on page 13 to help guide you. Please be sure to note that:
1. There are separate venting charts for Natural Gas and LP Gas. Refer to the appropriate chart for your fuel type to determine your specific restrictor requirements. The settings in the charts have been deter­mined based on extensive testing.
2. Determine the total vertical vent rise and total horizontal vent run for your installation. All measure­ments are made from the center of the vent opening in the back of the fireplace.
3. If your fireplace will not be venting directly though an outside wall to a horizontal termination or if more than 30” of horizontal vent run is required, some vertical vent rise will be required for the fire­place to function and vent properly. Elbows will also be required for those installations. However, in­stallations are limited to a maximum of four 90° elbows (or 45° elbow equivalents).
4. Note: Two 45° elbows equal one 90° elbow.
5. The recommended restrictor settings in the venting charts allow up to two 90° elbows (or 45° elbow equivalents) to be used without affecting the restrictor settings. Additional elbows will require that you calculate a new equivalent horizontal run for your installation to account for the additional flow resis­tance caused by the extra elbows. For the purposes of calculating the equivalent horizontal vent run, each additional 90° elbow is equivalent to three feet of horizontal vent run. The total horizontal vent run including elbow equivalents can not exceed 10 feet.
6. The maximum vertical vent rise can not exceed 20 feet.
7. There are two exhaust restrictors that are provided with your fireplace. They are labeled “A” and “B”. The A restrictor provides less exhaust restriction than B.
8. An air restrictor plate is also provided with your fireplace. It is a ring with bendable tabs that can be set to adjust the amount of restriction in the air supply system. Once the appropriate number tabs are bent open (in accordance with the requirements for your installation), the plate is inserted between the fireplace and the vent starter pipe.
9
NATURAL GAS VENTING CHART
KEY
20
EXHAUST RESTRICTOR
A or B
NU = NOT USED
19
18
17
16
15
AIR RESTRICTOR
1— 6 TABS OPEN
NU = NOT USED
9
8
7
6
5
4
3
2
14
13
12
11
10
1
NOT ALLOWED
0
HORIZONTAL RUN IN FEET
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
A NU A NU A NU A NU A NU A NU A NU A NU A 4 A 4 A 4
A NU A NU A NU A NU A NU A NU A NU A NU A 4 A 4 A 4
0 1 2 3 4 5 6 7 8 9 10
B 4 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B 4 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B 4 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B 4 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B 4 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B 4 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
VERTICAL TERMINTIONS
NOT ALLOWED
0 1 2 3 4 5 6 7 8 9 10
NU NU NU NU NU NU NU NU
9
8
7
6
5
4
3
2
20
19
18
17
16
15
14
13
12
11
10
1
0
VERTICAL RISE IN FEET
10
LP GAS VENTING CHART
KEY
20
19
EXHAUST RESTRICTOR
A or B
NU = NOT USED
18
17
16
15
14
AIR RESTRICTOR
1— 6 TABS OPEN
NU = NOT USED
9
8
7
6
5
4
3
2
13
12
11
10
1
NOT ALLOWED
0
HORIZONTAL RUN (FEET)
B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3
B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4
B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4
B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU
A NU A NU A NU A NU A NU A NU A NU A NU A NU A NU A NU
A NU A NU A NU A NU A NU A NU A NU A NU A NU A NU A NU
0 1 2 3 4 5 6 7 8 9 10
B 4 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5
B 3 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5
B 3 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5
B 3 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5 B 5
B 2 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4
B 2 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4
B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2
B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2
B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2 B 2
B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3
B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3
20
19
18
17
16
15
14
13
12
11
10
VERTICAL TERMINATIONS
NOT ALLOWED
9
8
7
6
5
4
0 1 2 3 4 5 6 7 8 9 10
NU NU NU NU NU NU NU NU
3
2
1
0
VERTICAL RISE (FEET)
11
VENTING CHART WORKSHEET
A. FUEL TYPE: NATURAL GAS
LP GAS (PROPANE)
B. TOTAL VERTICAL VENT RISE (MEASURED FROM HORIZONTAL CENTERLINE OF VENT OPENING ON THE BACK OF THE FIREPLACE TO THE HORIZONTAL CENTERLINE OF THE VENT CAP (FOR HORIZONTAL VENT CAPS) OR TO THE FLANGE ON THE CAP (FOR VERTI­CAL CAPS)): _____________ FEET
C. TOTAL HORIZONTAL VENT RUN (MEASURED FROM THE VERTICAL CENTERLINE OF THE VENT OPENING ON THE BACK OF THE FIREPLACE TO THE FLANGE ON THE CAP (FOR HORIZONTAL CAPS) OR TO THE VERTICAL CENTERLINE OF THE CAP (FOR VERTICAL CAPS)): _____________ FEET
NOTE: THE VERTICAL VENT RISE AND HORIZONTAL VENT RUN ARE THE OFFSETS IN THE LO­CATIONS OF VENT CAP RELATIVE TO THE VENT OPENING ON THE FIREPLACE. VENT PIPE THAT RUNS AT 45° HAS BOTH A VERTICAL RISE AND HORIZONTAL RUN. SNORKEL CAPS HAVE BUILT-IN VERTICAL RISE THAT MUST BE COUNTED.
D. TOTAL NUMBER OF 90° ELBOWS: _______ NOTE: SNORKELS COUNT AS 2- 90° ELBOWS E. TOTAL NUMBER OF 45° ELBOWS: _______ TERMINATION (CAP) TYPE: HORIZONTAL VERTICAL
SNORKEL VENT BRAND: Simpson DuraVent GS/Pro® Selkirk Direct-Temp
®
Security Secure Vent™
AmeriVent Direct™ Metal Fab Direct Vent
ICC EXCELDirect
VENT CAP MODEL NO: _______________ NOTE: SEE APPROVED VENT CAPS ON PAGE 8
EXHAUST AND AIR INLET RESTRICTORS CALCULATOR
A. Fuel Type ________ B. Total Vertical Vent Rise: ________ feet C. Total Horizontal Vent Run (Actual): ________ feet D. 90° Elbows Needed: ________ E. 45° Elbows Needed: ________ F. Total 90° Elbows Equivalent: D +(E x ½) = ________ G. 90° Elbows in Excess of 2: F - 2 = ________ H. Additional Horiz. Feet Equivalent: G x 3 = ________ feet I. Horizontal Vent Run (Equivalent): C + H = ________ feet
Find _____ Chart Settings for:
B._________ feet Vertical Rise and I.__________ feet Horizontal Run (Equivalent).
Exhaust Restrictor Required: N Y IF YES: A or B
Air Restrictor Required: N Y IF YES: Number of Tabs Open: _______
12
VENTING CHART WORKSHEET EXAMPLES
A. Fuel: Natural Gas B. Total Vertical Vent Rise: 0 feet C. Total Horiz. Vent Run (Actual): 0 feet D. 90° Elbows Needed: 0 E. 45° Elbows Needed: 0 F. Total 90° Elbows Equivalent : 0 G. 90° Elbows in Excess of 2: 0 H. Additional Horiz. Feet Equivalent 0 I. Total Horizontal Vent Run (Equivalent): 0 Use Natural Gas Chart Settings for: 0 feet Vertical Rise, 0 feet Horizontal Run. Exhaust Restrictor Used: Restrictor Not Used Air Restrictor Tabs Open: Restrictor Not Used
A. Fuel: Natural Gas B. Total Vertical Vent Rise: 12 feet C. Total Horiz. Vent Run (Actual): 0 feet D. 90° Elbows Needed: 1 E. 45° Elbows Needed: 0 F. Total 90° Elbows Equivalent : 0 G. 90° Elbows in Excess of 2: 0 H. Additional Horiz. Feet Equivalent 0 I. Total Horizontal Vent Run (Equivalent): 0 Use Natural Gas Chart Settings for: 12 feet Vertical Rise, 0 feet Horizontal Run. Exhaust Restrictor Used: B Air Restrictor Tabs Open: Restrictor Not Used
A. Fuel: LP Gas B. Total Vertical Vent Rise: 1 feet C. Total Horizontal Vent Run (Actual): 3 feet D. 90° Elbows Needed: 2 E. 45° Elbows Needed: 0 F. F. Total 90° Elbows Equivalent:2+(0 x ½) = 2 G. 90° Elbows in Excess of 2: 2 - 2 = 0 H. Additional Horiz. Feet Equivalent: 0 x 3 = 0 I. Total Horiz. Vent Run (Equivalent): 3 + 0 = 3 Use LP Gas Chart Settings for: 1 feet Vertical Rise, 3 feet Horizontal Run. Exhaust Restrictor Used: Restrictor Not Used Air Restrictor Tabs Open: Restrictor Not Used
A. Fuel: LP Gas B. Total Vertical Vent Rise: 10 feet C. Total Horizontal Vent Run (Actual): 7 feet D. 90° Elbows Needed: 2 E. 45° Elbows Needed: 2 F. F. Total 90° Elbows Equivalent:2+(2 x ½) = 3 G. 90° Elbows in Excess of 2: 3 - 2 = 1 H. Additional Horiz. Feet Equivalent: 1 x 3 = 3 I. Total Horiz. Vent Run (Equivalent): 7 + 3 = 10 Use LP Gas Chart Settings for: 10 feet Vertical Rise, 10 feet Horizontal Run. Exhaust Restrictor Required: B Air Restrictor Tabs Open: 3
A. Fuel: Natural Gas B. Total Vertical Vent Rise: 6 feet C. Total Horizontal Vent Run (Actual): 6 feet D. 90° Elbows Needed: 3 E. 45° Elbows Needed: 0 F. Total 90° Elbows Equivalent: 3+(0 x ½) = 3 G. 90° Elbows in Excess of 2: 3 - 2 = 1 H. Additional Horiz. Feet Equivalent: 1 X 3 = 3 I. Total Horiz. Vent Run (Equivalent) 6 + 3 = 9 Use Natural Gas Chart Settings for: 6 feet Vertical Rise, 9 feet Horizontal Run. Exhaust Restrictor Required: B Air Restrictor Tabs Open: Restrictor Not Used
13
A. Fuel: LP Gas B. Total Vertical Vent Rise: 2 feet C. Total Horizontal Vent Run (Actual): 10 feet D. 90° Elbows Needed: 2 E. 45° Elbows Needed: 0 F. Total 90° Elbows Equivalent: 2+(0 x ½) = 2 G. 90° Elbows in Excess of 2: 2 - 2 = 0 H. Additional Horiz. Feet Equivalent: 0 x 3 = 0 I. Total Horiz.Vent Run (Equivalent): 10 + 0 = 10 Use LP Gas Chart Settings for: 2 feet Vertical Rise, 10 feet Horizontal Run. Exhaust Restrictor Used: A Air Restrictor Tabs Open: Restrictor Not Used
VENTING
The illustration below shows some of the many ways the fireplace may be installed in the home. This includes interior and exterior wall installations, corner installations and horizontal and vertical vent terminations.
HORIZONTAL TERMINATION
VERTICAL TERMINATION
14
VENT TERMINAL CLEARANCES
Venting terminals shall not be recessed into a wall or siding.
15
ASSEMBLY & INSTALLATION
UNPACKING AND INSTALLING THE
WALL MOUNT FIREPLACE
The fireplace components are shipped in three cartons. By now, you will have opened the top of the first carton, removed the glass protector and this manual. You will also have found the Left and Right decorative panels. Note that the right panel
has a touch pad control panel and cable attached. Use spe­cial care when unpacking and handling this panel to avoid damaging the cable or pad. The second carton contains the
vent starter pipe, vent heat shields and air and exhaust restric­tors. The third carton contains the fireplace surround.
1. Using the adjacent illustrations as a guide, first lift and re­move Tube 1 from the carton containing the firebox. Care­fully unpack the contents of the tube and set aside. This should include the bag of glass burner media, the remote control handset, a hardware bag and relief door with gasket.
2. Next lift and remove Tube 2 from the carton. Carefully re­move the contents of the tube. This includes the Top & Bottom decorative panels that will be attached to the fire­place during assembly.
3. Next, remove all remaining packaging materials from the carton.
4. Lift the firebox and the fireplace mounting plate as a unit up and out of the carton. The best place to lift is at sides. Remove the fireplace mounting template from the face of the fireplace. You should now have all of the parts as shown in the illustration below.
5. Next, unpack the vent starter pipe (with attached gasket), the inner and outer telescoping vent heat shields and the air and exhaust restrictors from the second carton and set aside for later use.
6. Finally, unpack the fireplace surround from the third carton and set aside on a soft surface for later use.
LEFT PANEL
TOP PANEL
MANUAL
WALL TEMPLATE
HARD­WARE PACK
REMOTE CONTROL
GLASS BURNER MEDIA
RIGHT PANEL
TUBE 1 TUBE 2
Left & Right Side
Panels
Use care not to damage the touch pad cable attached
to the underside of the Right Side Panel
WALL TEMPLATE
MANUAL
TUBE 1
LIFT AND REMOVE “TUBE 1” FROM CARTON. REMOVE THE FOLLOWING ITEMS FROM TUBE:
1. GLASS BURNER MEDIA 2. REMOTE CONTROL
3. HARDWARE BAG 4. RELIEF DOOR W/GASKET
TUBE 2
Relief Door
BOTTOM PANEL
LIFT AND REMOVE “TUBE 2” FROM CARTON. REMOVE THE DECORATIVE PANELS FROM TUBE:
1. TOP DECORATIVE PANEL 2. BOTTOM DECORATIVE PANEL.
16
ASSEMBLY & INSTALLATION
Before you begin the fireplace mounting process there are several important installation requirements that must be met. Careful planning will make the installation easier to accomplish and will reduce the chances of encountering problems after you start.
1. The fireplace is designed to be wall-mounted using four lag bolts to secure the fireplace mounting plate to the wall structure. The mounts are located 16” on center to correspond with standard building construction. If your home has non-standard construction or the location you have chosen for the fireplace does not have wall studs that correspond to location of the fireplace mounts, modifications to the wall structure will be needed. It is critical that the four lag bolts that are provided for mounting the fireplace are firmly imbed­ded into the wall structure at all four locations.
2. A hole must be provided in the wall for the vent to pass through. The hole must be large enough to provide 1 1/2” clearance around the outside of the vent pipe and to allow for installation of the vent heat shields that are provided with the fireplace. Follow the hole size requirements that are provided below exactly to avoid problems. If the location you have chosen does not allow for 1 1/2” clearance to wooden framing in the wall, modifications to the wall structure must made to obtain the needed vent pipe clearance.
3. All required minimum clearances to adjacent combustible materials (including side walls, ceiling and floor) must be achieved with the position you have chosen. See the clearance information on page 6. The listed clearances are measured from the outermost front edges of the fireplace surround and not from the fireplace body or mounting plate. In addition the requirements for clearance to combustible materials in­side the house, there are specific requirements and limitations that must be met for the location of the vent terminal relative to doors, windows, corners, eaves, gas supply components and other structural elements of the house. Please see page 15 for those specific requirements. Again, plan the installation in advance to avoid problems.
4. The gas supply line must be located within a specific area behind the fireplace.
17
ASSEMBLY & INSTALLATION
Once you are certain that the location you have chosen meets all the necessary mounting and safety require­ments, you can begin the installation.
1. Tape or pin the installation template to the wall in the posi­tion where the fireplace is to be mounted. Note: It is impor­tant that the fireplace is mounted in a level position. Use a spirit level placed on the cross-hairs in the upper mounting holes on the template and adjust the template position until the mounting holes are level. Refer to the adjacent illustra­tion.
2. Next, carefully transfer the location of the two upper and two lower mounting holes that you will use for your installa­tion. Use a sharp nail, awl or pin to pierce the template on the mounting hole cross-hairs to insure an accurate transfer to your wall.
3. Next transfer the location for the center of the vent pass­through hole on the wall. Also transfer at least one point on the diameter of the vent pass-through circle. This will make it easier to scribe the circle later.
MOUNTING
HOLES
GAS SUPPLY
CUTOUT
16” OC
LEVEL
Vent pass-
through
4. Finally, transfer the location of the gas supply line.
5. Remove the template and circle the transferred locations with a pencil or marker.
Vent Pass-Through (Parallel Wall Installation on an Outside Wall)
1. An unobstructed wall pass-through is required to allow for a safe installation of the fireplace vent com­ponents. This will necessitate removal of a portion of the interior wall covering (e.g., sheetrock or plas­ter and lath), outer wall sheathing and outer wall covering and any adjacent internal wall materials (like insulation).
2. Scribe a 9 5/8” diameter hole around the vent pass-through center mark using a compass.
3. Use a long drill (1/8” diameter) that is held square and level to the inside wall to transfer the vent pass­through center location from the inner wall covering through to the outer wall sheathing and outer wall covering.
4. Carefully cut the inner wall covering along the scribed line and remove the circular wall piece. Note: It is important to locate electrical wiring in the wall before beginning the installation process. An electri­cian should be consulted if there is any question about wiring locations. Failure to locate and protect wiring during the installation process my result in electrical shock or fire.
5. Remove any insulation materials from wall in the area defined by the pass-through hole.
6. Building codes in your area may require that you add blocking above and below the vent opening. The blocking should be above and below the 9 5/8” vent opening you made in the wall and should not ob­struct that opening. The blocking should extend to adjacent wall studs.
7. Next, mark and cut a 9 5/8” diameter hole through the outer wall covering and sheathing using the lo­cating hole you drilled in Step 2.
8. Follow the instructions included with the vent termination (cap) to remove the appropriate amount of outer wall covering (siding) or to install the vinyl siding shield if used. Do not install the chimney cap at this point.
18
ASSEMBLY & INSTALLATION
Vent Pass-Through (Parallel Wall Installation on an Interior Partition Wall)
1. An unobstructed wall pass-through is required to allow for a safe installation of the fireplace vent com­ponents. This will necessitate removal of a portion of the interior wall covering (e.g., sheetrock or plaster and lath), on both sides of the partition wall and any adjacent internal wall materials (like insu­lation).
2. Scribe a 9 5/8” diameter hole around the vent pass-through center mark using a compass.
3. Use a long drill (1/8” diameter) that is held square and level to the inside wall to transfer the vent pass­through center location from the inner wall covering through to the wall covering on the back side of the partition wall.
4. Carefully cut the inner wall covering along the scribed line and remove the circular wall piece. Note: It is important to locate electrical wiring in the wall before beginning the installation process. An elec­trician should be consulted if there is any question about wiring locations. Failure to locate and protect
wiring during the installation process my result in electrical shock or fire.
5. Remove any insulation materials from wall in the area defined by the pass-through hole.
6. Building codes in your area may require that you add blocking above and below the vent opening. The blocking should be above and below the 9 5/8” vent opening you made in the wall and should not ob­struct that opening. The blocking should extend to adjacent wall studs.
7. Next, mark and cut a 9 5/8” diameter hole through the wall covering on the back side of the partition wall using the locating hole you drilled in Step 2.
8. When installing the fireplace on a partition wall, the venting may be penetrating one or more interior walls, an exterior wall, the ceiling or the roof.
9. It is important to lay out the locations of all vent pass-through’s before you begin the installation to in­sure that the venting will line-up correctly and that the walls and ceiling meet the needed clearances to the vent pipe.
10. The vent pass-through in the partition wall where the fireplace is mounted must be done in accordance with the instructions for a parallel wall installation on an outside wall, following steps 1 through 6.
Vent Pipe Heat Shields Special telescoping double heat shields for the vent pipe are provided with the
fireplace. These heat shields are a critical part of a safe installation. They are designed to protect combustible materials in the wall immediately behind the fireplace. The only ex­ception to this is if the corner installation kit (Part Number CK-16-1) is used. With the corner kit, the heat shields are installed where the venting passes through the first adjacent side wall. See the instructions included with the corner kit for specific details.
19
ASSEMBLY & INSTALLATION
Gas Supply Line
1. Once the vent pass-through (or pass-through’s) are finished, the gas supply line should be installed. The supply line should exit the wall that the fireplace will be installed on at the location specified on the in­stallation template We suggest the installation of a shut-off valve in the supply line between the wall and the connection to the fireplace. Your professional gas installer or local gas company will determine the specific requirements for the gas supply line as the requirements may vary in different locations. In every case, the installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 or the Canadian Installation Code, CAN/CGA B149.
Installing the Fireplace Mounting Plate on the Wall
1. The fireplace mounting plate is attached to the wall structure using
four 1/4” X 1 1/2” long lag bolts and large diameter washers that are provided with the fireplace. It is important to use the included hardware as the full weight of the fireplace is supported by the mounting plate.
2. Drill a 5/32” diameter pilot hole at each of the mounting hole loca-
tions that you marked using the template. The pilot holes should be the full depth of the lag bolts. Be sure that there is solid wood at each mounting location. If not, the wall should be reconstructed to provide the needed support.
3. Before the mounting plate can be lagged to the wall the two tabbed
sections of the telescoping vent pipe heat shields that you set aside earlier must be attached to the mounting plate. Each heat shield half is held in place with three sheet metal screws (provided). The inner shield half (smaller diameter) is installed from the front of the mounting plate. Slide the inner heat shield half through the vent pipe opening in the mounting plate. Align the three tabs with the pilot holes in the mounting plate (as shown in the adjacent il­lustration) and install the three screws.
4. The outer vent pipe heat shield half (larger diameter) is installed on
the rear of the mounting plate. Slip the outer shield half over the inner shield and align and install the three screws. See the adjacent illustration.
5. The fireplace mounting plate is now ready to be lagged to the wall
structure.
6. With a helper pick up and align the mounting plate over the gas
supply line and line up with the four mounting lag bolt pilot holes. These holes are in recessed bosses.
7. Using the lag bolts and washers provided with the fireplace, install
the top lag bolts (with washers) first, followed by the lower ones. Use a 7/16” socket wrench to tighten the lag bolts.
Note: It may be helpful to put a light coating of dish or hand soap on the lag bolts to reduce resistance when tightening.
INNER VENT PIPE SHIELD
(Smaller Diameter)
OUTER VENT PIPE SHIELD
(Larger Diameter)
20
ASSEMBLY & INSTALLATION
Note: It may be helpful to put a light coating of dish or hand soap on the lag bolts to reduce resistance when tightening.
8. At this point, check to be sure that there is a 5/16” air gap be-
tween the entire flat back surface of the mounting plate and the wall surface. The gap is critical to a safe installation and if the gap is obstructed in any way, remove the obstruction be­fore proceeding.
9. Next check that the brackets on the mounting plate that actu-
ally hold the fireplace are level, again using a spirit level. If the brackets are not perfectly level, you can adjust the right bracket by loosening the bracket fasteners and moving the bracket until it is level with the left bracket. Remember to tighten the bracket fasteners once you have achieved a level position.
10. The next step is to install the vent starter pipe onto the fire-
place.
11. Remove the glass panel and glass frame assembly from the
front of the firebox by loosening and removing the four glass frame fasteners that are located along the top edge of the glass frame.
12. While holding the glass panel and glass frame along the outer
edges, tip the top of the glass frame forward a few inches.
13. Wrap your fingers around the frame and hold the glass and
frame together while you lift the frame up and out of the lower glass retainer. Set the glass and frame assembly aside in a safe place.
14. Carefully place the fireplace with the front down on a pro-
tected floor.
15. At this point, it is necessary to determine whether your instal-
lation will require the addition of flow restrictors to the com­bustion air inlet system or the exhaust outlet or both. Refer to
the venting section that starts on page 8 to make that determi­nation.
16. If your installation does not require any restrictors, place the
vent starter pipe gasket on the back of the fireplace aligning the holes in the gasket with the pilot holes on the rear of the fireplace.
17. Align the inner pipe of the vent starter pipe with the exhaust
outlet pipe on the fireplace. The vent pipe will fit tightly over the fireplace pipe. Gently push the starter pipe on to the fire­place pipe until the outer pipe flange makes contact with the starter pipe gasket. Be sure that the holes in the starter pipe flange align with the gasket and pilot holes. When the flange contacts the gasket, install the four fasteners provided with the starter pipe.
LAG BOLTS
& WASHERS
LEVEL
LEVEL THE BRACKETS
INSTALLING THE VENT STARTER PIPE & GASKET
21
ASSEMBLY & INSTALLATION
18. If your installation does require an air restrictor or exhaust restrictor or both, these must be installed before you install the vent starter pipe. Again, refer to the venting information starting on page 8 to determine the specific restrictor requirements for your specific installation.
19. The exhaust restrictor is installed by placing it through the exhaust outlet pipe and resting it on the in­ternal baffle in the firebox. It is held in place with a movable retainer clip. Simply hold the restrictor down against the baffle and push the retainer up and tighten screw to secure the restrictor. Note: Please take care to insure that the exhaust restrictor is centered in the exhaust outlet. Improper alignment could adversely affect the appearance of the flames. Refer to the adjacent illustrations for placement of the exhaust restrictor and clip.
20. If the air restrictor ring is required, first determine the number of tabs that must be bent open. Before bending any tabs, align the mounting holes in the ring over the four pilot holes on the back of the fireplace. When selecting the tabs to bend, it is important to maintain the most symmetrical pattern pos­sible. The first tabs bent must be opposite each other and ori­ented horizontally. If only one tab is specified, orient the ring over the pilot holes so the split tabs are oriented horizontally and bend up two opposing half-tabs. Additional tabs should be evenly spaced relative to the first two. With the appropri­ate tabs bent, re-align the mounting holes in over the pilot holes keeping the proper orientation AND with the bent tabs facing away from the fireplace body.
21. Place the vent starter pipe gasket on the back of the fireplace aligning the holes in the gasket with the pilot holes on the rear of the fireplace.
22. Align the inner pipe of the vent starter pipe with the exhaust outlet pipe on the fireplace. The vent pipe will fit tightly over the fireplace pipe. Gently push the starter pipe on to the fire­place pipe until the outer pipe flange makes contact with the vent pipe gasket. Be sure that the holes in the starter pipe flange align with the gasket and pilot holes. When the flange contacts the gasket, install the four fasteners provided with the starter pipe.
INSERTING THE EXHAUST RESTRICTOR
INSTALLING THE RETAINER CLIP AND SCREW
TABS FACING AWAY FROM FIREBOX
GASKET
STARTER PIPE
AIR RESTRICTOR RING
EXHAUST RESTRICTOR PROP­ERLY INSTALLATED
22
ASSEMBLY & INSTALLATION
12. You are now ready to install the fireplace on the mounting plate. This will require a helper as the fireplace is quite heavy. Lift the fireplace up and guide the vent pipe into the vent pipe opening in the mounting plate. The vent pipe must be at the highest location possible in the vent pipe opening (almost touching the inner vent pipe heat shield) to allow the mounting tabs on the rear of the fireplace to clear the top of the mounting brackets on the mounting plate. Refer to the adjacent illustration.
13. While looking in from the sides, guide the upper and lower mounting tabs on the back of the fire­place into the corresponding brackets on the mounting plate. When the tabs and brackets are aligned, push the fireplace down and in to engage the tabs in the brackets. Note: The weight of the fireplace is carried only on the top brackets. The bottom brackets function simply to keep the bot­tom of the fireplace from moving. Refer to the adjacent illustration.
14. If the fireplace is properly positioned on the brack­ets the vent starter pipe and vent heat shields should be concentric when viewed through the vent pass-through in the wall. Go outside and look in the hole to confirm this. If you are mounting the fireplace on a 45° partition wall, look in the pass-through using a mirror if needed. If the vent starter pipe and vent pipe heat shields do not ap­pear to be concentric, check to be sure that the mounting tabs on the fireplace are all fully en­gaged in the brackets on the mounting plate and that the upper two tabs are sitting down on the up­per brackets. If they are not, adjust the fireplace until they are.
4 TABS ON REAR OF FIREPLACE
4 BRACKETS ON MOUNTING PLATE
VENT PIPE AND SHIELDS SHOULD BE CONCENTRIC IF THE FIREPLACE IS PROPERLY INSTALLED
23
ASSEMBLY & INSTALLATION
Installing the Outer Vent Heat Shields and Vent Termination (Parallel Installation on Outside Wall)
1. Before you install the horizontal vent termination, you must first install the second halves of the two telescoping vent pipe heat shields. Each shield half simply slips over the half you previously at­tached to the fireplace mounting plate and can now be seen inside the vent pass-through in the wall.
2. Install the outer shield first and the inner second. Leave about 1-1/4” of the shields protruding past the house sheathing.
3. Install the horizontal vent termination (vent cap) by first removing the two mounting straps as they will not be used. Be sure the arrow on the cap (if present) is pointing up and reconfirm that all the vent cap location requirements per page 15 and the vent manufacturers requirements are met.
4. Slip the inner and outer vent termination pipes onto the vent starter pipe taking care to align the inner and outer pipes to prevent damage.
5. Slide the vent termination (cap) into the siding re­cess (or vinyl siding shield) until it bottoms out. Note: The rear surface of the vent termination will push the telescoping vent pipe heat shields inward. When the vent termination is in place the heat shields will just touch the rear surface of the termi­nation.
6. Pull the vent cap away from the sheathing and in­stall a small bead of non-hardening silicone sealer around the cap perimeter. Push the cap in place.
7. Install the mounting screws (included with the cap) to hold the vent cap to the sheathing See the venting manufacturers instructions for the location of the mounting holes. Typical mounting hole lo­cations are shown in the adjacent illustration. See the venting manufacturers instructions for more information or if using the vinyl siding shield.
INNER TELESCOPING SHIELD
HORIZONTAL VENT TERMINATION
TYPICAL VENT TERMINAL MOUNTING HOLES
OUTER TELE­SCOPING SHIELD
24
ASSEMBLY & INSTALLATION
Installing the Outer Vent Heat Shields (Partition Wall Installation)
BACK OF PARTITION WALL
1. Before you install the additional vent pipe and el­bow(s) that will complete the venting installation, you must first install the second sections of the
OUTER TELE­SCOPING SHIELD
vent pipe heat shields to protect the combustible materials around the vent pipe pass-through in the partition wall that the fireplace is mounted on. Each shield half simply slips over the half you pre­viously attached to the fireplace mounting plate and that can now be seen inside the vent pass­through in the partition wall.
2. Install the outer shield first and the inner second.
INNER TELESCOPING SHIELD
Leave at least 2” of both shields protruding past the partition wall framing or wall covering. See the illustration on page 24.
Vent Pipe and Vent Termination Installation (Partition Wall Installation)
1. The specific details of the vent configuration from the vent starter pipe on the fireplace to the horizontal or vertical vent termination (cap) when the fireplace is installed on an interior wall of the house will vary depending on the location of the fireplace on the wall, what is on the back side of the wall, where the vent termination will be located (roof or exterior wall) and on other code requirements for the loca­tion of the vent termination as shown page 15. However, the maximum vent length, measured along the centerline of the pipe, from the back of the fireplace to the start of the vent termination cannot exceed 30 feet, including a maximum of 20 feet of vertical rise and a maximum of 10 feet of horizontal run. If more than two 90° elbows (or equivalent 45° elbows) are needed for your installation, the maximum amount of horizontal run allowed is reduced. See the venting section starting on page 8 for specific in­formation. It is important to plan the installation in advance so that you can accurately locate the any wall or ceiling pass-through’s and the vent termination on the exterior wall or roof. The vent pipe sec­tions are available only in certain increments of length and in adjustable length sections. Plan carefully before you start!
2. You will find it helpful to leave access to the area behind the partition wall to facilitate installation of the vent components. The pipe sections may have twist lock connections which will be difficult to exe­cute without good access.
3. Be sure that the two vent pipe heat shields extend at least 2” beyond the rear side of the partition wall adjacent to the fireplace after the venting is installed.
4. Maintain a minimum 1 1/2” unobstructed air space around the vent pipe where it passes through other interior walls, the ceiling, the exterior wall or the roof.
5. Note: Vent manufacturer’s instructions and some building codes may require the addition of blocking above and below all wall pass-through’s, the addition of vent manufacturer supplied firestop’s, wall thimbles, attic insulation shields, interior trim collars, vent support brackets, or other components. Please check with the authority having jurisdiction in your area when planning the venting installation to determine the specific code requirements and exact venting components that are required for your installation.
25
ASSEMBLY & INSTALLATION
Gas Connection.
1. Verify that the gas type is correct for the fireplace by looking at the rating plate that is attached to the right side of the fireplace, adjacent to the control battery pack. Note: The fireplace is shipped from the factory equipped to burn the fuel listed on the rating plate. Fuel conversion in the field is not al­lowed.
2. The gas connection should now be made from the gas supply line to the inlet regulator on the fire­place. Use only a qualified gas installer to make the connection.
3. The fireplace is shipped from the factory with a plugged 3/8” NPT connection.
4. The gas supply piping should have a separate gas shut-off valve and a 1/8” NPT plugged tapping upstream of the valve. We recommend installing a shut-off valve between the gas supply line where it penetrates the wall / fireplace mounting plate and the inlet to the regulator on the fireplace. This will allow gas to be shut-off to the fireplace by simply removing the fireplace surround to gain access to the shut-off valve.
5. The fireplace and its inlet regulator and main burner valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5kPa).
6. The fireplace must be isolated from the gas supply piping system by closing the gas shut-off valve dur­ing any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi (3.5kPa).
After the gas supply has been connected, use a commercial gas leak detector or apply a soapy water so-
lution to all the fittings to check for gas leaks. Never use a flame to test for leaks.
CONNECT THE GAS SUP­PLY LINE TO REGULA­TOR INLET
RECOMMENDED LOCA­TION FOR A SHUT-OFF
}
VALVE
26
ASSEMBLY & INSTALLATION
Installing or Replacing the Batteries
1. The valve control module is powered by three “C” batteries. The battery pack is located on the right side of the fireplace and is held to a mounting bracket with a hook and eye strap. Refer to the adjacent illustration.
2. The battery pack is connected to the Electronic Module by a plug in type connector. It is located on the top of the Electronic Module. Unplug this connector.
3. Loosen the hook and eye strap and pull the battery pack off the mounting bracket.
4. Install the 3 “C” batteries, supplied, using the guides inside the battery pack to show you the cor­rect battery orientation.
5. Replace the battery pack on the bracket and secure with the hook and eye strap.
6. Reconnect the battery connector to the Electronic Module.
7. The remote handset is powered by two “AA” bat­tery. The access panel is located on the back of the handset and simply snaps open to provide access to the battery compartment. Install two batteries as shown on the label inside the remote control bat­tery compartment
8. Replace the remote handset access panel.
BATTERY PACK
Placing the Burner Glass Media The burner glass media poly-bag that you set aside when you unpacked the fireplace contains the correct amount of glass material to cover the burner. The en­tire contents of the bag should be evenly distributed over the burner tray.
1. Locate the burner in the fireplace. Refer to the ad­jacent illustration.
2. Carefully clip one corner of the poly-bag to form a pouring spout. The opening should be large enough to allow the glass media to flow but not so large that you can’t control the flow.
3. You will notice that the burner surface is designed with turned-up edges that form a tray to hold the glass media.
27
BURNER TRAY
ASSEMBLY & INSTALLATION
3. Starting at one end, pour the glass media onto the burner tray, keeping the pouring spout on the poly­bag toward the center of the burner to avoid spillage of glass pieces over the sides of the burner. See the adjacent illustrations.
4. Once you have poured all of the glass burner media into the burner tray, carefully smooth the glass pieces out so they have a uniform depth over the entire sur­face of the burner. When the burner glass media is properly placed, it should look like the adjacent illus­trations.
5. Note: If a few pieces of glass escape over the edges of the burner tray during installation, it is not a prob­lem. They will simply land in the area below the burner and will do no harm.
Relief Door Installation
1. The top relief door is shipped separated from the fireplace and must be installed on the top of the fire­box at this point in the installation. Note: The relief door includes a gasket that covers the full bottom surface. Use care in handling the relief door to avoid damage to the gasket material.
2. The first illustration below shows the relief openings and relief door retainers.
3. The relief door includes line-up tabs that correspond to slotted retainers on the firebox.
4. Tip the relief door enough to allow the rear line-up tab to engage the rear retainer slot. Refer to the sec­ond illustration below.
5. Rotate the front edge of each relief door so they line-up over front retainers.
6. Gently spring the front forward so it will allow the relief door front line-up tab to engage on the re­tainer. Refer to the first illustration on the top of page 29.
7. The relief door should be able to move up and down freely on the retainers if properly installed.
8. When the relief door installation is complete, the door should be in the full down position. Refer to the second illustration on the top of page 29.
BURNER GLASS MEDIA PARTIALLY INSTALLED
BURNER GLASS MEDIA FULLY INSTALLED
RETAINERS
RELIEF OPENINGS
RELIEF DOOR REAR TAB ENGAGED IN REAR RETAINERS
RELIEF DOOR FRONT TABS
28
RELIEF DOOR FRONT TAB ENGAGED ON RETAINERS
ASSEMBLY & INSTALLATION
RELIEF DOOR SHOWN IN PROPER OPERATING POSITION
Installing the Front Glass Panel and Frame After burner media and relief doors been installed, the next step is to replace the front glass panel and frame.
1. Carefully pick up the glass and glass frame assembly by grasping the sides of the frame and using your thumbs and fingers to hold the glass in place within the gasket and frame.
2. With the glass frame (and glass) held at a slight angle (leaving room for your fingers between the frame and the firebox) insert the bottom edge of the frame into the frame retainer located on the bottom front of the firebox. Take care to center the frame from left to right.
3. Once the bottom edge is in place, move your fingers out of the way and press the top of the frame against the firebox while pushing down to be sure the frame is fully engaged in the frame retainer.
4. Hold the frame in place with one hand and insert the four glass frame fasteners along the top edge of the glass frame. Tighten the fasteners until they are hand-tight.
5. Tighten each fastener 1/2 turn at a time, working from one side to the other, until the glass frame has made contact with the firebox face along the entire top edge. Do not over-tighten the fasteners as this can put excessive stress on the glass.
29
ASSEMBLY & INSTALLATION
Installing the Outer Panels
1. The four outer decorative panels are secured to the fireplace with philips head screws. The top and bottom panels are secured to the fireplace mounting plate with sheet metal screws. All other screws are philips head machine screws.
2. Install the top panel first. Align the three holes along the rear edge of the panel with pilot holes along the top edge of the fireplace mounting plate.
3. Insert and tighten the three sheet metal screws. A magnetic nut driver is helpful.
4. Install the left side panel next. Align the three holes along the rear edge of the panel with the PEM nuts along the edge of the fireplace mounting plate. Insert the three philips head screws but do not fully tighten.
5. Locate the fastener hole at the top front edge of the left side panel and align with the PEM nut in the front of the top panel. Insert the philips head screw.
6. Make sure the edges of the panel are aligned with the edges of the top panel and mounting plate and tighten all four philips head screws.
7. The right side panel has the manual control touch pad mounted along the rear edge. Before the panel can be installed, the touch pad must be connected to the touch pad cable (5 Pin connector). You will find this next to the electronic control module. Hold the side panel up near the fireplace and connect the cable end to the touch pad connector. Note that arrow on the on the cable end con­nector must align with the #5 on the touch pad connector in order to function correctly.
8. Route the cable through the cutout in the fireplace mounting plate flange and position the right side panel so it aligns with the three PEM nuts on the mounting plate and the front PEM nut on the top panel. Align the rear and top panel edges with the adjoining parts
LOWER SURROUND BRACKETS
and insert and tighten the four philips head screws.
9. Install the bottom panel next. Guide the rear flange on the panel upward until the mounting holes in the flange line up with the pilot holes in the mounting plate.
11. Attach the panel to the mounting plate using sheet metal screws along the back edge of the panel. Note: It may make installation of the sheet metal screws easier if you remove the two lower surround mount­ing brackets from the front of the fireplace. A magnetic nut-driver will also be helpful.
12. Attach the bottom panel to the side panels by aligning the fastener holes in the bottom panel with the PEM nuts in the front corners of the bottom flanges on the side panels. Insert and tighten the two phil­ips head screws.
13. Reinstall the lower surround brackets if you removed them by inserting and tightening the two sheet metal screws in each bracket.
30
ASSEMBLY
Installing the Fireplace Surround The decorative surround for the fireplace is held in place by four brack­ets. Two are located on the top of the fireplace and two on the bottom. There are mating brackets and catch plates on the surround itself. Refer to the adjacent illustrations when installing the surround.
1. Unpack the surround from shipping box.
2. With a helper, lift the surround up and identify the top by looking for the vertical brackets that are visible from the rear of the sur­round.
3. Move the surround into place, generally centering the surround opening over the glass panel. Keep the bottom of the surround tipped slightly away from the fireplace.
4. While looking behind the surround, guide the two surround brackets onto the mating brackets on the fireplace top. You might find it eas­ier to engage one bracket and then the other. Lower the surround until both bracket sets are fully mated.
5. Carefully swing the bottom of the surround toward the base of the fireplace until the catch plates on the bottom flange of the surround are aligned with the adjustable locating screws on the bottom flanges of the lower surround mounting brackets. NOTE: Adjustment of the locating screws may be required to pro­vide a snug fit. Use a philips screwdriver to shorten or lengthen the locating screws as necessary.
6. To remove the surround, pull the bottom edge of the surround out­ward to disengage the locating screws and then lift the top up and off the upper brackets.
7. To prevent damage to the surround, always set the surround in a safe place while it is removed from the fireplace.
UPPER SURROUND BRACKETS
CATCH PLATE
ADJUSTABLE LOCATING
SCREW.
UPPER SURROUND BRACKETS WHEN PROPERLY MATED
31
LIGHTING AND OPERATION
LIGHTING THE FIRE
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device that automatically lights the pilot. Do not try to
light the pilot by hand.
B. BEFORE OPERATING THE BURNER SYSTEM, smell around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
 Do not try to light the appliance.  Do not touch any electric switch; do not use any telephone in your building.  Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s instruc-
tions.
 If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to operate the gas controls. Never use tools. If a knob will not push in or turn by
hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service techni-
1. STOP! Read the safety information in A, B, C, & D above.
2. This appliance is equipped with an ignition device that automatically lights the pilot. Do not try to light the pilot by hand.
3. If using the Remote Handset, push the button until you hear an audible signal to insure the appliance is off.
4. Wait five (5) minutes to clear out any gas. Then smell for gas including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, proceed to step 5 or 6.
5. If you are using the Remote Handset, press “ON” button followed by “OK” button on the Remote Handset. An audible signal confirms the start sequence has begun.
6. If you are using the Manual Control Panel, push the ON/OFF (top) button on the Manual Control Panel (See Fig. 2) An audible signal confirms the start sequence has begun; release button.
7. Once the pilot is lighting, check for proper pilot flame appearance, see Fig. 3. To light the main burner press the button on either the Manual Control Panel, or Remote Handset.
NOTE: If the pilot does not stay lit after several tries, proceed to step 10.
8. Use the flame height adjustment buttons on either the Remote Handset or the Manual Control Panel to adjust the flame. Press the button to decrease the flame height, press the button to in­crease flame height. The Remote Handset can also be used to control the appliance thermostatically.
9. Press the button 3 times on either the Manual Control Panel or Remote Handset to set the appli­ance to pilot flame only.
10. If the appliance will not operate, follow the instructions “TO TURN OFF GAS TO THE APPLI­ANCE” and call your gas service technician or gas supplier.
32
LIGHTING AND OPERATION
10. To turn the appliance off completely, push and release the “OFF” button on either the Remote Handset or Manual Control Panel . You will hear an audible signal confirming the off setting.
11. TURN OFF GAS TO THE APPLIANCE by closing the shut-off valve on the gas supply line to the ap­pliance and call your service technician or gas supplier.
O.K./UP ON/DOWN
OFF
FIG. 1
FIG. 2
FIG. 3
PILOT AND MAIN BURNER OPERATION
Follow the lighting instructions on pages 32 and 33. When the pilot is lit and operating properly, it should look like the adjacent illustration. One flame will be directed at the pilot thermocouple and a second flame is directed toward the burner. If the pilot flames do not resem­ble those in the adjacent illustration, contact your gas service techni­cian or Solas Nua dealer. After the main burner has been in operation for a few minutes, the
CORRECT PILOT FLAMES
flames should look like those in the illustration below. Note: The flame height will vary depending on the firing rate setting but flames should be evenly distributed across the full width of the burner.
33
COPRECI R-emotion CONTROL SYSTEM
The R-emotion system contains:
 A motorized valve  A pilot assembly  A control unit  A battery box or power supply  A remote control  A touch control cable  An ignition cable
The system controls a gas fire with the follow­ing functions:
 Automatic switch on  Automatic switch off  4 different flame levels (pilot, high, medium,
low)
The flame level can be controlled in 3 different ways:
 Manually (via touch control or remote control)  Thermostatically (via remote control)  By timed program (via remote control)
The R-emotion system can be used with two different controls: touch control and remote control. Both meth­ods can be used at the same time to control the system.
1. Working with the touch control.
This touch control has only 3 buttons for manually controlling the appliance.
The touch control has:
1. LED display
2. ON / OFF button
3. UP button
4. DOWN button
With this control it is possible to turn on the fire, turn off the fire and control the flame level.
1.1 Switching on.
To turn the system on, just press the ON / OFF button. The system will emit a beep and begin the ignition
process, which can take about 20 seconds. Once the start up process is complete, the pilot flame is lit.
To turn on the main burner, press the UP button. A beep and a flash of the LED indicate that the system
has accepted the order, and the flame will light on the “High” setting.
To decrease the flame level, press the DOWN button. A beep and a flash of the LED indicate that the sys-
tem has accepted the order, and the flame will decrease to “Medium” setting.
Pressing the DOWN button again and the flame will decrease to “Low” setting.
Pressing the Down button a third time and the fireplace goes to “Standby”. Main burner off - Pilot
on.
34
COPRECI R-emotion CONTROL SYSTEM
1.2 Switching off.
To switch off the fire, the ON / OFF button should be pressed. After the system has emitted a beep, the fire
switches off.
2. Remote control.
2.1 Description.
The remote control contains:
LCD display
Four buttons:
OFF button
Left button Middle button Right button
Battery case (on the back)
2.1.1 LCD display
The LCD screen shows information about the instructions given by the user (desired status) and the current situation of the device (actual status).
It also helps us select our choices:
A: Day of the week B: Time C: Signal strength D: Selected working mode E: Selected setting F: Current flame status G: Current fan status (Not Applicable on this appliance) H: Current room temperature I: Child lock status J: Button labels (explained below)
NOTE: The bottom row of the screen is indi­cating buttons functionality. In this case:
1 ( ) button decreases the flame level 2 ( ) button increases the flame level 3 (Back) button goes back to the previous
screen
The screen changes depending on the input from the buttons, but the bottom row always displays the button function labels. The function of each button depends on the options available on the current screen (except for the OFF button, which always has the same function).
35
COPRECI R-emotion CONTROL SYSTEM
2.1.2 OFF button
This button switches off the appliance. If it is pressed for more than 40 seconds, the configuration menu is ac­cessed.
2.1.2 Left, middle and right buttons
These buttons change their function as shown by the on-screen labels. For some screens a button may have no function and is inactive. The active buttons for a particular screen are initially lit for 5 seconds to indicate that they are active.
2.2 Menu system.
The remote is organized by means of a menu system.
When first powered, the remote starts at the OFF screen (it is possible that the remote is locked in the OFF screen; to unlock it, just press the button below Unlock, and then OK).
2.3 Switching on.
Once the remote is unlocked, press ON (left button) and OK (middle button). A beep from the control unit will be heard, and the ignition process starts. Note that while in operation the RF signal strength indicator dis­appears.
Wait until the current flame status displays Pilot.
2.4 Adjust menu.
Before using the remote, there are various settings which should be made, such as the date, the language, the autolock option and the comfort temperature.
To adjust these settings, go to Menu Adjust Menu. There, the options shown below can be set. To change any of these settings just press Select and Change.
36
COPRECI R-emotion CONTROL SYSTEM
37
COPRECI R-emotion CONTROL SYSTEM
2.5 Setting the control mode.
There are three different modes for controlling the appliance:
Manual Automatic (Thermostatic) Program
Manual Mode
If Manual is pressed, Pilot appears as the selected setting. In the bottom row, and appear, indi­cating that the flame level can be changed by just pressing the left or middle button. Pressing “Back” (right button), returns to the initial screen.
Note that a safety temperature can be previously set in the configuration menu. This specified the maximum permitted room temperature. This temperature can never be set higher than 104º F (40º C). It is recommended you set to 95º F (35ºC).
While in manual mode the flame level may be set to HIGH, MEDIUM, or LOW. Automatic (Thermostatic) mode allows you to set a desired temperature to be maintained. Program mode offers automatic temperature con­trol for specific times of the day.
In the initial screen when the remote is turned on, three options are available; AUTO, MANUAL, and MENU. Auto and Manual are two of the three different modes for controlling the appliance with the remote.
Auto (Thermostatic) Mode
If Auto is pressed in the initial screen, 77º F (25º F) appears as the desired temperature in the se­lected setting. In the bottom row, and ap­pear, indicating that we can change the desired temperature value by just pressing the left or mid­dle button. In auto mode the appliance heats until this temperature is reached. Limits are 32 - 99º F (0 - 37º C ).
Pressing Back (right button), returns to the initial screen.
In this mode the main burner will be switched on and off to maintain the desired temperature.
The Auto mode feature is optional and can be en­abled or disabled in the configuration menu.
Program Mode
There are two types of program mode: a Daily mode and a Weekly mode. In the daily mode, every day uses the same program. In the weekly mode, every day has its own program, so it is pos­sible to have a different program for each day of the week.
38
COPRECI R-emotion CONTROL SYSTEM
2.6 Day programming menu (Menu Adjust Menu Change Program).
There are 8 menus like this. One for Daily, and the others for each day (Monday, Tuesday, Wednesday, Thurs­day, Friday, Saturday and Sunday). This day programming screen consists of:
Daily program.
A: Selected (including "Daily"). The selected
day can be changed by pressing Change (middle button).
B: Day schedule graphic. This bar displays the program for the whole day by showing the tem­perature setting for each hour of the day. To access the day schedule graphic, press (left button). To change the desired temperature, go to the hour you want to change by pressing (left button) and then press change (middle button). There are 3 possible temperature settings:
Off : The appliance is in pilot mode (no temperature control). Night Temp: The night temperature is set as the desired temperature and the appliance will heat until this temperature is reached. Comfort Temp: The comfort temperature is set as the desired temperature and the appliance will heat until this temperature is reached.
Finally, to launch the program mode, in the main menu, set Program to On, and select the desired Program Type (Daily or Weekly).
2.7. Other features
How to locking and unlock the remote (child lock):
To unlock the remote, press the Unlock button and then O.K.
To lock the remote, in the main screen press Menu go to the Lock option, press Select and then Change. The remote will immediately go into locked mode.
Automatic lock can be selected. This means that if no button is pressed for while, the remote automatically goes into locked mode.
How to change Language:
In the main screen, press Menu button. Select Language, press Change and select required language.
How to select the temperature unit (°F / °C)
In the main screen, press Menu button. Select Adjust Menu and then select Unit. To change the tem­perature unit press Change button.
39
COPRECI R-emotion CONTROL SYSTEM
2.8. Configuration Menu
To acess the configuration menu, press the OFF button on the remote control for 40 seconds. During
this time the screen may go blank, this is normal. After 40 seconds, the Configuration menu appears. This is a list of the settings that can be changed in the configuration menu:
Pairing: This feature establishes communication between the remote and the fire­place. Pairing will not be required unless communication is lost or, you have a new remote control. If pairing is required it must be done on channel A (go to the last option in the configuration menu by pressing and select channel A).
After that, go to pairing option again and press the select button (middle button) and when off is highlighted, press the change button (left button) off becomes on.
Once the pairing is on, you have 20 seconds to push (press and release) the button S1 (yellow) in the control unit.
Once this operation is done, you hear a beep in the control unit and on the control unit will appear:
To return to the home screen press the back button until you get to main screen.
PS: If pairing has been attempted previously and has not been achieved, try the follow­ing:
- Press and hold the OFF button for 40 seconds.
- Set the channel on channel A.
- Select On in the pairing setting.
- Unplug the batteries from the control unit (wait 10 seconds) and plug the batteries back in.
- Once the valve has finished moving, repeatedly push (press and release) the S1 but­ton (yellow button on the control unit), until you hear the beep that confirms that pair­ing has taken place.
Thermostat: This option enables or disables the auto thermostat mode. To enable it, select Yes. To disable it select No.
Gap Temp: this option refers to the tolerance between the desired temperature and the current one. If the dif­ference is greater than this gap temperature setting, the flame level increases. For example: the desired tem­perature is set at 20°C and the current temperature is 18°C:
• If the Gap Temp is 0.5°C: Flame level will go to maximum level because the difference is 2°C.
• If the Gap Temp is 1°C: Flame level will go to medium level as difference of 2°C is two times the gap set­ting. If the Gap Temp is 2°C: Flame level will go to minimum level as the difference of 2°C is equal to the gap setting.
40
COPRECI R-emotion CONTROL SYSTEM
Programming: this option enables or disables the program mode. To enable it, select Yes. To disable it, select No.
Fan System: Not applicable on this appliance always set to NO. Soft Start: Should always remain in “ON” setting. Ember bed: Not applicable on this appliance always set to NO. Sounder: This option enables or disables the sounder option. To enable it, select Yes. To disable it, select No. Safety Temp: This temperature is the maximum permitted room temperature. If the remote detects that the
temperature is higher than the Safety Temp, the appliance is switched off. This temperature can never be. set higher than 104°F (40°C). The possible range of values is 77-104°F (25-40°C). Suggested setting is 95°F (35° C). Channel: There are three different channels available: A, Band C. These different channels make it possible to have more than one appliance, each with its own remote. If you only have one unit the channel setting should remain on A. If you need to change the channel just press Select, choose one of other channels and then reset the control unit by disconnecting the power supply for a short period. Afterwards the connection between the remote and the control unit will be re-established. Change channel only if necessary.
The remote may be used in easy mode by disabling options in the configuration menu. If all options are disabled, the remote works in manual mode only. Furthermore the only on-screen option are Manual and Menu. Within the menu only Adjust Menu and Lock are accessible.
41
TROUBLESHOOTING
42
MAINTENANCE
A qualified service agency should conduct an annual inspection and maintenance of your includ­ing the overall installation and venting to keep it running safely. The following procedures should be per­formed only by a qualified service person. The gas supply should be turned off and the stove should be completely cool whenever a maintenance procedure is performed. All parts of the appliance that are removed for servicing must be replaced prior to operation.
WARNING: Do not operate the appliance with the glass front removed, cracked or broken. Replacement of the glass should be done by a qualified service person.
WARNING: Use only glass assembly, P/N 16-510 which includes the glass panel, frame and gasket. Do not use substitute materials. Do not strike or slam the glass front. The appliance area must be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
REPLACING THE GLASS
The glass mounting system consists of the glass panel, special glass gasket and the metal glass frame. Should the glass need to be replaced, you must replace the entire glass/glass frame assembly (PN 16-510). See page 46 for information on obtaining replacement parts. Use the following procedure and refer to the illustrations on page 29 of this manual.
1. Turn the fireplace completely off and allow it to cool to room temperature.
2. Remove the fireplace surround. See instructions on page 31.
3. If the glass is broken, be sure to wear gloves and eye protection.
4. Remove the glass frame fasteners from the top edge of the glass frame.
5. This will allow the glass frame to tip slightly forward. The glass may be loose in the frame, so it is very important to support both the glass and the frame when handling. Place your thumbs on the outside of the glass frame and wrap your fingers around the frame and onto the glass. Squeeze the frame and glass while moving. Carefully lift the glass frame and glass up and off the fireplace. Set the glass and frame aside on a padded surface. If the glass is broken, do this over spread out newspaper to catch all loose material. Wrap the old glass frame, glass and gasket in several layers of newspaper and discard.
Installing the replacement glass/glass frame assembly.
1. Unpack the new glass/glass frame assembly taking care when handling.
2. Carefully pick up the glass and glass frame assembly by grasping the sides of the frame and using your thumbs and fingers to hold the glass in place within the gasket and frame.
3. With the glass frame (and glass) at a slight angle (leaving room for your fingers between the frame and the firebox) insert the bottom edge of the frame into the frame retainer located on the bottom front of the firebox. Take care to center the frame from left to right. Once the bottom edge is in place, move your fingers out of the way and press the top of the frame against the firebox while pushing down to be sure the frame is fully engaged in the frame retainer. Hold the frame in place with one hand and rein­stall the glass frame fasteners, leaving them loose.
4. Tighten the glass frame fasteners in stages working from the center out. Continue the process until all fasteners are uniformly tight. Do not over-tighten the fasteners.
5. Replace the fireplace surround.. See instructions on page 31.
CLEANING THE GLASS WARNING: Never clean the glass while it is hot. Do not use abrasive cleaners or cleaners containing
ammonia. NOTE: A micro-fiber cleaning cloth and plain water is recommended by the glass manufacturer.
43
MAINTENANCE
Inspecting the Venting An inspection of both the inner and outer vent pipes and the vent terminal should be made as part of the an-
nual service appointment. The venting must have no blockage and be in good repair. The vent manufac­turer’s instructions may provide specific details on vent inspection. Any vent sections that are disassem­bled must be reassembled and sealed as required.
This appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive dust or lint from carpeting, bedding mate­rials, pets, etc. It is imperative that control compartments and circulating air passageways of this appliance be kept clean.
Cleaning the Burner and Firebox During the annual inspection and maintenance appointment, the service person should clean the burner and firebox. To gain access to the firebox and burner, follow the instructions beginning on page 34 of this man­ual. DO NOT USE A VACUUM CLEANER TO CLEAN THE GLASS BURNER MEDIA. A vacuum cleaner may be used to clean the metal parts of the firebox. Leave the glass burner media in place. Use a soft brush to clean the burner glass media. If the burner media does need to be removed, care­fully scoop it off the burner and avoid dropping glass pieces in the air gaps around the burner. Follow the instructions on page 27 of this manual when replacing the burner media on the burner top.
Air Flow The utilizes a convection air heat exchange system to maximize heat delivered from the fire­place. It is important that air flows freely through the convection air system and out the top and side air grills. Do not place objects under the fireplace that will block the convection air inlet flow or in front of
44
MAINTENANCE LOG
We strongly recommend that you keep a log of the regular maintenance that is performed on your fireplace. We have provided the forms below to make it easy. Simply ask your qualified service per­son to fill out one of the maintenance record forms below, each time the fireplace is serviced. This will help insure that all of the required maintenance procedures have been completed, at least annu­ally. Regular maintenance will help keep the fireplace functioning in a safe and reliable manner. Additional forms are available from your installer or service person when needed.
Date of Service ____________________ Serviced By ____________________ __ Service Performed
Inspect Venting Clean Burner & Firebox Clean Control Area Clean Convection Air System Leak Test Gas Connections Other __________________________
Date of Service ____________________ Serviced By ____________________ __ Service Performed
Inspect Venting Clean Burner & Firebox Clean Control Area Clean Convection Air System Leak Test Gas Connections
Date of Service ____________________ Serviced By ____________________ __ Service Performed
Inspect Venting Clean Burner & Firebox Clean Control Area Clean Convection Air System Leak Test Gas Connections Other __________________________
Date of Service ____________________ Serviced By ____________________ __ Service Performed
Inspect Venting Clean Burner & Firebox Clean Control Area Clean Convection Air System Leak Test Gas Connections
Other __________________________
Date of Service ____________________ Serviced By ____________________ __ Service Performed
Inspect Venting Clean Burner & Firebox Clean Control Area Clean Convection Air System Leak Test Gas Connections Other __________________________
Other __________________________
Date of Service ____________________ Serviced By ____________________ __ Service Performed
Inspect Venting Clean Burner & Firebox Clean Control Area Clean Convection Air System Leak Test Gas Connections Other __________________________
45
REPLACEMENT PARTS LIST
PART NAME P/N PART NAME P/N
Pilot Head NG/LP 26-501 Burner Orifice - NG 16N-509 Pilot Thermcouple* 26-502* Burner Orifice - LP 16P-509 Pilot-Injector -NG 26N-503 Glass/Frame/Gasket Ass'y 16-510 Pilot-Injector - LP 26P-503 Burner Glass Media-Clear 16-511 Valve Control Module (Copreci) 46-504 Burner Module - NG 16N-901 Manual Control Panel (Copreci) 46-505 Burner Module - LP 16P-901 3 - “C” Battery Holder (Copreci) 46-506 Firebox Panel - Rear 16-512 Remote Handset (Copreci) 46-507 Firebox Panel - Left 16-513 Gas Valve (Copreci) 46-515 Firebox Panel - Right 16-514 External Regulator (Maxitrol) 26-516
*This is a quick response thermocouple. Replace it only with Part No. 26-502
For replacement parts and customer service, contact your
dealer or:
Hearth Innovations Inc. 20 Airpark Road West Lebanon, NH 03784 Telephone: 603-298-5169
46
CONTROL SCHEMATIC
D
E
C
G
A
F
B
Caution: Label all wires prior to disconnection when servicing the controls. Wiring errors can cause improper and dangerous
H
operation. Verify proper operation after servicing.
Caution: Label all wires prior to disconnection when servicing the controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
47
INSTALLATION RECORD
The installer should complete the form below that describes the details of the installation. Having this writ­ten record of installation information available will greatly expedite trouble-shooting should any problem arise with your stove. The installer should keep a duplicate of this form for their records.
48
49 50
Manufactured by: Progressive Manufacturing Inc. 20 Airpark Road West Lebanon, NH 03784 USA www.hearthinnovations.com
V5 / 12.04.09