SolarMax SM30HT4, SM32HT4 Instruction Manual

SolarMax HT series
30HT4 / 32HT4
Instruction manual
Contents
1 Notes on this instruction manual � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
1.1 Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Target groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Where to keep this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Symbols used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Symbols on inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Description � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
3.1 Identication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Safety installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.6 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
4 Installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14
4.1 Transporting and storing inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
4.2 Lifting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
4.3 Checking the delivery for completeness . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.4 Selecting the installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.5 Mounting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
5 Electrical connection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21
5.1 Removing the cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 Connection area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.3 Connecting the inverter to the mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4 Connecting the inverter to the PV generator . . . . . . . . . . . . . . . . . . . . . . . . 25
5.5 Network connections (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.6 Connecting status signaling contacts (optional) . . . . . . . . . . . . . . . . . . . . . 29
5.7 External shutdown (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.8 External output control (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6 Commissioning� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 34
6.1 Activating the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2 Initial start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6. 2 .1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2
6.2.3 Country-specic menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3 Auto test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6. 4 .1 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.4.2 Setting the display language and system time. . . . . . . . . . . . . . . . 39
6.4.3 Setting the network parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.4.4 Conguring the status signaling contacts . . . . . . . . . . . . . . . . . . . 41
6.5 Displaying the conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6. 5 .1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.5.2 Description of extended functions and parameters . . . . . . . . . . . . 43
6.6 Displaying measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.7 Registering for MaxView. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7 Operation� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 51
7.1 Graphics display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.2 Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
7.3 Displaying the operating data overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.4 Displaying Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.5 Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.5.1 Displaying the daily statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.5. 2 Displaying the monthly statistics . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.5.3 Displaying the annual statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.5.4 Displaying the total statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.5.5 Deleting the statistics values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.6 Displaying information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.7 Displaying the operating status of the inverter . . . . . . . . . . . . . . . . . . . . . . 57
7.7.1 "Booting" operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.7. 2 "Mains operation" operating status. . . . . . . . . . . . . . . . . . . . . . . . 58
7.8 Displaying the operating status of the MPP trackers. . . . . . . . . . . . . . . . . . 59
8 Troubleshooting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 60
8.1 SolarMax Service Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.2 Diagnosis and actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8. 2.1 General troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.2.2 Warning messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.2.3 "Failure" operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.2.4 "Error" operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.2.5 "Blocked" operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
9 Maintenance � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 63
en
3
10 Decommissioning� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 64
10.1 Instructions for inverter replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.2 Dismounting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.3 Disposing of the inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11 Technical data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 66
11.1 Efciency curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
11.2 Temperature-dependent output reduction . . . . . . . . . . . . . . . . . . . . . . . . . 68
11.3 MaxComm compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
11.4 Country-specic settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
12 Accessories and options � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 70
13 Warranty � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 71
4

1 Notes on this instruction manual

1�1 Scope

This instruction manual is applicable to the following SolarMax inverters:
Type Item No�
SM 30H T4 10 006 012 SM 32H T4 10 006 011

1�2 Target groups

This instruction manual is intended for the operator of the plant and the installer of the PV power plant.
The instructions in chapters 5, 6�2, 8 (troubleshooting actions) and 10 may only be car- ried out by trained electricians (e.g. electricians, electric systems technicians, electrical mechanics, industrial electronics technicians).
The instructions in chapter 4 should only be carried out by specialist transport personnel.

1�3 Where to keep this manual

The plant operator must ensure that this instruction manual is available to the relevant persons at all times. If this original document is lost, an up-to-date version of this instruc­tion manual can be downloaded from our website at any time (www.solarmax.com).

1�4 Symbols used

The following safety instructions and general information are used within this instruction manual.
DANGER!
Non-observance of these safety instructions results in serious injuries or death.
en
WARNING!
Non-observance of these safety instructions may result in serious injuries or death.
CAUTION!
Non-observance of these safety instructions may result in minor or extensive injuries.
5
ATTENTION!
Non-observance of these safety instructions may result in material damage.
Note
Notes contain additional information or facilitate operation of the inverter.

2 Safety

2�1 Intended use

SolarMax HT series inverters are designed exclusively for the conversion of the direct cur­rent generated by PV modules into alternating current which conforms to the parameters of the public grid. Any other use is contrary to the intended use.
Inverters of the HT series may only be used in combination with PV modules which comply with the IEC 61730 standard. Inverters of the HT series may only be connected to Class II PV generators.

2�2 Safety instructions

DANGER! Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC voltage.
Make sure that all electrical input conductors to the inverter are de-ener-
gized before starting any work on the inverter or the input conductors.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage.
Never open the inverter while it is in operation.
WARNING! Risk of injury from electric arc!
Removing the DC connectors when live can lead to dangerous electric arcs.
Switch off the DC disconnector at the inverter before removing the DC
connectors.
6

2�3 Symbols on inverter

Symbol Description
The DC disconnector is switched off (the contacts are open).
O
I
The DC disconnector is switched on (the contacts are closed).
+ −
Positive or negative pole of input voltage (DC)
Risk of death from high voltages! Only qualied electricians may perform work on the inver ter.
Careful - hot surfaces!
en
5 min
Risk of death due to high voltages in the inverter! De-energize the inverter. Proceed to wait for 5 minutes before opening the inverter.
Only qualied electricians may perform work on the inverter.
Operating instructions - Please read and follow the instructions supplied with the inverter. Do not remove any symbols on the inverter. Replace any damaged symbols.
CE marking - The inverter complies with the requirements of the European EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC (see Section 11).
GS marking - The inverter complies with the relevant requirements of the German Product Safety Act.
Do not dispose of the inverter and its accessory components in the household waste.
7

3 Description

3�1 Identication
The inverter can be identied on the basis of the information provided on the nameplate (see Section 3.5).

3�2 Functionality

Automatic operation
Inverter operation is completely automatic and depends on the available output of the PV generator. If there is enough power, the inverter starts mains operation and feeds into the power grid. If there is not enough power available from the PV generator, the inverter disconnects from the grid and shuts down.
Operation
The graphics display with three function keys allows convenient inverter operation and reading of all important operating data. The graphics display is only switched on when the DC input voltage is high enough.
The DC disconnector can be used to switch the PV generator on or off at any time. The components of the inverter remain live even when the DC disconnector is switched off.
Remote monitoring
For the purpose of monitoring the PV plant remotely, Ethernet and RS485 interfaces are provided. The inverter can be directly connected to the internet via Ethernet (MaxView). The inverter is equipped with status signaling contacts for displaying the operating status remotely.
Extended functions
The inverter has functions for grid monitoring, limitation of output and reactive power control. These can be congured with additional software.
Remote controlled output limitation and reactive power control can be achieved using the MaxWebxp and MaxRemote accessory components.
Ventilation
The inverter is air cooled. Fans draw in the air through the air inlet on the right-hand side of the inverter. Then the air is conducted across the internal cooling elements. The air outlet is on the left-hand side of the inverter.
8

3�3 Safety installations

Surge protection
The inverter is tted with surge arresters (varistors) at its input and output. Each MPP tracker (plus and minus connections) is equipped with a surge arrester. On the AC side, each mains phase has a surge arrester (for details on the surge arresters tted, see Section 11).
When designing the PV system, it may be necessary to provide additional external light­ning protection.
Fault current monitoring
The inverter has an AC/DC sensitive leakage current sensor which monitors the stray currents occurring on the generator side. This sensor can distinguish between the oper­ational capacitive stray currents (caused by capacities of the PV modules to ground) and leakage currents (caused by touching a pole of the PV generator). If the inverter detects an excess in the permissible leakage or stray currents, it will disconnect from the grid.
Functions for current and output limitation
When it is needed, the inverter limits the DC feed-in current, the output power and the output current.
Temperature limitation
At ambient temperatures of more than 45°C the equipment temperature may reach more than 80°C. In such cases, the maximum in-feed power is temporarily reduced. When the equipment temperature rises above 85°C, the inverter disconnects from the grid.
en
9
[mm]
590
397

3�4 Dimensions

580
847
871
Figure 1 Dimensions (with wall mounting bracket)
10

3�5 Views of the unit

6
en
5
9
10
12 11
Figure 2 Views of the unit
8 7
4
7
3
1
2
11
No� Description
1 Ventilation inlet 2 Cover 3 Graphics display 4 Type plate 5 Safety brackets 6 Wall mounting bracket 7 Handles (for lifting the inverter by hand) 8 Ventilation outlet 9 "AC mains" cable gland (AC input conductor)
10 "COMM" multiple cable gland (for communication cables)
11 DC disconnector (can be locked with a padlock)
12 DC terminals
12

3�6 Block diagram

AC output
K2
K1
DC
Inverter
DC
Booster 1
U
K5
Ethernet
EMC lter
AC measurement AC measurement
Fan Fan
LC lter
AC
Inverter control Inverter control
Booster control
DC
DC
Booster 2
DC
Control unit MPP tracker 1/2
Control unit MPP tracker 3/4
DC measurement
DC measurement
RS485
Booster control
DC
RS485
Status signalling contact
MPP tracker 1/2
DC
Booster 3
External shutdown
Status signalling contact
MPP tracker 3/4
K4
K3
LC lter
AC
DC
Inverter
DC
DC
Booster 4
en
Communication module
Graphics display
EMC lter
U
DC input MPP tracker 1
Figure 3 Block diagram
EMC lter
EMC lter
U
DC input MPP tracker 2
EMC lter
U
DC input MPP tracker 3
EMC lter
U
DC input MPP tracker 4
I
0
DC disconnector Q1
13

4 Installation

4�1 Transporting and storing inverters

Make sure that the ambient conditions during transportation and storage are within the specied limits (for details see Section 11).

4�2 Lifting the inverter

The inverter is tted with handles (Figure 2/Pos. 7), which can be used to lift the inverter from the packaging by hand.
CAUTION! Risk of injury - the inverter is heavy!
The inverter weighs approx. 70 kg.
Do not mount the inverter without the help of a second person.
14

4�3 Checking the delivery for completeness

Check the contents of the delivered package for completeness and possible damage. In the case of an inadequate delivery, please contact your dealer or the SolarMax Service Center.
SolarMax HT-Serie
17
30HT4 / 32HT4
1
Gerätedokumentation
2
3
4
5 6 7
en
16
15
14
Figure 4 Content of delivery
No� Quantity Description
1 1 Inverter 2 1 Instruction manual 3 16 Locking clip (for locking the DC connector) 4 2 Safety brackets (for installation of inverter) 5 1 6-pole connector (for connection of status signaling contacts) 6 1 4-pole connector (RS485 connection) 7 1 3-pole connector (connection of external grid monitoring)
8
9 10 11 12 13
15
No� Quantity Description
8 3 Locking pins (for multiple cable gland) 9 1 M5 toothed washer (connection of second protective conductor) 10 1 M5 cable shoe (connection of second protective conductor) 11 1 M5 circlip (connection of second protective conductor) 12 1 M5 washer (connection of second protective conductor) 13 1 M5 nut (connection of second protective conductor) 14 8 10 x 50 wall plugs (mounting of inverter) 15 8 M6 x 18 washers (mounting of inver ter) 16 8 6 x 60 Torx pan head screws (mounting of inverter) 17 1 Mounting plate (mounting of inverter)

4�4 Selecting the installation location

DANGER! Fatal re or explosion hazard!
The inverter is an electrical device with heat generation and the possibility of sparking.
Install the inverter in an environment that is free of ammable gases and
uids.
Never install the inverter near combustible materials. The installation sub-
strate must be non-combustible.
Follow the local re safety regulations.
CAUTION! Risk of injury - the inverter is heavy!
The inverter weighs approx. 70 kg.
The installation substrate must have sufcient structural strength.
Location and installation conditions
The ambient conditions are specied in the specications, see Section 11.Select a dry location protected from water and snow.Do not expose the inverter to direct sunlight.Install the inverter in an easily accessible location, so that maintenance work can be
carried out easily.
When mounting the unit observe the following minimum distances:
16
50
[cm]
50
en
50 50
50
100
50
50
Figure 5 Minimum installation distances
Do not mount the inverter at an angle or on its side:
Figure 6 Unacceptable mounting positions
Appropriate cooling of the inverter can only take place when the ventilation openings
on the sides are kept clear.
The ambient air around the inverter must be free from dust, salt and ammonium
vapors.
The location must meet the requirements regarding emissions and freedom from
electromagnetic interference.
17

4�5 Mounting the inverter

Install the inverter to a vertical wall using the mounting plate. The mounting plate and the xing material are included in the delivery.
Fixing the mounting plate
1. Use the mounting plate as a drilling template.
2. Use a spirit level to align the mounting plate horizontally.
3. Mark 6 places for drilling:
89
205
553
23
226
25
574
226
25 25
23
230
12 x ø8.5
[mm]
Figure 7 Dimensions of mounting plate
4. Drill the Ø10 x 60 mm holes.
5. Fix the mounting plate.
18
– Installation sequence: 10 x 50 wall plugs, mounting plate, M6 washers, 6 x 60 Torx
pan head screws.
Figure 8 Fixing the mounting plate
Engage the inverter in the mounting plate
6. With the help of a second person, engage the inverter in the seats of the mounting plate:
en
Figure 9 Engaging the inverter in the mounting plate
19
Securing the inverter
7. Drill two Ø10 x 60 mm holes.
8. Secure the inverter with the 2 safety brackets (included in the delivery). – Installation sequence: 10 x 50 wall plugs, safety bracket, M6 washers, 6 x 60 Torx
pan head screws.
Figure 10 Securing the inverter
Note
The safety brackets can also be tted laterally.
20

5 Electrical connection

The DC terminals are freely accessible from the outside of the inverter. The AC terminals and all communication terminals are inside the inverter.
The inverter may only be installed by qualied electricians.

5�1 Removing the cover

The AC and communication terminals are accessible when the cover is removed.
Procedure
1. Disconnect the AC power supply to the inverter.
2. Disconnect all control cables connected to the inverter (status relays, external grid monitoring and shut-down).
3. Switch off the DC disconnector at the inverter.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage. After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.
Wait 5 minutes until the voltages inside the inverter have reduced before
removing the cover and carrying out connection work.
4. Release the M6 screws (Figure 11/No. 1) from the cover.
5. Remove the cover (Figure 11/No. 2).
O
en
5 min
Figure 11 Removing the cover
2
1
21

5�2 Connection area

All terminals and cable glands of the inverter are shown in Figure 12.
8
9
10
7
6
5
4
3
2
1
Figure 12 Connection area
No� Description
1 DC terminals (MC4 compatible plug-in terminals) 2 "COMM" multiple cable gland for communication cables (network connections, status
signaling contacts, external shutdown) 3 "AC mains" cable gland for the AC input conductor 4 M5 threaded "PE" bolt for the connection of the second protective conductor (optional) 5 AC terminals (screw terminals) 6 External shutdown (plug-in terminal) 7 Status signaling contacts (plug-in terminal) 8 RS485 (plug-in terminal)
9 Ethernet and RS485 communication sockets (RJ45) 10 Cable grips for restraining the cable (for the communication cables)
22

5�3 Connecting the inverter to the mains

DANGER! Fatal electric shock hazard!
Make sure the AC input conductor is not live during connection work.
Connection conditions
Comply with the connection conditions set by the grid operator.M40 cable gland; suitable for cable Ø: 24 to 33 mmConnection type: screw terminals (UWV 25)
Permissible conductor cross sections:
– exible conductor (with or without conductor sleeve): max. 25 mm – rigid conductors: max. 35 mm
The protective conductor of the AC input conductor should be cut at least 30 mm
2
longer than the other conductors.
The AC input conductor must be fused. Minimum conductor cross sections and sug-
gested mains fuses:
Minimum conductor cross sections 30HT4 32HT4
Phases L1, L2, L3 10 mm Neutral conductor N 4 mm Protective conductor PE 10 mm
Recommended mains fuses 30HT4 32HT4
Nominal current 63 A 63 A Characteristics C C
2
2
2
10 mm 4 mm 10 mm
2
2
2
2
en
Make sure the ambient temperatures for the mains fuses specied by the producer
are not exceeded.
WARNING! Fatal fire risk!
Provide separate fuses for each inverter.Do not connect any loads between the inverter and the mains fuse.
If you use external residual current devices (RCDs), use the type B RCDs with a nom-
inal fault current of 100 mA. For PV plants with large stray current capacities, the RCDs to be used should have a nominal fault current capacity of 300 mA.
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the AC input conductor through the cable gland.
23
3. Cut back the insulation of the conductor by 19 mm.
4 … 4.5 Nm
M5
4. Connect the wires in the following sequence: – the protective conductor to the "PE" terminal – the neutral conductor to the "N" terminal – the mains phases to the terminals "L1", "L2", and "L3". – Tightening torque: 4 to 4.5 Nm
L3 PE
L1
L2
N
19 mm
Figure 13 AC connection
5. Check the cable connections for rm seating.
6. Tighten the M40 cable gland.
7. Check the cable strain relief.
8. Connect the second protective conductor (optional): – Installation sequence (see Figure 14): M5 toothed washer (No. 1), cable shoe (No.
2), M5 washer (No. 3), M5 circlip (No. 4), M5 lock nut (No. 5);
– all xing elements are included in the delivery.
24
1
2
3 4 5
Figure 14 Connecting the second protective conductor (optional)
9. Close the inverter by tightening the cover.

5�4 Connecting the inverter to the PV generator

The HT series inverters have four independent MPP trackers which can be used to con­nect strands with different characteristics, such as orientation, size and module type. Each MPP tracker can be tted with two strands as standard.
en
1
3
Figure 15 Terminals of the MPP trackers 1 to 4
2
4
No� MPP tracker
1 1 2 2 3 3 4 4
25
Connection conditions
Type of connection: Wieland PST40i1C plug connectorOnly use Wieland PST40i1C connectors (not included in the delivery).
Maximum DC input current per MPP tracker: 18 AMaximum DC input voltage: 1 000 VSelect conductor cross sections to suit the plant conguration.The maximum short-circuit current (Iscpv) is 25 A.
DANGER! Fatal re risk!
High return currents can cause a re risk for the PV generator.
When Y plugs are used in order to connect more strands than specied,
each DC input conductor must be protected individually against dan­gerous return currents.
Parallel connection of the MPP trackers is not permitted:
26
Figure 16 Unacceptable parallel connection of MPP trackers
Do not t a ground connection to either the negative terminal or the positive terminal
of the PV generator.
Procedure
1. Make sure that the DC disconnector is switched off.
2. Disconnect the AC power supply to the inverter.
3. Connect the DC input conductors that have been pre-tted with the connector.
4. Use the locking clips (included in the delivery) to secure the plug connectors.
DC−
DC+
DC+
DC−
Figure 17 Connecting the strands
Close off any unused DC plug connectors�
Any unused DC plug connectors must be closed off to ensure that the installation com­plies with the IP65 protection rating requirements. Please use the following closing parts made by Wieland (www.wieland-electric.com):
for plug component: order number 05.566.6380.0for socket component: order number 05.566.6480.0
en

5�5 Network connections (optional)

The inverter has one Ethernet and three RS485 interfaces. These can be used to connect the inverter to the internet, a MaxComm network or other networks. The RS485 inter­faces are connected in parallel inside the unit. The connection can be made with RJ45 plug connectors or screw terminals.
27
12
A GND 15 V
B
3
4
Figure 18 Network connections
No� Description
1 RJ45 socket RS485 2 RS485 plug connection
B Bus B 15 V 15 V network input GND Network input ground connection
A Bus A 3 RJ45 socket RS485 4 RJ45 socket Ethernet
Note
You will nd further details about data communication in the technical infor­mation "MaxComm network". You can download this document from our web­site at: www.solarmax.com; Downloads/Data Communication/MaxComm.
28
Connection conditions
Connection types: 3 x RJ45 sockets / 4-pole plug (included in the delivery)Suitable conductor cross sections (plug connector): 0.25 to 2.5 mmMultiple cable gland; usable cable Ø: 5.5 to 7.0 mmYou should use shielded network cables (cat. 5)
2
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the network cables through the multiple cable gland.
Note
The RJ45 connectors can be pulled through the multiple cable gland.
3. Plug the network cables into the RJ45 sockets (Figure 19/No.1) and check that the connection is locked.
4. RS485 terminal connection (Figure 19/No.2): connect the RS485 network cable as follows:
– Wire stripping length: 7 mm – Tightening torque: 0.5 to 0.6 Nm
1
2
3
M3
0.5 … 0.6 Nm
7 mm
Figure 19 Network connection
5. Use cable ties to attach the cables to the housing grips (Figure 19/No. 3).
6. Close off the unused apertures in the multiple cable glands using the locking pins (No. 8 in Section 4.3).
7. Tighten the multiple cable gland (wrench size: 34 mm).
8. Fit the cover of the inverter.
en

5�6 Connecting status signaling contacts (optional)

The congurable status signaling contacts are used for the remote monitoring of the inverter. Both power units (MPP tracker 1/2 and MPP tracker 3/4) can be monitored indi­vidually using a status signaling contact. When the external deactivation is used (see Section 5.7) the status signaling contacts cannot be used.
The status signaling contacts can be congured, see Section 6.4.4.
29
NC1 COM1 NO1
NC2
COM2
NO2
Figure 20 Status signaling contacts
Status signaling contact MPP tracker 1 and 2
NC1 Opens in the case of an error COM1 Common 1 NO1 Closes in the case of an error
Status signaling contact MPP tracker 3 and 4
NC2 Opens in the case of an error COM2 Common 2 NO2 Closes in the case of an error
Connection conditions
Connection type: 6-pole connector (included in the delivery)Connectable conductor cross sections: min. 0.25 mmMultiple cable gland; usable cable Ø: 5.5 to 7.0 mmMax. switching voltage: 250 VAC / 30 VDCMax. switching current: 1.5 A (no internal fuse present)Max. cable length: max. 50 m
2
/ max. 2.5 mm
2
30
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the cable through the multiple cable gland.
3. Connect the control lines to the 6-pole connector (Figure 21/No. 1) as follows: – Wire stripping length: 7 mm – Tightening torque: 0.5 to 0.6 Nm
0.5 … 0.6 Nm
M3
1 2
en
3
Figure 21 Connecting the status signaling contacts
4. Plug in the 6-pole connector.
5. Plug in the 3-pole connector (Figure 21/No.2) in order to cover the open contacts.
6. Use cable ties to fasten the cables to the housing grips (Figure 21/No. 3).
7. Close off any unused apertures in the multiple cable gland using the locking pins (see No. 8 in Section 4.3).
8. Tighten the multiple cable gland (wrench size: 34 mm).
9. Fit the cover of the inverter.
7 mm

5�7 External shutdown (optional)

This interface can be used to connect the inverter to an external grid monitoring system which can disconnect the inverter from the mains grid from a remote location when this is needed.
1
Figure 22 External shutdown terminals
NA21 NA22 NA1
31
Contact Description
NA21 Control line terminal / external shutdown of MPP trackers 1 and 2 NA22 Control line terminal / external shutdown of MPP trackers 3 and 4 NA1 Neutral conductor terminal
For as long as the signal (phase voltage) of the external grid monitoring system is live on the NA21 / NA22 contacts, the respective MPP trackers can feed into the mains grid. When the signal stops, the K1/K3 or K3/K4 (see Section 3.6) grid relays of the inverter are opened. This immediately disconnects the inverter from the grid.
The control line of the external grid monitoring system should be connected to the two contacts, NA21 and NA22, using a bridge. When only one contact is connected, only that one MPP tracker will feed into the grid. When the status signaling contacts are in use (see Section 5.6) the external shutdown function cannot be used.
Connection conditions
Connection type: 3-pole connector (included in the delivery)Permissible conductor cross sections: 0.25 to 2.5 mmMultiple cable gland; permissible cable Ø: 5.5 to 7.0 mmNominal input voltage 230 VAC
2
Procedure
1. Remove the cover of the inverter as described in Section 5.1.
WARNING! Fatal electric shock hazard!
The control line of the thermal grid monitoring system may be live with mains voltage.
Ensure that the control line is not live during connection work.
32
2. Thread the cable through the multiple cable gland.
3. Connect the control line to the 3-pole connector (Figure 23/No. 2) as follows: – Wire stripping length: 7 mm – Tightening torque: 0.5 to 0.6 Nm
M3
1
2
0.5 … 0.6 Nm
en
3
Figure 23 Connecting the external shutdown
4. Plug in the 3-pole connector.
5. Plug in the 6-pole connector (Figure 23/No. 1) in order to cover the open contacts.
6. Check that the NA21 and NA22 contacts are bridged (Figure 22/No. 1).
7. Use cable ties to attach the cables to the housing grips (Figure 23/No. 3).
8. Close the unused apertures in the multiple cable gland using the locking pins (No. 8 in Section 4.3).
9. Tighten the multiple cable gland (wrench size: 34 mm).
10. Fit the cover of the inverter.
7 mm

5�8 External output control (optional)

The MaxWebxp data logger and its MaxRemote extension can be used to set the set values for active and reactive power (e.g. for remote controlled output limitation). The MaxWeb xp is connected via the Ethernet or via the inverter's RS485 interfaces (see Sec­tion 5.5), i.e. via a MaxComm network.
You can download the installation instructions for the MaxWebxp and MaxRemote acces­sory components from our website: www.solarmax.com; Downloads / Data communica­tion / MaxWebxp.
33

6 Commissioning

6�1 Activating the inverter

The inverter is connected to the PV generator when the DC disconnector is switched on. The graphics display and the communication functions are activated.
Procedure
1. Check that the inverter's cover is installed.
2. Switch on the DC disconnector at the inverter.
I
Figure 24 Switching on the DC disconnector
– When the input power is sufcient, the graphics display will show the "Overview".
3. Switch on the AC power supply to the inverter. – The "Start-up" status message is shown.
4. Wait for the "Mains operation" status message to be displayed. – This indicates that the inverter is in mains operation. – During initial start-up of the inverter, instead of the “Overview” menu, an “Initial
setup” menu appears (see Section 6.2).
34

6�2 Initial start-up

This section describes the initial start-up of the inverter and the graphics display set­tings required for this purpose. Once initial start-up has been successfully completed, the inverter will start feeding into the mains grid.
The initial start-up should be carried out by qualied electricians only. The operation of the graphics display is described in Section 7.

6�2�1 Requirements

The inverter has been installed and the electricity has been connected.The inverter's cover has been tted.There is sufcient solar irradiation (sufciently high DC input voltage).
Note
Entering an incorrect country setting may lead to problems regarding
inverter operation and to the withdrawal of the operating license by the respective grid operator.
Contact your grid operator or the SolarMax Service Center if you have any
doubt regarding the settings you must select.
You can restart initial start-up by pressing in the "Conrmation"
menu at any time.
6�2�2 Procedure
1. Switch on the inverter as described in Section 6 .1. The "Initial setup" menu will be displayed:
Figure 25 Selecting the display language and updating the system time
2. Select the display language from the "Language" menu.
3. If necessary, update the time and the date.
– The inverter saves the date entered as the initial start-up date.
4. Press on to conrm the entries.
– The "Country" menu will be displayed:
en
Figure 26 Selecting the country setting
5. Select the country setting.
– Press to conrm your entry. – Depending on the country setting selected, additional menus may be displayed
(see Section 6.2.3).
35
– The "Conrmation" menu is then displayed.
6. Check the data in the "Conrmation" menu.
7. To complete initial start-up, press . – The main menu will then be displayed (see Section 7.4 ). – In the case of commissioning in Italy, after initial start-up the auto test must be
carried out (see Section 6.3).
6�2�3 Country-specic menus
Depending on the country setting, additional menus will be displayed during initial start-up.
Country: Denmark Menu Setting Description
Plant system rating > 13.8 kVA – 30 kVA* The plant system rating is higher than 13.8
> 30 kVA The plant system rating is higher than 30
CosPhi(Pac) - QMCPP Inactive
On
* only available with the SM30HT4
Country: Germany Menu Setting Description
Grid connection Medium voltage The inverter is connected to the medi-
Low voltage The inverter is connected to the low-voltage
System power* > 13.8 kVA – 30 kVA** The plant system rating is higher than 13.8
> 30 kVA The plant system rating is higher than 30
CosPhi(Pac) - QMCPP* Inactive
On
* only available with "Low-voltage" grid connection ** only available with the SM30HT4
kVA and does not exceed 30 kVA .
kVA. External grid monitoring will be used. The "cosφ(Pac)" function is deactivated
(cosφ=1). The "cosφ(Pac)" function is activated.
um-voltage mains.
mains.
kVA and does not exceed 30 kVA .
kVA. External grid monitoring will be used. The "cosφ(Pac)" function is deactivated
(cosφ=1). The "cosφ(Pac)" function is activated.
36
Country: Luxembourg Menu Setting Description
System power > 13.8 kVA – 30 kVA* The plant system rating is higher than 13.8 kVA
> 30 kVA The plant system rating is higher than 30 kVA.
CosPhi(Pac) - QMCPP Inactive
On
* only available with the SM30HT4
and does not exceed 30 kVA.
External grid monitoring will be used. The "cosφ(Pac)" function is deactivated
(cosφ=1). The "cosφ(Pac)" function is activated.

6�3 Auto test

The auto test (only available in the "Italy" country setting) checks the inverter's grid mon­itoring function. The auto test consists of 7 test steps in which the triggering behavior is checked when the voltage and frequency limits are exceeded.
In the auto test the limit value is gradually changed until it reaches the triggering threshold (i.e. the current measured value). If the grid monitoring function is working, the inverter triggers the grid monitoring action. For each step of the test, the graphics display shows the current reading, the trigger value, the trip time and the set limit. During the test of the frequency limits, the activation status of the limit value is also displayed.
The auto test is performed automatically. Following completion of the auto test, the inverter returns to normal operation. If an error occurs or irradiation is too low during the auto test, the auto test is aborted. In this case the message "Auto-test aborted" is shown on the display. The auto tests lasts approximately 5 minutes.
en
Requirements
The auto test should be carried out when there is sufcient solar irradiation, i.e. not
at dusk or when there is extensive cloud cover.
The inverter has been connected to the mains and switched on for at least 10
minutes.
Procedure
1. In the Main Menu, select the "Auto Test" menu.
2. To start the auto test, press .
3. Wait for the display of the successful completion of the auto test:
37
Figure 27 Display after successful auto test
4. Ensure that the inverter resumes normal operation (in this case the status message
"Mains operation" will be shown on the graphics display).

6�4 Settings

Different communication parameters and monitoring functions can be set in the "Set­tings" menu of the graphics display. All settings except the IP mode can also be made using the MaxTalk service software.

6�4�1 Changing parameters

The parameters in the "Settings" menu can be changed as follows:
1. In the Main Menu select the "Settings" menu.
Figure 28 "Settings" menu
2. Press to select the parameter (e.g. "Time").
3. Press to change to the editing mode.
4. Press to select the required number.
38
Figure 29 Selecting the number and changing the value
5. Press to increase the value of the selected number.
6. Press to select the next number.
7. Press to conrm the parameter value.
8. Press to return to the Main Menu.
6�4�2 Setting the display language and system time
The inverter's display language and system time can be changed in the "Settings" menu.
1. Select the "Settings" menu:
Figure 30 Changing the display language and system time
2. Select the parameter and update it:
Parameter Description
Language Selection of the display language: German, English, French, Italian
or Spanish. The display language can be selected independent of the
country setting. Time Date and system time of the inverter Date
en
3. Press to return to the Main Menu.
39
6�4�3 Setting the network parameters
The network parameters can be assigned in the "Settings" menu.
Note
Please take note of the information relating to MaxComm compatibility in Sec­tion 11.3.
Device address
In order to communicate via an RS485 or Ethernet interface, the inverter needs a unique device address on the network.
1. In the "Settings" menu, select the "Device address" parameter.
2. Set the parameter to the required value:
Parameter Description
Device address Address range: 1 to 249
Configuring the Ethernet interface
In addition to the device address, the following settings must be made to communicate via Ethernet:
1. In the Main Menu select the "Network" menu.
2. In the "IP mode", select the required setting:
Setting Description
DHCP client The inverter is a DHCP client and is connected to a network with
Static The inverter is connected to a network with static IP addresses.
DHCP server (factory setting).
40
3. If appropriate, congure the following parameters. These settings are only required in "Static" IP mode (see step 2):
Parameter Description (in brackets: factory settings)
IP IP a ddr e ss ( 19 2 .16 8.1.123)
Gateway (192 .168.1.1) TCP port (1234) DNS1 Domain Name Server 1 (192.168.1.1) DNS2 Domain Name Server 2 (192.168.1.1) Netmask Subnet mask (255.255.255.0)
4. Check whether the Ethernet connection indicator appears on the graphics display (see Section 7.1).
6�4�4 Conguring the status signaling contacts
The two status signaling contacts for the remote monitoring of the inverter can be con­gured in four different ways.
Procedure
1. In the "Settings" menu, select the "Status relay" parameter.
2. Make the required setting:
Setting Description
Off The status signaling contacts are always open.
Grid When the inverter starts mains operation, the status signaling con-
tacts close and remain closed for as long as the inverter feeds into the grid. When a power unit (MPP tracker 1/2 or MPP tracker 3/4) is disconnected from the grid, the respective status signaling contact opens after an adjustable delay time.
Error When a warning, a failure or a device error occurs at a power unit
(MPP tracker 1/2 or MPP tracker 3/4) (error messages, see Section
8.2), the respective status signaling contact closes after the expiry of the adjustable delay time. The status signaling contact opens when the error has been eliminated (factory setting).
On When a power unit (MPP tracker 1/2 or MPP tracker 3/4) switches
on when the DC input voltage is sufciently high, the respectie status signaling contact closes. The status signaling contact opens when the power unit switches off due to insufcient DC input voltage.
3. Select the "Status relay delay" parameter.
4. Adjust the required delay time for the status signaling contacts:
Parameter Description Value range Unit
Status relay delay Delay time of status signaling contact 0 to 99 min
en
6�5 Displaying the conguration
All available operating parameters, standard-specic functions and their parameteriza­tion can be retrieved in the "Conguration" menu. Conguration of the standard-specic functions depends on the country setting selected.
Note
The MaxTalk 2 Pro service and communication software makes it possible for authorized personnel to individually adjust the operating parameters (see Section 12).
41

6�5�1 Procedure

1. In the Main Menu, select the "Conguration" menu.
Figure 31 "Configuration" menu
2. Press to select the parameter:
Entry Description
Country Country setting selected at the time of initial start-up. Grid Grid connection selected during initial start-up (only available
System power Plant rating selected at initial star t-up (only available with
SSF Menu of standard-specic functions and parameters
– The "SSF" menu contans the following sub-menus.
Menu Description
External input Display of external control functions (external shutdown and
Inverter start-up Those functions are displayed which are active before the
Grid operation Those functions are displayed which are active during the
Limitation Those functions are displayed which limit the inverter's output
Reactive power Those functions are displayed that have an impact on the
Reference parameters Display of nominal values and reference values.
with “Germany” country setting).
"Denmark", "Germany" and " Luxembourg" country settings).
external output control).
inverter is connected to the grid (start conditions).
inverter's grid operation (grid monitoring).
values, such as active and reactive power and output current (output limitation).
reactive power taken up or given out by the inverter (reactive power control).
42
3. Press to conrm the selection.
– Section 6.5.2 contains the description of the SSF functions and parameters.
4. Press to return to the Main Menu.
6�5�2 Description of extended functions and parameters
This section contains the description of the functions and parameters available from the "SSF" menu.
External input
Functions and parameters of the "External input" sub-menu:
Function / parameter Description Unit / status EISD Monitoring the N A21, NA22 and NA1 inputs of the
external shutdown.
EISD-ENA EISD function status Disabled/enabled
Inverter start-up
Functions and parameters of the "Inverter start-up" sub-menu:
Function / parameter Description Unit / status PVGIT Checking the insulation resistance of the PV gener-
ator to ground PV GIT-E N A PVGIT function status Disabled/enabled PV GIT-TH R Minimum permissible insulation resistance Ω RCMUT Checking the integrated fault current monitoring ­RCMUT-ENA RCMUT function status Disabled/enabled IST Checking the grid relay IS T-ENA IST function status Disabled/enabled GPT Checking the grid parameters ­GP T- ENA GPT function status Disabled/enabled GP T- MOT Duration of check s GPTVMIN Checking the minimum mains voltage ­ GPTVMIN-ENA Function status of GPT VMIN Disabled/enabled GPTVMIN-THR Minimum permissible mains voltage V GPTVMIN-DLY Trip time s GPTVMAX Checking the maximum mains voltage ­ GPTVMAX-ENA Function status of GPTVMA X Disabled/enabled GP T V M A X-TH R Maximum permissible mains voltage V GP T VMA X-DLY Trip time s GPTFMIN Checking the minimum mains frequency ­ GPTFMIN-ENA Function status of GPTFMIN Disabled/enabled GPTFMIN-THR Minimum permissible mains frequency Hz GPTFMIN-DLY Tr ip time s GPTFMAX Checking the maximum mains frequency ­ GPTFMAX-ENA Function status of GPTFMAX Disabled/enabled GPTFMAX-THR Maximum permissible mains frequency Hz GP TFM A X-DLY Trip time s
-
-
en
43
Grid operation
Functions and parameters of the "Grid operation" sub-menu:
Function / parameter Description Unit / status GVMMIN1 Checking the minimum permissible mains voltage
(limit 1) GVMMIN1-ENA GVMMIN1 function status Disabled/enabled GVMMIN1-THR Limit value V GVMMIN1-DLY Tr ip time s GVMMA X1 Checking the maximum permissible mains voltage
(limit 1) GVMMAX1-ENA GVMMAX1 function status Disabled/enabled GV M MA X1-T H R Limit value V GV MMA X1-DLY Trip ti me s GVMMIN2 Checking the minimum permissible mains voltage
(limit 2) GVMMIN2-ENA GVMMIN2 function status Disabled/enabled GVMMIN2-THR Limit value V GVMMIN2-DLY Tr ip time s GVMMAX2 Checking the maximum permissible mains voltage
(limit 2) GVMMAX2-ENA GVMMAX2 function status Disabled/enabled GV M MA X 2-T H R Limit value V GV MM A X 2- DLY Trip time s GVM10AMA X Checking the maximum permissible average value
for mains voltage over the last 10 minutes GVM10AMAX-ENA GVM10AMAX function status Disabled/enabled GV M10AM A X-THR Limit value V GV M10AMA X-DLY Tri p t ime s GVMT Monitoring for unacceptably high peaks in the
mains voltage. GVMT-ENA GVMT function status Disabled/enabled GFMMIN1 Checking the minimum permissible mains fre-
quency (limit 1) GFMMIN1-ENA GFMMIN1 function status Disabled/enabled GFMMIN1-THR Limit value Hz GFMMIN1-DLY Tr ip time s GFMMA X1 Checking the maximum permissible mains fre-
quency (limit 1) GFMMAX1-ENA GFMMAX1 function status Disabled/enabled GF MMA X1-T H R Limit value Hz GF MMA X1-DLY Tr ip time s
-
-
-
-
V
-
-
-
44
Function / parameter Description Unit / status GFMMIN2 Checking the minimum permissible mains fre-
quency (limit 2) GFMMIN2-ENA GFMMIN2 function status Disabled/enabled GFMMIN2-THR Limit value Hz GFMMIN2-DLY Tr ip time s GFMMAX2 Checking the maximum permissible mains fre-
quency (limit 2) GFMMAX2-ENA GFMMAX 2 function status Disabled/enabled GF MMA X2-T H R Limit value Hz GFMM A X 2- DLY Trip time s AIS Detection of island operation ­AIS-ENA AIS function status Disabled/enabled AI S-DLY Trip time s RBCM Monitoring the continuous leakage current ­RBCM-ENA RBCM function status Disabled/enabled RB CM-TH R Maximum permissible leakage current A RSCM Monitoring the leakage current step value ­RSCM-ENA RSCM function status Disabled/enabled DCCIM Monitoring the DC component in the AC current ­DCCIM-ENA DCCIM function status Disabled/enabled DCCIM-THR Maximum permissible DC component in AC current A DCCIM-DLY Trip time s
-
-
Limitation
Functions and parameters of the "Limitation" sub-menu:
Function / parameter Description Unit / status ACPPL Maximum increase in the active power during grid
connection ACPPL-ENA ACPPL function status Disabled/enabled ACPPL-MGDT Increase % of Pac nom/
ACPPL-INI ACPPL at every start-up Disabled/enabled ACPPL-RCN ACPPL at start-up after grid disconnection caused
by coupler breaker ACPL Limitation of active output power ­AC P L- LM T Limit value W APPL Limitation of the apparent power ­APPL-LMT Limit value VA OCL Limitation of the output current ­OC L- L MT Limit value A
-
min
Disabled/enabled
en
45
Function / parameter Description Unit / status PUL Active power limitation depending on mains voltage -
P U L- EN A PUL function status Disabled/enabled P U L- A V GM O T Average check duration s P U L- V TH R Limit value V P U L- RD N Reduction of active power % of Pac nom/
PUL-RNC Increase to rated output power % of Pac nom/
PFLM2 P(f) mode 2 ­PFLM2-STRTFQ Start frequency Hz PFLM2-RDN Reduction of active power
PFLM2-RNC Increase to rated output power % of Pac nom/
PFLM3 P(f) mode 3 ­PFLM3-STRTFQ Start frequency Hz PFLM3-RDN Reduction of active power
PFLM3-RNC Increase to rated output power % of Pac nom/
PFLM3-UFQTHR Maximum permissible mains frequency Hz PFLM3-LFQTHR Minimum permissible mains frequency Hz PFLM3-UVTHR Maximum permissible mains voltage V PFL M3-LVTHR Minimum permissible mains voltage V PFLM3-MOT Duration of check s PFLM4 P(f) mode 4 ­PFLM4-STRTFQ Start frequency Hz PFLM4-RDN Reduction of active power
PFLM4-RNC Increase to rated output power % of Pac nom/
PFLM4-UFQTHR Maximum permissible mains frequency Hz PFLM4-LFQTHR Minimum permissible mains frequency Hz PFLM4-UVTHR Maximum permissible mains voltage V PFLM4-LVTHR Minimum permissible mains voltage V PFLM4-MOT Duration of check s
min
min
% of PM/Hz
min
% of PM/Hz
min
% of PM/Hz
min
46
Reactive power
Functions and parameters of the "Reactive power" sub-menu:
Function / parameter Description Unit / status QMO-AM Reactive power control 0=OFF QMCQ Reactive power mode "Q" (xed reactive power) -
Function / parameter Description Unit / status
QMCQ-QSV Reactive power value % of Pac nom
QMCQ-VLE Status of the voltage-dependent reactive power
QMCQ-VLI Mains voltage switch on value V QMCQ-VLO Mains voltage switch off value V QMCQ-PLE Status of the active power-dependent reactive
QMCQ-PLI Active power switch on value W QMCQ-PLO Active power switch off value W
QMCPP
QMCPP-PSP1 to PSP10
QMCPP-CPSP1 to CP SP 10
QMCPP-VLE Status of mains voltage-dependent reactive power
QMCPP-VLI Mains voltage switch on value V QMCPP-VLO Mains voltage switch off value V QMQU1 Reactive power mode "Q( Vac) mode 1" ­QMQU1-VSP1 to VSP10 Characteristic values 1 to 10 of mains voltage ( Vac) V QMQU1-CPSP1 to
CP SP 10 QMQU1_DLY Delay time when mains voltage (Vac) changes s QMQU 1-V LE Status of active power-dependent reactive power
QMQU 1-V LI Active power switch on value % of Pac nom QMQU 1-V LO Active power switch off value % of Pac nom QMQU2 Reactive power mode "Q(Vac) mode 2" ­QMQU2-UPQ Upper reactive power value (OEX) % of Pac nom QMQU2-LOQ Lower reactive power value (UEX) % of Pac nom QMQU2-UPVLI Mains voltage switch on value for QMQU2-UPQ V QMQU2-UPVLO Mains voltage switch off value for QMQU2-UPQ V QMQU2-LOVLI Mains voltage switch on value for QMQU2-LOQ V QMQU2-LOVLO Mains voltage switch off value for QMQU2-LOQ V QMQU2-PLE Status of active power-dependent reactive power
QMQU2-PLI Active power switch on value % of Pac nom QMQU2-PLO Active power switch off value % of Pac nom
QMCCP
QMCCP-CPSV
control hysteresis for QMCQ
power control hysteresis for QMCQ
Reactive power mode "cosφ(Pac)"
Characteristic values 1 to 10 of Pac active power % of Pac nom
Characteristic values 1 to 10 of power factor cosφ
control hysteresis for QMCPP
Characteristic values 1 to 10 of reactive power Q % of Pac nom
control hysteresis for QMQU1
control hysteresis for QMQU2
Reactive power mode "cosφ"
cosφ value
[OEX/UEX] Disabled/enabled
Disabled/enabled
-
- [UEX/OEX]
Disabled/enabled
[UEX/OEX]
Disabled/enabled
Disabled/enabled
-
- [UEX/OEX]
en
47
Function / parameter Description Unit / status
QMCCP-VLE Status of mains voltage-dependent reactive power
control hysteresis for QMCCP QMCCP-VLIH Mains voltage switch on value V QMCCP-VLOL Mains voltage switch off value V QMCCP-PLE Status of active power-dependent reactive power
control hysteresis for QMCCP QMCCP-PLI Active power switch on value W QMCCP-PLO Active power switch off value W
Disabled/enabled
-
Grid stabilization
Functions and parameters of the "Grid stabilization" sub-menu:
Function / parameter Description Unit FRT Fault Ride-Through function ­FRT-ENA FRT function status Disabled/enabled FR T-T RV Mains voltage trip value V FRT-RCM Reactive power mode ­FRT-KF K factor ­FR T-T M1 Timer 1 s FR T-T M2 Timer 2 s
Reference parameters
Functions and parameters of the "Reference parameters" sub-menu:
Function / parameter Description Unit NAP Rated output power (Pac nom) -
NAP-VAL Value W NOC Rated output current ­NOC-VAL Value A GCD Coupler breaker switch delay ­GCD-CDLY Trip time s
48

6�6 Displaying measured values

The current measured values of the inverter can be accessed in the “Measured values” menu.
1. In the Main Menu, select the "Measured values" menu.
Figure 32 "Measured values" menu
2. Select a menu item:
Menu item Description
System Power Unit 1 Power Unit 2
3. Press or to scroll through the measured values: – Measured values under "System":
Measured value Description Unit
Vac L1, Vac L2, Vac L3
Iac L1, Iac L2, Iac L3
Pac S Q cos
φ
Frequency
Measured values Measured values of MPP trackers 1 and 2 Measured values of MPP trackers 3 and 4
Phase voltage L1, L2 and L3 V
Output current L1, L2 and L3 A
Output power W Apparent power VA Reactive power (+: overexcited / −: underexcited) var Power factor (OEX: overexcited / UEX: underexcited) ­Mains frequency Hz
en
– Measured values under "Power unit 1":
Measured value Description Unit
Vdc 1, Vdc 2 Idc1, Idc2 Pdc Tempe rat ure
Input voltage at MPP tracker 1 / MPP tracker 2 V Input current at MPP tracker 1 / MPP tracker 2 A Input power (total of MPP trackers 1 and 2) W Cooling element temperature (MPP trackers 1 and 2) °C
49
– Measured values under "Power unit 2":
Measured value Description Unit
Vdc 1, Vdc 2 Idc1, Idc2 Pdc Tempe rat ure
Input voltage at MPP tracker 3 / MPP tracker 4 V Input current at MPP tracker 3 / MPP tracker 4 A Input power (total of MPP trackers 3 and 4) W Cooling element temperature (MPP trackers 3 and 4) °C
4. Press to return to the Main Menu.
Note
The measured inverter values are not suitable for billing purposes or calcu­lating the efciency. The measuring error may amount to up to ±5% depending on the measured value. Only the measured values of a calibrated electricity meter can be relied upon for billing purposes.
MaxTalk measured values
The MaxTalk 2 service software can be used to display, in addition, the following mea­sured values of the inverter:
Measured value Description Unit
Vac 10 min 10 minute mean value of the mains voltage V Iac mean Mean value of output current A Ierr Ground leakage current mA Ierr DC Leakage current mA
50

6�7 Registering for MaxView

Register for the free web-based MaxView application. As well as facilitating an optimum after-sales service, MaxView enables you to display and graphically visualize the yield data of your PV power plant from anywhere.
Note
Frequently asked questions about MaxView and the replies to these can be found on our website at https://maxview.solarmax.com/faq.xhtml.
Procedure
1. Connect the inverter to the internet via the Ethernet interface (see Sections 5.5 and
6.4.3).
2. Enter your registration data in a web browser under https://maxview.solarmax.com.
3. Learn about the various functions of MaxView.

7 Operation

7�1 Graphics display

The graphics display shows the system values, status information, and the inverter’s failure messages. The graphics display can be used to obtain information on the current operating status, accessing the integrated data logger and entering various settings on the inverter.
5
4
1
2
3
Figure 33 Graphics display with the standard "Overview" display
No� Description
1 Graphics display with backlighting 2 Status LED: operating status display (see Section 7.7 ) 3 Function keys (membrane keys) 4 Symbol for Ethernet connection (link display) 5 Symbol for data communication
en
The function keys can be used for navigating within the menu structure:
Symbol Description
Select menu or parameter
Edit parameter
Highlight number (parameter editing) Increase highlighted number / select menu or parameter
Confirm
Cancel
51

7�2 Menu structure

Overview
Statistics
Days
Months
Years
Total
Reset
Status
Main menu
* only for country setting “Italy”
Information
Measured values
System
Power Unit 1
Power Unit 2
Conguration
SSF
External input
Inverter start-up
Grid operation
Limitation
Reactive power
Reference parameter
Auto test*
Settings
Language
Time
Date
Device adress
Network
IP-Mode
IP
Netmask
Gateway
TCP Port
DNS1
DNS2
Status relay
Status relay delay
Figure 34 Menu structure of graphics display
52

7�3 Displaying the operating data overview

The overview shows the inverter's most important operating data. The graphics display automatically switches to the "Overview" if no function button is pressed for 120 seconds.
1. In the Main Menu, select the "Overview" menu.
Figure 35 "Overview" menu
Display Description
19.06.2013 / 11:44:35 Date and system time of inverter (examples) Pac Output power [W] Today Daily yield [kWh] Tot al Total yield since commissioning [kWh] Status
Operating status of inverter (see Section 7.7 )

7�4 Displaying Main Menu

From the Main Menu you can open all menus.
1. In order to switch from "Overview" to the Main Menu, press any function key.
en
Figure 36 Main Menu
2. Press or to select the menu.
3. Press to conrm the selection.
53

7�5 Statistics

The "Statistics" menu can be used for accessing the inverter's data logger. The data logger saves the statistics values of the past 25 years. The daily, monthly, yearly and total statistics can be displayed. All statistics values can be deleted.

7�5�1 Displaying the daily statistics

The daily statistics consist of the statistics values for the last 31 days.
1. In the "Statistics" menu, select the "Day" sub-menu.
Figure 37 Daily statistics
2. Press or to select the day:
Statistics value Description
Yield Daily yield [kWh] Maximum Fed-in maximum power [W] Hours Number of operating hours in the "Mains operation" operating
3. Press to return to the "Statistics" menu.
status
54

7�5� 2 Displaying the monthly statistics

The monthly statistics consist of the statistics values for the last 12 months.
1. In the "Statistics" menu, select the "Month" sub-menu.
Figure 38 Monthly statistics
2. Press or to select the month:
Statistics value Description
Yield Monthly yield [kWh] Maximum Fed-in maximum power [W] Hours Number of operating hours in the "Mains operation" operating
status
3. Press to return to the "Statistics" menu.

7�5� 3 Displaying the annual statistics

The annual statistics consist of the statistics values for the last 25 years.
1. In the "Statistics" menu, select the "Year" sub-menu.
Figure 39 Annual statistics
2. Press or to select the year:
Statistics value Description
Yield Annual yield [kWh] Maximum Fed-in maximum power [W]
Hours
Number of operating hours in the "Mains operation" operating status
en
3. Press to return to the "Statistics" menu.

7�5� 4 Displaying the total statistics

The total statistics consist of the statistics values since commissioning.
1. In the "Statistics" menu, select the "Total" sub-menu.
55
Figure 40 Total statistics
Statistics value Description
Yield Total yield [kWh] Hours Total operating hours in the operating status "Mains
operation"
2. Press to return to the "Statistics" menu.

7�5�5 Deleting the statistics values

The statistics values in the data logger can be deleted.
1. In the "Statistics" menu, select the "Reset" sub-menu.
Figure 41 Resetting the inverter's data logger
Note
Once data are deleted, this cannot be undone!
2. Press to cancel the deletion process.
3. Press to delete all statistics values.
56

7�6 Displaying information

This menu displays information about the inverter. The menu can be used to identify the inverter.
1. In the Main Menu, select the "Information" menu.
Figure 42 "Information" menu
2. Press or to scroll.
Display Description
Device type Inverter type Serial No. Inverter serial number Firmware Firmware version installed in the inverter Status Current operating status Warning Current warning message Commissioning Date of initial start-up Operating hours Total operating hours in mains operation MAC address MAC address of the inverter
3. Press to return to the Main Menu.

7�7 Displaying the operating status of the inverter

The status LED (Figure 33/No. 2) signals the current operating status of the inverter by its different signal colors. The status message, which gives a more detailed description of the operating status, is displayed at the graphics display.
In addition to the status messages, the inverter also displays warnings. Warnings result from device errors or external failures. The inverter continues to feed power into the mains, but it is possible that yield is reduced. Warnings are independent of the oper­ating status and are displayed on the graphics display alternately with the current status message.
en
Status of LED Operating status Description
Off
Flashes green
Green
Flashes orange
Orange
Red
- Inverter is switched off
Booting Inverter is starting up
Mains operation Mains feed-in (normal operation)
-
Failure
Error
Warning no grid disconnection
External failure grid disconnection
Device error grid disconnection
57
Status of LED Operating status Description
Flashes red
Blocked
Inverter is blocked grid disconnection
The "Failure", "Error", and "Blocked" operating status messages, as well as the warn­ings, usually require certain actions to be carried out by the qualied electrician in charge (see Section 8).

7�7�1 "Booting" operating status

Status LED: ashes green
Status message Description
No response The specied power unit (MPP tracker 1 / 2 or MPP tracker 3 / 4)
Irradiation too low The solar irradiation or rather the available output is too low for
Star t-up… The inverter checks the internal hardware and software compo-
Restar t delay The inverter delays connection to the grid (after a disconnection
does not respond. The cause could be insufcient solar irradiation. The inverter uses the available MPP tracker to feed into the grid.
mains operation.
nents before connecting to the mains.
from the grid or when booting).

7�7� 2 "Mains operation" operating status

The status LED lights up green.
Status message Description
Maximum output power The inverter limits the in-feed power to the maximum possible
Mains operation The inverter is in feed mode. Idc limitation The inverter limits the PV generator current to the maximum per-
Iac limitation The inverter limits the output power to the maximum permissible value
Restar t limitation Following an external output limitation the inverter increases the
Frequency limitation The inverter temporarily limits the active power owing to an active
External limitation The inverter's fed-in active power is limited by external output
Temperature limitation The output power is temporarily reduced in order to limit the
value. This may occur if the PV generator is oversized.
missible value. This may occur if the PV generator is designed such that the current at the Maximum Power Point (MPP) exceeds the maximum permissible input current of the inver ter.
(where the PV generator is oversized).
active power with dened progression (Pac progression and/or Soft Start).
frequency-dependent power reduction.
control.
inverter's temperature.
58

7�8 Displaying the operating status of the MPP trackers

Via the "Status" menu it is possible to display the operating status of the MPP trackers and the inverter. The displayed warnings and status messages are described in the Sec­tions 7.7 and 8.2.
1. In the Main Menu, select the "Status" menu.
Figure 43 "Status" menu
Entry Description
System PU1 PU2
2. Press to return to the Main Menu.
Operating status of inverter (see also Section 7.7 ) Operating status of MPP trackers 1 and 2 (Power unit 1) Operating status of MPP trackers 3 and 4 (Power unit 1)
en
59

8 Troubleshooting

8�1 SolarMax Service Center

If you have technical questions or difculties, our Service Center will be happy to help you. To do that we need the following information:
Device typeSerial number (S/N)Installation locationInformation on the current failure (warning, status message, plant documents, etc.).
Contacting the SolarMax Service Center
The contact details of the SolarMax Service Center can be found on the back of this instruction manual.
Sputnik Engineering AG Länggasse 85 CH-2504 Biel/Bienne

8�2 Diagnosis and actions

The following tables describe possible actions for remedying faults. If the actions sug­gested do not correct the fault, please contact the SolarMax Service Center.

8�2�1 General troubleshooting

Problem Cause Actions
The graphics display remains blank
The graphics display only ashes briey.
The DC disconnector is switched off.
The irradiation is too low. Wait until irradiation is high
All DC input conductors (strands) are interrupted.
It is possible that the inver ter is defective.
The irradiation is too low. Wait until irradiation is high
Switch on the DC disconnector.
enough. Check the PV generator and
eliminate the interruption. Contact the SolarMax Service
Center.
enough.
60
8�2�2 Warning messages
The status LED ashes orange.
Warning Cause Actions
Temperature limitation The output power is temporarily
reduced in order to limit the inverter's temperature.
Fan failure A fan is defective or soiled. Contact the SolarMax Service
RTC error Date and time in the RTC (real-
time clock) were reset due to a failure.
Firmware mismatch The rmware versions of the
inverter controllers do not match.
Ensure that the recommended maximum ambient temperature is not exceeded and that the cooling ns are free from dust and dirt.
Center. Set the date and time (see
Section 6.4.2). If this problem occurs frequently, contact the SolarMax Service Center.
Contact the SolarMax Service Center.
en
Flash error An error has occurred in the ash
memor y.
Contact the SolarMax Service Center.
8�2�3 "Failure" operating status
The status LED lights up orange.
Note
MaxTalk can be used to display the last error messages.
Status message Cause Actions
Vdc too high The DC input voltage of the
inverter is too high.
Ierr too high The ground leakage current
has exceeded the permissible RBCM-THR limit value.
Leakage current step The leakage current has exceeded
the permissible RSCM step value.
No mains There is no mains voltage. Check the AC input conductor
Switch of f the DC discon­nector. Check the PV genera­tor’s conguration.
Check the PV generator.
(fuses).
61
Status message Cause Actions
Frequency too high The mains frequency is outside
Frequency too low The mains frequency is outside the
Mains error The inverter detects island mode. If this problem recurs, contact
Vac too high The mains voltage is outside the
Vac too low The mains voltage is outside the
Vac 10 min too high The maximum 10-minute average
DC insulation fault The insulation resistance of the PV
Error ext. input 1 The external grid monitoring
the GFMMA X1-THR, GFM­MAX2-THR or GPTFMA X-THR limit values.
GFMMIN1-THR, GFMMIN2-THR or GPTFMIN-THR limit values.
GV M MA X1-T H R, G V MMA X2-T H R or GPT VMAX-THR limit values.
GVMMIN1-THR, GVMMIN2-THR or GPT VMIN-THR limit values.
value of the mains voltage GVM10AMA X-THR is too high.
generator to ground is too low. Phase and neutral conductors are
inverted.
system has disconnected the inverter from the grid (active sig­nals at the "NA21" and/or "NA22" inputs).
If this problem recurs, contact the grid operator.
the grid operator.
If this problem recurs, contact the grid operator.
Check the PV generator.
Connect the AC input con­ductor as described in Section
5.3. If this problem recurs, contact
the grid operator.
62
8�2�4 "Error" operating status
The status LED lights up red.
Status message Cause Actions
Device error (+ error code) The inverter is defective. Write down the two-digit error
code displayed and contact the SolarMax Service Center.
8�2�5 "Blocked" operating status
The status LED will ash red.
Status message Cause Action
Firmware update The inverter's rmware is being
updated.
None. The inverter automati­cally resumes mains operation once the rmware update is complete.

9 Maintenance

The following maintenance tasks should be carried out at regular intervals:
Check the operating status of the inverter (see Section 7.7 ).Check that the ventilation inlet and outlet (see Figure 2) are not blocked. Clean the graphics display with a damp cloth. Do not use harsh or abrasive cleansing
agents.
Check the inverter for external damage. Report any such damage to the relevant
qualied electrician.
en
63

10 Decommissioning

O

10�1 Instructions for inverter replacement

When replacing the inverter, note the following:
Before replacing the inverter, write down the total yield. The procedure for viewing
the total yield is described in Section 7.5.4.

10�2 Dismounting the inverter

The inverter may only be dismounted by qualied electricians.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage. After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.
Before starting to dismount the inverter, the inverter must be fully discon-
nected in accordance with the procedure described in this chapter.
WARNING! Risk of injury from electric arc!
Dangerous electric arcs could occur when removing live DC input conductors.
Switch off the DC disconnector before removing the DC input
conductors.
64
Procedure
1. Disconnect the AC power supply to the inverter (switch off the external AC circuit breaker).
– The "No grid" status message is shown on the inverter.
2. Switch off the DC disconnector at the inverter.
Figure 44 Switching off the DC disconnector
3. Use a size 2 screwdriver to remove the locking clips on the DC plugs.
4. Pull out the DC input conductors to fully disconnect the inverter from the PV generator.
5. Remove the cover of the inverter as described in Section 5.1.
6. Use a suitable voltage detector to check that all terminals are free from voltage.
– When all terminals are free from voltage you can remove the AC input conductor
and all communication cables.
7. Fit the cover of the inverter.
8. Remove the two safety brackets.
CAUTION! Risk of injury - the inverter is heavy!
The inverter weighs approx. 70 kg.
Never dismount the inverter on your own.
9. When dismounting the inverter, ask a second person to help.

10�3 Disposing of the inverter

Dispose of the inverter as indicated by the local waste disposal regulations. You can also return the inverter, at your own cost, to Sputnik Engineering AG for professional disposal. The contact details of the SolarMax Service Center can be found on the back of this instruction manual.
en
65

11 Technical data

Input parameters
Output parameters Rated output power 30 000 W 3 2 000 W
Efciency Maximum efciency 98 % 98 %
Power input Own consumption, night 0 VA
Environment Protection class IP65
MPP voltage range
Minimum DC voltage 250 V 250 V
Maximum DC voltage 1 0 00 V 1 000 V
Maximum DC current 4 x 18 A 4 x 18 A
Number of MPP trackers 4 4
Number of string connections 4 x 2 4 x 2
Connection type Wieland PST40i1 (identical to MC 4)
Overvoltage category 2
Maximum apparent output power
Maximum AC current 3 x 44 A 3 x 47 A
Nominal mains voltage / range 230 / 184 to 276 V
Nominal mains frequency / range 50 / 45 to 55 Hz
Power factor cosφ
Distor tion factor at rated output power
Connection type Screw terminal
Grid connection Three-phase (L1 / L2 / L3 / N / PE)
Overvoltage category 3
Protection class
Europ. efciency 97.5 % 9 7. 5 %
Ambient temperature range (for rated power output)
Max. operating level above sea level
Relative humidity 0 to 98 % (without condensation)
Environmental category In the open
Suitable for wet rooms Yes
Level of pollution 3
1)
SM30 HT4 SM32HT4
430 to 850 V 460 to 850 V
30 00 0 VA 32 000 VA
Adjustable from 0.8 overexcited to 0.8 under-
excited
< 3 %
I
−20 to +60 °C (−20 to +4 5 °C)
2000 m
66
SM30 HT4 SM32HT4
Components Display Graphics display with backlighting and status
LED
Inverter topology Two-stage, without transformer
DC disconnector Integrated
Data logger Energy yields, peak output and operating
duration of the last 31 days, 12 months, 10 years
/ output curves of the last 7 days
Fault current monitoring Internal, AC/DC-sensitive
Casing / cover Aluminum
Components DC surge arrester Class C ( VDE 0 675- 6) and type 2 (EN 61643-11)
AC surge arrester Class D (VD E 0675-6) and type 3 (EN 61643-11)
Standards and guidelines
CE-compliant
EMC EN 61000-3-11 / EN 61000-3-12 /
Yes
2)
EN 61000 -6-2 / EN 61000-6-3
Grid connection VDE-AR-N 4105 / VDE 0126-1-1 A1:2012 / BDEW
MS Directive / G59 /3 / CEI 0-21 / CEI 0-16 /
PPC Guide / C10/11 / EN 50438
Device safety IE C 6 2109-1/-2
Interfaces Data communication RS4 85 (R J45 and terminals) / Ethernet (RJ45)
Status signaling contact Open / close device (terminals)
Connection to external grid
Yes (terminals)
monitoring
Weight and dimensions
Weight 70 kg 70 kg
Dimensions (W x H x D) 84 0 x 580 x 380 mm
Warranty Standard 5 years / ex tension to 10, 15, 20 or 25
years possible
1) for rated output power
2) the complete conformity declaration can be found on our website at ww w.solarmax.com
en
67
11�1 Efciency curve
125
100
98
96
94
92
Efciency η [%]
90
88
86
UDC=460 V UDC=580 V UDC=720 V
(460 V ) = 97.0 %
η
Euro
(580 V ) = 97.5 %
η
Euro
η
(720 V ) = 97.5%
Euro
84 82
80
0 10 20 30 40 50 60 70 80 90 100
Rated output power [%]
Figure 45 Efficiency curve - SolarMax HT series

11�2 Temperature-dependent output reduction

When the ambient temperature is too high, the inverter reduces its output as illustrated in Figure 46 (power derating).
100
68
75
50
Output Pac/Pac nom [%]
25
0
−20 −10 0 10 20 30 40 45 50 60
Ambient temperature [°C]
Figure 46 Power derating - SolarMax HT series

11�3 MaxComm compatibility

When establishing networks for the purpose of monitoring the plant, the MaxComm com­patibility of the inverters must be taken into consideration. The compatibility depends on the type of connection and the network (individual device or gateway device in a MaxComm network).
The "Static" and "DHCP client" conguration options of the Ethernet interface can be set at the inverter's graphics display, see Section 6.4.3.
Individual device Gateway device Ethernet RS485 Ethernet
Max Web xp Ma xTalk 2 MaxTalk 2 rmware
update MaxView
compatible / - not compatible
Static DHCP client Static DHCP client
-
- - -
- - -
-
-
11�4 Country-specic settings
The factory’s default settings for different countries can be viewed in the technical infor­mation “SSF - Standard specic functions and parameters”. This document can be down­loaded from our website at: www.solarmax.com; Downloads/String inverters/HT series.
en
69

12 Accessories and options

Accessory/option Description
MaxView Free web-based application with various functions for remote call-up,
graphics visualization and export of yield data.
Max Web xp MaxWebxp is a data logger, monitoring unit, and web server in one.
Ma xTalk Free communication and service software for local monitoring of the
MaxTalk Pro Professional version of MaxTalk for the conguration of inverters.
MaxMonitoring Using the free MaxMonitoring software you can display the perfor-
MaxDesign Free software for determining the size of PV power plants.
Together with the MaxWeb portal, MaxWebxp is the ideal pair for monitoring the plant.
PV power plant.
The "SolarMax HT series parameter conguration using MaxTalk 2 Pro" operating manual can be downloaded from our website at www. solarmax.com ("Downloads" area).
mance data of your PV power plant at any time from home. MaxMon­itoring is available for PC, MacOS and Linux and also as an app for Android and iOS.
You can nd further information on our website at www.solarmax.com.
70

13 Warranty

Sputnik Engineering AG (hereafter SPUTNIK) guarantees full function and lack of defects of its technical devices for a warranty period as specified below for each type of device. Such warranty period can be extended by means of a warranty extension, subject to the conditions named below.
This manufacturer’s warranty exists next to the seller’s warranty (if any) as prescribed by law. As far as identical with regards to the content, the rights under this manufacturer’s warranty supersede any rights under the seller’s warranty. Please contact the seller with regard to any claims based on the seller’s warranty.
1� Warranty Period (Basic)
Central inverters and accessories: 24 months from the date of purchase, but at maximum 30
months after dispatch of the device by SPUTNIK.
String inverters: 60 months from the date of purchase, but at maximum 72 months after dis-
patch of the device by SPUTNIK.
If in individual cases SPUTNIK has agreed in writing to a different warranty period, such arrange­ment supersedes the above provisions.
2� Scope of Manufacturer’s Warranty
In case of defect or malfunction of a device within the manufacturer’s warranty period, and upon fulfillment of the conditions for warranty claims named hereafter, the device will be repaired or replaced by SPUTNIK-service personnel within a reasonable time, in either case free of charge, unless this is impossible or disproportionate. SPUTNIK may decide at its own discretion whether a device will be repaired or replaced.
Replacement: E xchange of device free of charge. SPUTNIK’s separate conditions for exchange
of devices apply: This warranty covers the free delivery of an equivalent replacement device. Further, your installer is entitled to claim a flat rate compensation for the replacement work from SPUTNIK. Please do not hesitate to ask us about the current amount of such flat rate compensation.
Repair: Repair of device free of charge. This warranty covers costs for material, work and travel
by SPUTNIK personnel or by personnel authorized by SPUTNIK.
Please be aware that the per formances of SPUTNIK under this warranty are only free of charge in countries approved by SPUTNIK. Please contact your seller for details. A current list of approved countries can be found on our homepage. Repair and replacement outside of the approved countries are only possible after prior consultation of and approval by SPUTNIK. In such case, travel and shipment costs are borne by the customer.
Any further claims, especially claims for compensation of damages resulting directly or indirectly from the defect or claims for replacement of further costs in connection with the installation and removal of devices or claims for loss of profits are not covered by this warranty.
en
71
3� Extent of Repair and Replacement
SPUTNIK will maintain repair material and stock of each type of device during the warranty period only at its own reasonable discretion. In case repair materials for a certain type of inverter and/or an identical replacement device are not in stock anymore, the following applies:
SPUTNIK is allowed to replace the defective inverter with a comparable device of the same or
superior per formance. The costs (time and material) for technical adjustments necessary for the installation of such comparable devices are covered by this warranty only up to a limited amount; any flat rate compensation owed by SPUTNIK for the replacement is deductible. Please do not hesitate to ask us about the currently applicable amount. The exchange and connection of peripheral devices due to possible non-compatibility with the replacement device or other necessary adjustments to the surrounding installations of the device (including power lines, ventilation and safety installations) are not covered by this warranty. However, SPUTNIK shall within the bounds of reasonability do its best to minimize the effort of such adaptation work.
In case repair materials are not available with reasonable efforts anymore, SPU TNIK is allowed
to replace the inverter, subject to the conditions mentioned in the paragraph above.
4� Warranty Period in Case of Repair/Replacement
In case of repair or replacement of devices under this warranty, the repaired respectively replaced device will inherit the remaining warranty time of the original device.
5� Exclusion of Warranty
Especially in the following cases, this manufacturer’s warranty does not apply:
Transport damage;
Technical intrusions, modifications or repairs of the devices not authorized by SPUTNIK;
Use of devices for purposes they are not intended for, incorrect or unreasonable manipulation,
incorrect or unreasonable installation;
Failure to observe the manufacturer’s operating, installation and maintenance directions;
Inadequate environmental conditions (e.g. insufficient ventilation of the device; humidity etc.);
Superior force (e.g. lightning strike, overvoltage, floods, fire, etc.).
72
6� Handling of Warranty Cases
For the processing of warranty cases, use of SPT UNIK’s hotline is mandatory. The handling of war­ranty cases must take place in accordance with the instructions provided by the hotline. The hotline number for your country can be found on SPUTNIK’s homepage. Please hold the serial number, article description, a short description of the defect and the purchase receipt ready for transmission to the hotline.
Any repair action taken by the buyer or third parties without authorization by SPU TNIK will not be compensated.
In case these terms on the handling of warranty cases are not respected, SPUTNIK may refuse its warranty performances.
7� Suspension of Warranty
Sputnik reserves its right to suspend this manufacturer’s warranty temporarily or definitely in case a specific installation does not allow a correct functioning of the inverters (e.g. in case of one of the circumstances listed in cipher 5).
The suspension of the warranty can be lifted upon approval by SPUTNIK. Such approval must be issued by SPUTNIK in writing, confirming that the warranty has again become effective.
8� Warranty Extension
The warranty period can be extended through purchase of a warranty extension within the time limits mentioned hereafter. For certain types of devices, such warranty extensions can also be purchased only for a limited scope of warranty performances. The purchase of a warranty extension will be confirmed by SPUTNIK in form of a warranty certificate (including serial number of affected product). In case of replacement of a device, the serial number in such warranty certificate remains unchanged, without any influence on the validity of the warranty extension.
a) Time limits String inver ters: The extension of the basic warranty can be ordered within 60 months after pur­chase, but the latest within 72 months after dispatch of the device by SPUTNIK. Central Inverters: The extension of the basic warranty can be ordered within 3 months af ter pur­chase, but the latest within 12 months after dispatch by SPUTNIK.
b) Extent Full warranty extension – FULL (available for central inverters and string inverters): A full warranty extension includes all the warranty performances as described in the manufacturer’s basic warranty terms.
Limited warranty extension– LIMITED (available only for central inver ters): A limited warranty extension covers only the costs for the material required for the repair. The costs for travelling, labor and other expenses are not covered and will be invoiced on a time and expenses basis by SPUTNIK.
c) Effectiveness of Warranty Extension It is a mandatory requirement for the warranty extension to provide the completely filled out appli­cation form to SPUTNIK. The warranty extension becomes effective only after written confirmation and provision of the warranty cer tificate by SPUTNIK.
en
9� After Expiration of Warranty Period
The costs for repair or replacement of devices after expiration of the warranty period are invoiced by SPUTNIK on a time and material basis. SPUTNIK will maintain repair and replacement capabilities beyond the warranty time only at its own discretion.
10� Applicable Law, Jurisdiction
Only Swiss Law applies. The exclusive place of jurisdiction lies in Biel/ Bienne, Switzerland. (v 2013/0 5 )
73
SolarMax Service Center:
hotline@solarmax.com
www.solarmax.com/service
2014/ 05 en
Loading...