This instruction manual is applicable to the following SolarMax inverters:
TypeItem No�
SM 30H T410 006 012
SM 32H T410 006 011
1�2 Target groups
This instruction manual is intended for the operator of the plant and the installer of the
PV power plant.
The instructions in chapters 5, 6�2, 8 (troubleshooting actions) and 10 may only be car-
ried out by trained electricians (e.g. electricians, electric systems technicians, electrical
mechanics, industrial electronics technicians).
The instructions in chapter 4 should only be carried out by specialist transport personnel.
1�3 Where to keep this manual
The plant operator must ensure that this instruction manual is available to the relevant
persons at all times. If this original document is lost, an up-to-date version of this instruction manual can be downloaded from our website at any time (www.solarmax.com).
1�4 Symbols used
The following safety instructions and general information are used within this instruction
manual.
DANGER!
Non-observance of these safety instructions results in serious injuries or
death.
en
WARNING!
Non-observance of these safety instructions may result in serious injuries or
death.
CAUTION!
Non-observance of these safety instructions may result in minor or extensive
injuries.
5
ATTENTION!
Non-observance of these safety instructions may result in material damage.
Note
Notes contain additional information or facilitate operation of the inverter.
2 Safety
2�1 Intended use
SolarMax HT series inverters are designed exclusively for the conversion of the direct current generated by PV modules into alternating current which conforms to the parameters
of the public grid. Any other use is contrary to the intended use.
Inverters of the HT series may only be used in combination with PV modules which comply
with the IEC 61730 standard. Inverters of the HT series may only be connected to Class
II PV generators.
2�2 Safety instructions
DANGER!
Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC
voltage.
Make sure that all electrical input conductors to the inverter are de-ener-
gized before starting any work on the inverter or the input conductors.
DANGER!
Fatal electric shock hazard!
Components within the inverter are charged with a high voltage.
Never open the inverter while it is in operation.
WARNING!
Risk of injury from electric arc!
Removing the DC connectors when live can lead to dangerous electric arcs.
Switch off the DC disconnector at the inverter before removing the DC
connectors.
6
2�3 Symbols on inverter
SymbolDescription
The DC disconnector is switched off (the contacts are open).
O
I
The DC disconnector is switched on (the contacts are closed).
+ −
Positive or negative pole of input voltage (DC)
Risk of death from high voltages! Only qualied electricians may
perform work on the inver ter.
Careful - hot surfaces!
en
5 min
Risk of death due to high voltages in the inverter! De-energize the
inverter. Proceed to wait for 5 minutes before opening the inverter.
Only qualied electricians may perform work on the inverter.
Operating instructions - Please read and follow the instructions
supplied with the inverter. Do not remove any symbols on the inverter.
Replace any damaged symbols.
CE marking - The inverter complies with the requirements of the
European EMC Directive 2004/108/EC and the Low Voltage Directive
2006/95/EC (see Section 11).
GS marking - The inverter complies with the relevant requirements of
the German Product Safety Act.
Do not dispose of the inverter and its accessory components in the
household waste.
7
3 Description
3�1 Identication
The inverter can be identied on the basis of the information provided on the nameplate
(see Section 3.5).
3�2 Functionality
Automatic operation
Inverter operation is completely automatic and depends on the available output of the PV
generator. If there is enough power, the inverter starts mains operation and feeds into
the power grid. If there is not enough power available from the PV generator, the inverter
disconnects from the grid and shuts down.
Operation
The graphics display with three function keys allows convenient inverter operation and
reading of all important operating data. The graphics display is only switched on when the
DC input voltage is high enough.
The DC disconnector can be used to switch the PV generator on or off at any time. The
components of the inverter remain live even when the DC disconnector is switched off.
Remote monitoring
For the purpose of monitoring the PV plant remotely, Ethernet and RS485 interfaces are
provided. The inverter can be directly connected to the internet via Ethernet (MaxView).
The inverter is equipped with status signaling contacts for displaying the operating status
remotely.
Extended functions
The inverter has functions for grid monitoring, limitation of output and reactive power
control. These can be congured with additional software.
Remote controlled output limitation and reactive power control can be achieved using the
MaxWebxp and MaxRemote accessory components.
Ventilation
The inverter is air cooled. Fans draw in the air through the air inlet on the right-hand side
of the inverter. Then the air is conducted across the internal cooling elements. The air
outlet is on the left-hand side of the inverter.
8
3�3 Safety installations
Surge protection
The inverter is tted with surge arresters (varistors) at its input and output. Each MPP
tracker (plus and minus connections) is equipped with a surge arrester. On the AC side,
each mains phase has a surge arrester (for details on the surge arresters tted, see
Section 11).
When designing the PV system, it may be necessary to provide additional external lightning protection.
Fault current monitoring
The inverter has an AC/DC sensitive leakage current sensor which monitors the stray
currents occurring on the generator side. This sensor can distinguish between the operational capacitive stray currents (caused by capacities of the PV modules to ground) and
leakage currents (caused by touching a pole of the PV generator). If the inverter detects
an excess in the permissible leakage or stray currents, it will disconnect from the grid.
Functions for current and output limitation
When it is needed, the inverter limits the DC feed-in current, the output power and the
output current.
Temperature limitation
At ambient temperatures of more than 45°C the equipment temperature may reach more
than 80°C. In such cases, the maximum in-feed power is temporarily reduced. When the
equipment temperature rises above 85°C, the inverter disconnects from the grid.
10"COMM" multiple cable gland (for communication cables)
11DC disconnector (can be locked with a padlock)
12DC terminals
12
3�6 Block diagram
AC output
K2
K1
DC
Inverter
DC
Booster 1
U
K5
Ethernet
EMC lter
AC measurementAC measurement
FanFan
LC lter
AC
Inverter controlInverter control
Booster control
DC
DC
Booster 2
DC
Control unit MPP tracker 1/2
Control unit MPP tracker 3/4
DC measurement
DC measurement
RS485
Booster control
DC
RS485
Status signalling contact
MPP tracker 1/2
DC
Booster 3
External shutdown
Status signalling contact
MPP tracker 3/4
K4
K3
LC lter
AC
DC
Inverter
DC
DC
Booster 4
en
Communication module
Graphics display
EMC lter
U
DC input
MPP tracker 1
Figure 3 Block diagram
EMC lter
EMC lter
U
DC input
MPP tracker 2
EMC lter
U
DC input
MPP tracker 3
EMC lter
U
DC input
MPP tracker 4
I
0
DC disconnector Q1
13
4 Installation
4�1 Transporting and storing inverters
Make sure that the ambient conditions during transportation and storage are within the
specied limits (for details see Section 11).
4�2 Lifting the inverter
The inverter is tted with handles (Figure 2/Pos. 7), which can be used to lift the inverter
from the packaging by hand.
CAUTION!
Risk of injury - the inverter is heavy!
The inverter weighs approx. 70 kg.
Do not mount the inverter without the help of a second person.
14
4�3 Checking the delivery for completeness
Check the contents of the delivered package for completeness and possible damage. In
the case of an inadequate delivery, please contact your dealer or the SolarMax Service
Center.
SolarMax HT-Serie
17
30HT4 / 32HT4
1
Gerätedokumentation
2
3
4
5
6
7
en
16
15
14
Figure 4 Content of delivery
No�Quantity Description
11Inverter
21Instruction manual
316Locking clip (for locking the DC connector)
42Safety brackets (for installation of inverter)
516-pole connector (for connection of status signaling contacts)
614-pole connector (RS485 connection)
713-pole connector (connection of external grid monitoring)
8
9
10
11
12
13
15
No�Quantity Description
83Locking pins (for multiple cable gland)
91M5 toothed washer (connection of second protective conductor)
101M5 cable shoe (connection of second protective conductor)
111M5 circlip (connection of second protective conductor)
121M5 washer (connection of second protective conductor)
131M5 nut (connection of second protective conductor)
14810 x 50 wall plugs (mounting of inverter)
158M6 x 18 washers (mounting of inver ter)
1686 x 60 Torx pan head screws (mounting of inverter)
171Mounting plate (mounting of inverter)
4�4 Selecting the installation location
DANGER!
Fatal re or explosion hazard!
The inverter is an electrical device with heat generation and the possibility of
sparking.
Install the inverter in an environment that is free of ammable gases and
uids.
Never install the inverter near combustible materials. The installation sub-
strate must be non-combustible.
Follow the local re safety regulations.
CAUTION!
Risk of injury - the inverter is heavy!
The inverter weighs approx. 70 kg.
The installation substrate must have sufcient structural strength.
Location and installation conditions
The ambient conditions are specied in the specications, see Section 11.
Select a dry location protected from water and snow.
Do not expose the inverter to direct sunlight.
Install the inverter in an easily accessible location, so that maintenance work can be
carried out easily.
When mounting the unit observe the following minimum distances:
16
50
[cm]
50
en
5050
50
100
50
50
Figure 5 Minimum installation distances
Do not mount the inverter at an angle or on its side:
Figure 6 Unacceptable mounting positions
Appropriate cooling of the inverter can only take place when the ventilation openings
on the sides are kept clear.
The ambient air around the inverter must be free from dust, salt and ammonium
vapors.
The location must meet the requirements regarding emissions and freedom from
electromagnetic interference.
17
4�5 Mounting the inverter
Install the inverter to a vertical wall using the mounting plate. The mounting plate and the
xing material are included in the delivery.
Fixing the mounting plate
1. Use the mounting plate as a drilling template.
2. Use a spirit level to align the mounting plate horizontally.
3. Mark 6 places for drilling:
89
205
553
23
226
25
574
226
2525
23
230
12 x ø8.5
[mm]
Figure 7 Dimensions of mounting plate
4. Drill the Ø10 x 60 mm holes.
5. Fix the mounting plate.
18
– Installation sequence: 10 x 50 wall plugs, mounting plate, M6 washers, 6 x 60 Torx
pan head screws.
Figure 8 Fixing the mounting plate
Engage the inverter in the mounting plate
6. With the help of a second person, engage the inverter in the seats of the mounting
plate:
en
Figure 9 Engaging the inverter in the mounting plate
19
Securing the inverter
7. Drill two Ø10 x 60 mm holes.
8. Secure the inverter with the 2 safety brackets (included in the delivery).
– Installation sequence: 10 x 50 wall plugs, safety bracket, M6 washers, 6 x 60 Torx
pan head screws.
Figure 10 Securing the inverter
Note
The safety brackets can also be tted laterally.
20
5 Electrical connection
The DC terminals are freely accessible from the outside of the inverter. The AC terminals
and all communication terminals are inside the inverter.
The inverter may only be installed by qualied electricians.
5�1 Removing the cover
The AC and communication terminals are accessible when the cover is removed.
Procedure
1. Disconnect the AC power supply to the inverter.
2. Disconnect all control cables connected to the inverter (status relays, external grid
monitoring and shut-down).
3. Switch off the DC disconnector at the inverter.
DANGER!
Fatal electric shock hazard!
Components within the inverter are charged with a high voltage. After the
inverter has been disconnected, high residual voltages remain in the inverter
for approx. 5 minutes.
Wait 5 minutes until the voltages inside the inverter have reduced before
removing the cover and carrying out connection work.
4. Release the M6 screws (Figure 11/No. 1) from the cover.
5. Remove the cover (Figure 11/No. 2).
O
en
5 min
Figure 11 Removing the cover
2
1
21
5�2 Connection area
All terminals and cable glands of the inverter are shown in Figure 12.
8
9
10
7
6
5
4
3
2
1
Figure 12 Connection area
No�Description
1DC terminals (MC4 compatible plug-in terminals)
2"COMM" multiple cable gland for communication cables (network connections, status
signaling contacts, external shutdown)
3"AC mains" cable gland for the AC input conductor
4M5 threaded "PE" bolt for the connection of the second protective conductor (optional)
5AC terminals (screw terminals)
6External shutdown (plug-in terminal)
7Status signaling contacts (plug-in terminal)
8RS485 (plug-in terminal)
9Ethernet and RS485 communication sockets (RJ45)
10Cable grips for restraining the cable (for the communication cables)
22
5�3 Connecting the inverter to the mains
DANGER!
Fatal electric shock hazard!
Make sure the AC input conductor is not live during connection work.
Connection conditions
Comply with the connection conditions set by the grid operator.
M40 cable gland; suitable for cable Ø: 24 to 33 mm
Connection type: screw terminals (UWV 25)
Permissible conductor cross sections:
– exible conductor (with or without conductor sleeve): max. 25 mm
– rigid conductors: max. 35 mm
The protective conductor of the AC input conductor should be cut at least 30 mm
2
longer than the other conductors.
The AC input conductor must be fused. Minimum conductor cross sections and sug-
gested mains fuses:
Minimum conductor cross sections30HT432HT4
Phases L1, L2, L310 mm
Neutral conductor N4 mm
Protective conductor PE10 mm
Recommended mains fuses30HT432HT4
Nominal current63 A63 A
CharacteristicsCC
2
2
2
10 mm
4 mm
10 mm
2
2
2
2
en
Make sure the ambient temperatures for the mains fuses specied by the producer
are not exceeded.
WARNING!
Fatal fire risk!
Provide separate fuses for each inverter.
Do not connect any loads between the inverter and the mains fuse.
If you use external residual current devices (RCDs), use the type B RCDs with a nom-
inal fault current of 100 mA. For PV plants with large stray current capacities, the
RCDs to be used should have a nominal fault current capacity of 300 mA.
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the AC input conductor through the cable gland.
23
3. Cut back the insulation of the conductor by 19 mm.
4 … 4.5 Nm
M5
4. Connect the wires in the following sequence:
– the protective conductor to the "PE" terminal
– the neutral conductor to the "N" terminal
– the mains phases to the terminals "L1", "L2", and "L3".
– Tightening torque: 4 to 4.5 Nm
L3PE
L1
L2
N
19 mm
Figure 13 AC connection
5. Check the cable connections for rm seating.
6. Tighten the M40 cable gland.
7. Check the cable strain relief.
8. Connect the second protective conductor (optional):
– Installation sequence (see Figure 14): M5 toothed washer (No. 1), cable shoe (No.
– all xing elements are included in the delivery.
24
1
2
3
4
5
Figure 14 Connecting the second protective conductor (optional)
9. Close the inverter by tightening the cover.
5�4 Connecting the inverter to the PV generator
The HT series inverters have four independent MPP trackers which can be used to connect strands with different characteristics, such as orientation, size and module type.
Each MPP tracker can be tted with two strands as standard.
en
1
3
Figure 15 Terminals of the MPP trackers 1 to 4
2
4
No�MPP tracker
11
22
33
44
25
Connection conditions
Type of connection: Wieland PST40i1C plug connector
Only use Wieland PST40i1C connectors (not included in the delivery).
Maximum DC input current per MPP tracker: 18 A
Maximum DC input voltage: 1 000 V
Select conductor cross sections to suit the plant conguration.
The maximum short-circuit current (Iscpv) is 25 A.
DANGER!
Fatal re risk!
High return currents can cause a re risk for the PV generator.
When Y plugs are used in order to connect more strands than specied,
each DC input conductor must be protected individually against dangerous return currents.
Parallel connection of the MPP trackers is not permitted:
26
Figure 16 Unacceptable parallel connection of MPP trackers
Do not t a ground connection to either the negative terminal or the positive terminal
of the PV generator.
Procedure
1. Make sure that the DC disconnector is switched off.
2. Disconnect the AC power supply to the inverter.
3. Connect the DC input conductors that have been pre-tted with the connector.
4. Use the locking clips (included in the delivery) to secure the plug connectors.
DC−
DC+
DC+
DC−
Figure 17 Connecting the strands
Close off any unused DC plug connectors�
Any unused DC plug connectors must be closed off to ensure that the installation complies with the IP65 protection rating requirements. Please use the following closing parts
made by Wieland (www.wieland-electric.com):
for plug component: order number 05.566.6380.0
for socket component: order number 05.566.6480.0
en
5�5 Network connections (optional)
The inverter has one Ethernet and three RS485 interfaces. These can be used to connect
the inverter to the internet, a MaxComm network or other networks. The RS485 interfaces are connected in parallel inside the unit. The connection can be made with RJ45
plug connectors or screw terminals.
27
12
A
GND
15 V
B
3
4
Figure 18 Network connections
No�Description
1RJ45 socket RS485
2RS485 plug connection
BBus B
15 V15 V network input
GNDNetwork input ground connection
ABus A
3RJ45 socket RS485
4RJ45 socket Ethernet
Note
You will nd further details about data communication in the technical information "MaxComm network". You can download this document from our website at: www.solarmax.com; Downloads/Data Communication/MaxComm.
28
Connection conditions
Connection types: 3 x RJ45 sockets / 4-pole plug (included in the delivery)
Suitable conductor cross sections (plug connector): 0.25 to 2.5 mm
Multiple cable gland; usable cable Ø: 5.5 to 7.0 mm
You should use shielded network cables (cat. 5)
2
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the network cables through the multiple cable gland.
Note
The RJ45 connectors can be pulled through the multiple cable gland.
3. Plug the network cables into the RJ45 sockets (Figure 19/No.1) and check that the
connection is locked.
4. RS485 terminal connection (Figure 19/No.2): connect the RS485 network cable as
follows:
– Wire stripping length: 7 mm
– Tightening torque: 0.5 to 0.6 Nm
1
2
3
M3
0.5 … 0.6 Nm
7 mm
Figure 19 Network connection
5. Use cable ties to attach the cables to the housing grips (Figure 19/No. 3).
6. Close off the unused apertures in the multiple cable glands using the locking pins (No.
8 in Section 4.3).
7. Tighten the multiple cable gland (wrench size: 34 mm).
8. Fit the cover of the inverter.
en
5�6 Connecting status signaling contacts (optional)
The congurable status signaling contacts are used for the remote monitoring of the
inverter. Both power units (MPP tracker 1/2 and MPP tracker 3/4) can be monitored individually using a status signaling contact. When the external deactivation is used (see
Section 5.7) the status signaling contacts cannot be used.
The status signaling contacts can be congured, see Section 6.4.4.
29
NC1
COM1
NO1
NC2
COM2
NO2
Figure 20 Status signaling contacts
Status signaling contact MPP tracker 1 and 2
NC1Opens in the case of an error
COM1Common 1
NO1Closes in the case of an error
Status signaling contact MPP tracker 3 and 4
NC2Opens in the case of an error
COM2Common 2
NO2Closes in the case of an error
Connection conditions
Connection type: 6-pole connector (included in the delivery)
Connectable conductor cross sections: min. 0.25 mm
Multiple cable gland; usable cable Ø: 5.5 to 7.0 mm
Max. switching voltage: 250 VAC / 30 VDC
Max. switching current: 1.5 A (no internal fuse present)
Max. cable length: max. 50 m
2
/ max. 2.5 mm
2
30
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the cable through the multiple cable gland.
3. Connect the control lines to the 6-pole connector (Figure 21/No. 1) as follows:
– Wire stripping length: 7 mm
– Tightening torque: 0.5 to 0.6 Nm
0.5 … 0.6 Nm
M3
1
2
en
3
Figure 21 Connecting the status signaling contacts
4. Plug in the 6-pole connector.
5. Plug in the 3-pole connector (Figure 21/No.2) in order to cover the open contacts.
6. Use cable ties to fasten the cables to the housing grips (Figure 21/No. 3).
7. Close off any unused apertures in the multiple cable gland using the locking pins (see
No. 8 in Section 4.3).
8. Tighten the multiple cable gland (wrench size: 34 mm).
9. Fit the cover of the inverter.
7 mm
5�7 External shutdown (optional)
This interface can be used to connect the inverter to an external grid monitoring system
which can disconnect the inverter from the mains grid from a remote location when this
is needed.
1
Figure 22 External shutdown terminals
NA21
NA22
NA1
31
ContactDescription
NA21Control line terminal / external shutdown of MPP trackers 1 and 2
NA22Control line terminal / external shutdown of MPP trackers 3 and 4
NA1Neutral conductor terminal
For as long as the signal (phase voltage) of the external grid monitoring system is live
on the NA21 / NA22 contacts, the respective MPP trackers can feed into the mains grid.
When the signal stops, the K1/K3 or K3/K4 (see Section 3.6) grid relays of the inverter are
opened. This immediately disconnects the inverter from the grid.
The control line of the external grid monitoring system should be connected to the two
contacts, NA21 and NA22, using a bridge. When only one contact is connected, only that
one MPP tracker will feed into the grid. When the status signaling contacts are in use (see
Section 5.6) the external shutdown function cannot be used.
Connection conditions
Connection type: 3-pole connector (included in the delivery)
Permissible conductor cross sections: 0.25 to 2.5 mm
Multiple cable gland; permissible cable Ø: 5.5 to 7.0 mm
Nominal input voltage 230 VAC
2
Procedure
1. Remove the cover of the inverter as described in Section 5.1.
WARNING!
Fatal electric shock hazard!
The control line of the thermal grid monitoring system may be live with mains
voltage.
Ensure that the control line is not live during connection work.
32
2. Thread the cable through the multiple cable gland.
3. Connect the control line to the 3-pole connector (Figure 23/No. 2) as follows:
– Wire stripping length: 7 mm
– Tightening torque: 0.5 to 0.6 Nm
M3
1
2
0.5 … 0.6 Nm
en
3
Figure 23 Connecting the external shutdown
4. Plug in the 3-pole connector.
5. Plug in the 6-pole connector (Figure 23/No. 1) in order to cover the open contacts.
6. Check that the NA21 and NA22 contacts are bridged (Figure 22/No. 1).
7. Use cable ties to attach the cables to the housing grips (Figure 23/No. 3).
8. Close the unused apertures in the multiple cable gland using the locking pins (No. 8
in Section 4.3).
9. Tighten the multiple cable gland (wrench size: 34 mm).
10. Fit the cover of the inverter.
7 mm
5�8 External output control (optional)
The MaxWebxp data logger and its MaxRemote extension can be used to set the set
values for active and reactive power (e.g. for remote controlled output limitation). The
MaxWeb xp is connected via the Ethernet or via the inverter's RS485 interfaces (see Section 5.5), i.e. via a MaxComm network.
You can download the installation instructions for the MaxWebxp and MaxRemote accessory components from our website: www.solarmax.com; Downloads / Data communication / MaxWebxp.
33
6 Commissioning
6�1 Activating the inverter
The inverter is connected to the PV generator when the DC disconnector is switched on.
The graphics display and the communication functions are activated.
Procedure
1. Check that the inverter's cover is installed.
2. Switch on the DC disconnector at the inverter.
I
Figure 24 Switching on the DC disconnector
– When the input power is sufcient, the graphics display will show the "Overview".
3. Switch on the AC power supply to the inverter.
– The "Start-up" status message is shown.
4. Wait for the "Mains operation" status message to be displayed.
– This indicates that the inverter is in mains operation.
– During initial start-up of the inverter, instead of the “Overview” menu, an “Initial
setup” menu appears (see Section 6.2).
34
6�2 Initial start-up
This section describes the initial start-up of the inverter and the graphics display settings required for this purpose. Once initial start-up has been successfully completed, the
inverter will start feeding into the mains grid.
The initial start-up should be carried out by qualied electricians only. The operation of
the graphics display is described in Section 7.
6�2�1 Requirements
The inverter has been installed and the electricity has been connected.
The inverter's cover has been tted.
There is sufcient solar irradiation (sufciently high DC input voltage).
Note
Entering an incorrect country setting may lead to problems regarding
inverter operation and to the withdrawal of the operating license by the
respective grid operator.
Contact your grid operator or the SolarMax Service Center if you have any
doubt regarding the settings you must select.
You can restart initial start-up by pressing in the "Conrmation"
menu at any time.
6�2�2 Procedure
1. Switch on the inverter as described in Section 6 .1. The "Initial setup" menu will be
displayed:
Figure 25 Selecting the display language and updating the system time
2. Select the display language from the "Language" menu.
3. If necessary, update the time and the date.
– The inverter saves the date entered as the initial start-up date.
4. Press on to conrm the entries.
– The "Country" menu will be displayed:
en
Figure 26 Selecting the country setting
5. Select the country setting.
– Press to conrm your entry.
– Depending on the country setting selected, additional menus may be displayed
(see Section 6.2.3).
35
– The "Conrmation" menu is then displayed.
6. Check the data in the "Conrmation" menu.
7. To complete initial start-up, press .
– The main menu will then be displayed (see Section 7.4 ).
– In the case of commissioning in Italy, after initial start-up the auto test must be
carried out (see Section 6.3).
6�2�3 Country-specic menus
Depending on the country setting, additional menus will be displayed during initial
start-up.
Country: Denmark
MenuSettingDescription
Plant system rating> 13.8 kVA – 30 kVA*The plant system rating is higher than 13.8
> 30 kVAThe plant system rating is higher than 30
CosPhi(Pac) - QMCPPInactive
On
* only available with the SM30HT4
Country: Germany
MenuSettingDescription
Grid connectionMedium voltageThe inverter is connected to the medi-
Low voltageThe inverter is connected to the low-voltage
System power*> 13.8 kVA – 30 kVA** The plant system rating is higher than 13.8
> 30 kVAThe plant system rating is higher than 30
CosPhi(Pac) - QMCPP*Inactive
On
* only available with "Low-voltage" grid connection
** only available with the SM30HT4
kVA and does not exceed 30 kVA .
kVA. External grid monitoring will be used.
The "cosφ(Pac)" function is deactivated
(cosφ=1).
The "cosφ(Pac)" function is activated.
um-voltage mains.
mains.
kVA and does not exceed 30 kVA .
kVA. External grid monitoring will be used.
The "cosφ(Pac)" function is deactivated
(cosφ=1).
The "cosφ(Pac)" function is activated.
36
Country: Luxembourg
MenuSettingDescription
System power> 13.8 kVA – 30 kVA* The plant system rating is higher than 13.8 kVA
> 30 kVAThe plant system rating is higher than 30 kVA.
CosPhi(Pac) - QMCPP Inactive
On
* only available with the SM30HT4
and does not exceed 30 kVA.
External grid monitoring will be used.
The "cosφ(Pac)" function is deactivated
(cosφ=1).
The "cosφ(Pac)" function is activated.
6�3 Auto test
The auto test (only available in the "Italy" country setting) checks the inverter's grid monitoring function. The auto test consists of 7 test steps in which the triggering behavior is
checked when the voltage and frequency limits are exceeded.
In the auto test the limit value is gradually changed until it reaches the triggering threshold
(i.e. the current measured value). If the grid monitoring function is working, the inverter
triggers the grid monitoring action. For each step of the test, the graphics display shows
the current reading, the trigger value, the trip time and the set limit. During the test of the
frequency limits, the activation status of the limit value is also displayed.
The auto test is performed automatically. Following completion of the auto test, the
inverter returns to normal operation. If an error occurs or irradiation is too low during the
auto test, the auto test is aborted. In this case the message "Auto-test aborted" is shown
on the display. The auto tests lasts approximately 5 minutes.
en
Requirements
The auto test should be carried out when there is sufcient solar irradiation, i.e. not
at dusk or when there is extensive cloud cover.
The inverter has been connected to the mains and switched on for at least 10
minutes.
Procedure
1. In the Main Menu, select the "Auto Test" menu.
2. To start the auto test, press .
3. Wait for the display of the successful completion of the auto test:
37
Figure 27 Display after successful auto test
4. Ensure that the inverter resumes normal operation (in this case the status message
"Mains operation" will be shown on the graphics display).
6�4 Settings
Different communication parameters and monitoring functions can be set in the "Settings" menu of the graphics display. All settings except the IP mode can also be made
using the MaxTalk service software.
6�4�1 Changing parameters
The parameters in the "Settings" menu can be changed as follows:
1. In the Main Menu select the "Settings" menu.
Figure 28 "Settings" menu
2. Press to select the parameter (e.g. "Time").
3. Press to change to the editing mode.
4. Press to select the required number.
38
Figure 29 Selecting the number and changing the value
5. Press to increase the value of the selected number.
6. Press to select the next number.
7. Press to conrm the parameter value.
8. Press to return to the Main Menu.
6�4�2 Setting the display language and system time
The inverter's display language and system time can be changed in the "Settings" menu.
1. Select the "Settings" menu:
Figure 30 Changing the display language and system time
2. Select the parameter and update it:
ParameterDescription
LanguageSelection of the display language: German, English, French, Italian
or Spanish. The display language can be selected independent of the
country setting.
TimeDate and system time of the inverter
Date
en
3. Press to return to the Main Menu.
39
6�4�3 Setting the network parameters
The network parameters can be assigned in the "Settings" menu.
Note
Please take note of the information relating to MaxComm compatibility in Section 11.3.
Device address
In order to communicate via an RS485 or Ethernet interface, the inverter needs a unique
device address on the network.
1. In the "Settings" menu, select the "Device address" parameter.
2. Set the parameter to the required value:
ParameterDescription
Device addressAddress range: 1 to 249
Configuring the Ethernet interface
In addition to the device address, the following settings must be made to communicate
via Ethernet:
1. In the Main Menu select the "Network" menu.
2. In the "IP mode", select the required setting:
SettingDescription
DHCP clientThe inverter is a DHCP client and is connected to a network with
StaticThe inverter is connected to a network with static IP addresses.
DHCP server (factory setting).
40
3. If appropriate, congure the following parameters. These settings are only required in
"Static" IP mode (see step 2):
ParameterDescription (in brackets: factory settings)
IPIP a ddr e ss ( 19 2 .16 8.1.123)
Gateway(192 .168.1.1)
TCP port(1234)
DNS1Domain Name Server 1 (192.168.1.1)
DNS2Domain Name Server 2 (192.168.1.1)
NetmaskSubnet mask (255.255.255.0)
4. Check whether the Ethernet connection indicator appears on the graphics display
(see Section 7.1).
6�4�4 Conguring the status signaling contacts
The two status signaling contacts for the remote monitoring of the inverter can be congured in four different ways.
Procedure
1. In the "Settings" menu, select the "Status relay" parameter.
2. Make the required setting:
SettingDescription
OffThe status signaling contacts are always open.
GridWhen the inverter starts mains operation, the status signaling con-
tacts close and remain closed for as long as the inverter feeds into
the grid. When a power unit (MPP tracker 1/2 or MPP tracker 3/4) is
disconnected from the grid, the respective status signaling contact
opens after an adjustable delay time.
ErrorWhen a warning, a failure or a device error occurs at a power unit
(MPP tracker 1/2 or MPP tracker 3/4) (error messages, see Section
8.2), the respective status signaling contact closes after the expiry
of the adjustable delay time. The status signaling contact opens
when the error has been eliminated (factory setting).
OnWhen a power unit (MPP tracker 1/2 or MPP tracker 3/4) switches
on when the DC input voltage is sufciently high, the respectie
status signaling contact closes. The status signaling contact opens
when the power unit switches off due to insufcient DC input
voltage.
3. Select the "Status relay delay" parameter.
4. Adjust the required delay time for the status signaling contacts:
ParameterDescriptionValue rangeUnit
Status relay delayDelay time of status signaling contact0 to 99min
en
6�5 Displaying the conguration
All available operating parameters, standard-specic functions and their parameterization can be retrieved in the "Conguration" menu. Conguration of the standard-specic
functions depends on the country setting selected.
Note
The MaxTalk 2 Pro service and communication software makes it possible
for authorized personnel to individually adjust the operating parameters (see
Section 12).
41
6�5�1 Procedure
1. In the Main Menu, select the "Conguration" menu.
Figure 31 "Configuration" menu
2. Press to select the parameter:
EntryDescription
CountryCountry setting selected at the time of initial start-up.
GridGrid connection selected during initial start-up (only available
System powerPlant rating selected at initial star t-up (only available with
SSFMenu of standard-specic functions and parameters
– The "SSF" menu contans the following sub-menus.
MenuDescription
External inputDisplay of external control functions (external shutdown and
Inverter start-upThose functions are displayed which are active before the
Grid operationThose functions are displayed which are active during the
LimitationThose functions are displayed which limit the inverter's output
Reactive powerThose functions are displayed that have an impact on the
Reference parametersDisplay of nominal values and reference values.
with “Germany” country setting).
"Denmark", "Germany" and " Luxembourg" country settings).
external output control).
inverter is connected to the grid (start conditions).
inverter's grid operation (grid monitoring).
values, such as active and reactive power and output current
(output limitation).
reactive power taken up or given out by the inverter (reactive
power control).
42
3. Press to conrm the selection.
– Section 6.5.2 contains the description of the SSF functions and parameters.
4. Press to return to the Main Menu.
6�5�2 Description of extended functions and parameters
This section contains the description of the functions and parameters available from the
"SSF" menu.
External input
Functions and parameters of the "External input" sub-menu:
Function / parameterDescriptionUnit / status
EISDMonitoring the N A21, NA22 and NA1 inputs of the
external shutdown.
EISD-ENAEISD function statusDisabled/enabled
Inverter start-up
Functions and parameters of the "Inverter start-up" sub-menu:
Function / parameterDescriptionUnit / status
PVGITChecking the insulation resistance of the PV gener-
ator to ground
PV GIT-E N APVGIT function statusDisabled/enabled
PV GIT-TH RMinimum permissible insulation resistanceΩ
RCMUTChecking the integrated fault current monitoringRCMUT-ENARCMUT function statusDisabled/enabled
ISTChecking the grid relay
IS T-ENAIST function statusDisabled/enabled
GPTChecking the grid parametersGP T- ENAGPT function statusDisabled/enabled
GP T- MOTDuration of checks
GPTVMINChecking the minimum mains voltage GPTVMIN-ENAFunction status of GPT VMINDisabled/enabled
GPTVMIN-THRMinimum permissible mains voltageV
GPTVMIN-DLYTrip times
GPTVMAXChecking the maximum mains voltage GPTVMAX-ENAFunction status of GPTVMA XDisabled/enabled
GP T V M A X-TH RMaximum permissible mains voltageV
GP T VMA X-DLYTrip times
GPTFMINChecking the minimum mains frequency GPTFMIN-ENAFunction status of GPTFMINDisabled/enabled
GPTFMIN-THRMinimum permissible mains frequencyHz
GPTFMIN-DLYTr ip times
GPTFMAXChecking the maximum mains frequency GPTFMAX-ENAFunction status of GPTFMAXDisabled/enabled
GPTFMAX-THRMaximum permissible mains frequencyHz
GP TFM A X-DLYTrip times
-
-
en
43
Grid operation
Functions and parameters of the "Grid operation" sub-menu:
Function / parameterDescriptionUnit / status
GVMMIN1Checking the minimum permissible mains voltage
(limit 1)
GVMMIN1-ENAGVMMIN1 function statusDisabled/enabled
GVMMIN1-THRLimit valueV
GVMMIN1-DLYTr ip times
GVMMA X1Checking the maximum permissible mains voltage
(limit 1)
GVMMAX1-ENAGVMMAX1 function statusDisabled/enabled
GV M MA X1-T H RLimit valueV
GV MMA X1-DLYTrip ti mes
GVMMIN2Checking the minimum permissible mains voltage
(limit 2)
GVMMIN2-ENAGVMMIN2 function statusDisabled/enabled
GVMMIN2-THRLimit valueV
GVMMIN2-DLYTr ip times
GVMMAX2Checking the maximum permissible mains voltage
(limit 2)
GVMMAX2-ENAGVMMAX2 function statusDisabled/enabled
GV M MA X 2-T H RLimit valueV
GV MM A X 2- DLYTrip times
GVM10AMA XChecking the maximum permissible average value
for mains voltage over the last 10 minutes
GVM10AMAX-ENAGVM10AMAX function statusDisabled/enabled
GV M10AM A X-THRLimit valueV
GV M10AMA X-DLYTri p t imes
GVMTMonitoring for unacceptably high peaks in the
mains voltage.
GVMT-ENAGVMT function statusDisabled/enabled
GFMMIN1Checking the minimum permissible mains fre-
quency (limit 1)
GFMMIN1-ENAGFMMIN1 function statusDisabled/enabled
GFMMIN1-THRLimit valueHz
GFMMIN1-DLYTr ip times
GFMMA X1Checking the maximum permissible mains fre-
quency (limit 1)
GFMMAX1-ENAGFMMAX1 function statusDisabled/enabled
GF MMA X1-T H RLimit valueHz
GF MMA X1-DLYTr ip times
-
-
-
-
V
-
-
-
44
Function / parameterDescriptionUnit / status
GFMMIN2Checking the minimum permissible mains fre-
quency (limit 2)
GFMMIN2-ENAGFMMIN2 function statusDisabled/enabled
GFMMIN2-THRLimit valueHz
GFMMIN2-DLYTr ip times
GFMMAX2Checking the maximum permissible mains fre-
quency (limit 2)
GFMMAX2-ENAGFMMAX 2 function statusDisabled/enabled
GF MMA X2-T H RLimit valueHz
GFMM A X 2- DLYTrip times
AISDetection of island operationAIS-ENAAIS function statusDisabled/enabled
AI S-DLYTrip times
RBCMMonitoring the continuous leakage currentRBCM-ENARBCM function statusDisabled/enabled
RB CM-TH RMaximum permissible leakage currentA
RSCMMonitoring the leakage current step valueRSCM-ENARSCM function statusDisabled/enabled
DCCIMMonitoring the DC component in the AC currentDCCIM-ENADCCIM function statusDisabled/enabled
DCCIM-THRMaximum permissible DC component in AC current A
DCCIM-DLYTrip times
-
-
Limitation
Functions and parameters of the "Limitation" sub-menu:
Function / parameterDescriptionUnit / status
ACPPLMaximum increase in the active power during grid
connection
ACPPL-ENAACPPL function statusDisabled/enabled
ACPPL-MGDTIncrease% of Pac nom/
ACPPL-INIACPPL at every start-upDisabled/enabled
ACPPL-RCNACPPL at start-up after grid disconnection caused
by coupler breaker
ACPLLimitation of active output powerAC P L- LM TLimit valueW
APPLLimitation of the apparent powerAPPL-LMTLimit valueVA
OCLLimitation of the output currentOC L- L MTLimit valueA
-
min
Disabled/enabled
en
45
Function / parameterDescriptionUnit / status
PULActive power limitation depending on mains voltage -
P U L- EN APUL function statusDisabled/enabled
P U L- A V GM O TAverage check durations
P U L- V TH RLimit valueV
P U L- RD NReduction of active power% of Pac nom/
PUL-RNCIncrease to rated output power% of Pac nom/
PFLM2P(f) mode 2PFLM2-STRTFQStart frequencyHz
PFLM2-RDNReduction of active power
PFLM2-RNCIncrease to rated output power % of Pac nom/
PFLM3P(f) mode 3PFLM3-STRTFQStart frequencyHz
PFLM3-RDNReduction of active power
PFLM3-RNCIncrease to rated output power % of Pac nom/
PFLM3-UFQTHRMaximum permissible mains frequencyHz
PFLM3-LFQTHRMinimum permissible mains frequencyHz
PFLM3-UVTHRMaximum permissible mains voltageV
PFL M3-LVTHRMinimum permissible mains voltageV
PFLM3-MOTDuration of checks
PFLM4P(f) mode 4PFLM4-STRTFQStart frequencyHz
PFLM4-RDNReduction of active power
PFLM4-RNCIncrease to rated output power% of Pac nom/
Functions and parameters of the "Reactive power" sub-menu:
Function / parameterDescriptionUnit / status
QMO-AMReactive power control0=OFF
QMCQReactive power mode "Q" (xed reactive power) -
Function / parameterDescriptionUnit / status
QMCQ-QSVReactive power value% of Pac nom
QMCQ-VLEStatus of the voltage-dependent reactive power
QMCQ-VLIMains voltage switch on valueV
QMCQ-VLOMains voltage switch off valueV
QMCQ-PLEStatus of the active power-dependent reactive
QMCQ-PLIActive power switch on valueW
QMCQ-PLOActive power switch off valueW
QMCPP
QMCPP-PSP1 to
PSP10
QMCPP-CPSP1 to
CP SP 10
QMCPP-VLEStatus of mains voltage-dependent reactive power
QMCPP-VLIMains voltage switch on value V
QMCPP-VLOMains voltage switch off value V
QMQU1Reactive power mode "Q( Vac) mode 1"QMQU1-VSP1 to VSP10 Characteristic values 1 to 10 of mains voltage ( Vac) V
QMQU1-CPSP1 to
CP SP 10
QMQU1_DLYDelay time when mains voltage (Vac) changess
QMQU 1-V LEStatus of active power-dependent reactive power
QMQU 1-V LIActive power switch on value% of Pac nom
QMQU 1-V LOActive power switch off value % of Pac nom
QMQU2Reactive power mode "Q(Vac) mode 2"QMQU2-UPQUpper reactive power value (OEX)% of Pac nom
QMQU2-LOQLower reactive power value (UEX)% of Pac nom
QMQU2-UPVLIMains voltage switch on value for QMQU2-UPQV
QMQU2-UPVLOMains voltage switch off value for QMQU2-UPQV
QMQU2-LOVLIMains voltage switch on value for QMQU2-LOQV
QMQU2-LOVLOMains voltage switch off value for QMQU2-LOQV
QMQU2-PLEStatus of active power-dependent reactive power
QMQU2-PLIActive power switch on value% of Pac nom
QMQU2-PLOActive power switch off value% of Pac nom
QMCCP
QMCCP-CPSV
control hysteresis for QMCQ
power control hysteresis for QMCQ
Reactive power mode "cosφ(Pac)"
Characteristic values 1 to 10 of Pac active power% of Pac nom
Characteristic values 1 to 10 of power factor cosφ
control hysteresis for QMCPP
Characteristic values 1 to 10 of reactive power Q% of Pac nom
control hysteresis for QMQU1
control hysteresis for QMQU2
Reactive power mode "cosφ"
cosφ value
[OEX/UEX]
Disabled/enabled
Disabled/enabled
-
- [UEX/OEX]
Disabled/enabled
[UEX/OEX]
Disabled/enabled
Disabled/enabled
-
- [UEX/OEX]
en
47
Function / parameterDescriptionUnit / status
QMCCP-VLEStatus of mains voltage-dependent reactive power
control hysteresis for QMCCP
QMCCP-VLIHMains voltage switch on valueV
QMCCP-VLOLMains voltage switch off value V
QMCCP-PLEStatus of active power-dependent reactive power
control hysteresis for QMCCP
QMCCP-PLIActive power switch on valueW
QMCCP-PLOActive power switch off value W
Disabled/enabled
-
Grid stabilization
Functions and parameters of the "Grid stabilization" sub-menu:
Function / parameterDescriptionUnit
FRTFault Ride-Through functionFRT-ENAFRT function statusDisabled/enabled
FR T-T RVMains voltage trip valueV
FRT-RCMReactive power modeFRT-KFK factorFR T-T M1Timer 1s
FR T-T M2Timer 2s
Reference parameters
Functions and parameters of the "Reference parameters" sub-menu:
Function / parameterDescriptionUnit
NAPRated output power (Pac nom)-
NAP-VALValueW
NOCRated output currentNOC-VALValueA
GCDCoupler breaker switch delayGCD-CDLYTrip times
48
6�6 Displaying measured values
The current measured values of the inverter can be accessed in the “Measured values”
menu.
1. In the Main Menu, select the "Measured values" menu.
Figure 32 "Measured values" menu
2. Select a menu item:
Menu itemDescription
System
Power Unit 1
Power Unit 2
3. Press or to scroll through the measured values:
– Measured values under "System":
Measured value DescriptionUnit
Vac L1, Vac L2,
Vac L3
Iac L1, Iac L2,
Iac L3
Pac
S
Q
cos
φ
Frequency
Measured values
Measured values of MPP trackers 1 and 2
Measured values of MPP trackers 3 and 4
Phase voltage L1, L2 and L3V
Output current L1, L2 and L3A
Output power W
Apparent power VA
Reactive power (+: overexcited / −: underexcited)var
Power factor (OEX: overexcited / UEX: underexcited)Mains frequencyHz
en
– Measured values under "Power unit 1":
Measured value DescriptionUnit
Vdc 1, Vdc 2
Idc1, Idc2
Pdc
Tempe rat ure
Input voltage at MPP tracker 1 / MPP tracker 2V
Input current at MPP tracker 1 / MPP tracker 2A
Input power (total of MPP trackers 1 and 2)W
Cooling element temperature (MPP trackers 1 and 2)°C
49
– Measured values under "Power unit 2":
Measured value DescriptionUnit
Vdc 1, Vdc 2
Idc1, Idc2
Pdc
Tempe rat ure
Input voltage at MPP tracker 3 / MPP tracker 4V
Input current at MPP tracker 3 / MPP tracker 4A
Input power (total of MPP trackers 3 and 4)W
Cooling element temperature (MPP trackers 3 and 4) °C
4. Press to return to the Main Menu.
Note
The measured inverter values are not suitable for billing purposes or calculating the efciency. The measuring error may amount to up to ±5% depending
on the measured value. Only the measured values of a calibrated electricity
meter can be relied upon for billing purposes.
MaxTalk measured values
The MaxTalk 2 service software can be used to display, in addition, the following measured values of the inverter:
Measured valueDescriptionUnit
Vac 10 min10 minute mean value of the mains voltageV
Iac meanMean value of output currentA
IerrGround leakage currentmA
Ierr DCLeakage currentmA
50
6�7 Registering for MaxView
Register for the free web-based MaxView application. As well as facilitating an optimum
after-sales service, MaxView enables you to display and graphically visualize the yield
data of your PV power plant from anywhere.
Note
Frequently asked questions about MaxView and the replies to these can be
found on our website at https://maxview.solarmax.com/faq.xhtml.
Procedure
1. Connect the inverter to the internet via the Ethernet interface (see Sections 5.5 and
6.4.3).
2. Enter your registration data in a web browser under https://maxview.solarmax.com.
3. Learn about the various functions of MaxView.
7 Operation
7�1 Graphics display
The graphics display shows the system values, status information, and the inverter’s
failure messages. The graphics display can be used to obtain information on the current
operating status, accessing the integrated data logger and entering various settings on
the inverter.
5
4
1
2
3
Figure 33 Graphics display with the standard "Overview" display
No�Description
1Graphics display with backlighting
2Status LED: operating status display (see Section 7.7 )
3Function keys (membrane keys)
4Symbol for Ethernet connection (link display)
5Symbol for data communication
en
The function keys can be used for navigating within the menu structure:
Symbol Description
Select menu or parameter
Edit parameter
Highlight number (parameter editing)
Increase highlighted number / select menu or parameter
Confirm
Cancel
51
7�2 Menu structure
Overview
Statistics
Days
Months
Years
Total
Reset
Status
Main menu
* only for country setting “Italy”
Information
Measured values
System
Power Unit 1
Power Unit 2
Conguration
SSF
External input
Inverter start-up
Grid operation
Limitation
Reactive power
Reference parameter
Auto test*
Settings
Language
Time
Date
Device adress
Network
IP-Mode
IP
Netmask
Gateway
TCP Port
DNS1
DNS2
Status relay
Status relay delay
Figure 34 Menu structure of graphics display
52
7�3 Displaying the operating data overview
The overview shows the inverter's most important operating data. The graphics display
automatically switches to the "Overview" if no function button is pressed for 120 seconds.
1. In the Main Menu, select the "Overview" menu.
Figure 35 "Overview" menu
DisplayDescription
19.06.2013 / 11:44:35Date and system time of inverter (examples)
PacOutput power [W]
TodayDaily yield [kWh]
Tot alTotal yield since commissioning [kWh]
Status
Operating status of inverter (see Section 7.7 )
7�4 Displaying Main Menu
From the Main Menu you can open all menus.
1. In order to switch from "Overview" to the Main Menu, press any function key.
en
Figure 36 Main Menu
2. Press or to select the menu.
3. Press to conrm the selection.
53
7�5 Statistics
The "Statistics" menu can be used for accessing the inverter's data logger. The data
logger saves the statistics values of the past 25 years. The daily, monthly, yearly and total
statistics can be displayed. All statistics values can be deleted.
7�5�1 Displaying the daily statistics
The daily statistics consist of the statistics values for the last 31 days.
1. In the "Statistics" menu, select the "Day" sub-menu.
Figure 37 Daily statistics
2. Press or to select the day:
Statistics valueDescription
YieldDaily yield [kWh]
MaximumFed-in maximum power [W]
HoursNumber of operating hours in the "Mains operation" operating
3. Press to return to the "Statistics" menu.
status
54
7�5� 2 Displaying the monthly statistics
The monthly statistics consist of the statistics values for the last 12 months.
1. In the "Statistics" menu, select the "Month" sub-menu.
Figure 38 Monthly statistics
2. Press or to select the month:
Statistics valueDescription
YieldMonthly yield [kWh]
MaximumFed-in maximum power [W]
HoursNumber of operating hours in the "Mains operation" operating
status
3. Press to return to the "Statistics" menu.
7�5� 3 Displaying the annual statistics
The annual statistics consist of the statistics values for the last 25 years.
1. In the "Statistics" menu, select the "Year" sub-menu.
Figure 39 Annual statistics
2. Press or to select the year:
Statistics valueDescription
YieldAnnual yield [kWh]
MaximumFed-in maximum power [W]
Hours
Number of operating hours in the "Mains operation" operating
status
en
3. Press to return to the "Statistics" menu.
7�5� 4 Displaying the total statistics
The total statistics consist of the statistics values since commissioning.
1. In the "Statistics" menu, select the "Total" sub-menu.
55
Figure 40 Total statistics
Statistics valueDescription
YieldTotal yield [kWh]
HoursTotal operating hours in the operating status "Mains
operation"
2. Press to return to the "Statistics" menu.
7�5�5 Deleting the statistics values
The statistics values in the data logger can be deleted.
1. In the "Statistics" menu, select the "Reset" sub-menu.
Figure 41 Resetting the inverter's data logger
Note
Once data are deleted, this cannot be undone!
2. Press to cancel the deletion process.
3. Press to delete all statistics values.
56
7�6 Displaying information
This menu displays information about the inverter. The menu can be used to identify the
inverter.
1. In the Main Menu, select the "Information" menu.
Figure 42 "Information" menu
2. Press or to scroll.
DisplayDescription
Device typeInverter type
Serial No.Inverter serial number
FirmwareFirmware version installed in the inverter
StatusCurrent operating status
WarningCurrent warning message
CommissioningDate of initial start-up
Operating hoursTotal operating hours in mains operation
MAC addressMAC address of the inverter
3. Press to return to the Main Menu.
7�7 Displaying the operating status of the inverter
The status LED (Figure 33/No. 2) signals the current operating status of the inverter by
its different signal colors. The status message, which gives a more detailed description of
the operating status, is displayed at the graphics display.
In addition to the status messages, the inverter also displays warnings. Warnings result
from device errors or external failures. The inverter continues to feed power into the
mains, but it is possible that yield is reduced. Warnings are independent of the operating status and are displayed on the graphics display alternately with the current status
message.
en
Status of LEDOperating statusDescription
Off
Flashes green
Green
Flashes orange
Orange
Red
-Inverter is switched off
BootingInverter is starting up
Mains operationMains feed-in (normal operation)
-
Failure
Error
Warning → no grid disconnection
External failure → grid disconnection
Device error → grid disconnection
57
Status of LEDOperating statusDescription
Flashes red
Blocked
Inverter is blocked → grid disconnection
The "Failure", "Error", and "Blocked" operating status messages, as well as the warnings, usually require certain actions to be carried out by the qualied electrician in charge
(see Section 8).
7�7�1 "Booting" operating status
Status LED: ashes green
Status messageDescription
No responseThe specied power unit (MPP tracker 1 / 2 or MPP tracker 3 / 4)
Irradiation too lowThe solar irradiation or rather the available output is too low for
Star t-up…The inverter checks the internal hardware and software compo-
Restar t delayThe inverter delays connection to the grid (after a disconnection
does not respond. The cause could be insufcient solar irradiation.
The inverter uses the available MPP tracker to feed into the grid.
mains operation.
nents before connecting to the mains.
from the grid or when booting).
7�7� 2 "Mains operation" operating status
The status LED lights up green.
Status messageDescription
Maximum output powerThe inverter limits the in-feed power to the maximum possible
Mains operationThe inverter is in feed mode.
Idc limitationThe inverter limits the PV generator current to the maximum per-
Iac limitationThe inverter limits the output power to the maximum permissible value
Restar t limitationFollowing an external output limitation the inverter increases the
Frequency limitationThe inverter temporarily limits the active power owing to an active
External limitationThe inverter's fed-in active power is limited by external output
Temperature limitationThe output power is temporarily reduced in order to limit the
value. This may occur if the PV generator is oversized.
missible value. This may occur if the PV generator is designed such
that the current at the Maximum Power Point (MPP) exceeds the
maximum permissible input current of the inver ter.
(where the PV generator is oversized).
active power with dened progression (Pac progression and/or Soft
Start).
frequency-dependent power reduction.
control.
inverter's temperature.
58
7�8 Displaying the operating status of the MPP trackers
Via the "Status" menu it is possible to display the operating status of the MPP trackers
and the inverter. The displayed warnings and status messages are described in the Sections 7.7 and 8.2.
1. In the Main Menu, select the "Status" menu.
Figure 43 "Status" menu
EntryDescription
System
PU1
PU2
2. Press to return to the Main Menu.
Operating status of inverter (see also Section 7.7 )
Operating status of MPP trackers 1 and 2 (Power unit 1)
Operating status of MPP trackers 3 and 4 (Power unit 1)
en
59
8 Troubleshooting
8�1 SolarMax Service Center
If you have technical questions or difculties, our Service Center will be happy to help you.
To do that we need the following information:
Device type
Serial number (S/N)
Installation location
Information on the current failure (warning, status message, plant documents, etc.).
Contacting the SolarMax Service Center
The contact details of the SolarMax Service Center can be found on the back of this
instruction manual.
Sputnik Engineering AG
Länggasse 85
CH-2504 Biel/Bienne
8�2 Diagnosis and actions
The following tables describe possible actions for remedying faults. If the actions suggested do not correct the fault, please contact the SolarMax Service Center.
8�2�1 General troubleshooting
ProblemCauseActions
The graphics display
remains blank
The graphics display only
ashes briey.
The DC disconnector is switched
off.
The irradiation is too low.Wait until irradiation is high
All DC input conductors (strands)
are interrupted.
It is possible that the inver ter is
defective.
The irradiation is too low.Wait until irradiation is high
Switch on the DC disconnector.
enough.
Check the PV generator and
eliminate the interruption.
Contact the SolarMax Service
Center.
enough.
60
8�2�2 Warning messages
The status LED ashes orange.
WarningCauseActions
Temperature limitationThe output power is temporarily
reduced in order to limit the
inverter's temperature.
Fan failureA fan is defective or soiled. Contact the SolarMax Service
RTC errorDate and time in the RTC (real-
time clock) were reset due to a
failure.
Firmware mismatchThe rmware versions of the
inverter controllers do not match.
Ensure that
the recommended maximum
ambient temperature is not
exceeded and that the cooling
ns are free from dust and
dirt.
Center.
Set the date and time (see
Section 6.4.2). If this problem
occurs frequently, contact the
SolarMax Service Center.
Contact the SolarMax Service
Center.
en
Flash errorAn error has occurred in the ash
memor y.
Contact the SolarMax Service
Center.
8�2�3 "Failure" operating status
The status LED lights up orange.
Note
MaxTalk can be used to display the last error messages.
Status messageCauseActions
Vdc too highThe DC input voltage of the
inverter is too high.
Ierr too highThe ground leakage current
has exceeded the permissible
RBCM-THR limit value.
Leakage current stepThe leakage current has exceeded
the permissible RSCM step value.
No mainsThere is no mains voltage.Check the AC input conductor
Switch of f the DC disconnector. Check the PV generator’s conguration.
Check the PV generator.
(fuses).
61
Status messageCauseActions
Frequency too highThe mains frequency is outside
Frequency too lowThe mains frequency is outside the
Mains errorThe inverter detects island mode. If this problem recurs, contact
Vac too highThe mains voltage is outside the
Vac too lowThe mains voltage is outside the
Vac 10 min too highThe maximum 10-minute average
DC insulation faultThe insulation resistance of the PV
Error ext. input 1The external grid monitoring
the GFMMA X1-THR, GFMMAX2-THR or GPTFMA X-THR limit
values.
GFMMIN1-THR, GFMMIN2-THR or
GPTFMIN-THR limit values.
GV M MA X1-T H R, G V MMA X2-T H R
or GPT VMAX-THR limit values.
GVMMIN1-THR, GVMMIN2-THR or
GPT VMIN-THR limit values.
value of the mains voltage
GVM10AMA X-THR is too high.
generator to ground is too low.
Phase and neutral conductors are
inverted.
system has disconnected the
inverter from the grid (active signals at the "NA21" and/or "NA22"
inputs).
If this problem recurs, contact
the grid operator.
the grid operator.
If this problem recurs, contact
the grid operator.
Check the PV generator.
Connect the AC input conductor as described in Section
5.3.
If this problem recurs, contact
the grid operator.
62
8�2�4 "Error" operating status
The status LED lights up red.
Status messageCauseActions
Device error (+ error code) The inverter is defective.Write down the two-digit error
code displayed and contact the
SolarMax Service Center.
8�2�5 "Blocked" operating status
The status LED will ash red.
Status messageCauseAction
Firmware updateThe inverter's rmware is being
updated.
None. The inverter automatically resumes mains operation
once the rmware update is
complete.
9 Maintenance
The following maintenance tasks should be carried out at regular intervals:
Check the operating status of the inverter (see Section 7.7 ).
Check that the ventilation inlet and outlet (see Figure 2) are not blocked.
Clean the graphics display with a damp cloth. Do not use harsh or abrasive cleansing
agents.
Check the inverter for external damage. Report any such damage to the relevant
qualied electrician.
en
63
10 Decommissioning
O
10�1 Instructions for inverter replacement
When replacing the inverter, note the following:
Before replacing the inverter, write down the total yield. The procedure for viewing
the total yield is described in Section 7.5.4.
10�2 Dismounting the inverter
The inverter may only be dismounted by qualied electricians.
DANGER!
Fatal electric shock hazard!
Components within the inverter are charged with a high voltage. After the
inverter has been disconnected, high residual voltages remain in the inverter
for approx. 5 minutes.
Before starting to dismount the inverter, the inverter must be fully discon-
nected in accordance with the procedure described in this chapter.
WARNING!
Risk of injury from electric arc!
Dangerous electric arcs could occur when removing live DC input conductors.
Switch off the DC disconnector before removing the DC input
conductors.
64
Procedure
1. Disconnect the AC power supply to the inverter (switch off the external AC circuit
breaker).
– The "No grid" status message is shown on the inverter.
2. Switch off the DC disconnector at the inverter.
Figure 44 Switching off the DC disconnector
3. Use a size 2 screwdriver to remove the locking clips on the DC plugs.
4. Pull out the DC input conductors to fully disconnect the inverter from the PV
generator.
5. Remove the cover of the inverter as described in Section 5.1.
6. Use a suitable voltage detector to check that all terminals are free from voltage.
– When all terminals are free from voltage you can remove the AC input conductor
and all communication cables.
7. Fit the cover of the inverter.
8. Remove the two safety brackets.
CAUTION!
Risk of injury - the inverter is heavy!
The inverter weighs approx. 70 kg.
Never dismount the inverter on your own.
9. When dismounting the inverter, ask a second person to help.
10�3 Disposing of the inverter
Dispose of the inverter as indicated by the local waste disposal regulations. You can also
return the inverter, at your own cost, to Sputnik Engineering AG for professional disposal.
The contact details of the SolarMax Service Center can be found on the back of this
instruction manual.
en
65
11 Technical data
Input parameters
Output parameters Rated output power30 000 W3 2 000 W
EfciencyMaximum efciency98 %98 %
Power inputOwn consumption, night0 VA
EnvironmentProtection classIP65
MPP voltage range
Minimum DC voltage250 V250 V
Maximum DC voltage1 0 00 V1 000 V
Maximum DC current4 x 18 A4 x 18 A
Number of MPP trackers44
Number of string connections4 x 24 x 2
Connection typeWieland PST40i1 (identical to MC 4)
Ambient temperature range (for
rated power output)
Max. operating level above
sea level
Relative humidity0 to 98 % (without condensation)
Environmental categoryIn the open
Suitable for wet roomsYes
Level of pollution3
1)
SM30 HT4SM32HT4
430 to 850 V460 to 850 V
30 00 0 VA32 000 VA
Adjustable from 0.8 overexcited to 0.8 under-
excited
< 3 %
I
−20 to +60 °C (−20 to +4 5 °C)
2000 m
66
SM30 HT4SM32HT4
ComponentsDisplayGraphics display with backlighting and status
LED
Inverter topologyTwo-stage, without transformer
DC disconnectorIntegrated
Data loggerEnergy yields, peak output and operating
duration of the last 31 days, 12 months, 10 years
/ output curves of the last 7 days
Fault current monitoringInternal, AC/DC-sensitive
Casing / coverAluminum
ComponentsDC surge arresterClass C ( VDE 0 675- 6) and type 2 (EN 61643-11)
AC surge arresterClass D (VD E 0675-6) and type 3 (EN 61643-11)
Standards and
guidelines
CE-compliant
EMCEN 61000-3-11 / EN 61000-3-12 /
Yes
2)
EN 61000 -6-2 / EN 61000-6-3
Grid connectionVDE-AR-N 4105 / VDE 0126-1-1 A1:2012 / BDEW
MS Directive / G59 /3 / CEI 0-21 / CEI 0-16 /
PPC Guide / C10/11 / EN 50438
Device safetyIE C 6 2109-1/-2
InterfacesData communicationRS4 85 (R J45 and terminals) / Ethernet (RJ45)
Status signaling contactOpen / close device (terminals)
Connection to external grid
Yes (terminals)
monitoring
Weight and
dimensions
Weight70 kg70 kg
Dimensions (W x H x D)84 0 x 580 x 380 mm
WarrantyStandard 5 years / ex tension to 10, 15, 20 or 25
years possible
1) for rated output power
2) the complete conformity declaration can be found on our website at ww w.solarmax.com
en
67
11�1 Efciency curve
125
100
98
96
94
92
Efciency η [%]
90
88
86
UDC=460 V
UDC=580 V
UDC=720 V
(460 V ) = 97.0 %
η
Euro
(580 V ) = 97.5 %
η
Euro
η
(720 V ) = 97.5%
Euro
84
82
80
0102030405060708090100
Rated output power [%]
Figure 45 Efficiency curve - SolarMax HT series
11�2 Temperature-dependent output reduction
When the ambient temperature is too high, the inverter reduces its output as illustrated
in Figure 46 (power derating).
100
68
75
50
Output Pac/Pac nom [%]
25
0
−20−10010203040 45 5060
Ambient temperature [°C]
Figure 46 Power derating - SolarMax HT series
11�3 MaxComm compatibility
When establishing networks for the purpose of monitoring the plant, the MaxComm compatibility of the inverters must be taken into consideration. The compatibility depends
on the type of connection and the network (individual device or gateway device in a
MaxComm network).
The "Static" and "DHCP client" conguration options of the Ethernet interface can be set
at the inverter's graphics display, see Section 6.4.3.
The factory’s default settings for different countries can be viewed in the technical information “SSF - Standard specic functions and parameters”. This document can be downloaded from our website at: www.solarmax.com; Downloads/String inverters/HT series.
en
69
12 Accessories and options
Accessory/optionDescription
MaxViewFree web-based application with various functions for remote call-up,
graphics visualization and export of yield data.
Max Web xpMaxWebxp is a data logger, monitoring unit, and web server in one.
Ma xTalkFree communication and service software for local monitoring of the
MaxTalk ProProfessional version of MaxTalk for the conguration of inverters.
MaxMonitoringUsing the free MaxMonitoring software you can display the perfor-
MaxDesignFree software for determining the size of PV power plants.
Together with the MaxWeb portal, MaxWebxp is the ideal pair for
monitoring the plant.
PV power plant.
The "SolarMax HT series parameter conguration using MaxTalk 2
Pro" operating manual can be downloaded from our website at www.
solarmax.com ("Downloads" area).
mance data of your PV power plant at any time from home. MaxMonitoring is available for PC, MacOS and Linux and also as an app for
Android and iOS.
You can nd further information on our website at www.solarmax.com.
70
13 Warranty
Sputnik Engineering AG (hereafter SPUTNIK) guarantees full function and lack of defects of its
technical devices for a warranty period as specified below for each type of device. Such warranty
period can be extended by means of a warranty extension, subject to the conditions named below.
This manufacturer’s warranty exists next to the seller’s warranty (if any) as prescribed by law. As
far as identical with regards to the content, the rights under this manufacturer’s warranty supersede
any rights under the seller’s warranty. Please contact the seller with regard to any claims based on
the seller’s warranty.
1� Warranty Period (Basic)
Central inverters and accessories: 24 months from the date of purchase, but at maximum 30
months after dispatch of the device by SPUTNIK.
String inverters: 60 months from the date of purchase, but at maximum 72 months after dis-
patch of the device by SPUTNIK.
If in individual cases SPUTNIK has agreed in writing to a different warranty period, such arrangement supersedes the above provisions.
2� Scope of Manufacturer’s Warranty
In case of defect or malfunction of a device within the manufacturer’s warranty period, and
upon fulfillment of the conditions for warranty claims named hereafter, the device will be repaired
or replaced by SPUTNIK-service personnel within a reasonable time, in either case free of charge,
unless this is impossible or disproportionate. SPUTNIK may decide at its own discretion whether a
device will be repaired or replaced.
Replacement: E xchange of device free of charge. SPUTNIK’s separate conditions for exchange
of devices apply: This warranty covers the free delivery of an equivalent replacement device.
Further, your installer is entitled to claim a flat rate compensation for the replacement work
from SPUTNIK. Please do not hesitate to ask us about the current amount of such flat rate
compensation.
Repair: Repair of device free of charge. This warranty covers costs for material, work and travel
by SPUTNIK personnel or by personnel authorized by SPUTNIK.
Please be aware that the per formances of SPUTNIK under this warranty are only free of charge in
countries approved by SPUTNIK. Please contact your seller for details. A current list of approved
countries can be found on our homepage. Repair and replacement outside of the approved countries
are only possible after prior consultation of and approval by SPUTNIK. In such case, travel and
shipment costs are borne by the customer.
Any further claims, especially claims for compensation of damages resulting directly or indirectly
from the defect or claims for replacement of further costs in connection with the installation and
removal of devices or claims for loss of profits are not covered by this warranty.
en
71
3� Extent of Repair and Replacement
SPUTNIK will maintain repair material and stock of each type of device during the warranty period
only at its own reasonable discretion. In case repair materials for a certain type of inverter and/or an
identical replacement device are not in stock anymore, the following applies:
SPUTNIK is allowed to replace the defective inverter with a comparable device of the same or
superior per formance. The costs (time and material) for technical adjustments necessary for
the installation of such comparable devices are covered by this warranty only up to a limited
amount; any flat rate compensation owed by SPUTNIK for the replacement is deductible. Please
do not hesitate to ask us about the currently applicable amount. The exchange and connection
of peripheral devices due to possible non-compatibility with the replacement device or other
necessary adjustments to the surrounding installations of the device (including power lines,
ventilation and safety installations) are not covered by this warranty. However, SPUTNIK shall
within the bounds of reasonability do its best to minimize the effort of such adaptation work.
In case repair materials are not available with reasonable efforts anymore, SPU TNIK is allowed
to replace the inverter, subject to the conditions mentioned in the paragraph above.
4� Warranty Period in Case of Repair/Replacement
In case of repair or replacement of devices under this warranty, the repaired respectively replaced
device will inherit the remaining warranty time of the original device.
5� Exclusion of Warranty
Especially in the following cases, this manufacturer’s warranty does not apply:
Transport damage;
Technical intrusions, modifications or repairs of the devices not authorized by SPUTNIK;
Use of devices for purposes they are not intended for, incorrect or unreasonable manipulation,
incorrect or unreasonable installation;
Failure to observe the manufacturer’s operating, installation and maintenance directions;
Inadequate environmental conditions (e.g. insufficient ventilation of the device; humidity etc.);
Superior force (e.g. lightning strike, overvoltage, floods, fire, etc.).
72
6� Handling of Warranty Cases
For the processing of warranty cases, use of SPT UNIK’s hotline is mandatory. The handling of warranty cases must take place in accordance with the instructions provided by the hotline.
The hotline number for your country can be found on SPUTNIK’s homepage. Please hold the serial
number, article description, a short description of the defect and the purchase receipt ready for
transmission to the hotline.
Any repair action taken by the buyer or third parties without authorization by SPU TNIK will not be
compensated.
In case these terms on the handling of warranty cases are not respected, SPUTNIK may refuse its
warranty performances.
7� Suspension of Warranty
Sputnik reserves its right to suspend this manufacturer’s warranty temporarily or definitely in case
a specific installation does not allow a correct functioning of the inverters (e.g. in case of one of the
circumstances listed in cipher 5).
The suspension of the warranty can be lifted upon approval by SPUTNIK. Such approval must be
issued by SPUTNIK in writing, confirming that the warranty has again become effective.
8� Warranty Extension
The warranty period can be extended through purchase of a warranty extension within the time
limits mentioned hereafter. For certain types of devices, such warranty extensions can also be
purchased only for a limited scope of warranty performances. The purchase of a warranty extension
will be confirmed by SPUTNIK in form of a warranty certificate (including serial number of affected
product). In case of replacement of a device, the serial number in such warranty certificate remains
unchanged, without any influence on the validity of the warranty extension.
a) Time limits
String inver ters: The extension of the basic warranty can be ordered within 60 months after purchase, but the latest within 72 months after dispatch of the device by SPUTNIK.
Central Inverters: The extension of the basic warranty can be ordered within 3 months af ter purchase, but the latest within 12 months after dispatch by SPUTNIK.
b) Extent
Full warranty extension – FULL (available for central inverters and string inverters): A full warranty
extension includes all the warranty performances as described in the manufacturer’s basic warranty
terms.
Limited warranty extension– LIMITED (available only for central inver ters):
A limited warranty extension covers only the costs for the material required for the repair. The costs
for travelling, labor and other expenses are not covered and will be invoiced on a time and expenses
basis by SPUTNIK.
c) Effectiveness of Warranty Extension
It is a mandatory requirement for the warranty extension to provide the completely filled out application form to SPUTNIK. The warranty extension becomes effective only after written confirmation
and provision of the warranty cer tificate by SPUTNIK.
en
9� After Expiration of Warranty Period
The costs for repair or replacement of devices after expiration of the warranty period are invoiced by
SPUTNIK on a time and material basis. SPUTNIK will maintain repair and replacement capabilities
beyond the warranty time only at its own discretion.
10� Applicable Law, Jurisdiction
Only Swiss Law applies. The exclusive place of jurisdiction lies in Biel/ Bienne, Switzerland.
(v 2013/0 5 )
73
SolarMax Service Center:
hotline@solarmax.com
www.solarmax.com/service
2014/ 05 en
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.