SolarMax 4TP, 5TP2, 6TP2, 7TP2 Instruction Manual

SolarMax TP series
4TP / 5TP2 / 6TP2 / 7TP2
Instruction manual
Register here: maxview.solarmax.com
Sputnik Engineering AG
Länggasse 85
CH-2504 Biel/Bienne
© Sputnik Engineering AG 2014
Contents
1 Notes on the present instruction manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1 Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Target groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Where to keep this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Symbols used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Symbols on Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Identication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Safety installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.5 Views of the unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.6 Block circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1 Transporting and storing inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.2 Checking the delivery for completeness . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.3 Selecting the installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.4 Mounting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
5 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1 Open the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
5.1.1 Removing the cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
5.1.2 Removing the right-hand contact protection . . . . . . . . . . . . . . . . . 20
5.1.3 Removing the left-hand contact protection . . . . . . . . . . . . . . . . . . 21
5.2 Connection area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.3 Connecting the inverter to the mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4 Connecting the inverter to the PV generator . . . . . . . . . . . . . . . . . . . . . . . . 25
5.5 Connecting communication interfaces (optional) . . . . . . . . . . . . . . . . . . . . 28
5.5.1 Overview of connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.5.2 Installation of communication cables. . . . . . . . . . . . . . . . . . . . . . . 29
5.5.3 Network connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.5.4 External shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.5.5 External power control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.5.6 Multi-function relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.5.7 Lightning protection monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4
5.5.8 S0 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5.9 Control of self-consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.1 Activating the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.2 Initial start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6. 2 .1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.2.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.3 Description of country-specic menus . . . . . . . . . . . . . . . . . . . . . 44
6.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6. 3 .1 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.3.2 Setting the display language and system time. . . . . . . . . . . . . . . . 45
6.3.3 Setting the network parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.3.4 Conguring the status signaling contact . . . . . . . . . . . . . . . . . . . . 46
6.3.5 Conguring the lightning protection monitor . . . . . . . . . . . . . . . . . 47
6.3.6 Control of self-consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4 Displaying the conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6. 4.1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.4.2 Description of extended functions and parameters . . . . . . . . . . . . 52
6.5 Displaying the measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.6 Registering for MaxView. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.7 Update rmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1 Graphics display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.2 Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.3 Displaying the operating data overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.4 Displaying Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.5 Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.5.1 Displaying the daily statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.5.2 Displaying the monthly statistics. . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.5.3 Displaying the annual statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7.5.4 Displaying the total statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7.5.5 Deleting the statistics values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.6 Displaying information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.7 Displaying the operating status of the inverter . . . . . . . . . . . . . . . . . . . . . . 65
7.7.1 Booting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.7. 2 Mains operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
en
5
8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1 SolarMax Service Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.2 Diagnosis & measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8. 2 .1 General troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.2.2 Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.2.3 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.2.4 Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
8.2.5 Blockings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
9 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
10 Decommissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.1 Instructions for inverter replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.2 Inverter disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.3 Disposing of the inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11 Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
12 Accessories and options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
13 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
6
1 Notes on the present instruction
manual

1.1 Scope

This instruction manual is applicable to the following SolarMax inverters:
Type Item No.
SM4TP 10 006 747 SM5TP2 10 006 736 SM6TP2 10 006 735 SM7TP2 10 006 241

1.2 Target groups

This instruction manual is intended for the operator of the plant and the installer of the PV power plant.
The instructions in chapters 5, 6.2, 8 (troubleshooting actions) and 10 may only be car­ried out by trained electricians (e.g. electricians, electric systems technicians, electrical mechanics, industrial electronics technicians).
The instructions in chapter 4 should only be carried out by specialist transport personnel.

1.3 Where to keep this manual

The plant operator must ensure that this instruction manual is available to the relevant persons at all times. If this original document is lost, an up-to-date version of this instruc­tion manual can be downloaded from our website at any time (www.solarmax.com).
en

1.4 Symbols used

The following safety instructions and general information are used within this instruction manual.
DANGER!
Non-observance of these safety instructions may immediately cause serious injuries or death.
WARNING!
Non-observance of these safety instructions may cause serious injuries.
7
CAUTION!
Non-observance of these safety instructions may cause minor or medium injuries.
ATTENTION!
Non-observance of these safety instructions may cause material damage.
Note
Notes contain additional information or facilitate the inverter operation.

2 Safety

2.1 Intended use

The inverters of the SolarMax TP series are designed exclusively for the conversion of the direct current generated by PV modules into alternating current which conforms to the parameters of the public grid. Any other use, in particular the conversion of direct current from batteries or other storage elements into alternating current is not permissible.
Inverters of the TP series may only be connected to PV generators of protection class II.

2.2 Safety Instructions

DANGER! Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC voltage.
Make sure that all electrical feed-in lines to the inverter are de-energized
before starting any work on the inverter or the feed-in lines.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage.
Never open the inverter while it is in operation.
8
WARNING! Risk of injury from electric arc!
Removing the DC connectors when live can lead to dangerous electric arcs.
Switch off the DC disconnector at the inverter before removing the DC
connectors.
WARNING! A re risk can result from inappropriate repair!
The inverter does not contain any replaceable components. Defective
inverters must be sent to the SolarMax Service Center for repair or dis­posed of in accordance with Section 10.3.

2.3 Symbols on Inverter

Symbol Description
Protective conductor connection
The DC disconnector is switched off (the contacts are open).
The DC disconnector is switched on (the contacts are closed).
Risk of death through high voltages! Only qualied electricians may perform work on the inverter.
en
Caution - hot surfaces!
5 min
Risk of death due to high voltages in the inverter! De-energize the inverter. Proceed to wait for 5 minutes before opening the inverter.
Only qualied electricians may perform work on the inver ter.
Read the operating instructions - Please read and follow the instruc­tions supplied with the inverter. Do not remove any symbols on the inverter. Replace damaged symbols.
CE marking - The inverter complies with the requirements of the European EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC (see Section 11).
9

Symbol Description

GS marking - The inverter complies with the relevant requirements of the German Product Safety Act.
Do not dispose of the inverter and its accessory components in the household waste.
3 Description
3.1 Identication
The inverter can be identied on the basis of the information provided on the nameplate (see Section 3.5).

3.2 Functionality

MPP tracker & grid connection
The SM5TP2, SM6TP2 and SM7TP2 inverters have 2 independent MPP trackers which can be used to connect strings with different characteristics, such as orientation, size and module type. The SM4TP is tted with an MPP tracker. Each MPP tracker can be tted with one string as standard. The grid connection is a three-phase connection.
Automatic operation
Inverter operation is completely automatic and depends on the available output of the PV generator. If there is enough power, the inverter starts mains operation and feeds into the power grid. If there is not enough power available from the PV generator, the inverter disconnects from the grid and shuts down.
Operation
The graphics display with three function keys allows convenient inverter operation and reading of all important operating data. The graphics display is only switched on when the DC input voltage is high enough.
The inverter has congurable functions for grid monitoring, limitation of output and reac­tive power control.
10
Interfaces / remote monitoring
For the purpose of monitoring the PV power plant remotely, the inverter can be connected directly to the Internet via Ethernet.
The inverter is tted with a multi-function relay which can be congured for various pur­poses (status signaling contact, control of self-consumption).
The inverter is tted with interfaces for remote-controlled shutdown and output control (active and reactive power control).
Extended functions
The inverter has functions for grid monitoring, limitation of output, reactive power control and control of self-consumption. These can be congured using MaxTalk2.
Ventilation
The inverter is air cooled. To a large extent, ventilation is passive via the vertical cooling ns on the back of the inverter. The fan on the left-hand side of the inverter (not available with SM4TP and SM5TP2), which is accessible from the outside, sucks in air which is also directed across the cooling ns. All inverters of the TP series are tted with an internal fan.

3.3 Safety installations

Surge protection
The inverter is tted with surge arresters (varistors) at its input and output. Each DC input (plus and minus connection) is tted with a surge arrester. On the AC side, the phases and the neutral conductor are individually secured with surge arresters. The surge arresters have a common gas discharge tube to ground. For further information on the surge arresters, see Section11.
When designing the PV power plant, it may be necessary to provide additional external lightning protection (overvoltage protection). The inverter has an interface for monitoring external lightning protection modules.
en
Fault current monitoring
The inverter has an integrated AC/DC-sensitive leakage current sensor. This recognizes leakage currents generated due to PV module capacities to ground (capacitive ground leakage current) or through insulation faults (for example by touching a pole of the PV generator or a phase). In the case of the permissible leakage current being exceeded, the inverter disconnects from the grid.
Functions for current and output limitation
The inverter limits the DC feed-in current, the output power and the output current.
11
Temperature limitation
480 189
[mm]
361
At ambient temperatures of more than 45°C the equipment temperature may reach more than 80°C. In such cases, the maximum in-feed power is temporarily reduced. When the equipment temperature rises above 85°C, the inverter disconnects from the grid.

3.4 Dimensions

104.5
256.5
Figure 1 Dimensions
12

3.5 Views of the unit

2
1
3
en
4
5
6
8 7
Figure 2 Views of the unit
No. Description
1 DC disconnector 2 Type plate 3 Graphics display 4 Cover 5 Mounting rail 6 Fan (only SM6TP2 & SM7TP2) 7 Cooling ns 8 Connection area (only 2 DC plug connection points at the SM4TP)
13

3.6 Block circuit diagram

** only SM6TP2 and SM7TP2
L1 L2 L3
AC output
U
DC
Booster 1
EMC lter
Inverter
DC
K2K1
DC
EMC lter
LCL lter
AC
Fan **
AC measurement
Internal fan
Inverter control
DC
DC
Booster 2
EMC lter
Control unit
Communication module
DC measurement
Booster control
External energy meter
Monitoring lightning protection
External shutdown
External power control
Multi function relay
RS485
Ethernet
Graphics display
U
+
DC input MPP tracker 1 DC input MPP tracker 2 *
U
I
DC disconnector
+
0
* only SM5TP2, SM6TP2 and SM7TP2
Figure 3 Block circuit diagram
14

4 Installation

4.1 Transporting and storing inverters

Make sure that the ambient conditions during transportation and storage are within the specied limits (for details see Section 11). Only use the original packaging when shipping the inverter.

4.2 Checking the delivery for completeness

Check the contents of the delivered package for completeness and possible damage. In the case of an inadequate delivery, please contact your dealer or the SolarMax Service Center.
1
SolarMax TP-Serie
4TP / 5TP2 / 6TP2 / 7TP2
Gerätedokumentation
Register here: maxview.solarmax.com
3
4
5
6
2
7
8
9
en
Figure 4 Content of delivery
10 11
13
12
14
15
No. Quantity Description
1 1 Inverter 2 1 Instruction manual 3 1 Mounting rail 4 2 External hexagon wood screws 6 x 50 INOX (for the installation of the
5 2 Washers M6 x 18 INOX (for the installation of the inverter) 6 2 Plastic dowels 8 x 40 (for xing in brickwork) 7 2 Phillips head sheet metal screws 4.8 x 13 (for locking the inverter on the
8 6 Locking pins (for plugging unused holes in multiple cable connectors) 9 4 Locking clips (for DC plugs) 10 1 Toothed lock washer M5 11 1 Lug M5 x 10 mm 12 1 Washer M5 13 1 Spring washer M5 14 1 Phillips head screw M5 x 12
inverter)
mounting rail)
2
(for connection of 2nd protective conductor)

4.3 Selecting the installation location

DANGER! Fatal re or explosion hazard!
The inverter is an electrical device with heat generation and the possibility of sparking.
Install the inverter in an environment that is free of ammable gases and
uids.
Never install the inverter near combustible materials. The installation
base must be non-combustible.
Follow the local re safety regulations.
The ambient conditions are specied in the specications, see Section 11.
Location and installation conditions
If possible, select a dry location for installation that is protected from water and snow.Install the inverter in an easily accessible location, so that maintenance work can be
carried out easily.
Do not expose the inverter to direct sunlight.Never install one inverter above another (this can interfere with passive cooling).
16
Maintain the following installation distances:
50
50
20*
50
20
°C
[cm]
Figure 5 Minimum installation distance (20*: only SM4TP and SM5PT2)
The installation base must be vertical. Do not install the inverter in a horizontal or
inclined position.
OK !
Figure 6 Unacceptable mounting positions
The optimal cooling of the inverter is only guaranteed when the cooling ns (see
section 3.5) are absolutely free of dust and dirt.
When installing the inverter on a mast, a mounting plate with at least the same
dimensions as the back of the inverter is needed.
The ambient air around the inverter must be free from dust, salt and ammonium
vapors.
The location must meet the requirements regarding emissions and freedom from
electromagnetic interference.
en
17

4.4 Mounting the inverter

446
[mm]
6.5
The inverter is xed to the wall by a mounting rail. The mounting rail and the necessary xing accessories are included in the delivery package.
Procedure
1. Use the mounting rail as a template for drilling the holes.
2. Align the mounting rail in a horizontal position.
3. Mark 2 places for drilling.
376
26
26
Figure 7 Dimensions of wall mounting bracket
6.5
– For the other measurements see section 3.4.
4. Drill two 8 x 50 mm holes.
5. Fix the mounting rail. – Assembly sequence: plastic dowels 8 x 40, mounting rail, M6 washers, hexagon
head wood screws 6 x 50.
6. Attach the inverter to the mounting rail (see Figure 8).
7. Fix the inverter on both sides using the Phillips head screws:
A
B
C
Figure 8 Attaching and securing the inverter
18

5 Electrical connection

5.1 Open the inverter

For the purpose of connecting the AC and communication lines, the inverter has to be opened.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with dangerously high voltage.
De-energize the inverter completely before carrying out installation work.

5.1.1 Removing the cover

When the cover has been removed, the RJ45 grid sockets, the S0 interface and the inter­face for the lightning protection monitor are directly accessible.
Procedure
1. Disconnect the AC power supply to the inverter.
2. Disconnect all control cables connected to the inverter (status relay, external grid monitoring).
3. Switch off the DC disconnector at the inverter.
en
DANGER! Fatal electric shock hazard!
After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.
Wait for 5 minutes.
4. Loosen the two M5 screws at the bottom of the cover.
5. Remove the cover by gripping it at the bottom and pulling it away.
19
5 min
Figure 9 Removing the cover

5.1.2 Removing the right-hand contact protection

The right-hand contact protection covers the AC connection terminals and the AC feed-in lines.
Procedure
1. Operate the snap lock and pull the right-hand contact protection from its holder.
20
Figure 10 Remove the right-hand contact protection
2. Use a voltage tester to check that all connections in the inverter are de-energized.

5.1.3 Removing the left-hand contact protection

The left-hand contact protection covers the control connections and their supply conduc­tors, which may be charged with dangerously high voltages (external shutdown, status signaling contact).
Procedure
1. Operate the snap lock and pull the left-hand contact protection from its holder.
Figure 11 Removing the left-hand contact protection
2. Use a voltage tester to check that all connections in the inverter are de-energized.
en
21

5.2 Connection area

The connection area with the cover removed and without contact protection.
10
12
11
2
89
7
6
3
4
51
22
Figure 12 Connection area
No. Description
1 Left-hand cable pass-through (control connections) 2 DC connection - MPP tracker 1 3 Middle cable gland (communication and control connections) 4 DC connection for MPP tracker 2 (only with SM5TP2, SM6TP2, SM7TP2) 5 Right-hand cable pass-through (AC feed cable) 6 Connection for 2nd protective conductor 7 AC connection terminals (spring connection) 8 Lightning protection monitoring and S0 interface (spring connection) 9 Multi-function relay (spring connection) 10 RS485 socket (RJ45)
No. Description
11 Ethernet socket (RJ45) 12 External shutdown, external output control (spring connection)

5.3 Connecting the inverter to the mains

DANGER! Fatal electric shock hazard!
Make sure the AC line is not live during connection work.
Connection conditions
Comply with the connecting conditions set by the grid operator in charge.Connectable cable diameters: min. 9.5 mm / max. 12.5 mmPermissible conductor cross-sections:
– exible conductors (with or without ferrule) or rigid conductors: max. 16 mm – exible conductors with ferrules (with plastic sleeves): max. 10 mm
The AC input conductor must be fused. Minimum conductor cross sections and sug-
gested mains fuses:
Minimum conductor cross sections SM4TP SM5TP2 SM6TP2 SM7TP2
Phases L1, L2, L3 Neutral conductor N Protective conductor PE
Recommended mains fuses SM4TP SM5TP2 SM6TP2 SM7TP2
Nominal current 10 A 10 A 13 A 13 A Characteristics C C C C
1.5 mm21.5 mm22.5 mm22.5 mm
2
en
2
2
Temperature resistance of the AC feed cable: ≥ 80 °CMake sure the ambient temperatures for the mains fuses specied by the producer
are not exceeded.
23
WARNING! Risk of death by fire!
Provide separate fuses for each inverter.Do not attach any loads between inverter and fuse.
If you use external residual current devices (RCDs), use the type A or B RCDs with a
nominal leakage current of at least 100 mA. For PV plants with large leakage current capacities, the RCDs to be used should have a nominal leakage current capacity of at least 300 mA.
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
2. Remove the right-hand contact protection as described in Section 5.1. 2.
3. Thread the AC feed cable through the right-hand cable gland.
4. Pull the ferrite (included in the delivery) over the AC feed cable (Figure 13/0).
5
4
3
2
1
24
0
Figure 13 AC connection and connection for 2nd protective conductor
5. Remove an 18 mm length of conductor isolation.
6. Connect the wires as follows: – the protective conductor to the "PE" terminal – the neutral conductor to the "N" terminal – Phases L1, L2 and L3 to the terminals L1, L2 and L3
7. Press and close the levers completely. If a lever is not completely closed, the con-
ductor connection is not secured.
CBA
Abbildungen Klemme: Phoenix Contact
18 mm
Figure 14 Connect the AC terminals.
8. Check the cable connections for rm seating.
9. Tighten the cable gland (wrench size: 34 mm).
10. Check the cable strain relief.
11. Connect the second protective conductor (see Figure 13). – Assembly sequence: toothed lock washer M5 (1), lug (2), washer M5 (3), spring
washer M5 (4), Phillips head screw M5 x 12 (5)
12. Fit the contact protection.
13. Fit the cover of the inverter.

5.4 Connecting the inverter to the PV generator

The inverters of the TP series are operated in dual tracking mode. In the dual tracking mode a separate MPP tracker is available for each DC input.
Connection conditions
Connection of maximum 2 strings (1 string in the case of SM4TP)
DANGER! Risk of death by re!
High return currents can cause a re risk for the PV generator.
When Y plugs are used in order to connect more than 2 strings (more than
1 string in the case of SM4TP), each DC feed cable must be protected individually against dangerous return currents.
Maximum DC input current: 10 A per DC inputMaximum DC input voltage: 900 VSelect the conductor cross-section to suit the system conguration.Exclusively use Wieland PST40i1C connectors (the mating connectors are not
included in the package supplied)
Parallel connection of the MPP trackers is not permitted:
en
25
Figure 15 Unacceptable parallel connection of MPP trackers
Do not t a ground connection to either the negative terminal or the positive terminal
of the PV generator.
Procedure
1. Make sure the DC disconnector and the external AC disconnector are off.
2. Connect the pre-tted DC conductors.
26
1 2
DC− DC+DC+ DC−
Figure 16 DC connection
No. MPP tracker
1 1 2* 2 * only SM5TP2, SM6TP2 and SM7 TP2
3. Use the locking clips (included in the delivery) to secure the plug connectors.
Figure 17 Secure the plug-in connection
Close off any unused DC plug connectors.
> 900
V>
V
Any unused DC plug connectors must be closed off to ensure that the installation com­plies with the IP65 protection rating requirements. Please use the following closing parts made by Wieland (www.wieland-electric.com):
for plug component: order number 05.566.6380.0for socket component: order number 05.566.6480.0
Increasing the overvoltage protection
If you want to increase the overvoltage protection on the DC side using additional external surge arresters, the following connection conditions must be met:
Use a surge arrester with a response voltage of > 900 V.Connect the external surge arresters as follows:
en
V> 900
Figure 18 Increasing the overvoltage protection
Install the connector cables close together to avoid overvoltages in the case of a
> 900 V
900
lightning strike.
Avoid ground loops in the wiring.Wire the earth connections in a star conguration with the neutral point close to the
inverter.
27

5.5 Connecting communication interfaces (optional)

5.5.1 Overview of connections
The connection terminals for the various communication interfaces are illustrated in Figure 19. The RJ45 grid sockets can be seen in Figure 12.
S0+
S0−
BS+
BS−
11
12NC14
NANK5
K2
K6
K3K4K1
Figure 19 Connection terminals for communication
Contact Description
N External shutdown / external power control NA External shutdown K1 External power control K2 K3 K4 K5 K6 External power control NC Not used 11 Multi-function relay (status signaling contact / control of self-consumption) 12 14 S0+ S0 interface (control of self-consumption) S0 BS+ Lightning protection monitor BS
28
5.5.2 Installation of communication cables
To ensure the operational safety of the inverter, the cables have to be installed in the inverter as described in this section of the instructions. The left-hand contact protection covers the cables and connections with dangerously high voltages (> 50 V).
In order to ensure that the inverter remains sealed, the unused apertures in the cable glands must be closed with the locking pins (example see Figure 20 / Pos. 2). The locking pins are included in the delivery package.
5.5.3 Network connections
The inverter can be connected to Ethernet and RS485 networks.
Note
You will nd further details about data communication in the technical infor­mation "MaxComm network". You can download this document from our web­site at: www.solarmax.com; Downloads/Data Communication/MaxComm.
Connection conditions
Connection type: RJ45 socketsUse shielded cables.Connectable cable diameters: min. 5.5 mm / max. 7.0 mm
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1. – Do not remove any contact protection.
2. Route the grid cable through the middle cable gland ( Figure 20 / 1) .
Note
The RJ45 connectors can be pulled through the cable gland.
3. Depending on the type of network, connect the cable either to the "Ethernet" or
"RS485" socket.
en
29
1
2
Figure 20 Connecting the grid cables
4. Close the unused apertures in the multiple cable gland using the locking pins (Figure 20/2).
5. Tighten the multiple cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the cover of the inverter.
5.5.4 External shutdown
This interface can be used to connect the inverter to an external grid monitoring system which disconnects the inverter from the mains grid when this is needed.
While the external grid monitoring signal (the phase voltage) is active at the "NA" contact, the inverter feeds into the grid. When the signal stops, the grid relays K1 and K2 of the inverter are opened (see Figure 3). This immediately disconnects the inverter from the grid.
The interface can only be congured with the free MaxTalk2Pro service software (see Section 12).
Connection conditions
Connectable cable diameters: min. 9.5 mm / max. 12.5 mmConnectable conductor cross-sections: min. 0.25 mmMax. input current: 25 mAMax. input voltage: 230 VAC
2
/ max. 2.5 mm
2
30
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
2. Remove the left-hand contact protection as described in Section 5 .1. 3 .
WARNING! Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection inside the inverter.
Route the connection cable through the left-hand cable gland
(Figure 21 / 1).
3. Connect the wires as follows: – Wire stripping length: 7 mm
1
2
Figure 21 Connection of "external shutdown“
Contact Description
NA Control line N Neutral conductor
4. Close the unused apertures in the multiple cable gland using the locking pins
(Figure 21/2).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the contact protection.
8. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
en
31
5.5.5 External power control
Via this interface the inverter can receive digital signals for the specication of the set­point of active and reactive power. It is possible to connect ripple control receivers to this interface.
The interface is congured with the free MaxTalk2Pro service software (see Section 12).
Figure 22 shows the connection of the ripple control receiver to the interface.
Inverter
N
K6
K5
K4
K3
N
L
I = 25 mA
(230 V)
I max = 150 mA
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 543 2 1
c
b
c
b
a
c
b
a
c
b
a
b
a
K6 K5 K4 K3 K2 K1
Ripple control receiver
Figure 22 Connection diagram of ripple control receiver
Connection conditions
Max. 6 relay contacts can be connectedMax. input voltage: 230 VAC (phase)Connectable cable diameters: min. 9.5 mm / max. 12.5 mmConnectable conductor cross-sections: min. 0.25 mmInput current: 25mAMax. cable length: 200 m
2
K2
K1NA
c
c
b
a
a
/ max. 2.5 mm
2
32
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
2. Remove the left-hand contact protection as described in Section 5 .1. 3 .
WARNING! Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection inside the inverter.
Route the connection cable through the left-hand cable gland
(Figure 23 / 1).
3. Connect the wires as follows: – Wire stripping length: 7 mm
2
en
1
Figure 23 Connection of external power control
Contact Description
K1 Control signal relay K1 K2 Control signal relay K2 K3 Control signal relay K3 K4 Control signal relay K4 K5 Control signal relay K5 K6 Control signal relay K6 N Neutral conductor
4. Close the unused apertures in the multiple cable gland using the locking pins
(Figure 23 / 2 ).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
33
7. Fit the contact protection.
11
NC
8. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.6 Multi-function relay
The multi-function relay can be used as status signaling contact for the remote control of the inverter (see section 6.3.4) or for the control of self-consumption (see section 5.5.9).
12 14
Figure 24 Contact scheme of multi-function relay
Connection conditions
Connectable cable diameters: min. 9.5 mm / max. 12.5 mmConnectable conductor cross-sections: min. 0.25 mmMax. switching voltage: 250 VAC / 30 VDCMax. switching current: 1.5 A (no internal fuse present)Max. cable length: 50 m
Procedure
1. Remove the cover of the inverter as described in section 5.1.1.
2. Remove the left-hand contact protection as described in section 5 .1. 3 .
WARNING! Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection inside the inverter.
Route the connection cable through the left-hand cable gland
(Figure 25 / 1).
2
/ max. 2.5 mm
2
3. Connect the wires as follows. – Wire stripping length: 7 mm
34
1
2
Figure 25 Connection of multi-function relay
Contact Description
11 COM
12 Opener (when used as status signaling contact: opener in the case of error) 14 Closer (when used as status signaling contact: closer in the case of error) NC Not used
4. Close the unused apertures in the multiple cable gland using the locking pins (Figure 25/2).
5. Tighten the middle cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the contact protection.
8. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.7 Lightning protection monitor
This interface can be used for monitoring an external lightning protection module. The conguration is done using the inverter's graphics display (see Section 6.3.5) or with MaxTalk2.
When the remote signaling contact of the lighting protection module connected to the input closes, the inverter displays the corresponding status message/warning on the graphics display. It is possible to connect multiple lightning protection modules in parallel to the lightning protection input.
en
35
Connection conditions
Connectable cable diameters: min. 9.5 mm / max. 12.5 mmConnectable conductor cross-sections: min. 0.25 mmMax. cable length: 50 mDo not connect any external power sources.
2
/ max. 2.5 mm
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1. – Do not remove any contact protection.
2. Route the cable through the middle cable gland (Figure 26 / 1).
3. Connect the wires as follows: – Wire stripping length: 7 mm
Contact Description
BS+ Remote signaling contact of the lightning protection module
BS– COM
(potential-free)
2
36
1
2
Figure 26 Connection of the lightning protection module
4. Close the unused holes in the cable gland using the locking pins (Figure 26 / 2).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.8 S0 interface
In accordance with DIN EN 62053-31 this interface can be used to connect an energy counter to the inverter for the purpose of the control self-consumption (see Section 5.5.9). From experience, SolarMax can recommend the following electronic energy counters: Berg MCi32WP and Berg B23 311.
The S0 interface is congured with the free MaxTalk2Pro service software.
Connection conditions
Energy counters are only permitted with S0 pulses for feed-in (S0 pulses for both
directions of energy ow are not permitted).
The pulse rate of the energy meter must be between 1 000 and 10 000 pulses
per kWh.
Connectable cable diameters: min. 9.5 mm / max. 12.5 mmConnectable conductor cross-sections: min. 0.25 mmMax. cable length: 50 mDo not connect any external power sources.
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1. – Do not remove any contact protection.
2. Route the cable through the middle cable gland (Figure 27 / 1) .
3. Connect the wires as follows: – Wire stripping length: 7 mm – Ensure the polarity is right
Contact Description
S0+ Pulse input (plus pole) S0– COM (minus pole)
2
/ max. 2.5 mm
2
en
37
1
2
Figure 27 Connection of the S0 interface (energy counter)
4. Close the unused holes in the cable gland using the locking pins (Figure 27 / 2).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.9 Control of self-consumption
The inverter has functions for the control of self-consumption. The connection is made via the relevant communication interfaces. Several different operating modes can be selected.
Operating mode Description
Grid feed-in limitation As the inverter controls self-consumption it keeps within a
Pac electric meter The inverter controls the consumer loads in accordance with the
Pac inverter The inverter controls the consumer loads in accordance with its
maximum feed-in power at the grid connection point. The power output is measured with an energy counter.
power fed into the grid. The power output is measured with an energy counter.
output power.
38
5.5.9.1 Grid feed-in limitation
R
For the connection diagram in "Grid feed-in limitation" mode see Figure 28: the energy counter that measures the power fed in at the grid connection point is connected to the S0 interface of the inverter.
The grid feed-in limitation is congured using the free MaxTalk2 Pro service software (see Section 12).
12NC14
PV
N
S0+
11
BS+
S0−
BS−
kWh
kWh
Inv
60
80
40
20
100
0
120
°C
Figure 28 Wiring in "Grid feed-in limitation" operating mode
Legend: R: consumer / Inv: inverter / PV: PV generator / N: grid connection point / kWh: energy counter
en
Procedure
Connect the energy counter as described in Section 5.5.8.Use MaxTalk2Pro to congure the max. feed-in power and the S0 interface (electric
meter).
39
5.5.9.2 Pac electric meter
Connection diagram for "Pac electric meter" operating mode see Figure 29: the con­sumer loads are controlled via the inverter's multi-function relay. For example, the control voltage for a contactor or a relay can be switched on and off. The energy counter, which measures the fed in power at the grid connection point, is connected to the S0 interface of the inverter.
The "Pac electric meter" operating mode can be congured on the inverter's graphics display or using MaxTalk 2.
12NC14
PV
N
S0+
11
BS+
S0−
BS−
R
60
80
40
20
100
0
120
°C
Inv
kWh kWh
K
Figure 29 Wiring in "Pac electric meter" operating mode
Legend: R: consumer / Inv: inverter / PV: PV generator / N: grid connection point / kWh: energy counter / K: contactor, relay
Procedure
Connect the multi-function relay as described in Section 5.5.6.Connect the energy counter as described in Section 5.5.8.Congure the control of self-consumption as described in Section 6.3.6.1.Use MaxTalk2Pro to congure the S0 interface (electric meter).
40
5.5.9.3 Pac inverter
R
Connection diagram for "Pac inverter" operating mode see Figure 30: the consumer loads are controlled via the inverter's multi-function relay. For example, the control voltage for a contactor or a relay can be switched on and off.
The "Pac inverter" operating mode can be congured on the inverter's graphics display or using MaxTalk 2.
en
12NC14
PV
N
S0+
11
BS+
S0−
BS−
Inv
60
80
40
20
100
0
120
°C
kWh kWh
K
Figure 30 Wiring in "Pac inverter" operating mode
Legend: R: consumer / Inv: inverter / PV: PV generator / N: grid connection point / K: contactor, relay
Procedure
Connect the multi-function relay as described in Section 5.5.6.Congure the control of self-consumption as described in Section 6.3.6.2.
41

6 Commissioning

6.1 Activating the inverter

Procedure
1. Check that the cover is installed. – If the cover is not tted, close the inverter as follows: – t the left-hand and right-hand contact protection in the inverter; – then t the cover
2. Switch on the DC disconnector at the inverter.
Figure 31 Switching on the DC disconnector
– The graphics display shows the "Overview". The status message "Start up..."
appears.
3. Switch on the AC power supply to the inverter. – Wait for the "Mains operation" status message to be displayed. This indicates that
the inverter is in mains operation.
– During initial start-up of the inverter, instead of the “Overview” menu, an “Initial
setup” menu appears (see Section 6.2).
42

6.2 Initial start-up

This section describes the initial start-up of the inverter and the graphics display set­tings required for this purpose. Once initial start-up has been successfully completed, the inverter will start feeding into the mains grid.

6.2.1 Requirements

The inverter has been installed and the electricity has been connected.The contact protection and cover of the inverter are tted.There is sufcient solar irradiation (sufciently high DC input voltage).
Note
Entering an incorrect country setting may lead to problems regarding
inverter operation and to the withdrawal of the operating license by the respective grid operator.
Contact your grid operator or the SolarMax Service Center if you have any
doubt regarding the settings you must select.
You can restart initial start-up by pressing in the "Conrmation"
menu at any time.
6.2.2 Procedure
1. Switch on the inverter as described in Section 6 .1. The "Initial setup" menu will be displayed:
Figure 32 Selecting the display language and updating the system time
2. Select the display language from the "Language" menu.
3. If necessary, update the time and the date.
– The inverter saves the date entered as the initial start-up date. – The "Country" menu will be displayed:
en
Figure 33 Selecting the country setting
4. Select the correct country setting.
– Press to conrm your entry. – Depending on the country setting selected, additional menus may be displayed
(see Section 6.2.3).
– The "Conrmation" menu is then displayed.
43
5. Check the data in the "Conrmation" menu.
6. To complete initial start-up, press . – The main menu will then be displayed (see Section 7.4).
6.2.3 Description of country-specic menus
Depending on the country setting, additional menus will be displayed during initial start-up.
Country: Germany Menu Setting Description
Plant system rating > 3.68 – 13.8kVA The plant system rating is higher than 3.68 kVA
CosPhi(Pac) - QMCPP Inactive
On
and/or does not exceed 13.8 kVA. The "cosφ(Pac)" function is deactivated (no
reactive power generated, cosφ=1). The "cosφ(Pac)" function for reactive power
generation is activated.

6.3 Settings

Different communication parameters and monitoring functions can be set in the "Set­tings" menu of the graphics display. All settings except the IP mode can also be made using the MaxTalk2 service software.

6.3.1 Changing parameters

The parameters in the "Settings" menu can be changed as follows:
1. In the Main Menu select the "Settings" menu.
44
Figure 34 "Settings" menu
2. Press to select the parameter (e.g. "Time").
3. Press to change to the editing mode.
4. Press to select the required number.
Figure 35 Selecting the number and changing the value
5. Press to increase the value of the selected number.
6. Press to select the next number.
7. Press to conrm the parameter value.
8. Press to return to the Main Menu.
6.3.2 Setting the display language and system time
The inverter's display language and system time can be changed in the "Settings" menu.
1. Select the "Settings" menu:
Figure 36 Changing the display language and system time
2. Select a parameter:
Parameter Description
Language Selection of the display language: German, English, French, Italian
or Spanish. The display language selection does not depend on the
selected country. Time Date and system time of the inverter Date
en
3. Change the parameter as described in Section 6.3.1.
45
6.3.3 Setting the network parameters
Device address
In order to communicate via an RS485 or Ethernet interface, the inverter needs a unique device address on the network.
1. In the "Main menu" select the "Network" menu.
2. Select the "Device address" parameter.
3. Congure the parameter:
Parameter Description Value range
Device address Device address of inverter 1…249
Configuring the Ethernet interface
In addition to the device address, the following settings must be made to communicate via Ethernet:
1. In the "Main menu" select the "Network" menu.
2. In the "IP mode", select the required setting:
Setting Description
DHCP client The inverter is a DHCP client and is connected to a network with
Static The inverter is connected to a network with static IP addresses.
3. If appropriate, congure the following parameters. These settings are only required in "Static" IP mode (see step 2):
Parameter Description Value range
IP IP address 192.168.1.123*
Gateway Gateway of inverter 192 .168 .1.1* TCP port TCP port of inverter 12345* DNS1 Domain name server 1 192.168.1.1* DNS2 Domain name server 2 192 .16 8.1.1* Netmask Subnet mask 255.255.255.0* * Factory settings
4. Check whether the indicator for the Ethernet connection appears on the graphics display (see Section 7.1).
DHCP server (factory setting).
46
6.3.4 Conguring the status signaling contact
When the multi-function relay is used as status signaling contact, the operating mode and the delay time can be congured.
Procedure
1. In the "Settings menu" select the "MF relay" menu.
2. In "MF relay" select the "Status relay" setting.
3. Select the required setting under "Mode":
Setting Beschreibung
Off The status signaling contact is always open. Grid If the inverter starts mains operation, the status signaling contact
is closed immediately and remains closed as long as the inverter feeds into the grid. After the unit disconnects from the mains, the status signaling contact opens after expiry of the adjustable delay.
Error When a warning, a failure, or a device error occurs on the inverter
(for error messages see Section 8.2) the status signaling contact is closed after expiry of the adjustable delay time. The status signaling contact is immediately opened when the fault is no longer present (factory setting).
On When the inverter is switched on (suf ciently high DC input
voltage), the status signaling contact closes. The status signaling contact will not re-open unless the inver ter is switched off (DC input voltage too low).
4. Select "Delay".
5. Adjust the required delay time:
Parameter Description Value range Unit
Delay Delay time of status relay 0…9 9 min
6.3.5 Conguring the lightning protection monitor
The operating mode of the lightning protection monitor can be congured.
Procedure
1. In the "Settings" menu, select the "SPD Monitor" menu.
2. Select the required setting under "Mode":
Setting Description
Off The lightning protection monitoring is deactivated. Warning When the lightning protection operates, the warning "SPD failure"
is displayed (on the graphics display and in MaxTalk2). The inverter will continue to feed into the grid. The status signaling contact will be closed (factory setting).
Error When the lightning protection operates, the status message "SPD
failure" is displayed (on the graphics display and in MaxTalk). The inverter will disconnect from the mains. The status signaling contact will be closed.
en
47
6.3.6 Control of self-consumption
Status of multi function relay [on/off]
The control of self-consumption functions can be congured on the inverter's graphics display. The S0 interface for the connection of the energy counter and the "Grid feed-in limitation" operating mode for the control of self-consumption can only be congured with MaxTalk 2 Pro.
6.3.6.1 Conguring the "Pac electric meter" operating mode
The "Pac electric meter" operating mode for the control of self-consumption can be con­gured to suit the user's requirements. The functionality is illustrated in Figure 37.
Pac [W]
10000
8000
6000
Enable threshold
4000
2000
0
Start time End time
Figure 37 "Pac electric meter" operating mode
Enable delay
Disable threshold
Energy meter - Pac [W]
Status of multi function relay
On
Off
t
The time window of the control of self-consumption is dened by the "Start time" and "End time" parameters. Outside this time window the control of self-consumption is inactive.
When control of self-consumption is active, the multi-function relay closes when the power output measured with the energy counter at the grid connection point reaches the "Enable threshold". The consumers are then switched on. The "Enable delay" timer can be used to delay activation. When the output power falls below the "Disable threshold", the multi-function relay opens. The consumers are switched off.
Procedure
1. In the "Settings menu" select the "MF relay" menu.
2. In "MF relay" select the "Self-consumption" setting.
3. Under "Mode" select the "Pac electric meter" operating mode.
4. Congure the parameters:
48
Parameter Description Value range Unit
Enable threshold Activation value 1 000 … 10 000 W Disable threshold De-activation value 1 00 0 … 10 00 0 W Enable delay Activation delay 0 … 60 min Start time Activation time 00:00 … 23:59 hh:mm End time De-activation time
5. Use MaxTalk2Pro to congure the S0 interface (energy counter).
Procedure using MaxTalk 2
1. Start MaxTalk 2
2. Connect MaxTalk 2 to the inverter.
3. Select the inverter in the plant tree.
4. In the "Device" menu, click "Settings". The "Settings" tab will be opened.
5. In the “Mode” menu (Multi-function relay) select the "PacEm" setting.
6. Congure the parameters.
6.3.6.2 Conguring the "Pac inverter" operating mode
The "Pac inverter" operating mode for the control of self-consumption can be congured to suit the user's requirements. The functionality is illustrated in Figure 38.
Pac [W]
5000
4000
3000
Enable threshold
2000
1000
0
Start time End time
Enable delay
Disable threshold
Output of the inverter - Pac [W] Status of multi function relay [on/off]
Figure 38 "Pac inverter" operating mode
The time window of the control of self-consumption is dened by the "Start time" and "End time" parameters. Outside this time window the inverter's control of self-consump­tion is inactive.
Status of multi function relay
On
Off
t
en
49
When control of self-consumption is active, the multi-function relay closes when the inverter's output power reaches the "Enable threshold". The consumers are then switched on. The "Enable delay" timer can be used to delay activation. When the output power falls below the "Disable threshold", the multi-function relay opens. The consumers are switched off.
Procedure
1. In the "Settings" menu select the "MF relay" submenu.
2. In "MF relay" select the "Self-consumption" setting.
3. In "Mode" select the "Pac inverter" operating mode.
4. Congure the parameters:
Parameter Description Value range Unit
Enable threshold Activation value 100 … 10 000 W Disable threshold De-activation value 100 … 10 000 W Enable delay Activation delay 0 … 60 min Start time Activation time 00:00 … 23:59 hh:mm End time De-activation time
Procedure using MaxTalk 2
1. Start MaxTalk 2.
2. Connect MaxTalk 2 to the inverter.
3. Select the inverter in the plant tree.
4. In the "Device" menu, click "Settings". The "Settings" tab will be opened.
5. In the "Mode" menu (Multi-function relay) select the "PacInv" setting.
6. Congure the parameters.
50
6.4 Displaying the conguration
All available operating parameters, standard-specic functions and their parameteriza­tion can be retrieved in the "Conguration" menu. Conguration of the standard-specic functions depends on the country setting selected.
Note
The MaxTalk 2 Pro service and communication software makes it possible for authorized personnel to individually adjust the operating parameters (see Section 12).

6.4.1 Procedure

1. In the Main Menu, select the "Conguration" menu.
Figure 39 "Configuration" menu
2. Press to select the parameter:
Entry Description
Country Country setting selected at the time of initial start-up. Plant system rating Plant system rating selected at initial start-up (only available
with the "Germany" country setting).
SSF Menu of standard-specic functions and parameters
en
– The "SSF" menu contans the following sub-menus.
Menu Description
External input Display of external control functions (external shutdown and
external output control).
Inverter start-up Those functions are displayed which are active before the
inverter is connected to the grid (start conditions).
Grid operation Those functions are displayed which are active during the
inverter's grid operation (grid monitoring).
Limitation Those functions are displayed which limit the inverter's output
values, such as active and reactive power and output current (output limitation).
51
Menu Description
Reactive power Those functions are displayed that have an impact on the
Reference parameters Display of nominal values and reference values.
reactive power taken up or given out by the inverter (reactive power control).
3. Press to conrm the selection.
– Section 6.4.2 contains the description of the SSF functions and parameters.
4. Press to return to the Main Menu.
6.4.2 Description of extended functions and parameters
This section contains the description of the functions and parameters available from the "SSF" menu.
External input
Functions and parameters of the "External input" sub-menu:
Function / parameter Description Unit / status EISD Monitoring of "external deactivation" input (NA and
N inputs) EISD-ENA EISD function status Disabled/enabled EPC Output control by ripple control receiver or similar
external control unit EPC-ENA EPC function status Disabled/enabled
Inverter start-up
Functions and parameters of the "Inverter start-up" sub-menu:
Function / parameter Description Unit / status PVGIT Checking the insulation resistance of the PV gener-
ator to ground PV GIT-E NA PVGIT function status Disabled/enabled PV GIT-TH R Minimum permissible insulation resistance Ω RCMUT Checking the integrated fault current monitoring ­RCMUT-ENA RCMUT function status Disabled/enabled IST Checking the grid relay IS T-EN A IST function status Disabled/enabled GPT Checking the grid parameters ­GP T- ENA GPT function status Disabled/enabled GPTVMIN-THR Minimum permissible mains voltage V GP T V M A X-T HR Maximum permissible mains voltage V GPTFMIN-THR Minimum permissible mains frequency Hz GPTFMAX-THR Maximum permissible mains frequency Hz
-
-
-
52
Function / parameter Description Unit / status
GP T-MO T Checking duration s
Grid operation
Functions and parameters of the "Grid operation" sub-menu:
Function / parameter Description Unit / status GVMMIN1 Checking the minimum permissible mains voltage
(limit 1) GVMMIN1-ENA GVMMIN1 function status Disabled/enabled GVMMIN1-THR Limit value V GVMMIN1-DLY Trip time s GVMMA X1 Checking the maximum permissible mains voltage
(limit 1) GVMMAX1-ENA GVMMAX1 function status Disabled/enabled GV MMAX1-T HR Limit value V GV MMA X1-DLY Tri p t im e s GVMMIN2 Checking the minimum permissible mains voltage
(limit 2) GVMMIN2-ENA GVMMIN2 function status Disabled/enabled GVMMIN2-THR Limit value V GVMMIN2-DLY Trip time s GVMMAX2 Checking the maximum permissible mains voltage
(limit 2) GVMMAX2-ENA GVMMA X2 function status Disabled/enabled GV MMAX2-THR Limit value V GV MM A X 2-DLY Tri p t im e s GVM10AMA X Checking the maximum permissible average value
for mains voltage over the last 10 minutes GVM10AMAX-ENA GVM10AMAX function status Disabled/enabled GV M10A M A X-T H R Limit value V GV M10AM A X-DLY Trip time s GFMMIN1 Checking the minimum permissible mains fre-
quency (limit 1) GFMMIN1-ENA GFMMIN1 function status Disabled/enabled GFMMIN1-THR Limit value Hz GFMMIN1-DLY Tr ip time s GFMMA X1 Checking the maximum permissible mains fre-
quency (limit 1) GFMMAX1-ENA GFMMAX1 function status Disabled/enabled GF MMAX1-T HR Limit value Hz GF MM A X1-DLY Tr ip time s
-
-
-
-
V
-
-
en
53
Function / parameter Description Unit / status GFMMIN2 Checking the minimum permissible mains fre-
quency (limit 2) GFMMIN2-ENA GFMMIN2 function status Disabled/enabled GFMMIN2-THR Limit value Hz GFMMIN2-DLY Tr ip time s GFMMAX2 Checking the maximum permissible mains fre-
quency (limit 2) GFMMAX2-ENA GFMMAX2 function status Disabled/enabled GF MMAX2-THR Limit value Hz GFMM A X2-DLY Trip time s AIS Detection of island operation ­AIS-ENA AIS function status Disabled/enabled AI S- DLY Tri p t im e s RBCM Monitoring the continuous leakage current ­RBCM-ENA RBCM function status Disabled/enabled RB CM-T HR Maximum permissible leakage current A RSCM Monitoring the leakage current step value ­RSCM-ENA RSCM function status Disabled/enabled DCCIM Monitoring the DC component in the AC current ­DCCIM-ENA DCCIM function status Disabled/enabled DCCIM-THR Maximum permissible DC component in AC current A DCCIM-DLY Trip t ime s
-
-
Limitation
Functions and parameters of the "Limitation" sub-menu:
Function / parameter Description Unit / status ACPPL Maximum increase of the active power during grid
connection ACPPL-ENA ACPPL function status Disabled/enabled ACPPL-MGDT Increase % of Pac nom/
ACPPL-INI ACPPL at every start-up Disabled/enabled ACPPL-RCN ACPPL at boot after grid disconnection through
coupler breaker ACPL Limitation of active output power ­AC P L- L MT Limit value W APPL Limit of the apparent power ­APPL-LMT Limit value VA OCL Limitation of the output current ­OC L- L MT Limit value A
-
min
Disabled/enabled
54
Function / parameter Description Unit / status PFLM2 P(f) mode 2 -
PFLM2-STRTFQ Start frequency Hz PFLM2-RDN Reduction of active power
PFLM2-RNC Increase to rated output power % of Pac nom/
% of PM/Hz
min
Reactive power
Functions and parameters of the "Reactive power" sub-menu:
Function / parameter Description Unit / status QMO-AM Reactive power control 0=OFF QMCQ Reactive power mode constant "Q" -
QMCQ-QSV Reactive power value % of Pac nom
QMCQ-VLE Status of the voltage-dependent reactive power
QMCQ-VLIH Upper limit value of the mains voltage V QMCQ-VLOL Lower limit value of the mains voltage V QMCQ-PLE Status of the active power-dependent reactive
QMCQ-PLI Upper limit value of the active power W QMCQ-PLO Lower limit value of the active power W
QMCPP
QMCPP-PSP1…PSP10 Characteristic values 1 to 10 of Pac active power % of Pac nom QMCPP-CPSP1…
CP SP 10 QMCPP-VLE Status of mains voltage-dependent reactive power
QMCPP-VLIH Upper limit value of the mains voltage V QMCPP-VLOL Lower limit value of the mains voltage V
QMCCP
QMCCP-CPSV QMCCP-VLE Status of mains voltage-dependent reactive power
QMCCP-VLIH Upper limit value of the mains voltage V QMCCP-VLOL Lower limit value of the mains voltage V QMCCP-PLE Status of active power-dependent reactive power
QMCCP-PLI Upper limit value of the active power W QMCCP-PLO Lower limit value of the active power W QMQU1 Reactive power mode "Q(Vac) mode 1" ­QMQU1-VSP1 to VSP10 Characteristic values 1 to 10 of mains voltage (Vac) V
control hysteresis for QMCQ
power control hysteresis for QMCQ
Reactive power mode "cosφ(Pac)"
Characteristic values 1 to 10 of power factor cosφ
control hysteresis for QMCPP
Reactive power mode "cosφ" cosφ value
control hysteresis for QMCCP
control hysteresis for QMCCP
[OEX/UEX] Disabled/enabled
Disabled/enabled
-
- [UEX/OEX]
Disabled/enabled
-
- [UEX/OEX] Disabled/enabled
-
en
55
Function / parameter Description Unit / status
QMQU1-CPSP1 to CP SP 10
QMQU1_D LY Delay time when mains voltage ( Vac) changes s QMQU1-V LE Status of active power-dependent reactive power
QMQU1-V LI Active power switch on value % of Pac nom QMQU1-V LO Active power switch off value % of Pac nom QMQU2 Reactive power mode "Q(Vac) mode 2" ­QMQU2-UPQ Upper reactive power value (OEX) % of Pac nom QMQU2-LOQ Lower reactive power value (UEX ) % of Pac nom QMQU2-UPV LI Mains voltage switch on value for QMQU2-UPQ V QMQU2-UPV LO Mains voltage switch off value for QMQU2-UPQ V QMQU2-LOVLI Mains voltage switch on value for QMQU2-LOQ V QMQU2-LOVLO Mains voltage switch off value for QMQU2-LOQ V QMQU2-PLE Status of active power-dependent reactive power
QMQU2-PLI Active power switch on value % of Pac nom QMQU2-PLO Active power switch off value % of Pac nom
Characteristic values 1 to 10 of reactive power Q % of Pac nom
[UEX/OEX]
Disabled/enabled
control hysteresis for QMQU1
Disabled/enabled
control hysteresis for QMQU2
Reference parameters
Functions and parameters of the "Reference parameters" sub-menu:
Function / parameter Description Unit NAP Rated output power (Pac nom) -
NAP-VAL Value W NOC Rated output current ­NOC-VAL Value A GCD Coupler breaker switch delay ­GCD-CDLY Trip t ime s
56

6.5 Displaying the measured values

The current measured inverter values can be accessed in the “Measured values” menu.
1. In the main menu, select the "Measured values" menu.
Figure 40 "Measured values" menu
2. Press or to scroll through the measured values:
Measured value Description Unit
Vdc 1, Vdc 2 Idc / Idc1 / Idc2* Pdc / Pdc1 / Pdc2* Vac VacL1 / VacL2 /
VacL3 Iac IacL1 / IacL2 / IacL3 s Pac Q cos
φ
Pac electric meter* * Frequency Temperatur e * only available with SM5TP2, SM6TP2 and SM7TP2
** is only displayed when congured accordingly
Input voltage to tracker 1 / to tracker 2 V Total input current / to tracker 1 / to tracker 2 A Total input power / to tracker 1 / to tracker 2 W Output voltage V Phase voltage L1 / L2 / L3 V
Total output current A Phase current L1 / L2 / L3 A Apparent output power VA Output power W Reactive power (+: overexcited / −: underexcited) var Power factor (OEX: overexcited / UEX: underexcited) ­Measured value of external energy counter W Mains frequency Hz Equipment temperature °C
en
3. Press to return to the Main Menu.
Note
The measured inverter values are not suitable for billing purposes or calcu­lating the efciency. The measuring error may amount to up to ±5% depending on the measured value. Only the measured values of a calibrated electricity meter can be relied upon for billing purposes.
57
MaxTalk2 measured values
The following additional values can be viewed with the MaxTalk 2 service software:
Measured value Description Unit
Vac 10 min 10 minute average value of the mains voltage V Iac mean Mean value of output current A Ierr Effective value of leakage current mA Ierr DC Direct current component of leakage current mA

6.6 Registering for MaxView

Register for the free web-based MaxView application. With MaxView it is possible to view and graphically display the yield data of your PV power plant from anywhere.
Note
Frequently asked questions about MaxView and the replies to these can be found on our website at https://maxview.solarmax.com/faq.xhtml.
Procedure
1. Connect the inverter to the internet via the Ethernet interface (see Sections 5.5.3 and
6.3.3).
2. Enter your registration data in a web browser under https://maxview.solarmax.com.
3. Learn about the various functions of MaxView.
6.7 Update rmware
The inverter rmware can be updated with the help of the MaxTalk 2 service software. For further information, please refer to the MaxTalk 2 operating manual, which you can download from our website (www.solarmax.com; Downloads/Software/MaxTalk 2).
The current rmware le for the inverters of the TP series is available from our website (www.solarmax.com, Downloads/String inverters/TP series/Software).
58

7 Operation

7.1 Graphics display

The graphics display shows the system values, status information, and the inverter’s fault messages. The graphics display can be used for obtaining information on the current operating status, accessing the integrated data logger and entering various settings on the inverter.
5
4
1
2
3
Figure 41 Graphics display with the standard "Overview" display
No. Description
1 Graphics display with backlighting 2 Status LED: operating status display (see Section 7.7) 3 Function keys (membrane keypad) 4 Display with Ethernet connection (link display) 5 Symbol for data communication
en
The function keys can be used for navigating within the menu structure:
Symbol Description
Select menu or parameter
Edit parameter
Highlight number (parameter editing) Increase highlighted number / select menu or parameter
Confirm
Cancel
59

7.2 Menu structure

Overview
Main menu
Statistics
Days
Months
Years
Total
Reset
* is only displayed when congured accordingly
Information
Measured values
Conguration
SSF
External input
Inverter start-up
Grid operation
Limitation
Reactive power
Reference parameter
Settings
Language
Time
Date
Network
Device adress
IP-Mode
IP
Netmask
Gateway
TCP Port
DNS1
DNS2
MF Relay
Off
Status relay
Selfconsumption
Grid Feed-In limitation*
Pac electric meter
Pac inverter
SPD Monitor
60
Figure 42 Menu structure of graphics display

7.3 Displaying the operating data overview

The overview shows the most important operating data of the inverter. The graphics display automatically switches to the "Overview" if no function button is pressed for 120 seconds.
1. In the Main Menu, select the "Overview" menu.
Figure 43 "Overview" menu
Display Description
19.06.2013 / 11:44:35 Date and system time (examples) Pac Current output power [W] Today Daily yield [kWh] Tot al Total yield since commissioning [kWh] State Operating status of inverter (see Section 7.7 )

7.4 Displaying Main Menu

From the "Main menu", you can open all menus.
1. In order to switch from "Overview" to the "Main menu", press any function key.
en
Figure 44 Main Menu
2. Press or to select the menu.
3. Press to conrm the selection.
61

7.5 Statistics

The "Statistics" menu can be used for accessing the inverter's data logger. The data logger saves the statistics values of the past 25 years. The daily, monthly, yearly and total statistics can be displayed. All statistics values can be deleted.

7.5.1 Displaying the daily statistics

The daily statistics displays the statistics values for the last 31 days.
1. In the "Statistics" menu, select the "Day" sub-menu.
Figure 45 Daily statistics
2. Press or to select the day:
Statistics value Description
Yield Daily yield [kWh] Maximum Fed-in maximum power [ W] Hours Operating hours in the "Mains operation" status
3. Press to return to the "Statistics" menu.
62

7.5. 2 Displaying the monthly statistics

The monthly statistics displays the statistics values for the last 12 months.
1. In the "Statistics" menu, select the "Month" sub-menu.
Figure 46 Monthly statistics
2. Press or to select the month:
Statistics value Description
Yield Monthly yield [kWh] Maximum Fed-in maximum power [ W] Hours Operating hours in the "Mains operation" status
3. Press to return to the "Statistics" menu.

7.5.3 Displaying the annual statistics

The annual statistics displays the statistics values for the last 25 years.
1. In the "Statistics" menu, select the "Year" sub-menu.
Figure 47 Annual statistics
2. Press or to select the year:
Statistics value Description
Yield Annual yield [kWh] Maximum Fed-in maximum power [ W] Hours Operating hours in the "Mains operation" status
en
3. Press to return to the "Statistics" menu.

7.5.4 Displaying the total statistics

The total statistics shows the statistics values since commissioning.
1. In the "Statistics" menu, select the "Total" sub-menu.
Figure 48 Total statistics
63
Statistics value Description
Yield Total yield [kWh] Hours Total hours in the operating status "Mains operation"
2. Press to return to the "Statistics" menu.

7.5.5 Deleting the statistics values

The statistics values of the data logger can be deleted.
1. In the "Statistics" menu, select the "Reset" sub-menu.
Figure 49 Resetting the inverter's data logger
Note
The deletion process cannot be undone!
2. Press to cancel the deletion process.
3. Press to delete all statistics values.
64

7.6 Displaying information

This menu displays information about the inverter. The menu can be used to identify the inverter.
1. In the Main Menu, select the "Information" menu.
Figure 50 "Information" menu
2. Press or to scroll.
Display Description
Device type Inverter type Serial No. Inverter serial number Firmware Firmware version installed in the inverter State Current operating status Warning Current warning message Commissioning Date of initial start-up Operating hours Total operating hours in mains operation MAC address MAC address of the inverter
3. Press to return to the Main Menu.

7.7 Displaying the operating status of the inverter

The status LED (Figure 41/No. 2) signals the current operating status of the inverter by its different signal colors. The status message, which gives a more detailed description of the operating status, is displayed at the graphics display.
In addition to the status messages, the inverter also displays warnings. Warnings result from device errors or external failures. The inverter continues to feed power into the grid, but it is possible that yield is reduced. Warnings are independent of the operating status and are displayed on the graphics display alternately with the current status message.
Status LED Operating status Description
Off
Flashes green
Green
Flashes orange
Orange
Red
Flashes red
- Inverter is switched off
Booting Inverter is star ting up
Mains operation Mains feed-in (normal operation)
-
Failure
Error
Blocked
Warning no grid disconnection
External failure grid disconnection
Device error grid disconnection
Inverter is blocked grid disconnection
en
The "Fault", "Error", and "Blocked" operating status messages, as well as the warnings, usually require certain measures to be carried out by the qualied electrician in charge (see Section 8).
65

7.7.1 Booting

Status LED: ashes green
Status message Description
Irradiation too low The solar irradiation or rather the available output is too low for
Startup… The inverter checks the internal hardware and software compo-
Restar t delay The inverter delays connection to the grid (af ter a disconnection
mains operation.
nents before connecting to the mains.
from the grid or when booting).

7.7. 2 Mains operation

The status LED lights up green.
Status message Description
Maximum output power The inverter limits the in-feed power to the maximum permissible
Mains operation The inverter is in feed mode. Idc limitation The inverter limits the PV generator current to the maximum
Iac limitation The inverter limits the output power to the maximum permissible value
Restar t limitation Following an external output limitation the inverter increases the
Frequency limitation The inverter temporarily limits the active power owing to an active
External limitation The inverter's fed-in active power is limited by external output
Temperature limitation The output power is temporarily reduced in order to limit the
value. This may occur if the PV generator is oversized.
permissible value. This may occur if the PV generator is designed such that the current at Maximum Power Point (MPP) exceeds the maximum permissible input current of the inverter.
(where the PV generator is oversized).
active power with dened progression (Pac progression and/or Soft Start).
frequency-dependent power reduction.
control.
inverter's temperature.
66

8 Troubleshooting

8.1 SolarMax Service Center

If you have technical questions or difculties, our Service Center will be happy to help you. To do that we need the following information:
Device typeSerial number (S/N)Installation locationInformation about the failure you are experiencing (status message, etc.)
Contacting the SolarMax Service Center
The contact details of the SolarMax Service Center can be found on the back of this instruction manual.
Sputnik Engineering AG Länggasse 85 CH-2504 Biel/Bienne

8.2 Diagnosis & measures

The following tables describe possible actions for remedying faults. If the actions sug­gested do not correct the fault, please contact the SolarMax Service Center.

8.2.1 General troubleshooting

Problem Cause Actions
The graphics display remains blank
The graphics display only ashes briey.
The DC disconnector is switched off.
The irradiation is too low. Wait until irradiation is high
The strings are interrupted. Check the PV generator and
It is possible that the inverter is defective.
The irradiation is too low. Wait until irradiation is high
Switch on the DC disconnector.
enough.
eliminate the interruption. Contact the SolarMax Service
Center.
enough.
en
67
8.2.2 Warnings
The status LED ashes orange.
Warning Cause Actions
Temperature limitation The output power is temporarily
reduced in order to limit the inverter's temperature.
Fan failure The external or internal fan is
defective or soiled.
RTC error Date and time in the RTC (real-
time clock) were reset due to a malfunction.
Firmware mismatch The rmware versions of the
inverter controllers do not match.
Ensure that the recommended maximum ambient temperature is not exceeded and that the cooling ns are free from dust and dirt.
Contact the SolarMax Service Center.
Set the date and time (see Section 6.3.2). If this problem occurs frequently, contact the SolarMax Service Center.
Contact the SolarMax Service Center.
Flash error An error has occurred in the ash
memor y.
SPD failure A signal is active at the "lightning
protection monitoring" interface (inputs BS+ and BS-).
Electric meter failure The communication between
energy counter and inverter is interrupted.
Contact the SolarMax Service Center.
Check the external lightning protection module.
Check the connection cable and/or the energy counter.
8.2.3 Faults
The status LED lights up orange.
Note
MaxTalk2 can be used to display the last error messages.
Status message Cause Actions
Vdc too high The DC input voltage of the
inverter is too high.
Ierr too high The leakage current has exceeded
the admissible absolute limit value RB CM-T HR.
Ierr step to high The leakage current has exceeded
the permissible RSCM step value.
No mains There is no mains voltage. Check the AC conductor
Switch of f the DC discon­nector. Check the PV genera­tor’s conguration.
Check the PV generator.
(fuses).
68
Status message Cause Actions
Frequency too high The mains frequency is outside
Frequency too low The mains frequency is outside the
Mains error The inverter detects island mode. If this problem recurs, contact
Vac too high The mains voltage is outside the
Vac too low The mains voltage is outside the
Vac 10 min too high The maximum 10-minute average
DC insulation fault The insulation resistance of the PV
Error ext. input 1 The external grid monitoring
the GFMMAX1-THR, GFM­MAX2-THR or GPTFMA X-THR limit values.
GFMMIN1-THR, GFMMIN2-THR or GPTFMIN-THR limit values.
GV MMAX1-T HR, GV MMA X2-T HR or GPT VM AX-THR limit values.
GVMMIN1-THR, GVMMIN2-THR or GPT VMIN-THR limit values.
value of the mains voltage GVM10AMAX-THR is too high.
generator to ground is too low. Phase and neutral conductor are
interchanged.
has disconnected the inverter from the grid. An active signal is present at the "NA" input (external shutdown).
If this problem recurs, contact the grid operator in charge.
the grid operator in charge.
If this problem recurs, contact the grid operator in charge.
Check the PV generator.
Connect the AC input con­ductor as described in Section
5.3. If this problem recurs, contact
the grid operator in charge.
en
8.2.4 Error
The status LED lights up red.
Status message Cause Actions
Device error (+ error code) The inverter is defective. Note the displayed two-digit
error code and contact the SolarMax Service Center.
8.2.5 Blockings
The status LED will ash red.
Status message Cause Action
Firmware update The inverter's rmware is being
updated.
None. The inverter automati­cally resumes mains operation once the rmware update is complete.
69

9 Maintenance

The following maintenance work should be carried out when required:
Regularly check the operating status of the inverter on the graphics display, see Sec-
tion 7.7.
Clean the graphics display with a damp cloth. Do not use harsh or abrasive cleansing
agents.
Check the inverter for external damage. If any damage is found, inform the respective
qualied electrician.
70

10 Decommissioning

10.1 Instructions for inverter replacement

Before replacing the inverter, write down the total yield. The procedure for viewing the total yield is described in Section 7. 5 . 4 .

10.2 Inverter disassembly

DANGER! Fatal electric shock hazard!
Components within the inverter are charged with dangerously high voltage.
Before starting inverter disassembly, the inverter must be fully discon-
nected in accordance with the procedure described in this chapter.
WARNING! Risk of injury from electric arc!
Dangerous electric arcs could occur when removing live DC conductors.
Switch off the DC disconnector before pulling out the DC plugs.
ATTENTION! Electrostatic discharge can damage the inverter
Do not touch any electronic components inside the inverter.
Procedure
1. Switch off the external AC disconnector. – The "No grid" status message is shown on the inverter.
2. Switch off the DC disconnector at the inverter.
en
Figure 51 Switching off the DC disconnector
3. Use a size 2 screwdriver to remove the locking clips on the DC plugs.
4. Pull out the DC conductors to fully separate the inverter from the PV generator.
71
DANGER! Fatal electric shock hazard!
After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.
Wait for 5 minutes.
5. Open the inverter as described in Section 5.1.
6. Use a suitable charge indicator to check that all terminals are free from voltage. – When all terminals are de-energized, you can remove the AC feed cable, the 2nd
protective conductor and all communication lines from the inverter.
CAUTION! Risk of burns due to hot casing components!
Wait until the back of the casing has cooled down.
7. Fit the contact protection.
8. Fit the cover of the inverter.
9. Remove the 2 lateral Phillips head screws that secure the inverter on the mounting
rail.
10. Disengage the inverter from the mounting rail.

10.3 Disposing of the inverter

Dispose of the inverter as indicated by the local waste disposal regulations. You can also return the inverter, at your own cost, to Sputnik Engineering AG for professional disposal.
The contact details of the SolarMax Service Center can be found on the back of this instruction manual.
72
11 Specications
Input values
Output values
Efciency Maximum efciency 97. 5 % 9 7.6 % 97.6 % 97. 6 %
Environment Protection type IP 65
MPP voltage range
Control range 250…8 40 V 250…84 0 V 250…840 V 2 50…840 V
Minimum DC voltage 250 V 250 V 250 V 250 V
Maximum DC voltage 900 V 900 V 900 V 900 V
Maximum DC current 10 A 10 + 10 A 10 + 10 A 10 + 10 A
Number of MPP-Trackers 1 2 2 2
Max. P V generator output power per MPP tracker
Number of string connections 1 2 2 2
Connection type Wieland PST40 i1 (identical to MC 4)
Overvoltage category II
Rated output power
Maximum apparent output
2)
power
Maximum AC current
Nominal mains voltage / range
Mains nominal frequency / range
Power factor cosφ
Distortion factor at rated power
Connection type Terminal 2.5 - 10 mm
Grid connection Three-phase (L1 / L2 / L 3 / N / PE)
Overvoltage category III
Power input at night < 0.1 W
Europ. Efciency 96.0 % 96.5 % 9 6.6 % 96.7 %
Ambient temperature range (for rated power output)
Relative humidity 0…100% (condensation)
Max. operating level above sea level
Fire protection class UL94 V0
Environmental category In the open
Suitable for wet rooms Yes
Level of pollution 3
1)
2)
SM4TP SM5TP2 SM6TP2 SM7TP2
420…750 V 260…750 V 310…75 0 V 360…750 V
5 000 Wp 5 000 Wp 5 0 00 Wp 5 00 0 Wp
4 000 W 5 0 00 W 6 00 0 W 7 000 W
4 000 VA 5 00 0 VA 6 000 VA 7 000 VA
2)
3 x 6.5 A 3 x 7.5 A 3 x 9.5 A 3 x 10.2 A
3 x 400 V
50 / 45…55 Hz
Adjustable from 0.8 overexcited to 0.8 underexcited
< 3 %
−20…+60 °C (−20…+45 °C)
2000 m
2
en
73
SM4TP SM5TP2 SM6TP2 SM7TP2
Components Display Graphics display with backlighting and status LED
Inverter topology transformerless
DC disconnector integrated
Data logger Energy yields, peak output and operating duration of the
Fault current monitoring Internal, AC/DC sensitive
Casing / cover Aluminum / plastic AS A+PC
Overvoltage conductor DC /AC
Standards & guidelines
Interfaces Data communication RS485 / Ethernet (Plug&Play)
Weight & dimensions
Warranty Standard 5 years / extension to 10, 15, 20 or 25 years possible
1) for rated output power and symmetrical layout of the PV generator
2) different values are possible depending on the country setting selected; for further information visit www. solarmax.com
3) the complete conformity declaration can be found on our website at www.solarmax.com
CE-compliant
EMC EN 61000 -3-2 / EN 61000-3-3 / EN 61000 -6-2 / EN
Grid connection VDE 0126-1-1 (A1: 2012 / 2013) / VDE- AR-N 4105
Device safety IEC/ EN 62109-1/ -2
Status signalling contact integrated
Ripple control signal receiver integrated
External lightning protection monitor
External grid monitoring integrated
Energy counter S0
Weight 20kg 21kg 2 1kg 21kg
Dimensions (W x H x D) 476 x 360 x 180 mm
last 31 days, 12 months, 10 years / output cur ves of the
Requirement class D ( VDE 0 675-6) and/or type 3 (EN
last 7 days
616 43-11)
3)
Yes
61000-6-3
UTE C15-712-1 / E8001-4-712
integrated
Country-specific settings
The factory’s default settings for different countries can be viewed in the technical infor­mation “SSF - Standard specic functions and parameters”. This document can be down­loaded from our website at: www.solarmax.com; Downloads / String inverters / TP series.
74

12 Accessories and options

Accessory/option Description
Y-type plug connector Set consisting of two Y-type plug connectors for the parallel connec-
tion of solar modules (1 plug connector socket/socket to plug, 1 plug connector plug/plug to socket, item No. 10 005 602).
MaxView Free web-based application with various functions for remote call-up,
graphics visualization and export of yield data.
MaxTalk2 Free communication and service software for local monitoring of the
PV power plant. This software can be downloaded from our website (www.so larmax.com / D ownloads / Soft ware / MaxTalk).
MaxTalk2Pro Professional version of MaxTalk2 for the conguration of inverters.
This software can be downloaded from our website (www.solarmax. com / Download s / Softw are / MaxTalk). The "Solar Max TP series ­parameter conguration with MaxTalk 2 Pro" is also available from that link.
MaxMonitoring Using the free MaxMonitoring sof tware you can display the perfor-
mance data of your PV power plant at any time from home. MaxMon­itoring is available for PC, MacOS and Linux and also as an app for Android and iOS.
MaxDesign Free software for determining the size of PV power plants.
You can nd further information on our website at www.solarmax.com.
en
75

13 Warranty

Sputnik Engineering AG (hereafter SPUTNIK ) guarantees full function and lack of defects of its technical devices for a warranty period as specified below for each type of device. Such warranty period can be extended by means of a warranty extension, subject to the conditions named below.
This manufacturer’s warranty exists next to the seller’s warranty (if any) as prescribed by law. As far as identical with regards to the content, the rights under this manufacturer’s warranty supersede any rights under the seller’s warranty. Please contact the seller with regard to any claims based on the seller’s warranty.
1. Warranty Period (Basic)
Central inverters and accessories: 24 months from the date of purchase, but at maximum 30
months after dispatch of the device by SPUTNIK.
String inverters: 60 months from the date of purchase, but at maximum 72 months after dis-
patch of the device by SPUTNIK.
If in individual cases SPUTNIK has agreed in writing to a dif ferent warranty period, such arrange­ment supersedes the above provisions.
2. Scope of Manufacturer’s Warrant y
In case of defect or malfunction of a device within the manufacturer’s warranty period, and upon fulfillment of the conditions for warranty claims named hereafter, the device will be repaired or replaced by SPUTNIK-service personnel within a reasonable time, in either case free of charge, unless this is impossible or disproportionate. SPUTNIK may decide at its own discretion whether a device will be repaired or replaced.
Replacement: Exchange of device free of charge. SPUTNIK’s separate conditions for exchange
of devices apply: This warranty covers the free delivery of an equivalent replacement device. Further, your installer is entitled to claim a flat rate compensation for the replacement work from SPUTNIK. Please do not hesitate to ask us about the current amount of such flat rate compensation.
Repair: Repair of device free of charge. This warranty covers costs for material, work and travel
by SPUTNIK personnel or by personnel authorized by SPUTNIK.
Please be aware that the per formances of SPUTNIK under this warranty are only free of charge in countries approved by SPUTNIK. Please contact your seller for details. A current list of approved countries can be found on our homepage. Repair and replacement outside of the approved countries are only possible after prior consultation of and approval by SPUTNIK. In such case, travel and shipment costs are borne by the customer.
Any further claims, especially claims for compensation of damages resulting directly or indirectly from the defect or claims for replacement of fur ther costs in connection with the installation and removal of devices or claims for loss of profits are not covered by this warranty.
76
3. Extent of Repair and Replacement
SPUTNIK will maintain repair material and stock of each type of device during the warranty period only at its own reasonable discretion. In case repair materials for a certain type of inverter and/or an identical replacement device are not in stock anymore, the following applies:
SPUTNIK is allowed to replace the defective inverter with a comparable device of the same or
superior per formance. The costs (time and material) for technical adjustments necessary for the installation of such comparable devices are covered by this warranty only up to a limited amount; any flat rate compensation owed by SPUTNIK for the replacement is deductible. Please do not hesitate to ask us about the currently applicable amount. The exchange and connection of peripheral devices due to possible non-compatibility with the replacement device or other necessary adjustments to the surrounding installations of the device (including power lines, ventilation and safety installations) are not covered by this warranty. However, SPUTNIK shall within the bounds of reasonability do its best to minimize the effor t of such adaptation work.
In case repair materials are not available with reasonable efforts anymore, SPUTNIK is allowed
to replace the inverter, subject to the conditions mentioned in the paragraph above.
4. Warranty Period in Case of Repair/Replacement
In case of repair or replacement of devices under this warranty, the repaired respectively replaced device will inherit the remaining warranty time of the original device.
5. Exclusion of Warranty
Especially in the following cases, this manufacturer’s warranty does not apply:
Transport damage;
Technical intrusions, modifications or repairs of the devices not authorized by SPU TNIK;
Use of devices for purposes they are not intended for, incorrect or unreasonable manipulation,
incorrect or unreasonable installation;
Failure to observe the manufacturer’s operating, installation and maintenance directions;
Inadequate environmental conditions (e.g. insufficient ventilation of the device; humidity etc.);
Superior force (e.g. lightning strike, overvoltage, floods, fire, etc.).
en
6. Handling of Warranty Cases
For the processing of warranty cases, use of SPTUNIK’s hotline is mandatory. The handling of war­ranty cases must take place in accordance with the instructions provided by the hotline. The hotline number for your country can be found on SPUTNIK’s homepage. Please hold the serial number, article description, a short description of the defect and the purchase receipt ready for transmission to the hotline.
Any repair action taken by the buyer or third parties without authorization by SPUTNIK will not be compensated.
In case these terms on the handling of warranty cases are not respected, SPUTNIK may refuse its warranty performances.
77
7. Suspension of Warranty
Sputnik reserves its right to suspend this manufacturer’s warranty temporarily or definitely in case a specific installation does not allow a correct functioning of the inverters (e.g. in case of one of the circumstances listed in cipher 5).
The suspension of the warranty can be lifted upon approval by SPUTNIK. Such approval must be issued by SPUTNIK in writing, confirming that the warranty has again become effective.
8. Warranty Extension
The warranty period can be extended through purchase of a warranty extension within the time limits mentioned hereafter. For certain types of devices, such warranty extensions can also be purchased only for a limited scope of warranty performances. The purchase of a warrant y extension will be confirmed by SPUTNIK in form of a warranty certificate (including serial number of affected product). In case of replacement of a device, the serial number in such warrant y certificate remains unchanged, without any influence on the validity of the warranty extension.
a) Time limits String inver ters: The extension of the basic warranty can be ordered within 60 months after pur­chase, but the latest within 72 months af ter dispatch of the device by SPUTNIK. Central Inverters: The extension of the basic warrant y can be ordered within 3 months after pur­chase, but the latest within 12 months after dispatch by SPUTNIK.
b) Extent Full warranty extension – FULL (available for central inverters and string inverters): A full warranty extension includes all the warranty performances as described in the manufacturer’s basic warrant y terms.
Limited warranty extension– LIMITED (available only for central inverters): A limited warranty extension covers only the costs for the material required for the repair. The costs for travelling, labor and other expenses are not covered and will be invoiced on a time and expenses basis by SPUTNIK.
c) Effectiveness of Warranty Extension It is a mandatory requirement for the warranty extension to provide the completely filled out appli­cation form to SPUTNIK. The warranty extension becomes effective only after written confirmation and provision of the warranty certificate by SPUTNIK.
78
9. After Expiration of Warranty Period
The costs for repair or replacement of devices after expiration of the warranty period are invoiced by SPUTNIK on a time and material basis. SPUTNIK will maintain repair and replacement capabilities beyond the warranty time only at its own discretion.
10. Applicable Law, Jurisdiction
Only Swiss Law applies. The exclusive place of jurisdiction lies in Biel/Bienne, Switzerland. (v 20 13/0 5)
Notes
en
79
SolarMax Service Center
Please refer to our website for contact details:
www.solarmax.com/service
2014/ 05 en
Loading...