This instruction manual is intended for the operator of the plant and the installer of the
PV power plant.
The instructions in chapters 5, 6.2, 8 (troubleshooting actions) and 10 may only be carried out by trained electricians (e.g. electricians, electric systems technicians, electrical
mechanics, industrial electronics technicians).
The instructions in chapter 4 should only be carried out by specialist transport personnel.
1.3 Where to keep this manual
The plant operator must ensure that this instruction manual is available to the relevant
persons at all times. If this original document is lost, an up-to-date version of this instruction manual can be downloaded from our website at any time (www.solarmax.com).
en
1.4 Symbols used
The following safety instructions and general information are used within this instruction
manual.
DANGER!
Non-observance of these safety instructions may immediately cause serious
injuries or death.
WARNING!
Non-observance of these safety instructions may cause serious injuries.
7
CAUTION!
Non-observance of these safety instructions may cause minor or medium
injuries.
ATTENTION!
Non-observance of these safety instructions may cause material damage.
Note
Notes contain additional information or facilitate the inverter operation.
2 Safety
2.1 Intended use
The inverters of the SolarMax TP series are designed exclusively for the conversion of the
direct current generated by PV modules into alternating current which conforms to the
parameters of the public grid. Any other use, in particular the conversion of direct current
from batteries or other storage elements into alternating current is not permissible.
Inverters of the TP series may only be connected to PV generators of protection class II.
2.2 Safety Instructions
DANGER!
Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC
voltage.
Make sure that all electrical feed-in lines to the inverter are de-energized
before starting any work on the inverter or the feed-in lines.
DANGER!
Fatal electric shock hazard!
Components within the inverter are charged with a high voltage.
Never open the inverter while it is in operation.
8
WARNING!
Risk of injury from electric arc!
Removing the DC connectors when live can lead to dangerous electric arcs.
Switch off the DC disconnector at the inverter before removing the DC
connectors.
WARNING!
A re risk can result from inappropriate repair!
The inverter does not contain any replaceable components. Defective
inverters must be sent to the SolarMax Service Center for repair or disposed of in accordance with Section 10.3.
2.3 Symbols on Inverter
SymbolDescription
Protective conductor connection
The DC disconnector is switched off (the contacts are open).
The DC disconnector is switched on (the contacts are closed).
Risk of death through high voltages! Only qualied electricians may
perform work on the inverter.
en
Caution - hot surfaces!
5 min
Risk of death due to high voltages in the inverter! De-energize the
inverter. Proceed to wait for 5 minutes before opening the inverter.
Only qualied electricians may perform work on the inver ter.
Read the operating instructions - Please read and follow the instructions supplied with the inverter. Do not remove any symbols on the
inverter. Replace damaged symbols.
CE marking - The inverter complies with the requirements of the
European EMC Directive 2004/108/EC and the Low Voltage Directive
2006/95/EC (see Section 11).
9
SymbolDescription
GS marking - The inverter complies with the relevant requirements of
the German Product Safety Act.
Do not dispose of the inverter and its accessory components in the
household waste.
3 Description
3.1 Identication
The inverter can be identied on the basis of the information provided on the nameplate
(see Section 3.5).
3.2 Functionality
MPP tracker & grid connection
The SM5TP2, SM6TP2 and SM7TP2 inverters have 2 independent MPP trackers which
can be used to connect strings with different characteristics, such as orientation, size and
module type. The SM4TP is tted with an MPP tracker. Each MPP tracker can be tted
with one string as standard. The grid connection is a three-phase connection.
Automatic operation
Inverter operation is completely automatic and depends on the available output of the PV
generator. If there is enough power, the inverter starts mains operation and feeds into
the power grid. If there is not enough power available from the PV generator, the inverter
disconnects from the grid and shuts down.
Operation
The graphics display with three function keys allows convenient inverter operation and
reading of all important operating data. The graphics display is only switched on when the
DC input voltage is high enough.
The inverter has congurable functions for grid monitoring, limitation of output and reactive power control.
10
Interfaces / remote monitoring
For the purpose of monitoring the PV power plant remotely, the inverter can be connected
directly to the Internet via Ethernet.
The inverter is tted with a multi-function relay which can be congured for various purposes (status signaling contact, control of self-consumption).
The inverter is tted with interfaces for remote-controlled shutdown and output control
(active and reactive power control).
Extended functions
The inverter has functions for grid monitoring, limitation of output, reactive power control
and control of self-consumption. These can be congured using MaxTalk2.
Ventilation
The inverter is air cooled. To a large extent, ventilation is passive via the vertical cooling
ns on the back of the inverter. The fan on the left-hand side of the inverter (not available
with SM4TP and SM5TP2), which is accessible from the outside, sucks in air which is also
directed across the cooling ns. All inverters of the TP series are tted with an internal
fan.
3.3 Safety installations
Surge protection
The inverter is tted with surge arresters (varistors) at its input and output. Each DC
input (plus and minus connection) is tted with a surge arrester. On the AC side, the
phases and the neutral conductor are individually secured with surge arresters. The surge
arresters have a common gas discharge tube to ground. For further information on the
surge arresters, see Section11.
When designing the PV power plant, it may be necessary to provide additional external
lightning protection (overvoltage protection). The inverter has an interface for monitoring
external lightning protection modules.
en
Fault current monitoring
The inverter has an integrated AC/DC-sensitive leakage current sensor. This recognizes
leakage currents generated due to PV module capacities to ground (capacitive ground
leakage current) or through insulation faults (for example by touching a pole of the PV
generator or a phase). In the case of the permissible leakage current being exceeded, the
inverter disconnects from the grid.
Functions for current and output limitation
The inverter limits the DC feed-in current, the output power and the output current.
11
Temperature limitation
480189
[mm]
361
At ambient temperatures of more than 45°C the equipment temperature may reach more
than 80°C. In such cases, the maximum in-feed power is temporarily reduced. When the
equipment temperature rises above 85°C, the inverter disconnects from the grid.
3.4 Dimensions
104.5
256.5
Figure 1 Dimensions
12
3.5 Views of the unit
2
1
3
en
4
5
6
87
Figure 2 Views of the unit
No.Description
1DC disconnector
2Type plate
3Graphics display
4Cover
5Mounting rail
6Fan (only SM6TP2 & SM7TP2)
7Cooling ns
8Connection area (only 2 DC plug connection points at the SM4TP)
13
3.6 Block circuit diagram
** only SM6TP2 and SM7TP2
L1 L2 L3
AC output
U
DC
Booster 1
EMC lter
Inverter
DC
K2K1
DC
EMC lter
LCL lter
AC
Fan **
AC measurement
Internal fan
Inverter control
DC
DC
Booster 2
EMC lter
Control unit
Communication module
DC measurement
Booster control
External energy meter
Monitoring
lightning protection
External shutdown
External power control
Multi function relay
RS485
Ethernet
Graphics display
U
+
−
DC input MPP tracker 1DC input MPP tracker 2 *
U
I
DC disconnector
+
−
0
* only SM5TP2, SM6TP2 and SM7TP2
Figure 3 Block circuit diagram
14
4 Installation
4.1 Transporting and storing inverters
Make sure that the ambient conditions during transportation and storage are within the
specied limits (for details see Section 11). Only use the original packaging when shipping
the inverter.
4.2 Checking the delivery for completeness
Check the contents of the delivered package for completeness and possible damage. In
the case of an inadequate delivery, please contact your dealer or the SolarMax Service
Center.
1
SolarMax TP-Serie
4TP / 5TP2 / 6TP2 / 7TP2
Gerätedokumentation
Register here:
maxview.solarmax.com
3
4
5
6
2
7
8
9
en
Figure 4 Content of delivery
10 11
13
12
14
15
No.Quantity Description
11Inverter
21Instruction manual
31Mounting rail
42External hexagon wood screws 6 x 50 INOX (for the installation of the
52Washers M6 x 18 INOX (for the installation of the inverter)
62Plastic dowels 8 x 40 (for xing in brickwork)
72Phillips head sheet metal screws 4.8 x 13 (for locking the inverter on the
86Locking pins (for plugging unused holes in multiple cable connectors)
94Locking clips (for DC plugs)
101Toothed lock washer M5
111Lug M5 x 10 mm
121Washer M5
131Spring washer M5
141Phillips head screw M5 x 12
inverter)
mounting rail)
2
(for connection of 2nd
protective conductor)
4.3 Selecting the installation location
DANGER!
Fatal re or explosion hazard!
The inverter is an electrical device with heat generation and the possibility of
sparking.
Install the inverter in an environment that is free of ammable gases and
uids.
Never install the inverter near combustible materials. The installation
base must be non-combustible.
Follow the local re safety regulations.
The ambient conditions are specied in the specications, see Section 11.
Location and installation conditions
If possible, select a dry location for installation that is protected from water and snow.
Install the inverter in an easily accessible location, so that maintenance work can be
carried out easily.
Do not expose the inverter to direct sunlight.
Never install one inverter above another (this can interfere with passive cooling).
16
Maintain the following installation distances:
50
50
20*
50
20
°C
[cm]
Figure 5 Minimum installation distance (20*: only SM4TP and SM5PT2)
The installation base must be vertical. Do not install the inverter in a horizontal or
inclined position.
OK !
Figure 6 Unacceptable mounting positions
The optimal cooling of the inverter is only guaranteed when the cooling ns (see
section 3.5) are absolutely free of dust and dirt.
When installing the inverter on a mast, a mounting plate with at least the same
dimensions as the back of the inverter is needed.
The ambient air around the inverter must be free from dust, salt and ammonium
vapors.
The location must meet the requirements regarding emissions and freedom from
electromagnetic interference.
en
17
4.4 Mounting the inverter
446
[mm]
6.5
The inverter is xed to the wall by a mounting rail. The mounting rail and the necessary
xing accessories are included in the delivery package.
Procedure
1. Use the mounting rail as a template for drilling the holes.
2. Align the mounting rail in a horizontal position.
3. Mark 2 places for drilling.
376
26
26
Figure 7 Dimensions of wall mounting bracket
6.5
– For the other measurements see section 3.4.
4. Drill two 8 x 50 mm ∅ holes.
5. Fix the mounting rail.
– Assembly sequence: plastic dowels 8 x 40, mounting rail, M6 washers, hexagon
head wood screws 6 x 50.
6. Attach the inverter to the mounting rail (see Figure 8).
7. Fix the inverter on both sides using the Phillips head screws:
A
B
C
Figure 8 Attaching and securing the inverter
18
5 Electrical connection
5.1 Open the inverter
For the purpose of connecting the AC and communication lines, the inverter has to be
opened.
DANGER!
Fatal electric shock hazard!
Components within the inverter are charged with dangerously high voltage.
De-energize the inverter completely before carrying out installation work.
5.1.1 Removing the cover
When the cover has been removed, the RJ45 grid sockets, the S0 interface and the interface for the lightning protection monitor are directly accessible.
Procedure
1. Disconnect the AC power supply to the inverter.
2. Disconnect all control cables connected to the inverter (status relay, external grid
monitoring).
3. Switch off the DC disconnector at the inverter.
en
DANGER!
Fatal electric shock hazard!
After the inverter has been disconnected, high residual voltages remain in the
inverter for approx. 5 minutes.
Wait for 5 minutes.
4. Loosen the two M5 screws at the bottom of the cover.
5. Remove the cover by gripping it at the bottom and pulling it away.
19
5 min
Figure 9 Removing the cover
5.1.2 Removing the right-hand contact protection
The right-hand contact protection covers the AC connection terminals and the AC feed-in
lines.
Procedure
1. Operate the snap lock and pull the right-hand contact protection from its holder.
20
Figure 10 Remove the right-hand contact protection
2. Use a voltage tester to check that all connections in the inverter are de-energized.
5.1.3 Removing the left-hand contact protection
The left-hand contact protection covers the control connections and their supply conductors, which may be charged with dangerously high voltages (external shutdown, status
signaling contact).
Procedure
1. Operate the snap lock and pull the left-hand contact protection from its holder.
Figure 11 Removing the left-hand contact protection
2. Use a voltage tester to check that all connections in the inverter are de-energized.
en
21
5.2 Connection area
The connection area with the cover removed and without contact protection.
10
12
11
2
89
7
6
3
4
51
22
Figure 12 Connection area
No.Description
1Left-hand cable pass-through (control connections)
2DC connection - MPP tracker 1
3Middle cable gland (communication and control connections)
4DC connection for MPP tracker 2 (only with SM5TP2, SM6TP2, SM7TP2)
5Right-hand cable pass-through (AC feed cable)
6Connection for 2nd protective conductor
7AC connection terminals (spring connection)
8Lightning protection monitoring and S0 interface (spring connection)
9Multi-function relay (spring connection)
10RS485 socket (RJ45)
No.Description
11Ethernet socket (RJ45)
12External shutdown, external output control (spring connection)
5.3 Connecting the inverter to the mains
DANGER!
Fatal electric shock hazard!
Make sure the AC line is not live during connection work.
Connection conditions
Comply with the connecting conditions set by the grid operator in charge.
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
Permissible conductor cross-sections:
– exible conductors (with or without ferrule) or rigid conductors: max. 16 mm
– exible conductors with ferrules (with plastic sleeves): max. 10 mm
The AC input conductor must be fused. Minimum conductor cross sections and sug-
Phases L1, L2, L3
Neutral conductor N
Protective conductor PE
Recommended mains fusesSM4TPSM5TP2SM6TP2SM7TP2
Nominal current10 A10 A13 A13 A
CharacteristicsCCCC
1.5 mm21.5 mm22.5 mm22.5 mm
2
en
2
2
Temperature resistance of the AC feed cable: ≥ 80 °C
Make sure the ambient temperatures for the mains fuses specied by the producer
are not exceeded.
23
WARNING!
Risk of death by fire!
Provide separate fuses for each inverter.
Do not attach any loads between inverter and fuse.
If you use external residual current devices (RCDs), use the type A or B RCDs with a
nominal leakage current of at least 100 mA. For PV plants with large leakage current
capacities, the RCDs to be used should have a nominal leakage current capacity of at
least 300 mA.
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
2. Remove the right-hand contact protection as described in Section 5.1. 2.
3. Thread the AC feed cable through the right-hand cable gland.
4. Pull the ferrite (included in the delivery) over the AC feed cable (Figure 13/0).
5
4
3
2
1
24
0
Figure 13 AC connection and connection for 2nd protective conductor
5. Remove an 18 mm length of conductor isolation.
6. Connect the wires as follows:
– the protective conductor to the "PE" terminal
– the neutral conductor to the "N" terminal
– Phases L1, L2 and L3 to the terminals L1, L2 and L3
7. Press and close the levers completely. If a lever is not completely closed, the con-
ductor connection is not secured.
CBA
Abbildungen Klemme: Phoenix Contact
18 mm
Figure 14 Connect the AC terminals.
8. Check the cable connections for rm seating.
9. Tighten the cable gland (wrench size: 34 mm).
10. Check the cable strain relief.
11. Connect the second protective conductor (see Figure 13).
– Assembly sequence: toothed lock washer M5 (1), lug (2), washer M5 (3), spring
washer M5 (4), Phillips head screw M5 x 12 (5)
12. Fit the contact protection.
13. Fit the cover of the inverter.
5.4 Connecting the inverter to the PV generator
The inverters of the TP series are operated in dual tracking mode. In the dual tracking
mode a separate MPP tracker is available for each DC input.
Connection conditions
Connection of maximum 2 strings (1 string in the case of SM4TP)
DANGER!
Risk of death by re!
High return currents can cause a re risk for the PV generator.
When Y plugs are used in order to connect more than 2 strings (more than
1 string in the case of SM4TP), each DC feed cable must be protected
individually against dangerous return currents.
Maximum DC input current: 10 A per DC input
Maximum DC input voltage: 900 V
Select the conductor cross-section to suit the system conguration.
Exclusively use Wieland PST40i1C connectors (the mating connectors are not
included in the package supplied)
Parallel connection of the MPP trackers is not permitted:
en
25
Figure 15 Unacceptable parallel connection of MPP trackers
Do not t a ground connection to either the negative terminal or the positive terminal
of the PV generator.
Procedure
1. Make sure the DC disconnector and the external AC disconnector are off.
2. Connect the pre-tted DC conductors.
26
12
DC−DC+DC+DC−
Figure 16 DC connection
No.MPP tracker
11
2*2
* only SM5TP2, SM6TP2 and SM7 TP2
3. Use the locking clips (included in the delivery) to secure the plug connectors.
Figure 17 Secure the plug-in connection
Close off any unused DC plug connectors.
> 900
V>
V
Any unused DC plug connectors must be closed off to ensure that the installation complies with the IP65 protection rating requirements. Please use the following closing parts
made by Wieland (www.wieland-electric.com):
for plug component: order number 05.566.6380.0
for socket component: order number 05.566.6480.0
Increasing the overvoltage protection
If you want to increase the overvoltage protection on the DC side using additional external
surge arresters, the following connection conditions must be met:
Use a surge arrester with a response voltage of > 900 V.
Connect the external surge arresters as follows:
en
V> 900
Figure 18 Increasing the overvoltage protection
Install the connector cables close together to avoid overvoltages in the case of a
> 900 V
900
lightning strike.
Avoid ground loops in the wiring.
Wire the earth connections in a star conguration with the neutral point close to the
inverter.
27
5.5 Connecting communication interfaces (optional)
5.5.1 Overview of connections
The connection terminals for the various communication interfaces are illustrated in
Figure 19. The RJ45 grid sockets can be seen in Figure 12.
S0+
S0−
BS+
BS−
11
12NC14
NANK5
K2
K6
K3K4K1
Figure 19 Connection terminals for communication
ContactDescription
NExternal shutdown / external power control
NAExternal shutdown
K1External power control
K2
K3
K4
K5
K6External power control
NCNot used
11Multi-function relay (status signaling contact / control of self-consumption)
12
14
S0+S0 interface (control of self-consumption)
S0−
BS+Lightning protection monitor
BS−
28
5.5.2 Installation of communication cables
To ensure the operational safety of the inverter, the cables have to be installed in the
inverter as described in this section of the instructions. The left-hand contact protection
covers the cables and connections with dangerously high voltages (> 50 V).
In order to ensure that the inverter remains sealed, the unused apertures in the cable
glands must be closed with the locking pins (example see Figure 20 / Pos. 2). The locking
pins are included in the delivery package.
5.5.3 Network connections
The inverter can be connected to Ethernet and RS485 networks.
Note
You will nd further details about data communication in the technical information "MaxComm network". You can download this document from our website at: www.solarmax.com; Downloads/Data Communication/MaxComm.
Connection conditions
Connection type: RJ45 sockets
Use shielded cables.
Connectable cable diameters: min. 5.5 mm / max. 7.0 mm
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
– Do not remove any contact protection.
2. Route the grid cable through the middle cable gland ( Figure 20 / 1) .
Note
The RJ45 connectors can be pulled through the cable gland.
3. Depending on the type of network, connect the cable either to the "Ethernet" or
"RS485" socket.
en
29
1
2
Figure 20 Connecting the grid cables
4. Close the unused apertures in the multiple cable gland using the locking pins
(Figure 20/2).
5. Tighten the multiple cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the cover of the inverter.
5.5.4 External shutdown
This interface can be used to connect the inverter to an external grid monitoring system
which disconnects the inverter from the mains grid when this is needed.
While the external grid monitoring signal (the phase voltage) is active at the "NA" contact,
the inverter feeds into the grid. When the signal stops, the grid relays K1 and K2 of the
inverter are opened (see Figure 3). This immediately disconnects the inverter from the
grid.
The interface can only be congured with the free MaxTalk2Pro service software (see
Section 12).
Connection conditions
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
Connectable conductor cross-sections: min. 0.25 mm
Max. input current: 25 mA
Max. input voltage: 230 VAC
2
/ max. 2.5 mm
2
30
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
2. Remove the left-hand contact protection as described in Section 5 .1. 3 .
WARNING!
Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection
inside the inverter.
Route the connection cable through the left-hand cable gland
(Figure 21 / 1).
3. Connect the wires as follows:
– Wire stripping length: 7 mm
1
2
Figure 21 Connection of "external shutdown“
ContactDescription
NAControl line
NNeutral conductor
4. Close the unused apertures in the multiple cable gland using the locking pins
(Figure 21/2).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the contact protection.
8. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
en
31
5.5.5 External power control
Via this interface the inverter can receive digital signals for the specication of the setpoint of active and reactive power. It is possible to connect ripple control receivers to this
interface.
The interface is congured with the free MaxTalk2Pro service software (see Section 12).
Figure 22 shows the connection of the ripple control receiver to the interface.
Inverter
N
K6
K5
K4
K3
N
L
I = 25 mA
(230 V)
I max = 150 mA
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 543 2 1
c
b
c
b
a
c
b
a
c
b
a
b
a
K6K5K4K3K2K1
Ripple control receiver
Figure 22 Connection diagram of ripple control receiver
Connection conditions
Max. 6 relay contacts can be connected
Max. input voltage: 230 VAC (phase)
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
Connectable conductor cross-sections: min. 0.25 mm
Input current: 25mA
Max. cable length: 200 m
2
K2
K1NA
c
c
b
a
a
/ max. 2.5 mm
2
32
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
2. Remove the left-hand contact protection as described in Section 5 .1. 3 .
WARNING!
Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection
inside the inverter.
Route the connection cable through the left-hand cable gland
(Figure 23 / 1).
3. Connect the wires as follows:
– Wire stripping length: 7 mm
2
en
1
Figure 23 Connection of external power control
ContactDescription
K1Control signal relay K1
K2Control signal relay K2
K3Control signal relay K3
K4Control signal relay K4
K5Control signal relay K5
K6Control signal relay K6
NNeutral conductor
4. Close the unused apertures in the multiple cable gland using the locking pins
(Figure 23 / 2 ).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
33
7. Fit the contact protection.
11
NC
8. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.6 Multi-function relay
The multi-function relay can be used as status signaling contact for the remote control of
the inverter (see section 6.3.4) or for the control of self-consumption (see section 5.5.9).
12 14
Figure 24 Contact scheme of multi-function relay
Connection conditions
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
Connectable conductor cross-sections: min. 0.25 mm
Max. switching voltage: 250 VAC / 30 VDC
Max. switching current: 1.5 A (no internal fuse present)
Max. cable length: 50 m
Procedure
1. Remove the cover of the inverter as described in section 5.1.1.
2. Remove the left-hand contact protection as described in section 5 .1. 3 .
WARNING!
Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection
inside the inverter.
Route the connection cable through the left-hand cable gland
(Figure 25 / 1).
2
/ max. 2.5 mm
2
3. Connect the wires as follows.
– Wire stripping length: 7 mm
34
1
2
Figure 25 Connection of multi-function relay
Contact Description
11COM
12Opener (when used as status signaling contact: opener in the case of error)
14Closer (when used as status signaling contact: closer in the case of error)
NCNot used
4. Close the unused apertures in the multiple cable gland using the locking pins
(Figure 25/2).
5. Tighten the middle cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the contact protection.
8. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.7 Lightning protection monitor
This interface can be used for monitoring an external lightning protection module. The
conguration is done using the inverter's graphics display (see Section 6.3.5) or with
MaxTalk2.
When the remote signaling contact of the lighting protection module connected to the
input closes, the inverter displays the corresponding status message/warning on the
graphics display. It is possible to connect multiple lightning protection modules in parallel
to the lightning protection input.
en
35
Connection conditions
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
Connectable conductor cross-sections: min. 0.25 mm
Max. cable length: 50 m
Do not connect any external power sources.
2
/ max. 2.5 mm
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
– Do not remove any contact protection.
2. Route the cable through the middle cable gland (Figure 26 / 1).
3. Connect the wires as follows:
– Wire stripping length: 7 mm
ContactDescription
BS+Remote signaling contact of the lightning protection module
BS–COM
(potential-free)
2
36
1
2
Figure 26 Connection of the lightning protection module
4. Close the unused holes in the cable gland using the locking pins (Figure 26 / 2).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.8 S0 interface
In accordance with DIN EN 62053-31 this interface can be used to connect an energy
counter to the inverter for the purpose of the control self-consumption (see Section 5.5.9).
From experience, SolarMax can recommend the following electronic energy counters:
Berg MCi32WP and Berg B23 311.
The S0 interface is congured with the free MaxTalk2Pro service software.
Connection conditions
Energy counters are only permitted with S0 pulses for feed-in (S0 pulses for both
directions of energy ow are not permitted).
The pulse rate of the energy meter must be between 1 000 and 10 000 pulses
per kWh.
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
Connectable conductor cross-sections: min. 0.25 mm
Max. cable length: 50 m
Do not connect any external power sources.
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
– Do not remove any contact protection.
2. Route the cable through the middle cable gland (Figure 27 / 1) .
3. Connect the wires as follows:
– Wire stripping length: 7 mm
– Ensure the polarity is right
ContactDescription
S0+Pulse input (plus pole)
S0–COM (minus pole)
2
/ max. 2.5 mm
2
en
37
1
2
Figure 27 Connection of the S0 interface (energy counter)
4. Close the unused holes in the cable gland using the locking pins (Figure 27 / 2).
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Fit the cover of the inverter.
You can switch the inverter on as described in Section 6.1.
5.5.9 Control of self-consumption
The inverter has functions for the control of self-consumption. The connection is made
via the relevant communication interfaces. Several different operating modes can be
selected.
Operating modeDescription
Grid feed-in limitationAs the inverter controls self-consumption it keeps within a
Pac electric meterThe inverter controls the consumer loads in accordance with the
Pac inverterThe inverter controls the consumer loads in accordance with its
maximum feed-in power at the grid connection point. The power
output is measured with an energy counter.
power fed into the grid. The power output is measured with an
energy counter.
output power.
38
5.5.9.1 Grid feed-in limitation
R
For the connection diagram in "Grid feed-in limitation" mode see Figure 28: the energy
counter that measures the power fed in at the grid connection point is connected to the
S0 interface of the inverter.
The grid feed-in limitation is congured using the free MaxTalk2 Pro service software
(see Section 12).
12NC14
PV
N
S0+
11
BS+
S0−
BS−
kWh
kWh
Inv
60
80
40
20
100
0
120
°C
Figure 28 Wiring in "Grid feed-in limitation" operating mode
Legend: R: consumer / Inv: inverter / PV: PV generator / N: grid connection point / kWh:
energy counter
en
Procedure
Connect the energy counter as described in Section 5.5.8.
Use MaxTalk2Pro to congure the max. feed-in power and the S0 interface (electric
meter).
39
5.5.9.2 Pac electric meter
Connection diagram for "Pac electric meter" operating mode see Figure 29: the consumer loads are controlled via the inverter's multi-function relay. For example, the control
voltage for a contactor or a relay can be switched on and off. The energy counter, which
measures the fed in power at the grid connection point, is connected to the S0 interface
of the inverter.
The "Pac electric meter" operating mode can be congured on the inverter's graphics
display or using MaxTalk 2.
12NC14
PV
N
S0+
11
BS+
S0−
BS−
R
60
80
40
20
100
0
120
°C
Inv
kWhkWh
K
Figure 29 Wiring in "Pac electric meter" operating mode
Connect the multi-function relay as described in Section 5.5.6.
Connect the energy counter as described in Section 5.5.8.
Congure the control of self-consumption as described in Section 6.3.6.1.
Use MaxTalk2Pro to congure the S0 interface (electric meter).
40
5.5.9.3 Pac inverter
R
Connection diagram for "Pac inverter" operating mode see Figure 30: the consumer loads
are controlled via the inverter's multi-function relay. For example, the control voltage for
a contactor or a relay can be switched on and off.
The "Pac inverter" operating mode can be congured on the inverter's graphics display
or using MaxTalk 2.
Connect the multi-function relay as described in Section 5.5.6.
Congure the control of self-consumption as described in Section 6.3.6.2.
41
6 Commissioning
6.1 Activating the inverter
Procedure
1. Check that the cover is installed.
– If the cover is not tted, close the inverter as follows:
– t the left-hand and right-hand contact protection in the inverter;
– then t the cover
2. Switch on the DC disconnector at the inverter.
Figure 31 Switching on the DC disconnector
– The graphics display shows the "Overview". The status message "Start up..."
appears.
3. Switch on the AC power supply to the inverter.
– Wait for the "Mains operation" status message to be displayed. This indicates that
the inverter is in mains operation.
– During initial start-up of the inverter, instead of the “Overview” menu, an “Initial
setup” menu appears (see Section 6.2).
42
6.2 Initial start-up
This section describes the initial start-up of the inverter and the graphics display settings required for this purpose. Once initial start-up has been successfully completed, the
inverter will start feeding into the mains grid.
6.2.1 Requirements
The inverter has been installed and the electricity has been connected.
The contact protection and cover of the inverter are tted.
There is sufcient solar irradiation (sufciently high DC input voltage).
Note
Entering an incorrect country setting may lead to problems regarding
inverter operation and to the withdrawal of the operating license by the
respective grid operator.
Contact your grid operator or the SolarMax Service Center if you have any
doubt regarding the settings you must select.
You can restart initial start-up by pressing in the "Conrmation"
menu at any time.
6.2.2 Procedure
1. Switch on the inverter as described in Section 6 .1. The "Initial setup" menu will be
displayed:
Figure 32 Selecting the display language and updating the system time
2. Select the display language from the "Language" menu.
3. If necessary, update the time and the date.
– The inverter saves the date entered as the initial start-up date.
– The "Country" menu will be displayed:
en
Figure 33 Selecting the country setting
4. Select the correct country setting.
– Press to conrm your entry.
– Depending on the country setting selected, additional menus may be displayed
(see Section 6.2.3).
– The "Conrmation" menu is then displayed.
43
5. Check the data in the "Conrmation" menu.
6. To complete initial start-up, press .
– The main menu will then be displayed (see Section 7.4).
6.2.3 Description of country-specic menus
Depending on the country setting, additional menus will be displayed during initial
start-up.
Country: Germany
MenuSettingDescription
Plant system rating> 3.68 – 13.8kVAThe plant system rating is higher than 3.68 kVA
CosPhi(Pac) - QMCPP Inactive
On
and/or does not exceed 13.8 kVA.
The "cosφ(Pac)" function is deactivated (no
reactive power generated, cosφ=1).
The "cosφ(Pac)" function for reactive power
generation is activated.
6.3 Settings
Different communication parameters and monitoring functions can be set in the "Settings" menu of the graphics display. All settings except the IP mode can also be made
using the MaxTalk2 service software.
6.3.1 Changing parameters
The parameters in the "Settings" menu can be changed as follows:
1. In the Main Menu select the "Settings" menu.
44
Figure 34 "Settings" menu
2. Press to select the parameter (e.g. "Time").
3. Press to change to the editing mode.
4. Press to select the required number.
Figure 35 Selecting the number and changing the value
5. Press to increase the value of the selected number.
6. Press to select the next number.
7. Press to conrm the parameter value.
8. Press to return to the Main Menu.
6.3.2 Setting the display language and system time
The inverter's display language and system time can be changed in the "Settings" menu.
1. Select the "Settings" menu:
Figure 36 Changing the display language and system time
2. Select a parameter:
ParameterDescription
LanguageSelection of the display language: German, English, French, Italian
or Spanish. The display language selection does not depend on the
selected country.
TimeDate and system time of the inverter
Date
en
3. Change the parameter as described in Section 6.3.1.
45
6.3.3 Setting the network parameters
Device address
In order to communicate via an RS485 or Ethernet interface, the inverter needs a unique
device address on the network.
1. In the "Main menu" select the "Network" menu.
2. Select the "Device address" parameter.
3. Congure the parameter:
ParameterDescriptionValue range
Device addressDevice address of inverter1…249
Configuring the Ethernet interface
In addition to the device address, the following settings must be made to communicate
via Ethernet:
1. In the "Main menu" select the "Network" menu.
2. In the "IP mode", select the required setting:
SettingDescription
DHCP clientThe inverter is a DHCP client and is connected to a network with
StaticThe inverter is connected to a network with static IP addresses.
3. If appropriate, congure the following parameters. These settings are only required in
"Static" IP mode (see step 2):
ParameterDescriptionValue range
IPIP address192.168.1.123*
GatewayGateway of inverter192 .168 .1.1*
TCP portTCP port of inverter12345*
DNS1Domain name server 1192.168.1.1*
DNS2Domain name server 2192 .16 8.1.1*
NetmaskSubnet mask255.255.255.0*
* Factory settings
4. Check whether the indicator for the Ethernet connection appears on the graphics
display (see Section 7.1).
DHCP server (factory setting).
46
6.3.4 Conguring the status signaling contact
When the multi-function relay is used as status signaling contact, the operating mode and
the delay time can be congured.
Procedure
1. In the "Settings menu" select the "MF relay" menu.
2. In "MF relay" select the "Status relay" setting.
3. Select the required setting under "Mode":
SettingBeschreibung
OffThe status signaling contact is always open.
GridIf the inverter starts mains operation, the status signaling contact
is closed immediately and remains closed as long as the inverter
feeds into the grid. After the unit disconnects from the mains, the
status signaling contact opens after expiry of the adjustable delay.
ErrorWhen a warning, a failure, or a device error occurs on the inverter
(for error messages see Section 8.2) the status signaling contact
is closed after expiry of the adjustable delay time. The status
signaling contact is immediately opened when the fault is no longer
present (factory setting).
OnWhen the inverter is switched on (suf ciently high DC input
voltage), the status signaling contact closes. The status signaling
contact will not re-open unless the inver ter is switched off (DC
input voltage too low).
4. Select "Delay".
5. Adjust the required delay time:
ParameterDescriptionValue rangeUnit
DelayDelay time of status relay0…9 9min
6.3.5 Conguring the lightning protection monitor
The operating mode of the lightning protection monitor can be congured.
Procedure
1. In the "Settings" menu, select the "SPD Monitor" menu.
2. Select the required setting under "Mode":
SettingDescription
OffThe lightning protection monitoring is deactivated.
WarningWhen the lightning protection operates, the warning "SPD failure"
is displayed (on the graphics display and in MaxTalk2). The inverter
will continue to feed into the grid. The status signaling contact will
be closed (factory setting).
ErrorWhen the lightning protection operates, the status message "SPD
failure" is displayed (on the graphics display and in MaxTalk).
The inverter will disconnect from the mains. The status signaling
contact will be closed.
en
47
6.3.6 Control of self-consumption
Status of multi function relay [on/off]
The control of self-consumption functions can be congured on the inverter's graphics
display. The S0 interface for the connection of the energy counter and the "Grid feed-in
limitation" operating mode for the control of self-consumption can only be congured
with MaxTalk 2 Pro.
6.3.6.1 Conguring the "Pac electric meter" operating mode
The "Pac electric meter" operating mode for the control of self-consumption can be congured to suit the user's requirements. The functionality is illustrated in Figure 37.
Pac [W]
10000
8000
6000
Enable threshold
4000
2000
0
Start timeEnd time
Figure 37 "Pac electric meter" operating mode
Enable delay
Disable threshold
Energy meter - Pac [W]
Status of
multi function relay
On
Off
t
The time window of the control of self-consumption is dened by the "Start time" and
"End time" parameters. Outside this time window the control of self-consumption is
inactive.
When control of self-consumption is active, the multi-function relay closes when the
power output measured with the energy counter at the grid connection point reaches the
"Enable threshold". The consumers are then switched on. The "Enable delay" timer can
be used to delay activation. When the output power falls below the "Disable threshold",
the multi-function relay opens. The consumers are switched off.
Procedure
1. In the "Settings menu" select the "MF relay" menu.
2. In "MF relay" select the "Self-consumption" setting.
3. Under "Mode" select the "Pac electric meter" operating mode.
5. Use MaxTalk2Pro to congure the S0 interface (energy counter).
Procedure using MaxTalk 2
1. Start MaxTalk 2
2. Connect MaxTalk 2 to the inverter.
3. Select the inverter in the plant tree.
4. In the "Device" menu, click "Settings". The "Settings" tab will be opened.
5. In the “Mode” menu (Multi-function relay) select the "PacEm" setting.
6. Congure the parameters.
6.3.6.2 Conguring the "Pac inverter" operating mode
The "Pac inverter" operating mode for the control of self-consumption can be congured
to suit the user's requirements. The functionality is illustrated in Figure 38.
Pac [W]
5000
4000
3000
Enable threshold
2000
1000
0
Start timeEnd time
Enable delay
Disable threshold
Output of the inverter - Pac [W]
Status of multi function relay [on/off]
Figure 38 "Pac inverter" operating mode
The time window of the control of self-consumption is dened by the "Start time" and
"End time" parameters. Outside this time window the inverter's control of self-consumption is inactive.
Status of
multi function relay
On
Off
t
en
49
When control of self-consumption is active, the multi-function relay closes when the
inverter's output power reaches the "Enable threshold". The consumers are then
switched on. The "Enable delay" timer can be used to delay activation. When the output
power falls below the "Disable threshold", the multi-function relay opens. The consumers
are switched off.
Procedure
1. In the "Settings" menu select the "MF relay" submenu.
2. In "MF relay" select the "Self-consumption" setting.
3. In "Mode" select the "Pac inverter" operating mode.
4. In the "Device" menu, click "Settings". The "Settings" tab will be opened.
5. In the "Mode" menu (Multi-function relay) select the "PacInv" setting.
6. Congure the parameters.
50
6.4 Displaying the conguration
All available operating parameters, standard-specic functions and their parameterization can be retrieved in the "Conguration" menu. Conguration of the standard-specic
functions depends on the country setting selected.
Note
The MaxTalk 2 Pro service and communication software makes it possible
for authorized personnel to individually adjust the operating parameters (see
Section 12).
6.4.1 Procedure
1. In the Main Menu, select the "Conguration" menu.
Figure 39 "Configuration" menu
2. Press to select the parameter:
EntryDescription
CountryCountry setting selected at the time of initial start-up.
Plant system ratingPlant system rating selected at initial start-up (only available
with the "Germany" country setting).
SSFMenu of standard-specic functions and parameters
en
– The "SSF" menu contans the following sub-menus.
MenuDescription
External inputDisplay of external control functions (external shutdown and
external output control).
Inverter start-upThose functions are displayed which are active before the
inverter is connected to the grid (start conditions).
Grid operationThose functions are displayed which are active during the
inverter's grid operation (grid monitoring).
LimitationThose functions are displayed which limit the inverter's output
values, such as active and reactive power and output current
(output limitation).
51
MenuDescription
Reactive powerThose functions are displayed that have an impact on the
Reference parametersDisplay of nominal values and reference values.
reactive power taken up or given out by the inverter (reactive
power control).
3. Press to conrm the selection.
– Section 6.4.2 contains the description of the SSF functions and parameters.
4. Press to return to the Main Menu.
6.4.2 Description of extended functions and parameters
This section contains the description of the functions and parameters available from the
"SSF" menu.
External input
Functions and parameters of the "External input" sub-menu:
Function / parameterDescriptionUnit / status
EISDMonitoring of "external deactivation" input (NA and
N inputs)
EISD-ENAEISD function statusDisabled/enabled
EPCOutput control by ripple control receiver or similar
external control unit
EPC-ENAEPC function statusDisabled/enabled
Inverter start-up
Functions and parameters of the "Inverter start-up" sub-menu:
Function / parameterDescriptionUnit / status
PVGITChecking the insulation resistance of the PV gener-
ator to ground
PV GIT-E NAPVGIT function statusDisabled/enabled
PV GIT-TH RMinimum permissible insulation resistanceΩ
RCMUTChecking the integrated fault current monitoringRCMUT-ENARCMUT function statusDisabled/enabled
ISTChecking the grid relay
IS T-EN AIST function statusDisabled/enabled
GPTChecking the grid parametersGP T- ENAGPT function statusDisabled/enabled
GPTVMIN-THRMinimum permissible mains voltageV
GP T V M A X-T HRMaximum permissible mains voltageV
GPTFMIN-THRMinimum permissible mains frequencyHz
GPTFMAX-THRMaximum permissible mains frequencyHz
-
-
-
52
Function / parameterDescriptionUnit / status
GP T-MO TChecking durations
Grid operation
Functions and parameters of the "Grid operation" sub-menu:
Function / parameterDescriptionUnit / status
GVMMIN1Checking the minimum permissible mains voltage
(limit 1)
GVMMIN1-ENAGVMMIN1 function statusDisabled/enabled
GVMMIN1-THRLimit valueV
GVMMIN1-DLYTrip times
GVMMA X1Checking the maximum permissible mains voltage
(limit 1)
GVMMAX1-ENAGVMMAX1 function statusDisabled/enabled
GV MMAX1-T HRLimit valueV
GV MMA X1-DLYTri p t im es
GVMMIN2Checking the minimum permissible mains voltage
(limit 2)
GVMMIN2-ENAGVMMIN2 function statusDisabled/enabled
GVMMIN2-THRLimit valueV
GVMMIN2-DLYTrip times
GVMMAX2Checking the maximum permissible mains voltage
(limit 2)
GVMMAX2-ENAGVMMA X2 function statusDisabled/enabled
GV MMAX2-THRLimit valueV
GV MM A X 2-DLYTri p t im es
GVM10AMA XChecking the maximum permissible average value
for mains voltage over the last 10 minutes
GVM10AMAX-ENAGVM10AMAX function statusDisabled/enabled
GV M10A M A X-T H RLimit valueV
GV M10AM A X-DLYTrip times
GFMMIN1Checking the minimum permissible mains fre-
quency (limit 1)
GFMMIN1-ENAGFMMIN1 function statusDisabled/enabled
GFMMIN1-THRLimit valueHz
GFMMIN1-DLYTr ip times
GFMMA X1Checking the maximum permissible mains fre-
quency (limit 1)
GFMMAX1-ENAGFMMAX1 function statusDisabled/enabled
GF MMAX1-T HRLimit valueHz
GF MM A X1-DLYTr ip times
-
-
-
-
V
-
-
en
53
Function / parameterDescriptionUnit / status
GFMMIN2Checking the minimum permissible mains fre-
quency (limit 2)
GFMMIN2-ENAGFMMIN2 function statusDisabled/enabled
GFMMIN2-THRLimit valueHz
GFMMIN2-DLYTr ip times
GFMMAX2Checking the maximum permissible mains fre-
quency (limit 2)
GFMMAX2-ENAGFMMAX2 function statusDisabled/enabled
GF MMAX2-THRLimit valueHz
GFMM A X2-DLYTrip times
AISDetection of island operationAIS-ENAAIS function statusDisabled/enabled
AI S- DLYTri p t im es
RBCMMonitoring the continuous leakage currentRBCM-ENARBCM function statusDisabled/enabled
RB CM-T HRMaximum permissible leakage currentA
RSCMMonitoring the leakage current step valueRSCM-ENARSCM function statusDisabled/enabled
DCCIMMonitoring the DC component in the AC currentDCCIM-ENADCCIM function statusDisabled/enabled
DCCIM-THRMaximum permissible DC component in AC current A
DCCIM-DLYTrip t imes
-
-
Limitation
Functions and parameters of the "Limitation" sub-menu:
Function / parameterDescriptionUnit / status
ACPPLMaximum increase of the active power during grid
connection
ACPPL-ENAACPPL function statusDisabled/enabled
ACPPL-MGDTIncrease% of Pac nom/
ACPPL-INIACPPL at every start-upDisabled/enabled
ACPPL-RCNACPPL at boot after grid disconnection through
coupler breaker
ACPLLimitation of active output powerAC P L- L MTLimit valueW
APPLLimit of the apparent powerAPPL-LMTLimit valueVA
OCLLimitation of the output currentOC L- L MTLimit valueA
-
min
Disabled/enabled
54
Function / parameterDescriptionUnit / status
PFLM2P(f) mode 2-
PFLM2-STRTFQStart frequencyHz
PFLM2-RDNReduction of active power
PFLM2-RNCIncrease to rated output power % of Pac nom/
% of PM/Hz
min
Reactive power
Functions and parameters of the "Reactive power" sub-menu:
Function / parameterDescriptionUnit / status
QMO-AMReactive power control0=OFF
QMCQReactive power mode constant "Q"-
QMCQ-QSVReactive power value% of Pac nom
QMCQ-VLEStatus of the voltage-dependent reactive power
QMCQ-VLIHUpper limit value of the mains voltageV
QMCQ-VLOLLower limit value of the mains voltageV
QMCQ-PLEStatus of the active power-dependent reactive
QMCQ-PLIUpper limit value of the active powerW
QMCQ-PLOLower limit value of the active powerW
QMCPP
QMCPP-PSP1…PSP10 Characteristic values 1 to 10 of Pac active power% of Pac nom
QMCPP-CPSP1…
CP SP 10
QMCPP-VLEStatus of mains voltage-dependent reactive power
QMCPP-VLIHUpper limit value of the mains voltage V
QMCPP-VLOLLower limit value of the mains voltage V
QMCCP
QMCCP-CPSV
QMCCP-VLEStatus of mains voltage-dependent reactive power
QMCCP-VLIHUpper limit value of the mains voltageV
QMCCP-VLOLLower limit value of the mains voltageV
QMCCP-PLEStatus of active power-dependent reactive power
QMCCP-PLIUpper limit value of the active powerW
QMCCP-PLOLower limit value of the active power W
QMQU1Reactive power mode "Q(Vac) mode 1"QMQU1-VSP1 to VSP10 Characteristic values 1 to 10 of mains voltage (Vac) V
control hysteresis for QMCQ
power control hysteresis for QMCQ
Reactive power mode "cosφ(Pac)"
Characteristic values 1 to 10 of power factor cosφ
control hysteresis for QMCPP
Reactive power mode "cosφ"
cosφ value
control hysteresis for QMCCP
control hysteresis for QMCCP
[OEX/UEX]
Disabled/enabled
Disabled/enabled
-
- [UEX/OEX]
Disabled/enabled
-
- [UEX/OEX]
Disabled/enabled
-
en
55
Function / parameterDescriptionUnit / status
QMQU1-CPSP1 to
CP SP 10
QMQU1_D LYDelay time when mains voltage ( Vac) changess
QMQU1-V LEStatus of active power-dependent reactive power
QMQU1-V LIActive power switch on value% of Pac nom
QMQU1-V LOActive power switch off value % of Pac nom
QMQU2Reactive power mode "Q(Vac) mode 2"QMQU2-UPQUpper reactive power value (OEX)% of Pac nom
QMQU2-LOQLower reactive power value (UEX )% of Pac nom
QMQU2-UPV LIMains voltage switch on value for QMQU2-UPQV
QMQU2-UPV LOMains voltage switch off value for QMQU2-UPQV
QMQU2-LOVLIMains voltage switch on value for QMQU2-LOQV
QMQU2-LOVLOMains voltage switch off value for QMQU2-LOQV
QMQU2-PLEStatus of active power-dependent reactive power
QMQU2-PLIActive power switch on value% of Pac nom
QMQU2-PLOActive power switch off value% of Pac nom
Characteristic values 1 to 10 of reactive power Q% of Pac nom
[UEX/OEX]
Disabled/enabled
control hysteresis for QMQU1
Disabled/enabled
control hysteresis for QMQU2
Reference parameters
Functions and parameters of the "Reference parameters" sub-menu:
Function / parameterDescriptionUnit
NAPRated output power (Pac nom)-
NAP-VALValueW
NOCRated output currentNOC-VALValueA
GCDCoupler breaker switch delayGCD-CDLYTrip t imes
56
6.5 Displaying the measured values
The current measured inverter values can be accessed in the “Measured values” menu.
1. In the main menu, select the "Measured values" menu.
Figure 40 "Measured values" menu
2. Press or to scroll through the measured values:
Pac electric meter* *
Frequency
Temperatur e
* only available with SM5TP2, SM6TP2 and SM7TP2
** is only displayed when congured accordingly
Input voltage to tracker 1 / to tracker 2V
Total input current / to tracker 1 / to tracker 2A
Total input power / to tracker 1 / to tracker 2W
Output voltageV
Phase voltage L1 / L2 / L3V
Total output currentA
Phase current L1 / L2 / L3A
Apparent output powerVA
Output powerW
Reactive power (+: overexcited / −: underexcited)var
Power factor (OEX: overexcited / UEX: underexcited)Measured value of external energy counter W
Mains frequencyHz
Equipment temperature°C
en
3. Press to return to the Main Menu.
Note
The measured inverter values are not suitable for billing purposes or calculating the efciency. The measuring error may amount to up to ±5% depending
on the measured value. Only the measured values of a calibrated electricity
meter can be relied upon for billing purposes.
57
MaxTalk2 measured values
The following additional values can be viewed with the MaxTalk 2 service software:
Measured valueDescriptionUnit
Vac 10 min10 minute average value of the mains voltageV
Iac meanMean value of output currentA
IerrEffective value of leakage currentmA
Ierr DCDirect current component of leakage currentmA
6.6 Registering for MaxView
Register for the free web-based MaxView application. With MaxView it is possible to view
and graphically display the yield data of your PV power plant from anywhere.
Note
Frequently asked questions about MaxView and the replies to these can be
found on our website at https://maxview.solarmax.com/faq.xhtml.
Procedure
1. Connect the inverter to the internet via the Ethernet interface (see Sections 5.5.3 and
6.3.3).
2. Enter your registration data in a web browser under https://maxview.solarmax.com.
3. Learn about the various functions of MaxView.
6.7 Update rmware
The inverter rmware can be updated with the help of the MaxTalk 2 service software.
For further information, please refer to the MaxTalk 2 operating manual, which you can
download from our website (www.solarmax.com; Downloads/Software/MaxTalk 2).
The current rmware le for the inverters of the TP series is available from our website
(www.solarmax.com, Downloads/String inverters/TP series/Software).
58
7 Operation
7.1 Graphics display
The graphics display shows the system values, status information, and the inverter’s fault
messages. The graphics display can be used for obtaining information on the current
operating status, accessing the integrated data logger and entering various settings on
the inverter.
5
4
1
2
3
Figure 41 Graphics display with the standard "Overview" display
No.Description
1Graphics display with backlighting
2Status LED: operating status display (see Section 7.7)
3Function keys (membrane keypad)
4Display with Ethernet connection (link display)
5Symbol for data communication
en
The function keys can be used for navigating within the menu structure:
Symbol Description
Select menu or parameter
Edit parameter
Highlight number (parameter editing)
Increase highlighted number / select menu or parameter
Confirm
Cancel
59
7.2 Menu structure
Overview
Main menu
Statistics
Days
Months
Years
Total
Reset
* is only displayed when congured
accordingly
Information
Measured values
Conguration
SSF
External input
Inverter start-up
Grid operation
Limitation
Reactive power
Reference parameter
Settings
Language
Time
Date
Network
Device adress
IP-Mode
IP
Netmask
Gateway
TCP Port
DNS1
DNS2
MF Relay
Off
Status relay
Selfconsumption
Grid Feed-In limitation*
Pac electric meter
Pac inverter
SPD Monitor
60
Figure 42 Menu structure of graphics display
7.3 Displaying the operating data overview
The overview shows the most important operating data of the inverter. The graphics
display automatically switches to the "Overview" if no function button is pressed for 120
seconds.
1. In the Main Menu, select the "Overview" menu.
Figure 43 "Overview" menu
DisplayDescription
19.06.2013 / 11:44:35Date and system time (examples)
PacCurrent output power [W]
TodayDaily yield [kWh]
Tot alTotal yield since commissioning [kWh]
StateOperating status of inverter (see Section 7.7 )
7.4 Displaying Main Menu
From the "Main menu", you can open all menus.
1. In order to switch from "Overview" to the "Main menu", press any function key.
en
Figure 44 Main Menu
2. Press or to select the menu.
3. Press to conrm the selection.
61
7.5 Statistics
The "Statistics" menu can be used for accessing the inverter's data logger. The data
logger saves the statistics values of the past 25 years. The daily, monthly, yearly and total
statistics can be displayed. All statistics values can be deleted.
7.5.1 Displaying the daily statistics
The daily statistics displays the statistics values for the last 31 days.
1. In the "Statistics" menu, select the "Day" sub-menu.
Figure 45 Daily statistics
2. Press or to select the day:
Statistics valueDescription
YieldDaily yield [kWh]
MaximumFed-in maximum power [ W]
HoursOperating hours in the "Mains operation" status
3. Press to return to the "Statistics" menu.
62
7.5. 2 Displaying the monthly statistics
The monthly statistics displays the statistics values for the last 12 months.
1. In the "Statistics" menu, select the "Month" sub-menu.
Figure 46 Monthly statistics
2. Press or to select the month:
Statistics valueDescription
YieldMonthly yield [kWh]
MaximumFed-in maximum power [ W]
HoursOperating hours in the "Mains operation" status
3. Press to return to the "Statistics" menu.
7.5.3 Displaying the annual statistics
The annual statistics displays the statistics values for the last 25 years.
1. In the "Statistics" menu, select the "Year" sub-menu.
Figure 47 Annual statistics
2. Press or to select the year:
Statistics valueDescription
YieldAnnual yield [kWh]
MaximumFed-in maximum power [ W]
HoursOperating hours in the "Mains operation" status
en
3. Press to return to the "Statistics" menu.
7.5.4 Displaying the total statistics
The total statistics shows the statistics values since commissioning.
1. In the "Statistics" menu, select the "Total" sub-menu.
Figure 48 Total statistics
63
Statistics valueDescription
YieldTotal yield [kWh]
HoursTotal hours in the operating status "Mains operation"
2. Press to return to the "Statistics" menu.
7.5.5 Deleting the statistics values
The statistics values of the data logger can be deleted.
1. In the "Statistics" menu, select the "Reset" sub-menu.
Figure 49 Resetting the inverter's data logger
Note
The deletion process cannot be undone!
2. Press to cancel the deletion process.
3. Press to delete all statistics values.
64
7.6 Displaying information
This menu displays information about the inverter. The menu can be used to identify the
inverter.
1. In the Main Menu, select the "Information" menu.
Figure 50 "Information" menu
2. Press or to scroll.
DisplayDescription
Device typeInverter type
Serial No.Inverter serial number
FirmwareFirmware version installed in the inverter
StateCurrent operating status
WarningCurrent warning message
CommissioningDate of initial start-up
Operating hoursTotal operating hours in mains operation
MAC addressMAC address of the inverter
3. Press to return to the Main Menu.
7.7 Displaying the operating status of the inverter
The status LED (Figure 41/No. 2) signals the current operating status of the inverter by its
different signal colors. The status message, which gives a more detailed description of
the operating status, is displayed at the graphics display.
In addition to the status messages, the inverter also displays warnings. Warnings result
from device errors or external failures. The inverter continues to feed power into the grid,
but it is possible that yield is reduced. Warnings are independent of the operating status
and are displayed on the graphics display alternately with the current status message.
Status LEDOperating statusDescription
Off
Flashes green
Green
Flashes orange
Orange
Red
Flashes red
-Inverter is switched off
BootingInverter is star ting up
Mains operationMains feed-in (normal operation)
-
Failure
Error
Blocked
Warning → no grid disconnection
External failure → grid disconnection
Device error → grid disconnection
Inverter is blocked → grid disconnection
en
The "Fault", "Error", and "Blocked" operating status messages, as well as the warnings,
usually require certain measures to be carried out by the qualied electrician in charge
(see Section 8).
65
7.7.1 Booting
Status LED: ashes green
Status messageDescription
Irradiation too lowThe solar irradiation or rather the available output is too low for
Startup…The inverter checks the internal hardware and software compo-
Restar t delayThe inverter delays connection to the grid (af ter a disconnection
mains operation.
nents before connecting to the mains.
from the grid or when booting).
7.7. 2 Mains operation
The status LED lights up green.
Status messageDescription
Maximum output powerThe inverter limits the in-feed power to the maximum permissible
Mains operationThe inverter is in feed mode.
Idc limitationThe inverter limits the PV generator current to the maximum
Iac limitationThe inverter limits the output power to the maximum permissible value
Restar t limitationFollowing an external output limitation the inverter increases the
Frequency limitationThe inverter temporarily limits the active power owing to an active
External limitationThe inverter's fed-in active power is limited by external output
Temperature limitationThe output power is temporarily reduced in order to limit the
value. This may occur if the PV generator is oversized.
permissible value. This may occur if the PV generator is designed
such that the current at Maximum Power Point (MPP) exceeds the
maximum permissible input current of the inverter.
(where the PV generator is oversized).
active power with dened progression (Pac progression and/or Soft
Start).
frequency-dependent power reduction.
control.
inverter's temperature.
66
8 Troubleshooting
8.1 SolarMax Service Center
If you have technical questions or difculties, our Service Center will be happy to help you.
To do that we need the following information:
Device type
Serial number (S/N)
Installation location
Information about the failure you are experiencing (status message, etc.)
Contacting the SolarMax Service Center
The contact details of the SolarMax Service Center can be found on the back of this
instruction manual.
Sputnik Engineering AG
Länggasse 85
CH-2504 Biel/Bienne
8.2 Diagnosis & measures
The following tables describe possible actions for remedying faults. If the actions suggested do not correct the fault, please contact the SolarMax Service Center.
8.2.1 General troubleshooting
ProblemCauseActions
The graphics display
remains blank
The graphics display only
ashes briey.
The DC disconnector is switched
off.
The irradiation is too low.Wait until irradiation is high
The strings are interrupted.Check the PV generator and
It is possible that the inverter is
defective.
The irradiation is too low.Wait until irradiation is high
Switch on the DC disconnector.
enough.
eliminate the interruption.
Contact the SolarMax Service
Center.
enough.
en
67
8.2.2 Warnings
The status LED ashes orange.
WarningCauseActions
Temperature limitationThe output power is temporarily
reduced in order to limit the
inverter's temperature.
Fan failureThe external or internal fan is
defective or soiled.
RTC errorDate and time in the RTC (real-
time clock) were reset due to a
malfunction.
Firmware mismatchThe rmware versions of the
inverter controllers do not match.
Ensure that
the recommended maximum
ambient temperature is not
exceeded and that the cooling
ns are free from dust and
dirt.
Contact the SolarMax Service
Center.
Set the date and time (see
Section 6.3.2). If this problem
occurs frequently, contact the
SolarMax Service Center.
Contact the SolarMax Service
Center.
Flash errorAn error has occurred in the ash
memor y.
SPD failureA signal is active at the "lightning
protection monitoring" interface
(inputs BS+ and BS-).
Electric meter failureThe communication between
energy counter and inverter is
interrupted.
Contact the SolarMax Service
Center.
Check the external lightning
protection module.
Check the connection cable
and/or the energy counter.
8.2.3 Faults
The status LED lights up orange.
Note
MaxTalk2 can be used to display the last error messages.
Status messageCauseActions
Vdc too highThe DC input voltage of the
inverter is too high.
Ierr too highThe leakage current has exceeded
the admissible absolute limit value
RB CM-T HR.
Ierr step to highThe leakage current has exceeded
the permissible RSCM step value.
No mainsThere is no mains voltage.Check the AC conductor
Switch of f the DC disconnector. Check the PV generator’s conguration.
Check the PV generator.
(fuses).
68
Status messageCauseActions
Frequency too highThe mains frequency is outside
Frequency too lowThe mains frequency is outside the
Mains errorThe inverter detects island mode. If this problem recurs, contact
Vac too highThe mains voltage is outside the
Vac too lowThe mains voltage is outside the
Vac 10 min too highThe maximum 10-minute average
DC insulation faultThe insulation resistance of the PV
Error ext. input 1The external grid monitoring
the GFMMAX1-THR, GFMMAX2-THR or GPTFMA X-THR limit
values.
GFMMIN1-THR, GFMMIN2-THR or
GPTFMIN-THR limit values.
GV MMAX1-T HR, GV MMA X2-T HR
or GPT VM AX-THR limit values.
GVMMIN1-THR, GVMMIN2-THR or
GPT VMIN-THR limit values.
value of the mains voltage
GVM10AMAX-THR is too high.
generator to ground is too low.
Phase and neutral conductor are
interchanged.
has disconnected the inverter
from the grid. An active signal is
present at the "NA" input (external
shutdown).
If this problem recurs, contact
the grid operator in charge.
the grid operator in charge.
If this problem recurs, contact
the grid operator in charge.
Check the PV generator.
Connect the AC input conductor as described in Section
5.3.
If this problem recurs, contact
the grid operator in charge.
en
8.2.4 Error
The status LED lights up red.
Status messageCauseActions
Device error (+ error code) The inverter is defective.Note the displayed two-digit
error code and contact the
SolarMax Service Center.
8.2.5 Blockings
The status LED will ash red.
Status messageCauseAction
Firmware updateThe inverter's rmware is being
updated.
None. The inverter automatically resumes mains operation
once the rmware update is
complete.
69
9 Maintenance
The following maintenance work should be carried out when required:
Regularly check the operating status of the inverter on the graphics display, see Sec-
tion 7.7.
Clean the graphics display with a damp cloth. Do not use harsh or abrasive cleansing
agents.
Check the inverter for external damage. If any damage is found, inform the respective
qualied electrician.
70
10 Decommissioning
10.1 Instructions for inverter replacement
Before replacing the inverter, write down the total yield. The procedure for viewing the
total yield is described in Section 7. 5 . 4 .
10.2 Inverter disassembly
DANGER!
Fatal electric shock hazard!
Components within the inverter are charged with dangerously high voltage.
Before starting inverter disassembly, the inverter must be fully discon-
nected in accordance with the procedure described in this chapter.
WARNING!
Risk of injury from electric arc!
Dangerous electric arcs could occur when removing live DC conductors.
Switch off the DC disconnector before pulling out the DC plugs.
ATTENTION!
Electrostatic discharge can damage the inverter
Do not touch any electronic components inside the inverter.
Procedure
1. Switch off the external AC disconnector.
– The "No grid" status message is shown on the inverter.
2. Switch off the DC disconnector at the inverter.
en
Figure 51 Switching off the DC disconnector
3. Use a size 2 screwdriver to remove the locking clips on the DC plugs.
4. Pull out the DC conductors to fully separate the inverter from the PV generator.
71
DANGER!
Fatal electric shock hazard!
After the inverter has been disconnected, high residual voltages remain in the
inverter for approx. 5 minutes.
Wait for 5 minutes.
5. Open the inverter as described in Section 5.1.
6. Use a suitable charge indicator to check that all terminals are free from voltage.
– When all terminals are de-energized, you can remove the AC feed cable, the 2nd
protective conductor and all communication lines from the inverter.
CAUTION!
Risk of burns due to hot casing components!
Wait until the back of the casing has cooled down.
7. Fit the contact protection.
8. Fit the cover of the inverter.
9. Remove the 2 lateral Phillips head screws that secure the inverter on the mounting
rail.
10. Disengage the inverter from the mounting rail.
10.3 Disposing of the inverter
Dispose of the inverter as indicated by the local waste disposal regulations. You can also
return the inverter, at your own cost, to Sputnik Engineering AG for professional disposal.
The contact details of the SolarMax Service Center can be found on the back of this
instruction manual.
last 31 days, 12 months, 10 years / output cur ves of the
Requirement class D ( VDE 0 675-6) and/or type 3 (EN
last 7 days
616 43-11)
3)
Yes
61000-6-3
UTE C15-712-1 / E8001-4-712
integrated
Country-specific settings
The factory’s default settings for different countries can be viewed in the technical information “SSF - Standard specic functions and parameters”. This document can be downloaded from our website at: www.solarmax.com; Downloads / String inverters / TP series.
74
12 Accessories and options
Accessory/optionDescription
Y-type plug connectorSet consisting of two Y-type plug connectors for the parallel connec-
tion of solar modules (1 plug connector socket/socket to plug, 1 plug
connector plug/plug to socket, item No. 10 005 602).
MaxViewFree web-based application with various functions for remote call-up,
graphics visualization and export of yield data.
MaxTalk2Free communication and service software for local monitoring of the
PV power plant. This software can be downloaded from our website
(www.so larmax.com / D ownloads / Soft ware / MaxTalk).
MaxTalk2ProProfessional version of MaxTalk2 for the conguration of inverters.
This software can be downloaded from our website (www.solarmax.
com / Download s / Softw are / MaxTalk). The "Solar Max TP series parameter conguration with MaxTalk 2 Pro" is also available from
that link.
MaxMonitoringUsing the free MaxMonitoring sof tware you can display the perfor-
mance data of your PV power plant at any time from home. MaxMonitoring is available for PC, MacOS and Linux and also as an app for
Android and iOS.
MaxDesignFree software for determining the size of PV power plants.
You can nd further information on our website at www.solarmax.com.
en
75
13 Warranty
Sputnik Engineering AG (hereafter SPUTNIK ) guarantees full function and lack of defects of its
technical devices for a warranty period as specified below for each type of device. Such warranty
period can be extended by means of a warranty extension, subject to the conditions named below.
This manufacturer’s warranty exists next to the seller’s warranty (if any) as prescribed by law. As
far as identical with regards to the content, the rights under this manufacturer’s warranty supersede
any rights under the seller’s warranty. Please contact the seller with regard to any claims based on
the seller’s warranty.
1. Warranty Period (Basic)
Central inverters and accessories: 24 months from the date of purchase, but at maximum 30
months after dispatch of the device by SPUTNIK.
String inverters: 60 months from the date of purchase, but at maximum 72 months after dis-
patch of the device by SPUTNIK.
If in individual cases SPUTNIK has agreed in writing to a dif ferent warranty period, such arrangement supersedes the above provisions.
2. Scope of Manufacturer’s Warrant y
In case of defect or malfunction of a device within the manufacturer’s warranty period, and
upon fulfillment of the conditions for warranty claims named hereafter, the device will be repaired
or replaced by SPUTNIK-service personnel within a reasonable time, in either case free of charge,
unless this is impossible or disproportionate. SPUTNIK may decide at its own discretion whether a
device will be repaired or replaced.
Replacement: Exchange of device free of charge. SPUTNIK’s separate conditions for exchange
of devices apply: This warranty covers the free delivery of an equivalent replacement device.
Further, your installer is entitled to claim a flat rate compensation for the replacement work
from SPUTNIK. Please do not hesitate to ask us about the current amount of such flat rate
compensation.
Repair: Repair of device free of charge. This warranty covers costs for material, work and travel
by SPUTNIK personnel or by personnel authorized by SPUTNIK.
Please be aware that the per formances of SPUTNIK under this warranty are only free of charge in
countries approved by SPUTNIK. Please contact your seller for details. A current list of approved
countries can be found on our homepage. Repair and replacement outside of the approved countries
are only possible after prior consultation of and approval by SPUTNIK. In such case, travel and
shipment costs are borne by the customer.
Any further claims, especially claims for compensation of damages resulting directly or indirectly
from the defect or claims for replacement of fur ther costs in connection with the installation and
removal of devices or claims for loss of profits are not covered by this warranty.
76
3. Extent of Repair and Replacement
SPUTNIK will maintain repair material and stock of each type of device during the warranty period
only at its own reasonable discretion. In case repair materials for a certain type of inverter and/or an
identical replacement device are not in stock anymore, the following applies:
SPUTNIK is allowed to replace the defective inverter with a comparable device of the same or
superior per formance. The costs (time and material) for technical adjustments necessary for
the installation of such comparable devices are covered by this warranty only up to a limited
amount; any flat rate compensation owed by SPUTNIK for the replacement is deductible. Please
do not hesitate to ask us about the currently applicable amount. The exchange and connection
of peripheral devices due to possible non-compatibility with the replacement device or other
necessary adjustments to the surrounding installations of the device (including power lines,
ventilation and safety installations) are not covered by this warranty. However, SPUTNIK shall
within the bounds of reasonability do its best to minimize the effor t of such adaptation work.
In case repair materials are not available with reasonable efforts anymore, SPUTNIK is allowed
to replace the inverter, subject to the conditions mentioned in the paragraph above.
4. Warranty Period in Case of Repair/Replacement
In case of repair or replacement of devices under this warranty, the repaired respectively replaced
device will inherit the remaining warranty time of the original device.
5. Exclusion of Warranty
Especially in the following cases, this manufacturer’s warranty does not apply:
Transport damage;
Technical intrusions, modifications or repairs of the devices not authorized by SPU TNIK;
Use of devices for purposes they are not intended for, incorrect or unreasonable manipulation,
incorrect or unreasonable installation;
Failure to observe the manufacturer’s operating, installation and maintenance directions;
Inadequate environmental conditions (e.g. insufficient ventilation of the device; humidity etc.);
Superior force (e.g. lightning strike, overvoltage, floods, fire, etc.).
en
6. Handling of Warranty Cases
For the processing of warranty cases, use of SPTUNIK’s hotline is mandatory. The handling of warranty cases must take place in accordance with the instructions provided by the hotline.
The hotline number for your country can be found on SPUTNIK’s homepage. Please hold the serial
number, article description, a short description of the defect and the purchase receipt ready for
transmission to the hotline.
Any repair action taken by the buyer or third parties without authorization by SPUTNIK will not be
compensated.
In case these terms on the handling of warranty cases are not respected, SPUTNIK may refuse its
warranty performances.
77
7. Suspension of Warranty
Sputnik reserves its right to suspend this manufacturer’s warranty temporarily or definitely in case
a specific installation does not allow a correct functioning of the inverters (e.g. in case of one of the
circumstances listed in cipher 5).
The suspension of the warranty can be lifted upon approval by SPUTNIK. Such approval must be
issued by SPUTNIK in writing, confirming that the warranty has again become effective.
8. Warranty Extension
The warranty period can be extended through purchase of a warranty extension within the time
limits mentioned hereafter. For certain types of devices, such warranty extensions can also be
purchased only for a limited scope of warranty performances. The purchase of a warrant y extension
will be confirmed by SPUTNIK in form of a warranty certificate (including serial number of affected
product). In case of replacement of a device, the serial number in such warrant y certificate remains
unchanged, without any influence on the validity of the warranty extension.
a) Time limits
String inver ters: The extension of the basic warranty can be ordered within 60 months after purchase, but the latest within 72 months af ter dispatch of the device by SPUTNIK.
Central Inverters: The extension of the basic warrant y can be ordered within 3 months after purchase, but the latest within 12 months after dispatch by SPUTNIK.
b) Extent
Full warranty extension – FULL (available for central inverters and string inverters): A full warranty
extension includes all the warranty performances as described in the manufacturer’s basic warrant y
terms.
Limited warranty extension– LIMITED (available only for central inverters):
A limited warranty extension covers only the costs for the material required for the repair. The costs
for travelling, labor and other expenses are not covered and will be invoiced on a time and expenses
basis by SPUTNIK.
c) Effectiveness of Warranty Extension
It is a mandatory requirement for the warranty extension to provide the completely filled out application form to SPUTNIK. The warranty extension becomes effective only after written confirmation
and provision of the warranty certificate by SPUTNIK.
78
9. After Expiration of Warranty Period
The costs for repair or replacement of devices after expiration of the warranty period are invoiced by
SPUTNIK on a time and material basis. SPUTNIK will maintain repair and replacement capabilities
beyond the warranty time only at its own discretion.
10. Applicable Law, Jurisdiction
Only Swiss Law applies. The exclusive place of jurisdiction lies in Biel/Bienne, Switzerland.
(v 20 13/0 5)
Notes
en
79
SolarMax Service Center
Please refer to our website for contact details:
www.solarmax.com/service
2014/ 05 en
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.