SolarMax 2000P, 5000P, 3000P, 4000P, 4600P Instruction Manual

Gerätedokumentation Instruction manual Documentation d’appareil
Documentación del dispositivo Documentazione dell’apparecchio
SolarMax P-Serie
2000P / 3000P / 4000P / 4600P / 5000P
Sputnik Engineering AG
Länggasse 85
Tel: +41 32 545 56 00
Fax: +41 32 346 56 09
E-Mail: info@solarmax.com
© Sputnik Engineering AG 2013
66
Contents
1 Notes on the present instruction manual 68
1.1 Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
1.2 Target groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
1.3 Where to keep this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
1.4 Symbols used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
2 Safety instructions 69
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
2.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
2.3 Symbols on the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
3 Description 71
3.1 Identication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3.2 Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3.3 Safety installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
3.5 Views of the unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
3.6 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
4 Installation 75
4.1 Transporting and storing inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.2 Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.3 Selecting the installation location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4.4 Mounting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5 Electrical connection 79
5.1 Opening the inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.1.1 Removing the cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.1.2 Removing the contact protection. . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.2 Connection area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.3 Connecting the inverter to the mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5.4 Connecting the inverter to the PV generator . . . . . . . . . . . . . . . . . . . . . . . . 84
5.5 Grid connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6 Commissioning 88
6.1 Activating the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.2 Initial start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.2.1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.2.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.2.3 Description of country-specic menus . . . . . . . . . . . . . . . . . . . . . 90
6.3 Auto-test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
en
67
6.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.4.1 Setting the display language and system time. . . . . . . . . . . . . . . . 93
6.4.2 Setting the network parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.5 Displaying the conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
6.6 Displaying the measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6.7 Registering for MaxView. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.8 Update rmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
7 Operation 103
7.1 Graphics display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2 Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
7.4 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
7.5 Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.5 .1 Displaying the daily statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.5 .2 Displaying the monthly statistics. . . . . . . . . . . . . . . . . . . . . . . . . 106
7.5 .3 Displaying the annual statistics . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.5 .4 Displaying the total statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.5.5 Deleting the statistics values. . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
7.6 Displaying information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
7.7 Operating status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
7.7.1 Booting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110
7.7.2 Mains operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110
8 Troubleshooting 111
8.1 SolarMax Service Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
8.2 Diagnosis & measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
8.2.1 General troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
8.2.2 Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
8.2.3 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
8.2.4 Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
8.2.5 Blockings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114
9 Maintenance 114
10 Decommissioning 115
10.1 Instructions for inverter replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
10.2 Inverter disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
10.3 Disposing of the inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
11 Technical data 117
12 Accessories and options 123
13 Warranty 124
68
1 Notes on the present instruction
manual
1.1 Scope
This instruction manual is applicable to the Solarmax 2000P, 3000P, 4000P, 4600P and 5000P inverters.
1.2 Target groups
Plant operators
Chapter 2 "Safety instructions" Chapter 7 "Operation"
Fitters
Chapter 2 "Safety instructions" The instructions in chapters 4 to 6 and 8 to 10 are only allowed to be performed by
trained skilled electricians (e.g. electricians, electric systems technicians, electrical mechanics, industrial electronics technicians).
1.3 Where to keep this manual
The plant operator must ensure that this instruction manual is available to the relevant persons at all times. If this original document is lost, an up-to-date version of this instruc­tion manual can be downloaded from our website at any time (www.solarmax.com).
1.4 Symbols used
The following safety instructions and general information are used within this instruction manual.
DANGER!
Non-observance of these safety instructions may immediately cause serious injuries or death.
WARNING!
Non-observance of these safety instructions may cause serious injuries.
CAUTION!
Non-observance of these safety instructions may cause minor or medium injuries.
en
69
ATTENTION!
Non-observance of these safety instructions may cause material damage.
Note
Notes contain additional information or facilitate the inverter operation.
2 Safety instructions
2.1 Intended use
The SolarMax P series inverters are designed exclusively to convert the direct current generated by PV modules into alternating current which conforms to the parameters of the public grid. Any other use is contrary to the design purpose.
The inverters of the P series may only be connected to Class II PV generators.
2.2 Safety instructions
DANGER! Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC voltage.
Make sure that all electrical feed-in lines to the inverter are de-energized
before starting any work on the inverter or the feed-in lines.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage.
Never open the inverter while it is in operation.
WARNING! Risk of injury from electric arc!
Removing the DC connector when live can lead to dangerous electric arcs.
Switch off the DC disconnector at the inverter before removing the DC
connectors.
70
2.3 Symbols on the inverter
Symbol Description
Protective conductor connection
The DC disconnector is switched off (the contacts are open).
The DC disconnector is switched on (the contacts are closed).
Risk of death through high voltages! Only qualied electricians may perform work on the inverter.
Careful - hot surfaces!
5 min
Risk of death due to high voltages! De-energize the inverter. Proceed to wait for 5 minutes before opening the inverter.
Only qualied electricians may perform work on the inverter.
Read the operating instructions - Please read and follow the instruc­tions supplied with the inverter. Do not remove any symbols on the inverter. Replace damaged symbols.
CE marking - The inverter complies with the requirements of the European EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC (see Section 11).
VDE-GS mark - The inverter complies with the relevant requirements of the German Product Safety Act.
Do not dispose of the inverter and its accessory components in the household waste.
en
71
3 Description
3.1 Identication
The inverter can be identied on the basis of the information provided on the nameplate (see Section 3.5).
3.2 Functionality
Inverter operation is completely automatic and depends on the available output of the PV generator. If there is enough power, the inverter starts mains operation and feeds into the power grid. If there is not enough power available from the PV generator, the inverter disconnects from the grid and shuts down.
The graphics display with three function keys allows convenient inverter operation and reading of all important operating data. The graphics display is only switched on when the DC input voltage is high enough.
The inverter has congurable functions for grid monitoring, limitation of output and reac­tive power control.
For the purpose of monitoring the PV power plant remotely, the inverter can be connected directly to the Internet via Ethernet.
With the optional I/O module, the inverter can be remotely switched off and its output controlled.
3.3 Safety installations
Overvoltage protection
P series SolarMax inverters feature integrated surge arrestors (varistors) at both input and output. Each DC input (plus and minus connection) is tted with a surge arrester. The surge arresters have a common gas discharge tube to ground. On the AC side a surge arrester is installed between the phase and neutral. A second surge arrester with gas discharge tube is tted between neutral and ground (for details regarding the tted surge arresters see section 11).
When designing the PV system, it may be necessary to provide additional external light­ning protection. The optional I/O module can be used to monitor external lightning protec­tion modules.
Fault current monitoring
The inverters in the SolarMax P series have an integrated AC/DC-sensitive fault current sensor. This sensor can distinguish between the operational capacitive stray currents
72
(caused by capacities of the PV modules to ground) and leakage currents (caused by touching a pole of the PV generator). If the inverter detects an excess in the permissible leakage or stray currents, it will disconnect from the grid.
Functions for current and power limitation
The inverters of the P series limit the DC feed-in current, the output power and the AC output current.
Temperature limitation
At ambient temperatures of more than 45 °C the equipment temperature may reach more than 80 °C. In such cases, the maximum in-feed power is temporarily reduced. When the equipment temperature rises to over 85 °C, the inverter disconnects from the grid.
3.4 Dimensions
104.5
480 189
[mm]
256.5
361
en
73
3.5 Views of the unit
4 1
5
7
23
6
No. Description
1 Cover 2 Graphics display 3 Type plate 4 DC disconnector 5 Cooling ns 6 Connection area 7 Mounting rail
74
3.6 Block diagram
+
+
I
0
U
U
U
Status signalling contact
Ethernet
DC measurement
AC measurement
Fan
RS485
External shutdown
Monitoring lightning protection
Inverter control
Booster control
Inverter
LCL lter
Booster 2
Booster 1
SolarMax P series
DC
DC
AC
K2K1
DC
DC
DC
External power control
Control unit
Communication module
Graphics display
* Tracker 2 only SolarMax 4000P / 4600P / 5000P ** optional
DC disconnector
DC input Tracker 1
DC input Tracker 2 *
I/O module **
AC output
EMC lter
EMC lter
EMC lter
en
75
4 Installation
4.1 Transporting and storing inverters
Make sure that the ambient conditions during transportation and storage are within the specied limits (for details see section 11).
4.2 Checking the delivery
Check the contents of the delivered package for completeness and possible damage. In the case of an inadequate delivery please contact your dealer or the SolarMax Service Center.
3
1
2
6
7
8
9 11 12 13 1410
54
Gerätedokumentation
SolarMax P-Serie
2000P / 3000P / 4000P / 4600P / 5000P
No. Quantity Description
1 1 Inverter 2 1 Instruction manual
76
No. Quantity Description
3 1 Mounting rail 4 2 Plastic dowels 8 x 40 (for xing in brickwork) 5 2 Washers M6 x 18 INOX (for the installation of the inverter) 6 2 External hexagon wood screws 6 x 50 INOX (for the installation of the
inverter)
7 2 Phillips head sheet metal screws 4.8 x 13 (for locking the inverter on the
mounting rail) 8 3 Locking pins (for plugging unused holes in multiple cable connectors) 9 4 Locking clips (for DC plugs) 10 1 Toothed lock washer M5
(for connection of 2nd protective conductor)
11 1 Cable lug M5 x 10mm
2
12 1 Washer M5 13 1 Spring lock washer M5 14 1 Phillips head screw M5 x 12
4.3 Selecting the installation location
DANGER! Fatal fire or explosion hazard!
The inverter is an electrical device with heat generation and the possibility of sparking.
Install the inverter in an environment that is free of ammable gases and
uids.
Never install the inverter near combustible materials. The installation
base must be non-combustible.
Follow the local re safety regulations.
The ambient conditions are specied in the specications, see Section 11.
Location and installation conditions
Select a dry location protected from water and snow. Install the inverter in an easily accessible location, so that maintenance work can be
carried out easily.
Do not expose the inverter to direct sunlight. Never install one inverter above another (this would reduce the cooling effect; see
Section „Temperature dependent output reduction“; page 122).
en
77
Maintain the following installation distances:
50
50
[cm]
°C
20
20
Install the inverter in a vertical position. Do not install the inverter in a horizontal or inclined position.
OK !
The optimal cooling of the inverter is only guaranteed when the cooling ns (see sec-
tion 3.5) are absolutely free of dust and dirt.
When installing the inverter on a mast, a mounting plate with at least the same
dimensions as the back of the inverter is needed.
The ambient air around the inverter must be free from dust, salt and ammonium
vapors.
The location must meet the requirements regarding electromagnetic immunity and
interference emission.
78
4.4 Mounting the inverter
The inverter is xed to the wall by a mounting rail. The mounting rail and the necessary xing accessories are included in the delivery package.
Procedure
1. Use the mounting rail as a template for drilling the holes.
2. Use a spirit level to position the mounting rail horizontally.
3. Mark two drilling holes.
446
376
26
[mm]
26
6.5
6.5
– For the other measurements see section 3.4.
4. Drill two holes ø8 x 50 mm.
5. Fix the mounting rail. – Assembly sequence: plastic dowels 8 x 40, mounting rail, M6 washers, hexagon
head wood screws 6 x 50.
6. Attach the inverter to the mounting rail (A).
7. Fix the inverter on both sides with the Phillips head sheet metal screws 4.8 x 13 (B)
and (C):
(A)
(B)
(C)
en
79
5 Electrical connection
5.1 Opening the inverter
For the purpose of connecting the AC and communication lines, the inverter has to be opened.
5.1.1 Removing the cover
Once the cover is removed, the low voltage and communication terminals are accessible.
Procedure
1. Disconnect the AC power supply to the inverter.
2. Disconnect all control cables connected to the inverter (status relays, external grid monitoring and shut-down).
3. Switch off the DC disconnector at the inverter.
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage. After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.
Wait 5 minutes until the voltages inside the inverter have reduced before
removing the cover and carrying out connection work.
4. Loosen the two M5 screws at the bottom of the cover.
5. Remove the cover by gripping it at the bottom and pulling it away.
5 min
80
5.1.2 Removing the contact protection
When the contact protection has been removed, the internal connections - with dan­gerous voltage charges - are accessible.
Procedure
1. Press slightly on the two side snap closures and take the contact protection out of the holder.
2. Use a voltage tester to check that all connections at the inverter and, if applicable, at the I/O module, are de-energized.
en
81
5.2 Connection area
The connection area with the cover removed and without contact protection.
10
9 8
7
6
5
4
3
2
1
No. Description
1 DC connections 2 Left-hand cable pass-through (multiple cable gland for the communication cables) 3 Right-hand cable pass-through (AC connection) 4 Locking screw (the locking screw is replaced by the cable gland when the I/O module
is installed) 5 Connection option for 2nd protective conductor 6 Slot for the optional I/O module 7 AC connection 8 RS485 socket 9 Ethernet socket 10 DC bridges for single tracking (tted ex works)
82
5.3 Connecting the inverter to the mains
DANGER! Fatal electric shock hazard!
Make sure the AC line is not live during connection work.
Connection conditions
Comply with the connecting conditions set by the grid operator in charge. Connectable cable diameter: min. 9.5 mm / max. 12.5 mm Permissible conductor cross-sections:
– exible conductors (with or without ferrule) or rigid conductors: max. 16 mm
2
– exible conductors with ferrules (with plastic sleeves): max. 10 mm
2
The AC feed cable must be fused. Minimum conductor cross sections and suggested mains fuses:
SM2000P SM3000P SM4000P SM4600P SM5000P
Minimum conductor cross-section 1.5 mm
2
1.5 mm22.5 mm24 mm
2
4 mm
2
Mains fuses (characteristic C) 10A 16A 20A 25A 25A
Make sure the ambient temperatures for the mains fuses specied by the producer
are not exceeded.
WARNING! Risk of death by fire!
Provide separate fuses for each inverter. Do not attach any loads between inverter and fuse.
If you use an external leakage current circuit breaker (RCD switch), you must comply
with the following connection conditions:
– Use an A type RCD (residual current device) switch with a rated fault current of at
least 100 mA.
– In PV power plants with high leakage capacities, an RCD switch with a rated fault
current of at least 300 mA. must be used.
en
83
Procedure
1. Open the inverter as described in section 5.1.
2. Route the AC conductor through the right-hand cable gland to the AC connection terminals.
3. Remove an 18 mm length of conductor isolation (A).
4. Connect the wires in the following sequence:
– the protective conductor to the "PE" terminal – the neutral conductor to the "N" terminal – the live conductor (phase L) to the "L" terminal – press and close the levers (B) and (C) completely. If a lever is not completely closed,
the conductor connection is not secured.
(C)
(D)
(B)(A)
[mm]
NPEL
18
Abbildungen Klemme: Phoenix Contact
5. Check the cable connections for rm seating.
6. Tighten the cable gland (wrench size: 34 mm).
7. Check the cable strain relief.
8. Connect the second protective conductor (D).
– Assembly sequence: toothed lock washer M5, lug, washer M5, spring washer M5,
Phillips head screw M5 x 12
9. Close the inverter:
– insert the contact protection until it engages; – then tighten the cover.
84
5.4 Connecting the inverter to the PV generator
The inverters of the P series can be operated in single tracking or dual tracking mode, depending on the conguration of the PV plant. In the dual tracking mode a separate MPP tracker is available for each DC input (2 trackers). The ex works conguration of the P series inverters is for single tracking (1 tracker).
Connection conditions
Connection of maximum 2 conductors (1 conductor in the case of SM2000P /
SM3000P)
DANGER! Risk of death by fire!
High return currents can cause a re risk for the PV generator.
When Y plugs are used in order to connect more than 2 conductors (more
than 1 conductor in the case of SM2000P and SM3000P), each DC con­ductor must be protected individually against dangerous return currents.
Maximum DC input current: 10 A per DC input / 20 A when operating in single tracker
mode (only SM4000P SM4600P and SM5000P)
Maximum DC input voltage: 600 V Select the conductor cross-section to suit the system conguration. Exclusively use Wieland PST40i1C connectors (the mating connectors are not
included in the package supplied)
Do not t a ground connection to either the negative terminal or the positive terminal
of the PV generator.
Procedure
1. Make sure the DC disconnector and the external AC disconnector are off.
2. Connect the pre-tted DC conductors (A).
3. Use the locking clips (included in the delivery package) to secure the connectors against manual opening (B).
en
85
DC− DC+DC+ DC−
(A) (B)
Configure the inverter for dual tracking operation
If necessary, congure the inverter for dual tracking operation (only SM4000P, SM4600P and SM5000P).
4. Remove the cover as described in section 5.1.1.
5. Remove both DC bridges (see Section 5.2 / No.10) using a size 2 screwdriver.
6. Close the inverter by tting and tightening the cover.
Close off any unused DC connection points.
Any unused DC connection points must be closed off to ensure that the installation com­plies with the IP65 protection rating requirements. Please use the following closing parts made by Wieland (www.wieland-electric.com):
for plug components: order number 05.566.6380.0 for socket components: order number 05.566.6480.0
86
Increasing overvoltage protection
If you want to increase the overvoltage protection on the DC side using additional external surge arresters, the following connection conditions must be met:
Use a surge arrester with a response voltage of > 600 V. Connect the external surge arresters as follows:
> 600 V> 600
V>
600 V> 600 V
Install the connector cables close together to avoid overvoltages in the case of a
lightning strike.
Avoid ground loops in the wiring. Wire the earth connections in a star conguration with the neutral point close to the
inverter.
en
87
5.5 Grid connections
The inverter is tted with two RJ45 sockets as standard to provide an interface to an Ethernet or RS485 network.
Note
You will nd more details about data communications in the technical informa­tion “MaxComm network”. This document can be downloaded from our web­site at: www. solarmax.com; Downloads/Data communication/MaxComm.
Connection conditions
Use shielded RJ45 cable Connectable cable diameter: min. 5.5 mm / max. 7.0 mm
Procedure
1. Remove the cover of the inverter as described in section 5.1.1.
2. Thread the network cables through the multiple cable gland (see Section 5.2) to the network terminals.
Note
The RJ45 connectors can be pulled through the multiple cable gland.
3. Depending on the type of network, connect the cable either to the "Ethernet" or "RS485" connection.
4. Close off any unused holes in the multiple cable gland using the locking pins (see No. 8 in Section 4.2).
5. Tighten the multiple cable gland (wrench size: 34 mm).
6. After that, check the cable strain relief.
7. Close the inverter by installing and tightening the cover.
88
6 Commissioning
6.1 Activating the inverter
Procedure
1. Check that the cover is installed. – If the cover is not tted, close the inverter as follows: – insert the contact protection until you hear the two snap closures engage – then t the cover and tighten.
2. Switch on the DC disconnector at the inverter.
– The graphics display shows the "Overview". The status message "Start up..."
appears.
3. Switch on the AC power supply to the inverter. – Wait for the "Mains operation" status message to be displayed. This indicates that
the inverter is in mains operation.
– During initial start-up of the inverter, instead of the “Overview” menu, an “Initial
setup” menu appears (see Section 6.2).
6.2 Initial start-up
This section describes the initial start-up of the inverter and the graphics display set­tings required for this purpose. Once initial start-up has been successfully completed, the inverter will start feeding into the public network.
6.2.1 Requirements
The inverter has been installed and is fully connected. The contact protection and cover of the inverter are tted. There is sufcient solar irradiation (sufciently high DC input voltage). When operating the inverter in dual tracking mode (2 trackers) the DC bridges have to
be removed (see Section „Congure the inverter for dual tracking operation“; page
85).
en
89
Note
Entering an incorrect country setting may lead to problems regarding
inverter operation and to the withdrawal of the operating license by the respective grid operator.
Contact your grid operator or the SolarMax Service Center if you have any
doubt regarding the settings you must select.
You can restart initial start-up by pressing in the "Conrmation"
menu at any time.
6.2.2 Procedure
1. Switch on the inverter as described in section 6.1. The "Initial setup" menu will be displayed:
2. Select the display language from the "Language" menu.
3. If necessary, update the time and the date.
– The inverter saves the date entered as the initial start-up date. – The "DC input cong." menu will be displayed (only with the SM4000P, SM4600P
and SM5000P):
4. Select the required setting:
Setting Description
1 Tracker The inverter has been congured for single tracking mode operation.
The DC bridges have been tted in the inverter (default conguration ex works).
90
Setting Description
2 Tracker The inverter has been congured for dual tracking mode operation. The
DC bridges have been removed from the inverter.
5. Conrm that the DC bridges have been tted (for "1 Tracker" setting) or that the DC bridges have been removed (for "2 Tracker" setting).
Note
If you select the "2 Tracker" setting while the DC bridges are still in place
in the inverter, you must abort the start-up at this point.
Open the inverter as described in Section 5.1 in order to remove the DC
bridges as per Section 5.4.
You can then carry out the initial start-up.
– The "Country" menu will be displayed:
6. Select the correct country setting.
– Press
to conrm your entry.
– Depending on the country setting selected, additional menus may be displayed
(see Section 6.2.3).
– The "Conrmation" menu is then displayed.
7. Check the data in the "Conrmation" menu.
8. To complete initial start-up, press
. – The main menu will then be displayed (see section 7.4). – Should commissioning be taking place in Italy, the auto-test must be carried out
after the initial start-up (see Section 6.3).
6.2.3 Description of country-specic menus
Depending on the country setting, additional menus will be displayed during initial start­up. This section describes these menus.
en
91
Country setting "Germany"
Menu Setting Description
System power ≤ 3.68 kVA The maximum plant system rating is 3.68 kVA.
> 3.68 – 13.8kVA The plant system rating is higher than 3.68 kVA
and/or does not exceed 13.8 kVA.
> 13.8 kVA – 30 kVA The plant system rating is higher than 13.8 kVA
and/or does not exceed 30 kVA.
> 30 kVA The plant system rating is higher than 30 kVA.
An external grid monitoring and remote shut­down will be used.
I/O module
1)
Inactive The function for the external shutdown is
deactivated (EISD-ENA status: Disabled).
On The function for the external shutdown is
activated (EISD-ENA status: Enabled).
CosPhi(Pac) - QMCPP Inactive
The "cosφ(Pac)" function is deactivated (no reactive power feed-in, cosφ=1).
On
The "cosφ(Pac)" function for the feed-in / input of reactive power is activated.
1)
the menu is only displayed when the optional I/O module has been tted.
Country setting "Great Britain"
Menu Setting Description
System power ≤ 16 A per phase The output current is max. 16 A (inverter
settings in accordance with standard G83/2; available only for SM2000P, SM3000P and SM4000P.)
> 16 A per phase The output current is greater than 16 A (inverter
settings in accordance with standard G59/2; available only for SM4000P, SM4600P and SM5000P).
Country setting "Italy"
Menu Setting Description
System power ≤ 3 kW The maximum plant system rating is 3 kW.
> 3 kW – 6 kW The plant system rating is higher than 3 kW
and/or does not exceed 6 kW.
I/O module
1)
Inactive Remote control of the inverter via SPI logic is
deactivated (SPIL-ENA status: Disabled).
On Remote control of the inverter via SPI logic is
activated (SPIL-ENA status: Enabled).
1)
the menu is only displayed when the optional I/O module has been tted.
92
Country setting “Greece”
Menu Setting Description
Location Mainland The PV power plant is to be installed on the
Greek mainland.
Islands The PV power plant is to be installed on an
island in Greece.
6.3 Auto-test
The auto-test (only available in the "Italy" country setting) checks the grid monitoring of the inverter. The auto-test consists of 7 test steps in which the triggering behavior is checked in the case that the voltage and frequency limits are exceeded.
In the auto-test, the respective limit value is successively changed until it reaches the triggering threshold (i.e. the current reading). If the grid monitoring function is working, the inverter triggers the grid monitoring. For each step of the test, the graphics display shows the current reading, the trigger value, the trip time and the set limit. During the test of the frequency limits, the activation status of the limit value is also displayed.
The auto-test is performed automatically. Following completion of the auto-test, the inverter returns to normal operation. If an error occurs or irradiation is insufcient during the auto-test, the auto-test is aborted. In this case the message "Auto-test aborted" is shown on the display. The auto-test takes approximately 5 minutes.
Requirements
Sufcient solar irradiation The inverter has been connected to the mains and switched on for at least 10
minutes.
Procedure
1. In the main menu, select the "Auto Test" menu.
2. To start the auto-test, press
.
3. Wait for the display of the successful completion of the auto-test:
4. Ensure that the inverter resumes normal operation (in this case the status message "Mains operation" will be shown on the graphics display).
en
93
6.4 Settings
Different communication parameters and monitoring functions can be set in the "Set­tings" menu of the graphics display. All settings except the IP mode can also be made using the MaxTalk service software.
In the "Main menu" select the "Settings" menu. The settings can then be made as follows:
back to the main menu / select parameter (e.g. "Time")
Edit parameter
Conrm parameter / increase number / highlight next number
6.4.1 Setting the display language and system time
After initial start-up, set the display language and check the system time of the inverter.
In the "Settings" menu, select the following parameters and enter the desired values:
Parameter Description
Language Selection of the display language: German, English, French, Italian or
Spanish. The display language selection does not depend on the selected
country. Time System time of the inverter Date The date displayed by the inverter
94
6.4.2 Setting the network parameters
Device address
In order to communicate via RS485 or Ethernet interface the inverter needs a unique device address on the network.
1. In the "Settings" menu, select the "Device address" parameter.
2. Set the parameter to the required value:
Parameter Description
Device address Address range: 1…249
Configuring the Ethernet interface
In addition to the device address, the following settings must be made to communicate via Ethernet:
1. In the "Main menu" select the "Network" menu.
2. Select the necessary setting in the "IP-Mode" menu:
Setting Description
DHCP-Client The inverter is a DHCP client and is connected to a network with DHCP
server (factory setting).
Static The inverter is connected to a network with static IP addresses and has
to be congured in accordance with step 3.
3. If appropriate, congure the following parameters. These settings are only required in “Static” IP mode (see step 2):
Parameter Description
IP IP addres s (192.16 8.1.123)
Gateway (192.16 8.1.1) TCP Port (1234) DNS1 Domain Name Server 1 (192.168.1.1) DNS2 Domain Name Server 2 (192.168.1.1) Netmask Subnet mask (255.255.255.0)
(in brackets: factory settings)
4. Check whether the indicator for the Ethernet connection appears on the graphics display (see Section 7.1).
en
95
6.5 Displaying the conguration
All available operating parameters, standard-specic functions and their parameteriza­tion can be retrieved in the "Conguration" menu. Conguration of the standard-specic function depends on the country setting selected.
Note
MaxTalk 2 Pro allows authorized qualied technicians to adjust the operating parameters individually (see section 12).
In the main menu, select the "Conguration" menu.
back to main menu / select parameter or menu / conrm selection
The following parameters and menus are available:
Menu / parameter Description Country Country setting selected at the time of initial start-up. DC input cong. Conguration selected at initial start-up: 1 tracker (single
tracking) or 2 trackers (dual tracking, only available with SM4000P, SM4600P and SM5000P).
System power Plant rating selected at initial start-up (only available with "Ger-
many", "Italy" and "Great Britain" country settings). I/O module Status display of I/O module
Location Part of country selected at initial start-up (only available with
"Greece" country setting). SSF Menu of standard-specic functions and parameters
To display the menus of the standard-specic functions, select "SSF". The following menus are available:
Menu Description
External input Display of external control functions (external shutdown and
external output control). To use these functions, the optional I/O
module is required. Inverter start-up Those functions are displayed which are active before the
inverter is connected to the network (start conditions). Grid operation Those functions are displayed which are active during the
inverter's grid operation (grid monitoring).
96
Menu Description
Limitation Those functions are displayed which limit the inverter‘s output
values, such as active and reactive powers and AC output cur­rent (output limitation).
Reactive power Those functions are displayed that have an impact on the reac-
tive power taken up or given off by the inverter (reactive power control).
Reference parameters Display of nominal values and reference parameters.
External input
Function / arameter Description Unit / status EISD Monitoring the "external shutdown" input at the I/O
module.
-
EISD-ENA EISD function status Disabled/enabled EISD-SL "External shutdown" input logic High active /
low active
EPC Output control by radio ripple control receiver or
similar external control unit.
-
EPC-ENA EPC function status Disabled/enabled SPIL Remote control using SPI logic (only available with
"Italy" country setting)
-
SPIL-ENA SPIL function status Disabled/enabled SPIL-SESL Signal logic of input "Segnale Esterno" (Input "K6"
on I/O module)
High active /
low active SPIL-CL Logic state of "Comando Locale" 0/1 SPILFM1 SPI frequency monitoring mode 1 ­SPILFM1-ENA SPILFM1 function status Disabled/enabled SPILFM1-THRMIN Minimum permissible mains frequency, mode 1 Hz SPILFM1-DLYMIN Tripping time s SPILFM1-THRMAX Maximum permissible mains frequency, mode 1 Hz SPILFM1-DLYMAX Tripping time s SPILFM2 SPI frequency monitoring mode 2 ­SPILFM2-ENA SPILFM2 function status Disabled/enabled SPILFM2-THRMIN Minimum permissible mains frequency, mode 2 Hz SPILFM2-DLYMIN Tripping time s
SPILFM2-THRMAX Maximum permissible mains frequency, mode 2 Hz SPILFM2-DLYMAX Tripping time s SPILFM3 SPI frequency monitoring mode 3 ­SPILFM3-ENA SPILFM3 function status Disabled/enabled SPILFM3-THRMIN Minimum permissible mains frequency, mode 3 Hz SPILFM3-DLYMIN Tripping time s SPILFM3-THRMAX Maximum permissible mains frequency, mode 3 Hz
en
97
Function / arameter Description Unit / status
SPILFM3-DLYMAX Tripping time s
Inverter start-up
Function / parameter Description Unit / status PVGIT Checking the insulation resistance of the PV
generator to ground
-
PVGIT-ENA PVGIT function status Disabled/enabled PVGIT-THR Minimum permissible insulation resistance Ω RCMUT Checking the integrated fault current monitoring ­RCMUT-ENA RCMUT function status Disabled/enabled IST Checking the grid relay IST-ENA IST function status Disabled/enabled GPT Checking the grid parameters ­GPT-ENA GPT function status Disabled/enabled GPTVMIN-THR Minimum permissible mains voltage V GPT V MA X-THR Maximum permissible mains voltage V GPTFMIN-THR Minimum permissible mains frequency Hz GPTFMAX-THR Maximum permissible mains frequency Hz GPT-MOT Checking duration s
Grid operation
Function / parameter Description Unit / status GVMMIN1 Checking the minimum permissible mains voltage
(limit 1)
-
GVMMIN1-ENA GVMMIN1 function status Disabled/enabled GVMMIN1-THR Limit value V GVMMIN1-DLY Tripping time s GVMMAX1 Checking the maximum permissible mains voltage
(limit 1)
-
GVMMAX1-ENA GVMMAX1 function status Disabled/enabled GVMMA X1-THR Limit value V GV M M A X1-DLY Tripping time s GVMMIN2 Checking the minimum permissible mains voltage
(limit 2)
-
GVMMIN2-ENA GVMMIN2 function status Disabled/enabled GVMMIN2-THR Limit value V GVMMIN2-DLY Tripping time s GVMMAX2 Checking the maximum permissible mains voltage
(limit 2)
-
98
Function / parameter Description Unit / status
GVMMAX2-ENA GVMMA X2 function status Disabled/enabled GVMMA X2-THR Limit value V GV MMA X2-DLY Tripping time s GVM10AMA X Checking the maximum permissible average value
for mains voltage over the last 10 minutes
V
GVM10AMAX-ENA GVM10AMAX function status Disabled/enabled GVM10AMA X-THR Limit value V GV M10AMAX-DLY Tripping time s GFMMIN1 Checking the minimum permissible mains fre-
quency (limit 1)
-
GFMMIN1-ENA GFMMIN1 function status Disabled/enabled GFMMIN1-THR Limit value Hz GFMMIN1-DLY Tripping time s GFMMAX1 Checking the maximum permissible mains fre-
quency (limit 1)
-
GFMMAX1-ENA GFMMAX1 function status Disabled/enabled GFMMA X1-TH R Limit value Hz GF MM A X1-DLY Tripping time s GFMMIN2 Checking the minimum permissible mains fre-
quency (limit 2)
-
GFMMIN2-ENA GFMMIN2 function status Disabled/enabled GFMMIN2-THR Limit value Hz GFMMIN2-DLY Tripping time s GFMMAX2 Checking the maximum permissible mains fre-
quency (limit 2)
-
GFMMAX2-ENA GFMMAX2 function status Disabled/enabled GFMMA X2-THR Limit value Hz GFMMA X2-DLY Tripping time s AIS Detection of island operation ­AIS-ENA AiS function status Disabled/enabled AIS-DLY Tripping time s RSCD Detection of recurring short circuits on the AC side ­RSCD-ENA RSCD function status Disabled/enabled RBCM Monitoring the continuous leakage current ­RBCM-ENA RBCM function status Disabled/enabled RBCM-THR Maximum permissible leakage current A RSCM Monitoring the leakage current step value ­RSCM-ENA RSCM function status Disabled/enabled AOT Auto-test (only available with the "Italy" country
setting)
-
AOT-EN A AOT function status Disabled/enabled
en
99
Function / parameter Description Unit / status DCCIM Monitoring the DC component in the AC current -
DCCIM-ENA DCCIM function status Disabled/enabled DCCIM-THR Maximum permissible DC component in AC current A DCCIM-DLY Tripping time s
Limitation
Function / parameter Description Unit / status ACPPL Maximum increase of the active power during grid
connection
-
ACPPL-ENA ACPPL function status Disabled/enabled ACPPL-MGDT Increase % of Pac nom/
min ACPPL-INI ACPPL at every boot Disabled/enabled ACPPL-RCN ACPPL at boot after grid disconnection through
coupler breaker
Disabled/enabled
ACPL Limit of active output power ­AC PL- L MT Limit value W APPL Limit of the apparent power ­APPL-LMT Limit value VA OCL Limit of the output current ­OC L-L M T Limit value A PFLM2 P(f) mode 2 ­PFLM2-STRTFQ Start frequency Hz PFLM2-RDN Reduction of active power
% of P
M
/Hz
PFLM2-RNC Increase to rated output power % of Pac nom/
min PFLM3 P(f) mode 3 ­PFLM3-STRTFQ Start frequency Hz PFLM3-STOPFQ Stop frequency Hz PFLM3-RDN Reduction of active power
% of P
M
/Hz
PFLM3-RNC Increase to rated output power % of Pac nom/
min PFLM3-UFQTHR Maximum permissible mains frequency Hz PFLM3-LFQTHR Minimum permissible mains frequency Hz PFLM3-UVTHR Maximum permissible mains voltage V PFLM3-LVTHR Minimum permissible mains voltage V PFLM3-MOT Checking duration s
100
Reactive power
Function / parameter Description Unit / status QMO-AM Reactive power control 0=OFF QMCQ Reactive power mode constant "Q" -
QMCQ-QSV Reactive power value % of Pac nom
[OEX/UEX]
QMCQ-VLE Status of the voltage-dependent reactive power
control hysteresis for QMCQ
Disabled/enabled
QMCQ-VLIH Upper limit value of the mains voltage V QMCQ-VLOL Lower limit value of the mains voltage V QMCQ-PLE Status of the active power-dependent reactive
power control hysteresis for QMCQ
Disabled/enabled
QMCQ-PLI Upper limit value of the active power W QMCQ-PLO Lower limit value of the active power W
QMCPP
Reactive power mode "cosφ(Pac)"
­QMCPP-PSP1…PSP10 Characteristic values 1 to 10 of Pac active power % of Pac nom QMCPP-CPSP1…
CP SP10
Characteristic values 1 to 10 of power factor cosφ
- [UEX/OEX]
QMCPP-VLE Status of mains voltage-dependent reactive power
control hysteresis for QMCPP
Disabled/enabled
QMCPP-VLIH Upper limit value of the mains voltage V QMCPP-VLOL Lower limit value of the mains voltage V
QMCCP
Reactive power mode "cosφ"
­QMCCP-CPSV
cosφ value
- [UEX/OEX] QMCCP-VLE Status of mains voltage-dependent reactive power
control hysteresis for QMCCP
Disabled/enabled
QMCCP-VLIH Upper limit value of the mains voltage V QMCCP-VLOL Lower limit value of the mains voltage V QMCCP-PLE Status of active power-dependent reactive power
control hysteresis for QMCCP
-
QMCCP-PLI Upper limit value of the active power W QMCCP-PLO Lower limit value of the active power W
Reference parameters
Function / parameter Description Unit NAP Rated output power (Pac nom) -
NAP-VAL Value W NOC Rated output current ­NOC-VAL Value A GCD Switching delay of the coupler breaker ­GCD-CDLY Tripping time s
en
101
6.6 Displaying the measured values
The current measured inverter values can be accessed in the “Measured values” menu.
In the main menu, select the "Measured values" menu.
back to the main menu / scrolling measured values
Measured value Description Unit
Vdc 1, Vdc 2
Input voltage at DC terminal 1 and DC terminal 2 (when oper­ating in single tracker mode, the DC terminal 2 = 0)
V
Idc1, Idc2
Input current to the DC terminal 1 and DC terminal 2 (when operating in single tracker mode, the Idc2 terminal = 0)
A
Vac
Mains voltage V
Iac
Output current A
Pac
Output power W
Q
Reactive power (+: overexcited / −: underexcited) var
cosφ
Power factor (OEX: overexcited / UEX: underexcited) -
Frequency
Mains frequency Hz
Temperatur e
Equipment temperature °C
Note
The measured inverter values are not suitable for billing purposes or calcula­ting the efciency. The measuring error may amount to up to ±5% depending on the measured value. Only the measured values of a calibrated electricity meter can be relied upon for billing purposes.
MaxTalk measured values
The following additional values can be viewed with the MaxTalk 2 service software:
Measured value Description Unit
Vac 10 min 10 minute average value of the mains voltage V Iac mean Mean value of output current A Ierr Ground leakage current mA Ierr DC Leakage current mA
102
6.7 Registering for MaxView
Register for the free web-based MaxView application. With MaxView it is possible to view and graphically display the yield data of your PV power plant from anywhere.
Note
Frequently asked questions about MaxView and the replies to these can be found on our website at https://maxview.solarmax.com/faq.xhtml.
Procedure
1. Connect the inverter to the Internet via the Ethernet interface (see Sections 5.5 and
6.4.2).
2. Enter your registration data in a web browser under https://maxview.solarmax.com.
3. Learn about the various functions of MaxView.
6.8 Update rmware
The inverter rmware can be updated with the help of the MaxTalk 2 service software. For further information, please refer to the MaxTalk 2 operating manual, which you can download from our website (www.solarmax.com; Downloads/Software/MaxTalk 2).
en
103
7 Operation
7.1 Graphics display
The graphics display shows the system values, status information, and the inverter’s fault messages. The graphics display can be used for obtaining information on the current operating status, accessing the integrated data logger and entering various settings on the inverter.
1
3
4
2
5
No. Description
1 Graphics display with backlighting 2 Status LED: operating status display (see section 7.7) 3 Function keys (membrane keypad) 4 Display with Ethernet connection (link display) 5 Display when data transfer takes place (communication).
The function keys can be used for navigating within the menu structure:
Symbol Description
Select menu or parameter
Edit parameter
Highlight number (parameter editing) Increase highlighted number / select menu or parameter
Confirm
Cancel
104
7.2 Menu structure
Main menu
Overview
Statistics
Conguration
Auto-test**
Information
Measured values
* only if I/O module is installed
** only for country setting “Italy”
Time
Language
Date
Device adress
Days
Months
Years
Total
Reset
Network
IP
IP-Mode
Netmask
Gateway
TCP Port
DNS1
DNS2
Status relay*
Status relay delay*
SPD Monitor*
SSF
Settings
Grid operation
External input
Inverter start-up
Limitation
Reactive power
Reference parameter
en
105
7.3 Overview
The overview shows the most important operating data of the inverter. The graphics display automatically switches to the "Overview" if no function button is pressed for 120 seconds.
In the main menu, select the "Overview" menu.
Display Description
Date and system time ­Pac Current output power [W] Today Daily yield [kWh] Tot al Total yield since commissioning [kWh] Status
Current operating status (see section
7.7 )
7.4 Main menu
From the "Main menu", you can open all menus.
In order to switch from "Overview" to the "Main menu", press any function key.
: select menu / conrm your selection
106
7.5 Statistics
The "Statistics" menu can be used for accessing the inverter's data logger. The data logger saves the statistics values of the past 25 years. The daily, monthly, yearly and total statistics can be displayed. All statistics values can be deleted.
7.5 .1 Displaying the daily statistics
The daily statistics displays the statistics values for the last 31 days.
In the "Statistics" menu, select the "Day" sub-menu.
Select day / back to the Statistics menu
Statistics value Description
Yield Daily yield [kWh] Maximum Fed-in maximum power [W]
Hours
Number of operating hours in the "Mains operation" operating status
7.5 .2 Displaying the monthly statistics
The monthly statistics displays the statistics values for the last 12 months.
In the "Statistics" menu, select the "Month" sub-menu.
Select month / back to the Statistics menu
Statistics value Description
Yield Monthly yield [kWh]
en
107
Statistics value Description
Maximum Fed-in maximum power [W] Hours Number of operating hours in the "Mains operation" operating
status
7.5 .3 Displaying the annual statistics
The annual statistics displays the statistics values for the last 25 years.
In the "Statistics" menu, select the "Year" sub-menu.
: select year / back to the Statistics menu
Statistics value Description
Yield Annual yield [kWh] Maximum Fed-in maximum power [W]
Hours
Number of operating hours in the "Mains operation" operating status
7.5 .4 Displaying the total statistics
The total statistics shows the statistics values since commissioning.
In the "Statistics" menu, select the "Total" sub-menu.
back to the Statistics menu
108
Statistics value Description
Yield Total yield [kWh] Hours Total operating hours in the operating status "Mains operation"
7.5.5 Deleting the statistics values
The statistics values of the data logger can be deleted.
In the "Statistics" menu, select the "Reset" sub-menu.
Note
The deletion process cannot be undone!
Cancel / Conrm deletion
7.6 Displaying information
This menu displays information about the inverter. The menu can be used to identify the inverter.
In the main menu, select the "Information" menu.
back to the main menu / scroll display
Display Description
Device type Inverter type Serial No. Inverter serial number Firmware Firmware version installed in the inverter
en
109
Display Description
Status Current operating status Warning Current warning message Commissioning Date of initial start-up Operating hours Total operating hours in mains operation Mac address Mac address of the inverter
7.7 Operating status
The status message displayed on the graphics display describes the current operating status of the inverter. Each status message relates to one of ve possible operating sta­tuses. The status LED has different colors with which to indicate one of these operating statuses.
In addition to the status messages, the inverter also displays warnings. Warnings result from device errors or external malfunctions. The inverter continues to feed power into the mains, but it is possible that yield is reduced. Warnings are independent of the oper­ating status and are displayed on the graphics display alternately with the current status message.
Status LED Operating status Description
Off
- Inverter is switched off
Flashes green
Booting Inverter is starting up
Green
Mains operation Mains feed-in (normal operation)
Flashes orange
-
Warning no grid disconnection
Orange
Fault
External fault grid disconnection
Red
Error
Device error grid disconnection
Flashes red
Blocked
Inverter is blocked grid disconnection
The "Fault", "Error", and "Blocked" operating status messages, as well as the warnings, usually require certain measures to be carried out by the qualied electrician in charge (see section 8).
110
7.7.1 Booting
Status LED: ashes green
Status message Description
Irradiation too low The solar irradiation or rather the available output is too low for
mains operation.
Startup… The inverter checks the internal hardware and software compo-
nents before connecting to the mains.
Restart delay The inverter delays connection to the grid (after a disconnection
from the grid or when starting up).
7.7.2 Mains operation
The status LED lights up green.
Status message Description
Maximum power The inverter limits the in-feed power to the maximum permissible
value. This may occur if the PV generator is oversized. Mains operation The inverter is in feed mode. Idc limitation The inverter limits the PV generator current to the maximum
permissible value. This may occur if the PV generator is designed
such that the current at Maximum Power Point (MPP) exceeds the
maximum permissible input current of the inverter. Iac limitation The inverter limits the output current to the maximum admissible value
(where the PV generator is oversized). Restart limitation Following an external output limitation the inverter increases the
active power with a dened progression (Pac progression and/or
Soft Start). Frequency limitation The inverter temporarily limits the active power owing to an active
frequency-dependent power reduction. External limitation The inverter's fed-in active power is limited by external output
control.
Temperature limitation The output power is temporarily reduced in order to limit the
inverter‘s temperature.
en
111
8 Troubleshooting
8.1 SolarMax Service Center
If you have technical questions or difculties, our Service Center will be happy to help you. To do that we need the following information:
Device type Serial number (S/N) Installation location Information about the failure you are experiencing (status message, etc.)
Contacting the SolarMax Service Center
The contact details of the SolarMax Service Center can be found on the back of this instruction manual.
Sputnik Engineering AG Länggasse 85 CH-2504 Biel/Bienne
8.2 Diagnosis & measures
The following tables describe possible actions for remedying faults. If the actions sug­gested do not correct the fault, please contact the SolarMax Service Center.
8.2.1 General troubleshooting
Problem Cause Actions
The graphics display remains blank
The DC disconnector is switched off.
Switch on the DC disconnector.
The irradiation is too low. Wait until irradiation is high
enough.
The strings are interrupted. Check the PV generator and
eliminate the interruption.
It is possible that the inverter is defective.
Contact the SolarMax Service Center.
The graphics display only ashes briey.
The irradiation is too low. Wait until irradiation is high
enough.
112
8.2.2 Warnings
The status LED ashes orange.
Warning Cause Actions
Temperature limitation The output power is temporarily
reduced in order to limit the
inverter‘s temperature.
Ensure that the recommended maximum ambient temperature is not exceeded; that the cooling ns are free from dust and dirt.
Fan failure A fan is defective or soiled. Contact the SolarMax Service
Center.
RTC error Date and time in the RTC (real-
time clock) were reset due to a
malfunction.
Set the date and time (see section 6.4.1). If this problem occurs frequently, contact the SolarMax Service Center.
Firmware mismatch The rmware versions of the
inverter controllers do not match.
Contact the SolarMax Service Center.
Flash error An error has occurred in the ash
memory.
Contact the SolarMax Service Center.
SPD failure An active signal is present at
the "SPD Monitor" input of the
I/O module (monitoring lightning
protection).
Check the external lightning protection module (or the device connected to the "SPD Monitor" input).
8.2.3 Faults
The status LED lights up orange.
Note
MaxTalk can be used to read out the last error messages.
Status message Cause Actions
Vdc too high The DC input voltage of the
inverter is too high.
Switch off the DC discon­nector. Check the PV genera­tor’s conguration.
Ierr too high The ground leakage current has
exceeded the permissible RBCM-
THR limit value.
Check the PV generator.
Ierr step too high The leakage current has exceeded
the admissible RSCM step value.
No mains There is no mains voltage. Check the AC conductor
(fuses).
en
113
Status message Cause Actions
Frequency too high The mains frequency is outside
the GFMMAX1-THR, GFMMAX2­THR or GPTFMAX-THR limit values.
If this problem recurs, contact the grid operator in charge.
Frequency too low The mains frequency is outside
the GFMMIN1-THR, GFMMIN2­THR or GPTFMIN-THR limit values.
Mains error The inverter detects island mode. If this problem recurs, contact
the grid operator in charge.
Vac too high The mains voltage is outside the
GVMMA X1-THR, GV M M AX 2-TH R or GPTVMAX-THR limit values.
If this problem recurs, contact the grid operator in charge.
Vac too low The mains voltage is outside the
GVMMIN1-THR, GVMMIN2-THR or GPTVMIN-THR limit values.
Vac 10 min too high The maximum 10-minute average
value of the mains voltage GVM10AMAX-THR is too high.
Insulation fault DC The insulation resistance of the PV
generator to ground is too low.
Check the PV generator.
Phase and neutral conductor are interchanged.
Connect the AC supply conductors as described in section 5.3.
Error ext. input 1 The external grid monitoring (NA
protection / Teledistacco) has disconnected the inverter from the grid. An active signal is present at the "NA" input (external shutdown) of the I/O module.
If this problem recurs, contact the grid operator in charge.
8.2.4 Error
The status LED lights up red.
Status message Cause Actions
Device error (+ error code) The inverter is defective. Note the displayed two-digit
error code and contact the SolarMax Service Center.
114
8.2.5 Blockings
The status LED will ash red.
Status message Cause Action
Programar rmware The inverter's rmware is being
updated.
None. The inverter automati­cally resumes mains operation once the rmware update is complete.
9 Maintenance
The following maintenance work should be carried out when required:
Regularly check the operating status of the inverter on the graphics display, see sec-
ti on 7.7.
Clean the graphics display with a damp cloth. Do not use harsh or abrasive cleansing
agents.
Check the inverter for external damage. If any damage is found, inform the respective
qualied electrician.
en
115
10 Decommissioning
10.1 Instructions for inverter replacement
When replacing the inverter, note the following:
Before replacing the inverter, write down the total yield. The procedure for viewing
the total yield is described in Section 7.5.4.
If an I/O module was used in the existing inverter, this can be re-used in the replace-
ment inverter.
10.2 Inverter disassembly
DANGER! Fatal electric shock hazard!
Components within the inverter are charged with a high voltage. After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.
Before starting inverter disassembly, the inverter must be fully discon-
nected in accordance with the procedure described in this chapter.
WARNING! Risk of injury from electric arc!
Dangerous electric arcs could occur when removing live DC conductors.
Switch off the inverter DC disconnector before removing the DC
conductors.
ATTENTION! Electrostatic discharge can damage the inverter
Do not touch any electronic components inside the inverter.
116
Procedure
1. Switch off the external AC disconnector. – The "No grid" status message is shown on the inverter.
2. Switch off the DC disconnector at the inverter.
3. Use a size 2 screwdriver to remove the locking clips on the DC plugs.
4. Pull out the DC conductors to fully separate the inverter from the PV generator.
5. Loosen the two M5 screws on the cover.
6. Open the inverter as described in Section 5.1.
7. Use a suitable charge indicator to check that all terminals are free from voltage. – When all terminals are de-energized, you can remove the AC supply conductor, the
second protective conductor and all communication lines from the inverter.
CAUTION! Risk of burns due to hot casing components!
Wait until the back of the casing has cooled down.
8. Close the inverter: – insert the contact protection until it engages; – then tighten the cover.
9. Remove the 2 Phillips head sheet metal screws (4.8 x 13) on the side which secure
the inverter on the mounting rail.
10. Disengage the inverter from the mounting rail.
11. Remove the I/O module if there is one.
10.3 Disposing of the inverter
Dispose of the inverter as indicated by the local waste disposal regulations. You can also return the inverter, at your own cost, to Sputnik Engineering AG for professional disposal. The contact details of the SolarMax Service Center can be found on the back of this instruction manual.
en
117
11 Technical data
SM2000P SM3000P SM4000P SM4600P SM5000P
Input values
MPP voltage range
1)
210…480 V 310…480 V 190…480 V 240…480 V 260…480 V
Minimum DC voltage
120 V 120 V 120 V 120 V 120 V
Maximum DC voltage
600 V 600 V 600 V 600 V 600 V
Maximum DC current
10 A 10 A 10 + 10 A 10 + 10 A 10 + 10 A
Number of MPP trackers
1 1 2 2 2
Number of string connections
1 1 2 2 2
Connection type Wieland PST40i1 (identical to MC4)
Overvoltage category
II
Output values
Rated output power 2,000 W 3,000 W 4,000 W 4,600 W 5,000 W
Maximum apparent output power
2,000 VA 3,000 VA 4,000 VA 4,600 Va 5,000 VA
Maximum AC current
9 A 13.5 A 17. 5 A 22A 22A
Nominal mains voltage / range
230 / 184 … 276 V
Mains nominal frequency / range
50 / 45…55 Hz
Power factor cosφ
Adjustable from 0.8 overexcited to 0.8 underexcited
Distortion factor at rated output power
< 1.5 %
Connection type Terminal 2.5 - 10 mm
2
Grid connection Single phase (L / N / PE)
Overvoltage category
III
Efciency Max. efciency 97. 5 % 9 7. 5 % 98 % 98 % 98 %
Europ. Efciency 97 % 97 % 97.5 % 9 7. 5 % 9 7. 5 %
Power input
Own consumption night
0 W
Environ­ment
Protection rating IP 65
Ambient tempera­ture range (for rated power output)
−20 to +60 °C (−20 to +45 °C)
Max. operating level above sea level
2000 m
Relative humidity
0 100 % (condensation)
Fire protection class V0
118
SM2000P SM3000P SM4000P SM4600P SM5000P
Environ­ment
Environmental category
In the open
Suitable for wet rooms
Yes
Degree of soiling 3
Congura­tion
Display Graphics display with backlighting and status LED
Inverter topology HERIC
®
, transformerless
DC disconnector Integrated
Data logger Energy yields, peak output and operating duration of the last 31 days, 12
months, 10 years / output curves of the last 7 days
Fault current monitoring
Internal, AC/DC sensitive
Casing / cover Aluminum / plastic ASA+PC
Overvoltage con­ductor, DC and AC
Requirement class D (VDE 0675-6) and/or type 3 (EN 61643-11)
Stan­dards & guidelines
CE-compliant
Yes
2)
EMC EN 61000-3-2 / EN 61000-3-3 / EN 61000-3-11 / EN 61000-3-12 / EN
61000-6-2 / EN 61000-6-3
Grid connection
VDE 0126-1-1 / VDE-AR-N 4105
3)
/ CEI 0-21 4) / RD 661 / RD 1699 /
G83/2 / G59/2 / PPC Guide / C10/11 / EN 50438
5)
Device safety IEC/ EN 62109-1/ -2
Interfaces Data
communication
RS 485 / Ethernet
Status signaling contact
Optional
Connection to radio ripple control signal receiver
Optional
Connection to external lightning protection
Optional
Connection to external grid monitoring
Optional
Weight & dimensions
Weight 17 kg 17 kg 19 kg 19 kg 19 kg
Dimensions (W x H x D)
476 x 360 x 180 mm
Warranty Standard 5 years / extension to 10, 15, 20 or 25 years possible
1) for rated output power
2) the complete conformity declaration can be found on our website at www.solarmax.com.
3) not for SM5000P
4) for installations ≤ 6 kW
5) Portugal and Czech Republic
en
119
Efficiency curve SM5000P
100.0
97.5
95.0
92.5
90.0
87.5 0 5 102 15 20 25 30 40 50 7060 80 75 90 100
η 260 V
DC
η 400 V
DC
η 480 V
DC
Standardised output Pac/Pac max [%]
Efciency η [%]
Pac/Pac max [%] η 260 V
DC
[%] η 400 V
DC
[%] η 480 V
DC
[%]
5 92.21 92.32 91.79 10 95.38 96.04 95.57 20 96.66 97. 5 2 97.2 2 30 96.89 97. 83 97.6 3 50 96.92 97. 88 97.78 100 96.30 97.4 3 97.4 0
Europ. Efciency η
EU
[%]
96.52 97.4 6 97. 30
120
Efficiency curve SM4600P
100.0
97.5
95.0
92.5
90.0
87.5 0 5 102 15 20 25 30 40 50 7060 80 75 90 100
η 260 V
DC
η 400 V
DC
η 480 V
DC
Standardised output Pac/Pac max [%]
Efciency η [%]
Pac/Pac max [%] η 260 V
DC
[%] η 400 V
DC
[%] η 480 V
DC
[%]
5 92.01 92.12 91.58 10 94.92 95.52 95.03 20 96.51 97. 3 8 97.0 3 30 96.88 97. 7 7 97.57 50 96.91 97. 89 97.77 100 96.45 97. 52 9 7.4 8
Europ. Efciency η
EU
[%]
96.50 97.42 97.2 5
en
121
Efficiency curve SM4000P
100.0
97.5
95.0
92.5
90.0
87.5 0 5 102 15 20 25 30 40 50 7060 80 75 90 100
η 260 V
DC
η 400 V
DC
η 480 V
DC
Standardised output Pac/Pac max [%]
Efciency η [%]
Pac/Pac max [%] η 260 V
DC
[%] η 400 V
DC
[%] η 480 V
DC
[%]
5 92.01 92.12 91.58 10 94.92 95.52 95.03 20 96.51 97. 3 8 97.0 3 30 96.88 97. 7 7 97.57 50 96.91 97. 89 97.77 100 96.45 97. 52 9 7.4 8
Europ. Efciency η
EU
[%]
96.50 97.42 97.2 5
122
Temperature dependent output reduction
The inverter can feed 100 % of its rated output for an unlimited time up to an ambient temperature of 45 °C. When operating in ambient temperatures in excess of 45 °C it is possible that the yield is reduced. For this reason excessive ambient temperature should be avoided. In the specied ambient temperature range the power output of the SM2000P will be consistent.
110
100
90
80
70
60
−20 −10 0 10 20 30 40 45 50 60
SM5000P
SM4600P
SM4000P
SM3000P
SM2000P
Output Pac/Pac nom [%]
Ambient temperature [°C]
Country-specific settings
The factory's default settings for different countries can be viewed in the technical infor­mation "SSF - Standard specic functions and parameters - Factory settings". This docu­ment can be downloaded from our website at: www.solarmax.com; Downloads/String inverters/P series/Manuals.
en
123
12 Accessories and options
Accessory/option Description
I/O module Communication module with the following congurable interfaces:
status signaling contact for remote monitoring of the inverter, inter­faces for remote control (external shutdown, external output control) and for lightning monitoring
MaxView Free web-based application with various functions for remote call-up,
graphic visualization and export of yield data.
Ma xTalk Free communication and service software for local monitoring of the
PV plant.
MaxTalk Pro Professional version of MaxTalk for the conguration of inverters. The
required "SolarMax P series parameter conguration using MaxTalk 2 Pro" operating manual can be downloaded from our website; www. solarmax.com ("Downloads" area).
MaxMonitoring Using the free MaxMonitoring software, you can display the per-
formance data of your photovoltaic system at any time from home. MaxMonitoring is available for PC, MacOS and Linux and also as an app for Android and iOS.
MaxDesign Free software for determining the size of PV plants.
You can nd further information on our website at www.solarmax.com.
124
13 Warranty
Sputnik Engineering AG (hereafter SPUTNIK) guarantees full function and lack of defects of its technical devices for a warranty period as specified below for each type of device. Such warranty period can be extended by means of a warranty extension, subject to the conditions named below.
This manufacturer’s warranty exists next to the seller’s warranty (if any) as prescribed by law. As far as identical with regards to the content, the rights under this manufacturer’s warranty supersede any rights under the seller’s warranty. Please contact the seller with regard to any claims based on the seller’s warranty.
1. Warranty Period (Basic)
Central inverters and accessories: 24 months from the date of purchase, but at maximum 30
months after dispatch of the device by SPUTNIK.
String inverters: 60 months from the date of purchase, but at maximum 72 months after dis-
patch of the device by SPUTNIK.
If in individual cases SPUTNIK has agreed in writing to a different warranty period, such arrange­ment supersedes the above provisions.
2. Scope of Manufacturer’s Warranty
In case of defect or malfunction of a device within the manufacturer’s warranty period, and upon fulfillment of the conditions for warranty claims named hereafter, the device will be repaired or replaced by SPUTNIK-service personnel within a reasonable time, in either case free of charge, unless this is impossible or disproportionate. SPUTNIK may decide at its own discretion whether a device will be repaired or replaced.
Replacement: Exchange of device free of charge. SPUTNIK’s separate conditions for exchange
of devices apply: This warranty covers the free delivery of an equivalent replacement device. Further, your installer is entitled to claim a flat rate compensation for the replacement work from SPUTNIK. Please do not hesitate to ask us about the current amount of such flat rate compensation.
Repair: Repair of device free of charge. This warranty covers costs for material, work and travel
by SPUTNIK personnel or by personnel authorized by SPUTNIK.
Please be aware that the performances of SPUTNIK under this warranty are only free of charge in countries approved by SPUTNIK. Please contact your seller for details. A current list of approved countries can be found on our homepage. Repair and replacement outside of the approved countries are only possible after prior consultation of and approval by SPUTNIK. In such case, travel and ship­ment costs are borne by the customer.
Any further claims, especially claims for compensation of damages resulting directly or indirectly from the defect or claims for replacement of further costs in connection with the installation and removal of devices or claims for loss of profits are not covered by this warranty.
en
125
3. Extent of Repair and Replacement
SPUTNIK will maintain repair material and stock of each type of device during the warranty period only at its own reasonable discretion. In case repair materials for a certain type of inverter and/or an identical replacement device are not in stock anymore, the following applies:
SPUTNIK is allowed to replace the defective inverter with a comparable device of the same or
superior performance. The costs (time and material) for technical adjustments necessary for the installation of such comparable devices are covered by this warranty only up to a limited amount; any flat rate compensation owed by SPUTNIK for the replacement is deductible. Please do not hesitate to ask us about the currently applicable amount. The exchange and connection of peripheral devices due to possible non-compatibility with the replacement device or other necessary adjustments to the surrounding installations of the device (including power lines, ventilation and safety installations) are not covered by this warranty. However, SPUTNIK shall within the bounds of reasonability do its best to minimize the effort of such adaptation work.
In case repair materials are not available with reasonable efforts anymore, SPUTNIK is allowed
to replace the inverter, subject to the conditions mentioned in the paragraph above.
4. Warranty Period in Case of Repair/Replacement
In case of repair or replacement of devices under this warranty, the repaired respectively replaced device will inherit the remaining warranty time of the original device.
5. Exclusion of Warranty
Especially in the following cases, this manufacturer’s warranty does not apply:
Transport damage;
Technical intrusions, modifications or repairs of the devices not authorized by SPUTNIK;
Use of devices for purposes they are not intended for, incorrect or unreasonable manipulation,
incorrect or unreasonable installation;
Failure to observe the manufacturer’s operating, installation and maintenance directions;
Inadequate environmental conditions (e.g. insufficient ventilation of the device; humidity etc.);
Superior force (e.g. lightning strike, overvoltage, floods, fire, etc.).
6. Handling of Warranty Cases
For the processing of warranty cases, use of SPTUNIK’s hotline is mandatory. The handling of war­ranty cases must take place in accordance with the instructions provided by the hotline. The hotline number for your country can be found on SPUTNIK’s homepage. Please hold the serial number, article description, a short description of the defect and the purchase receipt ready for transmission to the hotline.
Any repair action taken by the buyer or third parties without authorization by SPUTNIK will not be compensated.
In case these terms on the handling of warranty cases are not respected, SPUTNIK may refuse its warranty performances.
126
7. Suspension of Warranty
Sputnik reserves its right to suspend this manufacturer’s warranty temporarily or definitely in case a specific installation does not allow a correct functioning of the inverters (e.g. in case of one of the circumstances listed in cipher 5).
The suspension of the warranty can be lifted upon approval by SPUTNIK. Such approval must be issued by SPUTNIK in writing, confirming that the warranty has again become effective.
8. Warranty Extension
The warranty period can be extended through purchase of a warranty extension within the time limits mentioned hereafter. For certain types of devices, such warranty extensions can also be purchased only for a limited scope of warranty performances. The purchase of a warranty extension will be confirmed by SPUTNIK in form of a warranty certificate (including serial number of affected product). In case of replacement of a device, the serial number in such warranty certificate remains unchanged, without any influence on the validity of the warranty extension.
a) Time limits String inverters: The extension of the basic warranty can be ordered within 60 months after pur­chase, but the latest within 72 months after dispatch of the device by SPUTNIK. Central Inverters: The extension of the basic warranty can be ordered within 3 months after pur­chase, but the latest within 12 months after dispatch by SPUTNIK.
b) Extent Full warranty extension – FULL (available for central inverters and string inverters): A full warranty extension includes all the warranty performances as described in the manufacturer’s basic war­ranty terms.
Limited warranty extension– LIMITED (available only for central inverters): A limited warranty extension covers only the costs for the material required for the repair. The costs for travelling, labor and other expenses are not covered and will be invoiced on a time and expenses basis by SPUTNIK.
c) Effectiveness of Warranty Extension It is a mandatory requirement for the warranty extension to provide the completely filled out applica­tion form to SPUTNIK. The warranty extension becomes effective only after written confirmation and provision of the warranty certificate by SPUTNIK.
9. After Expiration of Warranty Period
The costs for repair or replacement of devices after expiration of the warranty period are invoiced by SPUTNIK on a time and material basis. SPUTNIK will maintain repair and replacement capabilities beyond the warranty time only at its own discretion.
10. Applicable Law, Jurisdiction
Only Swiss Law applies. The exclusive place of jurisdiction lies in Biel/Bienne, Switzerland. (v 2013/05)
en
127
Notes
2013/08
SolarMax Service Center
hotline@solarmax.com
www.solarmax.com/service
Loading...