10 Connector Assignments and Wiring .................................................................. 30
10.1 Notes on wiring the connections ........................................................................................................................ 30
3
10.2 RS485-A (only Solar-Log 1000, 1200 and 2000) ........................................................................................ 31
10.3 RS485/422 - B ............................................................................................................................................................ 32
10.4 RS485/422 - C (only Solar-Log 2000) ............................................................................................................. 33
10.5.1 S0 OUT / IN A (S0-OUT and S0-IN A) .............................................................................................................. 34
10.5.2 S0-IN B ..........................................................................................................................................................................35
12.1 Sensor Box Basic and Professional .................................................................................................................... 39
12.2 Sensor Box Professional Plus................................................................................................................................. 41
12.3 Ripple Control Receiver .......................................................................................................................................... 44
12.4 Large External Displays .......................................................................................................................................... 45
12.5 External power meter .............................................................................................................................................. 47
12.5.1 External power meters/accumulating meters .................................................................................................48
12.6 Wiring for S0 meter ................................................................................................................................................. 49
12.7 Wiring for RS485 meter .......................................................................................................................................... 51
12.8 Installation Utility Meter / Janitza UMG 104 / UMG 604 (only Solar-Log 1000 and 2000) ........ 54
12.11 Allnet Network Power Socket .............................................................................................................................. 61
12.11.1 Connecting the Allnet network power socket to the Solar-Log™ .......................................................... 62
13 Other connections .....................................................................................................63
13.1 Alarm contact (only Solar-Log 1000 and 2000) .......................................................................................... 63
13.2 Relay (only Solar-Log 1000, 1200 and 2000) ................................................................................................ 64
13.3 USB ................................................................................................................................................................................. 65
14.1 Connecting the Solar-Log™ to a network / PC .............................................................................................. 66
14.1.1 Instructions for connection through the PowerLine package .................................................................. 67
14.2 Initial installation Solar-Log 250 and 300 ....................................................................................................... 67
14.3 Initial set up of the Solar-Log 1200 .................................................................................................................... 68
14.4 Setting up of the Solar-Log™ with the configuration wizard .................................................................. 68
14.4.1 Carrying out the initial set up of the Solar-Log 250, 300, 1200 and 2000 (manually). ................. 75
14.5 Starting the configuration ..................................................................................................................................... 76
14.6 Using the browser menu ........................................................................................................................................ 80
14.6.1 Control elements ......................................................................................................................................................... 81
14.6.2 Explanations of the names in the main menu ................................................................................................82
4
15 Main menu .....................................................................................................................85
16.1.3 General Information about GPRS Devices ........................................................................................................92
16.2 Internet Configuration ............................................................................................................................................. 96
16.2.1 Access type .................................................................................................................................................................. 96
16.2.4 Text message (SMS) ..............................................................................................................................................100
16.3.4 General Information on the Pac Correction Factor ...................................................................................... 110
16.3.5 Configuring power meters .......................................................................................................................................111
16.4 Configuring Plant Data ........................................................................................................................................... 118
16.4.1 General ...........................................................................................................................................................................118
16.4.2 Plant groups ................................................................................................................................................................119
16.4.4 Defining the PV plant's forecast data ............................................................................................................. 120
16.4.5 Defining the Feed-in tari ..................................................................................................................................... 121
16.6.1 Explanation of the individual E-mail Functions: ............................................................................................ 129
16.6.2 Text message (SMS) notifications .....................................................................................................................132
16.7 Alarm (only Solar-Log 1000 and 2000) ................................................................................................................. 132
16.8 Power & Failure ......................................................................................................................................................... 132
16.8.1 General Information on Performance Monitoring .........................................................................................134
16.10 Smart Energy ............................................................................................................................................................ 139
16.10.1 Defining Smart Energy Switching .....................................................................................................................139
16.10.2 Smart Energy Switching Groups ........................................................................................................................ 140
16.10.3 Configuring switching groups ............................................................................................................................. 144
16.10.4 Control Logics Definition - Operating Mode Appliances ....................................................................... 144
16.10.5 Control Logics Definition - Operating Mode Generator ............................................................................ 150
16.10.6 Smart Energy Surplus Management ...............................................................................................................152
16.12 Active power ............................................................................................................................................................... 156
16.12.1 Active power deactivated....................................................................................................................................... 157
16.12.2 Remote controlled active power reduction (only Solar-Log™ PM+) ...................................................... 157
16.12.3 Remote controlled active power reduction with the calculation of self-consumption (only So-
16.12.7 Adjustable Reduction with the Calculation of Self-Consumption .......................................................... 162
16.12.8 Fixed reduction in watts ........................................................................................................................................... 163
16.12.9 Fixed reduction in watts with the calculation of self-consumption ....................................................... 163
16.12.10 Percentage of consumption for an adjustable reduction ......................................................................... 163
16.13 Reactive Power .......................................................................................................................................................... 164
16.13.1 Reactive power deactivated ..................................................................................................................................164
16.13.2 Fixed value cos (Phi) shift factor ..........................................................................................................................165
16.13.3 Fixed reactive power in Var .................................................................................................................................... 165
16.13.4 Variable cos (Phi) shift factor over characteristic curve P/Pn ................................................................... 166
16.13.5 Variable reactive power via the characteristic curve Q(U)
(only Solar-Log 2000 with Utility Meter) ............................................................................................................... 167
16.13.6 Remote-controlled fixed value cos (Phi) shift factor only Solar-Log™ PM+) ......................................... 170
16.13.7 Linking (only Solar-Log 1000 and 2000) ......................................................................................................... 172
16.14 Direct Marketing ......................................................................................................................................................... 175
16.15 Editing Data ................................................................................................................................................................ 176
16.15.2 Data correction ........................................................................................................................................................... 177
16.15.3 System backup ............................................................................................................................................................. 177
16.16 System Configuration ............................................................................................................................................... 183
16.16.1 Access control ............................................................................................................................................................. 183
17.2.1 Current Measurement Values .................................................................................................................................194
17.2.2 Charging History 1-Day .............................................................................................................................................195
17.2.3 Charging History 7-Days...........................................................................................................................................196
17.5.1 Explanation of the Values in the Power Reduction Section ......................................................................203
17.5.2 Explanation of the Symbols in the Feed-in power (% DC) column: .......................................................206
17.5.3 Explanation of the Values in the Reactive Power Reduction Section ...................................................206
17.5.4 PM History .....................................................................................................................................................................209
17.6 Accessing the SCB Monitor (only Solar-Log 1000 and 2000) ................................................................. 210
17.8 Smart Energy ............................................................................................................................................................... 214
17.8.1 Explanations of the Tabs .......................................................................................................................................... 214
17.8.2 History Section ............................................................................................................................................................. 216
17.10 Accessing Support ..................................................................................................................................................... 221
18 Accessing Yield Data ............................................................................................... 222
18.1 Current values ............................................................................................................................................................ 222
18.1.1 Energy flow .................................................................................................................................................................. 224
18.2 Production ................................................................................................................................................................... 226
18.2.1 Day view ........................................................................................................................................................................ 227
18.2.3 Year view ....................................................................................................................................................................... 231
18.2.4 Total view ..................................................................................................................................................................... 232
18.3 Consumption (only when consumption meters are connected) ............................................................ 233
18.4.1 Day balance ................................................................................................................................................................... 241
18.4.3 Year balance ................................................................................................................................................................ 243
18.4.4 Total balance ................................................................................................................................................................ 244
18.6 Sensor (only when a sensor is connected) ..................................................................................................... 247
18.7 System Information .................................................................................................................................................. 248
19 Direct Device Configurations (Solar-Log 1200 and 2000) .......................250
19.1 Navigating from the touch screen ...................................................................................................................... 250
19.1.1 Accessing the Dashboard ....................................................................................................................................... 252
19.1.2 Access Energy flow ................................................................................................................................................... 253
19.1.3 Accessing the Energy Balance ..............................................................................................................................254
19.1.4 Start Smart Energy .................................................................................................................................................... 255
19.4 Settings on the device ............................................................................................................................................ 258
19.4.1 Start menu (only Solar-Log1200) ........................................................................................................................ 258
19.4.2 Basic settings menu ................................................................................................................................................. 265
19.4.3 USB menu .................................................................................................................................................................... 266
19.4.4 Advanced settings menu ........................................................................................................................................269
7
19.5 Error and Fault Messages on the Display ............................................................................................................ 274
20 Notifications on the LCD Status Display (Solar-Log 250, 300, 1200 and
20.1 Meaning of the symbols on the LCD display ...................................................................................................... 276
20.2 Notifications on the LCD display ............................................................................................................................ 279
20.3 Normal operation ......................................................................................................................................................... 279
20.4 Power reduction ........................................................................................................................................................... 279
21.1.3 Restoring the factory settings .................................................................................................................................. 281
21.1.4 Rebooting and Resetting via the web menu ...................................................................................................... 282
21.2.9 Special cases .................................................................................................................................................................. 291
22 Cleaning and care.........................................................................................................292
22.2 Care tips ............................................................................................................................................................................ 292
25.1 Internet ports ............................................................................................................................................................ 298
25.2 Country specific inverter detection with Easy Installation. .................................................................... 299
25.3 Wiring meters to record self-consumption .................................................................................................. 300
25.3.1 Meter connection options to record the total consumption via an RS485/S0 interface. ..........300
25.3.2 Meter connection options for bi-directional recording of the total consumption via only an
25.4 Connection examples for ripple control receivers .................................................................................... 302
25.4.1 Variation with 4 relays (ENBW >100kWp) ................................................................................................... 303
25.4.2 Variation with two relays ..................................................................................................................................... 305
25.4.3 Variation with three relays ...................................................................................................................................307
25.4.4 Variation with 5 relays (including emergency stop) .................................................................................. 309
25.5 Digital Interfaces ....................................................................................................................................................... 311
25.6 Live data compact – summarized (complete plant)................................................................................... 312
25.6.1 Open JSON Interfaces .............................................................................................................................................313
After installing firmware 3.x, it is no longer possible to downgrade to the previous versi-
ons. It is not possible to install older firmware versions.
The following changes occur when upgrading to 3.x:
The data transfer function is no longer available.
•
The Smart Energy section has been completely revised. If the function External Switch (only So-
•
lar-Log 1000) is used, this part needs to be reconfigured after the update.
The settings and function of the power management have to be checked and, if need be, reconfi-
•
gured.
With the new modern web interface, old web browsers might sometimes cause problems with
•
the functionality. We recommend using the current version of Mozilla's Firefox, Google's Chrome,
Microsoft Edge or Microsoft's Internet Explorer.
As part of the update, the Solar-Log™ has a data reformatting process running in the background. This
process starts once the update is finished. This process could last several hours and the Solar-Log™ will
operate and react slower until the update finishes.
12
Safety information
4 Safety information
In order to protect people, the product itself, and other equipment, please pay attention to the following
before handling the product:
the content of this manual,
•
the safety information,
•
the warning signs and type plates attached to the product.
•
This manual is intended for solar energy technicians and qualified electricians who are installing a
Solar-Log 250 (read the additional information below), 300, 1200 and 2000, wiring them to inverters, con-
figuring them to operate in particular systems, and putting them into operation.
All the actions described in this manual for wiring and working on inverters must be carried out only by
specially trained electricians. All repairs should only be carried out by similarly trained personnel, or by the
manufacturers themselves.
Solare-Datensysteme GmbH is not liable for any personal injuries, property damages and system malfunc-
tions and their consequences which result from not adhering to the product documentation.
Note!
The Solar-Log 300 functions described in this manual are essentially identical to tho-
se of the Solar-Log 250. Refer to the Solar-Log 250 data sheet for the differences.
13
Safety information
4.1 Hazard Classes
The safety instructions in this document are represented with standard signs and symbols. Two classes of
risk are identified, depending on their probability of occurrence and the seriousness of their consequences.
Danger!
Caution!
Indicates an imminently hazardous situation to life
Non-compliance with this warning can lead to severe and irreversible injuries or death
Indicates an imminently hazardous situation to people, or a risk of material damage
Non-compliance with this warning can lead to irreversible injuries or to material dama-
ge.
14
5 Electric current
Danger!
Risk of death by electric shock if inverters are opened.
Never open the inverter housing when the inverter is connected to power.
See Switching off the inverters on page 38.
Always read the installation and safety instructions given in the manual for the corres-
ponding inverter.
Danger!
Danger of death if there is condensation in the power supply unit when started!
Condensation can occur if the power supply unit is moved directly from a cold environ-
ment to a warm environment.
Wait until the temperatures have equalized before doing this.
Electric current
Caution!
Caution!
Caution!
Caution!
Damage to the electrical components in inverters and on interface cards due to elec-
trostatic discharge.
Avoid contact with component connections and plug contacts.
Before picking up the component, ground yourself by holding the protective conduc-
tor (PE) or the unpainted part of the inverter housing.
Damage to the electrical components of the Solar-Log™ due to the wiring of the So-
lar-Log™!
Switch the Solar-Log™ off;
See Chapter 11.1 on page 38
Risk of electric shock.
Do not use the unit if the housing of the external power supply unit is damaged. A
damaged power supply unit must be replaced by one of the same type and from the
same manufacturer in order to avoid danger.
The Solar-Log™ may only be used indoors or enclosed spaces.
The device has the protection class IP20.
15
Package contents
6 Package contents
Check the package contents before proceeding to assembly and install.
Report any damage or missing parts to the forwarding agent and dealer immediately.
The unit is supplied with the following components:
Solar-Log™ basic unit
•
2x cover panels to be fitted to the top and bottom of the unit to protect the connections and reset
•
button
12 V power supply with country-specific adapters
•
Terminal block connector for all connections
•
4x wall plugs and screws for wall mounting
•
16
Wall mounting
7 Wall mounting
The device is produced according to protection class IP20 and is intended only for installation in interior
areas that are dry and dust-free.
Suitable wall plugs and screws are supplied for wall mounting.
Please remember that an electrical outlet and a local network connection are required near the Solar-Log™
in order for it to operate. GPRS and WiFi models do not require the network connection.
Put the housing where it is to be fitted and mark the drill holes.
•
Fig.: Solar-Log™ wall mounting
The Solar-Log™ should be fitted in an easily accessible place.
•
Drill the holes and insert the wall plugs
•
The information on dimensions of the case and the mounting points is in chapter 26.6 on page
•
315
17
Wall mounting
•
Note! concerning
Solar-Log™ GPRS
The SIM card should be inserted before attaching the unit, as the insertion slot will no
longer be accessible after wall mounting.
Fasten the housing with the screws
Cable feed through – top and/or bottom covers.
•
Using a file or a saw, clear the cable feed holes.
The top and bottom covers are identical.
Plug all cable connectors into their connections.
•
Attach the covers
•
18
8 Unit connections
8.1 Solar-Log 300 / Solar-Log 250
Top connections
Unit connections
Fig.: Top Connections Solar-Log 300
Solar-Log 300* / Solar-Log 250
S0-Out
S0-IN A*
USBUSB connection. Suitable for
S0-IN BS0 pulse input for connection
*Only the Solar-Log 300 is equipped with this connection.
S0 pulse output for connecting
to a large external display. S0
pulse input for connection to
an external power meter. Plea
se note the connection charac-
teristics of the S0 connection.
USB sticks.
Not suitable for a connection
to a PC
to an external power meter.
-
19
Unit connections
Bottom connections
Fig.: Bottom connections Solar-Log 300
Solar-Log 300 / Solar-Log 250
RS485/422 - BRS485 interface, 6 pin:
Power 12 V12 volt DC input
NetworkEthernet network interface,
Connection for inverters
and additional accessories
10/100 Mbit
20
8.2 Solar-Log 1200
Top connections
Fig.: Top Connections Solar-Log 1200
Solar-Log 1200
Unit connections
S0-Out
S0-IN A
USBUSB connection. Suitable
S0-IN BS0 pulse input for connec
S0 pulse output for
connecting to a large
external display. S0 pulse
input for connection to
an external power meter.
Please note the connection
characteristics of the S0
connection.
for USB sticks.
Not suitable for a connecti
on to a PC
tion to an external power
meter.
-
-
21
Unit connections
Bottom connections
Fig.: Top Connections Solar-Log 1200
Solar-Log 1200
RelayRelay with change-over
RS485 - ARS485 interface, 4 pin:
RS485/422 - BRS485 interface, 6 pin:
Power 12 V12 volt DC input
NetworkEthernet network interface,
contact
Connection for inverters
and/or accessories (inacti
ve if the optional Bluetooth
interface is used)
Connection for inverters
and additional accessories
10/100 Mbit
-
22
8.3 Solar-Log 2000
Top connections
Fig.: Top Connections Solar-Log 2000
Solar-Log 2000
Unit connections
S0-Out
S0-IN A
AlarmConnection for contact
CANCAN bus — which, for
USBUSB connection. Suitable
S0-IN BS0 pulse input for connec
S0 pulse output for
connecting to a large
external screen. S0 pulse
input for connection to
an external power meter.
Please note the connection
characteristics of the S0
connection.
strip for anti-theft protec
tion.
example, can be used to
connect Voltwerk, Conergy
or Suntechnics inverters
for USB sticks.
Not suitable for a connecti
on to a PC
tion to an external power
meter.
-
-
-
23
Unit connections
Bottom connections
Fig.: Top Connections Solar-Log 2000
Solar-Log 2000
RelayRelay with change-over
RS485 - ARS485 interface, 4 pin:
RS485/422 - BRS485 interface, 6 pin:
Power 12 V12 volt DC input
NetworkEthernet network interface,
RS485/422 - CRS485 interface, 6 pin:
contact
Connection for inverters
and/or accessories (inacti
ve if the optional Bluetooth
interface is used)
Connection for inverters
and additional accessories
10/100 Mbit
Connection for inverters
and additional accessories
=> It is not possible to
connect a large external
display on this interface.
-
24
Optional Connections
9 Optional Connections
Solar-Log™ devices are available as different models which can be equipped accordingly with additional
interfaces and connections depending on the application.
9.1 Solar-Log™ GPRS
Antenna connection and SIM card slot
In addition to the connections on the standard Solar-Log™, the Solar-Log™ GPRS model with an integrated
GPRS modem has a SIM card slot and a screw connection for an antenna.
Insert the SIM card in the slot on the rear right, inside the Solar-Log™ GPRS
•
Fig.: Insertion slot for SIM card inside on the right (Solar-Log™ GPRS)
Screw the external antenna into the antenna connection on the bottom of the unit.
•
Find a suitable position with good reception quality for the magnetic base antenna.
Fig.: Antenna connection on the top of the device (Solar-Log™ GPRS)
25
Optional Connections
Note!
9.2 Solar-Log™ Meter (Solar-Log 300 and 1200)
The Solar-Log Meter version of the Solar-Log™ has an integrated interface to connect up to six current
transformers (CTs). This optional Meter interface makes it possible to measure generating units (producti-
on meter) and consumption from individual appliances.
We recommend checking and cleaning SIM cards once a year.
The contact points of the SIM card could start corroding due to humidity and should
be cleaned regularly to ensure trouble-free operations.
Fig.: Connection for current transformers (Solar-Log™ Meter)
The current transformers (CTs) can record the current flow (AC) of one or two phase appliances in various
combinations. The output is calculated based on a defined reference voltage or one calculated by the
Solar-Log™.
Note!
With the Solar-Log 300 and 1200 Meter, the mounting direction of the current
transformer (CT) is not relevant because the energy flow direction cannot be defined. It lacks a direct voltage measurement.
26
Combinations:
2x3 Phases
•
1x3 Phases + 3x1 Phase
•
6x1 Phase
•
3x2 Phases
•
2x2 Phases + 2x1 Phase
•
1x2 Phases + 4x1 Phase
•
The current transformers have to be connected to the Meter interface with the secondary side.
Optional Connections
Fig.: Two 6-pin terminal block connectors for the Meter interface
Solar-Log™ Meter 1
InterfacePINDescriptionLabel
Meter 11Current transformer/CT 1aS1/k
Solar-Log™ Meter 2
InterfacePINDescriptionLabel
Meter 21Current transformer/CT 1aS1/k
Current transformer
2Current transformer/CT 1bS2/i
3Current transformer/CT 2a S1/k
4Current transformer/CT 2b S2/i
5Current transformer/CT 3a S1/k
6Current transformer/CT 3b S2/i
Current transformer
2Current transformer/CT 1bS2/i
3Current transformer/CT 2a S1/k
4Current transformer/CT 2b S2/i
5Current transformer/CT 3a S1/k
6Current transformer/CT 3b S2/i
27
Optional Connections
Characteristics of the Meter interface
The current transformer may not exceed a maximum output or secondary current of 200 mA. The input /
rated current is calculated by the maximum amount of power that is to be measured and has to be selec-
ted for each measuring point.
The current transformer's rated measuring ratio can be defined for each current transformer input.
The current transformers have to be set up in a way so that only one current-carrying conductor is measu-
red. Cables with multiple wires cannot be measured.
The maximum cable length between the current transformers and Solar-Log™ depends on the cable dia-
gram and the load of the current transformer.
We recommend a maximum cable length of 30 meters with a diameter of 0.75 mm
For other current transformers, please consult the manufacturer's specifications in regard to cable length
and the wiring diagram.
2
for our products.
Note!
Due to the lack of a voltage supple for the measurements, only the apparent power
– not the active power – is measured. Since in most cases the active power should
be measured, we recommend measuring with a power meter when there is a large
percentage of reactive power.
Current transformers from Solare-Datensysteme GmbH
Solare-Datensysteme offers the following current transformers that are specially tailored to the Solar-Log™
Meter:
Current transformer
NameDescriptionArticle
Number:
Solar-Log™ CT 16 ACurrent measurement 16 A, transformer: 16A/
200mA
255639
28
Solar-Log™ CT 100 A-cCurrent measurement 100 A, transformer: 100A/
200mA
sealed transformer
Solar-Log™ CT 100 A-oCurrent measurement 100 A, transformer: 100A/
200mA
open transformer (folding mechanism)
255640
255638
9.3 Solar-Log™ PM+
Fig.: 6-pin PM+ interface
PM+
PINAssignmentDescription
Optional Connections
1+5VControl voltage for active
2D_IN_1Control input 1
3D_In_2Control input 2
4D_In_3Control input 3
5D_In_4Control input 4
6+5VControl voltage for reactive
power control
power reduction
29
Connector Assignments and Wiring
10 Connector Assignments and Wiring
The following connecting cables, which may be needed for various purposes, are not included in the
package content.
To connect a router, you need a network cable with the appropriate length. If you want to connect
•
the Solar-Log™ directly to your PC or laptop, you need to use a crossover cable.
Cable to connect the Solar-Log™ to an inverter.
•
Sets of prefabricated cables are available as accessories suitable for the inverter concerned. The
•
length of these cable sets is 3 m.
If you want to connect several inverters to Solar-Log™, you need suitable cables and connectors to
•
connect the inverters to each other.
For each connection to the Solar-Log™ (RS485 - A and RS485/422 - B or - C) a separate cable
•
must be used.
When wiring with CAT cables, the twisted pair of wires should be used.
•
10.1 Notes on wiring the connections
The wiring of the inverters and accessories needs to be carried out with the greatest care and attention.
The most frequent source of errors when installing the Solar-Log™ is faulty wiring.
For this reason, we recommend:
Wiring with high quality cables
•
For example: LIYCY >=0.14mm2 or Cat 5/7 SSTP
Refer to the manufacturer's specifications in regard to UV resistance and mounting type when
•
wiring in outside areas.
A larger cable diameter is recommended for longer distances.
•
Use ferrules with flexible wires
•
Twist the corresponding wire pairs and shielding
•
Wire from left-to-right.
•
Wire from light to dark.
•
30
Fig.: Example wiring on a 4-pin terminal block connector
Connector Assignments and Wiring
Fig.: Terminal block connector with ferrules
10.2 RS485-A (only Solar-Log 1000, 1200 and 2000)
Use the provided terminal block connectors when connecting inverters or accessories to the RS485 A
interface.
Fig.: 4-pin Terminal block connector
RS485 - A
PINAssignment
1Data +
212 V
3Ground
4Data -
31
Connector Assignments and Wiring
10.3 RS485/422 - B
Use the provided terminal block connectors when connecting inverters or accessories to the RS485/422 -
B interface.
Fig.: 6-pin Terminal block connector
RS485/422 - B
PINAssignments RS485Assignments RS422
1Data +T/RX+
212 V12V
3GroundGround
4Data -T/RX-
5R/TX+
6R/TX-
Note!
If inverters that use the RS422 connection are connected to this interface (e.g. Fronius,
AEG, Riello), then it is not possible to connect accessories such as sensors, meters or
displays to this bus.
32
Connector Assignments and Wiring
10.4 RS485/422 - C (only Solar-Log 2000)
Use the provided terminal block connectors when connecting inverters or accessories to the RS485/422 C
interface.
Fig.: 6-pin Terminal block connector
RS485/422 C
PINAssignments RS485Assignments RS422
1Data +T/RX+
212 V12V
3GroundGround
4Data -T/RX-
5R/TX+
6R/TX-
Note!
If inverters that use the RS422 connection are connected to this
nterface (e.g. Fronius, AEG, Riello), then it is not possible to connect accessories such as
sensors, meters or displays to this bus.
33
Connector Assignments and Wiring
10.5 S0
Solar-Log™ devices are equipped with the following S0 interfaces:
combined SO_OUT_IN interface (S0-OUT and S0-IN) and
•
S0-IN (only Solar-Log 300, 1200 and 2000)
•
10.5.1 S0 OUT / IN A (S0-OUT and S0-IN A)
The S0_OUT_IN interface is a hardware interface used for recording measurement values from power
meters and an output for S0 pulses. Use the supplied terminal block connector for the connection to the
Solar-Log™.
S0_OUT_IN A
PINAssignment
127 mA output
227 mA max. input
3Measuring contact
4Ground
5S0 Out+
6S0 Out-
Fig.: Schematic diagram of the S0 output
Note!
We recommend not using the S0 output for sending current feed amount response signals to your grid operator.
Due to the internal calculating processes of the Solar-Log™, there would be a delay in
sending the pulses.
34
Connector Assignments and Wiring
10.5.2 S0-IN B
The S0 In interface is a hardware interface used for recording measurement values from power meters. Use
the supplied terminal block connector for the connection to the Solar-Log™.
Fig.: 4-pin Terminal block connector
S0-IN B
PINAssignment
1S0 + Output 27mA
2S0 - Input max 27mA
3Measuring contact
4Ground
Installation instructions for external power meters are also in chapter „12.5 External power meters“ on page
47.
35
Connector Assignments and Wiring
10.6 PM+
The Solar-Log™ PM+ models come with a 6-pin PM+ interface on the top side of the Solar-LogTM.
The interface has been designed to link the ripple control receivers or telecontrol plants with potential-free
signal contacts. Up to two ripple control receivers can be connected. This allows the commands from grid
operators for active and reactive power to be interpreted.
Fig.: 6-pin PM+ interface
Fig.: 6-pin Terminal block connector
PM+
PINAssignmentDescription
1+5VControl voltage for active
2D_IN_1Control input 1
3D_In_2Control input 2
4D_In_3Control input 3
5D_In_4Control input 4
6+5VControl voltage for reactive
power control
power reduction
To provide the highest possible flexibility, the individual active and reactive power values can be assigned
to inputs D_IN_1 to D_IN_4
See Chapter „Feed-In Management“for more information
See the appendix for more ripple control receiver connection examples
36
Connecting the inverters
11 Connecting the inverters
As each inverter manufacturer uses different wiring connections and connectors, the corresponding data
cables must be adapted correctly.
See Chapter„Connector Assignments and wiring“ for terminal block connector wiring diagrams for
•
the connection to the Solar-Log™
Please refer to the Component Connection Manual when connecting inverters supported by the
•
Solar-Log™.
Note!
Solare Datensysteme GmbH supplies suitable connection cables for most inverter manu-
facturers.
Always read the manufacturer-specific instructions for connecting the data cable. You will find these inst-
ructions in the manufacturer's documentation.
However, when assigning the inverter wiring on the Solar-Log™, follow the instructions in this manual,
otherwise the inverters will not be detected by Solar-Log™.
Danger!
Risk of death by electric shock if inverters are opened.
Never open the inverter housing when the inverter is connected to power.
See the chapter "Switching inverters off."
Always read the installation and safety instructions given in the manual for the corres-
ponding inverter.
37
Connecting the inverters
11.1 Switch o the inverters and the Solar-Log™.
Switching inverters off
Before a making a cable connection between the Solar-Log™ and the connections inside the inverter and
before installing an interface card in the inverter, always turn off all of the inverters first.
To do this, read the manufacturer's documentation for the inverter, and proceed as follows:
Disconnect the AC side
•
Disconnect the DC side
•
Wait at least 5 minutes until the condensers in the inverters have discharged.
•
Turn the Solar-Log™ off.
Unplug the power socket connection
38
Connecting accessories
12 Connecting accessories
12.1 Sensor Box Basic and Professional
These sensors record both Irradiation sensor and module temperature values.
The solar radiation sensor must be fitted in such a way that the sensor's solar cell and the plant's modules
are aligned as similarly as possible to the sun, i.e. the sensor must have the same alignment and inclination.
The sensors should be positioned in a way to best ensure that:
as little overshadowing as possible occurs
•
and snow cover does not interfere disproportionately with the sensor functions.
•
To achieve this, it is best to fit the sensor on the side or above the solar module. Fitting bars can normally
be used as a fitting surface with modules that are parallel to the roof protrusion. In other cases, a suitable
fitting support may have to be added.
Note!
When using inverters with RS422 communication, do not operate the sensor on the same
bus.
Wiring the Sensor Box Basic and Professional to the Solar-Log™
The wiring is done using a
4-wire data cable which also includes the 12 V power supply and the data connection to the
•
Solar-Log™.
The sensors are connected to the Solar-Log™ via the RS485 interface parallel to the inverter bus or
•
via a free RS485 interface. Please pay attention to the notes in the component database. Sensors
cannot be connected to the same bus with some inverters.
The cable shielding must be connected with an equipotential bonding system.
•
A separate power supply is generally not required.
The connection cable can be extended (max. 50 m). In this case, however, it must be ensured that a power
supply voltage of at least 8 V is provided for the Sensor Box Basic at the end of the cable and 10.5 V for
the Sensor Box Professional. If necessary, a separate power supply can be integrated into the bus wiring.
The cable must also be suitably protected in outside areas. The cabling in inside areas can consist of a
shielded data cable.
39
Connecting accessories
Procedure
The four wires in the connection cable must be connected to the 4-pin terminal block connector on
•
the Solar-Log™.
The connection assignments are printed on the back of the sensor.
•
Connect the wires according to the following diagram
Important!
Sensor Box Basic and Professional
RS485 Solar-Log™Sensor connection
Replacing the connection wires may cause damage to the sensor.
cables
PINAssignment
1 (Data +)Brown: Data +
2 (+12V)Red: 12 V
3 (Ground)Black: 0V (GND)
4 (Data -)Orange: Data -
Installation
When the Solar-Log™ is switched on, the sensor is also automatically powered.
Then the Sensor Basic and Professional have to be configured to the desired RS485 interface:
Select the "Mencke&Tegtmeyer" sensor via the device definition according to the device class and
•
manufacturer.
Define the bus.
•
Perform device detection.
•
The Sensor Box Basic and Professional are integrated into the system like an inverter.
•
DC
(VCC)
40
Connecting accessories
12.2 Sensor Box Professional Plus
The Sensor Box Professional Plus is used to record the Irradiation from the sun. This accessory allows the
Solar-Log™ to calculate the deviations in the current output compared to the potential output.
Up to 9 Sensor Box Professional Pluses can be connected to the Solar-Log™. The solar radiation sensor
must be fitted in such a way that the sensor's solar cell and the plant's modules are aligned as similarly as
possible to the sun, i.e. the sensor must have the same alignment and inclination.
The sensors should be positioned in a way to best ensure that:
as little overshadowing as possible occurs
•
and snow cover does not interfere disproportionately with the sensor functions.
•
To achieve this, it is best to fit the sensor on the side or above the solar module. Fitting bars can normally
be used as a fitting surface with modules that are parallel to the roof protrusion. In other cases, a suitable
fitting support may have to be added.
If there are various module alignments at a plant, every alignment should be fitted with a Sensor Box Pro-
fessional Plus.
The Solar-Log™ can record and save additional environmental data with the Sensor Box Professional Plus
(with optional accessories). This environmental data includes:
Solar irradiation (integrated)
•
Module temperature
•
Module temperature is recorded by an integrated cell sensor, thus avoiding the costly process of
mounting a sensor on the back of the module.
Ambient temperature (optional, Article Number: 220062)
•
Wind speed (optional, Article Number: 220061)
•
The above data form important parameters in further evaluations and analyses to measure yield.
Notes on roof mounting
The irradiation sensor is specially designed for continuous use in outside areas (IP65). The cables supplied
with the Sensor Box Professional Plus are UV and weather resistant.
Recommended installation Not allowed
Fig.: Mounting information for the Sensor Box Professional Plus
Please note when fitting the sensor that the connection cable must be arranged as shown in the drawing.
41
Connecting accessories
Fitting optional sensors
The ambient temperature sensor must be fitted in a shady place with a wall bracket. The connection plug is
screwed firmly into the 3 pin input on the Sensor Box Professional Plus.
It is best to install the wind sensor in a high, exposed position using the mounting bracket. The connection
plug is screwed firmly into the 2 pin input on the Sensor Box Professional Plus.
Caution!
Warning!
Risk of damage to the unit!
Penetrating moisture can cause short circuiting and can destroy the Sensor Box Professi-
onal Plus and Solar-Log™.
It is not necessary to open the sensor to fit it. All components are simply screwed on. If
the housing is opened, water resistance and proper operation cannot be guaranteed.
Wiring the Sensor Box Professional Plus to the Solar-Log™
The Sensor Box Professional Plus can also be integrated in the bus wiring of the inverters.
Note!
When using inverters with RS422 communication, do not operate the sensor on the same
bus.
For inverters using RS485 communication, please check the compatibility in our Compo-
nent Database.
The Sensor Box Professional Plus is connected to the Solar-Log
The connection cable between the Sensor Box Professional Plus and the Solar-Log
and includes the 12 volt power supply and the data connection to the Solar-Log
TM
using the RS485 interface.
TM
consists of 4 wires
TM
.
The cable shielding must be connected with an equipotential bonding system.
A separate power supply unit is not required.
The connection cable can be extended (max. 50 m). However, an 10.5 V power supply is needed at the end
of the cable. For longer stretches please select a larger cable diameter.
42
Connecting accessories
Procedure
The four wires in the connection cable must be connected to the 4-pin terminal block connector on
•
the Solar-Log™.
Connect the wires according to the following diagram:
•
Important!
Replacing the connection wires may cause damage to the sensor.
Sensor Box Professional Plus
RS485 Solar-Log™Connection cable
Sensor Box Professional
Plus
PINAssignment
1 (Data +)Brown: Data + A
2 (+12V)Red: 12 V
3 (Ground)Black: GND
4 (Data -)Orange: Data - B
Installation
When the Solar-Log™ is switched on, the Sensor Box Professional Plus is also automatically powered. Then
the Sensor Box Professional Plus must be configured to the desired RS485 interface:
Select "M&T Sensor" and the corresponding bus for the initial configuration.
•
Perform device detection:
•
The Sensor Box Professional Plus is integrated into the system like an inverter.
•
The rest of the configuration for the environmental data is carried out via the Solar-Log™'s web
•
interface.
DC
43
Connecting accessories
12.3 Ripple Control Receiver
The Solar-Log™ PM+ series contains an additional 6-pin interface which allows up to two ripple control
receivers or telecontrol plants each with four signals to be connected.
Wiring
The relay contacts for the ripple control receiver are connected to the Solar-Log™ PM+ via the 6 pin PM+
interface on the top side of the Solar-Log™.
Fig.: 6-pin PM+ interface
The ripple control receivers used by grid operators utilize various numbers of relays. These relays are labe-
led differently and have different reduction levels and/or shift factors cos (Phi).
To ensure the highest degree of flexibility, the reduction levels specified by the grid operators, together
with their signals from the ripple control receiver, can be evaluated by the Solar-Log™ via a maximum of
four digital inputs for each.
In order that the Solar-Log™ PM+ can evaluate the signal from the ripple control receiver, it needs to be
wired to the control voltage (for active and reactive power) from the PM+ interface. The control contracts
normally operate as make contracts; that means they are closed for the respective command.
The control voltage from Pin 1 is used for the active power command.
The control voltage from Pin 6 is used for the reactive power command.
The control voltage is connected to the common contact of each relay. The relay output (closed contact)
is then connected to a digital input of the PM+ interface.
44
Fig.: The basic principle of wiring the PM+ interface to the ripple control receiver for active power commands
See the Appendix for more ripple control receiver connection examples on page of this installation ma-
nual.
Further configurations of feed-in management are carried out via the Solar-Log™ PM+ web interface in the
Configuration | Feed-in Management menu with the Active Power | Remote-controlled and Reactive
Power | Remote-controlled shift factor cos(Phi)
functions. See page 250 for more information.
Connecting accessories
12.4 Large External Displays
Large external displays can be connected to the Solar-Log™ via two interfaces:
Connection via RS485
•
S0 pulse output
•
The connection via RS485 is preferred Cable lengths can be up to 1000 meters and the data which is dis-
played on the Solar-Log™ can specified.
Note!
It is not possible to connect a large external display on the RS485 / 422 C interface.
Note!
Connection via the RS485/422 interface
Wiring for displays made by Schneider Displaytechnik
The wiring consists of a 3-pin control cable, (3x0.5 mm2) and terminal block connector.
Schneider Large displays
RS485 Solar-Log™Terminal block connec-
If inverters that use the RS422 connection are connected to this interface (e.g. Fronius,
AEG, Riello), then it is not possible to connect a display to this bus.
If the display is connected via the same cable as the inverters, the display must be confi-
gured accordingly in the interface parameters.
tor
Schneider Display
PINAssignment
1 (Data +)A
3 (Ground)GND
4 (Data -)B
Further information about the connection can be obtained from the manufacturer of the display.
45
Connecting accessories
Wiring for displays from RiCo Electronic
The wiring consists of a 2-pin control cable, (2x0.5 mm2) and terminal block connector.
RiCo Large displays
RS485 Solar-Log™Terminal block connec-
PINAssignment
1 (Data +)Pin 1 - Data +
4 (Data -)Pin 2 - Data -
Further information about the connection can be obtained from the manufacturer of the display.
Connection through S0 output
If the S0 output is used, only the current feed-in power can be transmitted in the form of a pulse sequence.
The display has to calculate the power output and total yield by itself.
tor
RiCo Display
Wiring for a contact-controlled S0 output
Example: RiCo Electronic
The wiring consists of a 2-pin shielded cable (2 × 0.6 mm
2
,
max. length 100 m) and terminal block connector.
RiCo Large displays
RS485 Solar-Log™Display
PINAssignment
5S0-
6S0+
Further information about the connection can be obtained from the manufacturer of the display.
Pulse factor
In the standard setting, Solar-Log™ sends 1000 pulses/kWh over the S0 output. The pulse factor must be
configured according to the size of the plant (kWp) in the
Display
menu.
Pulse factor / plant size
Plant size kWpPulse factor
Configuration | Devices | Definition | External
46
30 kWp2000
60 kWp1000
100 kWp600
150 kWp400
300 kWp200
600 kWp100
Connecting accessories
Note!
The impulse factor in the Solar-Log™ and the connected device has to be identical.
12.5 External power meter
External power meters can be connected to every Solar-Log™ model via the S0 input and/or the RS-485
bus.
Solar-Log™ devices have a varying number of SO inputs:
S0 inputs
Solar-Log™Number of S0 inputs
Solar-Log™
300*, 1200 and 2000
* Solar-Log 200s prior to 2011 do not have an S0 input
The energy recorded by these meters can be used for numerous applications:
Inverter mode
•
This mode is used for inverters that are not directly supported by Solar-Log™.
Total yield meter
•
This mode is used to record the energy production of several inverters.
Consumption meter
•
This mode is used to measure power consumption and to make it possible to display this data and
to use Smart Energy functions.
Utility Meter (U) (only Solar-Log 1000, 2000)
•
This mode is used for voltage measurements for reactive power control with the characteristic
curve Q(U).
Utility Meter (U+I) (only Solar-Log 2000)
•
This mode is used to record the measurement data needed for the response signals sent to the grid
operator and for cos phi control at the feeding point.
Note!
2 - S0A and S0
B
Note!
We recommend using the meters that we have tested and offer.
We cannot guarantee the functionality of other products.
Consumption meters can be assigned to plant groups.
It is only possible to assign a meter after a rule with the calculation of self-consumption
has been activated in the power management configuration
Management
.
Configuration | Feed-in
47
Connecting accessories
12.5.1 External power meters/accumulating meters
With multiple phase meters, a basic distinction is made between phase-exact and accumulating meters.
Accumulating meters provide the total values from all three phases. The meter calculates the total output
(also to and from the grid) of the individual phases and provides this total as a single value.
In the example:
Phase 1 supplies 3 kW via an inverter (single phase).
Phase 2 refers to 2 kW (energy)
Phase 3 refers to 1 kW (energy)
With an accumulating meter, this results in a total of 0 kW.
Examples of accumulating meters are the Janitza UMG 104 and the Inepro Pro380-Mod.
48
Connecting accessories
12.6 Wiring for S0 meter
The SO connection for external power meters is connected to a 6-pin S0-Out/In connection (S0-OUT and
S0-IN)) or to 4-pin S0-IN as follows:
SO meters in general
S0
Power meter
Solar-Log™
PINAssignment
1S0+
2S0-
3
4
Place a cable bridge between pin 3 and 4 on the Solar-Log™.
The maximum cable length between the power meter and Solar-Log™ is 10 meters.
Wiring for Inepro 75D meter via S0
Article Number: 255420
Inepro 75D
S0
Power meter
Solar-Log™
PINAssignment
1Pin 6 - S0+
2Pin 5 - S0-
3
4
Place a cable bridge between pin 3 and 4 on the Solar-Log™.
49
Connecting accessories
Wiring for Inepro 1250D meter via S0
Article Number: 255421
Inepro 1250D
S0
Power meter
Solar-Log™
PINAssignment
1Pin 9 - S0+
2Pin 8 - S0-
3
4
Place a cable bridge between pin 3 and 4 on the Solar-Log™.
Wiring for Iskra WS0021 meter via S0
Article Number: 255346
Iskra WS0021
S0
Power meter
Solar-Log™
PINAssignment
1Pin 9 - S0-
2Pin 8 - S0+
3
4
Place a cable bridge between pin 3 and 4 on the Solar-Log™.
Wiring for Iskra WS0031 meter via S0
Article Number: 255347
Inepro 1250D
S0
Power meter
Solar-Log™
PINAssignment
1S0+
2S0-
3
4
Place a cable bridge between pin 3 and 4 on the Solar-Log™.
50
Connecting accessories
Note!
After selecting S0 from the menu Configuration | Device | Definition, a device detection needs to be performed.
After the detection is finished, the detected meter can be configured under
Configuration | Device | Configuration.
12.7 Wiring for RS485 meter
The meter's RS485 output can be connected to any RS485 interface (A, B and C) on the Solar-Log™.
Overview
2-pin wiring.
•
The communication address does not have to be assigned.
•
Installation steps
Switch off the inverters and the Solar-Log™.
•
Connect the meter to the Solar-Log™.
•
The wiring is done using a self-made, shielded 2-wire data cable and a 4-pin or 6-pin terminal block
connector.
Procedure
Connect the wires for the connecting line as shown in the following diagram.
•
Wiring for RS485 meter
Solar-Log™ RS485 terminal block connector
PINPIN
18 - 485A11 - 485A22 - B
47 - 485B10 - 485B23 - A
Insert the terminal block connector into the Solar-Log™ RS485 A, RS485/422 B or RS485/422 C
•
socket.
Perform a device detection: The power meter is connected to the system as if it were an inverter.
•
Configure the power meter functions under Configuration | Device | Configuration. See ff Seite
•
109for more information.
Generator
•
Total yield meter
•
Consumption meter
•
Utility Meter (U) (only Solar-Log 1000 and 2000)
•
Utility Meter (U+I) (only Solar-Log 1000 and 2000)
•
Utility Meter (U+I) + Consumption Meter (bi-directional) (only Solar-Log 1000 and 2000)
•
Sub-consumer
•
Inepro 75D
terminal block
connector
Article number: 255420
Inepro 1250D
terminal block
connector
Article number: 255421
PINPIN
Utility meter terminal
strip
Article Number: 255385
51
Connecting accessories
Note!
Note!
Note!
Inepro 1250D
Only one Inepro RS 485 meter can be used for
each Solar-Log™ interface.
These meters cannot be used together at the same bus input with inverters that are
connected to RS422 (e.g. Fronius).
All three phases have to be connected for the Solar-Log™ to accurately detect the meter.
If an Inepro 1250D is used, the PRG button on the meter must be pressed and held down
during entire detection process.
If it is not possible to hold down the PRG button during the whole process, we recom-
mend provisionally connecting the meter to the Solar-Log™ with a short cable after the
installation in order to be able to press and hold down
the PRG button during entire detection process.
In a second detection attempt with the inverter, the meter is then detected by the So-
lar-Log™ even if the PRG button is not pressed.
The detection of an Inepro 1250D in an existing installation can take up to 15 minutes.
After the detection, a restructuring of the data takes places which can take up to 45
minutes depending on the amount of data on the devices.
52
Note!
Inepro meter
Connecting accessories
Inepro meters are automatically given the mod bus address 234 by Solar-Log™ during
the detection process.
This address is therefore not allowed to be used for other devices.
After the configuration, the display on the Inepro meter alternates between the meter
status and the address display (ID=EA). This can be used to check if Solar-Log™ has cor-
rectly detected the meter.
All RS485 meters have to be terminated with an 120Ω resistor between the two pins
The Solar-Log™ Utility Meter is a universal metering device. It can be integrated in both low- and medi-
um-voltage networks (via a transformer) and is needed for various functions:
controlling voltage-dependent reactive power via the Q(U) function
•
controlling reactive power at the feeding point
•
recording the measurement data needed for the response signals sent to the grid operator
•
Only the voltage measurements are needed to control voltage-dependent reactive power via the Q(U)
function (Although, it is still recommended to perform voltage and current measurements to check that
the reduction function is operating properly). Current and voltage measurements are needed for the other
functions.
The previous chapter explains how to wire the Utility Meter to the Solar-Log™. This chapter deals with
connecting the Utility Meter for measurements in low- and medium-voltage power grids.
Utility Meter supply voltage / Janitza UMG 104 / UMG 604:
95-240Vac, 45-65Hz or 135-340Vdc
•
The Utility Meter's measuring inputs have the following limits:
Voltage line conductor AC (without a voltage transformer): 10…300 V AC
•
Voltage phase AC (without a voltage transformer): 17…520 V AC
•
Current (without a current transformer) 0.005, 7.5 A
•
Frequency of the fundamental component: 45 ..65 Hz
•
The limit may not be exceeded. For this reason, a measuring transformer needs to be installed for most
applications.
We recommend the following transformer ratio:
Voltage: Secondary 100V
•
e.g. at 20kV grid converter 20000:100V
Current: Secondary 5A
•
e.g. 100:5A
Note!
The Utility Meter that we use is produced by the company Janitza.
Refer to the Janitza UMG 104 / UMG 604 manual for further technical details.
We cannot guarantee the functionality of other Janitza devices.
=> The operating modes Utility Meter (U / U+I) are only possible with the Solar-Log 1000
and 2000.
54
Note!
The Utility Meter cannot be connected to the inverters with a single bus.
For this reason, use one RS485 connection for the inverters and one RS485 connection
for the Utility Meter.
Connecting the Utility Meter to the power grid
Connecting accessories
Fig.: Example - Utility Meter UMG 104 connection diagram for voltage measurements in low-voltage power grids
Fig.: Utility Meter connection diagram for voltage measurements with current transformers (medium volta-
ge)
55
Connecting accessories
Fig.: Example - Utility Meter UMG 104 connection diagram for current measurements with current transformers
Procedure
Enter the supply voltage into the Utility Meter
•
Note!
We recommend using a fuse to safeguard the connection lines for the supply voltage.
Please follow the instructions in the Janitza UMG 104 manual.
Note!
Supply voltages that do not correspond to the specifications on the rating plate can cau-
se malfunctions and damage the device.
56
Caution!
The inputs for the supply voltage are dangerous to touch.
Connect the measurement lines for current and/or voltage to the bottom of the Utility Meter.
•
Connecting accessories
Note!
The measurement voltage must in effect be at least 10V or an exact measurement is not
possible.
Connect the Utility Meter to the RS485 bus of the Solar-Log™ according to the following diagram:
•
Wiring
the Utility Meter
Terminal block connector RS485 Solar-Log™
only Solar-Log 1000 and 2000
PIN
122
423
The RS485 bus must be terminated.
•
Install a 120 Ohm, 0.25 W resistor between pin 22 and 23 of the Utility Meter to terminate.
Configuring the Utility Meter from the display
•
Setting MODBUS Address (PRG 200 = 1)
Setting Baud rate RS485 (PRG 202 = 2)
Setting Mode (PRG 203 = 0)
Setting Current converter primary (PRG 000)
Setting Current converter secondary (PRG 001)
Setting Voltage converter primary (PRG 002)
Setting Voltage converter secondary (PRG 003)
Refer to the accompanying manual of the device for the UMG 104 configuration procedure.
Utility meter
Terminal block
connector
Article Number: 255385
PIN
Note!
The parameter settings need to be adjusted before device detection.
If the parameters differ, the Utility Meter will not be detected by the Solar-Log™.
Perform an inverter detection
•
See the installation manual, Chapter "Performing inverter detections."
Configure the Utility-Meter under Configuration | Devices | Configuration, select the correspon-
•
Operating mode and click on Save.
ding
Check
Does the Utility Meter display a positive value for inverters feeding power, the current output
•
(kW)?
If this is not the case, the current measurements are incorrectly connected.
If necessary, switch the polarity of measuring inputs.
57
Connecting accessories
Note!
12.9 Solar-Log™ Smart Relay Box
The Smart Relay Box makes it possible to switch 8 relays via the Smart Energy control logic depending on
the current production (surplus).
The Relay Box has:
4 inverter contacts
•
4 make contacts
•
Characteristics of the relays:
Maximum current load:
0.5 A @ 120 V
0.25 A @ 240 V
1 A @ 30V
0.3 A @ 110V
Procedure:
•
Relay Box
Wiring
DC
Connect the Relay Box to the RS485 bus of the Solar-Log™ according to the following diagram:
When replacing the polarity, the cable must not be energized, since the converter can be
destroyed otherwise.
AC
AC
DC
Terminal block connector RS485 Solar-Log™
PINPIN
1Data + (Y)
4Data - (G)
Device detection is not necessary for this device.
•
The device only has to be selected from the Configuration | Smart Energy menu to be activated.
•
The power comes from the top-hat-rail power supply that was included with the Relay Box.
•
Note!
The Relay Box has to be defined and activated as a switch in the Configuration | De-
vices | Definition | Interfaces
For more information, refer to the chapter:
"Configuring the device interface" and
"Defining Smart Energy Switching."
Relay Box
Terminal block
connector
Article Number: 255656
with the plus symbol to be able to configure it.
58
Note!
The Solar-Log™ Smart Relay Box cannot be connected together with inverters on an
RS485 interface. The Relay Box requires its own separate RS485 bus.
It is possible to combine the Utility Meter with sensors.
Note!
The Solar-Log™ Smart Relay Box cannot be connected together with PM+ packages on a
With the WeMo Insight Switch, home appliances and electronic devices can be connected to a Wi-Fi
network, allowing the devices to be remotely turned on and off. The Wemo Insight Switch can also moni-
tor the devices and will send information about the device’s energy usage directly to your smartphone or
tablet. Follow the subsequent instructions to be able to use these functions with the Solar-Log™.
Procedure:
1. Connect a desktop/laptop and the Solar-Log™ to the router with a LAN cable.
2. Download the WeMo app to your smartphone or tablet.
3. Reset the WeMo Insight Switch (press the reset button for 5 seconds while turning on the power
for the WeMo Insight Switch).
4. The WeMo searches for the smartphone or tablet via WiFi.
5. Start the WeMe app and connect the WeMo Insight Switch to the router's WiFi network.
6. Connect to the Solar-Log™'s WEB interface with the desktop/laptop and go to the Configuration |
Devices | Definition menu.
7. Select the device class "Switch" with the +plus button.
8. Select "Belkin" as the manufacturer and "WeMo Insight" as the type. Enter the number of devices
and click on save.
9. Then start the device detection from the
10. The connection is now established.
Configuration | Devices | Detection menu.
Note!
A direct connection between the Solar-Log™ WiFi and WeMo is not possible.
The Solar-Log™ has to be connected to a router via a LAN cable or to be in a network.
The last step is configuring the Smart Energy Logics. Refer to the Solar-Log ™ Smart Energy Manual for
more information. It is available from our website at https://www.solar-log.com/en/support/downloads
60
Connecting accessories
12.11 Allnet Network Power Socket
Allnet network power sockets can switch connect electronic devices on and off. These switching opera-
tions can be set manual, time-controlled or based on consumption levels. Allnet network power sockets
can be integrated into the local network with a LAN cable connection. Follow the following steps
to be able to use these functions with the Solar-Log™:
Procedure:
1. Connect the Allnet socket to a laptop or PC with a LAN cable and plug the Allnet device into a
power socket.
2. Click on Control Panel
3. and then go to the Network and Sharing Center (for other operating systems, refer to the instructions for setting the IP address).
4. Click on Local Area Connection to open the Status window and then click on Properties.
5. Select the Internet Protocol Version 4 (TCP/IPv4) and then click on Properties
Important!
Note the displayed values before you change them because you will need them again later.
6. Adjust the displayed values as follows (using the following IP address):
IP address: 192.168.0.101
Subnet mask: 255.255.255.0
Gateway: 0.0.0.0
Confirm the settings with "OK."
7. Enter the IP address 192.168.0.100 as the URL in your browser to access the Allnet menu.
8. Click on settings and go to
Configuration | LAN Settings.
9. Configure a separate IP address for every Allnet network power socket. The new IP address need
to match the range for the existing network (refer to your computer's original settings).
For example, if our computer's original IP address was 192.168.178.2 and the next address is free,
the Allnet network power sockets would start with192.168.178.3 and continue. The Subnet mask is
255.255.255.0 by default and must be the same for every device in the subnet. The gateway is typically the IP address of the router or switch to which the computer is connected again later. Save
the settings when they are completed.
10. After adjusting the networks settings for the network power sockets, change the values for your
computer's networking settings back to the original values.
11. The configuration is then finished.
Note!
To ensure functionality with the Solar-Log™, the ALL3075v3 still has to be set to remote
control in the Allnet socket configuration.
The last step is configuring the Smart Energy Logics. Refer to the Solar-Log ™ Smart Energy Manual for
more information. It is available from our website at https://www.solar-log.com/en/support/downloads
61
Connecting accessories
12.11.1 Connecting the Allnet network power socket to the Solar-Log™
The Allnet socket has to be defined with the device detection function to connect to the Solar-Log™. From
the WEB interface of the Solar-Log™ go to
"Switch" with the blue plus symbol and then Allnet as the manufacturer followed by the type and number
of devices. Confirm the selection with OK and start the detection from the
tection
the
Click on save once everything is finished.
menu. Let the detection process run completely. After that, select the corresponding devices from
Configuration | Devices | Configuration menu, enter the IP address and perform the rest of the setup.
Configuration | Devices | Definition and select the device class
Configuration | Devices | De-
62
13 Other connections
13.1 Alarm contact (only Solar-Log 1000 and 2000)
The Solar-Log 1000 and 2000 have an alarm contact which is triggered if the connection is broken.
This function can be used for various applications:
Anti-theft protection for the modules or inverters
•
For wiring to the mounting frame or to the modules, use a thin weather-resistant cable that breaks
•
when strained. The maximum cable length is around 500 meters.
Access control via door contact
•
Monitoring of circuit breakers
•
Connection to an uninterruptible power supply (UPS).
•
Other connections
If the connection is broken, the Solar-Log™ can carry out the following actions:
Switch a relay
•
Send e-mail
•
Send text message (SMS)
•
Produce an audible signal
•
The notification actions can be set on the Solar-Log 2000 in the section Configuration | Notifications |
.
Alarm
Connection
The connection is done using a 3-pin terminal block connector according to the following diagram:
Fig.: Alarm contact connection diagram
If the connection between pin 1 and pin 3 is broken, the alarm is triggered. and the configured action is
carried out.
63
Other connections
13.2 Relay (only Solar-Log 1000, 1200 and 2000)
The Solar-Log™ has a potential-free control relay, which is activated under the following conditions:
Alarm contact triggered
•
Active power reduction activated
•
Optimization of self-consumption
•
The relay may be loaded with a maximum of 24 V DC and 2 A.
A 230 V appliance has to be connected via another load relay.
Connection
Fig.: Relay connection diagram
Wiring
The wiring is done using the supplied 3-pin connector;
usually pin 1 and pin 2 are used.
In the Off state,
pin 1-2 are open
•
and pin 2-3 are closed.
•
In the On state (alarm/fault/power reduction activated),
and pin 1-2 are closed.
•
pin 2-3 are open
•
Note!
If a relay is used for the optimization of self-consumption, it has to be defined as a switch
and recognized (see Chapter "Configuring the device interface").
The operating states are then recorded.
64
Other connections
Acknowledge notification
There are two options to acknowledge a notification of a relay:
Display
•
Solar-Log™ WEB interface
•
Display:
A notification is displayed in the top line of the display with a blinking red triangle. Tapping on this triangle
is enough to acknowledge the notification. Do not use any pointed objects which may damage the display.
Solar-Log™ WEB interface:
Go to the Diagnostic | Notifications
menu to acknowledge the notification via the WEB interface. The acknowledgment is automatic once the
notifications have been loaded.
13.3 USB
Solar-Log™ 300, 1000, 1200 and 2000 have a USB connection. This USB connection can only be used for
USB sticks and not for a direct PC connection.
Note!
When a USB stick is connected, the Solar-Log™ automatically saves a backup in the ba-
ckup folder. A maximum of 10 backup files are saved in the directory. Older backup files
are automatically deleted.
The backup is saved on the USB stick in the directory /Backup with the following file names:
solarlog_backup_YYMMDD.dat
•
YYMMDD = year, month and day - each two digits, e.g.
170322 is then 22 March 2017
65
Installation
14 Installation
The Solar-Log™ has an integrated web server, which contains all the software necessary for operation and
configuration.
No additional software needs to be installed on the PC to access the Solar-Log™.
A common web browser with JavaScript enabled is required.
We recommend using the current version of Mozilla's Firefox, Google's Chrome, Microsoft Edge or Micro-
soft's Internet Explorer.
To run the web browser, a network connection is required between the PC and Solar-Log™, and Solar-Log™
must be up and running.
It is recommended to have DHCP enabled on the router.
Before setting up, ensure that there is no damage to the power supply. If in doubt, please contact
•
the address indicated on the back cover of this manual.
Before startup, check that the input voltage on the unit is the same as the voltage supply in your
•
country.
The unit must be operated only with the power supply unit supplied.
•
The unit is intended only for installation in interior areas that are dry and dust-free.
•
(IP20)
Note!
The maximum plant size for the various Solar-Log™ devices:
Solar-Log 300 up to 15 kWp
•
Solar-Log 1200 up to 100 kWp
•
Solar-Log 2000 up to 2000 kWp (2MW)
•
14.1 Connecting the Solar-Log™ to a network / PC
The Solar-Log™ is equipped with a standard Ethernet RJ45 socket, which can be connected through any
commercially available network cable. Speeds of 10 Mbit and 100 Mbit are supported.
In general, any PC networking technology can be used for connecting the Solar-Log™. The following tech-
nologies are available:
Connection through an Internet router
•
Ethernet RJ45 network cable
Direct cable connection from PC to Solar-Log™
•
Ethernet RJ45 network patch cable
If connecting directly to a PC, the cable must be the crossover network cable type (patch cable).
•
Connection through a power network (PowerLine package)
•
Connection through a wireless network (Solar-Log™ WiFi)
•
66
If the Solar-Log™ is operated via a router, ensure that the necessary ports have been activated (see Chap-
ter „Internet-Ports“).
Since the Solar-Log™ obtains its IP address while booting, it needs to be connected to the network before
being turned on.
14.1.1 Instructions for connection through the PowerLine package
If using the Solar-Log™ PowerLine package, the Solar-Log™ can be connected to the PowerLine adapter
using the network cable supplied.
Next, connect the PC, switch or Internet router through the second PowerLine adapter.
The two power connectors are connected to each other automatically and then act as "power supply net-
work cables".
The PowerLine adapters should not be connected to a multi-outlet power strip, as other power adapters
will affect the data quality.
Note!
The Solar-Log™ may not be connected directly to a TNV (Telecommunication Network
Voltage) circuit.
Installation
14.2 Initial installation Solar-Log 250 and 300
The Solar-Log 250 and 300 devices are configured completely from a connected PC or laptop.
Requirements
All cables and accessories (if any) have been connected to the Solar-Log 250 or 300.
•
The Solar-Log 250 or 300 is connected to an Internet router.
•
The DHCP service is enabled on the Internet router.
•
or
The DHCP service is enabled when connecting directly to the Solar-Log™ with a PC. (We recom-
•
mend using a patch cable.)
Easy Installation
After selecting the language and country, the initial set up can be carried out with the "Easy Installation"
configuration wizard. However, Easy Installation can currently only be used with certain inverters. Depen-
ding on the country, different inverter brands are integrated into the Easy Installation mode. Easy Installati-
on cannot be performed with GPRS.
The Solar-Log
For more information, please refer to the Quick Start Guide that was included with the device.
TM
then carries out the initial set up intuitively step by step.
67
Installation
14.3 Initial set up of the Solar-Log 1200
The initial configuration of the Solar-Log 1200 can be performed either with the touch display or the So-
lar-Log™’s web browser menu.
Requirements
All cables and accessories (if any) have been connected to the Solar-Log 1200.
•
The Solar-Log 1200 is connected to an Internet router.
•
The DHCP service is enabled on the Internet router.
•
The DHCP service is also enabled on the PC or laptop.
•
Easy Installation
After selecting the language and country, the initial set up can be carried out with the „Easy Installation“
configuration wizard. However, Easy Installation can currently only be used with certain inverters. Depen-
ding on the country, different inverter brands are integrated into the Easy Installation mode.
The Solar-Log
For more information, please refer to the Quick Start Guide that was included with the device.
TM
then carries out the initial set up intuitively step by step.
14.4 Setting up of the Solar-Log™ with the confi guration wizard
After the initial set up of the Solar-Log™ (see chapter 14.2 and 14.3), the Solar-Log™ starts to ask about the
following settings:
Language
•
Country and time
•
Display access control
•
At the end, a pop-up window appears where you can start the Solar-Log™ configuration wizard. (See the
following image: „Startup screen of the Solar-Log™ configuration wizard“).
At this point, if you do not want to continue with the setup, the configuration wizard can be stopped by
clicking on the „Cancel“ button. After clicking on „Cancel,“ the local „Cockpit“ WEB page is started. The
setup can be done manually from this menu. The Solar-Log™ configuration wizard can also be started at
any time from the
Note
Configuration | System | Configuration Wizard menu.
The configuration wizard can be stopped at any time by clicking on the „Cancel“ button
(left below the progress bar). The previously entered settings remain active.
68
Fig.: Startup screen of the Solar-Log™ conguration wizard
Click on the „Start“ button to run the configuration wizard. Once started, the Ethernet Settings menu ap-
pears (see image „Solar-Log™ Ethernet Settings via the Solar-Log™ configuration wizard“). In the network
settings can be entered in the IP address, subnet mask and gateway boxes. Instead of manually entering
the network settings, „Obtain IP address automatically (DHCP)“ function can be activated. A router with
DHCP enabled is required for this function.
Installation
Fig.: Solar-Log™ Ethernet Settings via the Solar-Log™ conguration wizard
Click on the „Connection Test“ button in the Internet connection section to check if the settings are cor-
rect.
Fig.: Example of a successful connection test
69
Installation
Fig.: Example of an unsuccessful connection test
Note
All settings are automatically saved using the „Next“ button. With the „Back“ button it is
possible to change the settings at any time.
If the test is successful, click on the „Next“ button to go to the next section. A dialog window appears.
From this window, you can check if a new Solar-Log™ firmware version is available (see image „Displayed
Firmware Update Window“).
Fig.: Displayed Firmware Update Window
By clicking on „Yes,“ the configuration wizard checks for a new firmware version and can install it after
that. At the end, the device detection is performed. Otherwise, the device detection menu appears by
clicking on „
No“ for the firmware update check.
70
Installation
Fig.: Device Detection with help text displayed
Note
The device detection is to be performed after the components have been connected.
Otherwise the corresponding boxes for the components are grayed out..
„Easy Installation“ selection
When „Easy Installation“ is selected, the detection is started automatically after clicking on the „Start“ but-
ton. Two functions are available during the detection:
Stop search:
•
Use the „
inverts have been detected. After the search is completed, the Interface assignments menu is displayed. Manual adjustments can be made here.
Next interface:
•
Use the „
correct.
After the detection has been successfully completed, the Device Configuration is the next step.
Stop search“ button to abort the detection process. This is useful, for example, when no
Next interface“ to skip to the next interface if the number of components detected is
“Manual Installation“ selection
Selecting „Manual Installation“ displays the Interface Assignment menu. From this menu, the connected
devices need to be manually selected with the plus symbol. After that click on the „Start“ button to start
the detection. (Also refer to Chapter „
Device Definition“)
71
Installation
Note
It is important to let the detection process finish running and then to click on OK at the
end.
Click on „OK“ after a successful detection. Then click on „Next.“ The device configuration menu ap-
pears. In the device configuration, one can, for example, define the generator output, the module
fields and the names of the individual components. (Also refer to Chapter „
Device Configuration“)
Fig.: Example - Con guration Wizard - Device Con guration
The „Portal“ menu appears after clicking on the „Next“ button. The data transfer to the Solar-Log WEB
Enerest™ portal and local monitoring can be activated from this menu.
The box „Portal Server“ appears once the data transfer to the Solar-Log WEB Enerest™ portal is activated.
There are two options for entering the portal server:
Option when the Solar-Log™ has already been registered on the portal:
•
The portal server can be manually entered if it is known. Otherwise, it is possible to enter it automatically with the obtain portal server function (by clicking on the globe symbol).
Option when the Solar-Log™ has not been registered on the portal:
•
If the Solar-Log™ has not been registered on the portal, the function to obtain portal server automatically can be triggered with the globe symbol. Then the box „Portal Server“ is grayed out and
the Solar-Log™ enters a waiting state. The Solar-Log™ remains in this waiting state until it has been
registered in the Enerest portal (see the Solar-Log WEB Enerest™ User Manual, available to download from https://www.solar-log.com). After that the Solar-Log™ obtains the portal server automatically.
After activating local monitoring, the process can be completed by clicking on the „Next“ button. The
E-mail Settings menu then appears.
72
If local monitoring remains deactivated, the configuration wizard is finished once you click on the „Next“
button. The system information page appears with a summary. (See illustration: „Summary of the configu-
ration wizard with deactivated data transfers“)
Installation
Fig.: Example - Summary of the con guration wizard with deactivated data transfers
Note
When local monitoring is deactivated, the e-mail, text message notifications, FTP export
and FTP backup functions are also deactivated.
When local monitoring is activated, the wizard goes to the E-mail Settings menu. The e-mail settings can
be configured and tested in this menu (see Chapter „E-mail“).
Note
When the E-mail function is not activated, the configuration wizard is finished once you
click on the „Next“ button.
73
Installation
After the E-mail Configuration, the Device Notification menu appears. The error and status codes that, for
example, are sent as e-mails can be defined in this menu. The maximum number of e-mails per day can also
be defined. (See Chapter „Setting up Notifications for more information“)
When the Definition is completed, click on „Next“ to configure Performance and Failure Monitoring. The
individual monitoring parameters can be configured here (see Chapter „Power & Failure“).
Clicking on „Next“ takes you to the last menu „Notification by E-mail.“ In this menu, there is the option
to configure the type of yield overview (e.g. short yield overview) and the sending time. After clicking
on „Next,“ the configuration wizard is finished and a summary is displayed. (See the following illustration:
Example of the Configuration Wizard Summary)
74
Fig.: Example of the Conguration Wizard Summary
14.4.1 Carrying out the initial set up of the Solar-Log 250, 300, 1200 and
2000 (manually).
The initial configuration of the Solar-Log 250, 300 and 2000 is performed via a web browser. All of the
device connections need to be established and it is best to connect the Solar-Log™ to an Internet router.
All settings made at the initial startup can be changed later.
Procedure:
Enter the address http://solar-log in the address bar of the web browser.
•
A selection of display languages is displayed.
•
Select the desired Display Language.
•
The browser access control configuration window appears. Click on save after the defining the user
•
password.
Sign in by clicking on the log in button (bottom right).
•
Define the country and time zone. Click on “save.”
•
Select the installation parameters for the component detection. Click on “manual installation” or
•
start.”
“
After selecting “manual installation,” the Welcome screen with the interface configuration section
•
appears.
After selecting “start,” the detection is started. Once completed, the menu Yield data | System
•
information appears. Click on “
The following menus have to be configured:
•
Internet
Network
Device
Plant and
System
Configuration” in the configuration bar at the top.
Installation
75
Installation
14.5 Starting the configuration
The various options to open the main menu of the Solar-Log™ are listed below:
Device URL
Start the web browser
•
Enter http://solar-log in the address bar and press the ENTER key
•
The main menu of the Solar-Log™ is displayed
•
Fig.: Main menu of the Solar-Log 2000 PM+ GPRS
76
Alternatively, the Solar-Log™ can also be accessed as follows:
IP address from an automatic IP range
Start web browser
•
Enter http://169.254.wx.yz in the address bar and press the ENTER key.
•
Here wxyz stands for the last 4 digits from serial number of the
Solar-Log™. The serial number is printed on the model tag.
Fig.: Solar-Log™ model tag
The main menu of the Solar-Log™ is displayed.
Installation
IP address that was entered during the initial configuration
Start the web browser
•
Enter IP address from the Initial Configuration in the address bar and press the ENTER key.
•
The main menu of the Solar-Log™ is displayed.
•
Device URL when there are several Solar-Log™ devices on the network
Start the web browser
•
Enter http://solar-log-wxyz in the address bar and press the ENTER key
•
Here wxyz stands for the last 4 digits from serial number of the Solar-Log™.
The serial number is printed on the model tag.
The main menu of the Solar-Log™ is displayed.
•
77
Installation
Setting passwords
If no password has been defined after the update to firmware 3.5.3, the following window appears with
security information.
Fig.: Pop-up window with security information
Click on “Yes” here to directly define a user password. The following configuration page appears:
78
Fig.: Conguration page “Access control”
In the Access protection for the browser section, the user password can be activated and defined. Click on
“save” after the defining the password. It is necessary to log in as a user with the newly defined password
(log in button on the button right) to continue with the configuration.
Set password later (not recommended)
It is possible to define the user password later by clicking on “No” or by clicking on “No” after checking the
box “I am aware of the security risks.” Close the “Do not show this dialog automatically any more” window.
If “Do not show this dialog automatically any more” was checked, the security warning will no longer appe-
ar each time when accessing the web interface.
As a reminder to define a password, a small red triangle appears in the top right corner. Click on this icon
at any time to define the user password. Once a password has been defined, the triangle disappears.
Installation
79
Installation
14.6 Using the browser menu
The browser menu of the Solar-Log™ functions like a website and is divided into fourth main sections:
Header bar (A)
•
Left navigation (B)
•
Tabs (C)
•
Configuration page (D)
•
The sections Yield data and Diagnostic are described in the user manuals of the respective models.
80
Fig.: Layout of the main menu
14.6.1 Control elements
The following control elements are used:
Control elements in the browser menu
Control elementMeaning
Text eld
Text eld with incorrect or
missing entry
Drop-down selection list
Virtual switch
deactivated and activated
The question mark boxes
display additional information
Installation
Check boxes
Several boxes can be selected at one time
Command buttons for various functions
Fig.: Control elements in the browser menu
After making changes in the browser menu, the follow message is displayed at the bottom of the page:
The changes have not been saved.
After clicking on the Save button the following message is displayed:
The changes have been saved.
81
Installation
14.6.2 Explanations of the names in the main menu
Header bar
The header contains three main sections:
Yield data:
•
Here you will find your plant’s yield overview within certain periods of time such as day, month,
year and the total yield to date.
Diagnostics:
•
Here you can view the fault and process messages while filtering them according to specified criteria.
Configuration:
•
Here you can change the device settings as required.
Left-side navigation menu
Depending on the tab selected, you can access additional functions from the navigation menu (left-side).
Tabs
Additional configuration sections appear according to the function selected.
Configuration Page
Here you can make necessary configurations for the optimal monitoring and evaluation of your plant. You
can also view information on the power output, yields and the device.
Log in button
You can entered a password protected section by clicking on the log in button (at the bottom right corner
of the screen) and entering your user and password. On the right side on the bottom, there is a blue line
next to the log in button which indicates if you are logged in and with which user level. (Refer to the Ac-
cess Control
Fig.: Log in button with selection box
Hide arrow
The “Hide Arrow” (on the right of the header bar) allows you to increase the amount of the page displayed
in the browser by hiding the Welcome header.
section for more information)
82
Fig.: Header bar with the “Hide Arrow”
New Firmware
A notification is sent via the Web browser when a new firmware is version available; a green triangle with
an exclamation mark is displayed at the top in the status line. (See illustration: Signal for new firmware)
Fig.: Signal for new rmware
Note!
The Automatic Firmware Update Check has to be activated in the Configuration |
System | Firmware
menu to use this function. (See illustration: Automatic Firmware
Update Check with notification text displayed)
Installation
Fig.: Automatic Firmware Update Check with noti cation text displayed
The following notification text is displayed by clicking on the question mark:
“This settings allows firmware versions with critical errors to be automatically updated. However, generally,
this setting only indicates that a new firmware version is available (green exclamation mark at the top).
83
Installation
Clicking on the green exclamation mark in the header displays the following window:
Fig.: Window displayed indicating that a new rmware version is available
Selecting “OK” redirects you to the page of the Solar-Log™ for firmware updates. Selecting “Cancel” closes
the window.
84
15 Main menu
The main menu is divided into the following sections:
Configuration
•
Diagnostics
•
Yield data
•
In addition, the following sub-menus are displayed in this view:
Cockpit
•
Energy flow
•
Table
•
These are also located on the left side of the of the VLCD Display (see “VLCD Display” section for more
details) and in additional sub-menus (depending on connected the devices) and as a selection in the main
navigation menu.
Main menu
15.1 VLCD Display
The VLC Display is located above the left navigation menu and displays the notifications from the So-
lar-Log™in the form of codes and symbols in addition to the date and time. The codes and symbols corre-
spond to those for the LCD display. (Refer to the illustration “VLCD Display” and the chapter “
the symbols on the LCD display”
The notifications are in real-time and are identical to those on the Solar-Log™ LCD Display. (Solar-Log 300,
1200 and 2000) (Also refer to the chapter “Notifications on the LCD Status Display”)
Fig.: VLCD Display
)
Meaning of
85
Configuration Menu
16 Confi guration Menu
The Configuration menu is divided into the following sub-sections:
Network
•
Internet
•
Devices
•
Plant
•
Notifications
•
Smart Energy
•
Feed-In Management
•
Direct Marketing (as long as a license has been purchased and entered)
•
Data
•
System
•
The following sub-sections of the menu will be explained separately in the following chapters.
16.1 Confi guring network settings
Open the dialog box.
Select Configuration | Network from the menu.
The Network menu is divided into the following sub-sections:
Ethernet
•
GPRS (only Solar-Log™ GPRS)
•
WiFi (only Solar-Log™ WiFi)
•
Proxy
•
Note!
Requests and control commands are sent to the inverters, battery systems and intelli-
gent appliances via the network interface. For this reason, the network should always be
available (24/7). If the Solar-Log™ is connected via WiFi, we recommend deactivating
the overnight shutdown function.
86
16.1.1 Ethernet
Fig.: Ethernet settings
Configuration Menu
The Ethernet settings for the Solar-Log™ are adjusted in this tab.
Obtain IP address automatically (DHCP)
Here the following options are available:
Activate Obtain IP address automatically
•
Deactivate Obtain IP address automatically.
•
.
With the default settings of the Solar-Log™, the Obtain IP address automatically option is deactivated.
If the Solar-Log™ should
This is only possible if the Solar-Log™ is connected to an Internet router with DHCP enabled. When the
search is started, the Solar-Log™ attempts to obtain an IP address through an Internet router. This can take
up to 60 seconds.
If the DHCP server is disabled in the router, the network settings must be configured manually. If neces-
sary, please consult a network specialist who can assign a suitable network address in regard to IP address,
Subnet mask and Gateway, for example.
If the Solar-Log™ is to have a
to be
deactivated. The following fields need to be adjusted according the network's configurations.
IP address
The address needs to be entered manually in order to allow remote PC access, when using a direct PC
connection or a router without DHCP service.
Obtain its IP address automatically (DHCP), this switch needs to be activated.
fixed IP address, the Obtain IP address automatically (DHCP) switch needs
Subnet mask
The Subnet mask is 255.255.255.0 by default and must be the same for every device in the subnet.
Gateway
The gateway is typically the IP address of the router to which Solar-Log™ is connected. That IP address is
to be entered here.
87
Configuration Menu
Alternate DNS server
In some networks, the DNS server is a separate address for resolving Internet addresses (unlike a gate-
way). If an Alternate DNS server is needed, switch the function to activated and enter the IP address of the
DNS server.
Once finished, click on
Save.
Connection Test
Use the „Connection Test“ button to determine if the entries are correct and if a connection can be suc-
cessfully established. The message indicates if the connection was successful or not. (See the following
illustrations)
Fig.: Example of a successful connection test
Fig.: Example of an unsuccessful connection test
88
16.1.2 GPRS (only Solar-Log™ GPRS)
Configuration Menu
Fig.: GPRS settings
In many cases where no DSL or telephone connection is available, a GPRS mobile network is the only opti-
on to connect to the Internet to send e-mails, text messages (SMS) and data to the homepage.
In order to establish a GPRS connection, the data from the GPRS service provider needs to be entered in
the following fields.
Note!
The Signal Strength of the GPRS connection is indicated on the LCD display with the
symbol.
Note!
Lists of international APN settings and providers is available at
Selection of major mobile service providers (APN user and password are automatically filled in)
APN
APN (Access Point Name) of the mobile service provider
Users
User name for your mobile phone account
Password
Password for the mobile phone account
SIM PIN
PIN number of the SIM card
Limiting the number of dial-in attempts
Activating this function provides the option to limit the maximum number of dial-in attempts for the mo-
dem per day.
Note!
When the number of dial-in attempts allowed is too low, it is possible that certain tasks
such as sending error messages or data transfers via FTP export or HTTP can no longer
be reliably executed.
Always stay online
Activate this option when continuous data transmissions are required.
If this option is activated, the GPRS modem is continuously connected to the service provider. This setting
is only recommended for flat-rate data plans.
Roaming allowed
By activating the roaming function, the Solar-Log™ can also connect to other mobile networks when the
home network is unavailable.
Note!
Activating the roaming function could potentially result in enormous additional costs.
90
PUK entry
A locked SIM card can be unlocked in the SIM PUK menu. Enter the PUK code / super PIN of the SIM card
and then go to
Send.
Configuration Menu
Caution!
After sending the PUK code / super PIN, the PIN of the SIM card is reset to the one de-
fined in the
GPRS Settings | SIM PIN menu.
Status and Test section
The GPRS connection can be tested and disconnected with this function. The error codes displayed under
Last Error are „21.2.1 Fault messages GPRS“ explained.
The number of attempts for the day can be viewed in the field "
The count can be reset to 0 by clicking on the "
Reset" button.
Note!
The field "Previous Dial-in Attempts" and "Reset" button are only visible once the Limit
Dial-in Attempts function has been activated.
Previous Dial-in Attempts."
Note!
The dial-in Attempts count is reset once per day or also when the device has been re-
booted.
91
Configuration Menu
16.1.3 General Information about GPRS Devices
We recommend checking and cleaning SIM cards once a year.
The contact points of the SIM card could start corroding due to humidity and should
be cleaned regularly with a suitable medium (no screwdriver or cleaning solvents) to ensure trouble-free
operations.
Caution!
Corrosion on the SIM card contact points is an indication that the installation location does conform to the
IP20 protection class.
Only remove the SIM card after the Solar-Log™ has been turned off. Removing the SIM
card during normal operation may cause a card defect.
92
16.1.4 WiFi (only Solar-Log WiFi)
Configuration Menu
Fig.: WiFi settings
The Solar-Log™ WiFi models are equipped to be connected in a wireless local area network.
Status section
The WiFi function can be switched on and off with the Activate WiFi function. In the status box, the cur-
rent status of this function is displayed.
Possible Status:
Initializing
•
Initialization error
•
Disconnected
•
Connected
•
Connecting
•
Connection lost
•
Searching
•
Search finished
•
The Signal Quality is indicated on the LCD display with the symbol.
93
Configuration Menu
Network Settings section
The Start search button is used to initiate a search for wireless networks. The status Searching is display-
ed.
Once the search is completed, the wireless networks found are listed and can be selected from the SSID.
The Solar-Log™ automatically switches to the encryption used by this network. If the network name is hid-
den ("Hidden SSID"), the Access Point is not displayed by the network scan. In this case, enter the network
name and security key.
The following encryption options are available:
WEP
•
WPA-AES
•
WPA-TKIP
•
WPA2-AES
•
WPA2-TKIP
•
After selecting a network, the network's security method is automatically selected. Enter the network's
security key
in the password box. Save the settings.
Network address settings section
Note!
These settings apply to the wireless connection to the router. We recommend using
DHCP. The IP address is obtained automatically if the Solar-Log™ is connected to an In-
ternet router with the DHCP service enabled. After saving and the automatic restart, the
new IP address is displayed.
All routers usually come with the DHCP service enabled by default, so that all the subsequent data are
entered automatically:
IP address, Subnet mask, Gateway and DNS server
The settings can also be manually configured in these boxes. For this, the DHCP function has to be deacti-
vated.
If necessary, please consult a network specialist who can assign a suitable network address in regard to IP
address, Subnet mask and Gateway, for example.
Alternate DNS server
In some networks, the DNS server is a separate address for resolving Internet addresses (unlike a gate-
way). In this case, the IP address of the DNS server is entered here. The alternate DNS server can also be
configured manually from the
Network | Ethernet menu.
94
16.1.5 Proxy
Fig.: Proxy settings
Configuration Menu
The proxy function is not enabled by default. Configure the proxy in the Configuration | Network | Proxy
menu.
The proxy settings need to be configured in the Solar-Log™ to enable Internet communication via the pro-
xy server. Proxy servers are typically used in the networks of organizations and companies.
The data transfer only refers to the FTP transfer.
Procedure
When using a proxy, select Connect Method.
•
Enter proxy server, port, user name and password.
•
SAVE the settings.
•
95
Configuration Menu
16.2 Internet Confi guration
Select Configuration | Internet from the menu.
The following tabs can be displayed:
Access type
•
Portal
•
When local monitoring is activated under Configuration | Internet | Portal , the following tabs are visible:
E-mail
•
Text message (SMS)
•
Export
•
Backup
•
16.2.1 Access type
The type of Internet access that the Solar-Log™ uses to connect to a portal or server is adjusted in this tab.
Procedure
Select the type of Internet Access
•
Selection options:
Network Router (DSL, cable, WiFi)
GPRS (mobile network)
Mobile router (GPRS, UMTS, LTE)
SAVE the settings.
•
16.2.2 Portal
The following functions are available in this tab (Solar-Log 250, 300, 1200 and 2000):
Activate / Deactivate transfers
•
Activate:
•
• Portal Server
• Transfer interval
Local monitoring can be activated
•
The following functions are available in this tab (Solar-Log 200, 500 and 1000):
Select the Internet portal platform for the transmission of the data from the Solar-Log™
•
Local monitoring can be activated
•
Note!
Please download the Solar-Log WEB Enerest™ User Manual from our website to efficient-
ly use and configure the Solar-Log WEB Enerest™.
Located here: https://www.solar-log.com/en/support/downloads
96
Configuration Menu
Solar-Log WEB Enerest™ settings section (Solar-Log 250, 300, 1200 and
1000)
In this section, the following selection options are available:
Activate / Deactivate transfers
•
Portal Server
•
Transfer interval
•
WEB-Portal settings section (Solar-Log 200, 500 and 1000)
In this section, the type of portal used can be selected. The following selection options are available:
No portal
•
Solar-Log WEB Enerest™
•
Selfmade
•
Classic 1st Edition
•
The function is activated from the portal selection box by checking the Local Monitoring box. After selec-
ting local monitoring, additional tabs appear.
Procedure
Select the type of Portal.
•
In the Transfer Settings section.
•
Activate transfers.
•
Portal Server (see above)
•
Select the transfer interval.
•
SAVE the settings.
•
Status (Solar-Log WEB) Section
The following fields are displayed in the Status section:
Date (Last Export)
•
Error (Last Export)
•
97
Configuration Menu
Test Solar-Log WEB Section
A connection test can be performed in the Test section. A separate pop-up window is displayed with the
progress of test. The connection test also indicates if the test was successful or not. If it was not successful,
it displays the error. After the tests are finished, possible causes for the connection problems are listed.
(See the following example illustration).
Fig.: Example - Transfer Test with an Error Image
After confirming with OK, an additional field with the status of the test is displayed in the Test section.
Question marks indicate that the test was unsuccessful and possible causes are listed.
Fig.: Example - Connection Test with an Error
98
Configuration Menu
16.2.3 E-mail
The settings in this section serve as the basic configuration for sending e-mails via the e-mail client integra-
ted into the Solar-Log™. The Solar-Log™ can send e-mails in the following situations:
Daily yield overview
•
Inverter faults
•
Inverter failure
•
Deviation from target power
•
We recommend using the e-mail address provided by Solare Datensysteme GmbH for sending e-mails.
This is sent to you by e-mail as part of the portal registration process.
In addition, you also have the option of saving your own address.
Note!
Many e-mail providers have switched their servers to secure connections and now only
allow e-mail to be send via these secure connections. Users with such e-mail providers
have to adjust the settings in the Solar-Log according to the instructions from the provi-
ders.
Note!
The certificates from the following providers have been integrated to send e-mail via a
secure connection: GMX, WEB.DE, GMAIL and T-ONLINE. Other e-mail servers or certifi-
cates cannot be used.
E-mail settings section
Enter the settings for sending e-mail via the Solar-Log™'s e-mail client in this section. The data for the
boxes SMTP Server, SMTP user name, SMTP password and sender is in the confirmation message from the
portal registration. Enter this data in the corresponding boxes. Enter the recipient's e-mail address in the
corresponding box.
99
Configuration Menu
Connection security
The security method from the particular e-mail provider has to be selected next to the point Connection
security. The port for the secure connection is to be entered after the SMPT server.
Fig.: Example conguration STATTLS to send e-mail with GMX
Status & Test e-mail section
In this section, the e-mail settings can be tested and the information from the last sent e-mail displayed.
16.2.4 Text message (SMS)
The Solar-Log™ text message (SMS) program sends customized messages with any of the following cont-
ent:
Daily yield overview
•
Inverter faults
•
Inverter failure
•
Deviation from target power
•
There are two options to send text messages (SMS):
Text messages (SMS) direct via GSM modem
•
This option is only available with GPRS models.
Text messages (SMS) via e-mail forwarding
•
Text messages (SMS) are sent in two stages: First, an e-mail message is sent to an e-mail service
provider who provides the text message (SMS) service. From a keyword in the Subject line, this
provider detects that the message is to be forwarded as a text message (SMS) to a certain number.
For the incoming e-mails, some e-mail providers forward a text message (SMS) free of charge with
the Subject line for information.
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.