Solar Energy FWS 20 Installation And Instruction Manual

Fresh Water Station
Installation and Instruction manual
FWS 20
For tradesman Accurately read before installing
EN
2
E & OE, subject to change without notice.
Usage1 . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety instructions and symbol legend2 3
Safety instructions2.1 . . . . . . . . . . . . . . . . . 3
Symbol legend2.2 . . . . . . . . . . . . . . . . . . . 4
Scope of delivery3 . . . . . . . . . . . . . . . . . . 4
Provisions4 . . . . . . . . . . . . . . . . . . . . . . . . 5
Statutory provisions4.1 . . . . . . . . . . . . . . .5
Manufacturer’s specifi cations4.2 . . . . . . . . 5
Technical data5 . . . . . . . . . . . . . . . . . . . . 6
Installation6 . . . . . . . . . . . . . . . . . . . . . . . 7
Installation on buffer tank6.1 . . . . . . . . . . .7
Wall fastening6.2 . . . . . . . . . . . . . . . . . . . .8
Hydraulic installation6.3 . . . . . . . . . . . . . . . 9
Circulation unit (optional)6.4 . . . . . . . . . . .10
Design of circulation unit6.4.1 . . . . . . . . . . . . . . 10
Installation of circulation unit6.4.2 . . . . . . . . . . . 11
Electric connection of circulation unit6.4.3 . . . . . 11
Operating modes of circulation unit6.4.4 . . . . . . 12
Initiation7 . . . . . . . . . . . . . . . . . . . . . . . . 13
Malfunctions 8 . . . . . . . . . . . . . . . . . . . . 14
No hot water8.1 . . . . . . . . . . . . . . . . . . . . 14
No circulation8.2 . . . . . . . . . . . . . . . . . . .15
No/wrong switching times8.3 . . . . . . . . . . 15
Constant circulation mode8.4 . . . . . . . . . 15
Fresh Water Station leaks8.5 . . . . . . . . . . 15
Terms of warranty9 . . . . . . . . . . . . . . . . 16
Appendix10 . . . . . . . . . . . . . . . . . . . . . . . . 17
Example of use10.1 . . . . . . . . . . . . . . . . . . 17
Cascade connection10.2 . . . . . . . . . . . . . .18
Table of contents
Table of contents
3Usage
E & OE, subject to change without notice.
Usage1
The Fresh Water Station is used to heat up tap water in connection with a buffer tank. It will be installed next to the buffer tank at the wall or directly onto the buffer tank at special system solutions.
Another use or installation is not intended. The manufacturer is not liable for damages due to inappropriate use and the operator bears the risk.
Do not connect the Fresh Water station directly to any heat generator.
The Fresh Water Station includes a self-suffi cient regulation and can be upgraded with an optional circulation unit.
Safety instructions and symbol legend2
Safety instructions2.1
The installation, initiation and maintenance must only be accomplished by qualifi ed tech- nical professionals.
The operation of this device is not allowed to persons (including children) with limited physi­cal, sensory or intellectual abilities. Uninformed or unacquainted persons may operate the de­vice only under the supervision or at a trained person’s disposition.
Replacements or repairing of electrical parts like the power cord must be conducted by a professional electrician.
Follow the instructions in this manual closely to ensure proper functioning.
Exclusively use the Fresh Water Station for heating up tap water.
Only install the device in dry and frost-free locations.
Operate the device only at ambient tempera- tures between +2°C and +40°C.
Interrupt the power supply of the heating sy- stem (230 V/AC) prior to installation.
During operation the device can heat up and burns are possible.
The device must be connected to an exter- nal circuit breaker to allow a shutdown at any time.
Installation and operation must be performed according to regional laws, regulations and common practice.
At the occurrence of malfunctions – regardless of nature – please contact your authorized technical professional.
4 Scope of delivery
E & OE, subject to change without notice.
Scope of delivery3
Symbol legend2.2
Safety instructions
are marked with a warning triangle as illustrated on the left.
Safety instructions indicate important information for potentially dangerous situations for person and device. Additional buzzwords describe nature and severity of the danger.
Advices
are marked with an information sign as illustrated on the left..
Advices highlight important information for situa­tions without severe danger for person and de­vice.
max. tightening
torque [Nm]
Screw wrench
indicates the maximum tighte­ning torque and the rotational direction.
Fresh Water Station
Fresh Water StationPicture 1:
Connection Set
Connection setPicture 2:
Mounting Set
Mounting setPicture 3:
5Provisions
E & OE, subject to change without notice.
Provisions4
Statutory provisions4.1
The Device must be installed and operated accor­ding to the following norms and country specifi c directives and provisions.
DIN EN 12828• DIN 1988• DIN 4708• DIN 4753• DIN 4757• DIN 18380• DIN 18381
DIN 18382• DIN EN 12975• VDE 0100• VDE 0185• VDE 0190• ÖNORM H5195
Manufacturer’s specifi cations4.2
The stated values are guideline values which can deviate under certain operating conditions.
Material damage
Deviations from the values stated in table 1 may lead to damages and functional limitations of the device. Noncompliance with these values leads inevitably to a loss of guarantee.
Material damage
For operating the Fresh Water Station, the following specifi c values have to be adhered:
permissible dissolved matter and maximum values.Table 1:
Dissolved matter Unit Specifi c values (copper brazed)
pH-value 7-9 (considering Saturation index) Saturation index (delta pH-value) -0,2 < 0 < +0,2 Degree of hardness °dH 6-15 conductivity μS/cm 10...500 Filterable matter mg/l <30 Free chlorine mg/l <0,5 Hydrosulfi de (H2S) mg/l <0,05 Ammoniac (NH3/NH4+) mg/l <2 Sulfate mg/l <100 Hydrocarbonate mg/l <300 Hydrocarbonate/Sulfate mg/l >1,0 Sulfi de mg/l <1 Nitrate mg/l <100 Nitrite mg/l <0,1 Iron, solute mg/l <0,2 manganese mg/l <0,1 Free aggressive carbonic acid mg/l <20
6 Technical data
E & OE, subject to change without notice.
Technical data5
8
7
5
4
3
2
1
6
B
C
A
D
E
9
1 Thermostatic head 2 Electricity box 3 Plate heat exchanger 4 Flow-Switch 5 Charge pump 6 Coiled probe 7 Push-in connection for
circulation unit (incl.
blind cap) 8 Circulation unit (optional) 9 Bleed screw charge
pump A Cold water B Hot water
C From buffer tank (
ow) D To buffer tank (return) E Circulation pipe (not
included)
Design of Fresh Water StationPicture 4:
Fresh Water Station 20
Max. flow rate 20 l/min
Charge pump 230 V (50 Hz)
Rotation speed 2200 U/min
Power input 95 W
Nominal current 0,4 A
Circulation unit 230 V (50 Hz)
Power input 8 W
Nominal current < 0,1 A
Max. operating pressure
Tap water circuit 10 bar
Buffer water circuit 3 bar
PPEnoitalusnI
gk 71 thgieW
Fresh Water Station 30
Temperatures min. - max.
Ambiance 2°C - 40°C
Buffer water 2°C - 95°C
Dimensions
mm 004htdiW
mm 008thgieH
mm 033htpeD
Connections
Cold water G1” internal thread
Hot water G1” internal thread
Buffer
ow G1” external thread
Buffer return G1” external thread
Circulation G ½“ internal thread
Technical dataTable 2:
7Installation
E & OE, subject to change without notice.
Installation6
Material damage
Avoid tightening torque and force effects on already installed parts and connections of the device.
Regulation The Fresh Water Station includes a self-suffi cient regulation. An additional external regulation is not intended and not allowed..
Installation on buffer tank6.1
1
10 mm
40 mm
max. 10 Nm
Installation of Fresh Water StationPicture 5:
3
max. 70 Nm
Installation of connection setPicture 6:
2
max. 70 Nm
Installation of water pipingPicture 7:
4
90°
90°
45°
Shaping of fl exible hosesPicture 8:
0 Nm
8 Installation
E & OE, subject to change without notice.
Wall fastening6.2
5
Final assembly of shaped connection set Picture 9:
1
2
1
2
3
Wall fasteningPicture 10:
max. 70 Nm
4
max. 10 Nm
60
min. 80
S12
12 mm
Ø12
max. 70 N
9Installation
E & OE, subject to change without notice.
Hydraulic installation6.3
Install the hydraulic piping according to the in­structions in chapter 6.1 or 6.2.
Piping Piping between buffer tank and Fresh Water Station ought to be as short as possible.
When using different piping materials take care of the installation sequence to avoid electrochemical corrosion.
Personal and material damage
The tap water supply needs to be constructed according to specifi cation (see picture 12).
Specifi cation of tap water supplyPicture 12:
9 10 13 14 15 16 17
K
Expansion vessel (optional) Manometer Security valve (6bar) Cut-off valve Backfl ow preventer Pressure reducer (necessary if K >= 6 bar) Fine fi lter Tap water main connection
9
13
14
10
15 16
14
K
8
0
0
400
3
5
9
,
5
Drilling plan for wall fastening
Drilling plan for wall fasteningPicture 11:
17
60
min. 80
S12
12 mm
400
800
395,5
Ø12
10 Installation
E & OE, subject to change without notice.
Circulation unit (optional)6.4
This chapter is only relevant for Fresh Water Stations with a circulation unit.
Design of circulation unit6.4.1
1
3
8
9
7
6
2
5
5
4
1 Circulation pump 2 Gasket ring 3 Plug-in adapter 4 Non-return valve 5 Flat gasket 6 Cut-off cock 7 Swivel nut 8 Eccentric tappet 9 Circulation pipe (not
included)
Circulation unitPicture 13:
11Installation
E & OE, subject to change without notice.
Installation of circulation unit6.4.2
Personal and material damage
Suffi cient expansion and overpressure safety devices must be installed in the circulation circuit.
A rinsing port needs to be installed in the circulation circuit.
1
2
3
4
5
Installation circulation unitPicture 14:
Electric connection of circulation unit6.4.3
Danger to life
Manipulation of electrical parts • must be conducted by a profes­sional electrician. Deenergize the device before • opening it. Local regulations must be ob-• served.
Connect the circulation unit according to the desired operating mode. The connector assign­ment for time-dependent circulation is depicted in picture 16 and the connector assignment for pulsed circulation is depicted in picture 17.
12 Installation
E & OE, subject to change without notice.
A
B
C
Circulation unitPicture 15:
A B C
Temperature dial Timer clock with switching segments Operation mode selector
Circulation shutdown temperature
The circulation will be deactivated when the shut­down temperature is reached.
The preset temperature at the tem­perature dial (A) must be at least 10 K below the set temperature at the Fresh Water Station to avoid non-stop operation of the circulation unit.
Set the temperature dial to the desired tempera­ture.
Manual deactivation of circulation unit
Set operation mode selector ( C ) to “OFF”.
Time-dependent circulation (factory pre- setting)
Set the switching times of the circulation unit with on the timer clock (B)
Set operation mode selector (C) to “TIMER”.
Timer clock switching segments (B) Circulation unit status Up
Down
Activated Deactivated
NLNL
HT-PUMP 230V IN
NLL2
FLS CIRC PUMP
M
~
M
~
2
1
3
5
4
Connector assignment time-dependent circulationPicture 16:
1 2 3 4 5
Flow-Switch (FLS) Charge pump Fresh Water Station (HT PUMP) Circulation pump (CIRC PUMP) Connection clamp Power supply (230 V / 50 Hz)
Pulsed circulation
The circulation unit is activated by a short actuati­on of a hot water tapping point.
Set operation mode selector (C ) to “ON”.
NLNL
HT-PUMP 230V IN
NLL2
FLS CIRC PUMP
M
~
M
~
2
1
3
5
4
Connector assignment pulsed circulationPicture 17:
1 2 3 4 5
Flow-Switch (FLS) Charge pump Fresh Water Station (HT PUMP) Circulation pump (CIRC PUMP) Connection clamp Power supply (230 V / 50 Hz)
Operating modes of circulation unit6.4.4
13Initiation
E & OE, subject to change without notice.
Initiation7
Material damages
Put Fresh Water Station into operation only after completed fi lling.
Check tightness of swivel nuts.• Fill device and check for leak-tightness.• Open valves on both buffer and tap water
sides slowly to avoid pressure blows. Connect device to power supply.• De-aeration and rinsing of device:
Open a nearby hot water tapping point and » turn thermostatic head to maximum.
The buffer-side is de-aerated with the » charge pump bleed screw (see picture 4). Continue the process until the system is completely de-aerated.
Stream noises in the charge pump are an indication of air in the system.
Set the hot water temperature as desired by • turning the thermostatic head.
Set circulation unit (optional)• Clip on insulation.
After initiation the complete system needs to be checked for function and leak-tightness.
14 Malfunctions
E & OE, subject to change without notice.
Malfunctions 8
Prior to malfunction diagnostics, make sure that the following parameters are met:
Suffi cient fl ow temperature, minimum 55°C at maximum 45°C tap water temperature.
Faultless electrical connection.
Personal and material damage
Execute fault repair only with ade- quate qualifi cation.
Disconnect the device from power supply before opening it.
Adhere to regional norms and regulations!
No hot water8.1
Cause Relief
Buffer tank not hot enough Increase temperature in buffer tank Charge pump doesn’t
convey buffer water
Check water level in buffer tank (extraction of buffer water for the Fresh Water Station happens at the highest point of the tank).
De-aerate buffer circuit and check system pressure. Check, if all shutoffs (buffer and tap water side) are open. If not,
open them. Check hydraulic resistance between buffer tank and Fresh Water
Station and reduce it, if necessary. Check at initiation if the Fresh Water Station is correctly con-
nected to the buffer circuit and drinking water system. Check Flow-Switch and electricity box. Replace broken charge pump.
Flow-Switch sends no signal to charge pump
Remove Flow-SwitchA Clean Flow-Switch housingB Reintegrate Flow-SwitchC If the Flow-Switch still sends no signal to the charge pump, D
replace Flow-Switch.
Electricity box broken (relay doesn’t switch)
Check if power cord is connected to the electricity network.A Close shutoff valvesB Remove Flow-SwitchC Activate Flow-Switch manually. A working relay causes a swit-D
ching noise in the electricity box. If there is no switching noise, replace electricity box.E
Wrong hot tapping water temperature
Tap hot water. Turn the thermostatic head to max. temperature A for a short time.
Hot water is prepared: set then thermostatic head to the desired temperature.
No hot water is prepared:
Check buffer water temperature. » Check the heat exchanger for thermal furring. »
15Malfunctions
E & OE, subject to change without notice.
Cause Relief
Thermal furring of plate heat exchanger
Clean plate heat exchanger
No circulation8.2
Cause Relief
Circulation pump doesn’t convey.
Check if shutoff at circulation connection is open. Check electric connections. Circulation pump is not set properly. To check that, set the
operation mode selector to “ON”
If the pump conveys water, check settings on the pump » and eventually switch to “Timer Mode”
If no water is conveyed, replace circulation pump. »
Hydraulic resistance of tap water piping is too big for circu­lation pump
Check dimensioning of tap water piping.
No/wrong switching times8.3
Cause Relief
Circulation unit was switched to time-independent circulation
Reconnect wiring of circulation pump for time-dependent circulation
Timer clock misaligned Set timer clock and switching times
Constant circulation mode8.4
Cause Relief
Circulation unit is not set properly
Check settings of circulation pump
Set timer clock » Set operation mode selector to desired mode »
Set temperature on circulation unit is higher than the set tem­perature on the thermostatic head
Align the temperature setting of the circulation unit (approxi- mately 10°C below the set tap water temperature)
Fresh Water Station leaks8.5
Cause Relief
Fresh Water Station is leaking Check connection of pipes and sealings at the leaking de-
vice. Replace broken sealings.
16 Terms of warranty
E & OE, subject to change without notice.
Terms of warranty9
The Manufacturer issues a warranty of two years from the invoice date on the device and its consti­tuent parts.
Without proper installation and use of the device the warranty is void.
17Appendix
E & OE, subject to change without notice.
Appendix10
Example of use10.1
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19
Buffer tank Fresh Water Station Tapping point Heating boiler Solarstation Solar collector Heating Circuit group Heating circuit Expansion vessel Manometer Buffer charge pump (heating boiler) Bleeder Security valve Shutoff valve Backfl ow preventer Pressure-reducing valve Fine fi lter Bare tube-heat exchanger Layer separating plate
A
B C D E
F G H
I
J K
Heating boiler fl ow Solar fl ow Heating boiler return Solar return Buffer water fl ow Heating circuit fl ow Buffer water/heating circuit return Tap water (hot) Circulation return (optional) Tap water (cold) Tap water supply
Example of usePicture 18:
1
2
3
4
7
8
5
9
9
9
6
18
11
12
13
13
13
14
14
10
15
16
14
10
I
10
H
J
A
C
D
G
F
E
B
19
19
K
17
18 Appendix
E & OE, subject to change without notice.
Cascade connection10.2
4
1
2
3
5
5
A
B
C
E
D
25 kPa
35 kPa
Cascade connectionPicture 19:
1 2 3
4 5
Fresh Water Station – Station 1 Fresh Water Station – Station 2 Fresh Water Station – Station 3 (max. 3 stations) Circulation unit (optional) Overfl ow valve
A B C D E
Buffer water return Buffer water fl ow Tap water (hot) Circulation return (optional) Tap water supply
19Appendix
E & OE, subject to change without notice.
Notes:
700369-1201-en
Contact
SEG Solar Energy GmbH Hauptplatz 7 A-9300 St.Veit/Glan
www.solarsales.eu
Loading...