SolarEdge SE43.2KUS User Manual

Three Phase Inverter with Synergy Technology
for the 208V Grid for North America
SE43.2KUS
12-20
WARRANTY
INVERTERS
Specically designed to work with power optimizers
Easy two-person installation – each unit mounted separately, equipped with cables for simple
connection between units
Balance of System and labor reduction compared to using multiple smaller string inverters
Independent operation of each unit enables higher
uptime and easy serviceability
No wasted ground area: wall/rail mounted, or horizontally mounted under the modules (10  inclination)
Integrated arc fault protection and rapid shutdown for NEC 2014, NEC 2017 and NEC 2020 per article
690.11 and 690.12
solaredge.com
Fixed voltage inverter for superior efficiency (97%) and longer strings
Integrated DC Safety Switch
Built-in RS485 surge protection, to better withstand surges caused by lightning or other events
Built-in module-level monitoring with Ethernet or cellular GSM
150% DC oversizing, enabling higher energy production
Three Phase Inverter with Synergy Technology
for the 208V Grid for North America
SE43.2KUS
SE43.2KUS
OUTPUT
Rated AC Power Output 43200 VA
Maximum AC Power Output 43200 VA
AC Output Line Connections 4-wire WYE (L1-L2-L3-N) plus PE or 3 wire Delta
AC Output Voltage Minimum-Nominal-Maximum
AC Output Voltage Minimum-Nominal-Maximum
AC Frequency Min-Nom-Max
Maximum Continuous Output Current (per Phase) @208V 120 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Congurable Power Factor, Country Congurable Thresholds
(1)
INPUT
Maximum DC Power (Module STC), Inverter / Unit
Transformer-less, Ungrounded Ye s
Maximum Input Voltage DC to Gnd 300 Vdc
Maximum Input Voltage DC+ to DC- 600 Vdc
Nominal Input Voltage DC to Gnd 200 Vdc
Nominal Input Voltage DC+ to DC- 400 Vdc
Maximum Input Current 38 x 3 Adc
Maximum Input Short Circuit Current 135 Adc
Reverse-Polarity Protection Ye s
Ground-Fault Isolation Detection 350kΩ Sensitivity per Unit
CEC Weighted Eciency 97 %
Nighttime Power Consumption < 12 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown NEC2014, NEC2017 and NEC2020 compliant/certied, upon AC Grid Disconnect
RS485 Surge Protection Built-in
DC SAFETY SWITCH
DC Disconnect 1000V / 3 x 40A
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, CSA 2.22
Grid Connection Standards IEEE 1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class A
INSTALLATION SPECIFICATIONS
Number of units 3
AC Output Conduit Size / Max AWG / Max PE AWG 2” / 4/0 / 4
DC Output Conduit Size / Terminal Block AWG Range /
Number of Strings
Dimensions (H x W x D)
Weight Primary Unit: 105.8 / 48; Secondary Unit 99.2 / 45 lb / kg
Operating Temperature Range -40 to +140 / -40 to +60
Cooling Fan (user replaceable)
Noise < 60 dBA
Protection Rating NEMA 3R
Mounting Brackets provided
(1) For other regional settings please contact SolarEdge support
(2) Single input option per unit (up to 3AWG) available (3) For power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
(2)
(1)
(L-N) 105-120-132.5 Vac
(1)
(L-L) 183-208-229 Vac
59.3 - 60 - 60.5 Hz
Ye s
64800 / 21600
2 x 1.25” / 6-14 / 9 󰎯rings
Primary Unit: 37 x 12.5 x 10.5 / 940 x 315 x 260;
Secondary Unit: 21 x 12.5 x 10.5 / 540 x 315 x 260
(3)
in / mm
W
F / ˚C
© SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 03/2021 DS-000030-1.0-NA. Subject to change without notice.
Loading...