SolarEdge Managing an Alternative Power Source User Manual

Managing an Alternative Power Source with a Power Plant Controller
0
Managing an Alternative Power Source with a Power Plant Controller MAN-01-00xxx

Disclaimers

Important Notice

Copyright © SolarEdge Inc. All rights reserved.
No part of this document may be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior written permission of SolarEdge Inc.
The material furnished in this document is believed to be accurate and reliable. However, SolarEdge assumes no responsibility for the use of this material. SolarEdge reserves the right to make changes to the material at any time and without notice. You may refer to the SolarEdge web site (www.solaredge.com) for the most updated version.
All company and brand products and service names are trademarks or registered trademarks of their respective holders.
Patent marking notice: see http://www.solaredge.com/patent
The general terms and conditions of delivery of SolarEdge shall apply.
The content of these documents is continually reviewed and amended, where necessary. However, discrepancies cannot be excluded. No guarantee is made for the completeness of these documents.
The images contained in this document are for illustrative purposes only and may vary depending on product models.
1
Managing an Alternative Power Source with a Power Plant Controller
2

Emission Compliance

This equipment has been tested and found to comply with the limits applied by the local regulations.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, you are encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance may void the user’s authority to operate the equipment.
Managing an Alternative Power Source with a Power Plant Controller
3

Version History

Version 1.6 (January 2021) – updated configuration process
Version 1.5 (July 2020) – updated connection scheme
Version 1.4 (April 2020):
Updated configuration UI Added section – Dynamic Site Limitation configuration Added Appendix – debug mode configuration
Version 1.3 (January 2020) – added IOD (Input/Output Driver) algorithm
Version 1.2, December 2019 – support for external configuration file
Version 1.1, November 2019 – updated IOD software configuration procedure
Version 1.0, November 2019 – first release

Contents

Disclaimers .......................................................................................................................................................... 1
Version History .................................................................................................................................................. 3
Contents ............................................................................................................................................................... 3
Handling and Safety Instructions ............................................................................................................... 4
Introduction ........................................................................................................................................................ 5
System Requirements ..................................................................................................................................... 6
System Overview ............................................................................................................................................... 7
Installing and Configuring the System ................................................................................................. 10
Appendix A - Identifying the Inverter CPU Firmware Version .................................................... 19
Appendix B – Debug Mode Configuration ......................................................................................... 20
Supported Standards ................................................................................................................................... 24
Support Contact Information ................................................................................................................... 25
Managing an Alternative Power Source with a Power Plant Controller
4
WARNING
Denotes a hazard. It calls attention to a procedure that, if not correctly performed or adhered to, could result in injury or loss of life. Do not proceed beyond a warning note until the indicated conditions are fully understood and met.
CAUTION!
Denotes a hazard. It calls attention to a procedure that, if not correctly performed or adhered to, could result in damage or destruction of the product. Do not proceed beyond a caution sign until the indicated conditions are fully understood and met.
NOTE
Denotes additional information about the current subject.
IMPORTANT SAFETY FEATURE
Denotes information about safety issues.
NOTE
Discard this product according to local regulations or send it back to SolarEdge.

Handling and Safety Instructions

During installation, testing and inspection, adherence to all the handling and safety instructions is mandatory. Failure to do so may result in injury or loss of life and damage to the equipment.

Safety Symbols Information

The following safety symbols are used in this document. Familiarize yourself with the symbols and their meaning before installing or operating the system.
Disposal requirements under the Waste Electrical and Electronic Equipment (WEEE) regulations:
Managing an Alternative Power Source with a Power Plant Controller
5

Introduction

Energy-generation systems (such as PV inverters) connected to the grid may include different types of energy generating sources. In some cases, when grid power is
disconnected, PV inverters should operate in parallel with other voltage sources, such as diesel generators. In this document, “generator” is used as a general term for such
sources.
When inverters operate concurrently with generators, they may be subjected to voltage
and frequency fluctuations that exceed trip settings, which are preset according to regional grid connection requirements. To support simultaneous operation of the inverter and a generator, the inverter extends its voltage and frequency operating
range once it receives a signal that the grid is unavailable (“Alternative Power Source
mode”). When the grid power is restored, the inverter automatically reverts to its
default country setting, which includes the original voltage and frequency operating
range.
A diesel generator (DG), specifically, requires a minimum production value in order to
maintain healthy operation. When a DG runs in parallel with a PV inverter, and the solar power generated is similar to the power consumed by the site, the DG might not carry
enough load to reach its minimum recommended production value. In a worst case scenario, a reverse power flow may occur, tripping generator protections, and causing a
site outage, or possibly damaging the generator.
To prevent such a scenario, while maintaining the benefits of a PV inverter installation,
the SolarEdge Power Plant Controller (PPC) can be used to dynamically limit solar production in order to ensure a minimum required power supply from the DG. This
capability, known as Alternative Power Source (APS) Controller, also protects the DG in the event of an extreme load drop. This allows the PV inverter to continuously maximize
power production without harming the other components in the system.
This document describes how to configure a PPC for use with SolarEdge inverters and
for simultaneous operation with a generator.
Managing an Alternative Power Source with a Power Plant Controller
6
NOTE
Due to the possibility of a loss of power for a second or more on the site during a state change, it is highly recommended to install a UPS and connect it to the PPC.

System Requirements

Alternative Power Source (APS) or Diesel Generation (DG) mode is supported by SolarEdge inverters as follows:
Inverters using SetApp: CPU version 4.8.xxx or higher
Inverters with display: CPU version 3.25xx or higher
To check the inverter’s CPU version, see Appendix A.
The generator must be able to support the entire load independently. The generator
must not work in parallel with the grid (either grid or generator supply the power). The generator connected to the PPC must have dry contact discrete outputs.
Managing an Alternative Power Source with a Power Plant Controller
7
Component connected to the PPC
Connection Method
Leader inverter
Modbus/TCP
Consumption Meter
RS-485
Diesel Generator dry contacts
2 wire

System Overview

The PPC’s digital input is connected to the generator's dry contacts. When an outage occurs and the generator is started, the normally-open dry contact closes, and the PPC
signals the PV inverters to transition to DG mode. In DG mode, the PPC manages the inverters’ production levels - reading the consumption meter and tracking inverter
power production, calculating the current site load, and dynamically setting production limitation levels on the inverters.
The PPC is connected to the leader inverter via Modbus-TCP, while the leader inverter is connected to its follower inverters via RS485. The PPC receives meter consumption
meter readings via Modbus-RTU (Over RS-485). The following table and diagram summarize the connections.
Managing an Alternative Power Source with a Power Plant Controller
Table 1: PPC Connections
8
Figure 1: Single Generator with a Power Plant Controller
Managing an Alternative Power Source with a Power Plant Controller
9
Figure 2: System Flowchart
Managing an Alternative Power Source with a Power Plant Controller
10

Installing and Configuring the System

Installation and Configuration

Figure 3: Power Plant Controller
Managing an Alternative Power Source with a Power Plant Controller
To install and configure the system:
1. Connect the generator to the PPC dry contacts.
11
Figure 4: Connection Scheme with DG trigger to Power Plant Controller
Managing an Alternative Power Source with a Power Plant Controller
12
NOTE
Connect negative to negative (D- to B-), positive to positive (D+ to A+) and GND to G. When configuring the IOD Controller, refer to the left connector as /dev/ttyS1 and to the right connector as /dev/ttyS4 (as labelled in the figure above).
2. Setup the Consumption Meter next to the grid access point (see Error! Reference
ource not found. above). This solution is supported by SolarEdge Meter model WND-3Y-400-MB. Ensure that DIP switches 2 and 7 are in the ON (set to 1) position.
Figure 5: Consumption Meter
3. Connect the consumption meter directly to the PPC using an RS485 connection:
Figure 6: Meter to PPC RS485 Connection
Managing an Alternative Power Source with a Power Plant Controller
4. Connect the PPC to its power supply (included in the package).
Figure 7: PPC Power Supply Connector
5. Connect the PPC to the target network using a LAN cable.
13
Figure 8: PPC LAN Connection
6. Power on the PPC.
Following power-up of the PPC, if a DHCP service is active in the router of the target network, an IP address will be automatically allocated to the PPC within a few
seconds. In order to learn the automatically assigned IP address, look at the router’s client
table or use an IP scanner. If these options are not available, refer to 0Appendix B – Debug Mode Configuration, which provides guidelines for connecting a debug
cable to the PPC.
Managing an Alternative Power Source with a Power Plant Controller
14
7. Use your browser to connect to the PPC configuration software.
The default credentials are:
User: Admin
Password: password
It is recommend to change the password following login.
8. Click on SYSTEM in the sidebar menu. Configure the required network details and
timezone.
Managing an Alternative Power Source with a Power Plant Controller

APS (Alternative Power Source) Configuration

To configure APS:
1. Click on APS CONTROLLER on the sidebar menu. The APS Controller page
appears as shown in the figure below. The page is divided into 4 sections:
General Configuration: for general algorithm parameters
Meter Configuration: for meter connection configuration
Master Inverter Configuration: for Leader Inverter connection configuration
Process Management: For controlling process automatic start.
15
Figure 9: APS Controller Tab
2. Update the settings as required, and click on the Save button. The service MUST
be restarted manually to put the updates into effect (see the Error! Reference ource not found. section for guidelines on restarting the service).
The individual settings are described in the following sections.
Managing an Alternative Power Source with a Power Plant Controller
16
Parameter
Values
Description
Minimum Required Consumption
Float > 0
[Watts]
The minimum consumption required for applying the algorithm. If the meter reads a value under this threshold, the site will be limited to 0 percent production.
Minimum Required Power from DG
Float > 0
[Watts]
The minimum power required by the generator to operate normally. The controller will use the input from the consumption meter to limit the solar system in order to hold this minimum value.
Total Inverter Nominal Production
Float > 0
[Watts]
The sum of each inverter’s nominal power (therefore
the total power of the plant) in Watts.
CT AMPS
Integer
0 - 3000
Register AC Power on Follower Inverter #2 (#1 is the Leader Inverter)
Parameter
Values
Description
Modbus Device Id
Integer 1-255
The meter device id (Default is 2)
Serial Port
A drop-down menu to choose one of the 2 serial ports on the controller
Meter Location
If the meter is connected on the load side and is always powered on, choose After ATS.
If the meter is connected on the generator side and is powered on only when the generator is working choose “DG supply only”.

General Configuration

This section is used for configuration of the basic algorithm parameters.

Meter Configuration

Managing an Alternative Power Source with a Power Plant Controller
17

Leader Inverter Configuration

The Leader Inverter should be only configured with an IP Address, TCP Port and Modbus Device ID. If there are follower inverters connected to it, they can be added by clicking on the Add Follower button. The Name is only a mnemonic identifier, the Modbus Device ID represents the follower’s identifier on Modbus (and is mandatory).
Managing an Alternative Power Source with a Power Plant Controller
18

Supervisor Tab

This tab is used for controlling the services running on the controller in real time.
There are three services running on the controller:
APS – Contains the main logic for the APS solution. This service needs to be
restarted after a configuration change. By clicking on “Tail -f” you can see the operation in real time.
APSTelemetry – Used to feed the Professional services monitoring tab in the SolarEdge monitoring portal.
MsdcMonitor – Used for monitoring purposes by the Professional-Services team.
Managing an Alternative Power Source with a Power Plant Controller
19

Appendix A - Identifying the Inverter CPU Firmware Version

To check the inverter’s CPU firmware version, perform one of the
following actions:
For inverters using the SetApp mobile application: Select Commissioning Information. The information page, containing the CPU version, appears as shown below:
For devices with a display: Short press the LCD light button on the inverter
until the screen below is displayed.
I D : # # # # # # # # # #
D S P 1 / 2 : x . x x x x / x . x x x x
C P U : 0 0 0 3 . 2 4 6 7
C o u n t r y : X X X X X
Managing an Alternative Power Source with a Power Plant Controller
20

Appendix B – Debug Mode Configuration

To set the PPC to run in debug mode:
1. Connect the LAN cable and make sure that it is connected to the Internet over
TCP/IP.
Figure 10: PPC LAN Connection
1. Connect a serial cable to the PPC’s DEBUG port.
Figure 11: PPC Serial Connection
Managing an Alternative Power Source with a Power Plant Controller
NOTE
The serial/debug cable must have communications (and not just charging) capabilities.
2. Open the Device Manager and locate the serial port being used:
21
Figure 12: Device Manager Tree
Managing an Alternative Power Source with a Power Plant Controller
22
3. Open the PuTTY tool’s configuration window (on MS-Windows). Serial line
should be set to the serial port displayed in the Device Manager. The connection speed should be set to 115200.
Figure 13: Setting Terminal Bit Rate
4. Connect the serial cable to a laptop. Open a terminal session on the serial
port displayed in the Device Manager, as shown above.
Managing an Alternative Power Source with a Power Plant Controller
23
5. Login using the following credentials:
User: Installer Password: PSinstaller
Figure 14: Open a Terminal Session
6. The PPC’s IP address was assigned using DHCP, get the address by entering in
the terminal:
ifconfig <Enter>
The address can be found in the eth0 section of the reply.
Figure 15: Finding the IP Address
Managing an Alternative Power Source with a Power Plant Controller
24

Supported Standards

Directive 2004/108/CE Electromagnetic Compatibility
Low Voltage Directive 2006/95/CE for electrical equipment (voltage between
50-1000VAC 75-15000VDC)
Restriction of Hazardous Substances Directive 2002/95/EC
Waste Electrical & Electronic Equipment (WEEE) Directive 2012/19/CE
EMI Standards EN 55022; EN 55024
Safety Requirement EN 61010-1
Managing an Alternative Power Source with a Power Plant Controller

Support Contact Information

If you have technical problems concerning SolarEdge products, please contact us:
https://www.solaredge.com/service/support
Before contact, make sure to have the following information at hand:
Model and serial number of the product in question.
The error indicated on the product SetApp mobile application LCD screen or
on the monitoring platform or by the LEDs, if there is such an indication.
System configuration information, including the type and number of modules
connected and the number and length of strings.
The communication method to the SolarEdge server, if the site is connected.
{color red}{color red}The product's software version as it appears in the ID status screen.
25
Managing an Alternative Power Source with a Power Plant Controller
26
Managing an Alternative Power Source with a Power Plant Controller
Loading...