CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified kit is used.
“Zero Clearance”
Direct Vent Gas Fireplace
ANZI Z21.88b-2008, CSA2.33b-2008, CGA 2.17-M91
Read this complete manual before beginning installation.
These instructions must be kept with the unit for future reference.
FOR YOUR SAFETY
WARNING: If the information in these instructions are not followed exactly, a fire
or explosion may result causing property damage, personal injury or loss of life.
Warning: Improper installation, adjustment, alteration, service or maintenance
can cause property damage, personal injury or loss of life. Refer to this manual.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
What To Do If You Smell Gas
Do not try to light any appliance.
Extinguish any open flame.
Do not touch any electrical switch.
Do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone.
If you can not reach your gas supplier, call the fire department.
For Propane Horizontal installations the venting must be a minimum of one foot vertical
off the flue before going horizontal.
It is normal for your fireplace to give off some odour. This is due to the curing of the paint, adhesives,
silicones and any undetected oil from the manufacturing process as well as the finishing materials used
with the installations (e.g. marble, tile and the adhesives used to adhere this product to the walls can
react with heat and cause odours).
It is recommended that you burn your gas fireplace or stove for a minimum of four hours at a time with
the fan off after the curing of the paint has been completed. These odours can last upward to 40 hours
of burn time, keep burning at a minimum of four hours per use until odours dissipate.
About curing of the paint
Your stove or fireplace has been painted with the highest quality silicone stove paint. This paint dries
quickly in 15-20 minutes when first applied at the factory. However, due to the high temperature silicone components, the paint will cure when heat is applied to the appliance as it is first used.
The following information applies to the curing process to get the paint fully hard and durable.
Fire the appliance four successive times for 10 minutes each firing and a 5 minute cool down between
each. Be aware during log and firebox paint curing that a white deposit may be developing on the
inside of the glass doors. It is important to remove this white deposit from the glass doors with an
appropriate cleaner to prevent build-up (such as Windex or a commercial fireplace glass cleaner).
• Babies, small children, pregnant women and pets should leave the area during the cure phase.
• Ventilate well, open doors and windows.
• Do not touch during curing.
Noise coming from the fireplace?
• Noise caused by metal expanding and contracting as it heats up and cools down, similar to the
sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of your fireplace.
• Different types and thicknesses of steel will expand and contract at different rates resulting in
“cracking” and “ticking” sounds throughout the heating and cooling periods.
• You should also be aware that as temperatures change within the unit these sounds will likely reoccur. Again this is normal for steel fireboxes, and is not a defect.
Cleaning the Glass
During the first few fires, a white film may develop on the glass front, as part of the curing process.
The glass should be cleaned after the unit has cooled down or the film can bake on and become very
difficult to remove. Use a non-abrasive cleaner and do not attempt to clean the glass while it is hot.
This Direct Vent System Appliance must be installed in accordance with the manufacturer’s installation instructions and the
Manufactured Home Construction and Safety Standard Title 24 CFR, Part 3280, or the current Standard for Fire Safety Criteria for
Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240 MH Mobile Home Standard
in Canada.
THE MQZDV3318, MQZDV3318LP, MQZDV3622N and MQZDV3622LP MAY BE INSTALLED IN MANUFACTURED
(MOBILE) HOMES AFTER FIRST SALE IN THE USA. IN CANADA THE MQZDV3318, MQZDV3318LP, MQZDV3622N
and MQZDV3622LP MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES.
Please follow the current ANSI/NFPA 70 National Electrical Code in the USA and CAN/CSA C22.1 Canadian National Electrical Code
in Canada.
An appliance must be grounded to the steel chassis of the home with 8 ga. copper wire using a serrated or star washer to penetrate paint
or protective coating to insure grounding.
Use carriage bolt at the attachment point (see diagram above) to secure the appliance to the floor.
Warning: Do not compromise the structural integrity of the manufactured home wall, floor or ceiling, during
installation of appliance or venting.
For required venting components see venting installation in appropriate section of this manual.
Certified for installation in a bedroom or bed/sitting room. In Canada must be installed with listed milli volt thermostat. In USA
see local codes.
4
Installation and Operation
Installation Regulations
This gas appliance must be installed by a qualified installer
in accordance with local building codes, or in the absence of
local codes, with the current CAN/CGA-B149.1 or .2
Installation Code (in Canada) or the current National Fuel
Gas Code Z223.1 when installed in the United States.
This appliance, when installed, must be electrically connected and grounded in accordance with local codes, or in the
absence of local codes, with the current CSA C22.1
Canadian Electrical Code or with the national Electrical
Code; ANSI/NFPA 70-1987 when installed in the United
States.
Vertical Venting in Cold Climates
In cold climate conditions where temperatures go
below -10 degrees Celsius or 14 degrees
Fahrenheit, we recommend that the chase be insulated and where the vent pipe enters into the attic
space that the pipe be wrapped with an insulated
mylar sleeve. This will increase the temperature of
the vent and help the appliance to vent properly in
cold weather conditions.
It is also important in vertical vented direct vent
appliances that the appliance be operated daily during the winter months as this will help stop the
Termination from freezing up. We recommend
using a thermostat set at room temperature to allow
the unit to cycle.
FOR SAFE INSTALLATION AND OPERATION OF
YOUR GAS FIREPLACE PLEASE NOTE THE FOLLOWING:
1. This appliance gives off high temperatures and should be
located out of heavy traffic areas and away from furniture and draperies.
2. Children and adults should be alerted to the hazards of
the high surface temperatures of this appliance and
should stay away to avoid burns or ignition of clothing.
3. Children should be carefully supervised when they are in
the same room as your fireplace appliance.
4. Under no circumstances should this appliance be modified. Any parts that have to be removed for servicing
should be replaced prior to operating this appliance.
5. Installation and repair should be done by a qualified service person. The appliance should be inspected before
use and at least annually by a professional service person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etcetera.
It is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
6. Control compartments, burners and air passages in this
appliance should be kept clean and free of dust and lint.
Make sure that the gas valve and pilot light are turned off
before you attempt to clean this unit.
7. The venting system (chimney) of this appliance should
be inspected at least once a year and if needed, your venting system should be cleaned.
8. Clothing or other flammable material should not be
placed on or near the appliance. This appliance should
not be used as a drying rack for clothing nor should
Christmas stockings or decorations be hung from it.
9. Under no circumstances should any solid fuels (wood,
paper) be used in this appliance.
10. For safe operation, glass doors must be closed.
11. Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect
the heater and to replace any part of the control system
and any gas control which has been under water.
12. WARNING: Do not operate appliance with the glass
front removed, cracked or broken. Replacement of glass
should be done by a licensed or qualified service person.
13. Do not operate appliance unless completely installed as
per installation instructions.
14. In the Commonwealth of Massachusetts a CO detector
must be installed in the same room as the appliance.
15. Gas fired appliances may be used only for supplemental
heat and/or decorative purposes and under no circumstances shall they provide a primary heat source.
NOTE: It is recommended that a Carbon Monoxide (CO)
Detector be installed in or near bedrooms and on all levels
of your home. Place a detector about 15 feet (4.5 meters)
outside the room that houses your gas appliance.
Warning: When purging the gas line, the glass front must be
removed.
Never use your gas fireplace as a cooking device.
The Burner/Log Assembly has been engineered and permanently adjusted for proper flame control.
Do not alter gas orifice.
Periodically remove the logs from the grate assembly and
vacuum any loose particles from the grate and burner areas.
See log/rock placement on pages 36-40 to remove logs, vacuum burner parts and replace logs.
Note: It is normal for your gas fireplace to give off some
odor the first time it is burned. This is due to the curing of
the paint and any undetected oil from the manufacturing
process.
Please ensure that your room is well ventilated - open all
windows. It is recommended that you burn your gas fireplace for at least four (4) hours the first time you use it
without the fan on.
Make adequate accessibility clearances for servicing and
proper operation.
This appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance.
Be sure that the flow of combustion and ventilation air is not
obstructed.
5
Installation Requirements for the Commonwealth of Massachusetts
In the Commonwealth of Massachusetts, the installer or service agent shall be a plumber or gas fitter licensed by the
Commonwealth.
When installed in the Commonwealth of Massachusetts or where applicable codes; the unit shall be installed with a CO detector
per the requirements listed below.
1. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the
vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:
A If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm shall be placed in the
living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
B. A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall:
a. Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the appliance and
the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI./UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
d. Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR.
C. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict
compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the
completion of the installation.
D. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The
plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air
intake is installed above four feet above grade the following requirements must be satisfied:
A If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm shall be placed in the
living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
B. A carbon monoxide detector shall:
a. Be located in the room that houses the appliance or equipment;
b. Be either hard-wired or battery powered or both; and
c. Shall comply with NFPA 720 (2005 Edition).
C. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict
compliance with the manufacturer instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
6
Installing with Top Vent
MQZDV3318 - Locating your Appliance
A - Flat on a wallD - As a room divider
B - Across the cornerE - Flat on wall corner
C - As an islandF - Exterior wall
Island installation with a top vent is possible as long as the horizontal portion of the vent system does not exceed 20 feet (6.1 m).
MQZDV3318 Fireplace Dimensions
MQZDV3318 louvered
MQZDV3318 -CVCK (Clean View Circulating Kit)
7
MQZDV3318 - Framing for your Gas Fireplace
Framing Specifications
1. Cold climate installation recommendation: When installing this fire-
place against non insulated exterior wall or chase, it is recom mended that the outer walls be insulated to conform to applicable
insulation codes. Drywall must be installed over insulation to
prevent contact of insulation and unit.
2. Choose fireplace location and frame in accordance with the fire-
place framing dimensions specified (See Framing Diagrams). Bend
nailing tabs forward on left and right of unit and place fireplace into
framed enclosure. This allows for 1/2” in front of framing tabs for
finishing materials.
3. Drywall or other material can extend flush with the appliance on the
bottom, sides and top of fireplace. (louvered models only)
For Propane Horizontal Installations the venting must be a minimum of one foot vertical off the flue before the elbow on any
horizontal runs of one foot or greater. This allows for cleaner combustion and greatly reduces carboning and cleaning of glass.
4. When installing horizontal with a 90 degree bend maintain a minimum of two and a half (2.5”) inches above the bend in enclosures.
5.
For a fireplace with louvers combustible floor can raise 1”
above the bottom of the fireplace. For a fireplace with
33CVCK (Clean view Circulating Kit) floor or hearth can
raise 7” above the bottom of the fireplace with portions
being combustible and non combustible. See drawing on following page.
6. When installing MQSWF surround, the fireplace must be
raised a minimum of 2 7/8” above the finished floors, to
accommodate the wall surround. The fireplace may be raised
higher but the 60” clearance measured from the bottom of
the fireplace to the ceiling must be maintained at all times.
(i.e. For an 8 ft. ceiling the unit can be raised only 36 inches.)
MQZDV3318 Louvered
MQZDV3318 WITH CVCK (CLEAN VIEW CIRCULATING KIT)
8
Z33CVCK - Framing and Facing Requirements
MQZDV3318 WITH Z33CVCK (CLEAN VIEW CIRCULATING KIT)
Z33CVCK - with Wall Surround
9
Installing with Top Vent
MQZDV3622 - Locating your Appliance
A - Flat on a wallD - As a room divider
B - Across the cornerE - Flat on wall corner
C - As an islandF - Exterior wall
Island installation with a top vent is possible as long as the horizontal portion of the vent system does not exceed 20 feet (6.1 m).
MQZDV 3622 Fireplace Dimensions
MQZDV3622 louvered
MQZDV3622 -CVCK (Clean View Circulating Kit)
10
MQZDV3622 - Framing for your Gas Fireplace
Framing Specifications
1. Cold climate installation recommendation: When installing this fireplace against non insulated exterior wall or chase, it is recom mended that the outer walls be insulated to conform to applicable
insulation codes. Drywall must be installed over insulation to
prevent contact of insulation and unit.
2. Choose fireplace location and frame in accordance with the fireplace framing dimensions specified (See Framing Diagrams). Bend
nailing tabs forward on left and right of unit and place fireplace into
framed enclosure. This allows for 1/2” in front of framing tabs for
finishing materials.
3. Drywall or other material can extend flush with the appliance on the
bottom, sides and top of fireplace. (louvered models only)
It is recommended for Propane Horizontal Installations that the venting should be a minimum of one foot vertical off the flue
before the elbow on any horizontal runs of one foot or greater. This allows for cleaner combustion and greatly reduces carboning and cleaning of glass.
MQZDV3622 Louvered
4. When installing horizontal with a 90 degree bend maintain a minimum of two and a half (2.5”) inches above the bend in enclosures.
5.
For a fireplace with louvers combustible floor can raise 1”
above the bottom of the fireplace. For a fireplace with
36CVCK (Clean view Circulating Kit) floor or hearth can
raise 7” above the bottom of the fireplace with portions
being combustible and non combustible. See drawing on following page.
6. When installing MQ36SWF surround, the fireplace must be
raised a minimum of 2 1/2” above the finished floors, to
accommodate the wall surround. The fireplace may be raised
higher but the 60” clearance measured from the bottom of
the fireplace to the ceiling must be maintained at all times.
(i.e. For an 8 ft. ceiling the unit can be raised only 36 inches.)
MQZDV3622 WITH CVCK (CLEAN VIEW CIRCULATING KIT)
11
Z36CVCK - Framing and Facing Requirements
MQZDV3622 WITH Z36CVCK (CLEAN VIEW CIRCULATING KIT)
Z36CVCK - with Wall Surround
12
MQZDV3318/ZDV3622 -
Installing Clean View Kit (CVCK)
For ZDV3318/ZDV3622/ZDV6000/ZDV3320/MQZDV3318/MQZDV3622
1.Install optional fan kit (See Fan Instructions)
2.(a)All styles except ZDV6000 & ZDV3320. Make sure small standoff is folded up and fastened into position. If not fold standoff
up into position and fasten with supplied screws. (Fig 1)
(b) For ZDV6000 & ZDV3320 only. Fold eight inch standoff up into position and install with supplied screws. Do not remove
small standoff. The eight inch standoff will fit over the top of the small standoff. (Fig 1)
3.For ZDV6000 & ZDV3320 only. All others skip to Step 4.
Using screws provided, fasten the non-combustible header onto the top of CVCK assembly.
4.Hang CVCK onto top of fireplace retainer tabs and rotate into position. (Fig 2)
5.Using [4] supplied #6 screws, fasten CVCK kit to the inside frame of unit.
Note:Holes are pre-punched into side frame of unit, one hole at the top and one at the bottom.
6.Using [10] supplied screws, install the top heat shield to the top inner side of CVCK. (Fig 3 )
Note:It will be easier to install leading edge screws first and side screws last. Some pressure will be required when installing
side screws to push top edge up into unit.
7.Kit is supplied with 2 valve extension knob. Align the notches and slide extension knobs onto valve knobs.
8.DO NOT brick or tile beyond the inside area of the CVCK kit to allow for removal of door
HOW TO INSTALL CLEAN VIEW KIT (CVCK)
13
CLEARANCES - MQZDV3318/3622 - Mantels & Surrounds
Warning: Combustible objects must not be placed on a non-combustible mantel unless the non-combustible mantel meets the
minimum height and width require ments for a combustible mantel.
14
Mantel Leg Clearances
Mantels
Depending on the depth of the fireplace mantel, it may be installed higher or lower from the top of the fireplace opening. See drawings
for proper installation height of your combustible mantel. Non-combustible mantels may be installed at any height above the fireplace
opening except when using MQHBSW.
Non combustible materials such as brick, tile, etc. can extend up to or over the front face of the fireplace (NO PORTION OF GRILL
AREA OR DOOR AREAS CAN BE COVERED) except where designer clean view kit is used.
Combustible material can extend flush to unit up to the top, bottom and sides of fireplace to stand-offs.
For COMBUSTIBLE materials extending in front of fireplace consult (Mantel and Mantel Leg Drawings).
Surrounds
If installing wide or slim line surrounds, the finish materials must be flush with the front facing of the fireplace.
Note: When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant (250˚F) to prevent
discoloration.
15
MQZDV3318 - Clearance to Combustibles
Clearance to Combustibles
Back (from Standoffs)0 inches/0 mm
Side (from standoffs)0 inches/0 mm
Floor0 inches/0 mm
Ceiling (from bottom of fireplace)60 inches/150 cm
Top (from standoffs)0 inches/0 mm
Louvered Unit
Top of 90 degree bend in Minimum
Enclosure of 37.75 to 40 inches3 1/4 inches/140 mm / All Vent Systems
Enclosure over 40 inches2 1/2 inches/38mm/All Vent Systems
CVCK Unit (non louvered)
Top of 90 degree bend in Minimum
Enclosure of 40.5inches to 43 inches5 inches/38 mm / All Vent Systems
Enclosure over 43inches2 1/2 inches/38mm All vent Systems
Top of Horizontal Pipe1 1/2 inches/38 mm / All Vent Systems
Side & Bottom of Horizontal Pipe1 inch/25.5mm / All Vent Systems
Vertical Vent Pipe1 inch/25.5mm / Kingsman Vent Systems
Vertical Vent Pipe1 1/4 inch/32mm / Simpson/AmeriVent/Selkirk Direct Temp
Systems
MQZDV3622 - Clearance to Combustibles
(NOTE -Floor) if installing the
appliance directly on carpeting or
other combustible materials other
than wood flooring, the appliance
shall be installed on a metal or
wood panel, the full width and
depth of the appliance. Carpet
may extend 1 inch above the
floor of appliance.
For units with CVCK (Clear
View Circulating Kit) see
framing with CVCK to establish
floor heights
Clearance to Combustibles
Back (from Standoffs)0 inches/0 mm
Side (from standoffs)0 inches/0 mm
Floor0 inches/0 mm
Ceiling (from bottom of fireplace)60 inches/150 cm
Top (from standoffs)0 inches/0 mm
Louvered Unit
Top of 90 degree bend in Minimum
Enclosure of 42 to 46 inches5 1/2 inches/140 mm / All Vent Systems
Enclosure over 46 inches2 1/2 inches/38mm/All Vent Systems
CVCK Unit (non louvered)
Top of 90 degree bend in Minimum
Enclosure of 44.5inches to 48.5 inches 5 inches/38 mm / All Vent Systems
Enclosure over 48.5inches2 1/2 inches/38mm All vent Systems
Top of Horizontal Pipe1 1/2 inches/38 mm / All Vent Systems
Side & Bottom of Horizontal Pipe1 inch/25.5mm / All Vent Systems
Vertical Vent Pipe1 inch/25.5mm / Kingsman Vent Systems
Vertical Vent Pipe1 1/4 inch/32mm / Simpson/AmeriVent/Selkirk Direct Temp
Systems
(NOTE -Floor) if installing the
appliance directly on carpeting or
other combustible materials other
than wood flooring, the appliance
shall be installed on a metal or
wood panel, the full width and
depth of the appliance. Carpet
may extend 1 inch above the
floor of appliance.
For units with CVCK (Clear
View Circulating Kit) see
framing with CVCK to establish
floor heights
16
MQSW Wall Mount Surround Dimensions
MQ36SWF
A
35-5/16” 37-5/32”
B
45-13/16” 50-5/16”
C
28-3/8” 32-15/16”
D
17-13/16” 19-5/8”
E
8-3/4” 8-3/4”
F
8-3/4” 8-3/4”
G
8-3/4” 8-3/4”
H
1” 1”
I
1-3/16” 1-3/16”
1. Set Surround Lip on CVCK Ledge and ensure that it is securely in place.
2. Swing the upper portion of the Surround so that the Surround Ledge is resting on top of the
CVCK Deflector Lip.
3. Align the Mounting Screw Holes and fasten the Surround in place with the supplied screws.
4. Attach optional decorative bands as desire.
5. To remove, simply reverse these steps.
MQ33SWF
Installation of MQ Wall Mount Surrounds
17
Fan Kit Installation
Fan installation Instructions for ZDV6000/3320/3318/3318MQ
with or without CVCK (Clean View Circulating Kit).
Note:
Install Fan Kit Before Installing optional CVCK (Clean
View Circulating Kit).
If CVCK has been installed into framing additional access is
provided by removing screws from bottom panel of CVCK. See Installing Clean View Kit (CVCK).
1. Slide fan housing into unit and place over 2 Fan Retainer Tabs. Tabs
are pre punched and bent up (*Note: on 6000/3320 units, these Tabs are located on the right side of the unit). Rubber grommets
at the base of the fan should fit snugly over the tabs.
2. For Fan Disc Installation these units have been installed with a sliding
track system. Install the Thermodisc provided with the Fan Kit. Place
Thermodisc into sliding assembly (Fig.1), and attach 2 leads exiting
right side of the fan housing into thermodisc. Now slide disc assembly
into thermodisc track (Fig.2). Place swivel handle of disc assembly
on track to lock into position. To service disc simply pull swivel handle
slide towards you while rotating handle to access disc.
Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerous operation.
Verify proper operation after servicing.
Parts List:
1ea. Fan comes with 4ft cord. Two 14” leads (female ends)
1ea. Variable speed control (wall mount type)
1ea. Thermodisc
1 Thermodisc mount assembly
CAUTION: DO NOT ATTACH 120V FAN ASSEMBLY TO MILLIVOLT GAS VALVE SYSTEM
3. Wire Junction Box and wall mounted variable speed control to
120v. Install a duplex outlet to junction box and plug fan into
outlet.
4. Turn the wall switch on (clockwise). Turn fireplace on. Once the
5. To set the minimum fan speed, remove the variable switch from
Electrical Services
All optional Fan Kits are equipped with a 120V, 60Hz, .4amp blower.
Note: All electric connections are to be made in accordance with
CSA Standard C22.1 – Canadian Electrical Code part I or with the
National Electrical Code, ANSI/NFPA 70 (latest edition) and /or in
accordance with local codes.
sensor in the unit reaches operating temperature (approximately
10 to 15 minutes) the fan will turn on. The fan can be switched
off if desired by turning the wall switch fully counter clockwise.
the wall mount. Turn the variable speed wall controller to its
minimum setting (fully counterclockwise). Use the set screw on
the side of the variable speed controller to increase or decrease
the minimum fan speed (lowering the minimum fan speed will
decrease sound level created by fan).
Reinstall switch into wall mount and cover with face plate.
Note:
To service fan with CVCK Kit installed see Removing
Burner System in manual. If CVCK is finished with a MQSW
Wall Surround the MQSW may be removed by removing the
4 attachment screws and removing the MQSW
allowing access into the bottom of the fireplace to service
blower.
Warning:
appliance is equipped with a three-pronged (grounding)
plug for your protection against shock hazard and
should be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the
grounding prong from this plug.
Electrical Grounding Instructions. This
18
for ZDV3318/3622 models only
for ZDV3318/3622
models only
Brick Installation - For Models MQZDV3318/MQZDV3622
1.Remove 3 mounting screws from air adjustment plate and remove plate.
If this is a ZDV3318 or ZDV3622 the false bottom will also have to be removed.
(Note: Air adjustment plate must be reinstalled in the same position in which it was removed.
2.Remove top brick clip and screws from firebox side. Screws will be reused for the installation of side Liner Panels. (Fig. 1)
3.Remove four side screws from the firebox bottom. There are two screws per side. Screws will be reused for the installation of side
Liner Panels. (Fig. 1)
4Place rear Liner Panel against back of firebox. When placing Panel tilt panel towards you and lift panel over the burner assembly. (Fig. 2)
5.To place side Liner Panels rotate panel towards you and place bottom edge of panel over the front ledge of firebox. (Fig. 3) Rotate
panel upright and slide back up to face of rear Liner Panel. Make sure top of side Liner Panel is engaged with top of rear Liner
Panel. (Fig 4 - Detail: A) To finish the installation fasten bottom of side Liner Panel with screws removed in step 3 and fasten top
of side Liner Panel with screws removed in step 2.
6.Using screws removed in step 1 reinstall air adjustment plate and false bottom.
(Note: If air adjustment plate was required to be installed in the up position it is not required to reinstall the air adjustment plate.
Not installing the air adjustment plate will leave mor of the rear Liner Panel exposed for a more finished appearance.
1.Make note of the position of the air adjustment plate before removing it. This position will have to be recalled when the air
adjustment plate is reinstalled.
2.Remove three (3) mounting screws from air adjustment plate and extract it from the firebox. (NOTE: The false bottom will have to
be removed on models ZDV3318 and ZDV3622.)
3.Remove the top brick clips, and their respective screws, from the inside sides of the firebox. These removed screws will be reused
for installation of the side liner panels.
4.Place the rear liner panel against the back of the firebox. When placing the panel, tilt it towards you while lifting it over the burner
assembly,
5.To place the side liner panels, rotate it towards you while placing the bottom edge over the front ledge of the firebox, Then, rotate
the panel upright and slide it back towards the rear liner panel. Make sure the top of the side panel is engaged with the top of the
rear panel as shown in the illustration below. Once all the liner panels are installed, ensure they are sitting flush to the walls of the
firebox.
6.Reinstall the air adjustment plate back to its original position. (NOTE: Only for instances where the adjustment plate is in the
extreme up position, it is not necessary to reinstall the plate. One may prefer not to install the plate for a more finished
appearance.)
7.If applicable, reinstall the false bottom.
20
General Glass Information
Glass Cleaning
It will be necessary to clean the glass periodically. During start-up, condensation, which is normal, forms on the inside of the glass and causes
dust, lint etc. to cling to the glass surface. Also, initial paint curing can
deposit a slight film on the glass. It is therefore recommended that initially the glass be cleaned two or three times with non-abrasive
mon household glass cleansers and warm water. After that, the glass
should be cleaned two or three times a season depending on the circumstances.
com-
Cautions and Warnings
• Do not clean when the glass is hot.
• The use of substitute glass will void all product warranties.
• Care must be taken to avoid breakage of the glass.
• Do not operate this fireplace without the glass front or with a broken
glass front.
• Do not strike or abuse glass.
Glass Replacement
The glass should be replaced by a qualified person.
REPLACEMENT GLASS FOR BOTH DIRECT VENT UNITS
These models can use either tempered glass or Robax ceramic or coated Neaoceram glass. Must be 5mm thick.
To replace glass, clean all materials from door frame. Scrape off old
silicone down to metal. Using a high heat silicone (temperature-resistant to 500°F (260°C) apply a continuous bead of approximately 1/32”
to all four sides of frame and insert glass with new gasket. Frame
should be on flat surface, with a small amount of weight pressing glass
into silicone. Let dry approximately 15 to 20 minutes. The door can be
re-installed by reversing Steps 1 & 2. Use caution when removing broken glass, wear gloves.
Removal of the Glass Door
1. Unlatch the two latches located behind the upper grill.
2. To remove, pull frame forward and lift from bottom door retainer.
Gas Line Installation
This gas appliance should be installed by a qualified installer in accordance with
local building codes and with current CAN/CGA - B149.1 or .2 installation codes for
Gas Burning appliances and equipment in Canada and the National Fuel Gas Code
ANSI Z223 in the U.S.A.
1. The gas pipeline can be brought in through either the right or the left side of the
appliance. A knockout is provided at either location to allow for the gas pipe
installation and testing of any gas connection.
2. The gas control inlet is 3/8” NPT. Typical installation layout for rigid pipe is
shown at right.
3. When using copper or flex connector, use only approved fittings. Always pro-
vide a union so that gas line can be easily disconnected for burner or fan servicing. See gas specification for pressure details and ratings.
4. When a vertical section of gas pipe is required for the installation, a condensation trap is needed. See CAN/CGA-B149.1 or .2 for code details.
5. For natural gas, a minimum of 3/8” iron pipe with gas minimum pressure of 4.5”
w.c. must be used for supply from the gas meter. Consult with the local gas utility if any questions arise concerning pipe sizes.
6. A 1/8” NPT plugged tappings are accessible for test gauge connection both on the
inlet and outlet of the gas valve.
7. Turn the gas supply ON and check for
leaks. DO NOT USE OPEN FLAME FOR
THIS PURPOSE. Use an approved leak
testing solution.
8. The appliance and its individual shutoff
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 PSIG (3.5 KPa).
9. The appliance must be isolated from the
gas supply piping system by closing its
individual shutoff valve during any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2
PSIG (3.5 KPa).
Gas Specifications
ModelsMQZDV3318NMQZDV3318LPMQZDV3622NMQZDV3622LP
FuelNaturalPropaneNaturalPropane
Gas ControlMillivolt adjustableMillivolt adjustableMillivolt adjustableMillivolt adjustable
Air Shutter3/16” Open9/32” Open3/16” Open3/8” Open
Gas Inlet Size S.I.T. 820 Nova, 3/8” NPT
Gas Supply PressureMinimumNormalMaximum
Natural Gas5.5”7”9”
Liquid Propane11”11”12”
Manifold PressureNatural GasLiquid Propane
Manifold Pressure High3.5 IN. W.C./.87 KPa10 IN. W.C./2.61 KPa
Manifold Pressure Low1.6 IN. W.C./.40 KPa6.3 IN. W.C./1.57 KPa
For the state of Massachusetts a T-handle gas shut-off valve must be used on a gas appliance.
This T-handle gas shut-off valve must be listed and approved by the state of Massachusetts.
This is in reference to the state of Massachusetts state code CMR238.
Note: The gas line connection may be made of 1/2” rigid pipe or an approved
flex connector. Since some municipalities have additional local codes, it is
always best to consult your local authorities and the current CAN/CGA - B149.1
or .2 installation code in Canada or the National Fuel Gas code ANSI Z223.1 in
the U.S.A.
Important: Always check for gas leaks with a soap and water
solution. Do not use open flame for leak testing.
21
Burner System Removal for MQZDV3318/3622
If fireplace has been installed with optional CVCK (Clean View Circulating Kit) to service fan system or burner system controls, the access cover and
burner system pan will have to be removed.
*CAUTION BEFORE STARTING REMOVAL OF PARTS TURN OFF GAS SUPPLY. DISCONNECT 110 VOLTS TO FAN SYSTEM
AND DISCONNECT 110 VOLTS TO ELECTRONIC IGNITION BURNER SYSTEM IF APPLICABLE
Access Cover Removal
1.Remove door, logs, brick panels, burner grate, rock platform and burner from firebox.
2.Burner grate or optional rock platform are fastened by 2 screws. There is one right and one left assembly Remove screws and take out grate or
rock platform.
3.Remove Log Support Plates right and left of burner, log support plates are loose and not fastened in place.
4.Loosen screws from burner retainer tabs and slide burner to the left to remove from orifice.
5.Remove 10 screws holding access cover in place. Push down on one corner of access cover to break seal of cover. Once loose cover can be slid
under firebox bottom to expose gas connection.
*CAUTION ALL WORK SHOULD BE PERFORMED BY A QUALIFIED AND CERTIFIED TECHNICIAN
Removing Burner System
1.Complete all steps in Access Cover Removal Instructions.
2.Disconnect gas line connection at burner system through access cover opening.
3Remove extension knobs and wiring from face of gas valve.
4.Remove screws from perimeter of burner system pan. Lift pan at one back corner and rotate pan up from back of firebox. Make sure, when tilting up and removing burner system that all fan and valve control wiring is disconnected at this time.
To re-install access cover/burner system. Remove old Mil Pac sealant and apply new sealant. After new sealant is applied, reverse removal procedure to re-install parts.
*Caution high temperature sealant has been applied to access cover and burner system pan. New sealant will have to be applied when reinstalling access cover and burner system to maintain the integrity of the sealed combustion chamber. Mil Pac part #840099 or Kingsman
part # 100-15MP sealant can be purchased from your Kingsman retailer or distributor.
MQZDV3318 /3622 Fireplace
MQZDV3318 /3622 Burner System
22
Millivolt System, Lighting, & Burner Control
Recommended Maximum Lead Length (Double
Wire) When Using Wall Switch or Thermostat
Wire SizeMax. Length
14 GA.100 FT.
16 GA.64 FT.
18 GA.40 FT.
20 GA.25 FT.
22 GA.16 FT.
Pilot Burner
Adjustment
1. Adjust pilot screw to provide
proper sized flame.
Caution: Do Not Wire
120 Volt Power To
Millivolt Switches Or
Thermostats.
23
Gas Conversion - MQZDV3318 and MQZDV3622
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable
codes and requirements of the authority have jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion or
production of cabon monoxide may result, causing probperty damage, persoanl injury or loss of life. The qualified service agency is respon-
sible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is
checked as specified in the manufacturer’s instructions supplied with kit.
1.Remove Grate Bar assembly or optional Rock Platform by removing the two mounting screws, one from each side.
2.Remove Log Support Plates right and left of burner, log support plates are loose and not fastended in place.
3Loosen screws from burner retainer tabs and slide burner to the left to remove tfrom orifice.
4Remove main orifice using a 1.2” wrench and replace with new conversion orifice.
5Install new pilot orifice and Hi/Low valve regulator by following instructions uspplied with conversion kit.
6.Adjust the primary air setting to the correct setting as specified in the manual or label plate. To adjust air setting. Loosen screw on the side of air
mixing tube and rotate to the correct opening using a dirll bit or tape measure. Tighten screw.
7.After converting parts to the new type of gas, reverse all step’s to reassemble burner system.
24
Section B - Installation Instructions
Gas Conversion Kit for Top Convertible Pilot - Series 091065X
Instructions for converting SIT 190 series pilot burner injection from NG to LPG and from NG to LPG Only.
This information should be considered as supplemental to the Appliance Manufacturer’s Instructions.
WARNING!
The installation of this conversion kit must only be undertaken by a qualified and certified gas appliance installer.
1Shut off the gas supply to the appliance.
2Allow the pilot burner to cool to room temperature.
WARNING: Touching a hot pilot burner can result in injury.
3The pilot hood is held in place by spring pressure.
Remove the hood by pulling it directly up from the pilot bracket (1).
4Insert a 5/32” or 4mm Allen wrench into the hexagonal key-way of the
injector (2), and rotate it counter clockwise until it is free of the injector journal (3).
5Verify that the new injector is proper for the application. The injector
size is stamped on the side of the injector near the top. LPG injectors
have a groove machined around their circumference near the top,
while NG injectors do not have a groove (5).
Refer to the Appliance Manufacturers instruction sheet for the proper
injector size.
6Insert the Allen wrench into the end of the injector. Then, insert into
injector journal, and rotate the injector clockwise until a torque of 9 inlbs. is achieved.
7Replace the pilot hood by aligning the tab on the base of the hood with
the slot in the side of the pilot journal, and push the hood down, directly onto the pilot bracket (4). The hood must sit squarely on the bracket
for proper operation. Check to insure that the hood is properly seated
onto the pilot bracket.
WARNING!
This conversion kit must only be applied as part of a conversion kit supplied by the appliance Manufacturer for
the specific appliance, and type of gas being converted.
INSTALLER NOTICE. These instructions must be left with appliance.
SIT Group
25
Trouble Shooting The Gas Control System
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE THE GLASS FRONT.
NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the “On” position.
ProblemPossible CausesCorrective Action
Spark igniter will not light.Defective or misalignedCheck for spark at electrode and pilot: if no spark and electrode
electrode at pilot.wire is properly connected, replace igniter.
Defective igniterUsing a match, light pilot. If pilot lights, turn off pilot and push
(push-button)the red button again. If pilot will not light - check gap at elec-
trode and pilot should be 1/8” to 1/4” to have a strong spark.
Pilot will not stay lit after Defective thermocoupleCheck pilot flame. Must impinge on generator and thermocarefully following lighting(flame switch where applicable)couple. Clean and/or adjust pilot for maximum flame impingeinstructions.ment on generator and thermocouple. Replace thermocouple if
pilot will not hold. (Hand tight 1/8 turn on replacement)
Defective valve magnet.Replace valve, if pilot won’t hold after the thermocouple is
replaced.
Pilot burning, no gas to burner,Wall switch or wiresCheck wall switch and wires for proper connections. Jumper
Valve knob “ON”, Walldefectivewire across terminals at wall switch. If burner comes on, replace
Switch “ON”.defective wall switch. If okay, jumper wires, across wall switch
wires at valve. If burner comes on, wires are faulty or connections are bad.
Generator may not be generating Check generator with millivolt meter. Take reading at generator
sufficient voltage.terminals of gas valve. Should read 325 millivolts minimum
while holding valve knob depressed in pilot position and wall
switch “off”. Replace faulty generator if reading is below speci-
fied minimum.
Plugged burner orifice.Check burner orifice for stoppage and remove.
Defective automatic valveRemove wall switch wires from gas valve. Install jumper wires
operator.from top bottom terminals of gas valve. Turn valve on “ON”.
If main burner does not light, replace valve.
Frequent Pilot outage problem.Pilot flame may be too low orClean and/or adjust pilot flame for maximum flame impinge-
blowing (high) causing the pilotment on generator and thermocouple.
safety to drop out.
Flame lifts off burner and goes Inner 4” liner has come off flueAttach 4” liner to flue or termination using screws, silicone and
out in less than 30 secondsor termination, flame is starvingclamps as stated in manual.
Flame lifts off burner onImproper installation of Be sure to position firebrick against firebox walls and be sure to
one side while the rest offirebrick. Firebrick is likely use brick clips attached to the inner side of firebox.
the flame remains lit.leaning.
for oxygen
26
MQLOGC22 for MQZDV3318/3622
Parts ListLava Rock
Vermiculite
Rock Wool
Logs, 1,2,3,4
STEP 1: Place Log #1 onto the rear burner pan sliding it left
until it stops against the right burner mount.
Location Points
Place glowing rock wool on burner as shown in step 1 being
sure to leave the multiple porting areas open. For Lp only, the
multiple porting areas can be completely covered.
Do not cover the Rear Porting areas with rock wool.
STEP 2: Align the 2 holes on the bottom of log #2 with the 2
log #2 placement tabs as shown.
STEP 3: Align the hole on the bottom of log #3 with the log #3
placement tab and the rest log #3 on log #2 as shown.
27
MQLOGC22 for MQZDV3318/3622
Step 4: Place Log #4 into place as shown. Do Not
place directly over top of the multiple porting area
on the left side.
Finished log set is displayed with optional VLBIT6
Step 5: Fill in the rest of the burner pan and ember
plates with lava rock and vermiculite. Do not place
lava rock or vermiculite on any of the burner ports.
Finished log setup
28
MQRSP5 for MQZDV3318/3622
MQRSP5 Parts List
1 eachMQRSP5 Rock Platform
1 eachLava Rock
1 eachVermiculite
Step 2: Place the MQRSP5 rock platform into position around
the burner as shown.
Step 1: Remove the grate bar by removing the 2 Screws
located on the left and right side of the grate bar as illustrated.
Remove the 2 ember plates once the grate bar is removed. The
2 screws removed must be re-installed once the grate bar is
removed.
Step 3: Using the left ember plate mounting bracket,
slide the left ember plate into position as shown.
Repeat the same for the right ember plate
Step 4: Place rocks #1 into position as shown.
Step 5: Place rocks #3 into position as shown.
29
MQRSP5 for MQZDV3318/3622
Step 6: Place rocks #6 into place as shown. Do not place
directly over the multiple porting areas.
Step 8: Place rock #3 and rock #1 into position as shown to
complete the setup. Lava rock and vermiculite are optional for
placement around the rock platform on the burner pan.
Step 7: Place rocks #4 into position as shown. Place the
highlighted rocks into position being sure that they are crossing
over the single line porting.
MQRSP5 finished setup and burn.
Note: If flame impingement on the rocks causes sooting,
you may have to move or remove one or more rocks. Do
not place rocks directly over top of the burner tube.
30
Vent Termination
V
Vent Terminal
Air Supply
Area Where Terminal Not Permitted.
A - Clearance above grade, veranda, porch, deck, or balcony 12
inches (30cm) minimum.
B - Clearance to window or door that may be opened. 12 inches (30cm)
minimum for appliances 100 000 Btuh (30 kW) and lower, in
Canada. 9 inches2(23cm) for appliances 50 000 Btuh and lower, in
USA.
C - Clearance to permanently closed window minimum 12 inches
(30cm) recommended to prevent condensation on window, in
Canada. 9 inches2(23cm) for appliances 50 000 Btuh and
lower, in USA.
D - Vertical clearance to ventilated soffit located above the termina-
tion within a horizontal distance of 2 feet (60cm) from the cen-
ter line of the termination. 18 inches (46cm) minimum.
E - Clearance to unventilated soffit 12 inches (30cm) minimum.
F - Clearance under veranda, porch, deck or balcony 12 inches
(30cm) minimum.4US
G - Clearance from a perpendicular inside wall or outer corner to
the edge of the vent terminal plate is 3” (minimum).
H - Clearance to each side of center line extended above
meter/regulator assembly 3 feet (91cm) within a height 15
feet (4.5m) above the meter/regulator assembly.
I - Clearance to service regulator vent outlet 3 feet (91cm) mini-
mum.1 US
J - Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance: In Canada, 6 inch-
es (15cm) for appliances ≤10,000 Btuh (3kW), 12 inches
(30cm) minimum for appliances >10,000 Btuh(3kW) and
≤100,000 Btuh (30kW), 36 inches (91cm) for appliances
>100,000 Btuh (30kW). In the USA, 6 inches2(15cm) for
appliances ≤10,000 Btuh (3kW), 9 inches (23cm) for appli-
ances >10,000 Btuh (3kW) and ≤50,000 Btuh (15kW), 12
inches (30cm) for appliances >50,000 Btuh (15kW).
K - Clearance to a mechanical air supply inlet 6 feet (1.8m) min-
imum.1,in Canada. In USA, 3 feet (91cm) above if within
10 feet2(3m) horizontally.
L - Clearance above paved sidewalk or a paved driveway locat-
ed on public property 7 feet (2.1m) minimum.
M - Clearance above highest point of exit on roof 18 inches
(45cm).
5
1-2
5
1
5
1
3
N - Clearance to perpendicular wall 24 inches (60 cm).
(Recommended to prevent re-circulation of exhaust products.
For additional requirements check local codes.)
NOTE: Clearances are to the edge of terminal plate, add 6-
NOTE: Local Codes or Regulations may require different
Termination
It is imperative that the vent termination be located observing
the minimum clearances as shown. There must not be any
obstruction such as bushes, garden sheds, fences, decks or utility
buildings within 24” from the front of the termination plate.
Do not locate termination where excessive snow or ice build-up
may occur. Be sure to check vent termination area after snow
falls and clear to prevent accidental blockage of venting system.
When using snow blowers, make sure snow is not directed
towards vent termination area.
General Venting Information
The gas fireplace is approved to be vented either through the
side wall or vertically through the roof.
This appliance is approved with Kingsman flex vent system and
also approved for use with Simpson Duravent Direct Vent
System (model DV-GS series), AmeriVent Direct Vent Pipe
System and Selkirk Direct Temp.
Kingsman flex vent system can be used with Simpson Duravent
Direct Vent termination’s (model DV-GS series).
When using Simpson Duravent, AmeriVent Direct Vent pipe, or
Selkirk Direct Temp a Kingsman/Duravent adapter must be
used.
ONLY VENTING COMPONENTS SPECIFICALLY
APPROVED AND LABELED FOR THIS FIREPLACE MAY
BE USED.
Venting terminal shall not be recessed into a wall or siding. If
finishing the outside wall with vinyl or wood siding it is recommended that a Siding Shield be installed, Part Number
ZDVSSLR.
1 - In accordance with the current CSA B149.1, Natural Gas
2 - In accordance with the current ANSI Z223.1/NFPA 54,
3 - A vent shall not terminate directly above a sidewalk or
4 - Permitted only if veranda, porch, deck, or balcony is
5 - Clearance in accordance with local installation codes
31
3/4” to clearances to arrive at center line.
clearances.
and Propane Code.
National Fuel Gas Code.
paved driveway that is located between two single family dwellings and serves both dwellings.
fully open on a minimum of two sides beneath the floor.
and the requirements of the gas supplier.
General Vent Installation Information
par t # ZDVDFA for fireplaces
and part # ZDVDKA for Stoves, Serenity and ZDV3624B
Simpson Dura-Vent for Mason ry Chim ney Conversion Kits
Simpson Dura-Vent for Factor y bu ilt metal C himney Conver sion Kits
This gas appliance is approved to be vented either through the side wall or vertically through the roof. Only Kingsman Flex(Z-Flex)Venting Kits and com-ponents specifically approved and LABELED for this stove may be used. This appliance is also approved for use with Simpson-Duravent Direct Vent system (Model DV-GS Series), Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
exhaust gases intake air through the side of the masonry chimney. Use Simpson Dura-Vent kit numbers 46DVA-KMC or 46DVA-KCT.
Termination Cap, Kingsman/Dura-Vent adapter, and 4” flex are sold separately.
wood stove chimney and route the exhaust gases and intake air through the existing wood burning metal chimney. Use Simpson Dura-Vent Kit
numbers 46DVA-KCA for 6 5/8” to 8 5/8” OD sized chimney, 46DV-KCB for 8 3/4” to 10 1/2” OD sized chimneys and 46DVA-KCC for 10 5/8”
to 13” OD sized chimneys. Kits 931, 932, and 933 include a cap adapter and Retro Connector. Termination Cap, Kingsman/Dura-Vent adapter, and
4” flex are sold separately.
RIGID OR HARD PIPE
When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal DV and
or Selkirk Direct Temp a Duravent hardpipe adapter must be used (p
). Follow installation instructions provided by Simpson Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel Direct, Metal Fab Sure-Seal
DV for installation of pipe and adhere to the clearance to combustibles provided in this manual.
Apply a bead of Mill Pac high temp sealant to all joints of pipes, adapters and termination, when
using Kingsman Flex(Z-Flex)Venting venting and Simpson Duravent venting.
NOTE: Increase framing depth by one inch when using hardpipe.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
Flex Pipe Venting
Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the lengths.
Pipe can be expanded to twice their lengths e.g. 4ft. to 8ft. Fully expand pipe and cut off excess.
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an installation attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 4” flex in the center of 7”
flex. When forming bends place spring in bend or before and after. (See Fig. 1).
Horizontal runs require support metal straps every 2 feet. In off set installation support straps
should be used to stabilize pipe.
Expand 4” and 7” flex pipe to the point that the 7” protrudes approximately 2 to 3 inches past outer
wall and the 4” flex protrudes approximately 2 to 3 inches past the 7” flex. See Fig. 1. Attach the 4”
pipe to the termination first and secure with sealant and screws then attach the 7” flex to the termination with caulking and screws. Termination may then be moved back to the outer wall and attached
to home screwing into the framing. Silicone around termination to waterproof. If siding shield is
going to be used attach this using same attaching hole as the top of termination after termination has
been caulked for water proofing.
Use Hi Temp Sealant
Apply a bead of mill pac high temp sealant to all joints and use four screws to secure each pipe at
fireplace, termination and any joint if joining any sections of pipe.
may be used with this appliance Use your existing masonry chimney and route the
may be used with this appliance. Use your existing through the ceiling,
FRAMING DIMENSION
Combustible Wall
Cut a 11” hole through exterior wall and frame as shown
below.
Non combustible Wall
Cut or drill 8” or 204mm diameter hole.
SEAL WITH HIGH TEMP. SEALANT
MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS
OPTIONAL
CLAMPS
SEAL WITH HIGH TEMP. SEALANT
FIGURE 1
OPTIONAL
CLAMPS
NOTE: It is critical to the proper and safe operation of
this fireplace that on all connections the inner liner and
the outer casing are both caulked with liberal amounts of
sealant. Do not use any kind of tape or silicone other than
that recommended in this manual, Mill Pac Sealant
Installation Of Side Wall Venting
1. To determine the minimum distance from the bottom of fireplace to centre of vent see page
7 for the MQZDV3318 and page 10 for the MQZDV3622. Cut a hole through the wall
allowing for a 11” x 11” (inside diameter) in combustible walls for wall thimble or an 8”
diameter hole in a non-combustible wall (See Figure 2).
FIGURE 1
2. For the clearance to combustible above a 90 degree bend see page 15.
3. Select the approximate vent length, precise measurements are not needed as your flex pipe
can be expanded to twice its shipped length for ease of installation.
4. To install wall thimble centre over 11” x 11” (inch) framing from both sides of wall and
secure. Route flex vent pipe through wall thimble (See Figure 1).
5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of pipe.
First attach the four inch (4”) flue pipe to the vent termination with sealant, and secure with
the four screws provided. At this time make sure the spacer springs are attached to the (4”)
flex pipe as required. Then attach the seven inch (7”) pipe by the same method.
6. Mount vent termination and seal to wall using caulking around the wall thimble to weather
proof. After installing the vent termination, double check to make sure the pipe extends
properly through wall thimble and into vent termination.
7. Before joining pipes to fireplace flue, apply a bead of high temperature sealant (Mill Pac) to
end of pipe. First attach the four inch (4”) flue pipe to fireplace with sealant, and secure
with the four screws provided. At this time verify that the spacer springs are attached properly to the (4”) flex pipe as required. Then attach the seven inch (7”) pipe by the same
method.
8. Support horizontal pipes every two (2) feet (61 cm) with metal strap bands. Re-check fireplace to make sure it is levelled and properly positioned and secured.
9. Support vertical pipes to maintain a minimum of 1” or greater clearance to combustibles
with metal strapping bands.
10. If finishing the outside wall with vinyl or wood siding it is recommended that a Siding
Shield be installed, Part Number ZDVSSLR.
Note: Vent Termination must not be recessed into wall or siding.
32
COMBUSTIBLE AIR INLET
FLUE GAS OUTLET
MINIMUM OF
1.0" TO
COMBUSTIBLES
31.0”MINIMUM
FOR ZDV3318
33.0"MINIMUM
FOR ZD
V3622
11.0"
11.0"
THROUGH COMBUSTIBLE
WALL
NOTE: See Pages
7,10 and 31 for
proper framing
dimensions.
FRAMING DETAIL
8" DIA
31.0" TO CENTERS MINIMUM FOR ZDV3318
33.0" TO CENTERS MINIMUM FOR ZDV3622
THROUGH
NON-COMBUSTIBLE WALL
FIGURE 2
Venting Routes And Components
Since it is very important that the vent system maintain its balance between the combustion air intake and the flue gas
exhaust, certain limitations as to vent configurations apply and
must be strictly adhered to.
The table showing the relationship between vertical and horizontal side wall venting will help to determine the various vent
lengths.
The maximum horizontal run with the 90 degree bend at the
fireplace flue outlet is 4 ft/122cm (Figure #1). The maximum
horizontal run is 20 ft/6.1 m when the vertical run is 7 ft/2.1m
(Figure #2). Note: 1/4” vertical rise is required for every 12” of
horizontal run.
The maximum number of 45 degree bends per side wall installation is two (2) in the horizontal run and then you must reduce
the length of the horizontal by 18 inches for each 45 degree
bend.
The maximum vertical run is 40 ft/12.2 meters.
Special Note: For each 45 degree bend installed in the horizontal run, the length of the horizontal run must be reduced
by 18” (45cm). This does not apply if the 45 degree bends
are installed on the vertical part of the vent system.
Example: If according to the table, the length of the horizontal
run is 10 feet, and two 45 degree bends are required, the horizontal run length must be reduced to 7 feet.
2 additional 90° bends or equals are allowed. The horizontal
run must be reduced by 36” per each 90° bend, or 18” per each
45° bend.
Important: Always locate the fireplace in such a way that a minimum of offsets and/or horizontal runs are required. 1/4” vertical rise is
required for every 12” horizontal run.
How To Use The Horizontal Vent Table
1. Determine the height of the system and the number of bends
required.
2. Having determined the vertical distance determine the maximum horizontal section allowed.
3. Vent table has been established for 90˚ horizontal/vertical
runs. With use of flex pipe distance not having 90˚ bends will
not fall into vent table standards. See Fig. B.
If the vertical dimension
from the floor of the fireplace is 6ft, the horizontal
run to the wall flange of the
vent termination must not
exceed 12ft.
NOTE: The final location
of the fireplace must be
such that the horizontal
vent dimensions fall within those stated on the
graph. The Maximum
Vertical vent run is 40ft.
(12.2 meters).
Important: Minimum
clearance between vent
pipes and combustible materials is 1 inch (25mm).
It is recommended for Propane Horizontal Installations
that the venting should be a minimum of one foot vertical
off the flue before the elbow on any horizontal runs of
one foot or greater. This allows for cleaner combustion
and greatly reduces carboning and cleaning of glass.
(Does not apply to Back Flue Models).
33
Venting Straight Up Through Roof
1. An Attic Insulation Shield must be installed where the vent passes
from a lower living space into an attic space where the chimney is
not enclosed. It is designed to keep insulation materials away from
the chimney. See Fig. 1.
2. When installing the Attic Insulation Shield where the chimney passes from a living space to an attic space, install the shield from below
and nail in place using 1” spiral nails.
3. A fire stop must be installed on the bottom side of the joists when
passing through a ceiling or floor. If an attic insulation shield is to
be used, a fire stop is not required.
Roof Flashing
Ensure that you have the proper roof flashing by checking your
roof pitch using a level and two rulers, or by using a roof pitch
card. See figure below.
Slide a Roof Flashing suitable to your roof slope over the vent.
Place the edge of the flashing plate that will be on the higher part
of the roof slope under the shingles. Both the sides and the lower
edge lay on top of the shingles.
NOTE: At the top edge of the flashing plate, lift the shingles
and nail the plate to the roof deck, then cement the shingles to
the plate with a suitable waterproof mastic.
Ensure that the chimney is plumb. Square up the flashing plate
and nail in place to the roof deck. Use 12 nails with neoprene
washers or cover the heads with a suitable waterproof mastic.
Wrap the storm collar around the vent above the flashing. Secure
the ends together loosely with nut and bolt supplied. Slide the collar down the vent until it comes in contact with the flashing.
Tighten the bolt and seal the Storm Collar to the vent with a suitable waterproof non-combustible mastic.
The flashing and storm collar should be painted to match the roof
shingles. This will extend its life and improve the appearance.
Clean, prime and paint with suitable painting products.
Vertical Venting in Cold
In cold climate conditions
where temperatures go below 10 degrees Celsius or 14
degrees Fahrenheit, we recommend that the chase be insulated
and where the vent pipe be
wrapped with an insulated
mylar sleeve. This will increase
the temperature of the vent and
help the appliance to vent properly in cold weather conditions.
It is also important in vertical
vented direct vent appliances
that the appliance be operated
daily during the winter months
as this will help stop the
Termination from freezing up.
We recommend using a thermostat set at room temperature to
allow the unit to cycle.
Climates
Using Flex Bends
4. Avoid cutting joists by offsetting the flex pipe. See Fig. 2.
5. When using 45˚ bends a bend support is required directly above the
highest bend.
6. When installing a bend in a joist area a minimum of 2 1/2” clearance
to combustible to the top of bend must be maintained, sides and bottom of pipe, a 1” clearance to combustibles must be maintained. If
running horizontal through an area a 1 1/2” minimum clearance to
the top of the horizontal pipe must be maintained.
7. Maximum vertical height of system should not exceed 40 feet.
8. Use roof support and 7” rigid pipe at roof level. Flex not permitted
within roof support.
9. When penetrating the roof a rigid 7” galvanized pipe must be used.
Attach the 7” flex to the 7” rigid with high temperature sealant,
secure with four screws assuring the flex and rigid pipe are secured.
4” flex pipe must be secured the same way with 4 screws but must
penetrate the 4” flex and 4” section of termination. Attach 7” rigid
pipe to 7” termination with sealant and screw with 4 sheet metal
screws. (See Fig. 3).
10. Vertical termination clearance is 18” (inches) above the roof, measured from highest point of exit on the roof line.
11. Support vertical pipes to maintain minimum of one inch or greater
clearances to combustibles.
34
Vertical Venting over 15 Feet
The Air Intake plate must be adjusted down to the lowest position when venting over 15 ft. vertical.
15’ OR OVER VERTICAL VENTING
AIR INTAKE ADJUSTMENT PLATE
NOTE: Unit comes preset for short horizontal or vertical venting under a 15 feet run.
Follow these instructions when venting exceeds 15 foot run.
1. Locate the 3 x 1/4” hex screws and using a nut driver loosen the screws 1 turn.
2. Lower the Air Adjustment Plate as shown in the diagrams. (Fully Down Position).
MQLOGC22Log Set - 5 pce. - /Fibre Split Oak
MQROCK1Rock Set
MQRSP5Rock Platform, Support
FIREPLACE ACCESSORIES OPTIONS
Fireplace Wall Mount Finishing Surrounds for
Z33CVCK Unit
MQ33SWFBLSurround Flat Black
(Coverage 35 5/16” H x 45 13/16” W)
MQ33SWFPWSurround Flat Pewter
(Coverage 35 5/16” H x 45 13/16” W)
Marquis Wall Surround Accents (Four Pieces)
MQ33SWAKSBWall Surround Accents - Keystone Black
MQ33SWAKSCWall Surround Accents - Keystone Chrome
MQ33SWABBCWall Surround Accents -
Band Black x 4, Chrome x 2
MQ33SWACBWall Surround Accents - Corner Black
Fireplace Surrounds - Trims
Z6SABSurround - Antique Brass
Z6SCRSurround - Chrome
Z6SPBSurround - Polish Brass
Z33SLABSurround Slim Line - Antique Brass
Z33SLCRSurround Slim Line - Chrome
Z33SLPBSurround Slim Line - Polish Brass
Z33SLBLSurround Slim Line - Gun Metal Black
Designer Doors for 33” Fireplaces - Operative
Z33DDA1BLDesigner Door Arch - Series 1 - Black
Z33DDTA1ATrim - Antique for Designer Arch - Series 1
Z33DDTA1CTrim - Chrome for Designer Arch - Series 1
Z33DDTA1PTrim - Polish Brass for Designer Arch - Series 1
Z33DDS1BLDesigner Door Straight - Series 1 - Black
Z33DDS3BLDesigner Door Straight - Series 3 - Black
Z33DDTS1ATrim - Antique for Designer Straight - Series 1
Z33DDTS1CTrim - Chrome for Designer Straight - Series 1
Z33DDTS1PTrim - Polish for Designer Straight - Series 1
Child Safety Screens
Z33CSSChild Safety Screen - 33” DV Fireplaces
Overlays
Z33ADDXArch Door Frame - Deluxe Black (352)
Z33ADTHArch Door Frame - Top Half Black (353T)
Z33ADDAArch Door Frame - Double Arch Black (354)
Z33ADDDArch Door Frame - Double Door Arch Black
Fan Kit/ Blower
Z33FKFan Kit w/Variable Speed Wall Mount Control
6000-P930Blower Motor QLN657/1800(Z33FK MOTOR)
Refractory Liners
Z3318PRLPorcelain Reflective Liner
Z3318MLMetal Liner Traditional
MQLOGC22Log Set - 5 pce. - /Fibre Split Oak
MQROCK1Rock Set
MQRSP5Rock Platform, Support
FIREPLACE ACCESSORIES OPTIONS
Fireplace Wall Mount Finishing Surrounds for
Z36CVCK Unit
MQ36SWFBLSurround Flat Black
(Coverage 37 5/32” H x 50 5/16” W)
MQ36SWFPWSurround Flat Pewter
(Coverage 37 5/32” H x 50 5/16” W)
Marquis Wall Surround Accents (Four Pieces)
MQ36SWAKSBWall Surround Accents - Keystone Black
MQ36SWAKSCWall Surround Accents - Keystone Chrome
MQ36SWABBCWall Surround Accents -
Band Black x 4, Chrome x 2
MQ36SWACBWall Surround Accents - Corner Black
Fireplace Surrounds - Trims
Z36SABSurround - Antique Brass
Z36SCRSurround - Chrome
Z36SPBSurround - Polish Brass
Z36SLABSurround Slim Line - Antique Brass
Z36SLCRSurround Slim Line - Chrome
Z36SLPBSurround Slim Line - Polish Brass
Z36SLBLSurround Slim Line - Gun Metal Black
Designer Doors for 36” Fireplaces - Operative
Z36DDA1BLDesigner Door Arch - Series 1 - Black
Z36DDTA1ATrim - Antique for Designer Arch - Series 1
Z36DDTA1CTrim - Chrome for Designer Arch - Series 1
Z36DDTA1PTrim - Polish Brass for Designer Arch - Series 1
Z36DDS1BLDesigner Door Straight - Series 1 - Black
Z36DDS3BLDesigner Door Straight - Series 3 - Black
Z36DDTS1ATrim - Antique for Designer Straight - Series 1
Z36DDTS1CTrim - Chrome for Designer Straight - Series 1
Z36DDTS1PTrim - Polish for Designer Straight - Series 1
Child Safety Screens
Z36CSSChild Safety Screen - 33” DV Fireplaces
Overlays
Z36ADDXArch Door Frame - Deluxe Black (352)
Z36ADTHArch Door Frame - Top Half Black (353T)
Z36ADDAArch Door Frame - Double Arch Black (354)
Z36ADDDArch Door Frame - Double Door Arch Black
Fan Kit/ Blower
Z36FKFan Kit w/Variable Speed Wall Mount Control
6000-081Blower Motor QLN657/1800(Z36FK MOTOR)
Refractory Liners
Z3622PRLPorcelain Reflective Liner
Z3622MLMetal Liner Traditional
Door Glass
3600-311Tempered Glass - ZDV3622
1000-305Ceramic Glass - for all ZDV3600
Replacement Burner Assembly
3622MQ-BNGSI Burner Assembly - Natural Gas c/w Valve
3622-CKLPPropane Conversion Kit
3622-CKNGNatural Gas Conversion Kit
(Temperature Sensing)
System (MQZDV3622N)
System (MQZDV3622LP)
37
Kingsman Parts MQZDV3318/3622
Catalog
NumberDescription
Valve System Parts - New Top convertible SIT
1000-P136WRGenerator/Thrermopile
1001-P069SIElectrode Sparker 915.069 TC SIT
1001-P216SIThermocouple 290.216 TC SIT
1001-P165SIOrifice Pilot NG 977.165 TC SIT
1001-P167SIOrifice Pilot LP 977.167 TC SIT
1001-P280SITubing 24”
1001-P633SIValve Nova LP Hi/Lo 0820651
1001-P634SIValve Nova NG Hi/Lo 0820652
1001-P713SIPilot Burner LP 199.713 TC SIT
1001-P714SIPilot Burner NG 199.714 TC SIT
Miscellaneous Parts
1000-150GE#Silicone GE Red IS806 #736
1000-150MP#Hi-Temp Millpac Sealant 840099
1000-214#Piezo-Igniter 1244-17 MARK 21
1000-215#Pal Nut (18MMXI.5MM)BLK (1364.03)
1000-218#Switch Ivory (1451/001)
1000-227#Cover Ivory (86001/001)
1000-255#Orifice Brass - (State Size)
6000-130#Explosion felt Gasket
2000-080#Thermodisc 2450 (For Blower)
1000-306Thermalcord - Adhesive Back for Door
Frame
1000-085#Control Variable Speed KBWC-13BV
Accessories
Z1MTThermostat Millivolt Wall Mount
Z80PTThermostat Programmable Digital Millivolt
Wall Mount (1F80-40)
ZIRCRemote Control Millivolt (On/Off with
LED)(Model1)
ZARTRemote Control Thermostat Millivolt (Model K)
RMCBNRemote Control - Basic - Natural Gas
(On/Off,Hi/Lo Flame Adjustment)
RMCBPRemote Control - Basic - Liquid Propane
(On/Off, Hi/Lo Flame Adjustment)
DCHSRemote Control Heatshield
VLBIT4Log Bits - Large Four Piece Kit
VLBIT6Log Bits - Small Six Piece Kit
*Kits are complete with spring stand-offs, silicone.
ZDV4FCFlex Connector 4” Diameter
ZDV7FCFlex Connector 7” Diameter
ZDV4SSSpring 4” Standoff Spacer
ZDVDFADura-Vent Fireplace Adapter
(for ZDV33/36/42/47, ZDV6000, MDV30/38 &
HB models)
38
LIMITED LIFETIME WARRANTY
This Limited Lifetime Warranty applies only while the unit remains at the site of the original
installation and only if the unit is installed inside the continental United States, Alaska, Hawaii,
and Canada. The warranty applies only if the unit is installed and operated in accordance
with the printed instructions and in compliance with applicable installation and building codes
and good trade practices.
BASIC ONE YEAR WARRANT Y
During the first year after installation, we will provide a replacement for any component part of your unit found to be defective in materials
or workmanship, including labour costs. Repair work requires prior approval by Kingsman, labour costs are based on a predetermined rate
schedule and any repair work must be done through an authorized Kingsman dealer.
LIMITED LIFETIME WARRANTY
The heat exchanger, combustion chamber and burner of every Kingsman product excluding the Outdoor Firepit are warranted against
materials or workmanship during the period the product is owned by the original owner. The part to be replaced must be returned to our
distributor in exchange for the replacement part. Any labor, material, freight and/or handling charges associated with any repair
or replacement pursuant to this Limited Lifetime Warranty will not be covered by this warranty.
GENERAL TERMS
In lieu of providing a replacement part, we may, at our option, provide the distributor's component purchase price from us or a credit equal
to the distributors component purchase price from us toward the purchase of any new unit which we distribute. If a credit is given
in lieu of a replacement part, the rating plate from the unit being replaced must be submitted on a warranty claim, and the unit being
replaced must be made available to our distributor for disposition.
In establishing the date of installation for any purpose, including determination of the starting date for the term of this Limited Lifetime
Warranty, reasonable proof of the original installation date must be presented*, otherwise the effective date will be based upon the date of
manufacture plus thirty (30) days.
We will not be responsible for and you, the user, will pay for: (a) damages caused by accident, abuse, negligence, misuse, riot, fire, flood,
or Acts of God (b) damages caused by operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any other
damaging chemicals (other than in a normal residential environment) (c) damages caused by any unauthorized alteration or repair
of the unit affecting its stability or performance (d) damages caused by improper matching or application of the unit or the unit's components
(e) damages caused by failing to provide proper maintenance and service to the unit (f) any expenses incurred for erecting, disconnecting
or dismantling the unit (g) parts or supplies used in connection with service or maintenance (h) damage repairs, inoperation or inefficiency
resulting from faulty installation or application (i) electricity or fuel costs or any increase in electricity or fuel cost whatsoever including
additional or unusual use of supplemental electric heat.
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit.
We have not made and do not make any representation or warranty of fitness for a particular use or purpose, and there is no implied condition
of fitness for a particular use or purpose. We make no express warranties except as stated in this Limited Lifetime Warranty. No one is authorized
to change this Limited Lifetime Warranty or to create for us any other obligation or liability in connections with this unit. Any implied
warranties shall last for one year after the original installation. Some states and provinces do not allow the exclusion or limitation of incidental
or consequential damages or do not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply to you. The provisions of this limited warranty are in additions to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
Save this certificate. It gives you specific legal rights, and you may also have other rights which may vary from state to state and province to province.
In the event your unit needs servicing, contact your dealer or contractor who installed or serviced your unit. When requesting service,
please have the model and serial number from each unit readily available. If your dealer needs assistance, the distributor is available for support
and we, in turn support the distributor's efforts.
Fill in the installation date and model and serial numbers of the unit in the space provided below and retain this limited warranty for your files.
Model No.Serial No.Date installed
Dealer or Contractor Name :
To receive advantage of your warranty, you must retain the original records that can establish the installation date of your unit.
*
The Ultimate in Design, Engineering & Quality
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.