STC-SS Series - Data/Signal Line Protection
The STC-SS Series suppressors are designed for the
water and wastewater industry. These multi-stage hybrid
suppressors address overvoltage transients with gas tube
and silicon avalanche technology. In addition, sneak and
electrical fault currents are mitigated with PTC devices
which consist of solid-state resettable fuses. The units are
encapsulated in stainless steel pipe nipples making them
suitable for use in severe environments.
Application
• Water and wastewater
• Industrial applications
Features
• Automatic recovery features make it ideal for use in
severe environments
• Transient protection for low-voltage signal lines
• Gas tube and silicon avalanche technology
• Sneak/fault current protection
• Resettable solid-state fuses - PTCs
• Differential and common mode protection
• Multi-stage hyrbid suppressor
• Encapsulated in stainless steel pipe nipples
• UL497BCertied
• Five year limited warranty
Certifications and Compliances
• Listed
- UL 497B
• RoHS Compliant
Dimensional Drawing
Selection Table
Catalog Number Description
STCSS640362
1/2" Metal Conduit Capped
Specifications
Description Signal Line Protection
Operating Voltage
Maximum Operating Current
Clamping Voltage
Peak Surge Current
SPD Technology
Frequency Range
Insertion Loss
Series Resistance
(per Conductor)
Capacitance (Zero Volts Bias)
Operating Temperature
Life Cycle
Weight - lbs (kg)
GDT/PTC/SAD Hybrid
(L-G) 1200 pf (typical)
400 @ 500 Amps (10x1000 µs)
E516380
28 Vdc
150 mA
(L-G) 36 Vdc
(L-L) 72 Vdc
10 kA (8x20 µs)
0 to 20 MHz
<0.1 dB at 20 MHz
5 Ohms (typical)
(L-L) 600 pf (typical)
-40 °C to +85 °C
0.35 (0.16)
Certifications
Warranty