SolaHD SDP Series Data Sheet

4
SDP™ Series Specifications (24 V models)
Power Supplies
Description
SDP 06-24-100T SDP 1-24-100T SDP 2-24-100T SDP 4-24-100LT SDP 4-24-100RT
Input
Input Voltage
Input Frequency
Input Current
External Fusing
Hold-Up Time
Efficiency
Losses
1
0.4 A / 0.25 A 0.7 A / 0.4 A 1.1 A / 0.7 A 1.8 A / 1.0 A 2.2 A / 1.2 A
> 80% typ. > 83% typ. > 86% typ. > 88% typ.
< 3.75 W typ. < 6.1 W typ. < 8.1 W typ. < 12 W typ.
85-264 Vac, 90-375 Vdc 85-132 / 176-264 Vac, 210-375 Vdc
47-63 Hz
Not required. Unit provides internal fuse (T3A, not accessible)
> 25 ms
Output
Output Voltage
Voltage Regulation
Ripple/Noise
Overvoltage Protection (OVP)
Output Noise Suppression
Rated Continuous Loading
Overload Behavior
Protection
Power Back Immunity
2
0.63 A @ 24 Vdc /
0.54 A @ 28 Vdc
24 V (22.5 - 28.5 Vdc Adj.) 24 V (24 - 25.7 Vdc Adj.) 24 V (22.5 - 28.5 Vdc Adj.)
Static 0.5% V
> 30 Vdc, but < 33 Vdc, auto recovery
Radiated EMI values below EN61000-6-2
1.3 A @ 24 Vdc /
1.1 A @ 28 Vdc
Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous
Unit is continuously protected against short-circuit, overload and open-circuit.
, dynamic + 2% V
out
< 50 mVpp
2.1 A @ 24 Vdc /
1.8 A @ 28 Vdc
35 V
overall\
out
> 26 Vdc, but < 27.2
Vdc, auto recovery
3.8 A @ 24.5 Vdc
> 30 Vdc, but < 33 Vdc,
auto recovery
4.2 A @ 24.5 Vdc /
3.6 A @ 28 Vdc
Installation
Status Indicators
Case & Mounting
Green LED on, when V
Molded plastic housing using UL 94 approved ameproof material rating 94V-2.
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
out
“OK”.
Dimensions
(H x W x D) (in/mm)
Weight - lbs (kg)
Mounting Orientation
Ventilation/Cooling
•Free space for cooling
Connection
•Connector size range
2.95 x 0.9 x 3.8
(75 x 22.8 x 96.7)
0.35 lbs (.16 kg) 0.5 lbs (.23 kg) 0.7 lbs (.32 kg)
Input: screw terminals, connector size range: 20-12AWG (1.5 - 6 mm
2.95 x 1.77 x 3.58 (75 x 45 x 91)
Standard: Vertical; Optional: Horizontal or on top (Contact Technical Services).
Normal convection, no fan required; Above/below: 25 mm recommended.
2
) for solid or stranded conductors.
2.95 x 2.85 x 3.8
(75 x 72.5 x 96.7)
General
Temperature
MTBF
Humidity
Electromagnetic Emissions (EME)
Electromagnetic Immunity (EMI)
Safe Low Voltage
Protection Class/Voltage
Warranty
Storage: -25°C...+85°C Operation: -10°...+60°C full power with linear derating to half power from 60°C to 70°C.
(Convection cooling, no forced air required).
> 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1.
Up to 90% RH, noncondensing; IEC 68-2-2, 68-2-3
EN61000-6-3 (Includes EN61000-6-4) Class B (EN 55022) incl. Annex A
EN61000-6-2 (Includes EN61000-6-1) (EN55024) Criterion A: no derogation of performance
SELV (acc. EN60950)
IP20 (IEC529), Protection Class 1 (IEC536)
3 years
Safety
CB Scheme, EN60950, UL60079-15 (Class 1, Zone 2 Hazardous Locations, Temp Class T3), UL508 Listed, cULus, UL 60950, cURus, CE (LVD 73/23 & 93/68/EEC). (EMC 89/336 & 93/68/EEC). EN61000-3-2, NEC Class 2 power supply acc. To NFPA 70 art. 725-41 (a)(2).
3
Notes:
1. Not UL listed for DC input.
2. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
3. For all models except SDP 4-24-100LT.
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
119
4
Power Supplies
SDP™ Series Specifications (Other Voltages)
Description Catalog Number
SDP 5-5-100T SDP 2-12-100T SDP 3-15-100T SDP 1-48-100T
Input
Input Voltage
Input Frequency
Input Current
External Fusing
Hold-Up Time
Efficiency
Losses
Output Voltage
Voltage Regulation
Ripple/Noise
Overvoltage Protection (OVP)
Output Noise Suppression
Rated Continuous Loading
Overload Behavior
Protection
Power Back Immunity
Status Indicators
Case & Mounting
(H x W x D) (in/mm)
Weight - lbs (kg)
Mounting Orientation Standard: Vertical; Optional: Horizontal or On Top (Contact Technical Services).
Ventilation/Cooling
•Free space for cooling
Connection
•Connector size range
Temperature
MTBF
Humidity
Electromagnetic Emissions (EME)
Electromagnetic Immunity (EMI)
Safe Low Voltage
Protection Class/Voltage
Warranty
CB Scheme, EN60950, UL60079-15 (Class 1, Zone 2 Hazardous Locations, Temp Class T3), UL508 Listed, cULus, UL 60950, cURus, CE (LVD 73/23 & 93/68/EEC), (EMC 89/336 & 93/68/EEC). EN61000-3-2, NEC Class 2 power supply acc. To NFPA 70 art. 725-41 (a)(2).
Notes:
1. Not UL listed for DC input.
2. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
3. Not to exceed 30 watts total.
1
0.6 A @ 102 Vac;
0.33 A @196 Vac
Not required. Unit provides internal fuse (T3A, not accessible)
> 80% typ. > 86% typ. > 90% typ.
7.5 W typ. 8.1 W typ. < 8.1 W typ.
5 - 5.5 Vdc (5 - 6 min adj.) 12 Vdc (9.9 - 12.1 min adj. ) 15 Vdc (11.9 - 15.1 min adj.) 48 Vdc (48 - 56 min adj.)
2
> 6.7 Vdc > 18 Vdc > 20 Vdc > 56 Vdc
l
= 5A @ V
out
= 5.1V
out
Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous
Unit is continuously protected against short-circuit, overload and open-circuit.
10 V 22 V 80 V
Molded plastic housing using UL 94 approved ameproof material rating 94V-2.
Normal convection, no fan required; Above/below: 25 mm recommended.
Input: screw terminals, connector size range: 20-12 AWG (1.5 - 6 mm
Storage: -25°C...+85°C Operation: -10°...+60°C full power with linear derating to half power from 60°C to 70°C.
> 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1.
EN61000-6-3 (Includes EN61000-6-4) Class B (EN 55022) incl. Annex A
EN61000-6-2 (Includes EN61000-6-1) (EN55024) Criterion A: no degradation of performance
3A @ 10 Vdc
2.5A @12 Vdc
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
(Convection cooling, no forced air required).
Up to 90% RH, noncondensing; IEC 68-2-2, 68-2-3
85-264 Vac, 90-375 Vdc
47-63 Hz
1.0 A @ 102 Vac;
0.6 A @ 196 Vac
> 25 ms
Output
< 2% Dynamic; < 0.5% Static
< 50 mVpp
Radiated EMI values below EN61000-6-2
4.2A @ 12 Vdc
3.4A @ 15 Vdc
Installation
Green LED on, when V
out
“OK”.
Dimensions
2.95 x 1.77 x 3.58 (75 x 45 x 91)
0.5 lbs (.23 kg)
2
) for solid or stranded conductors.
General
SELV (acc. EN60950)
IP20 (IEC529), Protection Class 1 (IEC536)
3 years
Safety
<1.0 A @ 100 Vac;
<0.6 A @ 196 Vac
Up to 1.05A @ 48 V
0.9A @ 56 V
3
120
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
Loading...