16 A (192 W)5 A (120 W)10 A (240 W) 20 A (480 W)40 A (960 W)
>40ms (Full load, 100 Vac
Input @ T
95% output voltage
< 18 V No damage,
auto-recovery
> 18 but < 20 Vdc,
auto-recovery
Storage: -40°C to +85°C, Operation -40°C to +60°C full power, with linear derating to 75% power from +60°C to 70°C (Convection cooling).
Catalog Number
Input
100 - 240 Vac (85-264 Vac)
100-340 Vdc (90-375 Vdc)
100-250 Vdc
(90-275 Vdc)
43 - 67 Hz
Typ. <3.7A at 120 Vac,
<7.4A at 230 Vac,
measured at 25°C
Typ. <12.7A at 120 Vac,
<24.8A at 230 Vac,
measured at 25°C
Typ. <5.8A at 120 Vac,
<11.5A at 230 Vac,
measured at 25°C
Typ. <5.8A at 120 Vac,
Active power factor correction typ. 0.98 @ 115 Vac/ 0.92 @ 230 Vac
Output
< ±2 % overall (combination Line, load, time and temperature related changes)
100 mVpp max
Single or Parallel operation selectable via front switch.Active Paralleling.
< 1 s after AC is applied to input at full resistive load ( Tamb=+25°C ). <1.5 ms with capacitive load 7000μF
=+25°C) to
amb
<150 mS from 95% to 10% rated voltage @ full load (T
>20 ms (Full load, 100 Vac Input @ T
=+25°C) to 95% output voltage
amb
=+25°C)
amb
Protection
Output automatically goes to near zero and output is protected from continuous short circuit. Auto-recovery.
1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 20 Vdc (> 10 Vdc for SDN 16-12-100C)
PowerBoost™
< 35 V No damage, auto-recovery
> 30.5 but < 33 Vdc, auto-recovery
LED Alarm and Output shutdown , auto-recovery
Environmental Data
EN61000-6-3, EN61000-6-4, Class B EN55011, EN61000-3-2 Class A,
Class B EN 55032, EN 61326-1 Class B, EN 61000-3-3
EN 55024, EN 61000-6-1, EN 61000-6-2, EN 61326-1, SEMI F47
Protected against continuous short circuit, continuous overload, continuous open circuit.
IEC 60950-1: Class I Earthed, Output is SELV (Safety Extra Low Voltage), Environmental Rating: Pollution Degree 2
IEC 60529 Ingress Protection Rating: IP20
Operation up to 50% load with sideways or front-side-up mounting orientation.
5 to 95 % RH Non-condensing; IEC 60068-2-2, IEC 60068-2-3
2.5g RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6
10(g) RMS, three axes, 11mseconds for each axis - IEC 60068-2-27
0 to 6000 meters (0 to 20,000 feet) per MIL-STD-810F
120-340 Vdc
(108-375 Vdc)
<11.5A at 230 Vac,
measured at 25°C
1. Input current ratings are conservatively specied with low AC input, worst case efciency and power factor.
2. Losses are heat dissipation in watts at full load, nominal AC input line.
3. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
4. All models are capable of paralleling. For redundant operation, please use external Redundancy module. Only the 40A uses Active paralleling scheme. Please refer to user
manual for details.
5. Peak current is calculated at nominal voltage levels.
Input Branch fuse or circuit breaker should be provided by customer. See manual for details.
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
16–10 AWG (1.5–6 mm
Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
16–10 AWG (1.5–6 mm
Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
0.98 in (25 mm)1.6 in (40 mm)0.98in (25mm)
4.85 × 1.97 × 4.36
(123.0 × 50.0 × 110.0)
Fully enclosed metal housing with ne ventilation grid to keep out small parts. IP20 touch proof
Signal Active when Vout > 18.5 Vdc +/-5% (Vout > 10.8 Vdc for SDN 16-12-100C)
> 550,000 hours @ 115 Vac
>650,000 hours @ 230 Vac
>300,000 hours @ 115 Vac
>400,000 hours @ 230 Vac
2
) solid or stranded conductors.
2
) for solid or stranded conductors.
0.39 in (10mm)0.59in (15mm)
0.59 (15)
4.85 × 2.36 × 4.36
(123.0 × 60.0 × 110.0)
General
Visual: 3 status LEDs (Input, Output, Alarm)
Relay: N.O. contact rated 200mA/50 Vdc
5 Year Limited Warranty
>800,000 hours @ 115 Vac
>850,000 hours @ 230 Vac
>500,000 hours @ 115 Vac
>570,000 hours @ 230 Vac
4.85 x 3.42 x 4.98
(123.0 x 87.0 x 127.0)
>550,000 hours @ 115 Vac
>570,000 hours @ 230 Vac
>360,000 hours @ 115 Vac
>370,000 hours @ 230 Vac
(3-6 mm2) solid/stranded
Screw Torque: 4.4 lb-inch
13-10 AWG
conductors.
(50 N-cm).
7–6 AWG (10.6–13
mm2 ) solid/stranded
conductors.
Screw Torque: 15.6
lb-inch
(176 N-cm)
4.85 x 7.09 x 4.81
(123.0 x 180.0 x 122.0)
7. Screw terminals. Use only one copper wire per terminal. Non-ratcheting torque driver recommended.
8. SDN 40-24-100C only — Provided with Signal Mode terminal block which includes the following features: DC OK, Ground signal, PS ON, I_share connection. Refer to Signals
SDN 5-24-480CSDN 10-24-480CSDN 20-24-480CDSDN 40-24-480C
380 - 480 Vac (320 - 540 Vac), 3-phase
Nominal DC Voltage (Range)
Frequency
Nominal Current
2
-Inrush current max.
Efficiency (Losses
3
)
Power Factor Correction
Nominal Voltage
4
3 x 0.5 A3 x 0.8 A3 x 0.9A3 x 1.6A
Typ. < 25 ANegligible
> 85% (18 W)91% (24W)93% (42 W)94% (78 W)
Meets EN61000-3-2 Class AActive Power Factor Correction > 0.92
Initial Voltage Setting
-Tolerance
5
-Ripple
PARD
(Periodic and Random Deviation)
Nominal Current (Rated Power)
Parallel Operation
6
Turn On Time
Holdup Time
(Full load,
5 A (120 W)10 A (240 W) 20 A (480 W)40 A (960 W)
< 1 s after AC is applied to input at full resistive load ( Tamb=+25°C ). <1.5 s With capacitive load 7000μF
< ±2 % overall (combination Line, load, time and temperature related changes)
< 50 mVpp< 100 mVpp
100 mVpp max200 mVpp max
Single or Parallel operation selectable via front switch.Active Paralleling.
20 ms15 ms
100 Vac Input @ T = +25°C)
Voltage Fall Time
-Short Circuit Current
-Peak Current
7
Voltage output automatically goes to near zero and output is protected from continuous short circuit. Auto-recovery.
<150 mS from 95% to 10% rated voltage @ full load (T =+25°C)
1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 20 Vdc
-Current Limit
Back EMF Immunity
Overvoltage Protection
Over Temperature Protection
Emissions
Immunity
EN 61000-6-3, EN 55011 Class B, EN 55022 Class B, EN 61326-1,
EN 61000-3-2, EN 61000-3-3
EN 55024, EN 61326-1, EN 61000-6-1, EN 61000-6-2, SEMI F47
> 30.5 but < 33 Vdc, auto-recovery
LED Alarm and Output shutdown , auto-recovery
Protected against continuous short circuit, continuous overload, continuous open circuit.
General Protection/ Safety
Temperature
8
Storage: -40°C to + 85°C, Operation -40°C to +60°C full power, with linear derating to 75% power from 60 to 70°C (Convection cooling, no
forced air required). Operation up to 50% load permissible with sideways or front-side-up mounting orientation.
Humidity
Vibration
Shock
Altitude
1. In the event of a phase loss, the power supply will continue to operate normally. However, the resulting lower rectied RMS voltage can cause excessive heat build up, which may eventually cause the unit
to shut down if maximum operating temperature is exceeded.
2. Input current ratings are specied with low AC 3-phase input, line conditions, worst case efciency values and power factor spikes. Input current at nominal AC 3-phase input will typically be half these
values.
3. Losses are heat dissipation in watts at full load, nominal line.
4. 24-28 Vdc adjustable guaranteed at full load.
5. Ripple/noise is stated as typical values when measured with a 20 MHZ, bandwidth scope and 50 Ohm resistor
6. All models are capable of paralleling. For redundant operation, please use external Redundancy module. Only the 40A uses active paralleling scheme. Please refer to user manual for details.
7. SDN 20 and SDN 40 are capable of delivering 150% load for approximately 4s before the unit will go to HICCUP mode. SDN 5 and 10 will maintain minimum 4s to deliver 150% load then drops to almost
zero Vout. The output voltage will immediately drop to almost zero when load rises above 150%.
8. Contact Tech Support for operation -40°C.
IEC 60950-1: Class I Earthed, Output is SELV (Safety Extra Low Voltage),
SDN 5-24-480CSDN 10-24-480CSDN 20-24-480CDSDN 40-24-480C
Reliability
>1,100,000 hours @ 380 Vac
>900,000 hours @ 480 Vac
>600,000 hours @ 380 Vac
>500,000 hours @ 480 Vac
Relay: N.O. contact rated 200mA/50 Vdc, Signal Active when Vout> 18.5 Vdc +/-5%
Input Branch fuse or circuit breaker should be provided by customer. See manual for details.
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for
wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
0.98 in (25 mm)1.6 in (40 mm)2.80 in (70mm)
4.85 × 1.97 × 4.36
(123.0 × 50.0 × 110.0)
1.2 (0.5)1.5 (0.7)2.7 (1.2)5.3 (2.4)
Fully enclosed metal housing with ne ventilation grid to keep out small parts. IP20 touch proof
Relay: N.O. contact rated 200mA/50 Vdc, Signal Active when Vout> 18.5 Vdc +/-5%
>1,400,000 hours @ 380 Vac
>900,000 hours @ 480 Vac
>910,000 hours @ 380 Vac
>600,000 hours @ 480 Vac
Visual: 3 status LEDs (Input, Output, Alarm)
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
16-10 AWG (1.5-6 mm
Screw Torque: 4.4 lb-in (~ 50 N-cm).
16-10 AWG (1.5-6 mm
Screw Torque: 7 lb-inch (~ 80 N-cm)
(123.0 × 60.0 × 110.0)
2
) for solid conductors.
4.85 × 2.36 × 4.36
Visual: 3 status LEDs (Input, Output, Alarm)
5 Year Limited Warranty
>630,000 hours @ 380 Vac
>630,000 hours @ 480 Vac
>460,000 hours @ 380 Vac
>450,000 hours @ 480 Vac
Installation
2
) for solid conductors.
0.98in (25mm)
0.59 in. (15 mm)
General
SDN 20-24-480CR
4.85 x 3.42 x 4.98
(123.0 x 87.0 x 127.0)
>600,000 hours @ 380 Vac
>550,000 hours @ 480 Vac
>380,000 hours @ 380 Vac
>360,000 hours @ 480 Vac
7–6 AWG (10.6–13 mm2 ) solid
or stranded conductors.
Screw Torque: 15.6 lb-inch
(176 N-cm)
4.85 x 7.09 x 4.66
(123.0 x 180.0 x 119.0)
9. Screw terminals. Use only one copper wire per terminal. Non-ratcheting torque driver recommended.
10. SDN 40-24-480C only: Output signaling terminal block features (Shut down, Power Good, Current Monitor, Current Balance, signal GND). Please refer to Signals Manual
for details.