The SDN-C DIN rail power supplies are the next generation
of the popular SDN series. These models combine high
efciency and compact size with new visual diagnostic
LEDs to offer the most performance available from SolaHD.
Essential industrial features such as Sag Immunity, Power
Factor Correction, and universal voltage input have been
retained in this series. Wide temperature operating range
and parallel operation capability make the new SDN-C units
suitable to a variety of industrial applications.
Features
• Compact packaging to save space on the DIN rail
• New visual diagnostic LEDs for input and output status
at a glance
• High MTBF means high reliability and long life
• Higher efciency saves energy and lowers amount of
heat generated in panel
TM
• PowerBoost
inrush loads
• Accepts Universal voltage 85-264 Vac, 50/60 Hz input
• Single phase models meet SEMI F47 Sag Immunity
standard
• Active Power Factor Correction
• Class I, Zone 2 Hazardous Locations
– Single and three-phase input available
• Patented DIN rail mounting clip
• User Adjustable output voltage accessible via front face
No. 213; Class I, Div. 2, Groups A,B,C and D, T4 in a 40
60oC ambient and ATEX EN60079-0, EN60079-15 II 3 G Ex nC IIC pending
no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
> 550,000 hrs > 450,000 hrs
Protected against continuous short -circuit, continuous overload, continuous open circuit.
Protection Class 1 (IEC536), degree of protection IP20 (IEC60529) Safe low voltage: SELV (acc. IEC60950-1)
wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
Input: Screw terminals, connector size range: 16-10 AWG (1.5-6 mm
Output: Two terminals per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
Fully enclosed metal housing with ne ventilation grid to keep out small parts.
15 mm in front, 25 ~ 40 mm above and below, 10 mm left and right.
1.10 (0.5)1.76 (0.8)2.6 (1.2)
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
Catalog Number
Input
115/230 Vac
85 - 264 Vac
90 - 375 Vdc
43 - 67 Hz
Active power factor correction to better than 0.92
Output
24 V (23.5~28.5 Vdc Adj.)
24.5 V ± 1%
> 30.5 but < 33 Vdc, auto recovery
< 35 V
PowerBoost™
=+25°C) to 95% output voltage
amb
< 0.5%
=+25°C)
amb
General
o
C ambient; CE IEC60950-1:2005 2nd ed, EN60950-1:2006+A11:2009;
5 Years
Visual: 3 status LEDs (Input, Output, Alarm)
Relay: N.O. contact rated 200ma/50 Vdc
Installation
Internally fused
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
4. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth
scope and 50 Ohm resistor.
5. Peak current is calculated at 24 Volt levels.
6. Contact tech support for operation at -25
7. Demonstrated through extended life test.
2
) for solid conductors.
o
C.
103
4
II3G
Power Supplies
SDN-C Specifications (Three Phase)
Description
Nominal Voltage
Two - phase input
-AC Range
2
-DC Range
-Frequency
Nominal Current
-Inrush current max.
Efficiency (Losses
3
4
)
Power Factor Correction
Turn on time
Voltage Rise Time
Power Back Immunity
Overvoltage Protection
Nominal Voltage
Voltage Regulation
Initial Voltage Setting
5
-Ripple
PARD
Nominal Current
-Peak Current
6
-Current Limit
Derating
Holdup Time
Voltage Fall Time
Parallel Operation
7
Case
Min. Required
Free Space
H×W×D inches (mm)
4.85 × 1.97 × 4.36 (123 × 50 × 111) 4.85 × 2.36 × 4.36 (123 × 60 × 111) 4.85 x 3.35 x 4.68 (123 x 85 x 119) 4.85 x 7.09 x 4.66 (123 x 180 x 119)
Weight lbs (kg)
EMC: -Emissions
-Immunity
Approvals
Temperature
Humidity
Altitude
Vibration
Shock
Warranty
MTBF
General Protection/Safety
Over-temperature protection
Status Indicators
Fusing: -Input
-Output
Mounting
Connections
1. SDN 20 will operate at 75% load; SDN 40 will operate at 50% load under loss of 1 phase; SDN 5
and SDN 10 will operate with single phase input power at 100% of load. Unit will shut down if
thermal threshold is exceeded under this condition.
2. Unit passed input voltage overstress test at 600 Vac without failure.
3. Input current ratings are specied with low input, line conditions, worst case efciency values and
power factor spikes. Input current at nominal input settings will typically be half these values.
4. Losses are heat dissipation in watts at full load, nominal line.
5. Ripple/noise is stated as typical values when measured with a 20 MHZ, bandwidth scope and 50
Ohm resistor.
8
104
SDN 5-24-480CSDN 10-24-480CSDN 20-24-480CCSDN 40-24-480C
Input
450 - 760 Vdc450 - 760 Vdc450 - 760 Vdc
3 x 0.5 or 2 x 0.7 A3 x 0.8 or 2 x 1.2 A3 x 0.9 or 2 x 1.3 A3 x 1.6 A
Typ. <25 ANegligibleNegligible
> 85% (18 W)91.2% (23.6 W)93% (42 W)94% (78 W)
Power factor correction to meet EN61000-3-2 Class AActive Power Factor Correction
cULus Listed UL508, CSA C22.2 No. 107.1; UL 60950-1/CSA C22.2 No.60950-1 2nd ed; CE IEC60950-1:2005 2nd ed,
EN60950-1:2006+A11:2009; SDN 20-24-480C and SDN 40-24-480C - ANSI/ISA 12.12.01, CSA C22.2 No. 213; Class I, Div. 2, Groups
A,B,C and D, T4 in 60
IIC, Ex nA IIC, T4 in 60
Storage : -40 to + 85
3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, Semi F47 sag immunity.
o
C ambient; SDN 5-24-480C and SDN 10-24-480C - UL 60079-15/CSA C22.2 E60079-15 Class I, Zone 2 AEx nA
o
C ambient; ATEX: EN60079-0, EN60079-15 II 3 G Ex nC IIC Gc, T4 in 60oC ambient, DEMKO 11 ATEX 1057365U and
o
C, Operation -25 to +60oC full power, with linear derating to half power from 60 to 70oC (Convection cooling, no forced air
required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
< 90% RH, noncondensing; IEC 60068-2-2, 68-2-3
2.5(g) RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6
3(g) peak, three axes, 11mseconds for each axis - IEC 60068-2-27
>500,000 hrs MTBF (Nominal voltage, full load, T
Protected against short -circuit, overload, open circuit. Protection class 1 (IEC536), degree of protection IP20 (IEC 529)
LED Alarm, Output shutdown with automatic restart
Visual: 3 status LEDs (Input, Output, Alarm) Relay: SSR or dry relay contact, signal active when V
Installation
Not fused. Output is capable of providing high currents (PowerBoost) for motor load startup.
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Unit should handle normal shock and vibration of industrial use and transportation without falling off the rail.
Input: screw terminals, Wiring for the connector will be Ground on the left (when looking at the front of the unit),
connector size range: 16-10AWG (1.5-6mm2) for solid conductors. Output: connector size range, wire gauge 6-7 AWG for SDN40;
all other models: 16-10AWG (1.5-6mm2) for solid conductors.
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
Catalog Number
380 - 480 Vac
1
Yes
320 - 540 Vac
9
N/A
50/60 Hz
Typ. 1s
=+25°C )
amb
<35 V
>30.5 but <33 Vdc auto recovery
24 V (24 - 28 Vdc Adjustable)
< ±2 % overall
24.5 V ± 1%
<100 mVpp
20 A (480 W) (constant power,
not constant current)
40 A (960 W)
PowerBoost™
=+25°C)<50 ms from 95% to 10% rated voltage @ full load (T
amb
amb
SDN 40 uses active paralelling
70mm above and below or
25mm in front and 25mm left &
DEMKO 11 ATEX 1105449U
right
10
70mm above and below, 15mm in
front, 25mm left & right
0 to 3000 meters (0 to 10,000 feet)
5 Years
= 25oC)
amb
Safe low voltage: SELV (acc. EN60950)
= 18.5 Vdc = +/-5%
out
Externally fused
6. SDN 20 and 40 unit will go to HICCUP mode. SDN 5 and 10 will maintain min 4 secs to deliver
150% load then drops to almost zero V
when load rises above 150%.
7. All models except the 40amp unit are capable of parallel operation by use of a jumper pin,
accessible by the end user. 40 amp unit will have active current sharing signal.
8. SDN 40-24-480C only = Output signaling terminal block features (Shut down, Power Good,
Current Monitor, Current Balance, signal GND).
9. 70% maximum rated load.
10. Additional Installation requirements apply when used in hazardous locations. (refer to user manual)
. The output voltage will immediately drop to almost zero
out
=+25°C)
SDN-C Series Dimensions
W
D
H
Power Supplies
4
-
-
+
+
24 VDC/2.5A
OK
NEC Class2
Power Supply
24-28 V
Single
Parallel
SOLA
Power Supply
SDN 2.5-24-100P
SDN5-24-100C
U
C
USLISTED
L
115/230 VAC 1.3-0.7A50/60HZ
N
L
Catalog
Number
OK
SDN 5-24-100C
SDN 10-24-100C
SDN 20-24-100C
SDN 5-24-480C
SDN 10-24-480C
SDN 20-24-480CC
4.85 (123)1.97 (50)4.36 (111)
4.85 (123)2.36 (60)4.36 (111)
4.85 (123)3.42 (87)4.98 (127)
4.85 (123)1.97 (50)4.36 (111)
4.85 (123)2.36 (60)4.36 (111)
4.85 (123)3.35 (85)4.68 (119)
Dimensions - inches (mm)
HWD
Catalog
Number
SDN 40-24-480C
4.85 (123)7.09 (180)4.66 (118)
Dimensions - inches (mm)
HWD
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
105
4
SDN-C Series Mounting (cont.)
Power Supplies
Chassis Mounting
Instead of snapping a SolaHD SDN™ unit on the DIN Rail,
you can also attach it using the screw mounting set
SDN-PMBRK2.
This set consists of two metal brackets, which replace the
existing two aluminum proles.
Dimensions
SDN-C Series Mounting
DIN Rail Mounting
Snap on the DIN Rail:
1. Tilt unit slightly backwards
2. Put it onto the DIN Rail
3. Push downwards until stopped
4. Push at the lower front edge to lock
5. Shake the unit slightly to ensure that the retainer
has locked
Alternative Panel Mount: Using the optional SDN-PMBRK2
accessory, the unit can be screw mounted to a panel.
Visit our website at www.solahd.com or
106
contact Technical Services at (800) 377-4384 with any questions.
Detachment from DIN Rail:
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.