This manual contains important safety instructions� Read all safety, installation and operating instructions before
operating the SolaHD S5KC modular UPS system� Adhere to all warnings on the unit and in this manual� Follow all
operating and user instructions� Individuals must fully understand this equipment to install and operate it�
This product is designed for commercial/industrial use only� It is not intended for use with life support or other
designated critical devices� Maximum load must not exceed that shown on the rating label� Install and operate the
unit only in an indoor clean environment, free from conductive contaminants, moisture, ammable liquids, gases and
corrosive substances� This SolaHD S5KC contains no user serviceable parts other than the user replaceable modules� Refer
all faults to your local dealer, local representative or the Emerson SolaHD service group�
The SolaHD S5KC UPS system is designed for use on a properly earthed (grounded) “TN” electrical supply, for installation
by qualied personnel� A qualied electrician must review and approve customer supplied wiring, circuit breakers, and
intended loads and verify correct input, output, and earth connections to ensure compliance with the technical standards
and local electrical codes of practice� Installation instructions and warning notices are found in this manual�
!
WARNING
Risk of electric shock. Can cause equipment damage, injury and death.
The battery can present a risk of electrical shock and high short circuit current� The following precautions should be
observed before replacing the battery pack:
• Wear rubber gloves and boots
• Remove rings, watches and other metal objects�
• Use tools with insulated handles�
• Do not lay tools or other metal objects on the batteries�
• If the battery kit is damaged in any way or shows signs of leakage, contact your local representative immediately�
• Do not dispose of batteries in a re� The batteries may explode�
• Handle, transport and recycle batteries in accordance with local regulations�
!
WARNING
Risk of electric shock and re. Can cause equipment damage, injury and death.
Although the SolaHD S5KC UPS has been designed and manufactured to ensure personal safety, improper use can result
in electrical shock or re� To ensure safety, observe the following precautions:
• Clean the UPS with a dry cloth� Do not use liquid or aerosol cleaners�
• Never block or insert any objects into the ventilation holes or other openings of the UPS�
• Do not place the SolaHD S5KC where it might be damaged�
!
WARNING
Risk of electric shock. Can cause equipment damage, injury and death.
This UPS contains no user-serviceable parts except for the user-replaceable module assemblies� The UPS On/O push
button does not electrically isolate internal parts�
All service and maintenance operations must be performed by properly trained and qualied personnel� Under no
circumstances should unqualied or unauthorized personnel attempt to gain access to the internal portions of the
SolaHD S5KC�
ELECTROMAGNETIC COMPATIBILITY
The SolaHD S5KC complies with the limits of Category C2, pursuant to IEC/EN/AS 62040-2, and for a Class A digital device,
pursuant to Part 15 of FCC rules� Operation is subject to the following conditions:
• The output cables shall be no longer than 10m (32ft)�
• This device may not cause harmful interference�
• This device must accept any interference received, including interference that may cause undesired operation�
Operating this device in a residential area is likely to cause harmful interference that users must correct at their own
expense�
The SolaHD S5KC complies with the requirements of EMC Directive 2004/108/EC and the published technical standards�
Continued compliance requires installation in accordance with these instructions and use of accessories approved by
Emerson�
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F)� Install it in a clean
environment, free from moisture, ammable liquids, gases and corrosive substances�
Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or
the UPS performance alters in use� Refer all faults to your local service dealer�
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required
precautions� Keep unauthorized personnel away from the batteries� Proper disposal of batteries is required� Refer to your
local laws and regulations for disposal requirements�
Never block or insert any object into the ventilation holes or other openings�
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for example: electric
drills, vacuum cleaners, laser printers, hair dryers or any appliance using half wave rectication�
Storing magnetic media on top of the UPS may result in data loss or corruption� Turn O and isolate the UPS before
cleaning it� Use only a soft dry cloth; never use liquid or aerosol cleaners�
Information for the Protection of the Environment
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards, electronic
components)� The components removed must be taken to specialized collection and disposal centers�
NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This product has been supplied from an
environmentally aware manufacturer that complies with the Waste Electrical and Electronic Equipment (WEEE) Directive
2002/96/CE�
The crossed-out trash bin symbol at right is placed on this product to encourage users to recycle
components and units whenever possible� Please be environmentally responsible and recycle this
product through your recycling facility at its end of life� Do not dispose of this product as unsorted
municipal waste� Follow local municipal waste ordinances for proper disposal provisions to reduce the
environmental impact of waste electrical and electronic equipment (WEEE)�
For information regarding the scrapping/disposal of this equipment, please browse Sola Hevi Duty website (Products section or Contact us section) or call Emerson’s worldwide technical support�
Congratulations on your purchase of the SolaHD S5KC Uninterruptible Power System (UPS)� As with every other SolaHD
product, we stand behind our quality� If you have any questions concerning this UPS, please feel free to contact your local
dealer or SolaHD representative or call the appropriate Technical Support number listed on the back of this manual�
To ensure proper installation and operation of this unit, please read this manual thoroughly� The installation must be
completed by trained professionals and follow all local codes� General operation of the units can be conducted without
any specialized training�
This chapter provides the system description, features, operating principle, operating mode, main components and
specications of the SolaHD S5KC UPS�
1.1 System Description
The SolaHD S5KC power system is a modular UPS designed to provide high reliability� It is intended for use with
workstations, servers, networks, telecoms and other sensitive electronic equipment� It provides continuous, high-quality
AC power to your equipment, protecting it from any power disturbance due to blackouts, brownouts, surges or noise
interference�
The SolaHD S5KC UPS is an easily adaptable UPS system� By simply installing additional power or battery modules, you
can expand your current system capacity, extend your backup runtime, or provide redundancy� The SolaHD S5KC UPS
user interface enables the user to congure the operation according to application requirements� It also informs the user
on the status of the UPS and keeps a log of events�
The SolaHD S5KC series UPS contains both transformer-free and transformer-based UPS frames� The use of the
transformer-free or transformer-based frames is dependent upon the specic application requirements� The appearance
of the dierent frames is shown in Figures 1 through 4.
Table 1: Frame designation
UPS Model Number Digits 1-4Frame TypeFrame Rating
S5KCA or S5KE10 Bay Transformer-free15kVA redundant
S5KCB or S5KF16 Bay Transformer-free20kVA redundant
The operating principle of the SolaHD S5KC UPS is shown in Figure 5.
Input
S5KC SERIES USER MANUAL | 9
Manual Bypass
Output
EMI
Filter
Wiring
Power
Control
Figure 5: Operating principle diagram
The SolaHD S5KC UPS is composed of AC input, EMI lter, power module(s), battery module(s), user interface, control
interface, system control module, output and bypass contactor, manual bypass, output transformer (certain frames only)
and AC output�
The SolaHD S5KC UPS is a true online double-conversion system, having the following operating modes:
• Normal Mode
• Backup Mode
• Auto Restart Mode
• Bypass Mode
Normal Mode
The power module rectiers derive power from a utility AC source and supply regulated DC power to the inverter� The
module’s inverter regenerates precise AC power to supply the connected equipment� The battery charger is in the power
module and maintains a oat-charge on the batteries of the UPS; additionally, the optional charger module can also
charge the batteries to maintain a quicker recharge time for long backup time applications�
Backup Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains energy from the battery
modules� The output power will not be interrupted during the failure or restoration of the AC utility/mains source�
Auto Restart Mode
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will automatically restart
and resume supplying power to connected equipment� This feature is enabled at the factory, but can be disabled by the
user� The user can also program two auto restart delay settings from the LCD:
• Battery capacity level (%)
• Countdown timer
Bypass Mode
The bypass provides an alternate path for power to the connected equipment and operates in the following manner:
• Automatic: In the event of an internal fault or should the inverter overload capacity be exceeded, the UPS performs
an automatic transfer of the connected equipment from the inverter to the bypass source�
• Manual: Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the
bypass will cause an immediate transfer of the equipment from the inverter to the bypass source�
This section provides a general description of each component and its functions� Please review this section carefully, as it
will give you a better understanding of how the UPS operates�
1.5.1 UPS Frame
The UPS frames are shown in Figure 6.
Manual
Bypass
Breaker
Fan
(behind
display
bracket)
Manual
By
pass
aker
Bre
Fan
(behind
display
bracket)
10-Bay Transformer-Free UPS
16-Bay Transformer-Free UPS
Fan (behind
display
Fan
(behind
display
bracket)
Manual
Bypass
Breaker
Fans
12-Bay Transformer-Based UPS
bracket)
Manual
Bypass
Breaker
Fans
16-Bay Transformer-Based UPS
Figure 6: UPS frames, bezels removed
NOTE
In Figure 6, the power module and battery module are extended for illustration purposes only. Extending more than one
module at a time could cause the unit to tip over.
All UPS components are located in the SolaHD S5KC frame� The front of the UPS consists of a series of metal bezels� By
grasping these bezels from the sides and pulling straight out, you can remove the bezel to reveal the battery/power
module bays� The standard-model frame provides cooling fans and a manual bypass breaker on its top; the transformermodel frame provides a manual bypass breaker on its bottom and fans on both top and bottom� The user interface
module is located above the power/battery module bays for easy access, operation and for viewing UPS operating
information� On the lower right part of the user interface module, you will see the system control module bays�
The user interface module is the primary source of communication between the UPS and the user� The user interface
module permits:
• Viewing the UPS status
• Conguring the system
• Reviewing the event log
• Silencing the audible alarm
Refer to 4.0 - Operation and Display Panel for details on operating the user interface module�
1.5.3 System Control Module and System Monitor Module
The system control module and the system monitor module are the communication backbone of the UPS� They gather
input from all modules and process the data to control the operation of the system, including monitoring the condition
of each module� Except for the silkscreen, the appearance of the system control module and the system monitor module
is as shown in Figure 8.
Handle
Green Status LED
Yellow Fault LED
Figure 8: SolaHD S5KC system control module and the system monitor module
Under normal operation, the green status LED will blink and the yellow fault LED will be O� For any other condition, refer
to 5�0 - Troubleshooting�
Each power module is an independent 5kVA unit, consisting of a power factor corrected rectier, battery charger and
inverter, with associated monitoring and control circuitry� The modules are connected in parallel for greater capacity and/
or redundancy�
The power modules may be added or replaced on-line with no interruption or danger to the connected equipment or
user�
1.5.5 Battery Module
The battery module is shown in Figure 10.
Green Status LED
Yellow Fault LED
Locking Lever
Front View
Figure 10: Battery module appearance
When AC utility fails, the battery module will supply power to the load� Each battery module contains six individual 12V,
valve-regulated lead-acid (VRLA) battery blocks� Two battery modules are connected in series to form a battery string�
Each battery module has monitoring and controls to isolate the battery module in the event of a battery failure� The
battery strings are connected in parallel to provide backup time and/or redundancy�
NOTE
Two battery modules must be installed in the same row to make a complete battery string.
The battery modules may be added or replaced on-line with no interruption or danger to the connected equipment,
provided that the UPS is not operating on battery�
Under normal operation, the green status LED will blink continuously and the yellow fault LED will be O� For any other
condition, refer to 5.0 - Troubleshooting.
In AC mains mode, the charger module charges the system battery modules or external battery cabinet� Each charger
module is rated to deliver 10A charging current� The charger module has an independent control function and maintains
real-time communication with the system and the battery modules to ensure stable charging and fault protection�
The charger module may be added or replaced on-line with no interruption or danger to the user, connected battery
system or connected equipment�
1.5.7 External Battery Cabinet (EBC)
The external battery cabinet is divided into nine rows: the upper seven rows are for use with the intelligent battery
modules, and the lower two are used for overcurrent protection for each battery cabinet� For normal operation, two
battery modules must be inserted in the same row of the frame to create a complete string� The battery module strings
work in parallel to provide longer backup time for the UPS� A SolaHD S5KC can be congured with, at most, four external
battery cabinets� An external battery cabinet is shown in Figure 12.
This chapter describes UPS installation, including installation preparation, unloading the UPS, mechanical installation,
installing modules and cable connection�
2.1 Unpacking Inspection
Upon receiving the UPS, uncrate it and conduct the following checks:
• Inspect the UPS appearance for shipping damage� Report any shipping damage to the carrier and send a copy to
your Emerson® representative�
• Check against the delivery list to ensure that the package contains the correct number and type of accessories� If
there is any discrepancy, contact the distributor immediately�
2.1.1 Installation Environment
NOTE
Operating the UPS in temperatures above 77° F (25° C) will reduce battery life.
The UPS environment must be free of conductive contaminants and excessive moisture (water and condensation),
ammable vapors, chemical fumes, corrosive gases and liquids�
2.1.2 Installation Tools
The tools required to properly set up your UPS are listed below:
• Pallet jack
• 17mm (11/16”) wrench or socket
• 13mm (1/2”) wrench or socket
• 10mm wrench or socket
• #1 and #3 Phillips screwdrivers
• Torque wrench
2.1.3 Installation Site
Consider the weight and size of the SolaHD S5KC when deciding where to install the unit� Verify that the oor can support
the weight of a fully loaded unit, any accessories and external cabinets�
Verify that the UPS will be in a well-ventilated area with at least 12 inches (305mm) clearance behind it� The UPS is
air-cooled, utilizing internal fans� Air is drawn into the front of the UPS and is exhausted through ventilation grilles in the
back� The UPS should also have at least 39 inches (1m) clearance in front for service and to meet many local and national
building codes�
The unit frame is bolted to the shipping pallet to ensure safety during shipping� Emerson recommends keeping the unit
bolted to the pallet and using a pallet jack to transport the unit to its installation location�
NOTE
This UPS is very heavy. At least two people should assist in unloading it from the pallet.
To unload the UPS:
1. Move the UPS to its installation site and remove the package paper�
2. Use a 17mm (11/16”) wrench, to remove the four mounting bolts from the pallet brackets (see Figure 14).
3. Remove the mounting brackets from the UPS with a 10mm wrench or socket or a #3 Phillips screwdriver�
Figure 14: Remove the mounting brackets
4. Raise the four leveling feet to provide clearance between the pallet and the UPS frame�
5. Connect the ramp to the UPS pallet, as shown in Figure 15�
6. Roll the UPS slowly down the ramp until it is on a level surface, as shown in Figure 15�
6. Push the SolaHD S5KC frame slowly into the enclosure from the front, as shown in Figure 22. The rear of the UPS goes
into the rack rst when installing through the front of the rack�
Figure 22: Push the UPS frame into the rack
7. Use eight panel screws to secure the UPS frame to the rack posts, as shown in Figure 23.
NOTE
It might be necessary to use the leveling feet to get the holes to align
The SolaHD S5KC ships from the factory congured (modules prepopulated) and tested as a system to the customer’s
requirements� If any modules were removed to facilitate ease of installation, follow the steps below to reinsert them
properly�
2.4.1 Installing Power Module, Battery Module and Charger Module
1. Lift module to appropriate bay, resting end of module on bay shelf�
NOTE
Use caution not to rest the module on any of the bezels, this could damage the bezel.
Two battery modules must be installed in the same row to complete the battery string.
2. Push the module into the bay slowly� The module will not be locked until 1/3 is in�
a. At this point, lift the module up and continue pushing it until about 5cm of the module is still out of the bay�
b. Push it rmly and smoothly to ensure that the module is fully inserted, as shown in Figure 26�
1� Push module slowly into
the bay until it is 1/3 in�
4� Push module quickly and
rmly into the bay�
2� Raise the face
of the module�
50mm
3� Continue pushing module slowly|
until about 2” (50mm) remains out�
Figure 26: Insert the power module, battery module and charger module
3. Use a #2 Phillips screwdriver to install the module-securing bracket, and then press the lever down into the bracket,
as shown in Figure 27.
2.4.2 Installing System Control and System Monitor Modules
NOTICE
Risk of unintended shutdown� Can cause equipment damage�
Do not remove both the control and the monitor modules at the same time� Removing both the control module and
monitor module at the same time will cause the UPS to shut down and remove power from the load� Replace these
modules one at a time�
1. Remove the display bezel and the user interface (LCD) module on top of the frame, as shown in Figure 28.
Large Display Bezel
User Interface Module
Figure 28: Remove large display bezel and user interface module
2. Push the module slowly until about 1cm (2�54 in�) of the module is still out of the bay, and then press it rmly to
ensure that the module is fully inserted, as shown in Figure 29�
10mm
Insert
module
here
Figure 29: Insert the System Control and System Monitor module
3. Use a #2 Phillips screwdriver to install the screws into the holes on each end�
A junction box is factory-installed on each model of the SolaHD S5KC to ease cable connection� Select the appropriate
input cables according to Table 3 and Table 4 based on the UPS rating and mains frequency; however, it is recommended
that you size the over current protection and wiring for the frame rating to easily allow upgrades to the UPS system�
Table 3: Input cable selection list—60Hz
Input voltage - 200VACInput voltage - 208VACInput voltage - 240VAC
Maximum System
Rated Load
5kVA27A50A26A50A23A50A
10kVA53A63A51A63A45A63A
15kVA80A100A77A100A67A100A
20kVA106A125A102A125A90A125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable
cross-sectional area is 16mm2 (6AWG); the rated torque is 4�52Nm (40 in-lb)�
Use of 90°C copper wire is recommended
Maximum
Current in UPS
Mode
Table 4: Input cable selection list—50Hz
Input Voltage - 220VACInput Voltage - 230VACInput Voltage - 240VAC
Maximum System
Rated Load
5kVA25A50A24A50A23A50A
10kVA49A63A47A63A45A63A
15kVA73A100A70A100A67A100A
20kVA97A125A93A125A90A125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable cross- sectional area is
16mm2 (6AWG); the rated torque is 4�52Nm (40 in-lb)�
Use of 90°C copper wire recommended
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Recommended
Input Protection
Circuit Breaker
To connect the cable:
NOTE
Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box (see Figure 31) and pull the cables through them, leaving some slack for
2. Connect the cables to the corresponding terminal of the power input and output terminals�
3. Tighten the screws to 4�52Nm (40 in-lb) with a 13mm (1/2”) torque wrench�
4. Respectively, secure the conduit of the input/output cables through the cable bridges on the rear panel of the UPS
(see Figure 31)�
The connection methods in the single-phase input mode and the 3-phase input mode are shown in Figures 32 and 33, respectively� Installation of the factory-provided copper bar is essential in the single-phase input mode� The copper
busbar is in the accessory bag included with the UPS�
* This connection requires the factory-provided three-position busbar to connect the three terminal block positions
System
Nominal
Frequency
1234PE12PE
Input Terminal BlockOutput Terminal Block
2.5.2 Transformer-Based UPS Cable Connection
NOTE
After the output transformer is installed, if the startup is on bypass, the UPS has a six-cycle inrush current that is up to 20 times
the rated output current. This must be taken into account when selecting the input overload protection device at the AC input
supply distribution point.
To avoid random tripping on startup, Emerson® recommends that the AC input supply be protected with a circuit breaker
capable of withstanding this initial inrush (the MCB is derated according to the D curve or TYPE 4).
This UPS is tted with EMI lters. Earth leakage current is less than 40mA. Transient and steady state earth leakage currents may
occur when starting the UPS. This should be taken into account when selecting transient RCCB or RCCD (leakage current devices
of the UPS and load).
The MCB of the AC power supply connected to the UPS input must bear this warning:
Disconnect the connection with UPS before maintaining this circuit.
The warning is required because the UPS has no autofeeding protection device. The UPS grounding should be in accordance
with local regulations.
A junction box is factory-installed on all models of the SolaHD S5KC to ease cable connection�
Select the appropriate input cables according to Table 6 and Table 7 based upon the UPS rating and mains frequency�
Emerson recommends sizing the frame’s overcurrent protection and wiring to permit easier UPS system upgrades�
Table 6: Input Cable Selection for Transformer-Based Frames (60 Hz)
Input Voltage - 200VACInput Voltage - 208VACInput Voltage - 240VAC
Maximum System
Rated Load
5kVA27A50A26A50A23A50A
10kVA53A63A51A63A45A63A
15kVA80A100A77A100A67A100A
20kVA106A125A102A125A90A125A
The power input and output terminals accept a maximum cable cross-sectional area of 70mm2 (2/0AWG); the minimum cable cross-sectional area is
16mm2 (6AWG)� The rated torque is 12�43Nm (110 in-lb)�
90°C copper wire recommended�
Table 7: Input cable selection for transformer-based frames (50 Hz)
Input Voltage - 220VACInput Voltage - 230VACInput Voltage - 240VAC
Maximum System
Rated Load
5kVA25A50A24A50A23A50A
10kVA49A63A47A63A45A63A
15kVA73A100A70A100A67A100A
20kVA97A125A93A125A90A125A
The power input and output terminals accept a maximum cable cross-sectional area of is 70mm2 (2/0AWG); the minimum cable
cross-sectional area is 16mm2 (6AWG)� The rated torque is 12�43Nm (110 in-lb)�
90°C copper wire recommended�
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Conguring the Bypass Voltage
The UPS bypass voltage is factory-set and the copper busbar jumper has been factory-installed� If the jumper setting does
not match the input source, the bypass voltage jumper may need to be changed to ensure the correct output voltages
are provided when operating in bypass mode� Refer to Table 9 for the proper setting location according to the AC mains
voltage available and to Figures 34 and 35 for the jumper setting location�
Jumper
Figure 34: Setting bypass voltage jumper (default: 208VAC)
Jumper
Figure 35: Setting bypass voltage jumper (200/220/230/240VAC)
The UPS contains an isolation transformer that generates a neutral conductor for the connected load� The UPS is a
separately derived source and contains a neutral/earth jumper� A factory-installed neutral/earth jumper copper bar may
require removal to comply with local codes and regulations�
Neutral/Earth Jumper
Neutral/Earth Jumper
2
1
Figure 36: Conguring the neutral/earth jumper
Connecting Cables
To connect the cable:
NOTE
Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box (see Figure 37) and pull the cables through them, leaving some slack for
installation�
Output Cable Knockout
16-Bay SolaHD S5KC
With Transformer
Input Cable Knockout
12-Bay SolaHD S5KC
With Transformer
Output Cable Knockout
Input Cable Knockout
Figure 37: Knockouts
2. Connect the cable to the corresponding terminal of the power input and output terminals� Using a torque wrench,
tighten the screws to 12�43Nm (110 in-lb)� The connections are shown in Figure 38.
If the bypass voltage jumper copper bar is connected incorrectly, the system will report a fault alarm�
When wiring to single-phase panels, connect to output terminals 1, 3, 4 and PE (GND) only�
Set Output
Voltage by LCD
Bypass Voltage JumperOutput Voltage (Between Terminals)
208V TAP (1-2)240V TAP (2-3)1-43-42-31-3
173
(Do Not Use)
190
(Do Not Use)
199
(Do Not Use)
Table 10 shows the maximum load capacity of the output winding of the transformer-based UPS�
Table 10: Maximum Load Capacity of the Output Wiring
A junction box is factory-installed on all models of the SolaHD S5KC to ease cable connection� Select the appropriate
input cables according to Tables 11 and 12 based on the UPS rating and mains frequency� Emerson recommends sizing
the overcurrent protection and wiring for the frame rating for easing upgrades to the UPS system�
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable cross- sectional area is
16mm2 (6AWG); and the rated torque is 4�52Nm (40 in-lb);�
90°C copper wire is recommended�
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable
cross-sectional area is 16mm2 (6AWG); and the rated torque is 4�52Nm (40 in-lb);
90°C copper wire is recommended�
Maximum
Current in UPS
Mode
Input Voltage – 220/110VACInput Voltage – 230/115VACInput Voltage – 220/127VAC
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Maximum
Current in UPS
Mode
Recommended Input
Protection Circuit
Breaker
Recommended
Input Protection
Circuit Breaker
To connect the cable:
NOTE
Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box (see Figure 31) and pull the cables through them, leaving some slack for
installation�
Output Cable Knockout
Input Cable Knockout
10-Bay SolaHD S5KC
No Transformer
Output Cable Knockout
Input Cable Knockout
16-Bay SolaHD S5KC
No Transformer
Figure 39: Knockouts
2. Connect the cables to the corresponding terminal of the power input and output terminals�
3. Tighten the screws to 4�52Nm (40 in-lb) with a 13mm (1/2 in) torque wrench�
Up to four external battery cabinets may be connected to the SolaHD S5KC Series UPS to provide longer battery run
times�
The external battery cabinet (EBC) requires the use of one of the optional EBC cable kits for connection to the UPS� The
optional cable kits each contain the power and communication cables required for proper operation and monitoring of
the battery modules� The standard cable kit lengths are 1, 3, and 5 meters (3�2, 9�8 and 16�4 ft�) to accommodate dierent
site installation requirements�
To connect an external battery cabinet:
1. Verify that the EBC DC circuit breaker is open� The circuit breaker is on the front bottom of the EBC frame behind the
bottom two bezels�
2. Connect one end of the battery cable to the external battery connector on the rear of the UPS frame�
3. Connect the other end to the closest corresponding port on the rear of the EBC frame, as shown in Figures 42
and 43�
4. Install and tighten the grounding screw on the battery cable assembly, on both the UPS and EBC ends� This screw also
secures the cable assembly to the frames to prevent accidental disconnection�
5. For new systems that included an EBC, the EBC communication card should already be installed in the UPS frame
(IntelliSlot Port #3, typically)� If it is not already in the UPS frame, obtain the EBC communication card and insert it
into any open IntelliSlot port (preferably Port #3)� Connect the provided EBC communication cable to the UPS and
EBC as shown in Figures 42 and 43�
6. Check the EBC DIP switch settings on the top rear of each EBC frame� Verify they are set correctly according to
Table 13�
7. Close the EBC DC circuit breaker and replace the bezels back onto the EBC�
!
WARNING
Risk of hazardous voltage between UPS frames. Can cause damage to equipment, injury and death.
Failure to open the EBC DC circuit breaker before connecting or disconnecting the battery cable between the UPS
and EBC frames can result in hazardous voltages being present between the frames.
If the number displayed is not consistent with the actual installation number of external battery cabinets:
• Ensure each external battery cabinet contains two battery modules installed on the same row and both have the
locking levers in the locked position�
• Ensure the IntelliSlot® EBC card is installed properly and the communication cables are fully inserted in the
connectors�
• Determine that the DIP switch setting of each battery cabinet is correct using the following table
Table 13: EBC DIP Switch Settings
External Battery
Cabinet Number
EBC #1UPUP
EBC #2DownUP
EBC #3UPDown
EBC #4DownDown
DIP Switch Setting
12
2.5.5 Connecting Integrated Power AC Distribution (PAD)
The rear panel of the SolaHD S5KC UPS provides the capability to add integrated distribution outlets (PADs) as an option
to allow direct AC power connection of the supported equipment to the UPS� These PADs are intended to allow the user
to install and even change distribution, if necessary as equipment changes, while the UPS is still providing power� Follow
these steps to properly and safely add or change the optional PADs�
1. Ensure that the PAD breaker is in the O position�
NOTE
This is the breaker located near the PAD port.
2. Using a Phillips screwdriver, remove the two screws that are at the top of the PAD cover plate and retain these for
reattaching the PAD�
3. Remove the PAD cover plate to expose the PAD connectors�
4. Insert the bottom of the PAD into the slot provided, and then connect the PAD connectors�
NOTE
The connector should connect only one way, matching the color of the pins.
NOTE
Distribution PADs PD2-101, PD2-102, PD2-103, PD2-104, PD2-105, PD2-106 and PD2-107 should not be used if the UPS output
voltage is set to 220/127V.
NOTE
When connecting distribution PAD’s to an S5KCC or S5KCD frame, the L-L output receptacles will connect to the 240V taps of the
output transformer, not to the 208V tap. Verify receptacle voltage and load ratings before energizing the load.
5. Secure the PAD by using the two screws removed in Step 2�
6. Repeat Steps 1 through 5 to install a second PAD on the SolaHD S5KC (only the 16-bay frame has two PAD ports)�
7. Connect the equipment to the appropriate outlets�
8. Close the PAD breaker(s) to connect AC power to the outlets�
9. After commissioning the UPS, turn On the connected equipment per the manufacturer’s instructions (see 2.5.6 -
Commissioning/Startup Procedures)�
2.5.6 Commissioning/Startup Procedures
The SolaHD S5KC can be commissioned with or without AC power being connected� Follow these steps for the initial UPS
system startup:
Checks Before Commissioning/Startup
1. Verify that the AC power connections are wired properly and all connections are tight�
2. If using external battery cabinets or third-party battery systems, verify that the DC power and communication cables
are connected properly and all connections are tight�
3. Measure and record the AC input voltage and frequency� This will be needed to properly congure the output voltage
of the SolaHD S5KC system�
4. If any modules within the SolaHD S5KC system were removed during installation, verify that all modules are fully
inserted and that the module locking levers are in the locked position�
5. If the UPS is being connected into a Remote Emergency Power O (REPO) circuit, refer to 3.3 - REPO (Remote
Emergency Power O) for the REPO connection details and instructions� If no REPO circuit is required or used, the factory-installed jumper must be removed from the terminal block Pins 9-10 as described in 3.2 - Dry Contact Ports�
6. Verify that the UPS internal bypass breaker is in the open position with the guard in place and secure�
Commissioning/Startup with AC Power Available (Normal Mode Operation)
1. Verify that the upstream mains AC breaker is closed�
2. Turn On the UPS Enable switch on the rear of the unit (it is protected by a clear plastic cover)�
3. Close the UPS input breaker: it is on the front of transformer-free frame systems and on the rear of transformer-based
frame systems�
NOTE
This will begin the initial system checks and enable power to begin charging the battery
4. Press the ON/OFF button on the LCD panel�
5. When asked to conrm, press Enter (F5 button) to turn On the UPS�
6. Close the UPS output breaker on the rear of the unit�
7. If supplying power to an external distribution panel, close all breakers to provide power to the equipment� If using
the integral distribution PADs on the UPS or MBC, ensure the individual PAD breakers are closed�
Commissioning/Startup Without AC Power Available (Battery Mode Operation)
NOTE
Starting the UPS system without AC power will discharge the batteries. If AC mains power is not restored before the batteries
discharge, the UPS will shutdown and power will be lost to the connected equipment. If the UPS reaches the battery EOD level
and shuts down, AC mains power must be present to restart the UPS system.
1. Check to ensure the upstream mains AC breaker is closed�
2. Turn on the UPS “Enable” switch on the rear of the unit�
3. Locate the “Battery Start” push button that is on either of the two control modules� Press and hold this button for 5
seconds�
NOTE
This will begin the initial system checks and automatically enable output power.
4. Press the On/O button on the LCD panel�
5. When asked to conrm, press Enter (F5 button) to turn On the UPS�
6. Close the output breaker on the rear of the SolaHD S5KC�
7. If supplying power to an external distribution panel, close all breakers to provide power to the equipment� If using
the integral distribution PADs on the UPS or MBC, verify that the individual PAD breakers are closed�
8. Emerson recommends closing the UPS input breaker; it is on the front of transformer-free frame systems and on the
rear of transformer-based frame systems� If AC mains becomes available, the UPS will revert to AC power mode and
begin recharging the battery�
The rear panel of the SolaHD S5KC provides these communication ports:
• IntelliSlot® ports: 3
• Dry contact ports: 1
• REPO (Remote Emergency Power O): 1
• Long Run Time (LRT) Battery Temperature Probe Terminals: 1
• USB port: 1
3.1 IntelliSlot Ports
The three IntelliSlot communication ports (see Figure 45) are used for installing communication options, including the
IntelliSlot Unity card, dry contact card, MultiPort and IntelliSlot EBC card� The IntelliSlot ports and the USB port can be
used at the same time�
IntelliSlot
Ports
IntelliSlot Ports
(with protective covers)
Figure 45: IntelliSlot communication port location
IntelliSlot Unity Cards — IS-UNITY-DP
• IS-UNITY-DP: This optional card can be used instead of the standard card if communication to two third-party
platforms is required� Third-party platforms include SNMP and 485 (Modbus/Bacnet) protocols� This card would
still be used for communication between the SolaHD S5KC UPS and Emerson’s Trellis NMS and LIFE Services� All
communication protocols are active simultaneously�
IntelliSlot® Dry Contact Card (IS-RELAY)
Provides dry contact alarm information, including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and
On UPS signals for communication to a remote monitoring system or for use with MultiLink® software� This card also can
accept input signals to shut down the UPS while it is in any mode of operation�
Provides dry contact alarm information, including: On Battery, Low Battery signals for communication to four servers for
use with MultiLink software�
IntelliSlot EBC Card
This card is used for the SolaHD S5KC UPS to monitor and manage the intelligent battery modules in external matching
battery cabinets�
3.2 Dry Contact Ports
The UPS provides dry contact ports� See Figure 1 for location and Figure 46 for the pin layout�
Figure 46: Pin layout of the dry contacts
Table 14 shows the pin denition of each dry contact port�
Table 14: Pin Denition of Dry Contact Port
PositionNameDescription
1Battery ModeOutput dry contact of battery mode operation
2Battery ModeOutput dry contact of battery mode operation
3Low BatteryOutput dry contact of low battery operation
4Low BatteryOutput dry contact of low battery operation
5Any Mode Shut DownInput dry contact of any mode shut down
6GNDAny mode shutdown GND
7Battery Mode Shut DownInput dry contact of battery mode shut down
8GNDBattery mode shutdown GND
Battery Mode Dry Contact
Pins 1 and 2: Output dry contact, normally open� The dry contact is closed when the UPS is operating on battery� The
maximum voltage and current are 24VDC and 0�3A, respectively�
Low Battery Dry Contact
Pins 3 and 4: Output dry contact, normally open� When the UPS is operating on battery, the dry contact is closed upon
battery low voltage alarm� The maximum voltage and current are 24VDC and 0�3A, respectively�
Any Mode Shut Down
Pins 5 and 6: Input dry contact, normally open� After the external dry contact is closed (shorted), the UPS output will be
shut down during any mode of operation (mains, battery, bypass)�
Pins 7 and 8: Input dry contact, normally open� After the external dry contact is closed (shorted), the UPS output will be
shut down only during battery mode operation�
NOTE
The default for the Any Mode and Battery Mode Shutdown features is disabled. Using this function requires setting Remote
Comms shutdown to Enabled in the Settings through the LCD. Additionally, the shutdown delay can be accessed in the LCD
Settings to set the delay time for the UPS shutdown after the dry contact is closed. Enabling the feature on the LCD enables both
shutdown methods.
3.3 REPO (Remote Emergency Power O)
The SolaHD S5KC is equipped with a REPO (Remote Emergency Power O) connection� Only the SELV (Safety Extra Low
Voltage) circuit can be connected to the REPO terminal block� Figure 48 shows the REPO connection pin layout� See Table
15 for the pin denition�
Figure 47: REPO connector pin layout
Table 15: Pin Denition of the REPO Dry Contact
PositionNameDescription
9REPO +12VREPO power, 12VDC 100mA
10REPO Coil -NOREPO normally open nodes, shorting pins 9 and 10, REPO is triggered
11REPO Coil -NC
12GNDGND
Figure 47 shows the schematic diagram of REPO switch connections�
910
Figure 48: REPO switch connections
!
WARNING
Risk of electrical shock. Can cause property damage, injury and death.
Operating the REPO circuit will NOT trip the manual bypass breaker. If the REPO must shut o UPS output under
all circumstances, the user must tie the REPO into the breaker feeding the UPS source. Otherwise, voltage may be
present on the output connections if the unit is in manual bypass.
REPO normally closed nodes (fail-safe), shorting pins 9, 10, 11, 12,
and opening pins 11 and 12, REPO is triggered
Risk of improper installation� Can cause unintended UPS shutdown and loss of power to the load�
Run signal cables separately from power cables� Running cables in the same conduit can cause signal noise, possibly
causing the system to shut down�
NOTE
A jumper is factory-installed between Pins 9 and 10 to disable the Main Control Switch. This will prevent the UPS from being
started accidentally during shipment and installation. This jumper must be removed before the unit can be started.
If the installation does not require connection to a REPO system, the factory-installed jumper must be removed�
3.4 Long Run Time (LRT) Battery Temperature Probe Terminals
The SolaHD S5KC contains a temperature-compensated battery charging system� To use this feature with external LRT
battery systems, Pins 13-16 of the contact terminal strip are used to connect a temperature sensor� See Figure 49 and
Table 16 for the pin denition of the temperature sensor terminals�
Figure 49: Pin layout of the temperature sensor terminal
Table 16: Pin Denition of the Temperature Sensor Terminal
PositionNameDescription
13Inside Battery TemperatureLocate battery temperature signal close to the UPS
14Battery Temperature +12VBattery temperature signal power supply
15Outside Battery Temperature Locate battery temperature signal at UPS remote end
16GNDGND
3.5 USB Port
The SolaHD S5KC UPS contains a standard B type USB port on the rear of the unit to connect the UPS to a network server
or other computer for monitoring using any operating system, built-in UPS support or in conjunction with MultiLink®
software�
MultiLink monitors the UPS continuously and can shut down congured computers in the event of an extended power
failure� MultiLink can also be congured to shut down the UPS� MultiLink can also be congured for use without the USB
cable when the IntelliSlot® UNITY-DP SNMP Card is installed in the UPS� An optional MultiLink License Kit permits shutting
down the UPS over a network� For more information about the IntelliSlot SNMP Card, IntelliSlot Web Card and MultiLink
license kits, visit Sola Hevi Duty website or contact your local representative�
3.7 LCD Port
The LCD module contains the LCD port, which is used for power and data communication between the UPS monitor
module and display module� The LCD module can be removed from the SolaHD S5KC and remotely located� A longer
Ethernet cable must be used when installing the LCD module remotely� A standard Ethernet (Category 5, with RJ-45
connectors, both ends meet T568B standard) type cable can be used� Maximum cable length is 14 meters to ensure
proper communication signals between the UPS and the LCD module�
The user interface module provides three network ports and one USB port� Of those, one network port (LCD port) is used
for power supply and communication of the user interface module� Other network ports and the USB port are reserved
for use only by customer service personnel�
This chapter describes the functions and operation of the UPS display panel� The LCD is composed of an LED mimic power
ow diagram, fault LED indicator and LCD screen to show detailed operational information and UPS alarm list using the
menu buttons� For location and information about the display panel, refer to Figure 51 below
Figure 51: Operation and display panel
Mimic LEDs
The mimic power ow LEDs indicate current operating state of the UPS� The state descriptions of the LEDs are given in
Table 17�
Table 17: LED Descriptions
LEDStateDescription
On (Green)The rectier is functioning normally
AC LED
Battery LED
Bypass LED
Inverter LED
Output LED
Fault LED
Flashing (Green)The AC mains is normal, but the rectier is not functioning properly
On (Red)The rectier is faulty
OThe AC mains is abnormal, and the rectier is not functioning
On (Green)The battery is discharging
Flashing (Green)The battery has a pre-alarm of low voltage
On (Red)The DC-DC converter is faulty
OThe battery is charging, and the DC-DC converter is not functioning
On (Green)The bypass is supplying power
On (Red)The bypass is abnormal and not available
OThe bypass is normal, but not supplying output power
On (green)The inverter is supplying output power
Flashing (green)The inverter is starting up, in soft start or phase locked, and is not supplying output power
On (red)The inverter is faulty
OThe inverter is o
On (green)The UPS output is supplying power
Flashing (green)The UPS internal manual bypass is supplying output power
On (red)The UPS has output overload
OThe UPS does not have output power
On (yellow)The UPS has an alarm or alarms
On (red)The UPS has one or more faults
OUPS operating normally with no alarm or fault conditions
Three dierent audible alarms may occur during the UPS operation; see Table 18 for a description of the audible alarms�
Table 18: Audible Alarm Descriptions
Alarm soundMeaning
One beep per secondWhen the UPS has an alarm, for example, AC fault (mains failure)
One beep every 0.5 secondUpon UPS output overload or low battery voltage alarm during discharge
Continuous beepWhen the UPS has a fault
Control Buttons
The operation and display panel provides two control buttons� See Table 19 for their function descriptions�
Table 19: Control buttons functions
Control ButtonFunction
ON/OFF ButtonUsed to turn the UPS On and O
Alarm Silence Button
When an audible alarm sounds, pressing this button can silence the alarm|
Pressing this button again can restart the audible alarm�
LCD and Menu Buttons
The operation and display panel provides an LCD screen and ve menu buttons (F1, F2, F3, F4, F5)� See Table 20 for the
function description of each menu button�
Table 20: Function Descriptions of Menu Buttons
ButtonF1F2F3F4F5
Function 1
HOME
Function 2—ESC Exit
The LCD is a 320 × 240 dot matrix graphic display� Through the LCD interface and the easily operated menu, you can
browse the UPS input, output, load and battery parameters and obtain the current state and alarm information of the
UPS� You also can perform relevant function/parameter settings and control operations�
When the UPS starts up, it will conduct a self-test, and the LCD will display the startup screen, which lasts for 15 seconds
as shown in Figure 53�
Industrial Automation
Figure 53: Startup screen
4.2.2 Main Screen
The main screen is divided into four parts: system information window, data window, menu window and keyboard
window, as shown in Figure 54�
Figure 54: Main screen
The functions of F1 ~ F5 buttons will change automatically according to the currently-displayed screen� On any screen,
pressing the F1 button will return to the Output screen�
System Information Window
The system information window displays the current time and the UPS name without requiring user intervention� See
Table 21 for the detailed description�
Table 21: Item Description of System Information Window
The menu window shows the menu name and allows navigation to dierent menu items� Each menu item has a set of
data that is displayed in the data window� Using the menu window, you can browse the relevant parameters of the UPS
and can adjust/set some operational parameters� See Table 22 for the menu and data descriptions�
Table 22: Item Description of Menu Window and Data Window
Menu NameData ItemData Description
L-N Voltage (V)L-N input voltage
L-N Current (A)L-N input current
Mains
Battery
Output
Load
UPS Info
Redundant State
Frequency (Hz)Input frequency
L-L Voltage (V)L-L input voltage
kVAInput apparent power
Power FactorInput power factor
Batt Voltage (V )Battery bus voltage
Batt Current (A)Battery bus current
Runtime (Min�)Battery backup time remaining
Batt Capacity (%)Percentage of battery capacity
Batt StateCharging, discharging or fully charged
Batt String CountOnline battery string count
Batt Temp (°C)Battery temperature
Discharge CountMaximum historical discharge count within current battery modules
Discharge Time (H)Maximum historical discharge time within current battery modules
EBC CountNumber of connected External Battery Cabinets
L-N Voltage (V)L-N Output Voltage
L-N Current (A)L-N Output Current
Frequency (Hz)Output Frequency
Power FactorOutput Power Factor
Line Voltage (V )L-L Output Voltage (not displayed for single-phase output model)
kVAOutput apparent power
kWOutput active power
Load Level (%)Output loading, indicated in percentage of the UPS system rated load
Crest FactorOutput current peak value factor
UPS IDUPS ID
LCD ModuleIf the module is online, the serial number and software version will be displayed
Bypass Monitor ModuleIf the module is online, the serial number and software version will be displayed
Bypass Control ModuleIf the module is online, the serial number and software version will be displayed
Charger ModuleIf the module is online, the serial number and software version will be displayed
Power ModuleIf the module is online, the serial number and software version will be displayed
Battery ModuleIf the module is online, the serial number and software version will be displayed
PM InstalledThe number of installed power modules
PMWhether there are redundant power modules supplying power�
Table 22: Item Description of Menu Window and Data Window (continued)
Menu NameData ItemData Description
Disabled/ Enabled� If ‘Enabled,’ the system operational parameters will assume there is a
redundant power module in the frame; if ‘Disabled’, the system operational parameters
will assume that all power modules in the frame are not redundant�Note: This item is
closely related to the ‘Redundant alarm’ setting
Disabled/ Enabled� If ‘Enabled,’ this allows the UPS output power to be shutdown through
remote communication, including the dry contacts and IntelliSlot® communication cards�
Note: This item is closely related to ‘Remote shutdown delay’
Disabled/ Enabled� If ‘Enabled,’ once a low battery alarm is generated during a battery
discharge, the UPS will continue battery mode operation until it reaches the end of
discharge (EOD) setpoint, then will shutdown output power, whether the AC mains
recovers or not�
Because the slot 2 and the serial port on the rear panel cannot work at the same time, you
must select one of them to work� If ‘INTERFACE2’ is selected, the slot 2 can communicate; if
‘RS232’ is selected, the serial port can communicate�
Sets the battery capacity limit of auto restart feature� When AC mains power returns,
the UPS will charge the battery to the specied battery capacity before enabling output
power�
Sets the delay time of auto restart feature� When AC mains power returns, the UPS will
start a countdown timer based upon the setting before enabling output power�
Users can change the command password to prevent unauthorized user from changing
any user congurable settings� The default password is 1234567� Once the password is
changed, the default password is no longer operational and users are then required to
enter the new password to enter/change any ‘Settings’ or ‘Battery settings’� If the new
password is forgotten, contact your local customer service center for steps to reset the
password back to the factory default�
Sets the threshold of maximum load alarm� When the UPS loads exceed the threshold,
and the maximum load alarm is enabled, an alarm will be generated� This item is closely
related to ‘Max load alarm,’ for example, set this item to 5�0kVA, when the UPS loads
exceed 5�0kVA, an alarm will be generated�
Settings
Set Redundancy Mode
Remote Comms Shutdown
Bypass SettingEnables the bypass to supply power or not
Output FrequencySets the output frequency to allow frequency conversion operation
Output VoltageSets the output voltage level to match the mains input voltage
Inverter Sync RangeSets the range of inverter synchronization for bypass frequency operation and availability
Remote Shutdown DelaySets the shutdown delay time for the remote signal operation
Bypass Upper LimitSets the upper limit of bypass voltage operation and availability
Bypass Lower LimitSets the lower limit of bypass voltage operation and availability
Guaranteed Shutdown
Bypass Alarm ModeAllows an alarm to be generated when the bypass is abnormal
Set RS232 Protocol
Auto-Restart ModeAllows auto restart after a EOD shutdown and AC mains returns
Auto-Restart Capacity
Auto-Restart Delay
Display ContrastAdjusts the contrast of LCD backlighting
Date and TimeSets date and time
Command Password
Max Load AlarmSets a maximum load alarm� This item is closely related to ‘Max load threshold�’
Max Load Threshold
Redundant Alarm ModeAllows alarm to be generated when the system loses redundant power module
Table 22: Item Description of Menu Window and Data Window (continued)
Air Filter ReminderSet the reminder period of checking dust-proof lter
Air Filter Type
Settings (continued)
Battery settings
LanguageLanguage Options
AlarmsCurrent AlarmsDisplays the current alarms� See Table 25 for the UPS alarm list
RecordsHistorical AlarmsDisplays all historical alarms� See Table 25 for the UPS alarm list
Module replacement
IT System Compatibility
UPS ID
Company NameSet the local service company name of the UPS
Contact NumberSet the local service telephone number of the UPS
Load factory DefaultsRestores the setting items in ‘Settings’ menu to factory values
Low battery WarningSets the battery low voltage alarm time
Automatic Battery Test Interval
Auto Batt Test Start DaySets the day of the week for the automatic battery test
Auto Batt Test Start TimeSets the time of the day for the automatic battery test
External Battery AH
Load Factory DefaultsRestores the setting items in ‘Battery set’ menu to factory values
LCD ModuleDisplays the procedures for replacing LCD module
Bypass Monitor ModuleDisplays the procedures for replacing system monitor module
Bypass Control ModuleDisplays the procedures for replacing system control module
Power ModuleDisplays the procedures for replacing power module
Battery ModuleDisplays the procedures for replacing battery module
Charger ModuleDisplays the procedures for replacing charger module
Sets the UPS device address� This setting is only for the network card
communication of newly emerging market�
Standard: Use this setting if air lter is not installed�
Fine Dust: Use this setting if air lter is installed�
Enabled - Neutral back-feed relay will open on battery mode
Disabled (Default) - Neutral back-feed relay is always closed
Users can set the UPS name to facilitate managing the UPS through remote
communications
Sets the interval for the automatic battery test� Intervals of 8, 12, 16, 20, 26
weeks or Disable are available for selection� Factory default is 8 weeks�
Sets the AH capacity of external third party battery system to calculate the
battery capacity and estimate the battery time remaining
Provides a selection of seven languages:
Chinese, English, French, Spanish, Italian, Russian and German
UPS IDAllows customer service personnel to set the UPS ID, to facilitate maintenance
Site IDAllows customer service personnel to set the UPS address, to facilitate maintenance
Service
The Service screen is only for customer service personnel; it is not open to the user�
Tag NumberAllows customer service personnel to set the UPS tag, to facilitate maintenance
Company Name
Contact Number
Frame S/NReset this when replacing the LCD board� The frame S/N is labeled on the frame�
Normal ModeAllows customer service personnel to set the UPS operating mode to normal online mode
ECO ModeAllows customer service personnel to set the UPS operating mode to ECO mode
Enable Max Discharge
Protection
Disable Max Discharge
Protection
Battery maintenance test allows battery to discharge some voltage to obtain the battery
activity� The loads must be within 0% ~ 90%, the battery capacity must be larger than
70%, and there is no battery fault and alarm in the system�
A UPS self-test, used to test whether the LEDs are normal� When you start this function, 5
seconds later, the screen will prompt a window to display the system self-test result�
Allows customer service personnel to set the UPS company name, to facilitate
maintenance
Allows customer service personnel to set the UPS company contact number, to facilitate
maintenance
By default, the UPS has a maximum discharge time to protect the batteries from a deep,
slow discharge� After this time, the UPS will turn O its output�
If this variable is set, there will be no time limit and the UPS will stay on battery until the
EOD setpoint is reached� This may cause damage to some battery types and should only
be used for DC sources that do not have slow discharge issues�
Keyboard Window
For the functions of the menu buttons (F1 ~ F5) in the keyboard window, see Table 23
During the UPS operating process, if there are no active alarms, the LCD will go into a screen saver mode after 2 minutes
of no user navigation activity� The default screen saver is shown in Figure 55� After a brief delay, the LCD backlight will
also turn O� Pressing any button will return to the original screen�
Figure 55: Default screen/screen saver
4.3 LCD Screen Views
This section gives a detailed description of each display screen and its contents� The default “main screen” is the Output
menu and its data� The navigation indicated for each screen below is in reference to the Output screen�
4.3.1 AC Mains Screen
From the main screen, press the F3 button twice, until the AC mains screen is displayed, as shown in Figure 56�
Figure 56: Mains screen
The AC mains screen displays the input L-N voltage, L-N current, input frequency, L-L voltage, apparent power and power
factor of three phases (L1, L2, L3)�
From the main screen, press the F3 button once and the battery screen will be displayed, as shown in Figure 57�
SolaHD S5KC Series
Batt voltage (V)
Batt current (A)
Remain time (Min.)
Batt capacity (%)
Batt state
Batt string count
▲
ESC
157.0
0.03
407
100
Fullcharged
0
Battery
First Screen
2013- 08-01
10:45
:20
▲
▲
Second Screen
Figure 57: Battery screens
On the rst battery screen, pressing the F5 button will change the function of the F2, F3, and F4 buttons from the primary
functions to the secondary functions, as shown above in Table 23�
The battery screen displays Battery voltage, Battery current, Battery time remaining, Battery capacity, Battery state,
Battery string count, Battery temperature, cumulative discharge count (highest of all installed battery modules),
cumulative discharge time (in hours) and External battery cabinet count�
4.3.3 Output Screen
The main screen is the output screen by default, as shown in Figure 58�
Figure 58: Output screen
The output screen displays L-N or L-L voltage, L-N or L-L current, Frequency and Power factor�
From the main screen, press the F4 button once and the load screen will be displayed, as shown in Figure 59�
Figure 59: Load screen
The load screen displays output kVA (Sout/apparent power), output kW (Pout/active power), load level and crest factor�
4.3.5 UPS Information Screen
From the main screen, press the F4 button twice until the UPS info screen is displayed as shown in Figure 60�
Figure 60: UPS info screen
The UPS information screen displays UPS ID (name set by user), serial number and software version of LCD module,
system monitor module, system control module, charger module, power module and battery module (if the modules are
installed and are online)�
From the main screen, press the F4 button four times until the settings screen is displayed� The settings screen is
displayed in a total of nine screens as you scroll down, as shown in Figure 62�
SolaHD S5KC Series
Redundant set
Remote comms shutdown
Bypass set
Output Frequency
Output Voltage
Sync Range
Disabled
Enabled
Enabled
50Hz
230
± 5.0Hz
SolaHD S5KC Series
Auto restart mode
Auto restart capacity
Auto restart delay
Display contrast
Date & time
Command password
Figure 62: Settings screens
First Screen
2012-01-01 10:45:20
Third Screen
Enabled
20%
6second
*******
SolaHD S5KC Series
IT System Compatibility
UPS ID
Company Name
Contact Number
Load Factory Default
Fifth Screen
Second Screen
Fourth Screen
Disabled
No
On the rst settings screen, pressing the F5 button will prompt a password window to pop up� After you enter the correct
password, the function of the F2, F3, and F4 buttons will switch from the primary functions to the secondary functions, as
shown in Table 23�
4.4 Entering a Password
1. On the password prompt window, press the F5 button, the rst digit will become editable, press the F3 button to
enter the correct number�
2. Press the F4 button, the second digit will become editable, press the F3 button to enter the correct number�
3. Enter the rest of the password digits using the same method in Step 2, and press the F5 button when complete�
1. Press the F4 button to navigate to the parameter to be set, and press the F5 button to enter the edit mode�
2. Press the F3 or F4 button to select the setting item or change the setting value, then press the F5 button to conrm
the setting� Press the F2 button to exit the edit setting mode�
4.5.1 Battery Setting Screen
From the main screen, press the F4 button ve times until the battery settings screen is displayed, as shown in Figure 63�
SolaHD S5KC Series
Low battery warning
Auto batt test interval
Auto batt test start day
Auto batt test start time
External battery AH
Load factory default
Figure 63: Battery settings screen
10Min.
8weeks
Sunday
06:00
14AH
NO
On the rst settings screen, pressing the F5 button will prompt a password window to pop up� After you enter the correct
password, the function of the F2, F3, and F4 buttons will switch from the primary functions to the secondary functions as
shown above in Table 23� Refer to the notes listed above in 4�3�7 - Settings Screen for entering the password and making
changes to the battery setting parameters�
4.5.2 Language Selection Screen
From the main screen, press the F4 button six times until the language screen is displayed, as shown in Figure 64�
Figure 64: Language selection screen
The language selection screen displays a choice from seven languages: Chinese, English, German, Russian, French, Italian
and Spanish�
NOTE
The languages are displayed in their alphabet.
To set the language:
1. Press the F5 button, the language option is highlighted�
2. Press the F3 or F4 button to navigate to the desired language�
3. Press the F5 button to conrm the selection� Once the screen language changes, press the F2 button to exit the
From the main screen, press the F4 button seven times until the alarms screen is displayed, as shown in Figure 65�
Figure 65: Alarms screen
The alarms screen displays any current alarms of the UPS, including the alarm name, alarm ID code and alarm date/time
stamp�
4.5.4 Records Screen
From the main screen, press the F4 button eight times until the records screen is displayed, as shown in Figure 66�
Figure 66: Records screen
The records screen displays all historical alarms of the UPS, including the alarm name, alarm ID code, alarm date/time
stamp and record number/total record count�
From the main screen, press the F4 button nine times until the module replacement screen is displayed, as shown in
Figure 67�
SolaHD S5KC Series
LC board
Bypass monitor board
Bypass control board
power module
battery module
charger module
▲
ESC
Module Replacement Screen
Battery
2013- 08-01
10:45:20
▲
SolaHD S5KC Series
1. remove large plastic bezel
2. lift up user interface module
3. replace user interface module
4. insert user interface module
▲
5. replace large plastic bezel
Battery
▲
ESC
LCD Board Replacement Procedures
2013- 08-01
10:45:20
▲
▲
Figure 67: Module replacement screen
The module replacement screen displays the procedures for replacing all user replaceable module assemblies in the UPS
frame�
To view the procedure, press the F5 button to enter the module replacement� One module option is highlighted� Press
the F3 or F4 button to navigate to the specic module procedures, and then press the F5 button to view the procedures�
Once completed, press the F2 button to exit�
4.5.6 Prompt Window
During system operation, occasionally the UPS system needs to alert or remind the user of alarm notications or require
the user to conrm a command or perform other operations� When this occurs, a prompt window will pop up, as shown
in Figure 68� Refer to Table 23 below for possible prompts and the descriptions/actions to be taken�
Figure 68: Example of prompt window
Table 24: Information and Actions Required for the Prompt Window
When you press the ON/OFF-button while UPS is operating on bypass mode�
When you press the ON/OFF-button while UPS is operating on inverter mode and bypass is qualied�
When you press the ON/OFF-button while UPS is operating on inverter mode and bypass is not qualied�
S5KC SERIES USER MANUAL | 59
Enter password
*******
Output must be O
On manual bypass
can’t turn O the load
Please verify output settings before
starting the UPS
Escape: Ignore this message
Enter: Go to Settings Screen
Short Circuit RecoveryAfter the UPS output short circuits, wait 30 seconds before turning On the UPS again�
System is not ready
AC input not qualied,
cannot start UPS
Please check air lterWhen you set “Enabled” for “Air lter reminder,” this prompt appears after the reminder time is up�
After the control password is changed, you are required to enter the password when you want to enter
“Settings,” “Battery set” and “Service” screens�
While the UPS output is supplying power, this prompt appears when you want to set some key system
parameters� You need to close the output before setting key parameters�
This prompt appears when UPS operates on manual bypass and the ON/OFF button is pressed�
After the UPS is powered on, When you press the ON/OFF button for the rst time, this prompt appears to
remind you of viewing relevant setting�
When the power modules in the frame is initializing or there are no power modules, this prompt appears
when you press the ON/OFF button�
When the input voltage cannot meet the startup condition of the inverter, this prompt appears when you
press the ON/OFF button�
Removal of module will result
in loss of output power
New Alarms Present
Escape: Ignore this message
Enter: Go to Alarms Screen
Warning! Frame Fan Fault
Reduce load or replace fan
to avoid damage to bypass
Bypass source not qualied
Can not switch to bypass
When only one of the system monitor module OR system control module is installed and active, when the
locking level is moved to the unlock position, this prompt appears to remind user of loss of output power will
occur if the module is removed from the system�
This prompt appears when a new alarm occurs�
This prompt appears when frame fan is in fault and load is heavy, user should reduce load or replace fan�
This prompt appears when bypass source is not qualied and inverter can’t power on the load for transformer
based frame�
This chapter provides the basic troubleshooting guide and required actions for maintaining the SolaHD S5KC system�
5.1 Active Alarms
In the event of an alarm, the User Interface LCD will display the latest alarm message� A list of possible alarm messages
are displayed in Table 25� If an alarm occurs and you are uncertain of the corrective action to take, contact your local
Emerson SolaHD service representative�
Table 25: Alarm Message List
Alarm MessagePossible CauseCorrective Action
Power Module Warning
Power Module FailOne or more power modules has a fault�
Power Module Over Temp Warning
Power Module Over Temp Shutdown
One or more power modules is not operating
correctly�
One or more power modules is operating at an
internal high temperature�
One or more power modules has stopped
operating due to an internal over temperature�
View the corresponding module serial number
in the fault logs or event logs and contact your
local SolaHD service representative�
View the corresponding module serial number
in the fault logs or event logs and either replace
the module or contact your local SolaHD service
representative�
Check the air lters located behind the bezels
and clean if necessary, or check to see if the
ambient temperature is too high� If these
conditions do not exist, contact your local
Emerson personnel�
Check the air lters located behind the bezels
and clean if necessary, or check to see if the
ambient temperature is too high� If these
conditions do not exist, contact your local
SolaHD service representative�
Power Module Fan Failure
Insucient Capacity To Start Inverter
PM Locking Lever In Remove Position
Input Phase A Not QualiedA-phase voltage is too high or too low�
Input Phase B Not QualiedB-phase voltage is too high or too low�
Input Phase C Not QualiedC-phase voltage is too high or too low�
L1L2 Phase ReversedTwo phases are reversely connected�
One or more of the power module fans has
failed�
The load value exceeds the maximum load
capacity of all operating modules�
The power module locking lever is not in the
locked position�
Check to see if the fan is blocked� If not, contact
your local SolaHD service representative�
Ensure all power modules are inserted and the
locking lever is fully inserted� If all modules
are active, add power modules to increase
capacity or contact your local SolaHD service
representative�
Check the locking lever to ensure it is fully
inserted� If so, contact your local SolaHD service
representative�
Check the upstream feeder breaker or the UPS
input breaker and reset if necessary, or contact
your local SolaHD service representative�
Check the upstream feeder breaker or the UPS
input breaker and reset if necessary, or contact
your local SolaHD service representative�
Check the upstream feeder breaker or the UPS
input breaker and reset if necessary or contact
your local SolaHD service representative�
Have a qualied electrician check the phase
rotation at the distribution panel and/or at
the UPS input terminal block� If this is not the
problem, contact your local SolaHD service
representative�
Battery ReversedThe battery is reversely connected�
No Battery Modules Are Ready
All PM’s Are Not Ready
Power Module Redundancy AlarmThe UPS has no redundant power module�
Output Exceeds Max Load Setting
Turn Rocker Switch O Before Removing
Time to Check the Fan Filters for Excessive Dirt
The battery module is not ready, and the yellow
fault LED ashes�
The power module is not ready, and the yellow
fault LED ashes�
The maximum load alarm is eective, the actual
load is larger than the setting�
The bypass power is unqualied or the system
output is disconnected� There is only one
system monitor module or one system control
module in the system, and the control lever is
removed� The alarm reminds you to open the
startup switch before pulling out the control
module�
When the air lter reminder is ‘Enabled,’ this
message appears to remind users to check the
air lters�
rotation at the external battery cabinet� If this
is not the problem, contact your local SolaHD
service representative�
Ensure that the battery module is fully inserted
and locking levers are in the locked position�
If this is not the problem, contact your local
SolaHD service representative�
Ensure that the power module is fully inserted
in the upper frame bays and locking levers
are in the locked position� If this is not the
problem, contact your local SolaHD service
representative�
Add power modules or replace the faulty power
module to obtain redundancy, or contact your
local SolaHD service representative�
Either decrease load on the UPS or readjust
the user programmable alarm set point from
the LCD� It might also require another power
module to increase capacity� If this is not the
problem, contact your local SolaHD service
representative�
Open the startup switch�
Check the air lters and clean them if
necessary, or contact your local SolaHD service
representative�
No Matching Module
Load Exceeds Battery Module Capacity
Battery Cabinet Not Connected
BM Lock Lever in Remove PositionThe locking lever is not in the locked position�
BM Over Temperature Warning
Only one battery module is inserted into one
row of bays in the system�
The system has determined the load exceeds
the capacity of the battery�
The power cable of the external battery cabinet
is not connected or fully inserted�
The internal battery module temperature is at
an elevated level�
Ensure that there are a pair of battery modules
in the same row of the frame, or contact your
local SolaHD service representative�
Check to ensure that all battery modules are
fully inserted and the locking lever is in the
locked position� It is possible that more battery
modules are required to increase battery run
time� If this is not the problem, contact your
local SolaHD service representative�
Connect the cable or contact your local SolaHD
service representative�
Check the locking lever to ensure it is fully
inserted� If so, contact your local SolaHD service
representative�
Check the air lters located behind the bezels
and clean if necessary, or check to see if the
ambient temperature is too high� If this is not
the problem, contact your local SolaHD service
representative�
Battery Module WarningOne or more battery modules is abnormal�
Battery Module FailOne or more battery modules has a fault�
Battery Test Warning Weak Battery
BM Temp Unbalance
The battery capacity has reached the user
programmable set point�
One or more battery modules has detected
batteries that are no longer in specication due
to age or operating conditions�
The temperature dierence between all the
battery modules exceeds 10°C�
input breaker and reset if necessary�If this is not
the problem, begin the orderly shutdown of
all connected equipment as UPS shutdown is
imminent�
View the corresponding module serial number
in the fault logs or event logs and contact your
local SolaHD service representative�
View the corresponding module serial number
in the fault logs or event logs and either replace
the module or contact your local SolaHD service
representative�
Replace the battery string or contact your local
SolaHD service representative�
Check the air lters located behind the bezels
and clean if necessary, or check to see if the
ambient temperature is too high� If this is not
the problem, contact your local SolaHD service
representative�
Frame Fan Failure
Transformer Fan Failure
Transformer Temperature Warning
Bypass Source Not Qualied
Output Is O Abnormal Output VoltThe cable connection is wrong�Check the power distribution�
System Control Module Lock Lever in Remove
Position
System Monitor Module Lock Lever in Remove
Position
Charger Module WarningThe charger module is not operating correctly�
Charger Module FailThe charger module has a fault�
CM Power source Is Not QualiedCheck the power distribution�
The fan located behind the display panel has
failed�
There is a transformer on the UPS frame and at
least one transformer fan has failed�
A high temperature condition has occurred in
the output transformer area�
The UPS bypass functionality is not available
because the input source is out of tolerance to
the bypass voltage and/or frequency window�
The locking lever is not in the locked position�
The locking lever is not in the locked position�
Contact your local SolaHD service
representative for fan replacement�
Contact your local SolaHD service
representative for fan replacement�
Check the air lters located behind the bezels
and clean if necessary, or check to see if the
ambient temperature is too high� If this is not
the problem, contact your local SolaHD service
representative�
No action necessary unless the AC input has
been veried within bypass settings� If this is
not the problem, contact your local SolaHD
service representative�
Check the locking lever to ensure it is fully
inserted� If so, contact your local SolaHD service
representative�
Check the locking lever to ensure it is fully
inserted� If so, contact your local SolaHD service
representative�
View the corresponding module serial number
in the fault logs or event logs, and contact your
local SolaHD service representative�
View the corresponding module serial number
in the fault logs or event logs, and either replace
the module or contact your local SolaHD service
representative�
Check upstream feeder breaker or the UPS
input breaker and reset if necessary, or contact
your local SolaHD service representative�
Charger Module LOCK Lever in Remove Position The locking lever is not in the locked position�
Charger Module Fan Failure
Charger Module Temperature Warning
One or more of the charger module fans has
failed�
One or more charger modules is operating at an
internal high temperature�
Check the locking lever to ensure it is fully
inserted� If so, contact your local SolaHD service
representative�
Check to see if the fan is blocked� If not, contact
your local SolaHD service representative�
Check the air lters located behind the bezels
and clean if necessary, or check to see if the
ambient temperature is too high� If this is not
the problem, contact your local SolaHD service
representative�
5.2 Module Troubleshooting
The power, battery, charger, system control and system monitor module have two LEDs each to indicate the module
operating state� Figure 69 shows the location of these LEDs; the meaning of the LED indicators is detailed in Table 26�
Green Status LED
Green Status LED
Yellow Fault LED
Power Module
Battery Module
Yellow Fault LED
Green Status LED
Yellow Fault LED
Figure 69: Module LED location
System Control Module and
System Monitor Module
Table 26: Descriptions of Module LEDs
Green Status LEDYellow Fault LEDDescriptions of Module State
OO
OOnThe module is initializing (maximum 30 seconds)�
FlashingOThe module is operating normally�
FlashingFlashing
FlashingOn
OFlashing
OnO
OnOn
OnFlashing
1. If this condition persists for more than 30 seconds, verify that the lock lever is in the locked position; if it is not, the module is faulty�
2. If both green and yellow LEDs are ashing for more than 30 seconds, reinsert module�
The module is not inserted into the frame, lock lever is in
unlocked position or the system is o�
The module is in startup mode or the module has an
2
alarm�
The module is faulty and o-line, and the control
module is operating�
The module is not operating correctly, re-insert the
module� If this persists, contact technical support
personnel�
Follow the instructions below when replacing or adding a system control, system monitor, power, battery, or charger
module� Contact your local SolaHD representative if you need to purchase additional modules to expand your system or
contact authorized your Emerson representative for replacement modules�
5.3.1 Removing Modules
NOTICE
Risk of unintended shutdown� Can cause equipment damage�
Do not remove both the control and the monitor modules at the same time� Removing both the control module and
monitor module at the same time will cause the UPS to shut down and remove power from the load� Replace these
modules one at a time�
1. Remove bezel cover to locate the faulty module� The yellow fault LED will be illuminated on the faulty module�
NOTE
When removing bezels from a transformer-based UPS, note which have lters and replace them accordingly. Bezels from the
modules will have air lters. There will be no lters on the bottom three transformer bezels. The transformer has a separate air
lter.
For module removal, after unlocking the lever, wait a few seconds to remove the module.
If your system does not contain a redundant module, you may need to manually place the UPS into manual bypass before
removing modules to avoid accidental loss of output power for the connected equipment.
2. The method for removing a module varies depending on the module type� The two methods are as follows:
• When removing a power, battery or charger module, use a Phillips screwdriver to remove the fastener (if installed)�
Then pull out the lock lever slightly and lift up to unlock the module�
• When removing a system control or system monitor module, use a Phillips screwdriver to remove the two screws
from the securing holes on each end� Then pull out the lock lever slightly and slide it to the left to unlock the
module�
Locking
Lever
Fastener
Power Module
System Control Module or System Monitor Module
Figure 70: Lever and fastener
3. To pull out a power, charger or battery module:
a. When removing a power module, charger module or battery module: slide it 2/3 of the way out� It will be stopped
by the safety catch�
b. Lift the module up slightly while continuing to pull it out as shown in Figure 71�
c. Support the module and slide it completely out of the unit�
d. When removing a system control or a system monitor module, there is no safety catch because the modules are
Figure 71: Pull out a battery module, a power module or a charge module
!
WARNING
Risk of heavy unit falling over. Can cause equipment damage, injury or death.
Read all of the instructions before attempting to move the unit, lift it, remove packaging or prepare the unit for
installation.
The UPS presents a tipping hazard. Do not remove more than one module at a time. Failure to do so may cause
unit to tip over and cause serious injury.
5.3.2 Replacing the User Interface Module
Replace the User Interface Module only while the SolaHD S5KC is turned On (System Enable switch On and input power
available)� If this module is replaced while the UPS is O, the UPS settings will be reset to factory defaults when the UPS is
powered On with the new User Interface Module installed�
1. Remove the display bezel on top of the frame�
2. Lift up the user interface module, and put it on top of the UPS frame�
3. Disconnect the network cable from the user interface module�
4. Connect the network cable to the new user interface module�
5. Insert the new user interface module into the clips and replace the display bezel�
This chapter describes the routine maintenance for the SolaHD S5KC UPS, including proper care, scheduled maintenance
and procedures for cleaning fan lters�
6.1 Proper Care
Proper maintenance of the UPS is imperative to optimal performance and life of the unit� Emerson recommends that a
certied technician perform preventive and corrective maintenance� Emerson is dedicated to ensuring the highest level
of performance and unmatched support for your UPS� Contact your local SolaHD service representative for service�
6.2 Scheduled Maintenance
Emerson recommends performing the following maintenance at least monthly:
• Clean unit�
• Clean or replace lters�
• Verify proper airow�
Emerson recommends performing the following maintenance annually:
• Verify that all power modules are operating properly�
• Verify that all battery modules are operating properly�
• Verify redundancy (if applicable)�
6.3 Cleaning Fan Filters
The intake fans contain lters that will need to be replaced or cleaned periodically, depending on the surrounding
environment� Check lters; replace if they are very dirty or damaged�
To clean lters, either use a vacuum to remove the dirt and dust or rinse out the lters under running water (with the dirt
side down) to remove dirt and dust� Blot the lters dry with a towel and allow air-drying before reinstalling it�
6.3.1 Top Filter
1. Remove the display bezel�
2. Remove the user interface module, and lay it on top of the UPS frame�
3. Remove the two screws on the LCD mounting plate
4. Remove the screw in the middle of the lter assembly, remove the lter, as shown in Figure 73, and clean the lters as
described above�
5. Replace the lter, mounting plate, user interface module and display bezel�
Conducted and Radiated EMC LevelsIEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
Safety StandardsIEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22�2 No� 107�3
Immunity StandardsIEC/EN/AS 61000-4-2, 3, 4, 5, 6
TransportationISTA-1E
Dimensions, WxDxH17x28x38 in� (440x712x970mm)
Unit Weight147�7 lb� (67kg)
Shipping Weight209�4 lb� (95kg)
Environmental
Operating Temperature32 to 104°F (0 to 40°C)
Storage TemperatureWithout battery: -4 to 140°F (-20 to 60°C)
Relative Humidity0 - 95%, non-condensing
Altitude10,000 ft�(3000m)
Battery Module *
Lead-Acid Batteries (Per String)12
Backup Time (Full Load), MinutesSee Estimated Battery Run Times, 7�1 through 7�5
* Up to four external battery cabinets can be connected to each UPS frame and each external battery cabinet can be congured with up to seven
strings of batteries�
Table 40: 16-bay, single-phase, transformer-based unit Type R (& UPS model number 96 = R)
Rating
5 kVA /
4�5 kW
10 kVA /
9 kW
15 kVA /
13�5 kW
20 kVA /
18 kW
Run times in this table are approximate� They are based on new, fully charged standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS loading�
Table 41: 16-bay, single-phase, transformer-based unit Type F (& UPS model number 9 = F)
Rating
5 kVA /
4�5 kW
10 kVA /
9 kW
15 kVA /
13�5 kW
20 kVA /
18 kW
Run times in this table are approximate� They are based on new, fully charged standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS loading�
Table 46: 16-bay, two-phase, no transformer unit Type R (& UPS model number 9 = R)
Rating
5 kVA /
4�5 kW
10 kVA /
9 kW
15 kVA /
13�5 kW
20 kVA /
18 kW
Run times in this table are approximate� They are based on new, fully charged standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS loading�
Table 47: 16-bay, two-phase, no transformer unit Type F (& UPS model number 9 = F)
Rating
5 kVA /
4�5 kW
10 kVA /
9 kW
15 kVA /
13�5 kW
20 kVA /
18 kW
Run times in this table are approximate� They are based on new, fully charged standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS loading�
conversion and power quality solutions
products under Appleton Group, a business
unit of Emerson Industrial Automation�
Appleton Group is organized into three
focused businesses that provide distributors
and end-users expert knowledge and
excellent service�
Emerson Industrial Automation brings
integrated manufacturing solutions
to diverse industries worldwide� Our
comprehensive product line, extensive
experience, world-class engineering and
global presence enable us to implement
solutions that give our customers the
competitive edge�
For over 150 years, our electrical product
brands have been providing a rich tradition
of long-term, practical, high quality
solutions with applications ranging from
the construction and safe operation of
petrochemical and process plants to
providing quality power that precisely
controls automotive robotic production�
Engineers, distributors, contractors,
electricians and site maintenance
professionals around the world trust
Emerson Industrial Automation brands to
make electrical installations safer, more
productive and more reliable�
Electrical Construction Materials
This group is made up of the Appleton,
Nutsteel and O-Z/Gedney brands� They
manufacture a broad range of electrical
products including conduit and cable ttings,
plugs and receptacles, enclosures and
controls, conduit bodies and industrial and
hazardous lighting� Whether the application is
hazardous location, industrial or commercial,
the electrical construction materials group
has the products to meet your needs�
Power Quality Solutions
The SolaHD brand oers the broadest
power quality line, including uninterruptible
power supplies, power conditioners, voltage
regulators, shielded transformers, surge
protection devices and power supplies�
Heating Cable Systems
This group is made up of the EasyHeat
and Nelson brands� They oer a broad
range of electrical heating cable products
for residential, commercial and industrial
applications�