While every precaution has been taken to ensure accuracy and completeness in this manual, EGS Electrical Group, LLC.
assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or
omissions.
e SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Oce. All other product or service names
are the property of their registered owners.
Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death.
Refer all UPS and battery service to properly trained and qualied service personnel. Do not attempt to service this product
yourself and never work alone.
Opening or removing the cover may expose you to lethal voltages within this unit, even when it is apparently not operating
and the input wiring is disconnected from the electrical source.
SAVE THESE INSTRUCTIONS
is manual contains important safety instructions that must be followed during the installation and maintenance of the UPS
and batteries. Read this manual thoroughly before attempting to install or operate this UPS.
is UPS contains no user-serviceable parts. e O/Bypass push button does not electrically isolate internal parts. Under
no circumstances should you attempt to gain internal access other than to replace the batteries due to risk of electric shock or
burn. Do not continue to use the UPS if the front panel indicators are not in accordance with these operating instructions or
if the UPS performance alters in use. Refer all faults to your local distributor, SolaHD representative or SolaHD Technical
Support.
is UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the UPS is not
connected to utility input power.
Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the UPS is completely
shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard.
To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.
When the UPS is connected to an IT power distribution system, a short-circuit protection device must be installed on the
neutral line.
Install and use the S4K2UC in the following environments:
♦ Stable surface, not subject to vibrations or shocks
♦ Away from dust and other particulates
♦ Away from corrosive substances, salts and ammable gases
Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal temperature of the UPS and
can adversely aect the UPS and its batteries.
Keep liquid and foreign objects away from the UPS.
In case of re, use a dry chemical re extinguisher to put out the re. Using a uid re extinguisher may cause electric shock.
is UPS is not intended for use with life support and other designated critical devices. Maximum load must not exceed that
shown on the UPS rating label. is UPS is designed for data processing equipment. If uncertain, consult your local dealer or
SolaHD representative.
S4K2UC SERIES USER MANUAL | 7
is UPS is not for use in a computer room as dened in the standard for the Protection of Electronic Computer/Data
Processing Equipment, ANSI/NFPA 75.
e S4K2U3000-C was investigated under 30 A branch circuit in accordance with the National Electrical Code, ANSI/
NFPA 70, to reduce the risk of re; connect only a circuit provided with 30 A maximum branch overcurrent protection.
Battery Safety Notes
!
CAUTION
Do not dispose of batteries in a re; they may explode. Dispose of used batteries according to local regulations.
Do not open or mutilate the batteries. Released electrolyte is toxic and harmful to skin and eyes. If electrolyte comes into
contact with the skin, wash the aected area immediately and get medical attention.
!
CAUTION
A battery can present a risk of electrical shock and high short circuit current. e following precautions should be observed
when working with batteries:
♦ Remove watches, rings and other metal objects
♦ Use tools with insulated handles
♦ Wear rubber gloves and boots
♦ Wear protective eye ware (safety glasses)
♦ Do not lay tools or metal parts on top of batteries
♦ Disconnect charging source prior to connecting or disconnecting battery terminals
♦ Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground.
Contact with any part of a grounded battery can result in electrical shock. e likelihood of such shock will be reduced
if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not
having a grounded supply circuit).
Electromagnetic Compatibility
e S4K2UC complies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules.
Operation is subject to the following two conditions: (1) is device may not cause harmful interference and (2) is device
must accept any interference received, including interference that may cause undesired operation. Operating this device in a
residential area is likely to cause harmful interference that users must correct at their own expense.
e S4K2UC Series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards.
Continued compliance requires installation in accordance with these instructions and use of accessories approved by SolaHD.
Information for the Protection of the Environment
UPS Servicing: e UPS makes use of components dangerous for the environment (electronic cards, electronic components).
e components removed must be taken to specialized collection and disposal centers.
8 | Important Safety Instructions
Glossary of Symbols
Risk of electrical shock
!
-
PbH2SO4
R
Indicates caution followed by important instructions
Ac input
Ac output
i
+
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
Dc voltage
Equipment grounding conductor
Bonded to ground
Ac voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
WEEE
S4K2UC SERIES USER MANUAL | 9
1.0 Product Description
e SolaHD S4K2UC Series is a compact, on-line uninterruptible power system (UPS) that continuously conditions and
regulates its output voltage. It is designed to supply microcomputers and other sensitive equipment with clean sine wave
input power.
Upon generation, ac power is clean and stable. However, during transmission and distribution it is subject to voltage sags,
spikes and complete failure that may interrupt computer operations, cause data loss and damage equipment. e S4K2UC
protects equipment from these disturbances. e S4K2UC continuously charges its batteries from utility power, enabling it to
supply power to connected loads even when utility power fails.
is sections describes the UPS, its features, models, appearance and components, operating principles and operating mode.
1.1 Features
♦ Intelligent battery management to extend the battery life
♦ Operation and display panel with LED for monitoring load percentage and battery capacity independently
♦ Flexible network management with MultiLink™ software
♦ Fan fault self-inspection and automated diagnostic function
♦ Intelligent fan operation, automatically changing rotation speed depending on system requirements to decrease power
consumption and noise
♦ Input circuit breaker to ease recovery from overloads
♦ Safety approval from UL and cUL
♦ Communication options: USB port, IntelliSlot® port and terminal block communication
♦ Dry contacts for remote monitoring
♦ Input power factor greater than 0.99
♦ Output voltage selection function using the conguration software
1.2 Available Models
Available models of the UPS are shown in Table 1:
Table 1: UPS Models & Power Ratings
ModelNominal Power Rating
S4K2U700C700 VA/630 W
S4K2U1000C1000 VA/900 W
S4K2U1500C1500 VA/1350 W
S4K2U2000C2000 VA/1800 W
S4K2U3000C3000 VA/2700 W
10 | 1.0 Product Description
1.3 Appearance & Components
1.3.1 Front Panel & Controls
e SolaHD S4K2UC rack/tower models, in various power ratings, have the same general appearance, controls and features
(see Figure 1). e various rack/tower models dier largely in the type of receptacles each has.
Ventilation Slots
Figure 1: S4K2UC rack/tower models—front view
1.3.2 Rear Panel Features
e rear panel of the S4K2UC has these features (see Figure 2):
♦ USB port
♦ Cooling fan
♦ Power output receptacles
♦ Input circuit breaker
♦ IntelliSlot port
♦ Communication terminal block
♦ Input power cable
Operation and Display Panel
S4K2UC SERIES USER MANUAL | 11
IntelliSlot
Port
IntelliSlot
Port
700 VA, 1000 VA, 1500 VA Models
USB Port
Terminal Block
Communication
Cooling
Fan
Input Circuit
Breaker
External
Battery
Connector
2000 VA Model
USB Port
Input Circuit
Breaker
Input Power Plug
and Cable 5-15P
Output
Receptacles,
5-15R
Input Power Plug
and Cable, 5-20P
Output
Receptacles,
5-15/20R
Terminal Block
Communication
Cooling
Fan
External
Battery
Connector
3000 VA Model
Cooling
Fan
Input Circuit
Breaker
External
Battery
Connector
USB Port
IntelliSlot
Port
Terminal Block
Communication
Figure 2: S4K2UC 120 V rack/tower models—rear panel components
Input Power Plug
and Cable, L5-30P
Output
Circuit
Breakers
Output Receptacles,
5-15/20R
Output Receptacle,
L5-30R
12 | 1.0 Product Description
1.4 Major Components
e operating principle of the UPS is illustrated in Figure 3.
Output
L1
L2/N
GG
L1
L2/N
Input
SPD & EMI/
RFI Filters
Battery
Charger
Rectifier /
PFC
Dynamic
Bypass
Inverter
DC-to-DC
Converter
Battery
Figure 3: Operating principle diagram
e UPS is composed of utility input, SPD and EMI/RFI lters, rectier/PFC, inverter, battery charger, dc-to-dc converter,
battery, dynamic bypass and UPS output.
1.4.1 Surge Protection Device (SPD) & EMI/RFI Filters
e S4K2UC has surge protection and lters that protect the connected load from power surges, electromagnetic interference
(EMI) and radio frequency interference (RFI). ese features can minimize any surges or interference present in the utility
power. e lters also prevent surges or interference generated by the UPS from adversely aecting devices connected on the
same branch as the UPS.
In normal operation, the S4K2UC’s rectier/power factor correction (PFC) circuit converts utility power to regulated
dc power for use by the inverter, while ensuring that the wave shape of the input current used by the UPS is near ideal.
Extracting this sine wave input current achieves two objectives:
♦ Ecient power use by the UPS
♦ Reduced reected harmonics
is results in cleaner power being available to other devices in the building not protected by the S4K2UC.
S4K2UC SERIES USER MANUAL | 13
1.4.3 Inverter
In normal operation, the S4K2UC’s inverter utilizes the dc output of the PFC to produce precise, regulated sine wave ac
power. When utility power fails, the inverter receives dc power from the dc-to-dc converter. In either operation mode, the
UPS inverter is online, continuously generating clean, precise, regulated ac output power.
1.4.4 Battery Charger
e battery charger utilizes energy from the utility power and precisely regulates it to continuously oat charge the batteries.
e batteries are being charged whenever the S4K2UC is plugged in, even when the UPS is not turned on.
1.4.5 Dc-to-Dc Converter
e dc-to-dc converter raises the dc voltage from the battery to the optimum operating voltage for the inverter. is allows
the inverter to operate continuously at its optimum eciency and voltage, thus increasing reliability.
1.4.6 Battery
e S4K2UC uses valve-regulated, non-spillable, lead acid batteries. To maintain battery design life, operate the S4K2UC in
an ambient temperature of 0°C to 25°C (32°F to 77°F).
NOTE: Optional external battery cabinets are available to extend battery run times.
1.4.7 Dynamic Bypass
e S4K2UC provides an alternate path for utility power to the connected loads in the unlikely event of a UPS malfunction. Should the S4K2UC have an overload, overtemperature or UPS failure condition, the UPS automatically transfers the
connected loads to bypass.
NOTE: e bypass power path does not protect the connected loads from disturbances on the utility.
1.5 Operating Modes
e UPS operating modes include: Utility (V ac) Mode, Bypass Mode, Battery Mode, Battery Recharge Mode and
Frequency Converter Mode. For descriptions of indicators and control buttons, refer to “3.0 Controls & Indicators”.
1.5.1 Utility (V ac) Mode
During Utility (V ac) Mode, utility power provides energy to the S4K2UC. e lters, PFC circuit and the inverter process
this power to provide computer-grade power to connected loads. Meanwhile, the UPS maintains the batteries in a fully
charged state.
1.5.2 Manual Bypass Mode
Manual Bypass Mode occurs when the Standby/Manual Bypass button is pressed once, while the S4K2UC is in Utility (V ac)
Mode. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are
illuminated, refer to “8.0 Troubleshooting”). During Manual Bypass Mode, utility power bypasses the inverter and provides
energy to the connected load.
!
CAUTION
Turning o the UPS in Manual Bypass Mode will result in loss of output power and dropped loads.
14 | 1.0 Product Description
1.5.3 Battery Mode
e S4K2UC enters Battery Mode when utility power fails or is outside acceptable values. e battery system supplies power
through the dc-to-dc converter to the inverter to generate clean ac power for the connected loads.
When the S4K2UC enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals.
When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low
(this low battery warning is user-congurable).
In Battery Mode, the Ac Input indicator goes o and the Battery Level indicators illuminate. Each Battery Level indicator
represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to “8.0 Troubleshooting”.
For approximate battery run times, refer to “9.0 Specications—Table 13”. e times in Table 13 are approximate. ey are
based on resistive loads and an ambient temperature of 25°C (77°F). To increase this time, turn o non-essential loads (such
as idle computers and monitors) or add optional external battery cabinets.
!
CAUTION
Turning o the S4K2UC while in Battery Mode will result in loss of output power. If the UPS is turned o manually, it
must be manually restarted after utility power returns. If the UPS is turned o by a communication signal or because the
batteries are depleted, it will operate as selected in the conguration program for Auto-Restart (refer to “5.2.1 Conguration
Program”).
1.5.4 Battery Recharge Mode
Once utility power is applied to the S4K2UC, the battery charger begins charging the batteries.
1.5.5 Frequency Converter Mode
All models of the S4K2UC are capable of frequency conversion. Frequency Conversion Mode can be selected using the
conguration program. Allowable frequency operating modes include:
♦ Auto Sensing — 50 Hz or 60 Hz — Bypass Enabled
♦ Auto Sensing — 50 Hz or 60 Hz — Bypass Disabled
♦ Frequency Converter — 50 Hz — Bypass Disabled
♦ Frequency Converter — 60 Hz — Bypass Disabled
NOTE: e default for all models of the S4K2UC is “Auto Sensing — 50 Hz or 60 Hz — Bypass Enabled.”
!
CAUTION
Do not touch the ac input receptacle when the UPS is operating. Ac input voltages may still be present, even when the ac
input indicator is o.
S4K2UC SERIES USER MANUAL | 15
2.0 Installation
2.1 Unpacking & Inspection
Unpack the UPS and conduct the following checks:
♦ Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or
SolaHD representative immediately.
♦ Check the accessories against the delivery list. If there are any discrepancies, contact your local dealer or SolaHD repre-
sentative immediately.
2.2 What’s Included
♦ Compact disk containing: MultiLink, conguration program and user manual
♦ One, 6-1/2 ft. (2 m) long USB cable
♦ Mounting hardware, including screws and handles
♦ Two plastic tower stand sets (four pieces total)
♦ Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
NOTE: e S4K2UC external battery cabinet shipping package includes one battery cabinet, two spacers for tower conguration and one dc power cable.
2.3 Preparation for Installation
2.3.1 Installation Environment
♦ Install the UPS indoors in a controlled environment, where it cannot be accidentally turned o. e installation environ-
ment should meet the specications listed in “9.0 Specications”.
♦ Place the UPS in an area of unrestricted airow around the unit, away from water, ammable liquids, gases, corrosives,
and conductive contaminants. Avoid direct sunlight.
NOTE: Operating the UPS in temperatures above 25°C (77°F) reduces battery life.
2.3.2 Installation Clearances
Maintain at least 4 inches (100 mm) clearance in the front and rear of the UPS. Do not obstruct the air inlets on the front
panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of
the unit.
16 | 2.0 Installation
2.4 Mechanical Installation
e S4K2UC may be installed as a tower or in a rack, depending on space and use considerations. e S4K2UC may be used
alone, as a single UPS, or with up to four battery cabinets.
NOTE: When installing the UPS or making input/output connections, comply with all relevant safety codes and standards.
2.4.1 Tower Installation
To install the S4K2UC as a tower:
1. Take out support bases from the accessories (see Figure 4).
Connectors
Support Bases
Figure 4: Support bases
2. If optional external battery cabinets will be connected to the UPS, take out the spacers shipped with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 4. Each S4K2UC needs two assembled support bases, one
in the front and one in the rear.
4. Adjust the direction of the operation and display panel and logo on the S4K2UC.
a. Remove the front metal bezel cover as shown in Figure 5.
Spacers
Screws (2 pcs)
Front Metal Bezel Cover
Figure 5: Remove the front metal bezel cover
S4K2UC SERIES USER MANUAL | 17
b. Using the nger grips on the display panel, gently pull and rotate 90 degrees clockwise and snap it back into position
as shown in Figure 6.
Operation and Display Panel
Rotated Clockwise 90 Degrees
Figure 6: Rotate the operation and display panel
c. Replace the front metal bezel cover on the S4K2UC. At this point, the UPS operation and display panel and logo
have been rotated 90 degrees clockwise, which provides upright viewing for users.
5. Place the S4K2UC and any battery cabinets on the support bases. Each S4K2UC needs two support assemblies as shown
in Figure 7.
S4K2UC UPS
Operation and
Display Panel
Rotated for
Tower Operation
S4K2UC UPS and
External Battery Cabinet
Figure 7: Tower installation
Support Bases
Support Bases
18 | 2.0 Installation
2.4.2 Rack Installation
NOTES:
♦ When the S4K2UC is installed in a rack, it must be supported by a shelf, xed rails or slide rails on each side. e
factory-supplied rack mount handles cannot support the weight of the UPS. ey are used to move the UPS into and
out of the rack and to attach the UPS to the rack.
♦ Mounting hardware and slide rails are sold separately. Contact your local SolaHD representative for these options.
To install a S4K2UC in a rack:
1. Unpack the two slide rail assemblies and mounting hardware from the rack mounting kit (P/N: SRS1832). Slide rail
assembly includes inner member and front and rear members. ey are interchangeable between left-hand or right-hand.
Mounting hardware includes M4 screws and M5 screws.
2. Remove inner member of each slide rail assembly by extending it to its outermost position, depressing the retaining latch
and then pulling inner member from bracket assembly (see Figure 8).
t
u
o
l
l
u
P
Bracket assembly
Retaining latch
Inner member
Figure 8: Pulling inner member from each bracket assembly
3. Determine the S4K2UC’s mounting position inside the racks vertical rails.
!
CAUTION
Install the S4K2UC as low as possible in the rack to reduce the risk of tipping.
4. Attach the rear member of each slide rail assembly to the rack’s rails with two factory-supplied M5 screws (see Figure 9).
Vertical pole
M5 screw (4 pcs)
Rear member
Front member
Figure 9: Installing rear member of each slide rail assembly
S4K2UC SERIES USER MANUAL | 19
5. Extend the slide rail assembly by sliding the front member forward until it touches the rack’s front vertical rails (adjust-
able length: 18–32 inches/457–813 mm). Use two M5 screws to x each front member onto the front vertical rails
through the installation holes. Make sure that slide rail assemblies are at the same mounting height on all four rack rails,
as shown in Figure 10.
Front
Vertical
Pole
Front
Member
M5 Screw
(4 pcs)
Slide
Rear
Member
Figure 10: Installing front member of each slide rail assembly
6. Fasten rear member and front member together using four M4 screws and four M4 nuts (M4 nuts have been installed on
the rear member before delivery) per slide rail assembly as shown in Figure 11.
Rear Member
M4 Screw (8 pcs)
Front member
M4 Nut (8 pcs)
Figure 11: Fastening rear member and front member together
20 | 2.0 Installation
7. Fasten inner members (pulled from the slide rail assemblies in Step 2) to both sides of the UPS with eight M4 screws
provided in this kit. Make sure that the retaining latch is near the rear of the UPS as shown in Figure 12.
UPS
Inner member
Retaining latch
M4 screw (8 pcs)
Figure 12: Installing inner members
8. Use M4 screws to install ears on both sides of the UPS as shown in Figure 13.
UPS
Rack mount handles (2 pcs)
M4 screw (8 pcs)
Figure 13: Installing rack mount handles
9. Insert the UPS, with inner members attached, into the slide rail assemblies by inserting the top and bottom edges of the
inner members into the top and bottom curved tracks of the front members. Slide the UPS into the rack as shown in
Figure 14.
NOTE: e ends of the inner members are tapered to allow the rear of the UPS to be angled upward before insertion, if
space allows.
NOTE: e UPS should move smoothly into the slide rail assemblies. If not, recheck the alignment of the front and rear
members from Steps 4 through 6.
S4K2UC SERIES USER MANUAL | 21
Insert
Front Member
Inner Member
Figure 14: Insert the UPS
10. rough the rack mount handles, use M5 screws provided in this kit to secure the front of the UPS to the rack vertical
rails to prevent the UPS from sliding out of position.
11. If optional external battery cabinets are connected to the UPS, they can be placed all on one side of the UPS or stacked
beneath the UPS. e installation procedures are the same as those of the UPS.
NOTE: Up to four external battery cabinets can be connected to the S4K2UC. Each cabinet will increase the battery recharge time.
2.5 Cable Connection
e S4K2UC rear panel has an input cable and plug, output receptacles and output cable(s). (Output cables are on S4K2U3000
models only). Refer to “1.3.2 Rear Panel Features” for details. e battery cables are supplied with the battery cabinet.
2.5.1 Connecting Input Plug & Loads
NOTES:
♦ Ensure that all the loads are turned o.
♦ Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local elec-
trical codes. e wall receptacle must be grounded.
♦ e plug on the power supply cord is intended to serve as the disconnection device. e socket-outlet must be installed
near the equipment and must be easily accessible.
♦ SolaHD recommends installing an upstream circuit breaker of the same series as the S4K2UC’s input circuit breaker.
e upstream breaker should be the same or higher capacity than the UPS input circuit breaker.
e specication of input circuit breaker on the rear panel of UPS is shown in Table 2.
Table 2: Input Circuit Breaker Specication
ModelRated Circuit Breaker
S4K2U700C10 A
S4K2U1000C15 A
S4K2U1500C15 A
S4K2U2000C20 A
S4K2U3000C30 A
22 | 2.0 Installation
1. Plug all loads into the output receptacles on the rear panel of the S4K2UC. Distribute loads evenly across all receptacles
to prevent overloading individual receptacles.
2. Insert the input plug of the S4K2UC into the input power connection.
2.5.2 Ac Input/Output Hardwire Installation
!
CAUTION
is installation must be performed by electrical personnel and wired in accordance with local and national electrical codes.
Installation considerations:
On start-up, the UPS will take a half cycle inrush current of up to 3 times the rated current. is must be taken into account
when selecting the overload protection device at the input utility supply distribution point. To avoid random tripping on
startup, we recommend that input utility supply be protected with a MCB (Mechanical Circuit Breaker) capable of withstanding this initial inrush.
e utility input supply cable must be connected to the UPS via a wall mounted double pole circuit breaker. e UPS output
port must also be protected with a double pole circuit breaker connected to the load, rated to carry the input current, and
be capable of breaking the maximum prospective short circuit current of this branch circuit. e breakers are to be mounted
within six feet of the UPS and be readily accessible to the operator. Please refer to Table 3 for breaker specication.
High quality ground (earth) connections are required for the equipment ground conductors (protective earth) and grounding
electrode conductor (power system earth connection) to reduce electrical noise and provide for safe operation of the UPS
and connected loads. Conduit used alone without a grounding conductor wire is not an acceptable connection. Size ground
(protective earth) conductors equal to circuit conductors. For wiring information, please refer to Table 3.
♦ Make sure the UPS is turned o and unplugged before removing the original cord/receptacle board. To install the cable
box, the original cord/receptacle board must be removed and disconnected from the terminal block.
♦ e cable sizes and distribution methods used during installation are subject to local/national electrical codes of practice,
and therefore are not detailed here. Table 3 details the standard current ratings. e UPS rating plate gives details of the
current ratings for alternative output voltages.
♦ When choosing the input and output cables, users should strictly adhere to Table 3 for cable dimensions. Failure to
observe Table 3 could result in personnel injury or damage to the UPS.
♦ When installing the cable box, make sure that the input and output cables do not interfere with the position the UPS or
external battery connectors.
♦ User needs to supply hardware for securing input and output cables.
♦ Section 2.5.3 describes the connection of optional external batteries. Dc battery connections may not be hardwired.
Safety/EMC certication requires that the supplied battery cable be used.
S4K2UC SERIES USER MANUAL | 23
Installation procedures are as follows:
1. Remove the receptacle board on the UPS rear panel, as shown in Figure 15. Retain the six rear panel mounting screws for
securing the box assembly to the UPS.
UPS
Receptacle board
Screw (6 pcs)
Figure 15: Removing the receptacle board
2. Take out the box assembly from the accessories and split it into cover, box, Base 1 and Base 2, as shown in Figure 16. Set
the six screws aside for reassembly of the hardwire box.
Screw (6 pcs)
Cover
Box
Base 2Base 1
Figure 16: Splitting the box assembly
3. Use two rear panel mounting screws to install Base 1 to the UPS rear panel, as shown in Figure 17.
Figure 17: Installing base 1
Base 1Screw (2 pcs)
24 | 2.0 Installation
4. Connect the input power source line, neutral and ground cables to the input line (L), neutral (N) and ground (PE) termi-
nals on the UPS I/O terminal block and tighten the xing screws (see Figures 18 and 19).
5. Connect the UPS output line, neutral and ground cables to the output line (L), neutral (N) and ground (PE) terminals on
the UPS I/O terminal block and tighten the xing screws (see Figures 18 and 19).
Output cable
Input cable
Figure 18: I/O Cable placement
Figure 19: UPS I/O terminal block
6. Use two rear panel mounting screws to install Base 2 to the UPS rear panel, as shown in Figure 20.
Base 2
Figure 20: Installing Base 2
7. Insert the input and output cables/hardware into the slots on Base 2 and Base 1. Hand tighten the securing nuts to Base 2
and Base 1.
8. Set the box onto the Base 1 and Base 2 cable/hardware assemblies. Use the four box assembly screws to fasten the box to
the bases (see Figure 21).
9. Using the hardware securing nuts, tighten the input and output cable assemblies to the box and bases (see Figure 21).
Figure 21: Installing the box
Screw (2 pcs)
Base 1
Box
Base 2
Screw (4 pcs)
S4K2UC SERIES USER MANUAL | 25
10. Use two box assembly screws to install the cover onto the box, as shown in Figure 22.
Screw (2 pcs) Cover
Box
Figure 22: Installing the cover
11. Connect the other end of the UPS output line, neutral and ground cables to the load.
2.5.3 Connecting Battery Cables
1. Switch o the input breaker of the battery cabinet.
2. Take out the battery cable included with the battery cabinet.
3. Connect one end of the battery cable to the external battery connector on the rear panel of the UPS and connect the
other end to any battery port on the rear panel of the battery cabinet.
4. Switch on the battery breaker on the rear of the external battery cabinet.
5. Use the Conguration Program included with the UPS to specify the number of external battery cabinets connected to
the S4K2UC. See Table 14 for approximate battery run times.
2.6 Connecting Communication Cables
Communication cable connection includes: USB and option card cables.
2.6.1 Connecting USB Communication Cables
1. Take the USB communication cables out of the accessories box.
2. Insert one end of the USB communication cable into the USB port on the rear panel of the S4K2UC (see Figure 2).
3. Insert the other end of the USB communication cable into the USB port of the computer.
2.6.2 Installing the Optional IntelliSlot Card & Communication Cables
1. Remove the protective cover of the IntelliSlot port on the S4K2UC and set it aside.
2. Insert the IntelliSlot card into the IntelliSlot port and secure it with screws.
3. To connect any cable associated with a IntelliSlot card, refer to the user manual provided with the card.
To congure and use the IntelliSlot communication card, refer to the card’s user manual.
26 | 3.0 Control & Indicators
3.0 Control & Indicators
e operation and display panel, shown in Figure 23, is on the front panel of the S4K2UC.
Battery Level indicators
Load Level indicators
Fault indicator
Ac Input indicator
Bypass indicator
Inverter indicator
On/Alarm Silence/Manual
Battery Test button
Standby/Manual Bypass button
Battery indicator
Figure 23: Operation and display panel
3.1 Control Buttons
e operation and display panel has two control buttons: On/Alarm Silence/Manual Battery Test and Standby/Manual
Bypass.
3.1.1 On/Alarm Silence/Manual Battery Test Button
e On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and has three functions (see
Table 4).
Table 4: Functions of the On/Alarm Silence/Manual Battery Test Button
FunctionOperationDescription
OnPress the button once for 3 secondsTo start the UPS
Alarm Silence
Manual Battery Test
1
The low battery and bypass reminder alarms cannot be silenced.
2
After the alarm is silenced, the UPS will reactivate the alarm system to alert of additional problems.
1
Press the button for at least half a secondTo silence the alarms
Press the button for at least half a second while operating in Utility (V ac)
Mode with no alarms present
To initiate a manual battery test
2
S4K2UC SERIES USER MANUAL | 27
3.1.2 Standby/Manual Bypass Button
e Standby/Manual Bypass button controls output power to connected load(s) and has two functions (see Table 5).
Table 5: Functions of Standby/Manual Bypass Button
FunctionOperationDescription
Manual BypassPress the button once
Standby
3
If the bypass is not available due to voltage or frequency, pressing this button once will be ignored.
4
Perform all necessary shutdown procedures on connected loads before turning o the UPS.
Press the button twice within 4 seconds while the UPS is in
Manual Bypass or Battery Mode
3
4
To initiate a manual transfer of the connected loads to the
internal bypass, if available
To shutdown the UPS and shut o all power to the
connected loads
3.2 Indicators
e operation and display panel has seven indicators (see Figure 23). e indicators can be divided into two groups according
to the applications: level indicators and UPS status indicators.
3.2.1 Battery Level Indicators
e Battery Level indicator is composed of ve sets of LED bars that illuminate and ash to indicate the battery capacity
level. e S4K2UC battery capacity level is shown in 20% increments (± 5%). e battery level indicators will illuminate as
shown in Figure 24.
Charging
Discharging
0 - 20%
Flash OFFOFFOFFOFF
ONOFFOFF OFFOFF
21 - 40%
ON Flash OFF OFFOFF
ONONOFF OFFOFF
41 - 60%
ONONFlash OFFOFF
ONONONOFFOFF
61 - 80%
OFFONONON Flash
OFFONONONON
81 - 100%
FlashONONONON
ONONONONON
Fully
Charged
ONONONONON
ONONONONON
Figure 24: Battery Level indicators
28 | 3.0 Control & Indicators
3.2.2 Load Level Indicators
e Load Level indicator is composed of ve LED bars that illuminate to indicate the relative load on the UPS output in
25% increments (± 5%). e load level indicator will illuminate as shown in Figure 25.
0 - 25%
ONOFFOFF OFFOFF
26 - 50%
ONON
51 - 75%
ONONONOFFOFF
76 - 100%
ONONONON
Overload
ONONONONON
OFF OFFOFF
OFF
Figure 25: Load Level indicators
3.2.3 UPS Status Indicators
UPS status is indicated by ve symbols: Fault indicator, Ac Input indicator, Battery indicator, Inverter indicator and Bypass
indicator. Table 6 shows the symbols and their meanings.
Table 6: UPS Status Indicators
UPS Status IndicatorIconColorDescription
Fault indicator
Ac Input indicatorGreen
Battery indicatorAmberOn when the battery is supplying power; o when the battery is not supplying power
Inverter indicatorGreen
Bypass indicatorAmber
RedOn if the UPS has detected a fault; o if there is no fault
On when the utility input power is normal; o during utility failure; ashing when
utility power is outside the specications
On when the inverter is supplying power; o when the inverter is not supplying
power; and ashing when utility power is outside the specications
On when the bypass is supplying power; o when the inverter is supplying power;
and ashing when utility power is outside the specications
S4K2UC SERIES USER MANUAL | 29
4.0 Operation
is section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass,
shutting down the UPS and disconnecting the utility power from the UPS.
NOTE: e S4K2UC’s battery is fully charged before delivery, but some charge will be lost during storage and shipping. To
ensure that the battery has adequate reserve power to protect the connected load, charge the battery for 3 hours before putting
the UPS into service.
4.1 Startup Checklist for the S4K2UC
Before starting the UPS, perform these checks:
1. Check that the input plugs and loads are connected properly and reliably.
2. Check that all of the battery cables are connected properly.
3. Check that the communication cables are connected properly.
4.2 Starting the UPS
1. Turn on the input circuit breaker—see Figure 2 for its location.
2. Turn on the UPS by pressing the On/Alarm Silence/Manual Battery Test button for 3 seconds.
3. Turn on the connected loads.
4. Check the status indicators to determine whether the S4K2UC is operating normally.
5. Check the load level indicators to verify that the connected load does not exceed the UPS’s rated capacity.
e UPS is now providing conditioned power to the load.
4.3 Manual Battery Test
To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while
operating from utility power with no alarm conditions present.
♦ If only the rst two of the ve LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.
♦ Retest the batteries after 24 hours of charging the batteries.
♦ After the batteries have been retested, if only two of the ve battery LEDs illuminate, contact your local SolaHD repre-
sentative or SolaHD Technical Support.
♦ If none of the ve battery LEDs illuminate during a manual battery test, check the battery connection and allow the
UPS to recharge the batteries for 1 hour and initiate a manual battery test again.
♦ If none of the ve battery LEDs illuminate during the manual battery test a second time, replace the batteries, and
contact your local SolaHD representative or SolaHD Technical Support.
30 | 4.0 Operation
4.4 Manual Bypass
Press the Standby/Manual Bypass button once while the UPS is in Utility (V ac) Mode; the UPS will transfer the connected
loads to the internal bypass. If the internal bypass is not available due to utility power problems, pressing this button once will
be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. If other indicators are
illuminated, refer to “8.0 Troubleshooting”.
4.5 Shut Down the S4K2UC
1. Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button once. If manual bypass is not avail-
able, disregard the rst step.
2. Press the Standby/Manual Bypass button twice within 4 seconds to shut down the UPS.
Power to the connected loads is now o.
4.6 Disconnecting Input Power from the S4K2UC
1. Once the UPS has been shut down as detailed in “4.5 Shut Down the S4K2UC”, disconnect the input cable plug.
2. Wait 30 seconds and verify that all indicators have turned o and the fan has stopped; this indicates that the power-o is
complete.
3. If the UPS has an external battery cabinet, turn the external battery cabinet breaker switch to the o position.
After powering o the UPS, the UPS ceases output and the load is powered o.
S4K2UC SERIES USER MANUAL | 31
5.0 Communication
is section describes UPS communication over the three types of communication connections on the rear of the S4K2UC:
♦ IntelliSlot port
♦ USB port (standard B-type)
♦ Terminal block communication
!
CAUTION
To maintain safety (SELV ) barriers and for electromagnetic compatibility, signal cables should be segregated and run separately
from all other power cables.
e IntelliSlot SNMP card (Catalog number: SNMPWEB CARD) provides SNMP monitoring and control of the UPS
across the network.
e IntelliSlot Relay card (Catalog number: RELAYCARD INT) provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.
Follow instructions provided with the IntelliSlot card to congure MultiLink, the UPS or any additional ancillary product for
the S4K2UC. ese instructions are also available at: www.solahd.com/multilink.
5.1.1 MultiLink
MultiLink monitors the UPS continuously and can shut down your computer or server in the event of an extended power
failure. MultiLink can be congured to shut down the UPS as well.
MultiLink can also be congured for use without the USB cable when the IntelliSlot SNMP Card (Catalog number:
SNMPWEB CARD) is installed in the UPS. An optional MultiLink license kit permits shutting down the UPS over a
network. For more information about the MultiLink license kits, visit our Web site at: www.solahd.com or contact SolaHD
at: (800) 377-4384/(847) 268-6000.
5.2 USB Port Communication
e standard B-type USB port is used to connect the UPS and network server or other computer system using MultiLink.
e Conguration program can be completed through the communication port.
32 | 5.0 Communication
5.2.1 Conguration Program
Accessing the Conguration Program via USB is a new feature of the S4K2UC. For most users, the factory default settings
will be adequate. is section illustrates the features available for modication, as well as the factory default settings.
e USB conguration program allows these features of the S4K2UC to be changed:
♦ Enable/Disable Auto-Restart
♦ Select frequency converter operation with a xed output frequency of 50 Hz or 60 Hz, bypass disabled
♦ Set the Low Battery Warning alarm time from 2 to 30 minutes
♦ Enable/Disable the Auto-Battery test
♦ Enable/Disable Auto-Restart after removing Remote Shutdown
♦ Set the wiring mode of Remote Shutdown
♦ Set the Auto-Enable output
♦ Set the Auto-Battery test to 7, 14, 21 or 28 days
♦ Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by
software products
♦ Select one of multiple output voltages to match various voltages (see Table 7)
Table 7: Output Voltage Option, All Models
Factory Default, V acOutput Voltage Option, V ac
120110, 115, 120, 127
!
WARNING
e output voltage settings cannot be changed while the UPS is on and powering connected loads.
NOTES:
For all 120 V models, when the output voltage is programmed for 110 V ac, the UPS will be automatically derated as follows
(refer to “9.0 Specications” for VA and Watt ratings):
♦ 700 VA–1000 VA: Derated to 95% of both the VA and Watt ratings
♦ 1500 VA–3000 VA: Derated to 90% of both the VA and Watt ratings
NOTES:
♦ e conguration program is compatible with UPS models S4K2UXXXXC, as in S4K2U3000C. It is not compatible
with earlier versions of the S4K2U UPS.
♦ A computer running Windows 2000®, XP® or Vista® is required to set up and run the conguration program.
5.3 Terminal Block Communication
e terminal block includes eight pins, as shown in Figure 26.
S4K2UC SERIES USER MANUAL | 33
1
2
3
4
5
6
7
Any Mode
Shut Down
Battery Mode
Shut Down
Battery Mode
Low Battery
8
Figure 26: Terminal block layout
5.3.1 Any Mode Shutdown
e purpose of Any Mode Shutdown is to shut down the UPS output by turning o the rectier, inverter and static bypass
switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally and remotely, as described as follows:
♦ Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2
♦ Remote Any Mode Shutdown can be performed by a switch connected to Pin 1 and Pin 2 and mounted at a remote
location
NOTES:
♦ Remote Power o will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings
in the conguration program
♦ A current-limited source (+12 V dc, 50 mA) will be available from the UPS
♦ e connection to the UPS for remote connection will be via terminal block connector
♦ Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations
!
WARNING
When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the S4K2UC’s
output can turn on automatically and without warning if the Pin 1 and Pin 2 connection is changed.
5.3.2 Battery Mode Shutdown
Battery Mode Shutdown permits shutting down the UPS by turning o the rectier, inverter and static bypass switch so that
there is no power to the load when the UPS is on battery.
Battery Mode Shutdown can be performed locally or remotely:
♦ Local Battery Shutdown can be performed by shorting Pin 3 and Pin 4
♦ Remote Any Mode Shutdown can be achieved by a switch connected to Pin 3 and Pin 4 and mounted at a remote location
34 | 5.0 Communication
NOTES:
♦ Remote power o will be performed by NO contact
♦ A current-limited source (+12 V dc, 50 mA) will be available from the UPS
♦ e connection to the S4K2UC for remote connection will be via terminal block connector
♦ Battery mode shutdown wiring will follow local wiring codes and laws
♦ is signal must last for 1.5 seconds or longer
♦ A battery shutdown signal will not cause an immediate shutdown. It will start a 2 minute shutdown timer. is timer
cannot be stopped once triggered. If utility power returns during this countdown, the S4K2UC will still shut down and
must remain shut down for 10 seconds. Whether the UPS turns back on when the power is restored depends on the
auto-restart setting.
5.3.3 On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry
contact will be closed.
5.3.4 Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and
has reached the Low Battery Warning time selected in the conguration program, this dry contact will be closed.
e rated values for the dry contacts are:
♦ Rated Voltage: 5 V dc
♦ Working Voltage Range: 4.5–10 V dc
♦ Rated Current: 30 mA
S4K2UC SERIES USER MANUAL | 35
6.0 Battery Cabinet
Optional battery cabinets are available for the S4K2UC. e battery connectors and input breaker are on the battery cabinet’s
rear panel, as shown in Figure 27. For battery cabinet specications, refer to Table 12. For battery run times, refer to Table 14.
Input Breaker
Battery Connectors
Figure 27: Battery cabinet
!
WARNING
Do not contact the battery connectors and ground without wearing protective gloves and clothing and taking other precautions against electrical shock. e battery loop and ac input are not insulated, which may cause a dangerous voltage between
the battery connectors and ground.
36 | 7.0 Maintenance
7.0 Maintenance
is section describes replacing the internal battery pack, precautions, and checking the UPS’s status and functions.
7.1 Replacing the Internal Battery Pack
e S4K2UC is designed to allow properly trained and qualied service personnel to replace the internal battery pack safely.
Read the safety cautions before proceeding. Contact your SolaHD representative to obtain the part number and pricing of the
appropriate replacement battery pack. Replace batteries with the same type and number of batteries or battery packs.
!
CAUTION
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to local regulations.
7.1.1 Battery Replacement Procedures
1. Remove the front metal bezel cover from the UPS.
2. Loosen and remove the six screws on the battery door, as shown in Figure 28.
3. Lay the battery door and screws aside for reassembly.
Battery Door
Front Metal
Bezel Cover
Figure 28: Removing the front metal bezel cover and battery door
4. Gently pull the battery wire out and disconnect the polarized battery plug and battery receptacle, as shown in Figure 29.
S4K2UC SERIES USER MANUAL | 37
Battery ConnectorBattery Receptacle
Figure 29: Disconnecting the battery plug and battery receptacle (front view)
5. Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in Figure 30.
Internal Battery Pack
Battery
Handle
Pull Out with Battery Handle
Figure 30: Pull out the internal battery pack
6. Unpack the new internal battery pack. Take care not to destroy the packaging. Compare the new and old internal battery
packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are dierent, stop
and contact your local SolaHD representative or SolaHD Technical Support immediately.
7. Line up and slide in the new internal battery pack.
8. Reconnect the polarized battery plug and battery receptacle.
9. Gently push the battery wire and internal battery pack back into the UPS.
10. Reattach the front battery door with the six screws.
11. Reattach the front metal bezel cover to the UPS.
NOTE: e internal battery pack is hot-swappable. However, caution should be exercised during this procedure because the
load is unprotected from disturbances and power outages. Do not replace the battery while the UPS is operating in Battery
Mode. is will result in a loss of output power and will drop the connected load.
7.2 Battery Charging
e batteries are valve-regulated, non-spillable, lead acid and should be kept charged to attain their design life. e S4K2UC
charges the batteries continuously when it is connected to the utility input power.
If the S4K2UC will be stored for a long time period of time, SolaHD recommends connecting the UPS to input power for at
least 24 hours every four to six months to ensure full recharge of the batteries.
38 | 7.0 Maintenance
!
WARNING
e battery can present a risk of electrical shock and high short circuit current. e following precautions should be observed
before replacing the battery pack:
♦ Remove rings, watches and other metal objects
♦ Use tools with insulated handles
♦ Do not lay tools or other metal objects on the batteries
♦ If the battery kit is damaged in any way or shows signs of leakage, contact your SolaHD representative immediately
♦ Do not dispose of batteries in a re; they may explode
♦ Handle, transport and recycle batteries in accordance with local regulations
7.3 Precautions
Although the S4K2UC has been designed and manufactured to ensure personal safety, improper use can result in electrical
shock or re. To ensure safety, observe the following precautions:
♦ Turn o and unplug the S4K2UC before cleaning it
♦ Clean the UPS with a dry cloth—do not use liquid or aerosol cleaners
♦ Never block or insert any objects into the ventilation holes or other openings of the S4K2UC
♦ Do not place the S4K2UC power cord where it might be damaged
7.4 Checking UPS Status
SolaHD recommends checking the UPS operation status every six months.
♦ Check if the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm?
♦ Check if the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode; if it is operating in
Bypass Mode, stop and contact your local SolaHD representative or SolaHD Technical Support.
♦ Check if the battery is discharging. When the utility input is normal, the battery should not discharge. If the UPS is
operating in Battery Mode, stop and contact your local SolaHD representative or SolaHD Technical Support.
7.5 Checking UPS Functions
NOTE: UPS function check procedures may interrupt power supply to the connected load. Back up all critical load data
before conducting the UPS functions check.
SolaHD recommends checking the UPS functions once every six months.
Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are on and the UPS is
operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for 3 seconds after Inverter Mode; the UPS should initiate
battery self-test. Check to determine whether the battery is operating normally. If not, stop and contact your local
SolaHD representative or SolaHD Technical Support.
S4K2UC SERIES USER MANUAL | 39
ABCDE
8.0 Troubleshooting
is section indicates various UPS symptoms a user may encounter and troubleshooting steps in the event the UPS develops
a problem. Use the following information to determine whether external factors caused the problem and how to remedy the
situation.
8.1 UPS Symptoms
e following symptoms indicate the S4K2UC is malfunctioning:
♦ e relative indicators will illuminate, indicating the UPS detected a problem
♦ An alarm will sound, indicating that the UPS requires attention
8.1.1 Indicators
In addition to the fault indicator being illuminated, one or more of LED segments of Battery Level indicator will also be
illuminated to provide a diagnostic aid to the user, as shown in Figure 31. e descriptions are listed in Table 8.
Figure 31: Battery Level indicator
Table 8: Indicator Descriptions
IndicatorDiagnosisAudible Alarm
A–EOn bypass from output overloadHalf-second beep every half second
AOn bypass due to overtemperature condition1-second beep every 4 seconds
BOn bypass due to dc bus overvoltage1-second beep every 4 seconds
COn bypass due to dc/dc power supply failure1-second beep every 4 seconds
DPFC failure1-second beep every 4 seconds
EOn bypass due to inverter failure1-second beep every 4 seconds
A & CUPS failed battery test2-second beep every 60 seconds
C & EUPS shutdown by command from communication (USB port or IntelliSlot port) No audible alarm
A & B
Battery indicator ashing
Ac Input indicator ashing
Bypass indicator ashingUtility power voltage or frequency is our of tolerance; bypass is unavailablen/a
Note: A–E indicators are shown in Figure 23
UPS failure (includes dual-fan failure, single-fan failure under certain conditions, and battery charger failure)
Internal battery source not available. Check battery connection, power down
and reboot the UPS.
Line-to-neutral reversal in the ac input power supply or a loss of proper
grounding for the UPS. UPS cannot start in standby status.
Continuous alarm
Continuous alarm
Continuous alarm
40 | 8.0 Troubleshooting
8.1.2 Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. e
audible alarm will sound as described in Table 9.
Table 9: Audible Alarm Descriptions
ConditionAlarm
Battery dischargeHalf-second beep every 10 seconds
Low batteryTwo half-second beeps every 5 seconds
UPS fault, load on bypass1-second beep every 4 seconds
UPS fault, no power to loadContinuous
OverloadHalf-second beep every half second
Battery replacement2-second beep every 60 seconds
Battery lossContinuous
Wiring problem (including line-to-neutral reversal or a loss of proper
grounding for UPS)
Bypass reminder1-second beep every 2 minutes
Continuous
8.2 Troubleshooting
In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the issue persists, contact
SolaHD Technical Support.
Table 10: Troubleshooting
ProblemCauseSolution
UPS fails to start when the On/Alarm Silence/
Manual Battery Test button is pressed
Battery indicator is illuminated
UPS has reduced battery backup time
UPS is short-circuited or overloaded
UPS is not plugged in
UPS input protection breaker has opened
Utility power is out of tolerance
Batteries are not fully charged
UPS is overloaded
Batteries may not be able to hold a full charge
due to age
Ensure the UPS is o. Disconnect all loads and
ensure nothing is lodged in the output receptacles. Ensure loads are not defective or shorted
internally.
UPS is operating from Battery Mode. Ensure
UPS is securely plugged into the wall receptacle.
UPS is operating from Battery Mode. Save data
and close applications. Reset input breaker,
then restart the UPS.
UPS is operating from Battery Mode. Save data
and close applications. Ensure utility supply
voltage is within acceptable limits for the UPS.
Keep the UPS plugged in continuously for at
least 24 hours to recharge the batteries
Check Load Level indicator and reduce the load
on the UPS
Replace the batteries. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for replacement battery kits.
Fault and Bypass indicators and all LED
segments of the Battery Level indicator are
illuminated
UPS is overloaded or the load is faulty
Check the Load Level indicator and remove
non-essential loads. Recalculate the load and
reduce the number of loads connected to the
UPS. Check the load for faults.
Table 10: Troubleshooting
ProblemCauseSolution
Fault and Bypass indicators and Diagnostic A
indicator are illuminated
Fault and Bypass indicators and Diagnostic B
indicator are illuminated
Fault and Bypass indicators and Diagnostic C
indicator are illuminated
Fault indicator and Diagnostic D indicator are
illuminated
Fault and Bypass indicators and Diagnostic E
indicator are illuminated
Fault indicator and Diagnostic A and C indicators are illuminated
Fault and Bypass indicators and Diagnostic C
and E indicator are illuminated
Fault indicator and Diagnostic A and B indicators are illuminated; continuous alarm sounds
Ac Input indicator is ashing
Battery indicator is ashing; continuous alarm
sounds
Bypass indicator is ashing
UPS shutdown due to overtemperature condition
Load is on bypass power
UPS internal dc bus overvoltage
UPS dc/dc fault
UPS PFC (Power Factor Correction Circuit) fault
UPS inverter fault
UPS failed the battery test
UPS shut down by a command from the
communication port(s)
UPS failure (includes dual-fan failure, single-fan
failure under certain conditions, and battery
charger failure)
UPS detected a line-to-neutral reversal or a loss
of proper grounding for the UPS. A continuous
alarm will sound; the UPS cannot start up in
standby status.
This is active only when power is rst applied to
the input. Once the UPS is running, the Ac Input
indicator will ash, unless the input wiring is
correctly changed.
Battery source is not available
The bypass is disabled because the voltage or
frequency is outside the acceptable limits
S4K2UC SERIES USER MANUAL | 41
Ensure the UPS is not overloaded, ventilation holes are not blocked, or room ambient
temperature is not excessive. Wait 30 minutes
to allow the UPS to cool, then restart the UPS.
If the UPS cannot restart, contact your local
dealer, SolaHD representative or SolaHD Technical Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
UPS requires service. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for assistance.
Replace the batteries. Contact your local dealer,
SolaHD representative or SolaHD Technical
Support for replacement battery kits.
UPS has received a signal or command from
the attached computer. If this was inadvertent, ensure the communication cable used is
correct for your system. For assistance, contact
SolaHD Technical Support.
Ensure fan is not blocked up. If the fault is not
resolved, contact SolaHD Technical Support for
assistance.
Contact a qualied electrician to verify site
wiring.
Check battery connections, completely power
down and restart the UPS.
NOTE: If the battery circuit opens while the UPS
is running, it will be detected when the next
battery test is performed.
The ac input powers the PFC input and serves
as the bypass source. If the ac is present but the
voltage or frequency exceeds the acceptable
range for safe operation with a load, the bypass
will be disabled and this indicator will ash,
indicating that the bypass is unavailable.
For further assistance, please contact SolaHD Technical Support at (800) 377-4384/(847) 268-6000 or by e-mail at tech@solahd.com.
When reporting an issue to Technical Support, please include the UPS model number and serial number. This information is located on the top
panel of the UPS.