Sola HD s3k1000 User Manual

2
Uninterruptible Power Supplies
S5KC Modular Series On-Line Uninterruptible Power Systems (UPS)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The S5KC Modular UPS is scalable from 5 to 20 kVA,
offering many exible options by adding a few standard modules. Designed to be fully congured, tested and shipped in the conguration you need, the S5KC Modular UPS also has the ability to be easily upgraded in the eld to either higher VA ratings (up to 20 kVA maximum), longer back-ups time or to add N+x parallel redundancy. Congurations can be cost-effectively upgraded keeping your S5KC Modular UPS current without a large reinvestment in a new system.
The optional N+x redundancy provides a fault-tolerant group of power modules and controls. The modular design is easy to upgrade so the UPS can grow with the needs of the system that is being protected.
Each of the modular components, including 5 kVA power modules, LCD display, battery modules and system control modules, can be hot-swapped making it easy to increase power, extend your back-up time or add redundancy while still providing power protection to the load.
This fault-tolerant system uses intelligent power and battery modules which take themselves off-line if there is a problem without interrupting power to the load. Self-diagnostic capabilities simplify maintenance and troubleshooting. Each unit incorporates an internal automatic bypass.
Applications
With multiple standard options in a smaller footprint, providing more exibility for capacity and communication both pre- and post-installation, the S5KC delivers the power protection needs in applications such as
• Oil and Gas (Pure OEMs)
• Pharmaceutical
• Automotive
• Food & Beverage
Features
• Module level redundancy provides multiple layers of protection to ensure your machine has the power it needs to run safely with no single point of failure, critical loads continue to run on conditioned battery power even if a system component malfunctions.
• An industry leading 0.9 power factor keeps machines performing awlessly when running on battery power.
• Superior overload capabilities deliver conditioned power during temporary power anomalies without unnecessarily transferring to and from bypass power.
• Independently controlled maintenance bypass is designed to provide maximum system availability to critical equipment by allowing transfer of connected equipment to an alternate power path. The UPS can then be turned Off and removed from service with no interruption of power to connected equipment.
• True on-line double conversion with a large input voltage range (low line transfer down to 110 Vac) isolates sensitive equipment from power uctuations while
minimizing transfers to increase battery life.
• ENERGY STAR® qualied UPS models – UPS products meeting the EPA’s requirements use an average of 35% less energy than their standard counterparts.
• To enhance the availability and trouble-free operation, every pre-congured S5KC UPS arrives standard with one IS-UNITY-DP communications card installed. Enabling you to take advantage of the remote monitoring and diagnostic service available with your system during your initial standard warranty period.
• Start-up services available, contact your local SolaHD sales representative for details.
Certifications and Compliances
- UL 1778, Fourth Edition
- CSA C22.2 No. 107.3
• Series S5KCA, S5KCB,S5KCC,S5KCD
- CE (Low Voltage and EMC Directive)
EN62040-1, EN62040-2 EAC - TR CU 004/2011
Safety of Low-Voltage Equipment, TR CU 020/2011
EMC
E179213
Listed, UPS Equipment
2
Uninterruptible Power Supplies
Chassis Selection
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The S5KC Modular UPS system has multiple chassis available to build on:
Select the proper chassis based on your applications current and future need for expansion. Also consider if redundancy will be required for your application then consider your application power and location wiring needs. To help with selecting the appropriate chassis series, we have provided a useful selection ow chart to guide you to an appropriate
chassis series for your needs.
Steps to Selection
1. Determine the maximum kVA you will need for future expansion.
Which Product Do I Select?
Xfmr-free (2W + G)
L
L
N X
L
L(N)
S5KC-A and
S5KC-B
INV
L
L(N)
All loads are
200-240V
2. Determine the kVA and run time value for your
immediate need.
3. Using the ow chart to the right, determine the voltage, phase conguration and chassis requirements.
4. Determine if you need redundancy. If the exact run time is critical and you are not sure which unit is appropriate, please contact our technical support team to aid in
selection.
5. Select the unit that meets both your immediate
requirements, and is expandable to your future needs. Each chassis will have a “Maximum Upgrade” capacity. The Maximum Upgrade is the highest kVA expansion that particular conguration is capable of without removing any of the battery modules from the original conguration.
6. External Battery Cabinets (EBC). Depending on extended run-times desired or your location's spacing requirements, you may be able to add an optional EBC to extend your run-time.
7. Optional External Maintenance Bypass (EMB) or other available accessories. Review your application's current and future needs and consider all functional options including lters and spare modules if desired.
L
L(
N)
L
N
L
L
N X
L
Xfmr-based (3W + G)
INV
S5KC-C and
S5KC-D
Xfmr-free (3W + G)
INV
INV
S5KC-E and
S5KC-F
L
N
L
L
N
L
2
Uninterruptible Power Supplies
Table 16: Specifications
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Capacity
Conducted and radiated EMC levels Compliant immunity standards Environmental
ENERYGY STAR® qualified
Width Depth Height
Weight (frame rating populated)
Operating temperature Relative humidity Altitude Efficiency (AC-AC) Heat dissipation
Nominal input voltage
Input Voltage Range
Power Factor
Input Frequency Range
Battery capacity Battery Back-up Time (full load) Maximum Charge current (full load) Nominal Voltage Recharge time
Output voltage
Voltage regulation Voltage stability (100% step load) Voltage Recovery time
Voltage distortion
Output frequency
Output overload capability
Unit Weight
Shipping Weight
10 Bay (A) 16 Bay (B) 12 Bay (C) 16 Bay (D) 10 Bay (E) 16 Bay (F)
Xfmr-free Xfmr-based Xfmr-free dual inverter
15 kVA 20 kVA 15 kVA 20 kVA 15 kVA 20 kVA
13.5 kW 18 kW 13.5 kW 18 kW 13.5 kW 18 kW
General and Environment
IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A, FCC Part 15 Class A
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Yes
All Models
440 mm (17 in) 440 mm (17 in) 440 mm (17 in) 440 mm (17 in) 440 mm (17 in) 440 mm (17 in)
800 mm (32 in) 850 mm (34 in) 800 mm (32 in) 850 mm (34 in) 800 mm (32 in) 850 mm (34 in)
695 mm (27 in) 970 mm (38 in) 1060 mm (42 in) 1240 mm (49 in) 695 mm (27 in) 970 mm (38 in)
256 kg (565 lbs) 318 kg (700 lbs) 361 kg (795 lbs) 417 kg (920 lbs) 256 kg (565 lbs) 318 kg (700 lbs)
274 kg (605 lbs) 336 kg (740 lbs) 379 kg (835 lbs) 435 kg (960 lbs) 274 kg (605 lbs) 336 kg (740 lbs)
91.8-92.0% 91.6-92.0% 88.5-89.9% 88.6-89.7% 90.4-91.0% 90.0-91.0%
4208 BTU / Hr 5747 BTU / Hr 5528 BTU / Hr 7965 BTU / Hr 4904 BTU / Hr 6768 BTU / Hr
380/400/415 Vac; 3 Phase Not Applicable
Single-phase input, > 0.99 Cos;
three-phase input, > 0.95 Cos
5 minutes (for non-redundant system which has equal number of battery strings and power modules)
200/208/220/230/240 Vac; Single
Phase
5%, non-linear load 7%, non-linear load 5%, non-linear load
Yes
All Models
Dimensions — mm (in) & Weight kg (lbs)
200/208/220/230/240 Vac; Single Phase
The input voltage range based on the ouput loading, refer to User Manual
< 5 hours to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)
WEEE and ROHS2 (6 by 6), REACH Compliant
Yes
10, 15, 20 kVA
Environmental
0 °C - 40 °C (32 °F - 104 °F)
0 - 95%, non-condensing
3000 m (10000 ft) @ 25°C (77°F)
Input Data
40 Hz to 70 Hz auto-sensing
Battery Module
36W @ 15min-rate to 1.67V per cell @ 25°C (77°F)
Power module internal charger: 1.8A / Charger module: 10A
144 VDC
Output Data
100/100/173/200,110/110/
190/220, 115/115/199/230,
120/120/208/240 Vac; Single Phase
60 minutes
3%, linear load
50/60 Hz
< 104% continuous
105% - 130% for 1 min
131% - 150% for 10 sec
151% - 200% for 1 sec
> 201% for 250 msec
Yes
10, 15, 20 kVA
Single-phase input, > 0.99 Cos
230/115, 240/120 Vac; Single Phase
±3%
±7%
All Models
200/100, 208/120, 220/110,
200/100, 208/120, 220/110,
Yes
All Models
230/115, 240/120 Vac;
Single Phase
Yes
2
Uninterruptible Power Supplies
Table 17: Mechanical Description
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Dimension mm (In)
Chassis Height (H) Depth (D)
S5KC-A SERIES
S5KC-B SERIES
S5KC-C SERIES
S5KC-D SERIES
S5KC-E SERIES
S5KC-F SERIES
Chassis Designation Number of Bays Description
695 (27) 800 (32)
970 (38) 850 (34)
1060 (42) 800 (32)
1240 (49) 850 (34)
695 (27) 800 (32)
970 (38) 850 (34)
440 (17) (W)
(H)
(D)
SOLAHD
Chassis Dimensions
S5KC-A 10 Bay
S5KC-B 16 Bay
S5KC-C 12 Bay
S5KC-D 16 Bay
S5KC-E 10 Bay
S5KC-F 16 Bay
5-15 kVA, 1PH, Xfmr-free, 200-240 VAC input/output
5-20 kVA, 1PH, Xfmr-free, 200-240 VAC input/output
5-15 kVA, 1PH, Xfmr-based, 200-240 VAC input - 200/100-240/120 VAC output
5-20 kVA, 1PH, Xfmr-based, 200-240 VAC input - 200/100-240/120 VAC output
5-15 kVA, 2PH, Xfmr-free, 200/100-240/120 VAC input/output
5-20 kVA, 2PH, Xfmr-free, 200/100-240/120 VAC input/output
2
Uninterruptible Power Supplies
S5KC Operating Modes
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The S5KC UPS is a true online double-conversion system, having the following operating modes:
• Normal Mode
• Back-up Mode
• Auto Restart Mode
• Bypass Mode
Normal Mode
The power module rectiers derive power from a utility AC source and supply regulated DC power to the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment. The battery charger is in the power module and maintains a oat-charge on the batteries of the UPS; additionally, the optional charger module (S5KCCHRGRMOD) can also charge the batteries to maintain a quicker recharge time for long back-up time applications.
Back-up Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains energy from the battery modules. The output power will not be interrupted during the failure or restoration of the AC utility/mains source.
Auto Restart Mode
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will automatically restart and resume supplying power to connected equipment. This feature is enabled at the factory, but can be disabled by the user. The user can also program two auto restart delay settings from the LCD:
• Battery capacity level (%)
• Countdown timer
Bypass Mode
The bypass provides an alternate path for power to the connected equipment and operates in the following manner:
• Automatic: In the event of an internal fault or should the inverter overload capacity be exceeded, the UPS performs an automatic transfer of the connected equipment from the inverter to the bypass source.
• Manual: Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the inverter to the bypass source.
2
Uninterruptible Power Supplies
S5KC-A & S5KC-B Frames:
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Xfmr-Free
S5KC-C & S5KC-D Frames: Xfmr-Based
S5KC-E & S5KC-F Frames: Xfmr-Free
2
Uninterruptible Power Supplies
Table 18: Part Number Configuration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The S5KC modular is available in many combinations. Use the part number template below to identify the description of any given part number.
Series
Designation
Frame Configuration Type System kVA / kW
A = 10 Bay, Xfmr Free, 1PH, cULus Listed, GS/ CE/C-tick Marked
B = 16 Bay, Xfmr Free, 1PH, cULus Listed, GS/ CE/C-tick Marked
C = 12 Bay Xfmr Based, 1PH, cULus Listed, GS/CE/C-tick
Marked
D = 16 Bay Xfmr Based, 1PH, cULus Listed, GS/CE/C-tick
Marked
E = 10 Bay, Xfmr Free, 2PH, cULus Listed
F = 16 Bay Xfmr Free, 2PH, cULus Listed
05A = 5 kVA / 4.5 kW N = No charger module N = Non-redundant
10A = 10 kVA / 9 kW A = 1 charger module
15A = 15 kVA / 13.5
kW
20A = 20 kVA / 18 kW
Number of Charger
Modules
System Type
R = Redundant Power
and Controls
F = Redundant Power, Controls, and Battery
Battery Type and Number
Strings
NN = None (allows for empty replacement frames to be shipped)
C1 = 1 String, CSB UPS 12460 F2 FR
C2 = 2 Strings, CSB UPS 12460 F2 FR
C3 = 3 Strings, CSB UPS 12460 F2 FR
C4 = 4 Strings, CSB UPS 12460 F2 FR
C5 = 5 Strings, CSB UPS 12460 F2 FR
C6 = 6 Strings, CSB UPS 12460 F2 FR
C7 = 7 Strings, CSB UPS 12460 F2 FR
Example: 10 Bay, 1PH, 10 kVA/9 kW, No Charger Module, Non-Redundant, 2 strings, 208V, 60 Hz, L-L-G, No Distribution Slots, Standard Product
S5K A 10A A N C2 C N N C
2
Uninterruptible Power Supplies
1. Every pre-congured S5KC UPS arrives standard with one IS-UNITY-DP communications card installed. This allows you to take advantage of the
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
monitoring included with your system during your initial standard warranty period. Start-up services available, contact your local SolaHD sales representative
for details.
2. “Maximum Upgrade” capacity considerations. The Maximum Upgrade is the highest kVA expansion each conguration will provide without removing any of the battery modules from the original conguration. Please consider your future expansion and redundancy needs.
Configuration Notes:
Output Voltage/
Frequency/Wiring
A = 200V, 60Hz, L-L-G N = None N = None C = Standard product
B = 220V, 60Hz, L-L-G
C = 208V, 60Hz, L-L-G
D = 240V, 60Hz, L-L-G
E = 200/100V, 60Hz, L-L-N-G
F = 220/110V, 60Hz, L-L-N-G
G = 208/120V, 60Hz, L-L-N-G
H = 240/120V, 60Hz, L-L-N-G
J = 220/127V, 60Hz, L-L-N-G
Distribution Slot 1 Distribution Slot 2 Product Type
1 = (2) L6-30R, (8) 5-15/20R [PD2-101]
2 = (4) L6-20R, (4) 5-15/20R [PD2-102]
3 = (4) L6-30R, (4) 5-15/20R [PD2-103]
4 = (2) L6-30R, (2) L6-20R, (4) 5-15/20R [PD2-104]
5 = (2) L5-30R, (2) L5-20R, (4) 5-15/20R [PD2-105]
6 = (4) L6-20R, (4) L5­20R [PD2-106]
7 = (4) L5-20R, (4) 5-15/20R [PD2-107]
8 = (2) L6-30R, (2) L6­20R [PD2-108]
9 = (2) L14-30R [PD2­109]
A = (4) IEC320-C19, (4) IEC320-C13 [PD2-200]
B = (2) IEC320-C19, (8) IEC320-C13 [PD2­201]
C = (12) IEC320-C13 [PD2-202]
D = (2) IEC309-32A, (4) IEC320-C13 [PD2-204]
1 = (2) L6-30R, (8) 5-15/20R [PD2-101]
2 = (4) L6-20R, (4) 5-15/20R [PD2-102]
3 = (4) L6-30R, (4) 5-15/20R [PD2-103]
4 = (2) L6-30R, (2) L6-20R, (4) 5-15/20R [PD2-104]
5 = (2) L5-30R, (2) L5-20R, (4) 5-15/20R [PD2-105]
6 = (4) L6-20R, (4) L5­20R [PD2-106]
7 = (4) L5-20R, (4) 5-15/20R [PD2-107]
8 = (2) L6-30R, (2) L6­20R [PD2-108]
9 = (2) L14-30R [PD2­109]
A = (4) IEC320-C19, (4) IEC320-C13 [PD2-200]
B = (2) IEC320-C19, (8) IEC320-C13 [PD2­201]
C = (12) IEC320-C13 [PD2-202]
D = (2) IEC309-32A, (4) IEC320-C13 [PD2-204]
2
Uninterruptible Power Supplies
Table 19: Basic Recommended Part Numbers (scalable for your application needs)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Back-up time: 5 minutes minimum at full load with 1-battery string per 5 kVA
kVA/kW
5/4.5 S5KA05ANNC1CNNC 7/2 S5KA05ANRC1CNNC 6/2
10/9 S5KA10ANNC2CNNC 5/1 S5KA10ANRC2CNNC 3/1
15/13.5 S5KA15ANNC3CNNC 1/0 S5KA15ANRC3CNNC 0/0
5/4.5 S5KB05ANNC1CNNC 13/3 S5KB05ANRC1CNNC 12/3
10/9 S5KB10ANNC2CNNC 10/2 S5KB10ANRC2CNNC 9/2
15/13.5 S5KB15ANNC3CNNC 7/1 S5KB15ANRC3CNNC 6/1
20/18 S5KB20ANNC4CNNC 4/0 S5KB20ANRC4CNNC 3/0
5/4.5 S5KC05ANNC1GNNC 9/2 S5KC05ANRC1GNNC 8/2
10/9 S5KC10ANNC2GNNC 6/1 S5KC10ANRC2GNNC 5/1
15/13.5 S5KC15ANNC3GNNC 3/0 S5KC15ANRC3GNNC 2/0
5/4.5 S5KD05ANNC1GNNC 13/3 S5KD05ANRC1GNNC 12/3
Non-Redundant Catalog Number
S5KC Xfmr-Based (Input: 2W + G, Output: 3W + G)
S5KD Xfmr-Based (Input: 2W + G, Output: 3W + G)
Available
Expansion Bays
(Total/Power)
S5KA Xfmr-Free (2W + G)
S5KB Xfmr-Free (2W + G)
Redundant
Catalog Number
Available
Expansion Bays
(Total/Power)
10/9 S5KD10ANNC2GNNC 10/2 S5KD10ANRC2GNNC 9/2
15/13.5 S5KD15ANNC3GNNC 7/1 S5KD15ANRC3GNNC 6/1
20/18 S5KD20ANNC4GNNC 4/0 S5KD20ANRC4GNNC 3/0
S5KE Xfmr-Free (3W + G)
5/4.5 S5KE05ANNC1GNNC 7/2 S5KE05ANRC1GNNC 6/2
10/9 S5KE10ANNC2GNNC 5/1 S5KE10ANRC2GNNC 3/1
15/13.5 S5KE15ANNC3GNNC 1/0 S5KE15ANRC3GNNC 0/0
S5KF Xfmr-Free (3W + G)
5/4.5 S5KF05ANNC1GNNC 13/3 S5KF05ANRC1GNNC 12/3
10/9 S5KF10ANNC2GNNC 10/2 S5KF10ANRC2GNNC 9/2
15/13.5 S5KF15ANNC3GNNC 7/1 S5KF15ANRC3GNNC 6/1
20/18 S5KF20ANNC4GNNC 4/0 S5KF20ANRC4GNNC 3/0
1. Voltage Options: Additional Output Voltage Congurations are available. Refer to Table 16 and 18, part number conguration template table. Example: D = 240V, 60Hz, L-L-G ; S5KC05ANN1DNNC is a 240V conguration.
2. Every pre-congured S5KC UPS arrives standard with one IS-UNITY-DP communications card installed. This allows you to take advantage of the moni­toring included with your system during your initial standard warranty period. Start-up services available, contact your local SolaHD sales representative for
details.
3. Available Expansion Bays (Total/Power) equals the TOTAL available expansion bays still available and POWER is the number of bays that can be used for remaining POWER modules up to the maximum allowed for that conguration. For example: S5KA05ANNC1 either 6 battery modules, 1 charging module or 6 battery modules and 2 power modules.
4. Do you require an EBC or MBC? Please refer to conguration table 20 and 21 to build an appropriate part.
Configuration Notes:
CNNC, has 7 total, 2 power so you can add
Congurations with run-times in excess of 5 minutes are available, contact Technical Services.
2
Uninterruptible Power Supplies
Table 20: External Battery Cabinet (EBC) Part Number Configuration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The S5KC Modular UPS includes internal batteries. Optional, matching external battery cabinets, offer extended battery runtime. Use the part number template below to identify the description of any given part number.
Specifications
Mechanical
Conducted and Radiated EMC Levels
Safety Standards IEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22.2 No. 107.3
Immunity Standards IEC/EN/AS 61000-4-2, 3, 4, 5, 6 (C-tick)
Transportation ISTA-1E
Dimensions, WxDxH in (mm)
Unit Weight, lbs (kg) 148 lbs (67 kg)
Shipping Weight, lbs (kg) 209 lbs (95kg)
Environmental
Operating Temperature °F (°C) 32 °F to 104 °F (0 °C to 40 °C)
Storage Temperature, °F (°C)
Relative Humidity, % 0 - 95%, non-condensing
Altitude, ft. (m) 10000 ft (3000 m)
IEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
17x28x38 in
(440x712x970 mm)
Without battery: -4 °F to 140 °F (-20 °C to 60 °C)
With battery: 5 °F to 104 °F (-15 °C to 40 °C)
E179213
Number of Battery
Strings Battery Manufacturer Battery Model Overcurrent Protection Product Type
Series
Designation
Frame Configuration
Type
1 = 1 String C = CSB
2 = 2 Strings
3 = 3 Strings
4 = 4 Strings
5 = 5 Strings
6 = 6 Strings
7 = 7 Strings
N = None (allows for empty replacement frames to be shipped)
Example: 4 String, CSB, CSB UPS 12460 F2 FR, Circuit Breaker, Standard Product
N = None (allows for empty replacement frames to be shipped)
XX = CSB UPS 12460 F2 FR
NN = None (allows for empty replacement frames to be shipped)
B = Circuit Breaker
C = Standard
product
S5K EBC 4 C XX B C
2
Uninterruptible Power Supplies
Table 21: Maintenance Bypass Options
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The S5KC Modular Series Maintenance Bypass provides maximum system availability to business critical equipment by allowing transfer of connected equipment to an alternate power path allowing full isolation of the UPS for maintenance. The UPS can then be turned Off and removed from service with no interruption of power to connected equipment.
Specifications
Mechanical
Dimensions, W x D x H, mm (In) 440 x 862 355 mm (17.3 x 33.9 x 14.3 in)
IEC/EN/AS 62040-1:2008, UL 1778 4th Ed
and CSA 22.2 No. 107.3
E179213
Safety Standards
Transportation ISTA Procedure 1A
Weight, kg (lbs) 30 kg (66.1 lbs)
Environmental
Operating Ambient Temperature 0°C to +40°C (32°F to 104°F)
Storage Ambient Temperature -20°C to +60°C (-4°F to +140°F)
Humidity 0 to 95% non-condensing
R = Rackmount 1 = 15 kVA, 100A
Series Designation
Frame Configuration Type
Mounting Rating
2 = 20 kVA, 125A
Example: Rackmount, 15 kVA, 100A, 208V, 60Hz, L-L-G, UL, cUL Listed, No Distribution Slots, Standard Product
Voltage/Frequency/
Wiring
A = 200V, 60Hz, L-L-G
B = 220V, 60Hz, L-L-G
C = 208V, 60Hz, L-L-G
D = 240V, 60Hz, L-L-G
E = 200/100V, 60Hz, L-L-N-G
F = 220/110V, 60Hz, L-L-N-G
G = 208/120V, 60Hz, L-L-N-G
H = 240/120V, 60Hz, L-L-N-G
J = 220/127V, 60Hz, L-L-N-G
Agency Distribution Slot 1 Distribution Slot 2 Product Type
U = cULus N = None N = None
1 = (2) L6-30R, (8) 5-15/20R [PD2-101]
2 = (4) L6-20R, (4) 5-15/20R [PD2-102]
3 = (4) L6-30R, (4) 5-15/20R [PD2-103]
4 = (2) L6-30R, (2) L6-20R, (4) 5-15/20R [PD2-104] 5 = (2) L5-30R, (2) L5-20R, (4) 5-15/20R [PD2-105]
6 = (4) L6-20R, (4) L5-20R [PD2-106]
7 = (4) L5-20R, (4) 5-15/20R [PD2-107]
8 = (2) L6-30R, (2) L6-20R [PD2-108]
9 = (2) L14-30R [PD2-109]
A = (4) IEC320-C19, (4) IEC320-C13 [PD2-200] B = (2) IEC320-C19, (8) IEC320-C13 [PD2-201]
C = (12) IEC320­C13 [PD2-202]
D = (2) IEC309-32A, (4) IEC320-C13 [PD2-204]
1 = (2) L6-30R, (8) 5-15/20R [PD2-101]
2 = (4) L6-20R, (4) 5-15/20R [PD2-102]
3 = (4) L6-30R, (4) 5-15/20R [PD2-103]
4 = (2) L6-30R, (2) L6-20R, (4) 5-15/20R [PD2-104] 5 = (2) L5-30R, (2) L5-20R, (4) 5-15/20R [PD2-105]
6 = (4) L6-20R, (4) L5-20R [PD2-106]
7 = (4) L5-20R, (4) 5-15/20R [PD2-107]
8 = (2) L6-30R, (2) L6-20R [PD2-108]
9 = (2) L14-30R [PD2-109]
A = (4) IEC320-C19, (4) IEC320-C13 [PD2-200] B = (2) IEC320-C19, (8) IEC320-C13 [PD2-201]
C = (12) IEC320­C13 [PD2-202]
D = (2) IEC309-32A, (4) IEC320-C13 [PD2-204]
C = Standard
product
S5K MBC R 1 C U N N C
NOTES: RM-MBC (Rack Mount - Maintenance By-Pass Cabinet)
2
Uninterruptible Power Supplies
Optional Equipment S5KCCHRGRMOD, Charger Module
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
In AC mains mode, the charger module charges the system
Catalog Number Description
Communication Options
IS-UNITY-DP
IS-RELAY
S5KREPOKIT
IS Communications Card for multiple protocols: BACnet, Modbus, SNMP, Web, YDN23
Relay contact board, relay contact signals for “On Battery”, “Low Battery”, “On Bypass”, "On UPS", “Summary Alarm” and “UPS Fault”.
Remote Emergency Power Off Kit includes 50’ length of cable with connector to UPS and external push button switch.
battery modules or external battery cabinet. Each charger module is rated to deliver 10A charging current. The charger module has an independent control function and maintains real-time communication with the system and the battery modules to ensure stable charging and fault protection.
The charger module may be added or replaced on-line with no interruption or danger to the user, connected battery system or connected equipment.
Optional Equipment
Model Number Description
S5KCRACKKIT
S5KCEBCCBL1M
S5KCEBCCBL3M
S5KCEBCCBL5M
S5KCLRTCONNKIT
S5KCLRTTEMPKIT
S5KCCHRGRMOD
S5KCEBCCARD
S5KCBATMODCU
Rackmount Kit
EBC Cable 1 meter
EBC Cable 3 meters
EBC Cable 5 meters
LRT Connector Kit
LRT Temperature Sensor Kit
Charger Module, 10 amps
EBC Communication Card
Expansion Battery to increase run time. Note: Each kit includes one string (2 modules)
P = Power module B = Battery module C = Charger module * Where you have an empty spot you can add a power, battery or charger.
** Battery module only.
Example: 10-Bay Conguration (S5KC Chassis E and F)
S5KC5KPWRMOD1
(P, B, C) * (P, B, C) *
S5KCBATMODCU = 2 Modules or 1 string
B ** B **
B ** B **
(P, B, C) *
Spare Equipment Parts
Model Number Description
S5KC5KPWRMOD1
S5KC5KPWRMOD2
S5KCBATMODCU
S5KCBYPDSPMOD
S5KCBYPMCUMOD
S5KCLCDMOD
S5KCAFLTRKIT
S5KCAFLTRKIT-FD
S5KCBEZELHMI
S5KCBEZEL
Power Module (PM1), 208/120 VAC, 5 kVA / 4.5kW (E & F Chassis)
Power Module (PM2), 230, 208 VAC, 5 kVA /
4.5kW (A, B, C & D Chassis)
Replacement Battery Note: Each kit includes one string (2 modules)
Bypass DSP Module
Bypass MCU Module
LCD module
Air Filter Kit
Fine Dust Air Filter Kit
Metal HMI Bezel with Display Opening and Filter
Metal Bezel for Module Bays and Filter
2
Uninterruptible Power Supplies
UPS Extended Warranty Offering for the SolaHD S1K, S3K and S4K Series
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
S1K
Catalog Number Description
1-Year Extended Warranty
1EWPS1K320
1EWPS1K520
1EWPS1K650
1EWPS1K850
1EWPS1K1200
1EWPS1K1500
3EWPS1K320
3EWPS1K520
3EWPS1K650
3EWPS1K850
3EWPS1K1200
3EWPS1K1500
1-year extended warranty for S1K320
1-year extended warranty for S1K520
1-year extended warranty for S1K650
1-year extended warranty for S1K850
1-year extended warranty for S1K1200
1-year extended warranty for S1K1500
3-Year Extended Warranty
3-year extended warranty for S1K320
3-year extended warranty for S1K520
3-year extended warranty for S1K650
3-year extended warranty for S1K850
3-year extended warranty for S1K1200
3-year extended warranty for S1K1500
S3K
Catalog Number Description
1-Year Extended Warranty
1EWPS3K700
1EWPS3K1000
1EWPS3K1600
3EWPS3K700
3EWPS3K1000
3EWPS3K1600
1-year extended warranty for S3K700
1-year extended warranty for S3K1000
1-year extended warranty for S3K1600
3-Year Extended Warranty
3-year extended warranty for S3K700
3-year extended warranty for S3K1000
3-year extended warranty for S3K1600
S4KC Industrial – UPS Models
The extended warranty program extends the standard two-year product warranty by the term of the extension purchased, 1-year or 3 years. This results in warranty terms of 3 or 5 years (depending on the extension selected) from the date of purchase. SolaHD will repair or replace the unit at any point during the extension period, subject to the same conditions as the standard warranty. The warranty extension
is not transferable.
Catalog Number Description
1-Year Extended Warranty
1EWPS4K2U700C
1EWPS4K2U1000C
1EWPS4K2U1500C
1EWPS4K2U2000C
1EWPS4K2U3000C
1EWPS4K4U6000C
1EWPS4K6U10KC
3EWPS4K2U700C
3EWPS4K2U1000C
3EWPS4K2U1500C
3EWPS4K2U2000C
3EWPS4K2U3000C
3EWPS4K4U6000C
3EWPS4K6U10KC
Note: Warranty on S4K4U6000 covers electronics and internal battery.
1-year extended warranty for S4K2U700C
1-year extended warranty for S4K2U1000C
1-year extended warranty for S4K2U1500C
1-year extended warranty for S4K2U2000C
1-year extended warranty for S4K2U3000C
1-year extended warranty for S4K4U6000C
1-year extended warranty for S4K6U10KC
3-Year Extended Warranty
3-year extended warranty for S4K2U700C
3-year extended warranty for S4K2U1000C
3-year extended warranty for S4K2U1500C
3-year extended warranty for S4K2U2000C
3-year extended warranty for S4K2U3000C
3-year extended warranty for S4K4U6000C
3-year extended warranty for S4K6U10KC
S4KC Industrial – Battery Cabinets
Catalog Number Description
S4K4UC AND S4K6UC – Maintenance Bypass Switch
Catalog Number Description
1-Year Extended Warranty
1EWPS4K06KPAD
1EWPS4K10KPAD
3EWPS4K06KPAD
3EWPS4K10KPAD
1-year extended warranty for S4K4UC PADs
1-year extended warranty for S4K6UC PADs
3-Year Extended Warranty
3-year extended warranty for S4K4UC PADs
3-year extended warranty for S4K6UC PADs
1EWPS4K2U48BATC
1EWPS4K2U96BATC
1EWPS4K144BATC
1EWPS4K288BATC
3EWPS4K2U48BATC
3EWPS4K2U96BATC
3EWPS4K144BATC
3EWPS4K288BATC
1-Year Extended Warranty
1-year extended warranty for S4K2U48BATC
1-year extended warranty for S4K2U96BATC
1-year extended warranty for S4K144BATC
1-year extended warranty for S4K288BATC
3-Year Extended Warranty
3-year extended warranty for S4K2U48BATC
3-year extended warranty for S4K2U96BATC
3-year extended warranty for S4K144BATC
3-year extended warranty for S4K288BATC
2
Uninterruptible Power Supplies
Field Service Programs for the S4K4UC/6UC Industrial and S5KC Series
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
These programs are for Domestic coverage (valid only within the continental United States and Canada); additional travel expenses may be billed to customers with site locations more than 150 miles from a major metropolitan area.
S4K4UC/6UC Industrial Start-Up Programs
Start-Up includes one site trip within the contiguous 48 states by a factory trained technician. Any additional trips by the customer service engineer as a result of the site not being ready for start-up may result in additional costs to the customer. The site trip includes the following services for one UPS module:
• Rack construction, installation or re-conguration with UPS
accessories.
• Installation includes mounting and start-up of new UPS and internal batteries (excludes hard-wired applications).
• Services performed by factory trained technician.
• Services performed 24x7, excluding national holidays within the 48 contiguous states.
S5KC Modular Start-Up Programs
Start-up services should be ordered as a separate line item at the time of purchase. S5KC Series UPS sold with start-up Services are provided with a 2 year parts and labor warranty. Please refer to the following information for a menu of start­up options and please choose the appropriate start-up service required. If start-up is not ordered and performed, please note that this will reduce your warranty period to two years of parts and, 90 days labor.
A separate Preventative Maintenance Only plan is available in addition to the standard Start-Up plan.
Service Programs - S4K4UC/6UC and S5KC Series
Preferred service level options include 6-hour on-site response, 24x7 within 150 miles of nearest service centers. 24x7 emergency service includes parts (including internal batteries), labor, and travel. Also includes one (1) Preventive Maintenance (PM) visit per year, scheduled at the customer’s convenience (24x7).
Essential service level options include 6-hour on-site response, 24x7 within 150 miles of nearest service centers. 24x7 emergency service includes parts (including internal batteries), labor, and travel. Also includes one (1) Preventive Maintenance (PM) visit per year, scheduled by the customer for M-F 8AM-5PM.
Basic service level options include 6-hour on-site response, 24x7 within 150 miles of nearest service centers. 24x7 emergency service includes parts (excluding internal batteries), labor, and travel. Preventive Maintenance (PM) not included and is not available if the Basic Service plan is
selected.
2
Uninterruptible Power Supplies
Field Service Programs for the S4K4UC, S4K6UC Industrial and S5KC Series - continued
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
S4K4UC and S4K6UC Industrial Start-Up Programs S5KC Start-Up Services
Catalog Number Description
Domestic Only (7-Days/Week, 24 Hrs/Day)
SUS4K061U7
SUS4K101U7
6 kVA Start-Up
10 kVA Start-Up
S4K4UC and S4K6UC Industrial Service Programs
Preferred Service (w/ 1 PM)
Catalog Number Equipment
MUUS4K06PR1
MEUS4KBATPR1
MUUS4K10PR1
Catalog Number Equipment
MUUS4K06ES1
MEUS4KBATES1
MUUS4K10ES1
Basic Service (PM not available)
Catalog Number Equipment
MUUS4K06BA0
MEUS4KBATBA0
MUUS4K10BAO
S4K4U6000C
S4K144BATC & S4K288BATC
S4K6U10KC
Essential Service (w/ 1 PM)
S4K4U6000C
S4K144BATC & S4K288BATC
S4K6U10KC
S4K4U6000C
S4K144BATC & S4K288BATC
S4K6U10KC
Catalog Number Equipment
SUS5KCXXMF
SUS5KCXX24
SUPS5KCXXMF
SUPS5KCXX24
PM = Preventative Maintenance
S5KC Start-Up Monday-Friday 8-5
S5KC Start-Up 7x24
S5KC Start-Up Plus M-F 8-5 w/1PM over initial warranty period
S5KC Start-Up Plus 7x24 w/1PM over initial warranty period
S5KC Modular Service Programs
Contact Technical Services to obtain the catalog number for any of the Preferred, Essential or Basic Services (catalog number depends on the S5KC conguration).
X = Number of Power/Charger Modules (#1 through #6)
YY = Number of Battery Modules (#01 through #07)
Catalog Number Service Program
MUUS5KCXPRYY
MUUS5KCXESYY
MUUS5KCXBAYY
MS5KC1PM24
Note: Service programs are valid for one year.
Preferred Service
Essential Service
Basic Service
PM Only (7-Days/Week, 24 Hrs/Day) for all congurations
1 PM Only (Mon-Fri, 8 am - 5 pm)
Catalog Number Equipment
MS4K061PM85
MS4KBAT1PM85
MUUS4K10PM85
1 PM Only (7-Days/Week, 24 Hrs/Day)
Catalog Number Equipment
MS4K061PM24
MS4KBAT1PM24
MUUS4K10PM24
S4K4U6000C
S4K144BATC & S4K288BATC
S4K6U10KC
S4K4U6000C
S4K144BATC & S4K288BATC
S4K6U10KC
Loading...