SolaHD Product Manual: IP67 SCP-X Dual Stack Power Supply Manuals & Guides

Power Supplies
SCP-X Series
2 x 100 W Models
Installation Specications
2
DC 2
DC 12
2
DC 2
DC 12
Fuse
Input: Internally fused; fuses not replaceable. Output: NEC Class 2 per UL 1310.
Mounting
Chassis mounted using integral mounting tabs. Recommended Screw Size: M4 x 0.7. Tightening Torque: 1N-m.
Connections
An accessible disconnect device shall be installed external to the equipment.
Input: 3-PIN IP67 molded plug (quick disconnect). Output: 4-PIN IP67 molded receptacle (quick disconnect).
Use UL 758 wire rated min. 24 V , VW-1/FT-1, max. 3.05 m.
Recommended Connectors/Cord sets
Input 3-PIN Connector: Harting, P/N: 21 04 516 23** (**length in meters) Output 4-PIN Connector: Harting, P/N: 21 04 516 14** (**length in meters)
Notes
(1) Connections to be provided by the user. (2) This product is limited for use in a restricted access area that is under the control of authorized personnel. It can only be
installed and maintained by qualied technicians.
Electrical Connections
Input SCP 102D24X-C02 SCP 102D24X-D02
1 = Ground 2 = Power 3 = Neutral
INPUT 50/60/400 Hz 100–240 V ac / 2.4–1.4 A 100–353 V dc / 2.4–0.7 A
Output SCP 102D24X-C02 SCP 102D24X-D02
2
1
1 = +24 V--­2 = +24 V--­3 =
0 V---
4
3
1
3
DC 2
DC 1
2
4
4 = 0 V---
OUTPUT 24 V--- /3.8 A (x2) CLASS 2
3
4
2
DC 11
4
2
DC 12
1
1
3
3
1
1
3
DC 1
DC 2
1 = Ground 2 = Power 3 = Neutral
INPUT 50/60/400 Hz 100–240 V ac / 2.4–1.4 A 100–353 V dc / 2.4–0.7 A
2
1 = +24 V--­2 = +24 V--­3 = GROUND
4
4 = - V---
OUTPUT
2
24 V--- /3.8 A (x2) CLASS 2
4
3
4
1
2
DC 11
3
4
1
2
DC 12
Especicaciones de Instalación
Fusible
Entrada: Fusibles internos no reemplazables. Salida: NEC Clase 2 según UL 1310.
Montaje
Chasis instalado con lengüetas incorporadas. Recomendado tamaño de tornillo: M4 x 0,7. Par de Apriete: 1N-m.
Conexiones
Un dispositivo accesible de desconexión será instalado externo al equipo.
Entrada: Conector moldeado de 3 pines IP67 (de descon ex ión rápida). Salida: Receptáculo moldeado de 4 pines IP67 (de desconexión rápida).
Utilizar cable nominal UL 758 min. 24 V, VW-1/FT-1, máx. 3,05 m.
Conectores recomendados o conjuntos de cables
Entrada de 3 Pines Conector: Harting, P/N: 21 04 516 23** (**la longitud en metros) Salida de 4 Pines Conector: Harting, P/N: 21 04 516 14** (**la longitud en metros)
Notas
(1) Las conexiones para ser proporcionadas por el usuario. (2) Este producto es de uso limitado a un área de acceso restringido que está bajo el control del personal
autorizado. Sólo puede ser instalado y mantenido por técnicos cualicados.
Spécications d’installation
Fusible
Entrée : Fusibles internes, non remplaçables. Sortie : UL 1310 de NEC Classe 2.
Montage
Châssis monté au moyen des onglets de montage intégrés. Taille de vis recommandée : M4 x 0.7. Couple de vis : 1N-m.
Connexions
Un accessible débranche l’appareil sera installé externe à l’équipement.
Entrée : Fiche moulée IP67 à 3 broches (débranchement rapide). Sortie : Prise moulée IP67 à 4 broches (débranchement rapide).
Utiliser UL 758 l nominale min. 24 V, VW-1/FT-1, max. 3,05 m.
Connecteurs recommandées ou cordons
Entrée 3 Broches Connecteur : Harting, P/N: 21 04 516 23** Sortie 4 Broches Connecteur : Harting, P/N: 21 04 516 14** (**la longueur dans les mètres)
Notes
(1) Les connexions être fournis par l’utilisateur. (2) Ce produit est limité pour une utilisa­tion dans une zone d’accès restreint qui est sous le contrôle du personnel autorisé. Elle
ne peut être installé et entretenu par des techniciens qualiés.
(**la longueur dans les mètres)
Conexiones Eléctricas
Entrada SCP 102D24X-C02 SCP 102D24X-D02
1 = Tierra 2 = Potencia 3 = Neutral
ENTRADA 50/60/400 Hz 100–240 V CA / 2,4–1,4 A 100–353 V CC / 2,4–0,7 A
1 = Tierra 2 = Potencia 3 = Neutral
ENTRADA 50/60/400 Hz 100–240 V CA / 2,4–1,4 A 100–353 V CC / 2,4–0,7 A
Salida SCP 102D24X-C02 SCP 102D24X-D02
3
1
1 = +24 V--­2 = +24 V--­3 =
4
3
1
3
DC 1
2
4
4 = 0 V---
SALIDA 24 V--- /3,8 A (x2) CLASE 2
0 V---
4
2
DC 11
4
2
1
1 = +24 V--­2 = +24 V--­3 = GROUND
1
3
1
4
3
1
3
DC 1
2
4
4 = - V---
SALIDA 24 V--- /3,8 A (x2) CLASE 2
Connexions électriques
Entrée SCP 102D24X-C02 SCP 102D24X-D02
1 = Terre 2 = Puissance 3 = Neutre
Entrée 50/60/400 Hz 100–240 V c.a. / 2,4–1,4 A 100–353 V c.c. / 2,4–0,7 A
Sortie SCP 102D24X-C02 SCP 102D24X-D02
2
1
1 = +24 V--­2 = +24 V--­3 =
0 V---
4
3
1
3
DC 2
DC 1
2
4
4 = 0 V---
SORTIE 24 V--- /3,8 A (x2) CLASSE 2
3
4
2
DC 11
4
2
DC 12
1
1
3
3
1
DC 1
1
3
DC 2
1 = Terre 2 = Puissance 3 = Neutre
Entrée 50/60/400 Hz 100–240 V c.a. / 2,4–1,4 A 100–353 V c.c. / 2,4–0,7 A
2
1 = +24 V--­2 = +24 V--­3 = GROUND
4
4 = - V---
SORTIE
2
24 V--- /3,8 A (x2) CLASSE 2
4
3
4
1
2
DC 11
3
4
1
2
3
4
1
2
DC 11
3
4
1
2
DC 12
Dimensions/Dimensiones/Dimensions
6.52 in. [165.6 mm]
4.22 in. [107.1 mm]
4.73 in. [120.1 mm]
7.00 in. [177.8 mm]
While every precaution has been taken to ensure accuracy and completeness in this literature, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Specications are subject to change without notice. Aunque se ha tomado toda precaución para asegurar precisión e integridad en esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna responsabilidad y deniega toda responsabilidad por daños que resulten por el uso de esta información o por cualquier error u omisión. Las especicaciones están sujetas a cambios sin
previo aviso. Nous avons pris toutes les précautions possibles pour assurer l’exactitude et l’intégrité du présent document ; cependant
Appleton Grp LLC d/b/a Appleton Group n’assume aucune obligation et rejette toute responsabilité en ce qui concerne les dommages découlant de l’utilisation du présent document ou de toute erreur ou omission qu’il pourrait comprendre. Les spécications sont sujettes à modication sans préavis.
3.27 in. [83.0 mm]
6.15 in. [156.1 mm] TYP
(1)
Technical Specications
Input
Nominal Voltage 100–240 V ac Dc Range 100–353 V dc Nominal Current 2.4–1.4 A / 2.4–0.7 A Maximum Inrush Current Typically <30 A Power Factor Frequency 50/60/400 Hz
Output (x2)
Nominal Voltage 24 V dc Total Nominal Current 7.6 A total (3.8 A max. per pair) Power Back Immunity 35 V
Hold-up Time Tolerance <± 2% overall
• Line Regulation <0.5%
• Load Regulation <0.5%
• Time and Temperature Drift <1%
Initial Voltage Setting 24.5 V ± 1% Ripple Overvoltage Protection 25–25.5 V dc, auto recovery
Standards & Certications
Emmisions
Immunity
Approvals
Environmental Data
Temperature
Min. Free Space Required 1 in. (25 mm) all sides but base Humidity Up to 100% RH with condensation Altitude 0 to 3,000 m (0 to 10,000 ft.)
Vibration
Shock
MTBF
General Protection/Safety
General
Weight 3.3 lb. (1.5 kg) Warranty 5 years
Technical Support
(800) 377-4384/(847) 268-6651 • solahd.technicalservices@emerson.com • www.solahd.com
Notes
(1) Input current ratings are specied with low input, line conditions, worst case efciency values, and power factor. (2) Power factor correction at 50/60 Hz only. (3) Ripple/noise is stated as typical ac values when measured with a 20 MHz, bandwidth scope, and 50 Ohm termination. (4) Emissions and immunity are met by individual power supply modules.
(2)
(3)
(4)
(4)
0.95
>50 ms (Full load, 100 V ac input @ ambient temp = +25°C) to 95% output voltage
<50 mVpp
EN61000-6-3, EN61000-6-4, EN55011 Group 1, Class B, EN55022 Class B, EN61000-3-2, EN61000-3-3
EN61000-6-1, EN61000-6-2, EN55024, IEC61000-4-2, IEC61000­4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, SEMI F47 Sag Immunity
cULus Listed: UL 508, CSA C22.2 No. 107.1, UL 60950-1/CSA C22.2 60950-1, 2nd Ed. Outputs meet Class 2 limits in accordance with UL 1310/CSA C22.2 No. 223. CE: IEC60950-1:2005 (2nd Ed.), Am1:2009 + Am2:2013, EN60950-1:2006 + A11:2009 + A1:2010 + A12:2011 + A2:2013, EN60529: IP66, IP67 (Pending)
Storage: -40°C to +85°C. Operation: -25°C to +60°C full power with linear derating to half power from 60°C to 70°C. Convection cooling; no forced air required. Operation up to 100% load permissible with sideways or front side up mounting orientation.
1 g non-operating swept sine over 10–500 Hz (IEC 60068-2-6). Non-operating random vibration test: 1.87 g over 10–500 Hz (IEC 60068-2-64). Operating random vibration test: 0.15 g over 5–100 Hz (IEC 60068-2-64).
Non-operating: 30 g peak, 18 ms half-sine pulse (IEC 68-2-27). Operating: 4 g peak, 22 ms half-sine pulse (IEC 68-2-27).
>800,000 hr. according to Telcoredia/Bellcore SR-332 Issue 3 (Vin 120 V ac, ambient temp. = 40°C)
Protected against continuous short-circuit, continuous overload, continuous open circuit. Protection Class 1. Safety extra low voltage: SELV (acc. EN60950).
(1)
Datos Técnicos
Entrada
Voltaje nominal 100–240 V CA de entrada Rango de CC 100–353 V CC Corriente nominal 2,4–1,4 A / 2,4–0,7 A Corriente máx. de irrupción Tipicamente <30 A Factor de potencia Frecuencia 50/60/400 Hz
Salida (x2)
Voltaje nominal 24 V CC Corriente nominal total 7,6 A total (3,8 A máx. por par) Inmunidad inversa de potencia 35 V
Tiempo de retención Tolerancia <± 2% total
• Regulación de línea <0,5%
• Regulación de carga <0,5%
• Tiempo y deriva de temperatura <1%
Valor inicial de voltaje 24,5 V ± 1% Ondulación Protección contra sobrevoltaje 25–25,5 V dc, recuperación automática
Normas y Certicaciones
Emisiones
Inmunidad
Aprobaciones
Datos ambientales
Temperatura
Espacio libre mínimo requerido Humedad Altitud
Vibración
Choque
MTBF
Protección/Seguridad General
General
Peso 1,5 kg (3,3 lb.) Garantía 5 años
Servicio Técnico
(800) 377-4384/(847) 268-6651 • solahd.technicalservices@emerson.com • www.solahd.com
Notas
(1) Las clasicaciones de corriente de entrada se especican con valores de entrada baja, condiciones de línea, eciencia más
baja y factor de potencia. (2) Enchufe corrección de factor en 50/60 Hz sólo. (3) La ondulación y el ruido se expresan como valores típicos de CA cuando se miden con un alcance de ancho de banda de 20 MHZ y una terminación de 50 Ohmios. (4) Las emisiones y la inmunidad se cumplen por los distintos módulos de alimentación.
(2)
(3)
(4)
(4)
0,95
>50 ms (carga completa, 100 V CA de entrada a temp. amb. = +25°C) a un voltaje de salida del 95%
<50 mVpp
EN61000-6-3, EN61000-6-4, EN55011 Grupo 1, Clase B, EN55022 Clase B, EN61000-3-2, EN61000-3-3
EN61000-6-1, EN61000-6-2, EN55024, IEC61000-4-2, IEC61000­4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, SEMI F47 Inmunidad a Picos
cULus Listada: UL 508, CSA C22.2 No. 107.1, UL 60950-1/CSA C22.2 60950-1, 2a Ed. Productos cumplen con los límites de Clase 2 de conformidad con UL 1310/CSA C22.2 nO 223. CE: IEC60950-1:2005 (2a Ed.), Am1:2009 + Am2:2013, EN60950-1: 2006 + A11:2009 + A1:2010 + A12:2011 + A2:2013, EN60529: IP66, IP67 (Pendiente)
De almacenamiento: -40° a +85°C. De funcionamiento: -25°C a +60°C a toda potencia, con reducción lineal a media potencia de 60°C a 70°C. Refrigeración por convección; no necesita aire forzado. Es posible la operación con una carga de hasta el 100% utilizando una orientación lateral o frontal en la instalación.
25 mm (1 pulg.) en todos los lados excepto la base Hasta el 100% de HR con condensación 0 a 3.000 m (0 a 10.000 pies.)
1 g de no-sinusoidal de barrido de 10 a 500 Hz (IEC 60068-2 -6). De no-prueba de vibración aleatoria: 1,87 g de 10-500 Hz (IEC 60068-2 -64). Prueba de vibración aleatoria funcionamiento: 0,15 g de 5 a 100 Hz (IEC 60068-2 -64).
En reposo: 30 g de pico, 18 ms de pulso de media onda sinusoidal (IEC 68-2 -27). Funcionamiento: 4 g de pico, 22 ms de pulso de media onda sinusoidal (IEC 68-2 -27).
>800.000 horas según Telcoredia/Bellcore SR-332 Edición 3, (V de entrada 120 V CA, temp. amb. = 40°C)
Protegido contra cortocircuitos continuos, sobrecarga continua, circuito abierto continuo. Clase de protección 1. Tensión muy baja de seguridad: SELV (según EN60950).
(1)
Données Techniques
Entrée
Tension nominale Entrée de 100–240 V c.a. Plage c.c. 100-353 V c.c. Intensité nominale 2,4–1,4 A / 2,4–0,7 A Intensité maximale du courant d’appel Typiquement <30 A Facteur de puissance Fréquence 50/60/400 Hz
Sortie (x2)
Tension nominale 24 V c.c. Intensité nominale totale 7,6 A total (3,8 A max. par paire) Immunité contre les actions rétrogrades 35 V
Temps de maintien Tolérance <± 2% globale
• Régulation de ligne <0,5%
• Régulation de charge <0,5%
• Dérive de temps/température <1%
Réglage de tension initial 24,5 V ± 1% Ondulation Protection contre les surtensions autorécupération de 25–25,5 V c.c.
Normes et Autorisations
Emissions
(4)
Immunité
Homologations
Données environnementales
Température d’entreposage
Espace libre min. requis Humidité Altitude
Vibrations
Choc
MTBF
Protection générale/Sécurité
Général
Poids 1,5 kg (3,3 lb.) Garantie 5 ans
Assistance Technique
(800) 377-4384/(847) 268-6651 • solahd.technicalservices@emerson.com • www.solahd.com
Notes
(1) Les courants nominaux sont spéciés en tant qu’entrée faible, conditions de ligne, valeur d’efcacité la plus mauvaise
et facteur de puissance. (2) Alimenter la correction de facteur à 50/60 Hz seulement. (3) L’ondulation/bruit sont indiqués en valeurs types c.a. lorsque mesurées avec un appareil de largeur de bande 20 MHz et une terminaison de 50 ohms. (4) Emissions et immunité sont remplies par les différents modules d’alimentation.
(2)
(3)
(4)
0,95
>50 ms (pleine charge, Entrée 100 V c.a. à temp. ambiante = +25ºC) à une tension de sortie de 95%
<50 mVpp
EN61000-6-3, EN61000-6-4, EN55011 Groupe 1, Classe B, EN55022 Classe B, EN61000-3-2, EN61000-3-3
EN61000-6-1, EN61000-6-2, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000­4-6, IEC61000-4-8, IEC61000-4-11, SEMI F47 immunité sag
cULus Enuméré : UL 508, CSA C22.2 No. 107.1, UL 60950-1/ CSA C22.2 60950-1, 2nd Ed. Sorties conforme aux exigences de la catégorie 2 limites conformément à UL 1310/CSA C22.2 No. 223. CE: IEC60950-1:2005 (2nd Ed.), Am1:2009 + Am2:2013, EN60950-1: 2006 + A1 1:2009 + A1:2010 + A12:2011 + A2:2013, EN60529: IP66, IP67 (En attente)
Stockage : -40º à +85ºC. Fonctionnement : -25ºC à +60ºC à pleine puissance avec dégradation linéaire jusqu’à mi puissance de 60ºC à 70ºC. Refroidissement par convexion; pas besoin d’air pulsé. Fonctionnement jusqu’à 100% de la charge permis avec montage latéral ou avant vers le haut.
25 mm (1 po) sur tous les côtés sauf la base JUSQU’à 100% d’HR avec condensation 0 à 3000 mètres (0 à 10000 pieds) 1 g non-exploitation sinusoïdales de 10-500 Hz (IEC
60068-2-6). Non-fonctionnement essai de vibration aléatoire : 1,87 g à 10-500 Hz (IEC 60068-2 -64). Fonctionnement essai de vibration aléatoire : 0,15 g de 5-100 Hz (CEI 60068-2 -64).
Non-fonctionnement : 30 g crête, 18 ms demi-impulsion sinusoïdale (IEC 68-2 -27). Fonctionnement : 4 g crête, 22 ms demi-impulsion sinusoïdale (IEC 68-2 -27).
>800 000 heures selon Telcoredia/Bellcore SR-332 Issue 3, (Vin 120 V c.a., temp. amb. = 40 ºC)
L’appareil est protégé en permanence contre les courts­circuits, ouverts. Protection de Classe 1. Tension de sécurité extra-basse : SELV (suivant EN60950).
Loading...