socomec SUNSYS PCS2 IM UL, SUNSYS PCS2 IM UL 33 TR, SUNSYS PCS2 IM UL 100 TR, SUNSYS PCS2 IM UL 132 TL, SUNSYS PCS2 IM Installation And Operating Manual

...
Page 1
SUNSYS PCS2 IM UL
INSTALLATION AND OPERATING
MANUAL
Power Conversion System and Storage
with Islanding Mode
from 33 to 200 kVA
EN
www.socomec.com
Page 2
Page 3
CONTENTS
1. SAFETY STANDARDS 6
1.1 DESCRIPTION OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 ABBREVIATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2. FOREWORD 10
3. SUNSYS PCS² RANGES 12
3.1 IEC VERSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 UL VERSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4. ENVIRONMENTAL REQUIREMENTS AND HANDLING 13
4.1 ENVIRONMENTAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.3 FLOOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.4.1 PROCEDURE FOR PCS
4.4.2 PROCEDURE FOR PCS
2
IM 33 - 66 - 100 TR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2
IM 132 - 200 TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5. ELECTRICAL INSTALLATION 32
5.1 ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6. OVERVIEW 34
6.1 SWITCHES AND INTERFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2 DIAGRAM OF MAIN SYSTEM EXAMPLE FOR VERSION 100 TR . . . . . . . . . . . . . . . . 42
7. CONNECTIONS 43
7.1 INPUT CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.2 INSTRUCTIONS FOR SUNSYS PCS
2
IM 200 TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8. CONTROL PANEL 51
8.1 EXCEPTION FOR PCS
2
IM 132 - 200 TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.2 CONVERTER STATE MACHINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9. FIRST START-UP 54
10. MENU 57
10.1 DISPLAY OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
10.2 MENU TREE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
10.3 MENU DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
10.4 DEFAULT SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.4.1 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL VOLTAGES . . . . . . . 64
10.4.2 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL FREQUENCIES . . . 64
10.4.3 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL VOLTAGES . . . . . . . 64
10.4.4 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL FREQUENCIES . . . 64
10.4.5 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL VOLTAGES . . . . . . . 65
10.4.6 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL FREQUENCIES . . . 65
11. OPERATING PROCEDURES 66
11.1 SWITCHING ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
11.2 SWITCHING OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
12. STANDARD FEATURES AND OPTIONS 68
12.1 SERIAL COMMUNICATION INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
12.2 MODBUS TCP INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
12.3 ADC CARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
12.4 SERIAL COMMUNICATION INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
12.5 SIGNAL CABLES ROUTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
13. WARNINGS AND TROUBLESHOOTING 74
14. PREVENTIVE MAINTENANCE 77
14.1 BATTERIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
14.2 FANS & CAPACITORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
15. UL1741SA: HOW TO CONFIGURE GRID SUPPORT FUNCTIONS 78
15.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
15.2 TRIP THRESHOLDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
15.3 RIDE THROUGH MODE & TIMINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
15.4 RAMPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
15.5 ACTIVE/REACTIVE POWER CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
16. SAFEGUARDING THE ENVIRONMENT 86
17. TECHNICAL SPECIFICATIONS 87
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
3EN
Page 4
Page 5
SOCOMEC retains the full and exclusive ownership rights to this document. Only a personal entitlement to use the document for the application indicated by SOCOMEC is granted to the recipient of this document. The reproduction, modification, distribution of this document, either partially or wholly and in any manner, is strictly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC reserves the right to make any changes to the information provided without prior notice.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
5EN
Page 6
1. SAFETY STANDARDS
This user manual specifies installation and maintenance procedures, technical data and safety instructions for SOCOMEC products. For further information visit the Socomec website: www.socomec.com.
The input and output circuits are isolated from the enclosure; the system grounding, when required by Sections 690.41, 690.42, and 690.43 of the National Electric Code, ANSI/NFPA 70, is the responsibility of the installer.
The wiring methods in accordance with the National Electrical Code, ANSI/NFPA 70 and Canadian Electric Code (CEC) are to be used. All national standards applicable to batteries must be observed.
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 170 amperes maximum branch­circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.
This inverter complies with Part 15 of the FCC Rules Operation so it must be able to handle any interference and it must accept any interference received, including interference that may cause undesired operation.
Overcurrent protection for the AC circuit is to be provided by others.
Before carrying out any operations read the interconnection manual and Battery Energy System (BES) safety instructions carefully, in order to work under safe conditions.
If the Battery Energy System (BES) is not supplied by SOCOMEC, overcurrent protection for the BES is to be provided by others.
NOTE! Any work carried out on the equipment must be performed by skilled, qualified technicians.
NOTE! Before carrying out any operations on the unit read the installation and operating manual care­fully. Keep this manual safe for future reference.
DANGER! Failure to observe safety standards could result in fatal accidents or serious injury, and damage equipment or the environment.
CAUTION! If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact SOCOMEC. Do not operate the unit if it has suffered a violent mechanical shock of any kind.
NOTE! Install the unit in accordance with clearances in order to prevent access to handling devices and guarantee sufficient ventilation (see Environmental requirements chapter).
NOTE! Only use accessories recommended or sold by the manufacturer.
6 EN
NOTE! When the equipment is transferred from a cold to a warm place wait approx. two hours before operating the unit.
DANGER! Live device! RISK OF ELECTRIC SHOCK!
2
SUNSYS PCS
IM is connected to two separately protected power supplies:
1) DC cable - BES power supply
2) AC cable - Power from the mains network, supplied by the electricity company
NOTE! Before cleaning, performing maintenance work or connecting appliances to the unit, switch the unit off and disconnect all power sources.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 7
DANGER! Live device! RISK OF ELECTRIC SHOCK!
2
Carry out the following steps before SUNSYS PCS
IM maintenance:
- Disconnect the battery system’s main DC switch.
- Disconnect the AC power supplies.
- Disconnect the DC disconnection switches.
- Make sure the cable is fixed in position securely.
- Make sure the system cannot be restarted.
- Make sure the electricity supply (AC and DC voltages) has been disconnected.
- Cover or separate nearby live device units.
DANGER! RISK OF ELECTRIC SHOCK! After disconnecting all power sources wait approx. 5 minutes for the complete discharge of the unit.
CAUTION! RISK OF BURNS! During operation the casing can reach high temperatures. Do not touch the surfaces!
NOTE! Use AWG, 90 °C copper wire.
NOTE! The tightening torque for DC and AC terminals must be 180 lb-in (20.3 Nm).
NOTE! Any use other than the specified purpose will be considered improper. The manufacturer/supplier shall not be held responsible for damage resulting from this. Risk and responsibility lies with the system manager.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
7EN
Page 8
1.1 DESCRIPTION OF SYMBOLS
Comply with all internal and external precautions and warnings on labels and plates on the equipment.
Symbols Description
UL 1741; CSA-C22.2 NO.107.1-01; MET file E113907
General warning – Important safety information
The circuit-breaker is ON
The circuit-breaker is OFF
Waiting time before operating
5 min
Protective earth terminal (PE).
Authorised personnel only.
No smoking.
Risk of electric shock!
Risk of explosion! Avoid short circuits!
Read the user instructions carefully. Read the user manual before performing any operations.
Wear protective gloves
Wear safety shoes.
Wear protective goggles.
In the event of contact with the eyes, wash immediately with plenty of water and call a doctor. Call a doctor immediately in the event of accidents or illness.
8 EN
Do not dispose of in normal waste stream (symbol waste electrical and electronic equipment).
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 9
1.2 ABBREVIATIONS
For the purpose of this document, the following abbreviations are used:
BES Battery Energy Storage BMS Battery Management System EMC Electro Magnetic Compatibility EMS Energy Management System ESS Energy Storage System HMI Human Machine Interface IEC International Electrotechnical Commission IM Islanding Mode IMD Insulation Monitoring Device PCS Power Conversion System PE Protective Earth PMS Power Management System PV Photovoltaic SBMS System BMS SOC State of Charge SOH State of Health SPD Surge Protection Device THDI Total Harmonic Distortion in Current THDV Total Harmonic Distortion in Voltage TL Transformer-less TR Transformer based
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
9EN
Page 10
2. FOREWORD
Energy storage is the key solution to meeting the challenges of energy transition, using renewable energy and provid­ing energy cost reductions for the following 4 main applications.
Behind-the-Meter Energy Storage: Reduce peak consumption and maximise PV energy self-consumption. SUNSYS PCS² (IM) can limit the impact
of increases in the electricity retail price by supplying the load to cut peak demand (peak shaving), maximising PV energy self-consumption at building or community level. Any PV energy surplus is stored in the SUNSYS PCS² (IM) battery system. This stored energy is used later to supply the load.
1
PV plants: Manage the intermittence of renewable energy production. SUNSYS PCS
2
(IM) ensures the production profile of an intermittent renewable energy plant by limiting production to a predefined value, injecting energy to compensate for solar variations, setting constant ramp-up or ramp-down.
2
10 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 11
Grid support:
2
Meet the challenge of demand-response energy balance. When directly connected to the grid, SUNSYS PCS
(IM) improves stability and management of grid operators thanks to voltage and frequency regulation, load shifting, peak shaving and ancillary services for grid support.
3
Microgrids: Ensure energy availability and quality. The SUNSYS PCS² IM enables the microgrid to disconnect from the main grid
and be electrically autonomous thanks to local generation (PV, Wind, Diesel generators, etc.).
4
To sum up:
Products / Applications On-Grid On-Grid + Off-Grid Pure Off-Grid
SUNSYS PCS² • SUNSYS PCS² IM
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
11EN
Page 12
3. SUNSYS PCS² RANGES
3.1 IEC VERSIONS
SUNSYS PCS² SUNSYS PCS² IM
33 kVA 66 kVA 100 kVA 132 kVA 200 kVA 33 kVA 66 kVA 100 kVA 132 kVA 200 kVA
Internal transformer
(TR version)
External transformer
(TL version)
3.2 UL VERSIONS
33 kVA 66 kVA 100 kVA 132 kVA 200 kVA 33 kVA 66 kVA 100 kVA 132 kVA 200 kVA
Internal transformer
(TR version)
External transformer
(TL version)
SUNSYS PCS² SUNSYS PCS² IM
12 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 13
4. ENVIRONMENTAL REQUIREMENTS AND HANDLING
4.1 ENVIRONMENTAL REQUIREMENTS
Install the unit in an equipment room. The room must be:
• of a suitable size;
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight. The floor must support the weight of the unit and guarantee its stability. The unit is designed for indoor rooms only. For information regarding ambient temperature, dimensions and weights refer to 'Technical specifications' chapter. To position the unit correctly see the diagrams below.
ROOM POSITIONING
Top view
30 cm1.5 m
SUNSYS
PCS
SUNSYS
2
PCS
Free area
SUNSYS
2
PCS
2
SPACING-AIR FREE
To ensure the full unit power up to 40°C ambient temperature, observe the following minimum distances:
- rear space: 30 cm.
- above space: 45 cm.
This distance can be reduced depending on:
• the maximum ambient temperature accepted (Full load conditions).
Distance from the rear wall Space above the top panel Ambient temperature
30 cm
20 cm
10 cm
45 cm 40 °C 25 cm 35 °C 45 cm 35 °C 25 cm 30 °C 45 cm 25 cm
25 °C
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
13EN
Page 14
• the maximum power required from the load (at 40 °C ambient temperature).
Distance from the rear wall Space above the top panel Power
30 cm
20 cm
10 cm
45 cm 100% 25 cm 90% 45 cm 90% 25 cm 80% 45 cm 75% 25 cm 75%
SPACING-AIR FLOW
Typical air extraction structure
10 cm
air extractor
external environment
internal environment
Minimum air extractor flow
Models Minimum extraction fl ow
hood
SUNSYS
PCS
(1)
air
2
33 TR 600 m3/h
66 TR 1200 m 100 TR 1800 m 132 TL 1780 m 200 TL 2700 m
1. SUNSYS PCS2 at a distance of 10 cm from the rear wall (40 °C ambient temperature and full load).
3
3
3
3
/h /h /h /h
14 EN
NOTE: the hood must prevent air losses and enable the removal of the SUNSYS PCS2’s top panel for maintenance.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 15
CABINET LAYOUT
SUNSYS PCS2 IM
33 - 66 TR
SUNSYS PCS2 IM
100 TR
SUNSYS PCS2 IM
132 - 200 TL
4.2 HANDLING
• The packaging guarantees the stability of the unit during shipping and physical transfer.
• The unit must remain in a vertical position during all shipping and handling operations.
• Ensure that the floor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
WARNING! HEAVY WEIGHT! Move the unit using a fork lift truck taking the utmost caution at all times.
The unit MUST be handled by at least two people. The people MUST take position at the sides of the PCS with respect to the direction of movement.
Do not move the unit by putting pressure on the front door.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure that the unit does not fall over.
WARNING! The following instructions must be carried out prior to moving the unit (after initial positioning). Failure to heed this warning could result in the unit falling over, equipment damage, injury and even death.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
15EN
Page 16
4.3 FLOOR ASSEMBLY
• PCS2 IM range 33 - 66 - 100 TR:
• PCS
Remove the protective cover
2
IM 132 - 200 TL:
Level adjustment and floor fixing
Rear
SUNSYS PCS
30 cm
2
Fixing bolt
Level regulation bolt
720 mm
618 mm
16 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 17
4.4 INSTALLATION
POWER MODULE INSERTION
WARNING: before installing the module ensure that there is no voltage.
NOTE: the module must be handled by at least two people (34.5 kg / 76 lb).
WARNING! RISK OF TIPPING OVER: before carrying out any operations, ensure the SUNSYS
2
IM is secured at the feet.
PCS
WARNING! RISK OF TIPPING OVER: the modules must be inserted from the bottom upwards and removed from the top downwards to ensure the unit remains stable.
WARNING: the modules have to be moved individually. Never handle more than one module.
4.4.1 PROCEDURE FOR PCS2 IM 33 - 66 - 100 TR
• Open the door with the appropriate key.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
17EN
Page 18
• Position the cables in the hose clamp to enable correct module insertion.
• Remove the Lexan protection on the connectors.
18 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 19
• Place the module on the guides and insert it up to the limit starting by the lower one.
In order to ensure the safety of installers, installers shall be at least two people to process the installation (34.5 kg / 76 lb).
34.5
kg
76
lb
• Insert the connectors and secure them.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
19EN
Page 20
• Position the Lexan protection and secure it.
• Insert the module completely.
• Tighten the screws to secure the module to the SUNSYS PCS
2
IM.
20 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 21
• Connect the communication cable.
Communication cable
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
21EN
Page 22
4.4.2 PROCEDURE FOR PCS2 IM 132 - 200 TL
• Open the doors:
- With the appropriate key A open the lock, then pull the hook B and open the right door.
- Unhook the upper latch C and lower latch D and open the left door.
C
135°
135°
Left
door
A
Right
door
B
D
22 EN
NOTE: in PCS2 132 TL, module A and D are not present.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 23
• Position the cables in the hose clamp to enable correct module insertion.
• Remove the Lexan protection on the connectors.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
23EN
Page 24
• Insertion of the lower three modules. Place the module on the guides and insert it up to the limit starting by the lower one.
24 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 25
• Insertion of the upper three modules starting by the lower one. The Socomec shelf can be used to facilitate the insertion of the upper three modules. The shelf can be used only by persons authorized by Socomec. Keep this shelf available to service people for commissioning or future maintenance activities.
- Disconnect the CAN-BUS cables.
1
- Assemble the shelf on the PCS2 IM frame inserting its joints into the PCS2 IM frame holes.
1
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
25EN
Page 26
- Make sure the shelf is properly assembled.
1
• Place the module on the shelf.
34.5
kg
76
lb
26 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 27
• Place the module on the guides and insert it up to the limit.
• Insert the connectors and secure them.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
27EN
Page 28
• Position the Lexan protection and secure it.
• Insert the module completely.
• Remove the shelf.
28 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 29
• Tighten the screws to secure the module to the SUNSYS PCS2 IM.
In PCS2 132 TL, the unused slots are covered with a panel, do not remove this protection.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
29EN
Page 30
• Connect the communication cable.
Communication
cable
30 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 31
• Close the doors:
- Close the left door and hook it with the both upper latch C and lower latch D.
- Close the right leaf and close the hook B until the first clack. The door is locked but the lock is not activated.
- To lock the door, press the coupling B fully.
C
B
Left
door
st
1
clack!
Closure activated
Right
door
B
nd
2
clack!
Lock activated
D
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
31EN
Page 32
5. ELECTRICAL INSTALLATION
NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
5.1 ELECTRICAL REQUIREMENTS
The installation and system must comply with national plant regulations. The electrical distribution panel must have a sectioning and protection system installed for AC mains. The tables below show the connection features and the size of the protection devices recommended for correct
installation.
Size of AC input protection
Models
Required overcurrent
protection
33 TR 50 A type D
66 TR 100 A type D
100 TR 160 A type D
132 TL 315 A type C 200 TL 500A type C
1. It is advisable to carry out a preliminary check on the earth current leakage with the PCS installed and operational with the definitive configuration (batteries, etc.), so as to prevent the RCD tripping.
The auxiliary power supply socket must be protected with a 10 A magneto-thermal switch, curve C, and from cate­gory II overvoltages or greater.
DC input protection can be achieved either with a distributed or centralised fuse configuration (see example below).
Recommended Insu-
lation fault device
Differential switch
1
(RCD)
0.3 A
Type AC or A
Insulation Monitoring
Device (IMD)
AC cable Max
cross-section
300 kcmil
3 x 4/0 AWG
Type of cable
90 °C
copper wire
Tightening
torque
20 Nm
Size of DC input protection
Models
DC cable Max cross-section
1
Type of cable
33 TR
66 TR 160 A - 1000 V Ultrafast
100 TR 250 A - 1000 V Ultrafast
2 x 4/0 AWG
90 °C
Copper wire
Tightening
torque
20 Nm
Distributed fuses Centralised fuses
80 A - 1000 V Ultrafast
80 A – 1000 V
Ultrafast
132 TL 2 x 160 A - 1000 V Ultrafast 200 TL 2 x 250 A - 1000 V Ultrafast
1. Determined by the size of the terminals.
2. Standard configuration delivered with the product.
2
32 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 33
Distributed Fuses (example 100 kW) Centralised Fuses (example 100 kW)
+
-
Distributed Fuses 132 - 200 kW - Centralised fuses is not allowed
+
-
NOTE: If Socomec also provides the batteries the centralised fuse connection will be used and the fuses will be provided.
WARNING: the SUNSYS PCS2 IM is designed for transient over-voltages in category II installa-
2
tions for DC terminals. If the SUNSYS PCS
IM can be subjected to transient over-voltages in
category III installations, or if the distance from the SPDs of the battery cabinet is excessive,
2
protective SPDs must be fitted near the SUNSYS PCS
2
the SUNSYS PCS
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
IM directly.
IM. The SPD DC option can be fitted to
33EN
Page 34
6. OVERVIEW
6.1 SWITCHES AND INTERFACES
SUNSYS PCS2 IM 33 TR
Communication slots
Detail 1
Module A
Module A output disconnection switch
IEC320 AUX output for assistance
IEC320 AUX power input
SUNSYS PCS
2
output disconnection switch
Module A input disconnection switch
Detail 2
SPD AC
Q3
(1)
Q70
Q1
Detail 1 Detail 2: disconnection switches with fuse
12
RS232/485 RS232
1. Disconnection switch for IEC320 connector AUX power supply.
2. Disconnection switch for IEC320 connector for assistance.
1. Refer to 'Standard features and options' chapter for details.
34 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 35
WIRING DIAGRAM FOR SUNSYS PCS2 IM 33 TR
Batteries
DC +/–
X10A
AC
terminals
DC
terminals
Q1A
Q3A
T1
K1
Q70
X90
Option
SPD-IN
SPD-OUT
3Ph+PE
AC main network
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
35EN
Page 36
SUNSYS PCS2 IM 66 TR
Communication slots
Module A
Detail 1
Module A output disconnection switch
Module B output disconnection switch
IEC320 AUX output for assistance
IEC320 AUX power input
SUNSYS PCS
2
output disconnection switch
Module B input disconnection switch
Module A input disconnection switch
Detail 2
SPD AC
Q3
Q3
Q70
Q1
Q1
Module B
(1)
Detail 1 Detail 2: disconnection switches with fuse
RS232/485 RS232
1. Disconnection switch for IEC320 connector AUX power supply.
2. Disconnection switch for IEC320 connector for assistance.
3. Fan fuse.
1. Refer to 'Standard features and options' chapter for details.
36 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 37
WIRING DIAGRAM FOR SUNSYS PCS2 IM 66 TR
DC +/–
BatteriesBatteries
DC +/–
AC
terminals
DC
terminals
X10A X10B
Q1A
Q1B
Option
Q3A
SPD-IN
T1
K1
Q70
X90
3Ph+PE
Q3B
SPD-OUT
AC main network
Common
DC
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
37EN
Page 38
SUNSYS PCS2 IM 100 TR
Q70 SUNSYS PCS² AC disconnect switch
SPD AC
Detail 2
Q3 Module C AC disconnect switch
Q3 Module B AC disconnect switch
Q3 Module A AC disconnect switch
(1)
RS232/485 (see 'Standard features and options' chapter for details)
Communication slots
123 4 5 6 7
12
Module A
Module B
Module C
PCS AUX power supply socket
BES AUX power supply socket
Detail 1
Input AUX power supply plug
Output AUX power supply socket for assistance
Q1 Module A DC disconnect switch
Q1 Module B DC disconnect switch
Q1 Module C DC disconnect switch
Detail 1: disconnect switches with fuse Detail 2: disconnection switches with fuse
12
1. Disconnect switch for input AUX power supply plug.
2. Disconnect switch for output AUX power supply socket for assistance.
1. Refer to 'Standard features and options' chapter for details.
1. Disconnect switch for AUX power supply.
2. Disconnect switch for AUX power supply.
3. Disconnect switch for PCS AUX power supply socket.
4. Disconnect switch for PCS AUX power supply socket.
5. Disconnect switch for BES AUX power supply socket.
6. Disconnect switch for BES AUX power supply socket.
7. Transformer cabinet fans fuse.
123 4 5 6 7
38 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 39
WIRING DIAGRAM FOR SUNSYS PCS2 IM 100 TR
AC
terminals
Output PCS
AC
terminals
Batteries Batteries Batteries
2
DC
terminals
Common
DC
SBMS
Auxiliary mains
PCS
2
Option
SPD-IN
SPD-OUT
Cabinet transformer
AC mains networkAuxiliary mains
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
39EN
Page 40
SUNSYS PCS2 IM 132 - 200 TL
(1)
Communication slots
RS232/485
USB
Ethernet Network
RS232/Modem
Module A output disconnection switch
RS232/485
USB
Ethernet Network
RS232/Modem
Module B output disconnection switch
Module C output disconnection switch
Module D output disconnection switch
Module E output disconnection switch
Module F output disconnection switch
Module A
Q1A Module A input disconnec­tion switch
Upper
control
pnale
Q3
Lower
control
pnale
Q3
Q3
Q3
Q3
Q3
Module B
Module C
Module D
Module E
Q1B Module B input disconnec­tion switch
Q1C Module C input disconnec­tion switch
Q1D Module D input disconnec­tion switch
Q1E Module E input disconnec­tion switch
Detail 1
IEC320 AUX power input
IEC320 AUX output for assistance
Detail 1: disconnection switches with fuse
1. Disconnection switch for IEC320 connector AUX power supply (Upper Control Panel)
2. Disconnection switch for IEC320 connector AUX power supply (Lower Control Panel)
3. Disconnection switch for IEC320 connector for assistance
Module F
Q1F Module F input disconnec­tion switch
1. In PCS2 132 TL, module A & D are not present.
40 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 41
WIRING DIAGRAM OF SUNSYS PCS2 IM 132 - 200 TL
terminals
Option
SPD-IN
AC
DC
terminals
Batteries Batteries
Option
SPD-IN
(1) (1)
1. Module A not present in PCS 132 TL
2. Module D not present in PCS 132 TL
SPD-OUT
AC main network
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
41EN
Page 42
6.2 DIAGRAM OF MAIN SYSTEM EXAMPLE FOR VERSION 100 TR
The SUNSYS PCS² system is constructed using power electronics modules. Each power module incorporates circuit protection, sine filter, cooling fans and EMI filtering as shown in the diagram below.
2
• Example for PCS
100kW with transformer
1. AC voltage is set according to the country electric code.
42 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 43
7. CONNECTIONS
NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
7.1 INPUT CONNECTION
The SUNSYS PCS2 IM is connected to the batteries via the DC terminals. The SUNSYS PCS
• Remove the panels protecting the connection area in front of the terminals.
• Remove the horizontal support in order to facilitate the cable connections.
2
IM is connected to the AC mains via the AC power terminals.
SUNSYS PCS2 IM range 33 - 66 - 100 TR
SUNSYS PCS2 IM range 132 - 200 TL
• Fix the protection wire to the connection terminal.
• Fix the wires L1, L2, L3, N to the connection terminals.
• Fix the wires L+,L- to the connection terminals.
• Secure the power cables supplied between the transformer cabinet and the PCS
2
IM (only for 100 TR).
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
43EN
Page 44
• Secure the signal cables supplied between the transformer cabinet and the PCS2 IM (only for 100 TR).
• Secure the auxiliary mains cable supplied between the transformer cabinet and the PCS (only for 100TR).
• Secure the auxiliary mains cable supplied between the transformer cabinet and the BES (only for 100TR).
• Use only cables supplied by SOCOMEC for bridging connections between transformer cabinet and PCS for 100 TR).
• If desired fix the cables to the cable support guide using cable strapping.
SUNSYS PCS2 IM 33 TR SUNSYS PCS2 IM 66 TR
2
IM (only
L1 L3
PE
L2
Key
L1, L2, L3
PE
L+, L- DC connection terminals for the batteries
Connection terminals for the main AC network
Connection terminal for the protective earth wire
L–
L+
L1 L3
L2
3N
PE
L– L+
44 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 45
SUNSYS PCS2 IM 100 TR
Cable for PCS auxiliary mains
L1 L3
L2
N
Key
L1, L2, L3, N
L+, L- DC connection terminals for the batteries
Connection terminals for the main AC network
Connection terminal for the protective earth wire
PE
L1 L3
L2
Cables supplied
Signal cables
L–L+
3PH+N
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
45EN
Page 46
SUNSYS PCS2 IM 132 - 200 TL
L1
L3
L2
Key L1, L2, L3 Connection terminals for the AC mains - 3 phase
Connection terminal for the protective earth wire
L+, L- DC connection terminals for the batteries
L–
L+
L–
PE
L+
• Replace the horizontal support.
• Replace the panels protecting the connection area in front of the terminals.
For safety reason, the mounting of the protecting panels is compulsory.
46 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 47
• Fix the front base.
For safety reason, the mounting of the protecting panels is compulsory.
SUNSYS PCS2 IM range 33 - 66 - 100 TR
1
2
3
SUNSYS PCS2 IM 132 - 200 TL
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
47EN
Page 48
• Fix both the lateral bases
SUNSYS PCS2 IM 132 - 200 TL
AUXILIARY CONNECTION
2
The SUNSYS PCS
IM equipment is powered by a special single-phase voltage (refer to 'Technical specifications'
chapter). The auxiliary voltage must be connected to the relevant socket.
WARNING: risk of damage to the system if not observed!
SUNSYS PCS2 IM 33 - 66 TR SUNSYS PCS2 IM 100TR
Cable for PCS
auxiliary mains
Cable for
BES auxiliary
mains
Power supply
Interface protection
jumper
Interface protection
jumper
48 EN
NOTE! The auxiliary voltage is generated in the transformer cabinet and supplied to the PCS and BES through the cables supplied by SOCOMEC, as shown in figure.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 49
OPTIONAL INPUT FOR EXTERNAL INTERFACE PROTECTION
If local electricity supply company connection rules specify that external interface protection must be used, the external protection output signal (dry contact) can be used to control the internal contactor for the Sunsys PCS removing the jumper in figure.
NOTE: the auxiliary power supply cable must be fitted with a 10 A max. protection device.
SUNSYS PCS2 IM 132 - 200 TL
Auxiliary output voltage
(for service only)
Auxiliary input voltage
2
IM,
NOTE: the auxiliary power supply cable must be fitted with a 10 A max. protection device.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
49EN
Page 50
7.2 INSTRUCTIONS FOR SUNSYS PCS2 IM 200 TL
The SUNSYS PCS2 IM TL versions require the installation of a transformer coupling to the mains, in addition to the AC input protection.
Block diagram
X90
AC input
protection
Grid transformer
280/xxx V
LV grid: d/YN
MV grid: y/D
Transformer
protection
Grid protection
AC INPUT PROTECTION
Refer to 'Electrical installation' chapter.
GRID TRANSFORMER
2
The transformer is necessary to connect the PCS
IM to mains.
The main technical characteristics are outlined in the following specification.
Ratings
Parameter 132 TL 200 TL
Rated power 140 kW 210 kW Rated frequency 60 Hz Number of phases 3
Winding connection unit
LV=> YNd
MV=> Dy Primary voltage - grid side Same of grid voltage (LV => Y + N | MV => D) Secondary voltage - PCS side 280V (LV => d | MV => y) Grid voltage range +10% / -10% Primary rated current - grid side Depends on grid voltage Secondary rated current - PCS side 285.8 A 433 A
Shielded
Between primary and secondary winding, connected to ground.
Yes
Overvoltage category Depends on grid overvoltage category
Mains
TRANSFORMER PROTECTION
The transformer protections must be chosen by the installer or plant designer.
50 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 51
8. CONTROL PANEL
The control panel displays information regarding operating status, electrical measurements, access to control func­tions and configuration parameters. It includes a colour graphic display and a luminous status bar.
Display
UP button
Scrolls up through
the available menus/
values.
ESC button
Exits current page,
aborts operations.
DOWN button
Scrolls down through the available menus/ values.
ENTER button
Accesses the currently displayed menu, accepts/sends confi gurations and commands.
LUMINOUS STATUS BAR
Changes colour according to SUNSYS PCS
2
status.
- Red: SUNSYS PCS2 off due to alert.
- Flashing yellow: at least one warning is present and SUNSYS PCS switched on.
- Yellow: at least one warning is present and SUNSYS PCS
2
is switched off or
first maintenance period has elapsed.
2
- Flashing green: SUNSYS PCS
- Green: SUNSYS PCS
2
switched on.
in startup procedure phase.
2
is
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
51EN
Page 52
8.1 EXCEPTION FOR PCS2 IM 132 - 200 TL
The PCS2 IM 132 - 200 TL has two control panels:
- the upper one controls the upper three power modules (Module A, Module B, Module C).
- the lower one controls the lower three power modules (Module D, Module E, Module F).
So, the first start-up procedure must be applied to both control panels ('First start-up' chapter) and both have to be used to monitor measurements, alarms, etc. ('Menu' chapter).
NOTE: in PCS2 132 TL, module A and D are not present.
Module A
Module B
Module C
Module D
Module E
52 EN
Module F
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 53
8.2 CONVERTER STATE MACHINE
The SUNSYS PCS² IM implements the following state-machine concept:
INIT
SWITCHED-OFF ALARM
ON / OFF
SYSTEM READY
BLACK START
OFF-GRID MODE ON-GRID MODE
CHARGE / DISCHARGE
COMMAND
At system power-on by the auxiliary power supply, the SUNSYS PCS² IM automatically enters the SWITCHED-OFF status: the Control Panel shows the message SWITCHED-OFF on the Status line on the display and the luminous status bar is switched-off.
An ON command connects the DC source to the SUNSYS PCS² IM and it enters the SYSTEM READY status, after checking the battery conditions are satisfactory. On the control panel, the battery icon is green (or yellow if a Battery
(1)
Warning is present
) and the number of powered-on power modules appears.
The system can then operate in two modes, following two different paths:
• OFF-GRID MODE, operating in islanding conditions, as a grid-former;
• ON-GRID MODE, grid-tied and operating as a grid-follower. From the SYSTEM READY status, a BLACK START procedure can be performed, in order to energise an isolated
micro-grid by the battery system. After the black start procedure has completed, the SUNSYS PCS² IM enters OFF-GRID MODE status, generating the proper voltage and frequency references for the micro-grid.
From the SYSTEM READY status, with a Charge/Discharge command, the SUNSYS PCS² IM synchronizes and connects to the AC grid and enters ON-GRID MODE status. The SUNSYS PCS² IM follows P/Q references coming from an external control device.
The direction of the power flow on the display shows the instantaneous charging/discharging operation. The message INVERTER ON is displayed on the Status line on the display and the luminous status bar is switched-on
(1)
with a green or flashing yellow light (if at least one warning is present
). Transitions from OFF-GRID MODE to ON-GRID MODE and vice versa are supported by the SUNSYS PCS² IM: additional external devices and components shall be provided (e.g. synchronisation device, circuit breaker, measure-
ment system). Contact SOCOMEC for further information. In the event of an alarm, the system enters ALARM status and switches-off to ensure conditions are safe. The lumi-
nous status bar is switched-on with a red light and an alarm message appears on the display panel.
1. A Warning does not cause the ESS to stop.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
53EN
Page 54
9. FIRST START-UP
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
When the SUNSYS PCS2 IM is switched on for the first time the commissioning wizard is activated. The commissioning wizard is an interactive procedure that guides the user through the SUNSYS PCS
up procedure. The most important steps are described below.
LANGUAGE SETTING
2
IM ’s first start-
ACTIVATION CODE
The Activation code - four-digit code - must be entered to operate the SUNSYS PCS
2
IM in both control panels.
WARNING: If the code is not entered the ‘initial startup’ procedure cannot be completed and the equipment will not operate.
To get the activation code call the Service Centre and give the Serial Number, displayed on the control panel.
To insert the Activation Code:
- press INSERT (a screen keyboard appears);
- insert the Activation Code;
- press
;
- press ENTER.
54 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 55
DATE & TIME
SYSTEM SETUP
Set the number of modules installed (1, 2 or 3).
TRANSFORMER TYPE
Set the type of transformer connected to SUNSYS PCS
2
IM.
- SOCOMEC: if standard transformer is used.
- External: if a custom transformer is provided by the customer.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
55EN
Page 56
BATTERY TYPE
2
Set the type of battery connected to the SUNSYS PCS
IM (Generic, Lithium, Lead-acid, etc.).
Depending on the type of battery, after commissioning, some specific items will be shown in the Battery Setting Menu
2
to guarantee the correct SUNSYS PCS
IM set up.
COUNTRY/GRID CODE SETTING
Set the proper country/grid code according to local regulation. Grid code compatibility is always being upgraded, please contact SOCOMEC for grid code compatibility (subject to
change without notice).
NOTE: Once the country/grid code has been set the SUNSYS PCS2 IM will be automatically configured in compliance with the local standards.
OPTIMISATION MODE SETTING
Not present if Generic Battery is selected. Set the battery mode of use. It is possible to choose between:
- PERFORMANCE: maximises battery performance (full SOC operating range);
- LIFE: maximises battery life (reduced SOC operating range).
CONTROL MODE SETTING
Set the SUNSYS PCS
2
IM control mode. It is possible to choose between:
- local (using the control panel);
- external EMS (Energy Manager System);
56 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 57
10. MENU
10.1 DISPLAY OVERVIEW
Status bar
Energy direction
(1)
ESS
Status
SUNSYS PCS Power (kW)
2
IM Rated
Battery Status
Charge status as a %
SUNSYS PCS2 IM module
Help message area Always present, displays a help message to guide the user
through the display functions.
1. Energy Storage System (includes SUNSYS PCS
Alarms area
2
IM and Battery System).
Alarms area Present when an alarm is active. Enter ALARMS menu to display the complete alarms list.
Grid status
Instantaneous Power (kW)
System view
Status icons
Time: SUNSYS PCS
Commissioning Code not inserted or Scheduled Inspection warning: machine inspection required. Call SOCOMEC support service Key icon: Displayed if the keypad has been locked.
USB icon: Displayed if a USB memory stick is inserted. It must be formatted with a FAT32 fi le system.
Modem icon: reserved for technical service.
Network icon: Displayed if a valid link has been established on the ethernet. Flashes when a remote host is communicating with the SUNSYS
2
IM.
PCS
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
2
IM current time.
57EN
Page 58
SUNSYS PCS2 IM Status
Battery status
(grey icon) Battery not present
2
(green icon) SUNSYS PCS
(yellow icon) SUNSYS PCS
(red icon) SUNSYS PCS
IM normal operation
2
IM warning fl agged
2
IM alarm fl agged
SOC 87.5 %
62.5 % SOC 87.5 %
37.5% SOC 62.5 %
12.5 % SOC 37.5 %
Instant power level
10%
60%
SOC 12.5 %
20%
70%
30%
80%
40%
90%
50%
> 90%
58 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 59
Grid status
Local command
On-Grid mode
Off-Grid mode
Black-Start in progress
Local Command charge/discharge sequence
NOTE: the procedures available depend on the type of battery setting.
NOTE: the ‘Stop sequence‘ command must be selected to change the procedure.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
59EN
Page 60
10.2 MENU TREE
FIRST LEVEL SECOND LEVEL THIRD LEVEL
COUNTERS
DAILY TREND
STATISTICS
MEASUREMENTS
ALARMS AND WARNINGS
HISTORY LOG
COMMANDS
SETTINGS
PRODUCTION GRAPHS
PCS POWER
AC MEASURES
BATTERY MEASUREMENTS
SENSORS
ALARMS
WARNINGS
LOCAL PROCEDURE
ALARM RESET Alarm reset
TEST PROCEDURES
RESET STATISTICS Reset all production data
RESTART DISPLAY Restart display SISTEM CONFIG Start config procedure
PREFERENCES
SYSTEM CONFIGURATION
PCS SETTINGS
BATTERY SETTINGS
(1)
OPTIONAL DEVICES
CONNECTIVITY
DOD DISTRIBUTION
DISCHARGE DURATION
BATTERY TEMPERATURE
Start charge/discharge
PCS calibration
Stop procedure
Led bar test
AC contactors test
Start fan test
LANGUAGE
DATE AND TIME BUZZER DISPLAY PASSWORDS
Local/remote control
N° of modules
Transformer type
AC Interface Protection [Internal/External]
Energy saver mode
NOMINAL VOLTAGE/FREQUENCY
COUNTRY/NETWORK CODE
CONNECTION PARAMETERS
EQUIPMENT PROTECTION THRESHOLDS
Additional items depending on the Country/ Network Code selection
BATTERY TYPE
BATTERY PARAMETERS
BATTERY PARAMETERS MODE
CHARGE THRESHOLDS
DISCHARGE THRESHOLDS
MAINTENANCE PARAMETERS
SOH CALCULATION
OPTIMIZATION MODE
ADVANCED CONFIGURATION
OPTIONAL DEVICES 1 OPTIONAL DEVICES 2
PERIPHERALS
SERVICES
(5)
(5)
(5)
(2)(3)
(3)
(2)
(2)
(4)
60 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 61
FIRST LEVEL SECOND LEVEL THIRD LEVEL
PCS DESCRIPTION
SYSTEM
FIRMWARE VERSION
SERVICE
SERIAL NUMBER
COMMISSIONING CODE
UPGRADE FIRMWARE
MODULE1
MODULE2
MODULE3
UPGRADE HMI FIRMWARE
UPGRADE LANGUAGES
1. Password protected.
2. Shown only if Lead-Acid battery type is set.
3. Shown only if generic battery type is set.
4. Shown only if Lithium Samsung or Lithium Saft is set.
5. Access is allowed if Local mode is enabled: SETTING > SYSTEM CONFIGURATION > Local/remote control
KEYPAD LOCKING
The keypad can be locked by pressing the buttons in the following sequence: ESC > UP > DOWN > ENTER To unlock the keypad the buttons must be pressed in the reverse sequence: ENTER > DOWN > UP > ESC These sequences only work on the Mimic Panel page.
ENTERING PASSWORDS
Some operations and settings require a password in order to be performed. If this is the case, a padlock is displayed. When a password is required, a virtual keyboard is displayed. After inserting
a valid password, the padlock opens and the operation can be performed. The default password is SUNS.
WARNING: the password protects important settings and parameters which are essential for
2
correct SUNSYS PCS
IM operation. Only skilled and qualified technicians are allowed to access the protected parameters. Incorrect settings may damage the equipment.
NOTICE: It is advisable to change the password to prevent unauthorised access.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
61EN
Page 62
10.3 MENU DESCRIPTION
DISPLAY MENU
It is possible to view information corresponding to individual modules on the mimic panel by selecting the SUNSYS
2
IM serial number.
PCS
LANGUAGE UPGRADE
2
The SUNSYS PCS Further language packages can be provided by SOCOMEC, in case new markets are approached. Text translations are held in files with the *.lng extension which are provided by SOCOMEC. Language upgrades must
be performed through the USB port, using a standard USB memory stick. The USB device must be formatted with FAT16 or FAT32.
Step 1
The language file to be installed must be copied onto a USB stick and placed in the standard folder: {USB stick}\socomec\wghi
Step 2
Insert the USB stick into the USB port on the back of the SUNSYS PCS
Step 3
Enter the menu: SERVICE > UPGRADE FIRMWARE > UPGRADE LANGUAGES. The SUNSYS PCS selected beforehand on the main page.
Step 4
The list of files in the \socomec\wghi folder in the USB memory stick is shown. Select the file you want to install and follow the instructions displayed.
Step 5
At the end of the process select Yes to restart the display.
Step 6
Remove the USB stick when requested.
Step 7
The new language is available after restarting. To change the language go to the SYSTEM menu: SETTINGS > PREFERENCES > LANGUAGE.
To restore English as the default language press the ESC button for at least 4 seconds on the main page (mimic panel page).
IM is delivered with the following built-in languages: English, French, Italian, German, Spanish.
2
IM door.
2
IM has to be
62 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 63
STATISTICS MENU
This menu displays the COUNTERS and the PRODUCTION GRAPH:
• Counters store the Running Time [Hrs] and the Tot. Num. Of Cycles.
• Production graph illustrates the:
- Daily Trend, (last 7 days of SOC and Active Power).
- Depth of Discharge Distribution, (numbers of cycles with a specific DOD).
- Discharge Duration, (number of cycles with a specific discharge period).
- Battery Temperature (number of working hours at specific temperature).
COMMANDS
The menu contains a list of commands that the user can activate through the display:
• Local Procedure:
- Charge/discharge battery.
- Stop procedure.
2
- Calibration procedure of SUNSYS PCS
IM.
- Commissioning procedure (only for Lead Acid Battery).
- Equalisation procedure (only for Lead Acid Battery).
- SOH estimation (only for Lead Acid Battery).
SETTINGS
This menu contains the System Configuration Parameters, all of them are password protected and it contains param­eters for the PCS and battery configuration.
Please contact SOCOMEC for the correct configuration of the PCS according to the specific plant requirements. Please contact SOCOMEC for the correct configuration of the Battery according to the specific battery installed.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
63EN
Page 64
10.4 DEFAULT SETTINGS
NOTE! Changes to the threshold parameters listed below can lead to changes regarding conformity with the standard and must be approved by the on site electric utility company and/or the appropriate authority.
The system is qualified as a "Grid Support Utility Interactive Inverter", covering grid support functions specified in UL1741 Supplement SA.
The interconnection system default response to abnormal voltages and to abnormal frequencies is set in compliance with prescriptions given by UL1741 Supplement SA. Default values and ranges of adjustability (in brackets {..}) are provided in Tab. 10.4.1 and Tab. 10.4.2.
Specific information about the grid support functions are described in Chapter 15 "UL1741SA: How to configure grid support functions".
10.4.1 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL VOLTAGES
UL1741 Supplement SA
Threshold Voltage (% of UNOM) Clearing time (s)
UV3 < 50 {5 - 100} 1.50 {0.01 – 300} UV2 < 70 {5 - 100} 11.00 {0.01 – 300}
UV1 < 88 {5 - 100} 21.00 {0.01 – 300} OV1 > 110 {100 – 120} 13.00 {0.01 – 300} OV2 120 {100 – 120} 0.16 {0.01 – 300}
10.4.2 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL FREQUENCIES
UL1741 Supplement SA
Threshold Frequency (Hz) Clearing time (s)
UF2 < 57 {53 - 60} 0.16 {0.01 – 300} UF1 < 58.5 {53 - 60} 300 {0.01 – 300} OF1 > 60.5 {60 - 65} 300 {0.01 – 300} OF2 > 62 {60 - 65} 0.16 {0.01 – 300}
The system default response to abnormal voltages and to abnormal frequencies can be set to be compliant with IEEE 1547-2003 (Tab. 10.4.3 and Tab. 10.4.4) or with IEEE 1547a-2014 (Tab. 10.4.5 and Tab. 10.4.6), as well. Default values and ranges of adjustability (in brackets {..}) are provided in the tables.
10.4.3 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL VOLTAGES
IEEE 1547-2003
Threshold Voltage (% of UNOM) Clearing time (s)
UV1 < 50 {50 - 100} 0.16 {0 - 0.16} UV2 < 88 {50 - 100} 2.00 {0 - 21.00} OV1 > 110 {100 - 120} 1.00 {0 - 13.00} OV2 120 {100 - 120} 0.16 {0 - 0.16}
10.4.4 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL FREQUENCIES
IEEE 1547-2003
Threshold Frequency (Hz) Clearing time (s)
UF1 < 57 {57 - 59.8} 0.16 {0 - 0.16} UF2 < 59.3 {57 - 59.8} 0.16 {0 - 300.00} OF1 > 60.5 {60 - 64} 0.16 {0 - 0.16}
64 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 65
10.4.5 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL VOLTAGES
IEEE 1547a-2014
Threshold Voltage (% of UNOM) Clearing time (s)
UV1 < 45 {45 - 100} 0.16 {0 - 0.16} UV2 < 60 {45 - 100} 1.00 {0 - 11.00} UV3 < 88 {45 - 100} 2.00 {0 - 21.00} OV1 > 110 {100 - 120} 1.00 {0 - 13.00} OV2 120 {100 - 120} 0.16 {0 - 0.16}
10.4.6 INTERCONNECTION SYSTEM RESPONSE TO ABNORMAL FREQUENCIES
IEEE 1547a-2014
Threshold Frequency (Hz) Clearing time (s)
UF1 < 57 {56 - 60} 0.16 {0 - 10.00} UF2 < 59.5 {56 - 60} 2.00 {0 - 300.00} OF1 > 60.5 {60 - 64} 2.00 {0 - 300.00} OF2 > 62 {60 - 64} 0.16 {0 - 10.00}
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
65EN
Page 66
11. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care­fully.
11.1 SWITCHING ON
66 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 67
11.2 SWITCHING OFF
Q70 isn't present on PCS 100kW, 132kW and 200kW. If the auxiliary power supply also needs to be cut off, disconnect the cable from the auxiliary power supply input
socket or break the fuse connection.
2
This procedure will switch off all the auxiliary SUNSYS PCS
IM equipment, including the system controller and the
control panel. The general AC power contactor for the machine will also be opened.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
67EN
Page 68
12. STANDARD FEATURES AND OPTIONS
Features Type Description Availability
AC surge protection devices (SPD AC)
DC surge protection devices (SPD DC)
Electrical
Electrical
Serial communication interface Communication Available as standard Modbus TCP interface Communication Available as standard ADC card Communication Available as standard Communication card Communication Available as option
1. Standard on 33-66-100 TR and 132, 200 TL.
12.1 SERIAL COMMUNICATION INTERFACE
RS232/485 is a serial communication channel which can be used to connect to an external EMS or to a BMS (Battery Management System), depending on the battery type.
NOTE: RS485 cable has to be shielded.
This feature provides protection against AC overvoltage This feature provides protection against DC overvoltage
Available as option
Available as option
1
SUNSYS PCS2 IM 33-66-100 TR
Only for
service
JBUS
RS232/485
34521
8976
RS232
RS232/485 C1 pin key
1 Not connected 2 RX for RS232 3 TX for RS232 4 Data + 5 GND 6 Data ­7 Reserved 8 Not connected 9 +12V
RS232 pin key
1 Reserved 2 RX for RS232 3 TX for RS232 4 Reserved 5 GND for RS232 6 Not connected 7 RTS 8 CTS 9 +12V
68 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 69
SUNSYS PCS2 IM 132 - 200 TL
RS232/485
JBUS
RS232
RS232/485
JBUS
RS232
34521
8976
RS232/485 C1 pin key
1 Not connected 2 RX for RS232 3 TX for RS232 4 Data + 5 GND 6 Data ­7 Reserved 8 Not connected 9 +12V
RS232 pin key
1 Reserved 2 RX for RS232 3 TX for RS232 4 Reserved 5 GND for RS232 6 Not connected 7 RTS 8 CTS 9 +12V
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
69EN
Page 70
12.2 MODBUS TCP INTERFACE
The SUNSYS PCS2 IM can be managed from remote stations using MODBUS TCP network protocol. See menu SETTINGS > CONNECTIVITY > PERIPHERALS > NETWORK PARAMETERS to Enable/Disable DHCP setting. Restart the HMI after modifying the parameters. IP Addresses can be changed only if DHCP is disabled.
SUNSYS PCS2 IM 33 TR - 66-100 TR
A
Control
panel
B
SUNSYS PCS2 IM 132 - 200 TL
A
A
B
B
A
A
B
B
Key
A USB connector
B LAN RJ45 connector for ethernet
Upper
control
panel
Lower
control
panel
70 EN
NOTE: Ethernet cable has to be shielded.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 71
12.3 ADC CARD
This card manages four normally closed or normally open outputs and three digital inputs in configurable mode.
• Electrical data.
- Permitted rated current and voltage of normally open or normally closed contacts: 2 A 250 Vac depending on the terminal used.
- Inputs are activated on loop closing.
• External ESD connection. A remote emergency shutdown system (ESD) can be installed by means of the ADC card. Connect a normally closed
zero-potential contact to terminals IN1+ and IN1- of the ADC card.
Intervention of the ESD input switches off the SUNSYS PCS2 IM output.
2
To restore the SUNSYS PCS
IM to operation:
• Close the ESD contact on ‘IN 1’ on the ADC board.
• Send the Alarms Reset command.
The configuration and the designation of function for the card’s IN/OUT depends on the kind of batteries connected
2
to the SUNSYS PCS
IM, whose configuration table is included in the battery cabinet manual.
The following table refers to Lead-Acid batteries only.
ADC CARD CONFIGURATION DIP1: OFF - DIP2: OFF
IN/OUT Description Filter level
OUT 1 General Alarm 0 OUT 2 DC contactor command 1 OUT 3 Battery low 0 OUT 4 Fan command 0
(2)
IN 1 IN 2
ESD 0
(3)
Thermal protection 2
(1)
OUT1
IN1
IN2
OUT4
OUT2
IN3
OUT3
DIP2DIP1
IN 3 Temperature sensor /
1. The filter level indicates the activation delay: 0 (no delay),1 (1 s delay), 2 (60 s delay).
2. If the external ESD button is not used always insert a jumper to short circuit input IN 1.
3. If the external thermal protection is not used always insert a jumper to short circuit input IN 2.
If used in 132, or 200 TL the ADC cards must be n°2.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
71EN
Page 72
12.4 SERIAL COMMUNICATION INTERFACE
R
1
2
3
4
5
6
7
8
9
Isolated Serial RS232 DB9 and RS485 connectors are available on the card.
Isolated Serial RS232 DB9
RTX+
5
4
3
2
1
9
8
7
6
1 Reserved
RTX+
RTX–
2 RX for RS232 3 TX for RS232 4 Reserved 5 GND for RS232
Isolated RS485
If used in 132, or 200 TL the serial communication interface cards must be n°2.
RTX+
RTX–
6 Reserved 7 Reserved 8 Reserved 9 Reserved
72 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 73
12.5 SIGNAL CABLES ROUTE
PCS2 IM 132 - 200 TL
Cable fi xing points
Signal conduct
Power terminal area
WARNING: Signal cables must not entry inside the power terminal area.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
73EN
Page 74
13. WARNINGS AND TROUBLESHOOTING
The alarm messages offer immediate diagnosis of any faults, malfunctions or breakdowns in the batteries. The following events are indicated:
• Warning: non-serious alarm condition that causes the unit stop. This can be reset automatically.
• Alarm: serious alarm conditions that cause the unit stop. These alarm conditions require a manual reset. Alarm and warnings are divided into two categories:
• System Alarms/Warnings: these alarms/warnings relate to external parts of the unit (mains power network, output line, ambient temperature). Corrective actions are activated by the user (system installer or operator) or by the Support team.
• Unit Alarms/Warnings: these alarms/warnings relate to parts of the unit. Corrective actions are carried out by the Support Service.
System warnings
Warning Cause Remedy
The ambient temperature recorded
W01 Ambient over-temperature
by the unit is over 45° (see values on mimic panel).
Ambient temperature
W02
under the minimum thresh­old
W04
Internal over-temperature
W66
W20 High impedance to earth
Active Power reference too
(2)
W21
low for charging batteries
The ambient temperature recorded by the unit is under 15° (see value on mimic panel).
The temperature of the unit power structure is over 110° (see value on mimic panel).
The isolation controller and resistance to earth values recorded are too high.
The active power set point is too low to charge battery.
W23 Battery fully discharged Battery is fully discharged. Recharge the battery.
(2)
W24 W25
W26
W27
W28
W29
W30
Battery Low Voltage Battery cell voltage is critically low. Recharge the battery.
(2)
Battery Low Capacity Battery charge is critically low. Recharge the battery.
(2)
Battery Rest Time request
(2)
Battery Full Charge request
(2)
Battery Over-temperature Battery temperature too high. Reduce ambient temp. Calibration Procedure
(2)
request Equalisation Procedure
(2)
request
Battery has to wait for the Rest Time before charging/discharging.
Battery requires a Full Charge before discharging.
Execution of Calibration procedure is required. Execution of Equalisation procedure is
required. W31 Local Mode Enabled ESS is locally controlled through HMI. Use HMI to control. W32 General Battery Warning Other battery warnings are present. Solve the specific battery warning.
W33
W34
W36 W77
W38
W81
W39
W82
AC input network outside voltage on frequency range
Inverter overload condition
Active power limitation
Reactive power limitation
Input network is missing or insufficient
(voltage and/or frequency values
incorrect with reference to the infor-
mation provided in the technical data
table).
Inverter is working in overload condi-
tions.
Active power request by EMS isn’t
satisfied (due to temperature or
elapsed overload condition).
Reactive power request by EMS
not satisfied (due to temperature or
elapsed overload condition).
Check the ventilation or air-condition­ing system in the unit room.
Check the ventilation or air-condition­ing system in the unit room.
Check the ventilation or air-condition­ing system in the unit room.
Check the protective fuses. If the problem persists contact the support service. Increase the value of active power set point to allow correct battery charging current.
Wait for the rest time.
Full recharge of the battery.
Execute calibration procedure.
Execute equalisation procedure.
Check for the disconnection of protective devices upstream of the unit.
Check the applied voltage and frequency comply with the values set on the HMI.
Reduce the load.
Reduce the active power request.
Reduce the reactive power request.
74 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 75
System warnings
Warning Cause Remedy
W40 Low Insulation Resistance Detection of low insulation resistance. Check the Insulation to earth.
W41 Insulation Sensor Fault
(1)
W42 W43 W44
Module 1 on Alarm Module 1 stopped by alarm. Check Module 1.
(1)
Module 2 on Alarm Module 2 stopped by alarm. Check Module 2.
(1)
Module 3 on Alarm Module 3 stopped by alarm. Check Module 3.
Insulation sensor feedback not correct.
Check the Insulation Monitoring Device is properly connected.
Unit warnings
Warning Cause Remedy
W65 Unit in Derating
W69
AC input network outside frequency range
W70
The unit is reducing the power supplied/ drawn by the network.
Input network is missing or insufficient (voltage and/or frequency values incorrect with reference to the infor­mation provided in the technical data table).
Check the other alarms and/or visual warnings.
Check for the disconnection of protective devices upstream of the unit.
Check the applied voltage and frequency comply with the values set on the HMI.
Active power request by EMS not
W81 Unit Active power limitation
satisfied (due to temperature or
Reduce the active power request. elapsed overload condition). Reactive power request by EMS not satisfied (due to temperature or elapsed overload condition).
Reduce the reactive power request.
W82
Unit Reactive power limita­tion
System alarms
Alarms Cause Remedy
A01
A05 A06
command
(3)
SPD AC triggered AC overvoltage. Check and replace if necessary.
(3)
SPD DC triggered DC overvoltage. Check and replace if necessary.
Switch-off due to external
(3)
A07 Output contactor alarm
A08
Transformer over-temper­ature
A13 Watchdog elapsed
A15
Incorrect system configura­tion
The PCS is switched off due to an external instant switch-off command.
The output contactor status has not complied with machine command.
Over-temperature of the trasformer.
External EMS communication watch­dog elapsed.
System configuration wrong. Check the configuration setting.
Check if the external contact is
properly connected to ADC card. A
manual reset could be needed.
Contact the support service.
Check the ventilation or air-condition-
ing system in the unit room.
Check the cable between PCS and
External EMS device.
A22 Battery Overvoltage Battery voltage too high. Check the battery configuration.
A23
Battery Communication fault
No battery communications.
Check the cable between PCS and
battery.
A24 General Battery Alarm Other battery alarm are present. Solve the specific battery Alarm.
Check the thermal protection is
A25
BES Thermal protection
(2)
fault
Over temperature inside the cabinet.
properly connected to the ADC Card
and verify temperature inside battery
cabinet.
A26 DC Connection Fault Battery DC Contactor test failed.
(2)
A27
Battery Over Temperature Battery temperature too high. Reduce ambient temperature.
Check battery DC Contactor is prop-
erly connected to the ADC Card.
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
75EN
Page 76
Unit alarms
Alarms Cause Remedy
A68
Unit off due to over­temperature
Over-temperature cause. Reduce ambient temperature.
Make sure the air inlets and outlets on
A69 Fan fault Ventilation system breakdown.
the front and rear of the unit are free from obstructions.
A72 Unit locked Internal cause. Check the specific alarm.
A73 Input over-voltage
A76
Ambient under-tempera­ture
A77 Ambient over-temperature Ambient temperature is too high.
A78 Wrong phases rotation Wrong AC voltage phases rotation.
A84 AC Voltage Fault
The DC input voltage has exceeded 900 V.
Ambient temperature is too low.
AC voltage fault during Off-Grid operation.
Check the connections.
Check the ventilation or air-condition­ing of the unit room. Check the ventilation or air-condition­ing of the unit room. Check the phases rotation upstream of the unit. Check the load or faults downstream of the unit
A85 Overload elapsed Inverter stopped for elapsed overload. Reduce the load.
1. Only Power Module N° (1,2,3) has flagged an alarm, but the system is still operational.
2. Shown only if lead-acid battery type is set.
3. Available as option.
76 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 77
14. PREVENTIVE MAINTENANCE
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care­fully.
NOTE: any work carried out on the equipment must be performed by qualified technicians autho­rised by SOCOMEC.
Routine maintenance carried out annually is recommended in order to provide optimum operating efficiency and avoid equipment downtime.
Maintenance consists of thorough functionality checks on:
- Electronic and mechanical parts;
- Dust removal;
- Software updating;
- Environmental checks.
14.1 BATTERIES
The condition of the battery is fundamental to ESS operation. During the operating lifetime of the battery, the Sunsys PCS
for analysis. Expected battery lifetime is very much dependent on operating conditions:
- Number of charging and discharging cycles;
- Load rate;
- Temperature.
2
stores statistics on the conditions of use of the battery
NOTE: batteries must only be replaced with batteries recommended or sold by the manufacturer. Batteries must only be replaced by qualified technicians.
BEWARE: used batteries contain harmful substances. Do not open the cover!
NOTE: used batteries must be placed in appropriate containers. They should only be entrusted to a specialist waste disposal company.
14.2 FANS & CAPACITORS
The lifespan of consumable parts such as fans and capacitors (AC and DC) depends on whether or not the use and environmental conditions (premises, usage or load type) are abnormal or harsh for the equipment.
It is advisable to replace consumables as follows
Consumable part Years
Fan 5 AC and DC capacitor 7
1. Based on operation of the unit according to the manufacturer’s specification.
(1)
:
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
77EN
Page 78
15. UL1741SA: HOW TO CONFIGURE GRID SUPPORT FUNCTIONS
15.1 INTRODUCTION
Supplement SA to UL1741 standard covers grid support functions that are required to grid support utility interactive inverters and converters.
Installers are responsible for setting parameters according to the prescriptions defined in the local utility SRD(s) (Source Requirement Document). The wide range of parameter programmability covers the California Rule 21 and HECO Rule 14H.
NOTE: for transformer based models (PCS2 IM 33-66-100TR), formal compliance to UL1741SA standard requires 3-wire output only (w/o neutral connection), while operating in grid-tied mode. Contact Socomec for further information.
15.2 TRIP THRESHOLDS
MENU > SETTINGS > PCS SETTINGS > AC INTERFACE PROTECION Voltage and frequency trip thresholds can be set following the table below.
Name of parameter group
IP - VOLTAGE RANGE
IP - VOLTAGE TIMINGS
IP - FREQUENCY RANGE
IP - FREQUENCY TIMINGS
Name of parameter
UV3 50% 5 ÷ 100 Absolute minimum voltage admitted %Vn UV2 70% 5 ÷ 100 Intermediate minimum voltage admitted %Vn UV1 88% 5 ÷ 100 Minimum voltage admitted %Vn OV1 110% 100 ÷ 120 Maximum voltage admitted %Vn OV2 120% 100 ÷ 120 Absolute maximum voltage admitted %Vn
TimeOut UV3 1.50 s 0,01 ÷ 300 Trip time under UV3 voltage thr. TimeOut UV2 11.00 s 0,01 ÷ 300 Trip time under UV2 voltage thr. TimeOut UV1 21.00 s 0,01 ÷ 300 Trip time under UV1 voltage thr. TimeOut OV1 13.00 s 0,01 ÷ 300 Trip time over OV1 voltage thr. TimeOut OV2 0.16 s 0,01 ÷ 300 Trip time over OV2 voltage thr.
UF2 57.0 Hz 53,0 ÷ 60,0 Absolute minimum frequency admitted %fn UF1 58.5 Hz 53,0 ÷ 60,0 Minimum frequency admitted %fn OF1 60.5 Hz 60,0 ÷ 65,0 Maximum frequency admitted %fn OF2 62.0 Hz 60,0 ÷ 65,0 Absolute maximum frequency admitted %fn
TimeOut UF2 0.16 s 0,01 ÷ 300 Trip time under UF2 frequency thr. TimeOut UF1 300.00 s 0,01 ÷ 300 Trip time under UF1 frequency thr. TimeOut OF1 300.00 s 0,01 ÷ 300 Trip time over OF1 frequency thr. TimeOut OF2 0.16 s 0,01 ÷ 300 Trip time over OF2 frequency thr.
Default value
Programmable range
Description
78 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 79
15.3 RIDE THROUGH MODE & TIMINGS
The L/HVRT (Low and High Voltage Ride-Through) and L/HFRT (Low and High Frequency Ride-Through) define the behavior of the system in response to low and high voltage and frequency excursions outside the normal range of operation of the PCS.
The following pictures report an example of ride-through profiles that correspond to Rule 21 prescriptions.
Figure SA9.1
Example operating parameters that correspond to Rule 21 ride-through and must trip regions in
the time-voltage domain
Example operating parameters that correspond to Rule 21 L/HVRT
Table SA9.1
Region Voltage (% Nominal
High Voltage 2 (HV2) V 120 Not Applicable Not Applicable 0.16 s
High Voltage 1 (HV1) 110 <V<120 12s MomentaryCessation 13s
Near Nominal (NN) 88 ≤ V ≤ 110 ,QGH¿QLWe Continuous Operation Not Applicable
Low Voltage 1 (LV1) 70 V < 88 20 s Mandatory Operation 21 s
Low Voltage 2 (LV2) 50 V < 70 10 s Mandatory Operation 11 s
Low Voltage 3 (LV3) V < 50 1 s Momentary Cessation 1.5 s
a
While these operating parameters correspond to the Rule 21 parameters, they may be substituted with operating parameters
for other area EPS requirements.
Note 1: Manufacturer may evaluate product over wider ranges of adjustment than those within the table.
Note 2: The table voltage could be either at the PCC or equipment terminals.
Note 3: For LV3 or HV1 the EUT shall cease to energize in not more than 0.16 s (and not trip). This may differ in other SRD(s).
Voltage)
Ride-Through Until Operating Mode Maximum Trip Time
a
(s)
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
79EN
Page 80
Figure SA10.1
Example operating parameters that correspond to Rule 21 default ride-through and must trip
regions in the time-frequency domain
Example operating parameters that correspond to Rule 21 L/HFRT
Table SA10.1
Region System Frequency
High Frequency 2
(HF2)
High Frequency 1
(HF1)
Near Nominal (NN) 58.5 < f 60.5 Not Applicable ,QGH¿QLWe Continuous
Low Frequency 1
(LF1)
Low Frequency 2
(LF2)
a
While these operating parameters correspond to the Rule 21, 2015 parameters they may be substituted with operating
parameters for other area EPS requirements.
Note 1: Manufacturer may evaluate product over wider ranges of adjustment than those within the table.
Note 2: Frequency / Watt functionality is an option under the Rule 21, 2015 ¿OLQJ
Default Settings
f > 62 62.0 – 64.0 No Ride-Through Not Applicable 0.16
60.5 < f 62 60.1 – 62.0 299 Mandatory
57.0 < f 58.5 57.0 – 59.9 299 Mandatory
f 57.0 53.0 – 57.0 No Ride-Through Not Applicable 0.16
Minimum Range
of Adjustability
(Hz)
Ride-Through
Until (s)
MENU > SETTINGS > PCS SETTINGS > AC INTERFACE PROTECION Ride-through parameters can be set following the table below.
Ride-Through
Operational Mode
Operation
Operation
Operation
a
Trip Time (s)
300
Not Applicable
300
80 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 81
Name of parameter group
RIDE THROUGH MODE
Name of parameter
Name of parameter
Default value
sub-group
RIDE TROUGH ENABLE
Ride Through Enable
VOLTAGE RIDE THROUGH BEHAVIOR
HVR2 Mode
HVR1 Mode
LVR1 Mode
LVR2 Mode
LVR3 Mode
VOLTAGE RIDE THROUGH TIMINGS
Enabled Enabled/Disabled
Not Applicable
Momentary Cessation
Mandatory Operation
Mandatory Operation
Momentary Cessation
HVR2 Time 0s Not adjustable
HVR1 Time 12.00 s 0.01 ÷ 300
LVR1 Time 20.00 s 0.01 ÷ 300
LVR2 Time 10.00 s 0.01 ÷ 300
LVR3 Time 1.00 s 0.01 ÷ 300
FREQUENCY RIDE THROUGH BEHAVIOR
HFR2 Mode
HFR1 Mode
LFR1 Mode
LFR2 Mode
FREQUENCY RIDE THROUGH TIMINGS
Not Applicable
Mandatory Operation
Mandatory Operation
Not Applicable
HFR2 Time 0.16 s 0.01 ÷ 300
HFR1 Time 299.00 s 0.01 ÷ 300
LFR1 Time 299.00 s 0.01 ÷ 300
LFR2 Time 0.16 s 0.01 ÷ 300
Programmable range Description
Enable Ride-Through mode
Not Applicable/Momentary Cessation /Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation
Behaviour in HV2 region
Behaviour in HV1 region
Behaviour in LV1 region
Behaviour in LV2 region
Behaviour in LV3 region
Ride-Through time in HV2 region Ride-Through time in HV1 region Ride-Through time in LV1 region Ride-Through time in LV2 region Ride-Through time in LV3 region
Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation Not Applicable/Momentary Cessation/Mandatory Operation/Permissive Operation
Behaviour in HF2 region
Behaviour in HF1 region
Behaviour in LV1 region
Behaviour in LV2 region
Ride-Through time in HF2 region Ride-Through time in HF1 region Ride-Through time in LV1 region Ride-Through time in LV2 region
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
81EN
Page 82
15.4 RAMPS
Two types of ramp rate characteristics are defined:
- Soft-start ramp-up rate that defines the behavior of the device to ramp from zero to operating power after a trip or at first system power-on.
- Normal ramp-up rate when the inverter is adjusting the output power.
Parameters can be set in the following menu: MENU > SETTINGS > PCS SETTINGS > CONNECTION PARAMETERS
Name of parameter group
CONNECTION TIMINGS/RANGES
Name of parameter Default value Programmable
range
Soft Start Ramp 0,33 %Pn/s 0.10 ÷ 100.00
Normal Mode Ramp 100,00 %Pn/s 0.10 ÷ 100.00
Description
Ramp rate from zero to operating power after a trip Normal ramp rate when the inverter is adjusting the output power
15.5 ACTIVE/REACTIVE POWER CONTROL
Active and reactive power control represents one of the most important features of the Grid Support Utility Interactive Inverters. Reactive power can be controlled using the Specified Power Factor (SPF) or the Volt-VAr Mode (Q(V)) func­tionalities, while active power can be performed using the Frequency-Watt (P(f)) or Volt-Watt (P(V)) functions.
1) SPF - Specified Power Factor: the inverter operates at a specified, non-unity power factor
2) Volt/VAr Mode (Q(V)): the inverter supplies or absorbs reactive power in response to fluctuations in grid voltage. The figure below shows an example as reported in UL1741 Supplement SA standard.
Figure SA13.2
“Average” Volt-VAr curve for Q(V), Test 2
Page 83
3) Frequency-Watt (FW) function: the inverter may change its active power output with changes in grid frequency. The figure below shows an example as reported in UL1741 Supplement SA standard.
Figure SA14.1
Freq-Watt characteristic #1 (maximum slope)
4) Volt-Watt (VW) function: the inverter may change its active power output with changes in grid voltage. The figure below shows an example as reported in UL1741 Supplement SA.
Figure SA15.2
Volt-Watt characteristic #2
Page 84
The user must adjust the relevant parameters for each of the user modes as outlined below. MENU > SETTINGS > PCS SETTINGS > POWER SETTINGS
Name of parameter group
ACTIVE POWER
Name of parameter sub-group
FREQ/WATT PARAMETERS
Name of sub
Name of parameter
menu
FREQ/WATT PARAMETERS 1
P(f) Function Disabled Enabled/Disabled
P(f) over frequency threshold
P(f) statism over frequency
P(f) under frequency threshold
P(f) stat­ism under frequency
Default value
Programmable range
60.50 Hz 60.04 ÷ 65.00
1.60% 0.1 ÷ 6.0
59.50 Hz 55.00 ÷ 59.90
1.60% 0.1 ÷ 6.0
Description
Frequency/Watt function enable/disable
threshold to start over-
F
start
frequency F/W function
Over-frequency F/W cruve slope defined as
F
threshold to start under-
start
frequency F/W function
Under-frequency F/W curve slope defined as
VOLT/WATT PARAMETERS
ACTIVE POWER EXTERNAL CONTROL
REACTIVE POWER
FREQ/WATT PARAMETERS 2
P(f) Delay 0 ms 0 ÷ 1000
Wait Time after Freq/Watt
P(V) Function Disabled Enabled/Disabled
Min V 106 % Vn 100 ÷ 119
Max V 110 % Vn 100 ÷ 120
Histeresis on V Min
P(Max V) Charge %Pn
External Communication Watch-Dog
Watch-Dog timeout
0 s 0 ÷ 900
1% Vn 1 ÷ 5
100 % (charge)
1 ÷ 100
Disabled Enabled/Disabled
60 s 0 ÷ 120
Time delay before F/W func­tion start to avoid artifacts (short variation of frequency) Time delay to accept any new command ( power set point) after exiting from F/W function
Volt/Watt function enable/ disable Minimum voltage to start the algorithm Maximum voltage, corre­sponding to the power set below Voltage hysteresis %Vn around minimum voltage Power level to work with when voltage exceeds the Max V set above
Watchdog alarm enable to control the reception of the external watchdog Watch-Dog alarm timeout, if an extenrnal trigger is not received the machine stops
84 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 85
Name of parameter group
GENERAL SETTINGS
Name of parameter sub-group
CONTROL TYPE
CONSTANT POWER FACTOR
VOLT/VAR Q(V)
Name of sub
Name of parameter
Default value
menu
Reactive Power Control Type
Remote Q reference
Behaviour Capacitive
Fixed cosPhi 1.000 0.850 ÷ 1.000
Min P 5% Pn 0 ÷ 100
VOLT/VAR Q(V) PARAMS-1
V1 superior 108 % Vn 100 ÷ 120
V2 superior 110 % Vn 100 ÷ 120
V1 inferior 92 % Vn 80 ÷ 100
V2 inferior 90 % Vn 80 ÷ 100
VOLT/VAR Q(V) PARAMS-2
Q Max
100.00 %Sn
Q(V) Delay 0 s 0 ÷ 30
Q(V) - K
VOLT/VAR Q(V) PARAMS-3
0.000 %Qmax
P lock-in 20 % Pn 10 ÷ 100 P to start Volt/VAr function P lock-out 5 %Pn 0 ÷ 5 P to stop Volt/VAr function
CONSTANT REACTIVE POWER
Q value 0.00 %Pn 0.00 ÷ 100.00
Behaviour Capacitive
Q Max
P_Cmax
P_Dmax
100.00 %Sn
100.0 %Pn
100.0 %Pn
Priority Power Reactive Reactive/Active
Programmable
Description
range
Remote Q refer­ence/Fixed Q setpoint/Q=f(V) type A/Fixed
Reactive power management strategy
cosPhi/Disabled
Capacitive/ Inductive
System behaviour in reactive power production when SPF is selected CosPhi value for the SPF function Minimum power that allows the system to operate with SPF
Volt/Watt curve voltage, point 1 superior Volt/Watt curve voltage, point 2 superior Volt/Watt curve voltage, point 1 inferior Volt/Watt curve voltage, point 2 inferior
0.00 ÷ 100.00
Maximum reactive power production setting Delay to avoid unintentional reactive in case of short volt­age variation
-1.000 ÷ 1.000
Reactive power offset for the Volt/VAr curve
Set point of Q for fixed Q set
point control type Capacitive/ Inductive
0.00 ÷ 100.00
Reactive power behaviour
Absolute Q max that can be
set
0.00 ÷ 100.00 P Charge max (batteries)
0.00 ÷ 100.00 P Discharge max (batteries)
Power production priority in
case of over-load
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
85EN
Page 86
16. SAFEGUARDING THE ENVIRONMENT
Do not dispose of electrical appliances with normal waste, use separate collection facilities. Follow local council waste regulations for proper disposal arrangements to reduce the environmental impact of waste
electrical and electronic equipment or contact your local government for information regarding the collection arrange­ments available.
If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging health and wellbeing. Depleted batteries are considered as toxic waste. When battery replacement becomes necessary, only give rundown batteries to certified and licensed waste disposal companies. In accordance with local legislation, it is prohibited to dispose of batteries together with other industrial waste or household refuse.
The crossed-out trash bin symbol is placed on this product to encourage users to recycle components and units whenever possible. Please be environmentally responsible and recycle this product through your recy­cling facility at the end of its lifetime.
For any questions regarding the disposal of the product, contact local distributors or retailers.
86 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 87
17. TECHNICAL SPECIFICATIONS
Model 33 TR 66 TR 100 TR 132 TL 200 TL
DC Section
Range of DC operating volt­age
Number of power modules 1 2 3 4 6 Maximum discharging
current Maximum recharging
current
Battery Section
Lithium, Lead acid, Vanadium Redox, Generic Battery
AC Section
Maximum continuous power
Maximum continuous apparent power
On-grid overload 110% - 30 minutes
Off-grid symmetrical over­load
Off-grid asymmetrical over­load (mono phase load)
Nominal voltage (Un) VAC 480 (3ph + N) 280 (3ph) Operating voltage range VAC 423 to 528 (3ph + N) 246 to 308 (3ph)
Active power droop
Reactive power droop: percentage voltage variation
Rated frequency (Fn) Hz 60 Operating frequency range Hz 59.3 to 60.5 Rated current A 40 80 120 272 412 Maximum current at nomi-
nal voltage Overcurrent protection
device
Off-grid short-circuit current 3-phase (IK3 IEC60909-
0) and phase-phase (Ik2 IEC60909-0)
A 80 160 240 160 + 160 240 + 240
A 80 160 240 160 + 160 240 + 240
kW 33 66 100 132 200
kW 33 66 100 132 200
190% - 30 minutes 215% - 10 minutes
260% - 30 seconds
+3% Vnom @ Load cosfì 0.8 cap. (neg.)
–7% Vnom @ Load cosfì 0.8 ind. (pos.)
+9% Vnom @ nominal kVAR cap. (neg.) –11% Vnom @ nominal kVAR ind. (pos.)
A 60 120 180 408 618
50 A - Type D
75 A x 40
ms +
62 A x 60 ms
450 to 825 Vdc without derating
350 to 850 Vdc with derating
Supported in combination with PMS.
Please contact Socomec for compatibility.
110% - 30 minutes 125% - 10 minutes
150% - 30 seconds
Not applicable
–0.24 Hz @ nominal kW supplied
+0.24 Hz @ nominal kW absorbed
+2% Vnom @ Load cosfì 0.8
cap. (neg.)
–7% Vnom @ Load cosfì 0.8
ind. (pos.)
+5% Vnom@nominal kVAR
cap. (neg.)
-10% Vnom@nominal kVAR cap. (pos.)
100 A - Type D160 A - Type D315 A - Type C500 A - Type
C
150 A x 40
ms +
125 A x 60
ms
225 A x 40
ms +
187 A x 60
ms
462 A x 40
ms +
383 A x 60
ms
700 A x 40
ms +
580 A x 60
ms
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
87EN
Page 88
Model 33 TR 66 TR 100 TR 132 TL 200 TL
Off-grid short-circuit current phase-neutral (Ik1 IEC60909-0)
121 A x 40
ms +
96 A x 60 ms
242 A x 40
ms +
192 A x 60
ms
362 A x 40
ms +
287 A x 60
ms
Not applicable
Output power factor rating -1.00 to +1.00 THDI On-grid mode % < 3 < 4
Topology Single conversion with Output transformer
Parallel operation
Single conversion transfor-
merless
On-grid With any kind of generator (voltage or current type)
With other SUNSYS PCS² IM (power extension)
Off-grid
With generic current/power generators
Not operated in parallel with isochronous voltage generator
Other features
Islanding detection Yes Schedulded On-grid to
Off-grid transition
Without break
Capable of receiving frequency and voltage refer­ence in islanding mode from
Yes
external device (PMS) Capable of receiving
frequency and voltage refer­ence from external device (PMS) to synchronise the
Yes microgrid with the grid to perform off-grid to on-grid transition
Black start mode: capable of supplying the microgrid
Yes from power cut conditions
Effi ciency
Dissipated power (max) W 1810 3620 5710 4930 7470 Dissipated power (max) BTU/h 6180 12360 19490 16830 25500
Maximum efficiency
Typical Efficiency
Auxiliary AC power supply
Charge % 95.8 96.1 96.0 97.4 Discharge % 96.0 96.2 96.3 97.6 Charge % 94.8 94.8 94.6 96.4 Discharge % 95.1 95.2 95.0 96.7
Rated voltage from 120 to 240 VRMS Rated frequency Hz 60 Consumption during opera-
tion
W< 30
Consumption on standby W < 10
General data
Pollution class in accor­dance with UL 840 and IEC
3
60664-1 Over Voltage Category
(OVC) in accordance with UL 840 and IEC 60664-1
OVC IV
(AC terminals)
88 EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Page 89
Model 33 TR 66 TR 100 TR 132 TL 200 TL
External Over Voltage protection type (AC termi­nals)
1.8 kVPK [L-G] / 2.5 kVPK [L-L]
SPD type 2
Enclosure rating NEMA 1 Environmental category Non-air-conditioned indoor space
-5 °C to +50 °C (23 °F to 122 °F)
Operating ambient temper­ature
-5 °C to 0 °C (23 °F to 32 °F) with derating
40 °C to 50 °C (104 °F to 122 °F) with derating Rated temperature 0 °C to +40 °C (32 °F to 104 °F) Storage temperature -5 °C to +60 °C (23 °F to 140 °F) Relative humidity 5% to 95% condensation-free Cooling system Smart cooling
3
Required cooling capacity m
/h 480 1280 1760 1742 2880 Acoustic noise at 1 m dB < 60 < 64 < 65 < 67 Altitude (max) m 1000
Dimensions and Weight
Dimensions
Width Depth 795 806
mm
600 1200 805
Height 1400 2150
kg 355 530 206 + 610 486
Weight
Power module weight
Certifi cations
lb 782.6 1168.4
kg 34.5
lb 76
454.1 +
1344.8
1071.5
UL 1741
Safety
STANDARD FOR SAFETY. Inverters, Converters, Controllers and
Interconnection System Equipment for use with Distributed Energy
Resources.
EMC
Radio frequency devices: measurement of disturbance voltage.
FCC Part 15
IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2005
Grid Code
IEEE Standard for Interconnecting Distributed Resources with Electric
Power Systems.
Software
1. Depending on the specific country setting and regulations.
Standard for Software in Programmable Components
UL 1998
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
89EN
Page 90
Page 91
Page 92
Socomec: our innovations supporting your energy performance
10
1
independent manufacturer
3,200
worldwide
Your power management expert
employees
% of sales revenue
dedicated to R&D
400
dedicated to service provision
experts
POWER
SWITCHING
POWER
MONITORING
The specialist for critical applications
q Control, command of LV
facilities
qSafety of persons and assets
q Measurement of electrical
parameters
qEnergy management
A worldwide presence
8
production sites
qFrance (x3) qItaly qTunisia qIndia qChina (x2)
27
q TRSQ@KH@q!DKFHTLq"GHM@q%Q@MBD q&DQL@MXq(MCH@q(S@KXq-DSGDQK@MCR q/NK@MCq1NL@MH@q2HMF@ONQD q2KNUDMH@q2O@HMq2VHSYDQK@MCq3G@HK@MC q3TMHRH@q3TQJDXq4*q42
subsidiaries
POWER
CONVERSION
qEnergy quality qEnergy availability qEnergy storage
EXPERT
SERVICES
q Prevention and repairs qMeasurement and analysis qOptimisation q Consultancy, commissioning
and training
80
countries
where our brand is distributed
HEAD OFFICE
SOCOMEC GROUP
SAS SOCOMEC capital 10 633 100 € R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex Tel. +33 3 88 57 41 41 - Fax +33 3 88 57 78 78 info.scp.isd@socomec.com
www.socomec.com
YOUR DISTRIBUTOR / PARTNER
*IOMSUNPCXX07-EN 01*
IOMSUNPCXX07-EN 01 07.2019
-NMBNMSQ@BST@KCNBTLDMS¡2NBNLDB2 2 KKQHFGSRQDRDQUDC#NBTLDMSOQHMSDCNMO@ODQEQNLRTRS@HM@AKXL@M@FDCENQDRSR
Loading...