Socomec Field Junction Box is designed to make the connection of groups of strings (photovoltaic panels) to an inverter in photovoltaic applications.
Basic functions :
• Connection and combination of the photovoltaic strings
• Switching OFF and disconnection of the DC voltage of the installation
• Protection against the over-currents of all the polarities
• Fault signalling on the PV string (fuse indicator).
• Protection against atmospheric over-voltage
Optional functions
• Remote control switching OFF and disconnection.
• Canopy against solar radiations
1.2. GENERAL SAFETY RECOMMENDATIONS
• Always read this instructions manual before commissioning the equipment.
The DC voltage upstream fuse-disconnectors is never disconnected even the position of the switching products.
The DC voltage level is dangerous. Any contact can cause an electrocution or an electric shock.
• The devices shall be accessible to authorized personnel only.
• Unauthorized opening of the device or improper interventions can lead to personnel severe injury, death or material damage.
• Repairs on the boards must be carried out only by the manufacturer or by personnel authorized by the manufacturer.
• Any repair works must only be carried out by qualified personnel.
• Any repair works must only be car
• Original spare parts are available through SOCOMEC customer assistance service.
• Check protective devices regularly, following the indications in the chapter Electrical installation, operation and maintenance.
• Use only fuses of the correct dimensions. The rated current of the fuses must be calculated according to each plant specifications.
• The Socomec Field Junction Box must be used in accordance with the documentation as well as applicable directives and standards.
• The Socomec Field Junction Box must be handled with care, and protected against mechanical stresses.
• Do not bend any components.
• Do not change the isolating distances.
• Do not touch electronic components or contacts.
• The Socomec Field Junction Box contains components that are sensitive to electrostatic charges and may be damaged if handled
improperly.
• Any use of damaged or spoiled components shall be considered as a non-compliance with the applicable standard.
It is forbidden to make any modification to the Field Junction Box without the prior
ried out using original spare parts.
agreement of Socomec.
1.3. PERSONNEL QUALIFICATION
Personnel must be familiar with the installation, assembly, commissioning and operation of the device and know the possible sources
of danger and must have the required qualification to perform maintenance and commissioning.
This qualification must include:
• Mechanical installation of the device: Trained installation technician with basic electrical skills
• Electrical installation of the device: Trained electricians
• Commissioning of the device: Trained electricians
4
4
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
Page 5
2. PRODUCT OVERVIEW
2-1
Remote controlled switching and disconnecting
8 STRINGS
Box code
Box dimensions (H x W x D mm)
12 STRINGS
MANUAL DISCONNECTION
37PV0008
540 x 540 x 201
REMOTE DISCONNECTION
37PV1008
540 x 540 x 201
Box code
Box dimensions (H x W x D mm)
16 STRINGS
Box code
Box dimensions (H x W x D mm)
24 STRINGS
37PV0012
540 x 720 x 201
37PV0016
540 x 810 x 201
37PV1012
540 x 720 x 201
37PV1016
540 x 810 x 201
ENGLISH
Box code
Box dimensions (H x W x D mm)
37PV0024
540 x 1080 x 201
37PV1024
540 x 1080 x 201
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
5
Page 6
2-2
Product identifi cation labels
2. PRODUCT OVERVIEW
INTERNAL
Product code
Technical data
Serial number
Product code
Description
CE marking
Serial number
DE marking
EXTERNAL
Symbol class
2-3
Safety labels
Label on the cover
Attention
Câbles
courant
continu
sous
tension
Attention
Direct
current
cable under
voltage
Attenzione
Cavi in
corrente
continua
sotto
tensione
Label inside the box, on the polycarbonate protection screen
Attention
Ne pas
manœuvrer
en charge.
Attention
Do not
operate
under
voltage.
Attenzione
Non operare
sotto
tensione.
Atenção
Cabo
corrente
continua
sob tensão
Atenção
Não
manipular
sob tensão
Achtung
Gleich-
stromkabel
unter
spannung
Achtung
Nicht
unter last
betätigen
Atención
Cables de
corriente
continua
bajo tensión
Atención
No
manipular
en carga.
6
6
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
Page 7
3. INSTALLATION
3.1. ENVIRONMENTAL REQUIREMENTS
The following points must be considered for installation:
• The Field Junction Box is designed for both indoor and outdoor use.
• The Field Junction Box is exclusively designed for vertical fitting.
• Ensure a good flatness of foothold of the box fixations.
• If the wall is not flat, we recommend to use rigid profiles to fix the SOCOMEC Field Junction Box and to use wedges.
• The supports on which the Field Junction Box is fitted must be of non inflammable material. There must be no inflammable material
in the vicinity. If the device is fitted indoors, it is advisable to install a smoke detector.
• Ensure protection against wind, moisture, snow load and the direct exposure to sun radiation. (Special accessories may be
proposed by Socomec).
3.2. TRANSPORT – INSTRUCTIONS FOR HANDLING
CAUTION!
• Do not overturn the Field Junction Box.
The
Field Junction Box
•
• During transport and storage the Field Junction Box must remain in its original packaging.
can be transported only in horizontal position and in an appropriate manner.
WARNING!
• If visible signs of damages due to the transport are noticed on the delivered product, do not install it or put it
into service. Check that the quality, the material and the type of products received are as ordered.
• For insurance reasons, visible faults, such as external damage on the packaging and/or on the product, must
be notified to the sender within seven days.
CAUTION!
• The device is heavy. For transport at least two people are necessary.
•
If the
Field Junction Box
of transport.
box must be transported over long distances, use adequate lifting equipment and means
ENGLISH
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
7
Page 8
3.3. ASSEMBLING AND DISASSEMBLING OF THE COVER
Unscrew the fixing screws of the cover using a slotted head screw driver 10 mm.
2 x 8 screws for the Field Junction Box 24 strings
1 x 8 and 1 x 6 screws for the Field Junction Box 16 strings
1 x 8 screws for the Field Junction Box 8 strings and 12 strings
Fixing screws of the cover
3.3-1
3. INSTALLATION
3.4. FIXING OF THE FIELD
JUNCTION BOX
Recommended screw diameter: M5
Dimensions for the drilling of the Field Junction Box fixing screws
• Before starting any installation work, use personal protective equipment.
• During operation the temperature of some components may be high.
• Disconnect the DC switch-disconnector and then open all the fuse holders.
• Check the tightening torque of the fuse holder electrical connections before product installation.
4.2. DC SWITCH-DISCONNECTOR CABLES CONNECTIONS
• Switch-disconnector instructions must be respected.
• Do not remove the safety insulating screens separation between the terminals
A pre-break NO/NC contact is fi tted in standard on the DC switch-desconnector.
Tightening torque of the power cables connecting screws of the DC switch-disconnector:
DC switch disconnector
type
Confi guration (Nb of
strings)
Connecting screwsTightening torque (Nm)
With remote tripping8 – 12 – 16M814Nm
24M1031Nm
With manual tripping8 – 12 – 16 - 24M1024Nm
ENGLISH
Max. cable
cross-
section
(mm²)
The interphase barriers of the DC switch shall be equipped during normal operation of the Field Junction Box
4.3. REMOTE CONTROLLED DC SWITCH
It is possible to insert a trip coil on the main switch so that the switch can be remote controlled. The trip coil is supplied as an
option (equipped by the customer).
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
9
Page 10
4.4. DC STRINGS CONNECTION
Type of cable: cables with double insulation for photovoltaic
applications.
Cross-section Cu: 4 to 6 mm²
Cable glands: ISO 16 (max)
Tightening torque of the fuse disconnectors: 2 to 2.5 Nm
Bottom view
4.4-2
Outgoing gland plateStrings incoming gland plate
4. ELECTRICAL REQUIREMENTS
4.4-1
POSITIVE POLARITY +
NEGATIVE POLARITY -
4.5. INSTALLING THE FUSES
• Use only gPV fuses certifi ed for photovoltaic applications.
• Type de fuses: PV 10 x 38 gPV 1000V (compliance with IEC
60269-6)
• ISC STC max/string: 10 A
• PV module peak power current IMPP/string: 9 A
The rated current of the fuses must be calculated for each plant
•
separately (See maximum rated current ISC STC and Impp
STC values per string in the Technical Characteristics chapter).
• The fuse-holder terminals where the strings cables are
connected are always live even if the fuse holder is open.
• Before inserting the fuses of the strings, check the correct polarity of the inputs and check if there is no earth fault.
• Install/remove the fuses only after having disconnected the load (by opening the DC switch-disconnector) and using the appropriate personal protective equipment.
4.5-1
10
10
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
Page 11
4. ELECTRICAL REQUIREMENTS
4.6. REFERENCES OF SPARE FUSES
Minimum quantity to order: 10 pieces
Fuse ratingReference
2A
4 A60DC0004
6 A60DC0006
8 A60DC0008
10 A60DC0010
12 A
16 A60DC0016
4.7. SURGYS - SURGE PROTECTION DEVICE (SPD)
60DC0002
60DC0012
Installation
4.7-1
Cable cross-section: 6 mm² to 25 mm².
Maximum cable length: 0.5 m
Respect the rules of the class 2: the ground connecting cable
of the SPD device must not be yellow/green coloured.
PE cable tightening torque: 2.2 Nm
Maintenance
• Check the end of service life indicator of the Surgys.
• Reference of Surgys m-G51-1000PV with remote signal, 2
poles: 49822521
• Reference of spare plug-in module m-G51-1000PV:
49822529
4.8. PERIODIC MAINTENANCE CHECKS
Checklist
• Cable status.
• Box status.
• Connections status.
• Check tightening torques.
• Fuses status.
• DC switch-disconnector status.
• DC switch-disconnector remote trip operation.
• Surgys surge protection device Status (end of life indicators).
Periodicity: once a year minimum.
L+
L -
+
-
G51 G51 G51
T : Télésignalisation
T
11
121114
12
14
ENGLISH
4.9. STORAGE
The Field Junction Box must be stored appropriately.
• During storage the Field Junction Box must remain in its original packaging.
• The Field Junction Box must be stored in environments free from damp, protected against dust and condensation and exposed
to small variations in temperature.
• Observe the climate conditions in conformity with standard EN 50178.
• Ambient temperature for transport and storage: from -25 °C to +60 °C
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
11
Page 12
5. SCHEME
5-1
SOCOMEC Field Junction Box without monitoring
Number of strings
Load break Q1
Cross-section
PE cable 6
2
minimum (must not
be green/yellow)
Fuse disconnect
RM 32 DV - 1000V
DC switch
disconnector
12
12
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
Page 13
6. TECHNICAL CHARACTERISTICS
Confi gurations
Environmental conditions
Ambient temperature operating range
Storage temperature- 20 to +70 °C
Relative humidity/Altitude95% without condensation @ 40 °C / 2000 m
Electrical characteristics
Maximum open circuit voltage (Uoc MAX)1000 VDC
Rated impulse withstand voltage8 kV
Maximum rated current per string at 40 °CImpp STC / Isc STC (A)
Connection for rating 2 A1,30/1,401,30/1,401,30/1,401,30/1,40
Connection for rating 4 A2,40/2,662,40/2,662,40/2,662,40/2,66
Connection for rating 6 A3,60/4,003,60/4,003,60/4,003,60/4,20
Connection for rating 8 A4,60/5,104,60/5,104,60/5,104,90/5,40
Connection for rating 10 A5,70/6,305,70/6,305,70/6,306,20/6,80
Connection for rating 12 A6,90/7,606,90/7,606,90/7,607,40/8,10
Connection for rating 16 A9,10/10,009,10/10,009,10/10,009,10/10,00
Maximum rated current per string at 60 °CImpp STC / Isc STC (A)
Connection for rating 2 A1,30/1,401,30/1,401,30/1,401,30/1,40
Connection for rating 4 A2,40/2,662,40/2,662,40/2,662,40/2,66
Connection for rating 6 A3,50/3,853,60/4,003,50/3,853,80/4,20
Connection for rating 8 A4,50/5,004,60/5,104,50/5,004,90/5,40
Connection for rating 10 A5,70/6,255,70/6,305,70/6,256,20/6,80
Connection for rating 12 A6,80/7,506,90/7,606,80/7,507,40/8,10
Connection for rating 16 A7,50/8,209,10/10,007,50/8,207,70/8,50
Protection class
Mechanical characteristics
Degree of protectionIP65
Mechanical impact protectionIK09
Weight (kg)17202638
Dimensions (HxWxD mm)540 x 540 x 201540 x 720 x 201540 x 810 x 201540 x 1080 x 201
Standards
Specifi cation and testing of low voltage electrical assemblies
Power switchgear and controlgear assembliesIEC 61439-2 (Issue 2; 2011)
Photovoltaic installation guideUTE C 15-712-1
European conformity
(1)
8 strings12 strings16 strings24 strings
- 20 to +40 °C without derating
40 to 60 °C see derated values hereunder*
Class 2
Low voltage European Directive n°2006/95/CE - European Directive EMC n°2004/108/CE
ENGLISH
SUNSYS FJB - Ref.: IOMSUNIFXX01-GB 00
13
Page 14
Page 15
Page 16
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 816 800€
R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse
F-67235 Benfeld Cedex - FRANCE
Tel. +33 3 88 57 41 41
Fax +33 3 88 74 08 00
info.scp.isd@socomec.com
www.socomec.com
YOUR DISTRIBUTOR
*IOMSUNIFXX01-GB 00*
IOMSUNIFXX01-GB 00 01.2014