socomec STATYS Operating Manual

Page 1
OPERATING MANUAL
STATYS
Jbus / Modbus serial link
OPMSTAJB0810-GB_01
Page 2
STATYS
Jbus / Modbus serial link
Index
1. Foreword 3
ITALIANOENGLISH
aFety requIrement 3
2. 1. uSIng condItIonS 3
2. 2. StatyS operatIng reFerence 3
3. envIronment 3
3. 1. recyclIng oF electrIcal productS and equIpment 3
4. IntroductIon 4
4. 1. general purpoSe 4
4. 2. JbuS/modbuS protocol 4
4. 3. data decodIng 4
5. JbuS/modbuS SerIal InterFace InStallatIon InSIde StatyS 5
5. 1. ‘com-SlotSlocalISatIon 5
5. 2. JbuS/modbuS SerIal InterFace plug In 5
5. 3. connectIonS and wIrIng 6
6. JbuS/modbuS lInk 7
6. 1. SerIal lInk 1 and 2 deFault SettIngS 7
6. 2. How to cHange tHe SerIal lInk SettIngS ? 7
7. JbuS/modbuS protocol 8
8. StatyS JbuS/modbuS tableS 8
8. 1. How to read data: 8
8. 2. IncomIng data Structure: 8
8. 3. StateS tableS: StartIng addreSS 0x0140, 4 wordS 9
8. 4. alarmS tableS: StartIng addreSS 0x0148, 2 wordS 11
8. 5. meaSurementS tableS: SStartIng addreSS 0x0220, 64 wordS 12
8. 6. permISSIonS tableS: StartIng addreSS 0x0150, 1 wordS 14
8. 7. commandS tableS: StartIng addreSS 0x0190, wrIte 1 wordS 14
2 OPMSTAJB0810-GB_01
Page 3
STATYS
Jbus / Modbus serial link
1. Foreword
Thank you for the trust you have in our Static Transfer System.
This equipment complies with the IEC 62310-2 product standard concerning Static Transfer Systems (STS).
CAUTION : “This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent disturbances”.
SOCOMEC UPS reserves the right to modify their specifications at any time as far as this contrib­utes to technical progress.
2. SaFety requIrement
2. 1. uSIng condItIonS
ENGLISH
Do read carefully these operation instructions before using the JBUS/MODBUS interface.
Whatever the repairs, they must be made only by authorised stas, which have been suitably trained. It is recommended that the ambient temperature and humidity of the STATYS environment are maintained below the values specied by the manufacturer.
2. 2. StatyS operatIng reFerence
Respect the safety requirements.
Do read carefully the operation instructions of STATYS.
For an optimal operation, it is recommended to maintain the ambient temperature and humidity of the STATYS environment below the values specied by the manufacturer.
This equipment meets the requirements of the European directives applied to this product. As a conse­quence it is labelled as follows:
3. envIronment
3. 1. recyclIng oF electrIcal productS and equIpment
Provision is made in European countries to break up and recycle materials making up the system. The vari­ous components must be disposed of in accordance with the legal provisions in force in the country where the system is installed.
OPMSTAJB0810-GB_01 3
Page 4
STATYS
Jbus / Modbus serial link
4. IntroductIon
4. 1. general purpoSe
This document provides required information of the JBUS/MODBUS protocol serial link.
Before connecting a supervision equipment or BMS system (Building management system) to the STATYS,
ITALIANOENGLISH
it is necessary to install and set up the serial interface.
This interface is located in the STATYS « com-slot », and should be set through the control panel or via the graphic touch screen (optional).
STATYS is able to manage only 1 JBUS/MODBUS serial links.
4. 2. JbuS/modbuS protocol
This document does not explain the JBUS/MODBUS protocol management. Please refer on www.modbus.org web site for more information.
The STATYS JBUS/MODBUS uses the following functions :
function 3 for reading Input Registers (16 bits), function 6 for writing single Registers (to control STATYS).
The data eld is composed of words, dened by a MSB (most signicant byte) and a LSB (lowest signicant byte), and displayed in the following order on the serial link.
1 WORD DATA b7 MSB b0 b7 LSB b0 b15 b0
4. 3. data decodIng
Status and alarms Information This information are coding in bit. This means that 1 word denes 16 information. If the related bit is set to 1, this information is active or true.
Measurements and counters data 1 word denes a measurement or a counter. Some values are numeric decimal signed or unsigned (0 to 65535 or from -32767 to 32767), or in hexadecimal (0x0000 to 0xFFFF).
4 OPMSTAJB0810-GB_01
Page 5
STATYS
Jbus / Modbus serial link
5. JbuS/modbuS SerIal InterFace InStallatIon InSIde StatyS
5. 1. ‘com-SlotSlocalISatIon
ENGLISH
STATYS 63/100A rack:
SLOT 1
SLOT 2
SLOT 1
5. 2. JbuS/modbuS SerIal InterFace plug In
The serial interface should be plugged in the corresponding slot, and xed with 2 crews. STATYS is able to manage only 1 JBUS/MODBUS interfaces.
2 Com-Slots are present at the rear of the xed unit, the slot 1 receive the serial card.
STATYS 32/63A rack: only 1 Com-Slots is present at the rear of the products and receive the serial card.
STATYS 200/600A: 4 Com-Slots are present on the rack slot, in front of the cabinet, the slot 1 receive the serial card.
SLOT 1
SLOT 2
SLOT 3
SLOT 4
OPMSTAJB0810-GB_01 5
Page 6
STATYS
Jbus / Modbus serial link
5. 3. connectIonS and wIrIng
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
5. 3.1. RS232 connection:
Standard PC connection
ITALIANOENGLISH
Sub-D 9 pins connectorPin 2 : RxPin 3 : TxPin 5 : GND
5. 3.2. Isolated RS485 connection
2 wires connection« dip-switch 1 » allows connecting the terminal resistor Isolation via “opto-coupler”2 polarization resistors could be removed easily (if needed).
the shield should be earthing at one point.
rtx +
tx +
rtx -
tx -
5. 3.3. Isolated RS422 connection
4 wires connection« dip-switch 1 and 2 » allows connecting the terminal
resistor
Isolation via “opto-coupler”4 polarization resistors could be removed easily (if needed).
the shield should be earthing at one point.
Before making any connection, please check the cabling. A wrong connection or cabling can dam­age the serial link interface.
6 OPMSTAJB0810-GB_01
rx +
rx -
Page 7
STATYS
Jbus / Modbus serial link
6. JbuS/modbuS lInk
6. 1. SerIal lInk 1 and 2 deFault SettIngS
Baud rate: 9600 bauds Parity: NONE Data: 8 bits Stop: 1 bit Slave: 1
The serial link settings can be set from the control panel or from the graphic touch screen.
6. 2. How to cHange tHe SerIal lInk SettIngS ?
Available baud rate: 4800 - 9600 - 19200 bauds Parity: EVEN - ODD - NONE Slave number: 1 to 255
ENGLISH
Settings menu of the LCD mimic panel type D20 (see the operating manual):
Modbus link conguration (user access) Display: mod bus
Slave number Display: sla nb Default value: 1 Possible choice: 1 to 255
Link speed Display: bds Default value: 9600 Possible choice: 2400, 4800, 9600 or 19200
Link parity Display: par Default value: no Possible choice: odd, eve (even) or no
Settings screen of the Graphic mimic panel type ADICOM (see the operating manual):
6. 2-1
«Type» should be setup at Modbus mode.
OPMSTAJB0810-GB_01 7
Page 8
STATYS
Jbus / Modbus serial link
7. JbuS/modbuS protocol
Reminder: The JBUS/MODBUS protocol available on STATYS is slave and in RTU mode. It uses the function 3 as ‘read registers’ and the function 6 as ‘write register’. The slave number is set via the control panel or via the graphic touch screen.
Conventions: The table addresses are written in hexadecimal, beginning with ‘0x’. Some PLC systems request a relative address starting from 400 (0x0190) or 40001 (0x9C41), on this address
ITALIANOENGLISH
it’s necessary to add the rst address of the JBUS/MODBUS table.
Frame errors management: In case of wrong data request, the STATYS answers with the following frame error :
Error function code Error code Cause
80 + code function 1 Function error 80 + code function 2 Addresses error 80 + code function 3 Wrong data 80 + code function 6 busy 80 + code function 8 Write register error
8. StatyS JbuS/modbuS tableS
§ TABLE Start addresses Table length in words JBUS/MODBUS FUNCTION
1 States 0x0140 4 3 READ 2 Alarms 0x0148 2 3 READ 3 Measurements 0x0220 64 3 READ 4 Permissions 0x0150 1 3 READ 5 Commands 0x0190 1 6 WRITE
8. 1. How to read data:
The identication, status and alarms tables should be read completely (this means the number of word to read is equal to the table length). The measurements table should be read word by word or per group, without exceed the length of the table. (from 0x0220 to 0x025F).
8. 2. IncomIng data Structure:
Example of 6 words
1 2 3 4 5 6 7 8 9 10 11 12
MSB 0 LSB 0 MSB 1 LSB 1 MSB 2 LSB 2 MSB 3 LSB 3 MSB 4 LSB 4 MSB 5 LSB 5
WORD 0 WORD 1 WORD 2 WORD 3 WORD 4 WORD 5 b15 b0 b15 b0 b15 b0 b15 b0 b15 b0 b15 b0 S15 S00 S31 S16 S47 S32 S63 S48 A15 A00 A31 A16
M00 M01 M02 M03 M04 M05
8 OPMSTAJB0810-GB_01
Page 9
STATYS
Jbus / Modbus serial link
8. 3. StateS tableS: StartIng addreSS 0x0140, 4 wordS
CODE DESCRIPTION BIT ADDRESS Remarks
S00 Source 1 OK 0 0x0140
S01 Source 1 critical 1 0x0140
S02 Source 1 out of tolerance 2 0x0140
S03 Source 1 absent 3 0x0140
S04 PowerPath 1 OK 4 0x0140
S05 5 0x0140
S06 Source 2 OK 6 0x0140
S07 Source 2 critical 7 0x0140
S08 Source 2 out of tolerance 8 0x0140
S09 Source 2 absent 9 0x0140
S10 PowerPath 2 OK 10 0x0140
S11 11 0x0140
S12 Srcs perm. Synchronised 12 0x0140
S13 Sliding Sources 13 0x0140
S14 Srcs perm. Not Synchron. 14 0x0140
S15 Srcs Instant. Synchron. 15 0x0140
S16 S1 is preferred source 0 0x0141
S17 Load on preferred source 1 0x0141
ENGLISH
S18 Load on auxiliary source 2 0x0141
S19 Load not supplied 3 0x0141
S20 Load on manual by-pass1 4 0x0141
S21 Load on manual by-pass2 5 0x0141
S22 6 0x0141
S23 Load on S1 7 0x0141
S24 Load on S2 8 0x0141
S25 9 0x0141
S26 Transfer locked ext. 10 0x0141
S27 11 0x0141
S28 Output OK 12 0x0141
S29 Output out of tolerance 13 0x0141
S30 Output absent 14 0x0141
S31 15 0x0141
OPMSTAJB0810-GB_01 9
Page 10
STATYS
Jbus / Modbus serial link
CODE DESCRIPTION BIT ADDRESS Remarks
S32 ESD input active 0 0x0142
S33 Q41 closed 1 0x0142
S34 Q42 closed 2 0x0142
S35 SS1 closed 3 0x0142
ITALIANOENGLISH
S36 SS2 closed 4 0x0142
S37 Q30 closed 5 0x0142
S38 Q51 closed 6 0x0142
S39 Q52 closed 7 0x0142
S40 8 0x0142
S41 9 0x0142
S42 10 0x0142
S43 11 0x0142
S44 12 0x0142
S45 Remote controls enabled 13 0x0142
S46 Maintenance alert 14 0x0142
S47 User mode 15 0x0142
S48 Board 1 input 1 active 0 0x0143
S49 Board 1 input 2 active 1 0x0143
S50 Board 1 input 3 active 2 0x0143
S51 Board 2 input 1 active 3 0x0143
S52 Board 2 input 2 active 4 0x0143
S53 Board 2 input 3 active 5 0x0143
S54 Board 3 input 1 active 6 0x0143
S55 Board 3 input 2 active 7 0x0143
S56 Board 3 input 3 active 8 0x0143
S57 Board 4 input 1 active 9 0x0143
S58 Board 4 input 2 active 10 0x0143
S59 Board 4 input 3 active 11 0x0143
S60 12 0x0143
S61 13 0x0143
S62 14 0x0143
S63 15 0x0143
10 OPMSTAJB0810-GB_01
Page 11
STATYS
Jbus / Modbus serial link
8. 4. alarmS tableS: StartIng addreSS 0x0148, 2 wordS
CODE DESCRIPTION BIT ADDRESS Remarks
A00 Imminent stop 0 0x0148
A01 Output Isc detection 1 0x0148
A02 Manual By-Pass 2 0x0148
A03 Overload 3 0x0148
A04 4 0x0148
A05 Consecutive Detections 5 0x0148
A06 Switchback impossible 6 0x0148
A07 Transfer impossible 7 0x0148
A08 8 0x0148
A09 PowerPath1 deteriorated 9 0x0148
A10 PowerPath1 short circuit 10 0x0148
A11 PowerPath1 in failure 11 0x0148
A12 12 0x0148
A13 PowerPath2 deteriorated 13 0x0148
A14 PowerPath2 short circuit 14 0x0148
A15 PowerPath2 in failure 15 0x0148
A16 Backfeed1 protection open 0 0x0149
A17 Backfeed2 protection open 1 0x0149
ENGLISH
A18 Ambient temperature max 2 0x0149
A19 3 0x0149
A20 Insucient resources 4 0x0149
A21 5 0x0149
A22 6 0x0149
A23 7 0x0149
A24 8 0x0149
A25 Preventive Alarm 9 0x0149
A26 Conguration Alarm 10 0x0149
A27 HMI Alarm 11 0x0149
A28 Electronics 12 0x0149
A29 Custom input Alarm 13 0x0149
A30 Maintenance Alarm 14 0x0149
A31 General Alarm 15 0x0149
OPMSTAJB0810-GB_01 11
Page 12
STATYS
Jbus / Modbus serial link
8. 5. meaSurementS tableS: StartIng addreSS 0x0220, 64 wordS
CODE DESCRIPTION Unit ADDRESS Remarks
M00 S1 voltage L1N
M01 S1 voltage L2N
M02 S1 voltage L3N
M03 S1 voltage U12
M04 S1 voltage U23
ITALIANOENGLISH
M05 S1 voltage U31
M06 S1 frequency
M07 SS1 temperature
M08 S2 voltage L1
M09 S2 voltage L2
M10 S2 voltage L3
M11 S2 voltage U12
M12 S2 voltage U23
M13 S2 voltage U31
M14 S2 frequency
V
V
V
V
V
V
Hz
°C
V
V
V
V
V
V
Hz
0x0220
0x0221
0x0222
0x0223
0x0224
0x0225
0x0226
0x0227
0x0228
0x0229
0x022A
0x022B
0x022C
0x022D
0x022E
M15 SS2 temperature
M16 Output voltage L1
M17 Output voltage L2
M18 Output voltage L3
M19 Output voltage U12
M20 Output voltage U23
M21 Output voltage U31
M22 Output frequency
M23 0x0237
M24 Output current I1
M25 Output current I2
M26 Output current I3
M27 Output current IN
M28 0x023C
M29 Output load rate
°C
V
V
V
V
V
V
Hz
A
A
A
A
%
0x022F
0x0230
0x0231
0x0232
0x0233
0x0234
0x0235
0x0236
0x0238
0x0239
0x023A
0x023B
0x023D
M30 0x023E
M31 S1-S2 phase shift
M32 Output Apparent P. L1
12 OPMSTAJB0810-GB_01
°
KVA
0x023F
0x0240
Page 13
STATYS
Jbus / Modbus serial link
CODE DESCRIPTION Unit ADDRESS Remarks
M33 Output Apparent P. L2
M34 Output Apparent P. L3
M35 Output Power factor L1 0x0243
M36 Output Power factor L2 0x0244
M37 Output Power factor L3 0x0245
M38 0x0246
M39 0x0247
M40 Output crest factor L1 0x0248
M41 Output crest factor L2 0x0249
M42 Output crest factor L3 0x024A
M43 Output crest factor N 0x024B
M44 0x024C
M45 0x024D
M46 0x024E
M47 Ambient temperature
KVA
KVA
°C
0x0241
0x0242
0x024F
ENGLISH
M48 Output Active Power L1
M49 Output Active Power L2
M50 Output Active Power L3
M51 Global Active Power
M52 0x0254
M53 0x0255
M54 0x0256
M55 0x0257
M56 Output load rate L1
M57 Output load rate L2
M58 Output load rate L3
M59 Output load rate N
M60 0x025C
M61 0x025D
M62 0x025E
KW
KW
KW
KW
%
%
%
%
0x0250
0x0251
0x0252
0x0253
0x0258
0x0259
0x025A
0x025B
M63 0x025F
OPMSTAJB0810-GB_01 13
Page 14
STATYS
Jbus / Modbus serial link
8. 6. permISSIonS tableS: StartIng addreSS 0x0150, 1 wordS
CODE DESCRIPTION BIT ADDRESS Remarks
P00 Close SSP 0 0x0150
P01 Close SSA 1 0x0150
P02 Close SS1 2 0x0150
P03 Close SS2 3 0x0150
P04 S1 is preferred source 4 0x0150
ITALIANOENGLISH
P05 S2 is preferred source 5 0x0150
P06 6 0x0150
P07 Lock transfer ext. 7 0x0150
P08 Unlock transfer ext. 8 0x0150
P09 9 0x0150
P10 Allows remote controls 10 0x0150
P11 Forbid remote controls 11 0x0150
P12 Trsf Asynchro Forced 12 0x0150
P13 Trsf OnFly Abort 13 0x0150
P14 14 0x0150
P15 Load o 15 0x0150
8. 7. commandS tableS: StartIng addreSS 0x0190, wrIte 1 wordS
To modify a parameter, write 1 in the corresponding bit.
CODE DESCRIPTION BIT to write ADDRESS Remarks
C00 Close SSP 0 0x0190
C01 Close SSA 1 0x0190
C02 Close SS1 2 0x0190
C03 Close SS2 3 0x0190
C04 S1 is preferred source 4 0x0190
C05 S2 is preferred source 5 0x0190
C06 6 0x0190
C07 Lock transfer ext. 7 0x0190
C08 Unlock transfer ext. 8 0x0190
C09 9 0x0190
C10 Allows remote controls 10 0x0190
C11 Forbid remote controls 11 0x0190
C12 Force Asynchro Trsf 12 0x0190
C13 Abort OnFly Trsf 13 0x0190
C14 14 0x0190
C15 Load o 15 0x0190
It is advised to modify only one parameter per request.
14 OPMSTAJB0810-GB_01
Page 15
Page 16
Socomec worldwide
IN EUROPE
BELGIUM
UPS / Power Control & Energy Efficiency/
Solar
Tel. +32 2 340 02 30 Fax +32 2 346 28 99 info.be@socomec.com
FRANCE
UPS / Power Control & Energy Efficiency/
Solar
Tel. +33 1 45 14 63 00 Fax +33 1 48 67 31 12 dcm.ups.fr@socomec.com
GERMANY
Power Control & Energy Efficiency
Tel. +49 7243 65292 0 Fax +49 7243 65292 13 info.scp.de@socomec.com
UPS
Tel. +49 621 71 68 40 Fax +49 621 71 68 444 info.ups.de@socomec.com
ITALY
Power Control & Energy Efficiency
Tel.+39 02 98 49 821 Fax +39 02 98 24 33 10 info.scp.it@socomec.com
Solar
Tel. +39 0444 598611 Fax +39 0444 598627 info.solar.it@socomec.com
UPS
Tel.+39 02 98 242 942 Fax +39 02 98 240 723 info.ups.it@socomec.com
NETHERLANDS
UPS / Power Control & Energy Efficiency/
Solar
Tel. +31 30 760 0900 Fax +31 30 637 2166 info.nl@socomec.com
POLAND
Power Control & Energy Efficiency
Tel. +48 91 442 64 11 Fax +48 91 442 64 19 info.scp.pl@socomec.com
UPS
Tel. +48 22 825 73 60 Fax. +48 22 825 73 60 info.ups.pl@socomec.com
PORTUGAL
UPS / Solar
Tel.+351 261 812 599 Fax +351 261 812 570 info.ups.pt@socomec.com
ROMANIA
UPS / Power Control & Energy Efficiency/
Solar
Tel. +40 21 319 36 88 Fax +40 21 319 36 89 info.ro@socomec.com
RUSSIA
UPS / Power Control & Energy Efficiency/
Solar
Tel. +7 495 775 19 85 Fax +7 495 775 19 85 info.ru@socomec.com
SLOVENIA
UPS / Power Control & Energy Efficiency/
Solar
Tel. +386 1 5807 860 Fax +386 1 561 11 73 info.si@socomec.com
SPAIN
UPS / Power Control & Energy Efficiency/
Solar
Tel. +34 93 540 75 75 Fax +34 93 540 75 76 info.es@socomec.com
UNITED KINGDOM
Power Control & Energy Efficiency
Tel. +44 1462 440 033 Fax +44 1462 431 143 info.scp.uk@socomec.com
UPS
Tel.+44 1285 863 300 Fax+44 1285 862 304 info.ups.uk@socomec.com
TURKEY
UPS / Power Control & Energy Efficiency/
Solar
Tel. +90 216 540 71 20-21-22 Fax +90 216 540 71 27 info.tr@socomec.com
IN ASIA PACIFIC
AUSTRALIA
UPS
Tel. +61 2 9325 3900 Fax +61 2 9888 9544 info.ups.au@socomec.com
CHINA
UPS / Power Control & Energy Efficiency
Tel. +86 21 52 98 95 55 Fax +86 21 62 28 34 68 info.cn@socomec.com
INDIA
Power Control & Energy Efficiency
Tel. +91 124 4027210 Fax +91 124 4562738 info.scp.in@socomec.com
UPS/ Solar
Tel. +91 44 39215400 Fax +91 44 39215450 & 51 info.ups.in@socomec.com info.solar.in@socomec.com
SINGAPORE
UPS / Power Control & Energy Efficiency
Tel.+65 6506 7600 Fax +65 64 58 7377 info.sg@socomec.com
THAILAND
UPS
Tel. +66 2 941 1644 7 Fax +66 2 941 1650 info.ups.th@socomec.com
VIETNAM
UPS
Tel. +84 8 3559 1220 Fax +84 8 3559 1221 info.ups.vn@socomec.com
IN MIDDLE EAST
UNITED ARAB EMIRATES
UPS / Power Control & Energy Efficiency/
Solar
Tel.+971 4 29 98 441 Fax +971 4 29 98 449 info.ae@socomec.com
IN AMERICA
USA, CANADA & MEXICO
Power Control & Energy Efficiency
Tel. +1 617 245 0447 Fax +1 617 245 0437 info.us@socomec.com
OTHER COUNTRIES
NORTH AFRICA
Algeria / Morocco / Tunisia
info.naf@socomec.com
AFRICA
Other countries
info.africa@socomec.com
SOUTH EUROPE
Cyprus / Greece / Israel / Malta
info.se@socomec.com
SOUTH AMERICA
Tel. +34 93 540 75 75 info.es@socomec.com
MORE DETAILS
www.socomec.com/worldwide
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 info.scp.isd@socomec.com
www.socomec.com
YOUR DISTRIBUTOR
Non contractual document. © 2013, Socomec SA. All rights reserved. - To help protect the environment, this document has been printed on PEFC paper (Programme for the Endorsement of Forest Certification).
Loading...