socomec RESYS P40 Operating Instructions Manual

SOCOMEC - Ref.: 541 613 B
RESYS 066 B
INSTALLATION
Installation must only be carried out by qualified per­sonnel.
Before installation, disconnect from the power supply. Connect the device as shown on the diagram below
between the relay and the differential toroid as short as possible.
Do not put relay cables or the differential toroid beside power conductors.
Do not place differential toroids close to sources of intense magnetic fields.
>
Note
This differential relay conforms to type A which trips sinusoidal alternating currents and pulsed currents, whether they are applied suddenly or change slowly. This product is also immune to interference.
This relay must be installed in accordance with the regulations currently in force.
The device must be checked periodically to see that it complies with the regulations.
>
Test Function
Bargraph blinks
“Trip” LED and “Alarm” relay activated
> Continuous monitoring
Test OK NO NO
Toroid input short circuit NO NO
Relay/Toroid connection break YES NO
> Activation of “Test” button
(Press (>1s) or external button)
Test OK YES YES
Toroid input short circuit NO NO
Relay/Toroid connection break YES NO
>
Pre-alarm function
When the measured current exceeds 50% of the thres­hold value, the pre-alarm relay changes state (if selec­ted in this mode). Automatic reset to its original state if 30% lower than pre-set threshold.
>
Description of front panel
1 - Adjustment/setting I∆n 2 - Green “ON” LED 3 - “RESET” button 4 - Red “TRIP” alarm LED
5 - LED bargraph (% x I∆n)
6 - Configuration DIP switch
(x 4) 7 - “TEST” push-button 8 - Time setting
• With I∆n set at 30 mA, the timing is set at 0 (instanta-
neous) and can not be modified.
• The pre-configured factory setting for the device is 30
mA/0s. These values can be modified as needed for operation. A plastic seal is provided with the device in order to lock the protective cover and ensure the settings.
RESYS P40
EN
Operating instructions
Earth leakage relay A and AC types
>
Configuration (DIP switch)
Switch Relay configuration
A B AL1 AL2
0 0 Positive security Positive security
1 0 Negative security Pre-alarm (neg. security)
0 1 Negative security* Positive security*
1 1 Negative security Pre-alarm (pos. security)
C Storage mode
1 Automatic reset
0 Storage mode*
D Toroidal transformer ratio
1 600 : 1 > Socomec* toroid
0 1000 : 1 > other manufacturers
* factory configuration
• (negative security: relay excited in case of alarm/positive secu-
rity: relay not excited in case of alarm).
TERMINAL CONNECTION DIAGRAM
L1 L2 L3 N
E
Toroid
50 m* maxi
Alarm 2 (AL2)
or pre-alarm
Alarm 1
(AL1)
678910 11 12
12345
A2
(-)
A1 (+)
reset
test
50 m maxi
The output relays are shown in the non-excited state (for example, as if the auxiliary supply was not present)
The protective earth wire must not pass through the toroid. For single-phase applications, only the phase and the neutral must pass through the toroid.
* Cabling: For distances > 1 m, use a twisted pair for connection between the relay and the toroid.
>
Troubleshooting
If the product is not working properly, check that is it properly connected.
DIMENSIONS
4898022
48
32
TECHNICAL SPECIFICATION
• Us Supply (6, 7) :
12 - 125 VDC (85 - 110% de Us) 115, 230 VAC (85 - 115% de Us) (see terminal connection
diagram). All AC supplies are galvanically isolated frm toroid, TEST and RESET inputs.
• Frequency : 50/ 60Hz (AC supply)
• Isolation : Over-voltage cat. III
• Impulse voltage:
(1,2/ 50µS) IEC 60664 2,5kV (115 VAC supply) 4kV (230 VAC supply)
• Consumption (max.) :
6VA (AC supply) - 5W (DC supply)
• Measured residual current:
0 to 30A (15/ 400Hz) via external toroid with ratio 600:1 or 1000: 1 connected to terminals 4 and 5)
• Sensitivity In :
30, 100, 300, 500 mA, 1, 3, 5, 10, 30 A (adjustable)
• Tripping accuracy: 80 - 90% de I∆n
• Reset value: ≈85% of trip threshold
• Time delay Is : 0*, 60, 150, 300, 500, 800ms, 1, 4, 10s
(adjustable) *time set for “0” or “Instantaneous” < 25 ms
for residual current @ 5 x I∆n.
• Reset time:
<2 s (after eliminating the auxiliary power supply)
• Indication des Leds :
- Power supply present:: green
- Bargraph :
3 x green (30, 50 and 70% of the threshold value set)
- Tripping: red
• Operating temperature: -20 to +55°C
• Storage temperature: -30 to +70°C
• Relative humidity: +95%
Outputs
- Number of contacts:: 1 changeover contact relay + 1 single contact relay
- Type of contact :Alarm 1 (8, 9, 10)
AC1 (250 V) 8 A (2000 VA) AC15 (250 V) 2,5 A DC1 (25 V) 8 A (200W) Alarm 2/Pre-alarm (11, 12) AC1 (250 V) 6 A (1500 VA) AC15 (250 V) 4 A
DC1 (25 V) 6 A (150W)
- Lifetime: 150.000 operations at nominal load
- Dielectric voltage: 2kV AC (rms) IEC 60947-1
- Impulse voltage: 4kV (1,2/ 50µS) IEC 60664
• Remote Test and Reset (1, 2, 3) :
With N.O. contact (e.g. push-button)Min. contact closure
time: ≥80ms
• Box : black, self-extinguishable, NORYL UL94 VO (front
panel and clip in ABS)
• Weight: 120 g (DC auxiliary power supply)/ 200g (AC
auxiliary power supply)
• Installation: encastré, cut-out 45 x 45mm
• Connecting terminal:
≤ 2,5mm2 flexible
• Certification:
confor ms to IEC 60755, 60947, 61000-4-2, 6100 0-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-12, 61000-4­16, 61543. CE compliant.
>
 References :
Auxiliary power supply Reference 12-125 VDC 4942 3602 115 VAC 4942 3711 230 VAC 4942 3723
>Accessories
Toroids (C.T.) : ∆IC - Ø 15 mm 4950 6015 ∆IC - Ø 30 mm 4950 6030 ∆IC - Ø 50 mm 4950 6050 ∆IC - Ø 80 mm 4950 6080 ∆IC - Ø 120 mm 4950 6120 ∆IC - Ø 200 mm 4950 6200 ∆IC - Ø 300 mm 4950 6300
Use of toroids ≥ 120 mm: setting I∆n min = 300 mA Other toroids: consult us
CUTOUT
45
45
Loading...