socomec RESYS M40 Operating Instructions Manual

SOCOMEC - Ref. : 541 612 B
INSTALLATION
Installation must only be carried out by qualified per­sonnel.
Before installation, disconnect from the power supply. Connect the device as shown on the diagram below
(N.B. some optional functions do not need to be cabled). When installing the device, make the connections
between the relay and the differential toroid as short as possible.
Do not put relay cables or the differential toroid beside power conductors.
Do not place differential toroids close to sources of intense magnetic fields.
>Note
This differential relay conforms to type A which trips sinusoidal alternating currents and pulsed currents, whether they are applied suddenly or change slowly. This product is also immune to interference.
This relay must be installed in accordance with the regulations currently in force.
The device must be checked periodically to see that it complies with the regulations.
>
Test Function
Bargraph blinks
“Trip” LED and “Alarm” relay activated
> Continuous monitoring
Test OK NO NO
Toroid input short circuit NO NO
Relay/Toroid connection break YES NO
> Activation of “Test” button
(Press (>1s) or external button)
Test OK YES YES
Toroid input short circuit NO NO
Relay/Toroid connection break YES NO
>
Pre-alarm function
When the measured current exceeds 50% of the thres­hold value, the pre-alarm relay changes state (if selec­ted in this mode). Automatic reset to its original state if 30% lower than pre-set threshold.
>
Description of front panel
1 - Adjustment/setting I∆n 2 - Green “ON” LED 3 - “RESET” button 4 - Red “TRIP” alarm LED 5 - LED bargraph (% x In) 6 - Configuration DIP switch
(x 4) 7 - “TEST” push-button 8 - Time setting
• With In set at 30 mA, the timing is set at 0 (instanta­neous) and can not be modified.
• The pre-configured factory setting for the device is 30
mA/0s. These values can be modified as needed for operation. A plastic seal is provided with the device in order to lock the protective cover and ensure the settings.
RESYS M40
EN
Operating instructions
Earth leakage relay A and AC types
>
Configuration (DIP switch)
Switch SwitchRelay configuration
A B AL1 AL2
0 0 Positive security Positive security
1 0 Negative security Pre-alarm (neg. security)
0 1 Negative security* Positive security*
1 1 Negative security Pre-alarm (pos. security)
C Storage mode
1 Automatic reset
0 Storage mode*
D Toroidal transformer ratio
1 600 : 1 > Socomec* toroid
0 1000 : 1 > other manufacturers
* factory configuration
• (negative security: relay excited in case of alarm/positive secu­rity: relay not excited in case of alarm).
TERMINAL CONNECTION DIAGRAM
1 2 3 4 5 6 7
12-125 VDC
230 VAC*
400 VAC
115 VAC* Only
L1 L2 L3
N
PE
A1 (+)
A3
A2 (-)
Alarm 2 (AL2)
or Pre-alarm
Alarm 1
(AL1)
Toroid
reset
test
50m maxi
0
8 9 10 11 12 13 14
50m** maxi
* Dual voltage supply only available on 115/230 VAC model. For Us = 115VAC, connect the supply to terminals 6 and 7. For the other supply options, cable between 5 and 7.
The output relays are shown in the non-excited state (for example, as if the auxiliary supply was not present)
The protective earth wire must not pass through the toroid. For single-phase applications, only the phase and the neutral must pass through the toroid.
** Cabling: For distances > 1 m, use a twisted pair for connection between the relay and the toroid.
>
Troubleshooting
If the product is not working properly, check that is it properly connected.
DIMENSIONS
63.5 mm44 mm
49.5 mm
30 mm
45 mm
61 mm
85 mm
TECHNICAL SPECIFICATIONS
• Us supply (5, 6, 7):
12 - 125VDC (85 – 110% de Us) 115/230, 400VAC (85 - 115% de Us) (see terminal
connection diagram). All AC supplies are galvanically isolated frm toroid, TEST and RESET inputs.
• Frequency: 50/60Hz (AC supply)
• Isolation : Over-voltage cat. III
• Impulse voltage:
2,5kV (115 V AC supply) (1,2kV/ 50µs) IEC 60664 4kV (230 and 400VAC supply)
• Consumption (max.) :
6VA (AC supply) - 5W (DC supply)
• Measured residual current: 0 to 30A (15-400 Hz) (via external toroid with ratio 600:1 or 1000: 1 connected to terminals 8 and 9)
• Sensitivity In :
30, 100, 300, 500 mA, 1, 3, 5, 10, 30 A (adjustable)
• Tripping accuracy: 80 - 90% of In
• Reset value: ≈ 85% of trip threshold
• Time delay Is : 0*, 60, 150, 300, 500, 800ms, 1, 4, 10s
(adjustable) *time set for “0” or “Instantaneous” < 25 ms for residual current @ 5 x In.
• Reset time: < 2s (after eliminating the auxiliary power
supply)
• Indication des Leds :
- Power supply present: green
- Bargraph : 3 green (30, 50 and 70% of the threshold
value set)
- Tripping: red
• Operating temperature: -20 to +55° C
• Storage temperature: -30 to +70° C
• Relative humidity: +95%
Outputs
- Number of contacts: 1 changeover contact relay + 1 single contact relay
- Type of contact :
Alarm 1 (12,13,14)
AC1 (250V) 8 A (2000VA) AC15 (250V) 2,5A DC1 (25V) 8 A (200W)
Alarm 2 / Pre-alarm (10,11)
AC1 (250V) 6A (1500VA) AC15 (250V) 4A DC1 (25V) 6A (150W)
- Lifetime: 150 000 operations at nominal load
- Dielectric voltage: 2kV AC (rms) IEC 60947-1
- Impulse voltage: 4kV (1,2kV/ 50µs) IEC 60664
• Remote Test and Reset (1, 2, 3) :
With N.O. contact (e.g. push-button) Min. contact closure time: 80ms
• Box : grey, self-extinguishable, Lexan UL94 VO
• Weight: ≈ 190 g (AC) / ≈ 110 g (DC)
• Mounting: on 35 mm symmetrical DIN rail
(BS5584:1978-EN50 002 - DIN 46277-3)
• Connecting terminal:
2,5mm2 flexible, ≤ 4mm2 rigid
• Certification: conforms to IEC 60755, 60947, 61543, 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-12, 61000-4-16. CE compliant.
>
References :
Auxiliary power supply: Reference 12-125 VDC 4941 3602 115/230 VAC 4941 3723 400 VAC 4941 3740
>Accessories
Toroids (C.T.) : IC - Ø 15 mm 4950 6015 IC - Ø 30 mm 4950 6030 IC - Ø 50 mm 4950 6050 IC - Ø 80 mm 4950 6080 IC - Ø 120 mm 4950 6120 IC - Ø 200 mm 4950 6200 IC - Ø 300 mm 4950 6300
Use of toroids ≥ 120 mm: setting I∆n min = 300 mA Other toroids: consult us
RESYS 058 B
Loading...