- Ref.: IOMNETRTXX03-XX 02
IMPORTANT
WARNING!
This product is an accessory of the NETYS RT UPS and it can only be used in conjunction with the NETYS RT range.
• For installation and use of this accessory, please REFER To ThE UPS InSTAllATIon mAnUAl
• Please read the safety instructions carefully in the UPS manual before attempting to activate the product in any way
• The warranty conditions are also set out in the UPS installation manual
• Read this instruction carefully
• All cautions and warnings should be followed
• The incoming mains utility supply must be installed near the equipment and must be easily accessible
• The equipment must be used at a maximum 40 °C ambient temperature
• To avoid the risk of electrical shock DO NOT open the equipment
• The equipment has to be positioned to avoid objects falling or liquids dripping through the openings. This could cause a fire or eletrical shock
• Do not block any ventilation openings, they prevent the equipment from over-heating
• If the equipment is not used for a long period of time, disconnect the equipment from the power supply to avoid damage from any voltage peaks or lightning strikes
• An approved power cord greater or equal to H05VV-F, 1.0 mm
2
must be used
Option available for NETYS RT 1700 VA, 2200 VA and 3000 VA only.
• The battery charger has to be set up depending on the total number and capacity of the NETYS RT external battery modules (EBM) to be used
• Suggested set up value: ~10÷15% of the capacity (Ah)
WARNING!
To avoid damaging the batteries, due to a high recharging current, the minimum usable battery capacity is 40 Ah
• To size the battery charger correctly please refer to the NETYS RT external battery module (EBM) specifications
• In case of specific battery cabinets used instead of the NETYS RT external battery modules (EBM) , it is necessary to use the suitable connecting cable, available as an option. To display the correct autonomy value, the number of Ah has to be set via RT Battery Configurator software “STEP 4) Select the external battery Ah”.
• Set the switch on the back of the battery extension module to the ON posi­tion.
exTeRNAl bATTeRy chARgeR. NRT-OP-bch48V - NRT-OP-bch72V
166 DRWNETRT-GB
Page 3
3
- Ref.: IOMNETRTXX03-XX 02
ITALIANOENGLISH
ExTErNAL bATTEry cHArGEr. NrT-OP-bcH48V - NrT-OP-bcH72V
Battery charger Model NRT-OP-BCH48V NRT-OP-BCH72V
Compatible with UPS model NRT-U1700 nRT-U2200 nRT-U3000
Input Single-phase 230 V AC (100-250 V); 50/60 Hz
Input current (max) 5.2 A 7.8 A
Input protection 10 A fuse
Output power Selectable: 220 W or 440 W Selectable: 330 W or 660 W
Output current Selectable: 4 A ±0,4 A or 8 A ±0,4 A
Output protection 20 A fuse
Output voltage 54,6 V DC ±1% 81,9 V DC ±1%
Dimension (WxDxH) 440 x 135 x 88 mm
Weight 3,18 kg 3,28 kg
WARNING!
The input to the battery charger should be connected to mains or utility supply not to the UPS output.
Battery extension socket
IN 230 V~
Output current selector (4 A - 8A)
Status LED
- green: normal
- red: fault
148 DRWNETRT-XX
IN
OUT
LOAD 1 LOAD 2
RS232
BREAKER
INPUT
EPO
SURGE PROTECT
LOAD 3
INPUT
40A
48V
COM. SLOT
UPSEBM EBMBattery charger
149 DRWNETRT-XX
Page 4
4
- Ref.: IOMNETRTXX03-XX 02
4
• This instruction sheet completes the Installation and Operating manuals of the UPS
• The battery charger has to be set up depending on the total number and capacity of the NETYS RT external battery modules (EBM) to be used
• Suggested set up value: ~10÷15% of the capacity (Ah)
WARNING!
To avoid damaging the batteries, due to a high recharging current, the minimum usable battery capacity is 40 Ah
• To size the battery charger correctly please refer to the NETYS RT external battery module (EBM) specifications
• In case of specific battery cabinets used instead of the NETYS RT external battery modules (EBM), it is necessary to use the suit­able connecting cable, available as an option
• Technical specifications: please refer to the the Installation and Operating manual - see the specifications of the standard UPS with the same power except for what follows
UPS model NRT-U7000CLA NRT-U11000CLA
Power (UPS protection) 7000 VA
4900 W
11000 VA
8000 W
Battery recharging current 8 A
Dimensions (LxPxH) 440 x 670.5 x 88.7 mm 440 x 623 x 130.6 mm
Weight 16 kg 20.5 kg
UPS wITh POweRFUll bATTeRy chARgeR. NRT-U7000clA - NRT-U11000clA
lEVEl 1 lEVEl 2 lEVEl 3
BATTERY SETTING BATT LOW ALARM 20%
SHUTDOWN VOLTAGE SD VOLT:168VDC
DISCHARGE TEST no TEST
30 DAYS
60 DAYS
90 DAYS
BATT CABINET NUM NUM: 0
BATTERY AH BATTERY: ... Ah
Page 5
5
- Ref.: IOMNETRTXX03-XX 02
ENGLISH
Parallel redundant operation for business continuity
To achieve the highest level of availability and to power mission critical loads, NETYS RT UPS modules above 3 kVA can be config­ured for 1:1 redundancy.
Redundant operation (1+1) means: the system incorporates one more UPS module than is needed to protect the load; in the unlikely event of one module failure, it guarantees sufficient power supply capacity to the load by maintaining online protection.
Parallel technology is based on the principle of load sharing, whereby both units are always kept active.
by-PASS OF cONNecTION FOR UPS IN PARAllel
Connection of BY-PASS for UPS in parallel
+
CAUTION:
CONNECTOR
192Vdc
BATTERY
BREAKER 300VDC 50A
+
CAUTION:
CONNECTOR
192Vdc
BATTERY
BREAKER 300VDC 50A
COM. SLOT
EPO
PA EL
RS232
MINI COM. SLOT
OUTPUT
N
L
L
I
INPUT
BREAKER
230Vac
40A
230Vac
50/60Hz
230
CABLE UNDER LO
DO NOT DISCON
192Vdc 21.5A(5KVA)/30A(7KVA)
EXTERNAL BATTERY CONNECTOR
CAUTION:
SW
100
Network
10
+
CAUTION:
CONNECTOR
192Vdc
BATTERY
BREAKER 300VDC 50A
+
CAUTION:
CONNECTOR
192Vdc
BATTERY
BREAKER 300VDC 50A
COM. SLOT
EPO
PA EL
RS232
MINI COM. SLOT
OUTPUT
N
L
L
INP
INPUT
BREAKER
230Vac
40A
230Vac
50/60Hz
230Vac
CABLE UNDER LO
DO NOT DISCONN
192Vdc 21.5A(5KVA)/30A(7KVA)
EXTERNAL BATTERY CONNECTOR
CAUTION:
SW
100
Network
10
NL N
UPS1 BREAKER
230Vac 63A
INPUT OUTPUT
UPS2 BREAKER
230Vac 63A
INPUT OUTPUT
BYPASS BREAKER
230Vac 63A
TO UP S1
PARALLEL P LLEL
LN
L N
TO UPS1
230Vac
50/60Hz
TO UPS1 OUTPUT
L N
TO UPS2
230Vac
50/60Hz
TO UPS1 INPUT
TO UPS2 OUTPUT
AC INPUT 230Vac 50/60 Hz
UPS OUTPUT
LINE BREAKER
230Vac 63A
AC INPUT 230Vac 50/60 Hz
104 DRWNETRT-XX
Page 6
6
- Ref.: IOMNETRTXX03-XX 02
6
2
Close switches
Cin, C
out
, Din, D
out
3
Switch on both UPSs.
Close switch B
4
Load supplied by UPS
in parallel/redundant conguration
1
Close the MAINS
switch
Start-up.
by-PASS cONNEcTION OF UPS IN PArALLEL.
AC INPUT 230Vac 50/60Hz
L N
UPS OUTPUT
LINE BREAKER
230Vac 63A
UPS1 BREAKER
230Vac 63A
INPUT OUTPUT
UPS2 BREAKER
230Vac 63A
INPUT OUTPUT
BYPASS BREAKER
230Vac 63A
TO UPS1
LN
L N
TO UPS1
230Vac
50/60Hz
TO UPS1 OUTPUT
L N
TO UPS2
230Vac
50/60Hz
TO UPS1 INPUT
TO UPS2 OUTPUT
AC OUTPUT 230Vac 50/60Hz
LN
TO UPS2 INPUT
PARALLEL
TO UPS2
PARALLEL
L N
155 DRWNETRT-XX
B
A
D
in
C
out
C
in
D
out
Legend
A BY-PASS switch
B UPS OUTPUT Line breaker
Cin UPS1 INPUT switch
Cout UPS1 OUTPUT switch
Din UPS2 INPUT switch
Dout UPS2 OUTPUT switch
154 DRWNETRT-XX
C
in
C
out
D
in
D
out
A
B
UPS1 UPS2
C
in
C
out
D
in
D
out
UPS1 UPS2
UPS1
LOAD
UPS2
UPS1 UPS2
B
156 DRWNETRT-XX
151 DRWNETRT-XX
157 DRWNETRT-XX
LOAD
MAINS
LOAD
MAINS
LOAD
MAINS
Page 7
7
- Ref.: IOMNETRTXX03-XX 02
ENGLISH
2
Close switches
Cin, C
out
, Din, D
out
1
Load supplied by UPS
in parallel/redundant conguration
4
Load supplied by UPS
in parallel/redundant conguration
MAINTENANCE BY-PASS mode.
Back to NORMAL mode.
C
in
C
out
D
in
D
out
UPS1 UPS2
by-PASS cONNEcTION OF UPS IN PArALLEL.
UPS1
LOAD
UPS2
UPS1 UPS2
B
163 DRWNETRT-XX
151 DRWNETRT-XX
157 DRWNETRT-XX
2
Switch of both UPSs
by pressing OFF button. Close switch A
3
Close switch B.
Open switch A.
Switch on both UPSs
3
Open switches
B, Cin, C
out
, Din, D
out
4
Load supplied through
by-pass. Maintenance in progress
1
161 DRWNETRT-XX
162 DRWNETRT-XX
162 DRWNETRT-XX
UPS1
UPS1
UPS1 UPS1
UPS1
UPS2
UPS2
UPS2 UPS2
UPS2
A
B
160 DRWNETRT-XX
164 DRWNETRT-XX
LOAD
MAINS MAINS
MAINS
MAINS MAINS
MAINS
LOAD
MAINS
LOAD
LOAD
LOAD LOAD
LOAD
C
in
C
out
D
in
D
out
A
B
Page 8
Non contractual document. © 2008, Socomec SA. All rights reserved.
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 11 102 300 € - R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 ups.benfeld.admin@socomec.com
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY Tel. +39 0444 598611 - Fax +39 0444 598622 info.it.ups@socomec.com
S A L E S , M A R K E T I N G A N D SERVICE MANAGEMENT
SOCOMEC UPS Paris
95, rue Pierre Grange F-94132 Fontenay-sous-Bois Cedex - FRANCE Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12 ups.paris.dcm@socomec.com
Socomec UPS worldwide
In EURoPE
BELGIUM
Schaatsstraat, 30 rue du Patinage B - 1190 Bruxelles Tel. +32 (0)2 340 02 34 Fax +32 (0)2 346 16 69 be.ups.sales@socomec.com
FRANCE
95, rue Pierre Grange F - 94132 Fontenay-sous-Bois Cedex Tel. +33 (0)1 45 14 63 90 Fax +33 (0)1 48 77 31 12 ups.paris.dcm@socomec.com
GERMANY
Heppenheimerstraße 57 D - 68309 Mannheim Tel. +49 (0) 621 71 68 40 Fax +49 (0) 621 71 68 44 4 de.ups.all@socomec.com
ITALY
Via Leone Tolstoi, 73 - Zivido 20098 San Giuliano Milanese (MI) Tel. +39 02 98 242 942 Fax +39 02 98 240 723 siconmi@socomec.com
NETHERLANDS
Bergveste 2F NL - 3992DE Houten Tel. +31 (0)30 63 71 504 Fax +31 (0)30 63 72 166 nl.ups.sales@socomec.com
POLAND
Nowowiejska St 21/25 00-665 Warszawa Tel. +48 (0)22 2345 223 Fax +48 (0)22 2345 223 ups.poland@socomec.com
PORTUGAL
Rua Moinho do Cuco Bloco A Lj. Dta. - Paz 2640-566 MAFRA Tel. +351 261 812 599 Fax +351 261 812 570 portugal@socomec.com
RUSSIA
Kutuzovsky pr. 13, 44-45 121248 - Moscow Tel. +7 495 775 19 85 Fax +7 495 775 19 85 ups.russia@socomec.com
SLOVENIA
Savlje 89 SI - 1000 Ljubljana Tel. +386 1 5807 860 Fax +386 1 5611 173 si.ups.info@socomec.com
SPAIN
C/Nord, 22 Pol. Ind. Buvisa E - 08329 Teià (Barcelona) Tel. +34 935 407 575 Fax +34 935 407 576 info@socomec-aron.com
UNITED KINGDOM
Units 7-9 Lakeside Business Park Broadway Lane - South Cerney Cirencester - GL7 5XL Tel. +44 (0)1285 863300 Fax +44 (0)1285 862304 uk.ups.sales@socomec.com
In ASIA
CHINA
No.1 Yuanda Road Haidian District, Beijing, 100097 Golden Resource Times Shopping Mall No. 1001 section B the 2nd issue of business building Tel. +86 10 8889 2202 Fax +86 10 8889 2150 socomec@socomec.com.cn
INDIA
B1, IInd Floor, Thiru-Vi-Ka-Industrial Estate Guindy Chennai – 600 032 Tel. +91 44 3921 5400 Fax +91 44 3921 5450 — 51 sales@socomec-ups.co.in
MALAYSIA
31 Jalan SS 25/41- Mayang Industrial Park 47301 Petaling Jaya.- Selangor, Malaysia Tel. +603 7804 1153 Fax +603 7803 8901 sales@cspm.com.my
SINGAPORE
31 Ubi Road 1, Aztech Building # 01-00 (Annex) - SG - Singapore 408694 Tel. +65 6745 7555 Fax +65 6458 7377 sg.ups.sales@socomec.com
THAILAND
No.9 Soi Vibhavadirangsit 42 Vibhavadirangsit Rd, Ladyao Chatujak Bangkok 10900 Tel. +66 2 941-1644-7 Fax. +66 2 941-1650 info@socomec-th.com
VIETNAM
539/23 Luy Ban Bich St., Phu Thanh Ward, Tan Phu Dist Ho Chi Minh City Tel. +84-839734.990 Fax +84-839735.088 info@socomec-vn.com
www.socomec.com
Valid for France Valid for Italy
*IOMNETRTXX03-XX 02*
IOMNETRTXX03-XX 02 10.2009
Loading...