Socomec Non-fusible disconnect switches standards Catalog Page

SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
AC non-fusible
disconnect switches
sircm_132_a
sircm_133_a
sircm_174_a
sircm_175_a
sircm_003_a
Toggle switch SIRCO M 3 x 80 A + 2 auxiliary contacts
Rotary switch SIRCO M 3 x 80 A
Rotary switch SIRCO M 3 x 80 A
Function
SIRCO M UL / CSA are compact and modular non-fusible disconnect switches. They make and break under all types of load conditions and provide safe isolation for any low voltage circuit, especially for machine control circuits.
General characteristics
• Positive break indication.
• Direct or external operation.
• Compact footprint.
• DIN-rail, base or door mounting.
• Wide range of accessories.
• Up to 8 pole or 4 pole MTS.
> Industrial control systems
The solution for
> UL 508 listed,
Guide NLRV, File E173959
> CSA C22.2§14,
class 3211-05, File 112964
> IEC 60947-3
Conformity to standards
(1)
*
(1) Product reference on request.
> Positive break indication > Direct or external operation > Compact footprint > DIN-rail or base mounting > Wide range of accessories > Up to 8 pole or 4 pole MTS
Strong points
14 General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
References
Rating (A)
No. of
poles
Toggle switch (direct handle
included)
Rotary switch Direct handle
External front and right side
handles
(4)
Shaft for
external handles
Switched
fourth pole
module
Auxiliary contacts
Terminal
shrouds
Door
mounting kit
16 A 3 P
2205 3000 2200 3000
Blue
2299 5012
S00 type
I - 0
Black
3R, 12
(1)
1473 1111
Red / Yellow
3R, 12
(1)
1474 1111
Black
4, 4X
(1)
147D 1111
Red / Yellow
4, 4X
(1)
147E 1111
S0 type
I - 0
Black
1, 3R, 12
(1)
1483 1111
Red / Yellow
1, 3R, 12
(1)
1484 1111
Black 4, 4X
(1)
148D 1111
Red / Yellow
4, 4X
(1)
148E 1111
S00 / S0 type
150 mm
5.9 in
1407 0515
200 mm
7.9 in
1407 0520
320 mm
12.6 in
1407 0532
(2)
1 P
2200 1000
M type
1 AC
NO + NC
2299 0001
1 AC 2 NC
2299 0011
1 P
2294 1005
(3)
3 P
2294 3005
(3)
2299 3409
20 A 3 P
2205 3001 2200 3001
1 P
2200 1001
25 A 3 P
2205 3002 2200 3002
1 P
2200 1002
32 A 3 P
2205 3003 2200 3003
1 P
2200 1003
40 A 3 P
2205 3004 2200 3004
1 P
2200 1004
63 A 3 P
2205 3006 2200 3006
1 P
2200 1006
1 P
2294 1009
(3)
3 P
2294 3009
(3)
80 A 3 P
2205 3008 2200 3008
1 P
2200 1008
100 A CD
3 P
2200 3009
1 P
2200 1009
Common accessories - more available on next pages. (1) Nema / UL type. (2) Please order the shaft guide: 1419 0000 with the shaft. (3) Top and bottom. (4) There is no door interlocking when the switch is fitted on the side of the enclosure.
UL 508 manual motor controller “Suitable as motor disconnect”
coff_368_a_1_cat
Function
Enclosed SIRCO M switches allow safe control and disconnection of any motor application.
General characteristics
• Grey enclosure with red handle.
• Equipped with a 3 pole SIRCO M UL 508.
• 1 removable ground terminal.
• Possibility of adding 1 power pole
and 1 auxiliary contact.
• Nema / UL type 1, 3R, 12, 4, 4X.
UL 508 non-metallic polycarbonate 4, 4X enclosed SIRCO M
> UL 508,
Guide NLRV, file E173959
> CSA C22.2#14,
Class 3211-05, file 112964
> IEC 60947-3
Conformity to standards
(1)
(1) Product reference on request.
15General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
Shafts for external handle
acces_280_a_2_cat
Use
Standard lengths:
- 5.9 in / 150 mm
- 7.87 in / 200 mm
- 12.59 in / 320 mm Other lengths: please consult us.
For 3 / 4 pole switches, shaft extensions for external front and side handle.
For 6 / 8 pole switches and SIRCO M transfer switches.
Direct operation handle
acces_277_a_2_cat
Rating (A) Handle color Handle type Reference
16 … 100 CD Blue M00
2299 5012
Accessories
Ratg (A) Handle type
Length
Reference (in) (mm)
16 … 100 CD S00/S0 5.9 150
1407 0515
16 … 100 CD S00/S0 7.9 200
1407 0520
16 … 100 CD S00/S0 12.6 320
1407 0532
16 … 100 CD S01 7.9 200
1404 0520
16 … 100 CD S01 12.6 320
1404 0532
16 … 100 CD S01 15.7 400
1404 0540
For 3 / 4 pole
Rating (A) Handle type
Length
Reference (in) (mm)
16 … 100 CD S00/S0 5.9 150
1407 0515
16 … 100 CD S00/S0 7.9 200
1407 0520
16 … 100 CD S00/S0 12.6 320
1407 0532
For 6 / 8 pole
M00 handle
acces_279_a_2_catacces_304_a_2_cat
S0 handle
S01 handle
acces_264_a_2_cat
S00 handle
External operation handle
Use
The handle locking function prevents the user from opening the door of the enclosure when the switch is in the “ON” position (only if the handle is fitted on the door).
No interlock in the “OFF” position for S00 and S0 handles.
Opening the door when the switch is in the “ON” position is possible by defeating the interlocking function with the use of a tool (authorized persons only). The interlocking function is restored when the door is closed.
The handle is padlockable with 3padlocks.
Rating (A) Handle color Handle type Nema / UL type Reference
16 … 100 CD Black S00 3R, 12
1473 1111
16 … 100 CD Red / Yellow S00 3R, 12
1474 1111
16 … 100 CD Black S00 4, 4X
147D 1111
16 … 100 CD Red / Yellow S00 4, 4X
147E 1111
16 … 100 CD Black S0 1, 3R, 12
1483 1111
16 … 100 CD Red / Yellow S0 1, 3R, 12
1484 1111
16 … 100 CD Black S0 4, 4X
148D 1111
16 … 100 CD Red / Yellow S0 4, 4X
148E 1111
16 … 100 CD Black S01
(1)
3R, 12
140F 2111
16 … 100 CD Red / Yellow S01
(1)
3R, 12
140G 2111
16 … 100 CD Black S01
(1)
4, 4X
140D 2111
16 … 100 CD Red / Yellow S01
(1)
4, 4X
140E 2111
Front and right side handles I - 0
Rating (A) Handle color Handle type Nema / UL type Reference
16 … 100 CD Black S00 IP65
1473 1113
(1)
Front handle for transfer switches I - 0 - II
(1) Not compatible with door mounting kit.
Rating (A) Handle color Handle type Nema / UL type Reference
16 … 100 CD Black S01
(1)
4, 4X
140D 2911
16 … 100 CD Red / Yellow S01
(1)
4, 4X
140E 2911
Front handle for heavy duty I - 0 with metallic lever
(1) Not UL.
(1) Not UL.
16 General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
Terminal shrouds
sircm_049_a_1_cat
Use
Top and bottom additional protection against direct contact with the terminals or connection parts.
1 or 3pole are available.
Perforation on each terminal cover enables remote thermographic inspection without dismantling.
Rating (A) No. of poles Position Reference
16 … 40 1 P top and bottom
2294 1005
16 … 40 3 P top and bottom
2294 3005
63 … 100 CD 1 P top and bottom
2294 1009
63 … 100 CD 3 P top and bottom
2294 3009
Shaft guide for external handle
acces_260_a_2_cat
Use
This accessory enables handle to engage extension shaft with a misalignment of up to 0.59 in/15 mm.
Required for a shaft lenght from 12.6 in/320 mm.
Handle type Reference
S00 and S0
1419 0000
Accessories (continued)
Additional pole
sircm_072_b_1_cat
4th pole
Use
Transforms:
- 3 pole SIRCO M non-fusible disconnect
switch into a 4pole,
- 3 pole SIRCO M transfer switch into a 4 pole.
Rating (A) No. of poles Type Reference
16 1 P switched
2200 1000
20 1 P switched
2200 1001
25 1 P switched
2200 1002
32 1 P switched
2200 1003
40 1 P switched
2200 1004
63 1 P switched
2200 1006
(1)
80 1 P switched
2200 1008
(1)
100 CD 1 P switched
2200 1009
(1)
(1) Not UL.
N or PE
N or PE
N or PE
N or PE
N or PE
N or PE
sircm_078_a_1_gb_cat
Solid neutral pole
Use
Transforms the 3-pole switch into a 3-pole + solid neutral.
Rating (A) No. of poles Type Reference
16 … 40 1 P unswitched
2200 5005
63 … 100 CD 1 P unswitched
2200 5009
Ground module
Use
Adds 1 protective ground module pole to the non-fusible disconnect switch.
Rating (A) No. of poles Type Reference
16 … 40 1 P unswitched
2200 9005
63 … 100 CD 1 P unswitched
2200 9009
17General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
Conversion kit
sircm_086_b_1_cat sircm_097_b_2_x_cat
Conversion kit for 3 and 4-pole transfer switches (I - 0 - II) or (I - I+II - II)
sircm_050_c_2_cat
Conversion kit for 6 or 8 pole non-fusible disconnect switches
Use
These accessories enable the assembly of 2 switches in order to achieve:
- 6 or 8 pole switches
- 3 or 4 pole open or close transition transfer switches.
Rating (A) Type Reference
16 … 100 CD Non-fusible disconnect switches 6 / 8 pole
2269 6009
16 … 100 CD Transfer switch 3 / 4 pole (I - 0 - II)
2209 6009
16 ... 100 CD Transfer switch 3/4 pole (I - I+II - II)
2299 6009
sircm_051_b_2_cat
Door mounting kit
Use
This kit enables direct mounting of the switch on the panel door or on the right or left side of the panel with S00 and S0 handles.
The S0 and S00 external handles are quick and easy to install due to an internal locking nut mounted on the inside of the enclosure.
Rating (A) No. of poles Reference
16 … 100 CD 3 / 4 P
2299 3409
Rating (A) No. of AC AC type Reference
16 … 100 CD 1 AC NO + NC
2299 0001
16 … 100 CD 1 AC 2 NO
2299 0011
M type Auxiliary Contacts
sircm_081_a_1_x_cat sircm_075_b_2_cat
Use
Pre-break and signaling of positions 0 and I by NO+NC or 2 NO Auxiliary Contacts.
They can be mounted on the left or on the right side of the device.
Max 4 Auxiliary Contacts per product (2 modules).
Characteristics
A300.
Auxiliary contacts configurations for SIRCO M
Not compatible with S01 handle. No need of external shaft.
18 General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
Characteristics according to UL 508 / CSA22.2#14 suitable as motor disconnect
Characteristics
General use rating (A) 16 A 20 A 25 A 32 A 40 A 63 A 80 A 100 A CD
Short circuit rating at 600 VAC (kA) 65 65 65 65 10 / 65 50 / 65 50 / 65 50/65
Type of fuse J J J J J J J J
Max fuse rating (A) 30 30 30 30 60 / 30 100 / 60 100 / 60 100/60
Max. motor hp / FLA 3 ph motor max.
208 VAC 3 / 0.6 5 / 16.7 7.5 / 24.2 7.5 / 24.2 7.5 / 24.2 15 / 46.2 15 / 46.2 15/46.2
220-240 VAC 5 / 15.2 5 / 15.2 7.5 / 22 7.5 / 22 7.5 / 22 20 / 54 20 / 54 20/54
440-480 VAC 10 / 14 10 / 14 15 / 21 20 / 27 20 / 27 40 / 52 40 / 52 40/52
600 VAC 10 / 11 15 / 17 20 / 22 25 / 27 25 / 27 40 / 41 40 / 41 40/41
Connection terminals
Solid - 1 wire #14 - #10 #14 - #10 #14 - #10 #14 - #10 #14 - #10 #14 - #10 #14 - #10 #14 - #10
Solid - 2 wires 2 x #12 2 x #12 2 x #12 2 x #12 2 x #12 2 x #12 2x #12 2x #12
Stranded - 1 wire #14 - #4 #14 - #4 #14 - #4 #14 - #4 #14 - #4 #14 - #1 #14 - #1 #14 - #1
Stranded - 2 wires 2 x (#14 - #12) 2 x (#14 - #12) 2 x (#14 - #12) 2 x (#14 - #12) 2 x (#14 - #12) 2 x (#10 - #6) 2 x (#10 - #6) 2 x (#10 - #6)
Auxiliary contacts
Electrical characteristics A300 A300 A300 A300 A300 A300 A300 A300
Mechanical characteristics
Endurance (number of operating cycles) 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10000
Operating torque (lbs.in / Nm) 7 / 0.8 7 / 0.8 7 / 0.8 7 / 0.8 7 / 0.8 8.9 / 1 8.9 / 1 8.9/1
Thermal current Ith (40°C) 16 A 20 A 25 A 32 A 40 A 63 A 80 A 100 A CD
Rated insulation voltage U
i
(V) 800 800 800 800 800 800 800 800
Rated impulse withstand voltage U
imp
(kV) 8 8 8 8 8 8 8 8
Rated operational currents Ie (A)
Rated voltage Utilization A / B
(1)
A / B
(1)
A / B
(1)
A / B
(1)
A / B
(1)
A / B
(1)
A / B
(1)
A / B
(1)
415 VAC AC-23 A / AC-23 B 16 / 16 20 / 20 25 / 25 32 / 32 40 / 40 63 / 63 80 / 80 80/80
500 VAC AC-22 A / AC-22 B 16 / 16 20 / 20 25 / 25 32 / 32 40 / 40 63 / 63 80 / 80 -
500 VAC AC-23 A / AC-23 B 16 / 16 20 / 20 25 / 25 25 / 25 25 / 25 63 / 63 63 / 63
690 VAC AC-21 A / AC-21 B 16 / 16 20 / 20 25 / 25 32 / 32 40 / 40 63 / 63 80 / 80 100/100
690 VAC AC-22 A / AC-22 B 16 / 16 20 / 20 25 / 25 32 / 32 32 / 40 40 / 63 63 / 80 -
690 VAC AC-23 A / AC-23 B 16 / 16 20 / 20 25 / 25 25 / 25 25 / 25 40 / 40 40 / 40 -
Operational power in AC-23 (kW)
At 400 VAC without prebreaking AC in AC-23 (kW)
(1)(2)
7.5 9 11 15 18.5 30 37 -
At 500 VAC without prebreaking AC in AC-23 (kW)
(1)(2)
7.5 9 11 15 15 30 37 -
At 690 VAC without prebreaking AC in AC-23 (kW)
(1)(2)
7.5 11 15 18.5 18.5 30 37 -
Fuse protected short-circuit withstand (kA rms prospective)
Prospective short-circuit current (kA rms)
(3)
50 50 50 50 50 50 50 25
Associated fuse rating (A)
(3)
16 20 25 32 40 63 80 100
Overload capacity (Ue 415 VAC)
Rated short-time withstand current 0.3 s. ICW (kA rms)
(3)
2.5 2.5 2.5 2.5 2.5 3 3 1.5
Rated short-circuit making capacity I
cm
(kA peak)
(3)
6 6 6 6 6 9 9 2.1
Connection
Minimum Cu cable cross section (mm²) 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5
Maximum Cu cable section (mm
2
) 16 16 16 16 16 35 35 35
Tightening torque min / max (Nm) 2 / 2.2 2 / 2.2 2 / 2.2 2 / 2.2 2 / 2.2 3.5 / 3.85 3.5 / 3.85 3.5/3.85
(1) A / B: Category with index A = frequent operation - Category with index B = infrequent operation. (2) The power value is given for information only, the current values vary from one manufacturer to another. (3) For a rated operating voltage U
e
= 400 VAC.
Characteristics according to IEC 60947-3
19General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
Toggle operation
90°
2.68
F
T
M5
M
N
G
AC
3.19
2.52
6
1.97
2.87
F1 0.35F10.35
2
1
2
1
68
50
0.24
8.88.8
81
73
64
sircm_052_b_1_gb_cat
1. Position for 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective ground module or 1 auxiliary contact.
2. Position for 1 auxiliary contact only. Note: Maximum of 4 additional blocks.
Direct operation with handle
2.67
F
T
M5
M
N
G
AC
2.52
0.24
1.97
2.95
F1F10.35
2
1
2
1
75
64
6
50
68
8.88.8
0.35
sircm_053_b_1_gb_cat
External front handle External side handle
J
2.68
F
T
M5
M
1.42D
N
G
AC
E1.42
3.19
2.52
0.23
1.96
1.99
F10.35 F1
ø 2.79
36
81
64
50.6
6
50
8.8
8.8
68
ø 71
36
0.35
80
1.61
44
BAC
45
25
1.77
0.98
41
3.15
1.73
2
2
1
1
sircm-ul_002_c_1_gb_cat
1. Position for 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 ground module or 1 auxiliary contact.
2. Position for 1 auxiliary contact only.
Note: Maximum of 4 additional blocks.
Rating (A) Units
Overall dimensions Terminal shrouds Switch body Switch mounting Connection
D min D max E min E max AC F F1 G J M N T
16 … 40
in 1.18 9.25 3.94 14.64 4.33 1.77 0.59 2.67 0.59 1.18 2.95 0.59
mm 30 235 100 372 110 45 15 68 15 30 75 15
63 … 100 CD
in 1.18 9.25 3.93 14.64 4.33 2.06 0.69 2.99 0.69 1.38 3.35 0.69
mm 30 235 100 372 110 52.5 17.5 76 17.5 35 85 17.5
Direct front handle for 6 / 8-pole non-fusible disconnect switches or 3 / 4-pole transfer switches
External front handle for 6 / 8-pole non-fusible disconnect switches or 3 / 4-pole transfer switches
1.42E
1.77
3.07
1.361.69
0.24
3.50
ø 2.79
X
N
G
2.67
TT
0.29
2.06
MF22.06
F
J
F1F10.35
2
1
2
1
89
78
43
34.7
6
36
ø 71
45
52.5
68
8.8
52.5
8.8
7.5
0.35
sircm_055_c_1_gb_cat
1. Position for 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 ground module or 1 auxiliary contact.
2. Position for 1 auxiliary contact only.
Note: Maximum of 4 additional blocks.
Rating (A) Units
Overall dimensions Switch body Switch mounting Connection
E min E max F F1 F2 G J M N T X
16 … 40
in 4.13 14.64 3.83 0.59 1.77 2.67 1.92 1.18 2.95 0.59 0.29
mm 105 372 97.5 15 45 68 48.75 30 75 15 7.5
63 … 100 CD
in 4.13 14.65 4.13 0.69 2.06 2.99 2.06 1.38 3.35 0.69 0.34
mm 105 372 105 17.5 52.5 76 52.5 35 85 17.5 8.75
Dimensions (in / mm)
1.42E
1.77
3.07
1.361.69
0.24
3.50
ø 2.79
89
78
43
34.7
6
36
ø 71
45
16 to 100 A
20 General Catalog UL/CSA Ed. 2
SIRCO M UL 508
Non-fusible disconnect switches standards UL and CSA
from 16 to 100 A
External handles dimensions (in / mm)
0
I
90°
0
I
90°
1.57 40
2 Ø 0.28 2 Ø 7
Ø 1.22
Ø 31
1.57
40
0.53
13.5
Ø 0.89
Ø 22.5
0.12 3
With fixing nut
With 4 fixing screws
S00 type
Direction of operation Direction of operation Door drillingHandle type
Front operation Side operation
Ø 3.07
1.42
2.79
Ø 78
36
71
poign_059_c_1_us_cat
16 to 100 A
0
I
90°
0
I
90°
1.57 40
2 Ø 0.28 2 Ø 7
Ø 1.22
Ø 31
1.57
40
0.53
13.5
Ø 0.89
Ø 22.5
0.12 3
With fixing nut
With 4 fixing screws
S0 type
Direction of operation Direction of operation Door drillingHandle type
Front operation Side operation
Ø 2.80 Ø 71
1.46 37
3.46
88
poign_060_a_1_us_cat
S00 type
Transfer switches
0
or
I+II
III
90°
90°
0.53
13.5
Ø 0.88 Ø
22.5
0.12 3
40
1.10 28
Ø 1.45
Ø 37
4 Ø 0.27 4 Ø 7
With fixing nutWith 4 fixing screws
Direction of operation Door drillingHandle type
Front operation
Ø 3.07
1.42
2.79
Ø 78
36
71
poign_070_a_1_gb_cat poign_018_a_1_gb_cat
S01 type
With 4 fixing screws
Direction of operation Direction of operation Door drillingHandle type
Front operation Side operation
0
I
90°
0
I
90°
1.57
40
1.10 28
Ø 1.46
Ø 37
4 Ø 7 4 Ø 0.28
3.15
80
1.61
41
1.73 44
Ø 3.07
Ø 78
21General Catalog UL/CSA Ed. 2
Loading...