socomec NETYS PL, NETYS PR MT, NETYS PE Installation And Operating Manual

NETYS PL
600-800 VA
安装及操作手册
CN
Installations- und bedienungsanleitung
DE
Manual de instalación y uso
Manuel d’installation et d’utilisation
FR
Installation and operating manual
GB
Manuale di installazione e uso
IT
Installatie– en bedieningshandleiding
NL
Dokumentacja Techniczno-Ruchowa
PL
Manual de instalação e funcionamento
PT
Manual de instalare şi utilizare
RO
Руководство по установке и эксплуатации
RU
Navodila za priključitev in uporabo
SI
Kurulum ve kullanım kılavuzu
TR
2
NETYS PL - Ref.: IOMNETPLXX01-GB 02
This SOCOMEC UPS appliance is guaranteed against manufacturing and material defects for a period of 12 months from the date of purchase (local warranty conditions are applicable in addition to the general conditions). This warranty certificate should NOT be e-mailed, but kept by the customer along with proof of purchase, for use in the event of a claim being made for repairs or replacement under warranty.
The warranty period commences on the date the new product was purchased by the end user at an authorised showroom (reference details are shown on the receipt).
Return-to-base warranty is provided: components and labour for repairs supplied free of charge, any products to be replaced must be returned to SOCOMEC UPS or authorised service centres, at the customer’s own risk and expense.
The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall be limited to the cover of the parts used to repair the fault.
To claim service under the warranty please observe the following:
The product must be returned in the original packing. Any damage caused during shipping in packaging other than the original
will not be covered by the warranty;
The product must be accompanied by proof of purchase such as an invoice or receipt indicating the date of purchase and
product ID information (model, serial numer). The sender must also attach the reference number issued to authorise the return of the product, together with a detailed description of the defect. If any of this information is missing the warranty will be invalid. The authorisation number is issued by service centres over the telephone on receiving information on the malfunction in question;
If it is not possible to provide proof of purchase the serial number and date of manufacture will be used to calculate the probable
expiry date of the warranty; this could result in a reduction of the original warranty period.
The warranty on the product does not cover damage caused by carelessness (improper use: wrong input power, explosions, excessive humidity, temperature, poor ventilation, etc.), tampering or any unauthorised repair work.
During the warranty period, SOCOMEC UPS reserves the right to decide whether the product should be repaired, or whether to replace defective parts with new parts, or used parts that are equivalent to new parts in terms of functionality and performance.
In the case of batteries, warranty is valid only if the battery has been recharged regularly in accordance with the manufacturer’s instructions. On purchasing the product it is advisable to check that the next recharge date indicated on the packaging has not expired.
Battery
• Batteries are treated as consumable parts and warranty only covers manufacturing defects.
• Batteries must be stored in compliance with Supplier recommendations.
• Warranty is valid only if the battery has been recharged regularly in accordance with the manufacturer’s instructions. On purchasing the product it is advisable to check that the next recharge date indicated on the packaging has not expired.
Optionals
A 12-month return-to-base warranty is provided on optionals.
Software products
Software products are guaranteed for 90 days. The software is guaranteed to work as indicated in the manual accompanying the product. Hardware media or accessories (e.g. diskettes, cables, etc.) used with appliances are guaranteed free of material or manufacturing defects under normal conditions of use for a period of 12 months from the date of purchase.
SOCOMEC UPS will not be responsible for damages (including loss of income, interruption of business activity, loss of information or other financial losses, of any nature) arising from the use of the product.
These conditions are subject to Italian law. Disputes shall come under the jurisdiction of Court of Vicenza.
WARRANTY CERTIFICATE AND CONDITIONS
SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All reproduction, modification, disse­mination of this document whether in part or whole and by any manner are expressly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without prior notice.
3
NETYS PL - Ref.: IOMNETPLXX01-GB 02
CONTENTS
ENGLISH
1. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1. IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2.
DESCRIPTION OF THE SYMBOLS USED ON LABELS ATTACHED TO THE UNIT
. 5
2. GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1. UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2. ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION . . . . . . . . . . . . . . . . 7
4. PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5. CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.1. SWITCHING THE UPS ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.2. SWITCHING THE UPS OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.3. NORMAL MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.4. BATTERY MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.5. OVERLOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7. COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.1. SOFTWARE OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8. SOLUTIONS TO MINOR PROBLEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.1. TROUBLESHOOTING FOR MINOR PROBLEMS . . . . . . . . . . . . . . . . . . . . . . 12
9. TECHNICAL SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4
NETYS PL - Ref.: IOMNETPLXX01-GB 02
1.1. IMPORTANT
This manual should be kept carefully in a safe place near the UPS, so that it can be consulted by the operator at any time for any information that may be needed regarding correct use of the unit. Read the manual carefully before connecting the unit to the a.c. mains supply and to the downstream appliances. Before the UPS NETYS PL is put into commission, the user must be perfectly familiar with its operation, with the position of all the controls and with the technical and functional characteristics of the unit, so as to ensure there will be no risk to any persons or to the appliance itself.
Before being started up, the unit must be equipotentially bonded, in accordance with current safety regulations. The earth
wire of the UPS must then be connected to an efficient earth system.
If the earth connection is not made, the appliances connected to the UPS will not be equipotentially bonded. In this situation,
the manufacturer declines all liability for any damage or accidents that could derive from failure to observe the requirements.
Should a power outage occur (UPS in stand-alone mode), do not disconnect the power cord from the mains, as this will
break the earth connection to bonded appliances.
All subsequent maintenance operations must be entrusted only to authorized service engineers. The UPS generates high internal voltages that could be hazardous for a maintenance operative not in possession of the appropriate skills and training for this type of work.
If a hazard situation should arise at any moment when the UPS is in use, isolate the unit from the power supply (by operating
a switch at the upstream PDU if possible) and switch the appliance off completely by running the shutdown procedure.
The UPS houses a source of electrical energy, namely its batteries. The output of the UPS may be under power even
when the appliance is not connected to the a.c. mains supply.
Never force, break or attempt to open the batteries. These batteries are sealed, maintenance-free components contai-
ning substances that are harmful to health and a source of environmental pollution. If liquid can be seen leaking from the battery, or a white powdery residue is noticeable, do not switch the UPS on.
Avoid exposing the UPS to contact with water or any liquids generally. Do not insert foreign objects into the cabinet.
• Danger of explosion if the batteries are replaced with others of the wrong type.
• Replaced batteries must be disposed of at authorised waste disposal centres.
It is very dangerous to touch any part of the batteries as there is no isolation between the batteries and the mains power source.
CAUTION! A battery can present a risk of electrical shock and high short circuit current.
If the appliance is to be scrapped, it must be entrusted exclusively to a specialist waste disposal company. These companies
will split up and dispose of the various components in accordance with statutory regulations in the country of purchase.
• Since the power cord of the UPS functions as an isolating device, ensure ready access to the mains power socket where the UPS
is connected, and/or to the rear panel of the UPS, so the unit can be easily unplugged.
• The UPS generates a leakage current of approximately 3 mA. To guarantee the maximum leakage current of 3.5 mA, make certain
that the leakage current generated by the load is no greater than 0.5 mA. Should the leakage current from the load exceed this limit, instruct a skilled engineer to install an industrial type connection (to IEC 309 standard) between the UPS and the a.c. mains supply, sized to handle a current compatible with the rating of the appliance.
• Use the UPS in accordance with the technical specifications indicated in this manual (chapter 11).
• In the event that the equipment has no automatic backfeed protection contactor device, make certain that:
- the user/installer attaches warning labels to all mains isolating switches located remotely from the area where the UPS is sited, in
order to inform service personnel that the circuit is connected to a UPS.
- an external isolating device is installed, as indicated in figure 1-1.
• The product you have chosen is designed for commercial and industrial use only.
The product you have selected, given the specified conditions of use, capacity and performance limits, is designed exclusively for commercial and industrial service. The use of the product in “critical applications” could require compliance with statutory regula­tions and standards, or with specific local bylaws, or adaptation to SOCOMEC UPS recommendations. For this type of use, in any event, it is advisable to contact SOCOMEC UPS beforehand for confirmation regarding the capacity of products to meet required levels of safety, performance and reliability. The expression “critical applications” covers, in particular, life support systems, medical applications, commercial transport, nuclear facilities or any other systems where failure of the product might on occasion cause serious damage to persons or property.
1. SAFETY STANDARDS
5
NETYS PL - Ref.: IOMNETPLXX01-GB 02
ENGLISH
1. SAFETY STANDARDS
WARNING! This is a product for commercial and industrial application in the second environment – installation restrictions or additional measures may be needed to prevent disturbances.
CAUTION IF DAMAGED.
BATTERIES, NON SPILLABLE. Packages, crushed, punctured, or torn such that contents are revealed must be set aside in an isolated area and inspected by a qualified person. If the package is deemed to be not shippable, the contents must be promptly collected, segregated, and either the consignor or consignee contacted.
All packaging material must be recycled in compliance with the laws in force in the country where the system is installed.
1.2. DESCRIPTION OF THE SYMBOLS USED ON LABELS ATTACHED TO THE UNIT
All precautions and warnings on labels and plates on the inside and outside the equipment should be observed.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
GROUND TERMINAL
READ THE USER MANUAL BEFORE USING THE UNIT
6
NETYS PL - Ref.: IOMNETPLXX01-GB 02
The main purpose of the UPS is to protect sensitive and critical equipment from electrical disturbances that could compromise operation. Power cuts, voltage drops, variations in voltage and frequency, lightning, electrostatic discharges and rapid over voltages are phenomena found in all office and industrial environments and which cause damage to the hardware and loss of data.
NETYS PL is an Uninterruptible Power Supply designed to power computers and connected peripherals, with the exception of any other electrical device (such as household appliances, television sets, stereo systems and video recorders).
2.1. INTRODUCTION
The characteristic feature of these UPS systems is the constant monitoring of the power supply which, duly filtered and stabilised (on models with AVR) and if considered suitable, is used to supply consumers. In the case of a mains failure or if the mains is considered to be outside limits accepted by the load, the inverter (the heart of the UPS) is activated immediately. Drawing on the power stored in the batteries, the inverter generates a voltage that instantly takes over from the mains without any disruption to the equipment connected.
During operation under emergency conditions, the internal batteries discharge but are recharged again automatically when mains power returns.
Being hermetically sealed, the batteries do not require maintenance of any kind at any stage in their working life.
2. GENERAL DESCRIPTION
2.1-1
Block diagram
Mains input
Output
Surge protection
Output
UPS protection Surge protection
Battery charger
Battery
Mains fi lter and
surge protections
Inverter
(DC/AC)
Automatic
transfer
switch
7
NETYS PL - Ref.: IOMNETPLXX01-GB 02
ENGLISH
3. UNPACKING AND INSTALLATION
3.1. UNPACKING
Remove the UPS and all accessories provided (cables, CD-ROMs, etc) from the packing case.
It is always advisable to keep the original packaging which has been specially designed for safe transport, in case the unit has to be moved again.
3.2. ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION
Please read the following before installing the UPS.
• NETYS PL has been designed for use in closed environments.
• Place the UPS on a flat, stable surface, in a ventilated environment away from heat sources and exposure to direct sunlight.
• Keep ambient temperature between 0 °C and 35 °C and humidity less than 90% (non-condensing); the best temperature to guarantee longest battery lifetime is 15÷20 °C.
• Ensure that the environment where the UPS will be installed is not dusty, and leave a space of at least 20 cm around it to allow for adequate ventilation and access to the rear panel.
• Do not place the UPS or any other heavy object on the cables.
• Check that the voltage and frequency preset for operation is correct for your electrical power supply by consulting the information on the data plate.
• Use only manufacturer-supplied or recommended cables and accessories for connections to the USB serial interface.
It is recommended that the batteries are charged for 8 hours the first time the unit is used.
• A space of at least 25 cm must be left at the back for adequate ventilation (see figure 3.2-1).
UPS
25 cm
20 cm20 cm
3.2-1
8
NETYS PL - Ref.: IOMNETPLXX01-GB 02
4. PRODUCT
USB to charge mobile
devices
ON/OFF
Led
Mains Input cable
USB serial port
Fuse
Output sockets
9
NETYS PL - Ref.: IOMNETPLXX01-GB 02
ENGLISH
5. CONNECTIONS
Cables with an appropriate cross-section and which are compliant with safety standards in force should be used for connection to the mains and connection of the loads.
OUT 230 V~
2 load connection sockets for
surge protection.
OUT 230 V~
4 load connection socket for
UPS and surge protection.
IN 230 V~
Connect the UPS power cord to the mains power supply.
IN 230 V~
Connect the UPS power cord to the mains power supply.
10
NETYS PL - Ref.: IOMNETPLXX01-GB 02
6. MODES OF OPERATION
6.1. SWITCHING THE UPS ON
Switch the UPS on by pressing the ON/OFF button on the front panel.
The Normal Mode LED will light up; allow ten seconds for the self-configuration procedures to run.
6.2. SWITCHING THE UPS OFF
WARNING! This UPS has been designed to control and maintain the battery charge; therefore it should only be switched off completely in exceptional circumstances.
To shut down the UPS completely, press and hold down the ON/OFF button. The UPS switches off all LEDs and is then fully disa­bled. If the mains cable is not disconnected, the batter charger remains active.
6.3. NORMAL MODE
When mains power is available and the voltage falls within the acceptable range, the Normal Mode LED on the front panel remains on permanently. The loads are powered from the mains power supply either directly, the batteries are constantly recharged.
6.4. BATTERY MODE
The UPS automatically switches to this operating mode when mains power fails (spikes or lengthy power cuts) or if the mains is at a value considered to be dangerous; users are powered using the energy stored in the batteries converted to an AC voltage through the inverter.
In this mode, a slow intermittent alarm sounds, and the Battery Mode LED indicator on the front panel flashes.
In the case of prolonged mains failure, the UPS powers users until it shuts down when the batteries are fully depleted (see the chapter COMMUNICATION for ordered shutdown via software).
Just before shutdown, when the battery charge runs out fully, low battery charge is signalled via a rapid intermittent acoustic alarm.
The UPS automatically returns to normal operating mode about two seconds after the mains power is restored. The time taken to transfer from normal to battery mode and vice-versa is imperceptible to the load.
6.5. OVERLOAD
The UPS can power loads up to the power rating declared on the machine’s data plate; once this limit is exceeded, the machine goes into overload condition. Overloads are signalled by a rapid sounding acoustic alarm.
WARNING! Significant overloads could cause permanent damage to the UPS! Avoid connecting laser printers that generate absorption peaks liable to cause overloads on the UPS.
11
NETYS PL - Ref.: IOMNETPLXX01-GB 02
ENGLISH
The UPS provides excellent protection against interruptions or imperfections in the mains power supply. In such cases the computer (load) is powered by the UPS using battery power until this runs out.
Various software applications and communication options are available to optimise operation of the UPS and to correctly manage shutdown when backup power ends. The status of the UPS can be monitored, keeping track of all mains failures and battery discharges so as to activate an automatic and orderly procedure to close the programs and shut down the system. When mains power returns the system will restart automatically.
All NETYS PL models are equipped with a USB communication interface (not available on the standard model).
7.1. SOFTWARE OPTIONS
Software for monitoring and shutdown can be used on NETYS PL thanks to its USB connection. These solutions have been specially designed for the efficient management of power protection devices.
Local View ideal UPS monitoring and shutdown point-to-point solution for Windows®, Linux® and Mac OS X® operating systems.
Visit www.socomec.com and click on DOWNLOAD then SOFTWARE to find the communication software suitable for your require­ments. See the CD provided.
7. COMMUNICATION
12
NETYS PL - Ref.: IOMNETPLXX01-GB 02
8. SOLUTIONS TO MINOR PROBLEMS
Optimal operation of the unit is obtained by keeping it constantly powered (24 hours a day). This guarantees correct maintenance of the battery charge.
WARNING! The UPS internally generates hazardous electrical voltages. All maintenance must only be performed by authorised personnel.
If there is difficulty in getting the UPS to work, the reason may be among those listed below. For any other problems, you are advised to contact your dealer or service organisation directly.
For quick, effective action it is important to give precise details of the fault when you call, in addition to , the model number and manu­facturer's serial number which can be found on the compliance and inspection certificate or on the data plate on the bottom of the UPS.
8.1. TROUBLESHOOTING FOR MINOR PROBLEMS
Problem Possible cause Solution
The UPS works in battery mode even if mains power is available
Poor connection to the input mains
Check the cable connection going to the UPS and the mains outlet
The mains voltage is out of range
No solution because mode of operation is correct
Input protection triggered (blown fuse or automatic switch)
Replace the input fuse with another of the same type or reset the automatic switch
Backup time shorter than expected
Batteries not fully charged
Leave the batteries to charge for 8 hours consecutively
Batteries not working properly
Have the batteries replaced by author­ised personnel
The UPS stalls/goes into overload Overload on the load line
Check that the load applied is not greater than the maximum permitted or reduce the load power requirement
If the equipment is to be left unused for a long period, wait for the batteries to charge fully before switching off. While the UPS is not being used ensure the batteries are recharged for 24 hours at least once every 4 weeks.
13
NETYS PL - Ref.: IOMNETPLXX01-GB 02
ENGLISH
9. TECHNICAL SPECIFICATIONS
Models
Power (UPS protection) 600 (360 W) 800 VA (480 W)
Power (Surge protection) 1200 VA 1200 VA
Technology High Frequency Step Wave
Electrical specifications - Input
Voltage 180÷270 V
Frequency (nominal) 50/60 Hz with automatic selection
Mains connection Cable with plug
Electrical specifications - Output
Voltage (in Battery Mode) 230 V ±10%
Frequency (in Battery Mode) 50/60 Hz ±1 Hz
Wave form Stepwave
Protection Overload, deep discharge and short circuit
Load connection sockets
n° 4 load connection socket for UPS and surge protection
n° 2 load connection socket for surge protection
Battery
Typical back-up time (PC + 17” LCD monitor) 15 min 20 min
Battery recharge Under permanent charge even when the UPS is off (mains present)
Reporting and Communication
Communication interface
USB
Local communication software UPS Management software
Environment
Noise level at 1 meter < 40 dBA
Temperature 0÷40 °C (15÷25 °C for optimum battery life)
Environment Humidity: 90% non-condensing
Reference standards EN 62040-1 (safety), EN 62040-2 (EMC)
Mechanical characteristics
Dimensions (W x D x H) 220 x 220 x 123 mm
Net weight 3.6 kg 4.1 kg
*IOMNETPLXX01-GB 02*
IOMNETPLXX01-GB 02 09.2012
VALID FOR FRANCE VALID FOR ITALY
ISO 9001
FM 28237
ISO14001
EMS 553476
www.socomec.com
YOUR DISTRIBUTOR
To help protect the environment, this document has been printed on PEFC paper (Programme for the Endorsement of Forest Certification)
Non contractual document. © 2012, Socomec SA. All rights reserved.
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 11 149 200 € - R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 admin.ups.fr@socomec.com
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY Tel. +39 0444 598611 - Fax +39 0444 598622 hr.ups.it@socomec.com
SALES, MARKETING AND SERVICE MANAGEMENT
SOCOMEC UPS Paris
95, rue Pierre Grange F-94132 Fontenay-sous-Bois Cedex - FRANCE Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12 dcm.ups.fr@socomec.com
Socomec UPS worldwide
IN WESTERN EUROPE
BELGIUM
Schaatsstraat, 30 rue du Patinage B - 1190 Bruxelles Tel. +32 (0)2 340 02 34 info.ups.be@socomec.com
FRANCE
95, rue Pierre Grange F - 94132 Fontenay-sous-Bois Cedex Tel. +33 (0)1 45 14 63 90 dcm.ups.fr@socomec.com
GERMANY
Heppenheimer Straße 57 D - 68309 Mannheim Tel. +49 (0) 621 71 68 40 info.ups.de@socomec.com
ITALY
Via Leone Tolstoi, 73 - Zivido 20098 San Giuliano Milanese (MI) Tel. +39 02 98 242 942 info.ups.it@socomec.com
PORTUGAL
Núcleo Empresarial de Mafra II Av. Dr. Francisco Sá Carneiro, Fracção N 2640-486 Mafra Tel. +351 261 812 599 info.ups.pt@socomec.com
SPAIN
C/Nord, 22 Pol. Ind. Buvisa E - 08329 Teià (Barcelona) Tel. +34 935 407 575 info.ups.sib@socomec.com
THE NETHERLANDS
Duwboot 13 NL - 3991 CD Houten Tel. +31 (0)30 760 0911 info.ups.nl@socomec.com
UNITED KINGDOM
Units 7A-9A Lakeside Business Park Broadway Lane - South Cerney Cirencester - GL7 5XL Tel. +44 (0)1285 863300 info.ups.uk@socomec.com
OTHER COUNTRIES
Tel. +34 935 407 575 info.ups.europe@socomec.com
IN EASTERN EUROPE, MIDDLE EAST, AFRICA
UNITED ARAB EMIRATES
LIU-E17 DAFZA 371355 Dubai airport free zone Dubai (United Arab Emirates) Tel.: +971 (0) 4 29 98 441 info.ups.ae@socomec.com
POLAND
ul. Mickiewicza 63 01-625 Warszawa Tel. +48 22 825 73 60 info.ups.pl@socomec.com
ROMANIA
Heliade Intre Vii Street no.8, 2 District 023383 Bucharest Tel. +40 21 319 36 88 ( 89, 81, 82) info.ups.ro@socomec.com
RUSSIA
4th Street 8 Marta, 6A, 405 125167 - Moscow Tel. +7 495 775 19 85 info.ups.ru@socomec.com
SLOVENIA
Savlje 89 SI - 1000 Ljubljana Tel. +386 1 5807 860 info.ups.si@socomec.com
TURKEY
Masuklar Yokusu No:57/2 34357 Besiktas Istanbul Tel. +90 212 2580810 info.ups.tr@socomec.com
OTHER COUNTRIES
Tel. +39 0444 598 611 info.ups.emea@socomec.com
IN ASIA PACIFIC
AUSTRALIA
Unit 3, 2 Eden Park Drive (Rydecorp) Macquarie Park NSW 2113 Tel. +61 2 9325 3900 info.ups.au@socomec.com
CHINA
Universal Business Park B33, Floor 3, 10 Jiuxianqiao Lu, Chaoyang, Beijing 100016 P.R., China Tel. +86 10 59756108 info.ups.cn@socomec.com
INDIA
B1, IInd Floor, Thiru-Vi-Ka-Industrial Estate Guindy Chennai – 600 032 Tel. +91 44 3921 5400 info.ups.in@socomec.com
MALAYSIA
31 Jalan SS 25/41- Mayang Industrial Park 47301 Petaling Jaya.- Selangor, Malaysia Tel. +603 7804 1153 info.ups.my@socomec.com
SINGAPORE
31 Ubi Road 1 #01-00 (Lobby B) Aztech Building Singapore 408694 Tel. +65 6506 7600 info.ups.sg@socomec.com
THAILAND
No.9 Soi Vibhavadirangsit 42 Vibhavadirangsit Rd, Ladyao Chatujak Bangkok 10900 Tel. +66 2 941-1644-7 info.ups.th@socomec.com
VIETNAM
539/23 Luy Ban Bich St., Phu Thanh Ward, Tan Phu Dist Ho Chi Minh City Tel. +84-839734.990 info.ups.vn@socomec.com
ASIA PACIFIC HEAD OFFICE
Tel. +65 6507 9770 info.ups.apac@socomec.com
IN AMERICA
LATIN AMERICAN COUNTRIES
Tel. +34 935 407 575 info.ups.sib@socomec.com
Loading...