socomec MASTERYS IP Plus Installation And Operating Manual

IOMMASIPXX09-GB 04
INSTALLATION AND OPERATING MANUAL
10-40 kVA
MASTERYS IP+
ITALIANO
ENGLISH
3
10-40 kVA
MASTERYS IP+
INDEX
1. CERTIFICATE AND CONDITIONS OF WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2. SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1 Important. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.2 Description of the symbols used on the labels applied to the . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3. UNPACKING AND INSTALLATION OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.1 Shipping and moving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.2 Unpacking procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.3 Environmental requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.4 Identifying switching and connection devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Electrical requisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.5.1 Backfeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.6 Installation procedure and instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.7 ADC card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.8 External battery cabinet connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4.1 ON LINE operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4.2 Operation in high e ciency mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.3 Operation with internal manual maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4 Operation with external manual maintenance bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.5 Operation in GE con guration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
5. ACCESS TO CONTROLS AND COMMUNICATION INTERFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
5.1 Identifying the switches and interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.2 Functions of the switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
6. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.1 Advanced Mimic Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Meaning of ideograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3 Meaning of the luminous bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.4 Mimic panel menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7. OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
7.1 Start-up in normal mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.2 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.3 Extended out of service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
7.4 Switching onto manual bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5 Return to normal mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
7.6 Emergency shutdown (ESD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
ITALIANOENGLISH
4
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
INDEX
8 MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
8.1 “Allarms” menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
8.2 “Measurements” menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.3 “Commands” menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
8.4 “Parameters” menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.5 “Service” menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
8.6 “Event log” menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.7 Mimic Panel Concentrator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
9. COMMUNICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
9.1 Multi-Level Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
9.2 Standard Lan web page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
9.3 Accessories and SW options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
10. PROBLEM SOLVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
10.1 System alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
10.2 UPS Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.3 Preventive maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
11. OPTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
11.1 Kit GSS (Global Supply System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
11.2 Isolation Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
11.3 Remote mimic panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
11.4 ACS PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
11.5 ADC card with temperatur sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
11.6 External back-feed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
11.7 Pro bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
11.8 GSM modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
11.9 Serial connection PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
11.10 Cold Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
11. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
PARALLEL CONFIGURATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
IP52 VERSION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
ENGLISH
5
10-40 kVA
MASTERYS IP+
1
CERTIFICATE AND CONDITIONS OF WARRANTY
This SOCOMEC UPS continuous power system is guaranteed against any manufacturing and material defects.
The period of validity of the warranty is 12 (twelve) months from the date of commissioning, if said activation is carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS, and not however more than 15 ( fteen) months from the date of shipment by SOCOMEC UPS.
The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall be limited to the cover of the parts used to repair the fault.
The warranty is valid ex-works and covers labour and parts used to repair the fault.
The warranty shall not apply in the following cases:
• Failures due to fortuitous circumstances or force majeure (lightning,  oods, etc.);
• Failures due to negligence or improper use (use out of tolerance: temperature, humidity, ventilation, electric pow­er supply, applied load, batteries);
• Insu cient or inadequate maintenance;
• Attempted maintenance, repairs or modi cations not carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS.
• If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual, in cases of extended storage or UPS inactivity.
SOCOMEC UPS may, at its own discretion, opt for the repair of the product or for the replacement of the faulty or defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and performance.
Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS who becomes the sole owner.
Replacements or repairs of parts and any modi cations to the product during the warranty period cannot extend the duration of the warranty.
In no case will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earn­ings, interruption of activity, loss of information or other economic losses) deriving from the use of the product.
The present conditions are subject to Italian law. Any dispute falls under the province of the Court of Vicenza.
ITALIANOENGLISH
6
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
2.1 IMPORTANT.
• This document provides important instructions for the safe use, movement and connection of the MASTERYS™ un­interruptible power system (UPS).
• SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All reproduction, modi cation, dissemination of this document whether in part or whole and by any manner are expressly prohibited except upon Socomec’s express prior written consent.
• This document is not a speci cation. SOCOMEC UPS reserves the right to make any changes to data without prior notice.
• The unit must be installed and activated only by quali ed technical personnel and authorised by SOCOMEC UPS.
The UPS MUST only be moved by two people at least by the means of a forklift.
• The unit must remain in a vertical position in all circumstances.
• Connect the PE ground conductor  rst before you make any other connection.
• Do not expose the UPS to rain or liquids in general. Do not introduce external bodies.
• If the UPS is not equipped with automatic sectioning against back feed or if the switch is external to the UPS, a x a label bearing the following words on all the external switches of the UPS power supply:
• Keep this manual handy for future consultation.
• If the unit fails, it must be repaired only by authorised technicians that have been specially trained for this pur­pose.
• This equipment conforms to the European Community directives for professional equipment and bears the ap­proval mark
• The UPS requires three-phase plus neutral input connections (3P+N).
• The UPS can be supplied by an IT distribution system with a neutral conductor.
• The output neutral of the transformer is not connected to the ground. The internal isolation transformer modi es the neutral arrangements of the system.
WARNING! The output neutral of the transformer is not connected with the ground.
• Before connecting any external battery cabinet, ensure that it is fully compatible with the model of UPS it is to be used with.
SAFETY
2
ENGLISH
7
10-40 kVA
MASTERYS IP+
• The use of external battery cabinets not supplied by the manufacturers is not recommended.
FOR TECHNICAL PERSONAL: Switch o and isolate the UPS and then wait for 5 minutes before removing the protection panels
in order to carry out work on parts under dangerous voltage.
The product you have chosen is designed for commercial and industrial use only. In order to be used for particular “critical applications” such as life support systems, medical applications, commercial transportation, nuclear facilities or any other application or systems where product failure is likely to cause substan­tial harms to person or property, the products may have to be adapted. For such uses we would advise you to contact SOCOMEC UPS beforehand to con rm the ability of these products to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and speci cations.
WARNING! This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
2.2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT.
All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
GROUND TERMINAL
READ THE USER MANUAL BEFORE USING THE UNIT
2
SAFETY
ITALIANOENGLISH
8
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
UNPACKING AND INSTALLATION OF THE UNIT
3
The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as close as possible to the installation site.
3.1 SHIPPING AND MOVING.
• The UPS must remain in a vertical position during all shipping and moving operations.
• Ensure that the  oor is strong enough to support the weight of the UPS and of the battery cabinet, if used.
Avoid pressing on the front door when moving the unit.
The UPS MUST only be moved by two people at least by the means of a forklift.
CAUTION IF DAMAGED.
BATTERIES, NON SPILLABLE.
Packages, crushed, punctured, or torn such that contents are revealed must be set aside in an isolated area and inspected by a quali ed per­son. If the package is deemed to be not shippable, the contents must be promptly collected, segregated, and either the consignor or consignee contacted.
All packaging material must be recycled in compliance with the laws in force in the country where the system is installed.
Battery is NOT connected!
ENGLISH
9
10-40 kVA
MASTERYS IP+
3
UNPACKING AND INSTALLATION OF THE UNIT
3.2 UNPACKING PROCEDURE.
3.2-1 3.2-2
3.2-3
ITALIANOENGLISH
10
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
free areafree area
UNPACKING AND INSTALLATION OF THE UNIT
3
3.3 ENVIRONMENTAL REQUIREMENTS.
• The recommended operating temperature, humidity and altitude values are listed in the technical speci cations table. Cooling systems may be required to maintain these values.
• Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or chemical solutions).
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or to sources of excessive heat.
• A space of at least 40 cm must be left at the back for adequate ventilation (see  gure 3.3-1).
• The UPS switches are accessed from the front; a space of at least 1.5 metres should be left at the front of the UPS for maintenance purposes.
• Adequate access must be ensured on both sides (see  gure 3.3-2).
• Do not put any object on the upper part of the UPS.
3.3-1
3.3-2
MASTERYS
IP+
BATTER
CABINET
BATTERY CABINET
40 cm
1,5 m
MASTERYS
IP+
40 cm1,5 m
20 cm20 cm20 cm
3.3-3
Place the UPS in the installation area, then secure it to the  oor.
40 cm
door
door
ENGLISH
11
10-40 kVA
MASTERYS IP+
Q2 Q6
E
D
F
G
H
Masterys IP+ without battery.
UNPACKING AND INSTALLATION OF THE UNIT
3
3.4 IDENTIFYING SWITCHING AND CONNECTION DEVICES.
Legend.
A LAN RJ45 connector for Ethernet. B Serial RS232 connector for Modem. C Serial RS232/485 connector D Cable trunking for control cables. E Fans. F DIN rail (behind the panel). G Fuses. H Power connections (behind the plastic protection). I Battery pack. L Slots for communication cards (ADC card installed as
standard, 1 slot available for an additional card).
Q1 Battery switch. Q2 Input switch (MAINS). Q6 Output switch.
Q2Q1Q6
E
D
L
L
F
G
H
I
Masterys IP+ with battery.
CBA
ITALIANOENGLISH
12
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
UNPACKING AND INSTALLATION OF THE UNIT
3
3.5 ELECTRICAL REQUIREMENTS.
The installation and the system must comply with national plant regulations. The electrical distribution panel must have a protection and sectioning system installed for the input mains and the auxiliary mains. If a di erential switch is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel. The table below show the size of the input protection devices recommended for correct installation.
WARNING!
The default transformer is normally connected to the output.
Size of the input protection devices
UPS
[kVA]
Magneto-thermal
input
1
[A]
Magneto-thermal
Auxiliary Mains
1
[A]
Di erential
input
5
[A]
Input cable
core size
[mm2]
Output/Aux
cable core size
[mm2]
Battery cable
core size
[mm2]
Battery
protection
4
[A]
single parallel
2
single parallel2selective type
5
min-max
3
min-max
3
10 3/1
32 40
100 125 0.5 6÷35 16÷50 6÷35 50 Gr
100
if common
input mains
125
if common
input mains
15 3/1
32 40
100 125 0.5 6÷35 25÷50 6÷35 50 Gr
100
if common
input mains
125
if common
input mains
20 3/1
40 63
125 160 0.5 10÷35 35÷50 10÷35 50 Gr
125
if common
input mains
160
if common
input mains
30 3/1
63 80
160 200 0.5 16÷35 50 16÷35 100 Gr
160
if common
input mains
200
if common
input mains
10 3/3 32 40 32 40 0.5 6÷35 6÷35 6÷35 50 Gr
15 3/3 32 40 32 40 0.5 6÷35 6÷35 6÷35 50 Gr
20 3/3 40 63 40 63 0.5 10÷35 10÷35 10÷35 50 Gr
30 3/3 63 80 63 80 0.5 16÷35 16÷35 16÷35 100 Gr
40 3/3 80 100 80 100 0.5 25÷35 25÷35 25÷35 100 Gr
1
Recommended magneto thermal switch: four poles with intervention threshold ≥ 10 In
2
In systems with two or more UPSs operating in a redundant or power parallel con guration.
3
Determined by the size of the terminals.
4
Protection on the external battery cabinet.
5
Caution! Use type B four-pole selective (S) circuit breakers. Load leakage currents are added to those generated by the UPS and during transitory
phases (power failure and power return) short current peaks may occur. If loads with high leakage current are present, adjust the di erential protection. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the de nitive load, so as to prevent the sudden activation of the above switches.
ENGLISH
13
10-40 kVA
MASTERYS IP+
3
UNPACKING AND INSTALLATION OF THE UNIT
The UPS is designed for transitory overvoltages in category II installations. If the UPS is part of
the building’s electric circuit or if it is likely to be subject to transitory overvoltages in category III installations, further external protection must be provided, either on the UPS or in the AC power supply network to the UPS.
In the event of three-phase non-linear loads connected in output, the current on the neutral
conductor may have a value that is 1.5 - 2 times the phase value (also for the input bypass). In this case, size the neutral cables and the input/output protection properly.
3.5.1 Back-feed protection.
Since the UPS does not have an internal automatic protection device against current back-feed, the operator/install­er must add a warning label to all the mains power disconnecting switches installed at a distance from the UPS area. This is a reminder for the technicians about the circuit is connected to a UPS (see the CAUTION section in paragraph 2 of this manual and paragraph 4.5.3. of the EN62040-1-1 standard). The label is supplied with the system.
To install the external back-feed protection it is necessary to connect an external electromechanical switch. For further information on the connection and the type of remote switch, please read paragraph 11.6 of this manual.
ATTENTION.
The neutral is not disconnected as, even in the event of a single fault on the UPS, it never has high poten­tial when the mains and/or auxiliary power supplies are disconnected upstream. This is to avoid modi ca­tions of the electrical system in case of a power failure.
If, in certain anomaly states, or because of the installation upstream (e.g. undetected and protec­ted earth fault, or high leakage in a phase, or with IT systems) there is a hazardous potential on neutral, a suitable isolating switch must be provided on the neutral as well, or else there must be a detection, signalling and protection system.
NOTE. The neutral of the AUX Mains line must be electrically common with the neutral of the main input feed line.
ITALIANOENGLISH
14
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
3
UNPACKING AND INSTALLATION OF THE UNIT
Cable speci cations:
• stripping length: 18 mm
• tightening torque: 2,5÷4,5 Nm
3.6 INSTALLATION PROCEDURES AND INSTRUCTIONS.
WARNING!
Before carrying out work on the terminal board or on UPS internal parts, ensure that the UPS is switched o , remove the power supply, open the external battery cabinet disconnectors, isolate the system and wait 5 minutes.
WARNING!
The default transformer is normally connected to the output.
WARNING!
The transformer cannot be connected to the output on UPS units connected in parallel con guration.
WARNING!
Check the presence and the right position of the jumper on terminal socket labelled “TRAFO IN/ OUT SETTING”.
3.6-1
3.6-4
EXT. BATTERY
TA1
TA2
TA3
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
OUT
TRANSFORMER
AUXILIARY
MAINS
L11 L21 L31 N1 L14 L24 L34 N4 N3L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
COM1
COM2
NC1
NC2
OPEN
OPEN
For systems installed on raised  oor.
3.6-3
20 cm
90°
A
A
B
B
3.6-2
A. power cables B. control cables
Power connections.
REMOVE
REMOVE
ENGLISH
15
10-40 kVA
MASTERYS IP+
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
IN
TRANSFORMER
OUT
TRANSFORMER
L11 L21 L31 N1 L14 L24 L34 N4 L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
TA1
TA2
MAINS
SUPPLY
AUXILIARY
MAINS
N3
3
UNPACKING AND INSTALLATION OF THE UNIT
N3
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
OUT
TRANSFORMER
L11 L21 L31 N1 L14 L24 L34 N4 L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
TA1
TA2
AUXILIARY
MAINS
3/3
MAINS AND AUXILIARY MAINS ARE CONNECTED SEPARETELY.
Output transformer (standard con guration)
3/3
MAINS AND AUXILIARY MAINS ARE CONNECTED IN COMMON.
Output transformer
AUXILIARY
MAINS
cable section
ø 6÷35 mm
2
TO
LOAD
cable section
ø 6÷35 mm
2
TO LOAD
cable section
ø 6÷35 mm
2
MAINS
cable section
ø 6÷35 mm
2
MAINS
cable section
ø 6÷35 mm
2
Cable
Cable
provided
provided
Cables
Cables
provided
provided
Cables
Cables
provided
provided
Cable
Cable
provided
provided
ITALIANOENGLISH
16
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
WARNING!
Remove the connecting cables provided between OUTPUT and IN TRANSFORMER and use them to con­nect AUXILIARY MAINS and OUT TRANSFORMER.
Move the bridge cable provided from TA1-TA2 to TA2-TA3.
3
UNPACKING AND INSTALLATION OF THE UNIT
EXT. BATTERY
+B2 -B2 -B1 +B1
TA2
TA3
OUTPUT
IN
TRANSFORMER
OUT
TRANSFORMER
L11 L21 L31 N1 L14 L24 L34 N4 L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
MAINS
SUPPLY
AUXILIARY
MAINS
N3
3/3
MAINS AND AUXILIARY MAINS
ARE CONNECTED SEPARATELY.
Transformer on the recti er power supply input
3/3
MAINS AND AUXILIARY MAINS
ARE CONNECTED SEPARATELY.
Transformer on the bypass power supply input
TO LOAD
cable section
ø 6÷35 mm
2
MAINS
cable section
ø 6÷35 mm
2
AUXILIARY
MAINS
cable section
ø 6÷35 mm
2
WARNING!
Remove the connecting cables provided between OUTPUT and IN TRANSFORMER and use them to connect MAINS SUPPLY and OUT TRANSFORMER.
Move the bridge cable provided from TA1-TA2 to TA2-TA3.
EXT. BATTERY
+B2 -B2 -B1 +B1
TA2
TA3
OUTPUT
IN
TRANSFORMER
OUT
TRANSFORMER
L11 L21 L31 N1 L14 L24 L34 N4 L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
MAINS
SUPPLY
AUXILIARY
MAINS
N3
TO LOAD
cable section
ø 6÷35 mm
2
MAINS
cable section
ø 6÷35 mm
2
AUXILIARY MAINS
cable section
ø 6÷35 mm
2
Cable
Cable
provided
provided
Cable
Cable
provided
provided
Cables
Cables
provided
provided
Cables
Cables
provided
provided
ENGLISH
17
10-40 kVA
MASTERYS IP+
3
UNPACKING AND INSTALLATION OF THE UNIT
TO LOAD
cable section
ø 6÷35 mm
2
MAINS
cable section
ø 6÷35 mm
2
AUXILIARY
MAINS
cable section
ø 6÷35 mm
2
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
L11A L11 N11A N11 L14 N4 N3L13 L12 N2L1 L2 L3 N
AUXILIARY
MAINS
OUT
TRANSFORMER
3/1
MAINS AND AUXILIARY MAINS ARE CONNECTED SEPARETELY.
Output transformer
AUXILIARY
MAINS
cable section ø 16÷50 mm
2
TO
LOAD
MAINS
cable section
ø 6÷35 mm
2
Cables
Cables
provided
provided
Cables
Cables
provided
provided
N3
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
OUT
TRANSFORMER
L11 L21 L31 N1 L14 L24 L34 N4 L13 L23 L33 L12 L22 L32 N2L1 L2 L3
TA1
TA2
AUXILIARY
MAINS
3/3
UPS IN NEUTRAL VERSION WITHOUT NEUTRAL ON THE NETWORK
output transformer
Cables
Cables
provided
provided
Do not combine the main network and the auxiliary network
ITALIANOENGLISH
18
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
3
UNPACKING AND INSTALLATION OF THE UNIT
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
L11A L11 N11A N11 L14 N4 N3L13 L12 N2L1 L2 L3 N
AUXILIARY
MAINS
OUT
TRANSFORMER
3/1
MAINS AND AUXILIARY MAINS
ARE CONNECTED SEPARATELY.
Transformer on the bypass power supply input
WARNING!
Remove the connecting cables provided between OUTPUT and IN TRANSFORMER and use them to connect AUXILIARY MAINS and OUT TRANSFORMER. MAINS SUPPLY and AUXILIARY MAINS must be connected as shown in the picture below.
AUXILIARY
MAINS
cable section ø 16÷50 mm
2
TO
LOAD
MAINS
cable section
ø 6÷35 mm
2
Cables
Cables
provided
provided
WARNING!
MAINS SUPPLY and AUXILIARY MAINS must be connected as shown in the picture below.
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
L11A L11 N11A N11 L14 N4 N3L13 L12 N2L1 L2 L3 N
AUXILIARY
MAINS
OUT
TRANSFORMER
3/1
MAINS AND AUXILIARY MAINS
ARE CONNECTED IN COMMON.
Output transformer
AUXILIARY
MAINS
cable section ø 16÷50 mm
2
TO
LOAD
MAINS
cable section
ø 6÷35 mm
2
Cables
Cables
provided
provided
ENGLISH
19
10-40 kVA
MASTERYS IP+
3.7 ADC CARD.
This card can be con gured to control up to four outputs that can be set as normally closed or normally open and up to three digital inputs. The card is inserted in one of two slots provided (refer to paragraph 3.4). Up to four operating modes can be selected using the two DIP switches 1 or 2.
Electrical data.
- Admitted Nominal current and voltage of NO or NC contacts: 2 A 250 Vac depending on the terminal used.
- Inputs are activated on loop closing.
Connection of the generator.
If your system uses a generator, connect the “generator set ready” no-potential contact to connector IN 2 on the op­tional ADC card con gured in standard or power safe mode. This automatically extends the voltage and frequency value range when power is supplied by the generator set.
External E.S.D. connection.
A remote emergency shutdown system (E.S.D.) can be installed by means of the optional ADC card. Connect a normally closed zero-potential contact to terminals IN1+ and IN1- of the ADC card.
3
UNPACKING AND INSTALLATION OF THE UNIT
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
L11A L11 N11A N11 L14 N4 N3L13 L12 N2L1 L2 L3
AUXILIARY
MAINS
OUT
TRANSFORMER
3/1
UPS IN NEUTRAL VERSION WITHOUT NEUTRAL ON THE NETWORK
output transformer
AUXILIARY
MAINS
cable section ø 16÷50 mm
2
TO
LOAD
MAINS
cable section
ø 6÷35 mm
2
Cables
Cables
provided
provided
Do not combine the main network and the auxiliary network
1
ITALIANOENGLISH
20
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
3
UNPACKING AND INSTALLATION OF THE UNIT
The  lter level indicates the activation delay: 1 immediate activation (1 seconds minimum communication time), 2 10 s delay, 3 30 s delay.
(1) If the external E.S.D. button is not used, always insert a jumper to short circuit input IN 1
A
2
3
4
1
OUT
OUT
0 1 2 P3
C2 NO2 NC2 IN1- IN1+ IN3- IN3+ C3 NO3 NC3
C1 NO1 NC1 IN1- IN1+ IN2- IN2+ C4 NO4 NC4
OUT1
OUT2
DIP1 DIP2
IN3
OUT3
IN1
IN2
OUT4
STANDARD confi guration (default)
DIP1: OFF - DIP2: OFF
IN/OUT Description
Filter
level
OUT 1 General alarm 2
OUT 2 Battery discharging 3
OUT 3 Battery low or imminent stop 2
OUT 4 UPS on by-pass 2
IN 1
(1)
E.S.D. 1
IN 2 Supply from GenSet 1
IN 3 Isolation controller 2
SAFETY confi guration
DIP1: OFF - DIP2: ON
IN/OUT Description
Filter
level
OUT 1 General alarm 2
OUT 2 E.S.D. activation 1
OUT 3 Battery low or imminent stop 2
OUT 4 E.S.D. activation 1
IN 1
(1)
E.S.D. 1
IN 2 External alarm A39 2
IN 3 External alarm A40 2
POWER SAFE confi guration
DIP1: ON - DIP2: OFF
IN/OUT Description
Filter
level
OUT 1 General alarm 2
OUT 2 Power safe plug 1 2
OUT 3 Power safe plug 2 2
OUT 4 Power safe plug 3 2
IN 1
(1)
E.S.D. 1
IN 2 Supply from GenSet 1
IN 3
Management of energy consuption
1
ENVIRONMENTAL confi guration
DIP1: ON - DIP2: ON
IN/OUT Description
Filter
level
OUT 1 General alarm 2
OUT 2 Over-heating 2
OUT 3 Overload / Loss of redundancy 2
OUT 4 External alarm In2 2
IN 1
(1)
E.S.D. 1
IN 2 External alarm A39 2
IN 3 External alarm A40 2
1
ENGLISH
21
10-40 kVA
MASTERYS IP+
Intervention of the E.S.D. input switches o the UPS output.
To restore the UPS to operation:
• Close the E.S.D. contact on “In 1” on the ADC card.
• Give the reset alarms” command.
• Run the start procedure
Description of signals
Message on the mimic panel
General Alarm
Battery discharging Battery Low or Imminent stop UPS on bypass E.S.D. Supply from GenSet Isolation controller Power safe plug 1 Power safe plug 2 Power safe plug 3 Management of energy consumption E.S.D. activation Over-heating Overload/Loss of redundancy
Description
“General Alarm” contact output.
Battery discharging contact output Battery low voltage and imminent shutdown contact output. Contact input for emergency shutdown device. UPS on bypass contact output Generator ready signal input. Isolation leakage controller signal input Non privileged load 1 command output activated by overload or loss of redundancy. Non privileged load 1 command output activated by battery discharging. Non privileged load 1 command output activated by battery low. Input for the battery to help providing energy in the event of peak consumption. Shutdown for E.S.D. contact output. Internal over-heating contact output. Overload / loss of redundancy contact output
No alarm.
C1
NO1
NC1
3
UNPACKING AND INSTALLATION OF THE UNIT
1
ITALIANOENGLISH
22
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
3.8 EXTERNAL BATTERY CABINET CONNECTION.
If the UPS has internal batteries, connecting external battery cabinets is forbidden.
Position the battery cabinet next to the UPS.
Before carrying out any operation, ensure that:
• the UPS is not live,
• all mains or battery switches are open,
• the switches upstream of the UPS are open,
• the battery fuses located inside the battery cabinet are open.
• Remove the terminal boards protection.
• Connect the ground cable ( gure 3.8-1).
• Connect the cables between the UPS terminals and the battery cabinet terminals, strictly observing the polarity of each individual string ( gure 3.8-1) and the cross-sections indicated in the table at page 12.
Use double insulated cables or the cables supplied with the unit to connect the UPS to the Bat-
tery cabinet. The lenght L of battery cable must not be more than 8 metres long (if L > 8 m, please contact the support service).
Cabling errors with inversion of the battery polarity may cause permanent damage to the equip-
ment.
• Replace the terminal board’s protection.
If using cabinets not supplied by the SOCOMEC UPS, it is the installer’s responsibility to check the
electrical compatibility and the presence of appropriate protection devices between the UPS and the battery cabinet (fuses and switches of su cient capacity to protect the cables from the UPS to the battery cabinet). As soon as the UPS is switched on (before closing the battery switches) the battery parameters (voltage, capacity, number of elements, etc.) must be veri ed accordingly on the mimic panel menu. If the values indicated on the battery cabinet data plate are di erent from those shown on the mimic panel, use the SERVICE > CONFIGURATIONS menu to correct the settings.
3.8-1
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
OUT
TRANSFORMER
AUXILIARY
MAINS
L11 L21 L31 N1 L14 L24 L34 N4 L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
UPS
BATTERY CABINET
3
UNPACKING AND INSTALLATION OF THE UNIT
1
ENGLISH
23
10-40 kVA
MASTERYS IP+
4
MODES OF OPERATION
4.1 ON LINE OPERATIONS.
A special feature of the MASTERYS™ series is the “ON LINE” double conversion feature in conjunction with low dis­tortion mains power absorption. In ON LINE mode, the UPS is able to supply a voltage that is fully stabilised in frequency and amplitude, regardless of any interference in the mains power supply within the most stringent clas­si cation of UPS regulations. ON LINE operation provides three operating modes according to mains and load conditions:
“Normal” mode. This is the most frequent operating condition: the energy is drawn from the primary mains power supply and is converted and used by the inverter to generate the output voltage to power the loads connected. The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an overload or inverter shutdown) without any break in the power supply to the load. The battery charger supplies the energy required to maintain or recharge the battery.
“Bypass” mode.
In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in the power supply. This procedure may occur in the following situations:
- in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS output is switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter, returns automatically a few seconds after the overload disappears.
- when the voltage generated by the inverter goes is out of tolerances due to a major overload or a fault on the inverter.
- When the internal temperature exceeds the maximum value allowed.
“Battery” mode. In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on the battery status and on the back-up time available. The disconnection of non mission critical applications during battery discharge can be programmed (after a certain laps of time) by using the Power Share option, so that the battery resources can be reserved for the most critical applications.
4.2 OPERATION IN HIGH EFFICIENCY MODE.
The UPS has a selectable and programmable “economy” operating mode (ECO-mode) that can increase overall ef­ ciency by up to 98% for energy saving purposes. With this mode of operation, speci c daily or weekly time intervals can be selected and programmed to power the applications directly from the auxiliary mains. If the power supply outage, the UPS will automatically switch onto the inverter and continue to supply power to the load by drawing energy from the battery. This mode does not provide perfect stability in frequency and voltage like the ON LINE mode. Thus the use of this mode should be carefully evaluated according to the level of protection required by the application. The Eco Mode operation provides very high e ciency, since the application is powered directly from the auxiliary mains via the automatic bypass in normal operating conditions.
ITALIANOENGLISH
24
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
4.3 OPERATION WITH INTERNAL MANUAL MAINTENANCE BYPASS.
If the internal maintenance bypass is activated using the appropriate procedure, the load is powered directly from the maintenance bypass, while the UPS is separated from the power supply and can be switched o . This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions can be performed by service personnel without having to disconnect the power supply to the load.
4.4 OPERATION WITH EXTERNAL MANUAL MAINTENANCE BYPASS.
The external manual maintenance bypass connection is not allowed when the internal transformer
is placed on output or bypass.
For any further information, please contact SOCOMEC UPS.
4.5 OPERATION IN GE CONFIGURATION.
MASTERYS™ can be operated in conjunction with a generator (GE). With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instabil­ity of the GE and at the same time to avoid operation from the battery or risks of out-of-synchronisation switching onto the bypass. The use of the GSS interface, described in the options section, also increases the amount of diagnostic information exchanged between the continuous power system and the generator.
4
MODES OF OPERATION
1
ENGLISH
25
10-40 kVA
MASTERYS IP+
This chapter identi es the electromechanical switches described here below used for start-up, shutdown and maintenance bypass procedures.
Access to the control area is from the front by opening the door. The control area also contains the communication interface connectors and the slots for the optional signalling cards. Please refer to the relevant chapter for more details on the connection and use of the related communication interfaces/cards.
ACCESS TO CONTROLS AND COMMUNICATION INTERFACES
5
5.1-1
5.1 IDENTIFYING THE SWITCHES AND INTERFACES.
Legend.
Q1 Battery switch. Q2 Input switch (MAINS). Q6 Output switch.
MAINS
AUXILIARY
MAINS
IN
TRANSFORMER
OUT TRANSFORMER
0
2
1
B
B1
OUTPUT
Standard con guration.
Q2
Q6
Q1
Q2Q1Q6
Masterys IP+ with battery. Masterys IP+ without battery.
Q2 Q6
ITALIANOENGLISH
26
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
ACCESS TO CONTROLS AND COMMUNICATION INTERFACES
5
5.2 FUNCTIONS OF THE SWITCHES.
Input switch Q2.
The input switch provides the primary power supply to the UPS. In normal operating conditions it should be in position 1 ON. The position 0 OFF will cause the batteries to discharge. In a con guration with separate mains, the switch only interrupts the recti er power supply.
Output disconnecting switch Q6. The disconnecting switch Q6 has three positions with the following functions:
Position 1 “UPS”: this is the position for normal operation of the UPS for a continuous power supply to the load;
Position 2 “MANUAL BY-PASS”: This position should only be selected for ordinary or extraordinary maintenance operations (manual bypass); the load is connected directly to the mains power supply. It may be used in the event of a UPS failure to power applications from the auxiliary mains while awaiting the intervention of technical person­nel;
Position 0 “OFF”: This completely isolates the UPS output by removing the voltage from the applications in any operating condition. It is used for the emergency shutdown of the system (internal E.PO.).
Battery switch Q1 (UPS batteries).
When closed, this switch connects the batteries of the UPS to the DC/DC converter stage to power the inverter in
the event of a mains failure. The normal operating position is 1 (closed).
ENGLISH
27
10-40 kVA
MASTERYS IP+
6
MIMIC PANEL
6.1 MIMIC PANEL.
The LCD mimic panel ( gure 6.1-1) on the door of the UPS provides all the information relating to operating status, electrical measurements, access to controls and con guration parameters.
The information is grouped into four sections: A. ideograms that identify the subsets and the en-
ergy  ow;
B. multicoloured luminous bar that identi es the
condition of the power supply to the load;
C. alphanumeric information that uses a menu layout
to provide details on any alarms that may occur and on the measurements, controls and param­eters.
D. use of the buttons:
· ESC: exit from the current menu/parameter/action;
· UP
: scrolls the available menus/values upwards. It increases the value each time it is pressed when chang-
ing a parameter;
· DOWN
: scrolls the available menus/values downwards. It decreases the value each time it is pressed when
changing a parameter;
· ENTER: enters the menu displayed on the screen to con rm the choice/changes made.
6.1-1
A
B
C
D
ITALIANOENGLISH
28
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
6
MIMIC PANEL
6.2-1
M1
M2 M8
M9
M10 M11
M12 M13 M14 M15 M16 M17
M29
M30
M31
6.2 MEANING OF IDEOGRAMS.
M7
Meaning of ideograms
Code Description Condition
M1 Load on bypass, in Eco-mode or Maintenance bypass closed Steady Automatic bypass alarm Flashing
M2 Input recti er active. Steady Input recti er general alarm. Flashing
M3 Battery OK. Steady Battery alarm. Flashing
M4-M7 Remaining battery capacity. Steps of 25% Battery recharging. Sequence M7 M4
M8 Inverter on Steady Inverter general alarm. Flashing
M9 Switch Q6 in position 1. Steady M10 Input mains OK. Steady
Input mains alarm. Flashing M11 Inverter on. Steady M12 Module 1 present. Steady
Module 1 general alarm. Flashing M13 Module 2 present. Steady
Module 2 general alarm. Flashing M18 Load present. Steady
Overload. Flashing M19-M28 Output load indicator. Steps of 10% M29 Periodic maintenance alarm/warning. Flashing M30 Activation code alarm. Steady
General alarm. Flashing M31 LAN connection ready (Cable Connected). Steady
M4
M5
M6
M3
M25
M26
M27
M28
M24
M19
M18
M20
M21
M22
M23
1
ENGLISH
29
10-40 kVA
MASTERYS IP+
6
MIMIC PANEL
Meaning of the luminous bar
Colour Conditions displayed
RED  ashing Imminent shutdown alarm (the load will be disconnected in a few minutes) RED Load not powered or battery circuit open YELLOW  ashing UPS in stand-by or Ups on manual bypass
Alarm indicating request for ordinary maintenance according to conditions of use (type of load, temperature), after over 25.000 – 30.000 hours of operation (M29  ashing and alarm A44)
YELLOW Warning for preventive maintenance according to conditions of use (type of load, temperature), after over 10.000 - 12.000 hours of operation (M29  ashing)
YELLOW Load on battery or battery discharging if M11 is on steady and M10 is o YELLOW On automatic bypass if M1 is on steady YELLOW First maintenance period expired (10,000 hours of operation) UPS in maintenance mode GREEN  ashing Battery test in progress GREEN Load powered from inverter or in high e ciency mod
6.3 MEANING OF THE LUMINOUS BAR.
The luminous bar ( gure 6.1-1) provides an immediate indication of the condition of the power supply to the load:
• Red: power supply not present or shutdown imminent ( ashing).
• Yellow: power supply present but unstable or temporary.
• Green: power supply safe and stable.
6.4 MIMIC PANEL MENU.
The paragraph below describes the menus available on the mimic panel and their functions. The displays are organised into menus and submenus as shown in the  gure 6.1.3-1:
• to access a menu press the ENTER key;
• to return to the higher level press ESC key;
• Use the UP
and DOWN keys to scroll the information available at each level.
When the UPS is connected in parallel 1+1 redundant con guration, the mimic panel shows the system information as if it were a single UPS. Select the UPS number to display information on the individual units.
6.4-1
C
B
A
D
E
D
F
Legend.
A Current menu. B Active sub menu. C Additional values or information. D Scrolling contextual help line. E Scroll bar. F Statistical graphics display.
1
ITALIANOENGLISH
30
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
MIMIC PANEL
6
Parallel UPS
Single UPS
MAIN SYSTEM 1 ALARMS 1.1 ACTIVE ALARMS
2 MEASUREMENTS 2.1 PRESENT MEASURES
2.2 STATISTICS
3 COMMANDS
3.1 IMMEDIATE COMMANDS
3.2 EXTENDED COMMANDS
4 PARAMETERS 4.1 PRESENT CONFIG.
4.2 PRESENT DATA
5 SERVICE 5.1 COMMISSIONING
5.2 SETTING
5.3 SERVICE CODE
6 HYSTORY 6.1 HISTORY LOG
1 ALARMS 1.1 ACTIVE ALARMS
2 MEASUREMENTS 2.1 PRESENT MEASURES
MODULE 1
MODULE 2
4 PARAMETERS 4.1 PRESENT CONFIG
3 COMMANDS
3.1 IMMEDIATE COMMANDS
3.2 EXTENDED COMMANDS
5 SERVICE 5.1 SERVICE CODE
ENGLISH
31
10-40 kVA
MASTERYS IP+
7
OPERATING PROCEDURES
The operating modes to activate and manage the UPS are de ned in this chapter; please also refer to chapters 6 “Mimic panel” and 8 “Menus”.
For UPSs in parallel 1+1 redundant con guration:
• Carry out the procedures on all the UPSs before going on to the next operation.
• All procedures should be carried out on all the UPSs within 30 seconds.
• The mimic panel operations are carried out on the “LEFT” UPS with transformer con gured as concentrator. Be sure to operate on the SYSTEM menu.
7.1 START-UP IN NORMAL MODE.
• Check that all UPS and external battery switches are in position 0 (open);
• Supply the mains and auxiliary mains to the UPS and put switch Q2 into position 1 (mains ON);
• Wait for the mimic panel to switch on;
• Activate the procedure COMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
• Carry out the operations indicated on the mimic panel.
7.2 SHUTDOWN.
Shutdown interrupts the power supply to the load and causes the UPS and the battery charger to stop.
• Activate the procedure COMMANDS > IMMEDIATE COMMANDS > STOP PROCEDURE;
• Wait approx. 2 minutes for the UPS to shut down (the controlled shutdown of any servers is managed with shut-
down software);
• Carry out the operations indicated on the mimic panel.
7.3 EXTENDED OUT OF SERVICE.
If the UPS is deactivated for some time, the batteries must be recharged regularly; they should be recharged every three months.
• Supply the mains and auxiliary mains to the UPS;
• Put switch Q2 into position 1 (mains ON);
• Wait for the mimic panel to switch on;
• Activate the procedure COMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
• Put the battery breaker into position 1 (battery circuit closed).
• Put or keep switches Q6 in position 2 (inverter in output OFF and bypass OFF).
• The battery must be charged for at least ten hours.
• Once ten hours have elapsed, carry out the STOP PROCEDURE (please refer to paragraph “SHUTDOWN” to deac-
tivate the UPS.
ITALIANOENGLISH
32
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
7
OPERATING PROCEDURES
7.4 SWITCHING ONTO MANUAL BYPASS.
Switching onto the manual bypass creates a direct connection between the UPS input and output, completely excluding the equipment control part. This operation is performed in the event of ordinary maintenance on the equipment, so as not to remove the power supply from the load, or in the event of a serious failure while waiting for the equipment to be repaired.
• Activate the procedure COMMANDS > IMMEDIATE COMMANDS > BYPASS PROCEDURE;
• Carry out the operations indicated on the mimic panel.
7.5 RETURN TO NORMAL MODE.
• Put switch Q2 into position 1 (mains ON);
• Wait for the mimic panel to switch on;
• Activate the procedure COMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
• Carry out the operations indicated on the mimic panel.
7.6 EMERGENCY SHUTDOWN (E.S.D.).
Should it be necessary to interrupt the continuous power supply provided by the UPS quickly (emergency shut­down), this can be done by putting switch Q6 to position 0 or, where applicable, by activating the emergency button/switch connected to the ADC card.
The UPS output can only be electrically disconnected by putting Q6 to position 00.
If the UPS is operating from the manual bypass (Q6 in position 2) with mains present, the emer-
gency shutdown does not interrupt the power supply to the load. In emergency conditions all the power supplies upstream of the UPS must be disconnected.
ENGLISH
33
10-40 kVA
MASTERYS IP+
1
MENU
8
8.1 “ALLARMS” MENU
This is used to display all the alarms that are active at the time of access. The alarms menu is activated automatically when an alarm condition occurs.
ALARMS menu
Code Mimic panel description Meaning
A00 GENERAL ALARM A01 BATTERY ALARM Battery circuit failure or faulty operation. A02 OUTPUT OVERLOAD Power required in output over the limits. A06 AUXILIARY MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the bypass have been
exceeded. A07 OVER TEMPERATURE Temperature excessive or ventilation problems. A08 MAINTENANCE BYPASS ACTIVE Q5 in position 1. A17 IMPROPER CONDITION OF USE Improper conditions of use veri ed (load, mains, and temperature). A18 BLOCKING INVERTER FOR OVERLOAD Inverter shutdown due to overload. A20 WRONG CONFIGURATION Error in the con guration parameters (e.g. di erent parameters
between several UPSs in parallel). A22 INPUT MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the recti er have been
exceeded. A23 RECTIFIER GENERAL ALARM Recti er fault. A25 INVERTER GENERAL ALARM Inverter fault. A26 BATTERY CHARGER GENERAL ALARM Battery charger fault. A29 BYPASS GENERAL ALARM Bypass fault. A30 STOP FOR OVERLOAD The duration of the overload has inhibited the bypass. A32 MODULE 1 GENERAL ALARM Module 1 failure. A33 MODULE 2 GENERAL ALARM Module 2 failure. A38 EXTERNAL ALARM 1 Signalling from ADC input. A39 EXTERNAL ALARM 2 Signalling from ADC input. A40 EXTERNAL ALARM 3 Signalling from ADC input. A41 EXTERNAL ALARM 4 Signalling from ADC input. A42 E-SERVICE GENERAL ALARM Alarm that generates automatic sending of a signal to the support
centre (if the service has been activated). A43 REDUNDANCY LOST The power required by the load no longer allows the preset
redundancy N+x to be maintained (for UPSs in parallel only). A44 PERIODIC SERVICE CHECK-UP Warning for periodic check by support service. A47 MAX BATTERY TEMPERATURE Control of the temperature of battery cabinet. A49 BATTERY DISCHARGED The energy available in the battery has been used up. A51 OPTION BOARD GENERAL ALARM Fault related to the optional PCBs in the slots. A56 GENERATOR SET GENERAL ALARM Minor alarm on generator set. A57 GENERATOR SET FAULT Major alarm on generator set. A58 E.S.D. ACTIVATED The remote emergency shutdown command has been activated. A59 BATTERY CIRCUIT OPEN The battery switch is open. A60 FAN FAILURE Fans faulty or blocked. A61 PHASE ROTATION FAULT Wrong phase cycle direction.
1
ITALIANOENGLISH
34
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
MENU
8
8.2 “MEASUREMENTS” menu.
This menu is used to display all the measurements relating to the UPS input, output and to the battery. For models with single phase input or output, the voltage and current displays are adjusted automatically.
PRESENT MEASURES menu
Type of measurements Value Value Value Note OUTPUT STAR VOLTAGE ___ V ___ V ___ V
OUTPUT LOAD __ % __ % OUTPUT ACTIVE POWER ___ kW ___ kW ___ kW OUT APPARENT POWER __._ kVA __._ kVA __._ kVA OUTPUT CURRENT __._ A __._ A __._ A OUTPUT FREQUENCY __._ Hz __._ Hz __._ Hz AUXILIARY VOLTAGE ___ V ___ V ___ V AUXILIARY FREQUENCY __._ Hz __._ Hz __._ Hz INPUT STAR VOLTAGE ___ V ___ V ___ V INPUT PH-PH VOLTAGE ___ V ___ V ___ V INPUT FREQUENCY __._ Hz __._ Hz __._ Hz INPUT APPARENT POWER __._ kVA __._ kVA __._ kVA BATTERY VOLTAGE B1___ V B2___ V BATTERY CAPACITY __ % Charging BACKUP T___MIN Discharging INTERNAL TEMPERATURE __ °C BATTERY TEMPERATURE __ °C Only with a sensor present and set
8.2.1 “Statistical measurements” menu.
Once a (programmable) reference period has been de ned, the system reports measurements that are made avail­able in digital or graphical format. The values that are represented graphically can be used to analyse the situation over the last 24 hours. This informa­tion, together with the programmed interval information, provides an enhanced evaluation on the operating mode of the equipment in order to verify whether certain critical operating situations are repetitive or only casual.
STATISTICAL MEASUREMENTS menu
Measurement Value Option Option
INPUT APPARENT POWER MIN. AVERAGE MAX. ENTER displays ENTER displays weekly graphics 24 hr graphics
BACKUP TIME LESS THAN 2 MINUTES NUMBER OF EVENTS BACKUP TIME BETWEEN 2 AND 5 MINUTES NUMBER OF EVENTS BACKUP TIME MORE THAN 5 MINUTES NUMBER OF EVENTS OUTPUT LOAD MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics OVERLOAD TIME LESS THAN 5 SECONDS NUMBER OF EVENTS OVERLOAD TIME MORE THAN 5 SECONDS NUMBER OF EVENTS REDUNDANCY LOST NUMBER OF EVENTS INTERNAL TEMPERATURE MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics BATTERY TEMPERATURE MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics WORKING TIME ON GEN SET NUMBER OF HOURS
ENGLISH
35
10-40 kVA
MASTERYS IP+
MENU
8
8.3 “COMMANDS” MENU.
This is used to send some immediate commands to activate the UPS or various operating modes. It can also be used to send extended commands to de ne some UPS settings. To activate the commands select the command with
UP
or DOWN , press ENTER, select YES or NO to execute and press ENTER to con rm. The “Extended
controls” menu can only be seen if it is enabled in the menu CONFIGURATION.
IMMEDIATE COMMANDS menu
Command Description
START PROCEDURE UPS start-up command. STOP PROCEDURE UPS shutdown command. MAINTENANCE BY-PASS Control to activate the manual bypass and shutdown of the UPS.
PROCEDURE HIGH EFFICIENCY MODE Activates Eco mode / always on mode. NORMAL MODE Activates normal double conversion operation. ALARM RESET Resets all the alarms. LEDS TEST Performs the test on the mimic panel LEDs.
EXTENDED COMMAND menu
Command Description
MANUAL BATTERY TEST Activates the battery test. BATTERY COMMISSION Activates battery commissioning (use only if necessary for the type of battery). SET LAN DEFAULT VALUE Resets all the values of the LAN. JBUS TUNNELING ENABLE Enables the connection of advanced software (BMS or Uni vision) via the LAN network.
JBUS TUNNELLING DISABLE DHCP ENABLE Enables the automatic allocation of the IP address by the network server.
DHCP DISABLE FORCE MODEM DIAL OUT Forces sending of an immediate test modem call. DISABLE CHECK-UP Deactivates the periodic maintenance message.
ITALIANOENGLISH
36
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
MENU
8
8.4 “PARAMETERS” MENU
Displays only the con guration parameters set for the UPS. The messages in this menu are identi ed by an asterisk in the con gurations service menu. The parameters can only be changed by entering the service / con gurations menu.
CURRENT DATA menu
Message Description
MASTERYS 3/3 30 KVA Displays the size, input and output phases con guration and the serial number of UPS. UC FW. REVISION IIdenti es the software release of microprocessor
RV 000 CKS: 0000 DSP FW. REVISION Identi es the software release of DSP.
RV 000 CKS: 0000
8.5 “SERVICE” MENU.
This is used to change the con guration parameters, insert the warranty activation code and display the service code.
8.5.1 “Activation code” menu.
During activation of the equipment a warranty activation code, made up of four characters, is requested to com­plete the start-up procedure.
MANUFACTURER WARRANTY VALIDATION PLEASE INSERT THE CODE
The activation code is provided directly by the reference Support Centre upon communication of the serial number of the equipment which is displayed in the next message by pressing ENTER.
SEE INSTALLATION MANUAL FOR PROCEDURE SN: 0000000000
When contact is made with the Support Centre for the activation code, detailed information can be obtained on the UPS functions available and on the periodic preventive maintenance programmes.
ENGLISH
37
10-40 kVA
MASTERYS IP+
Once the code is obtained, enter it by pressing ENTER to activate the entry (two asterisks will appear). Select the  rst character with the UP
and DOWN keys and con rm with ENTER to accept the character. Then move
on to the next character. Pressing the ENTER key after selecting the fourth character activates code.
SEE INSTALLATION MANUAL FOR PROCEDURE CODE = - - - - **
An error message is displayed if the code is incorrect. Check that the code displayed corresponds to the one provided by the Support Centre and repeat the procedure.
8.5.2 “Present con gurations” menu.
This is used to change the con guration parameters. Press ENTER. Access is via the password MAST which is keyed in by using the UP
and DOWN keys and
ENTER to go on to the next letter.
Note. Column A shows whether the parameter is visible in the PARAMETERS “CONFIGURATIONS” menu.
PRESENT CONFIGURATIONS menu
A Parameter Description Allowed values
LANGUAGE SELECTION Selects the required language DE-EN-ES-FR-IT, others on request
• NUMBER OF MODULES Only appears in case of parallel systems. 1-6
Indicates the number of UPSs in the system.
• REDUNDANCY LEVEL Only appears in case of parallel systems. FROM 0 TO THE NUMBER
Indicates the number of redundant UPSs. OF MODULES LESS ONE
• OUTPUT VOLTAGE Sets the required output voltage value. 208/220/230/240
• OUTPUT FREQUENCY Sets the required output frequency value. 50/60
• CONVERTER Sets whether the UPS has to operate as a frequency YES/NO
converter.
WARNING!
Set only on UPS with mains power (MAINS) and auxiliary mains (AUX MAINS) separated
and with the auxiliary mains (AUX MAINS) disconnected! Do not set on UPS with common mains lines as it could damage the load!
• AUTO ON Sets whether the UPS has to restart automatically after YES/NO
shutdown due to minimum battery level.
BATTERY AVAILABLE Indicates whether the batteries are present YES/NO
BATTERY TEMP. PROBE Indicates if the battery sensor is present ENABLE/DISABLE
BATTERY TYPE Selects the type of batteries used SEALED, OPEN VENT, NI-CD
BATTERY RECHARGE Selects the type of recharge required AUTO, MAINTENANCE,
2 LEVELS, INTERMITTENT
• BATTERY CAPACITY Sets the battery capacity in Ah. 6,50 ÷ 1.000 (x number of UPS)
• BATTERY ELEMENTS Indicates the number of elements in series
114÷132
in a branch.
MENU
8
ITALIANOENGLISH
38
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
MENU
8
PRESENT CONFIGURATIONS menu
A Parameter Description Allowed values
• BATTERY RECHARGE Sets the recharge voltage compensation value YES/NO TEMP COMPENSATION according to the battery temperature (not present with external battery cabinets.
• BACKFEED TYPE Sets the type of backfeed protection. DISABLE BY-PASS-INPUT ALONE
BY-PASS-INPUT COMMON
• BATTERY TEST Sets the frequency rate of the battery test in days 0÷180 TEST EVERY XX DAYS (zero = do not perform the test).
• LAN IP STATICO Sets the static IP address of the LAN 255.255.255.255 XXX . XXX . XXX .XXX
• SERIAL LINK JBUS Sets the mimic panel jbus node 1÷15 SLAVE NUMBER
DATE AND TIME Sets the date and time DD/MM/YY HH:MM
• EXTENDED COMMAND Enables/Disables the mimic panel extended commands YES/NO
• REMOTE COMMAND Enables/disables the remote controls YES/NO BUZZER Enables/Disables the buzzer YES/NO LCD CONTRAST Sets the LCD display contrast 0/100
• STATISTICS PERIOD Indicates the time in weeks for the calculation of statistics 1÷10
• GSS TIME DELAY Sets the generator start up delay time (visible only when 1÷60 MINUTES the GSS PCB is installed)
E-SERVICE TYPE Select e-service operating mode NONE, MODEM, SMS E-SERVICE TELEPHONE Insert the phone number to call for e-service messages MAX 20 CHARACTERS
NUMBER
1
ENGLISH
39
10-40 kVA
MASTERYS IP+
8.6 “EVENT LOG” MENU.
Shows a list of UPS events in chronological order. It allows the user to analyse UPS operation with regard to variations in the power supply, load or the environment.
8.6-1
Legend.
A Shows date and time of event. B Shows the event code. C Describes the event. D ON/OFF status of event. E Progressive number of event.
A
C
B
D
E
8.5.3 “Service code” menu.
This displays the service code to be sent to the support service to make an accurate and rapid diagnostic of the problem. In the event of a fault, select the menu SERVICE > SERVICE CODE and inform the support centre of the code displayed.
8.5.3-1
8.7 MIMIC PANEL CONCENTRATOR.
In case of 2 UPS units connected in parallel 1+1 redundant con guration, the mimic panels can show an overall view of the system and a detailed view of the UPSs in a single point. The UPS with transformer (on the left side) and the relative mimic panel are con gured as “the concentrator”.
8.7.1 Keyboard blocking procedure.
It is possible to block/unblock the keyboard using the buttons in following sequence: ENTER, DOWN
, UP
, ESC (pressed for over 3 seconds). The sequence must be done in no more than 15 seconds.
MENU
8
1
ITALIANOENGLISH
40
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
9.1 MULTILEVEL COMMUNICATION.
MASTERYS™ is able to manage a variety of serial, contact and Ethernet communication channels simultaneously. The various PCBs and signalling accessories are inserted in the two standard communication slots. This gives MASTERYS™ immediate interfacing and integration  exibility as soon as the unit is installed with no need for trained personnel. The table below lists the possible connections between the communication channels and external devices.
As each channel is independent, simultaneous connections can be made to satisfy the di erent levels of signalling and remote monitoring. See the options paragraph to access the detailed functions of the PCBs installed in the slots.
Please note that two Net Vision cards or two GSS cards cannot be connected simultaneously.
Only one card of a kind can be used.
5 communication levels
Slot 1 Slot 2 RS 232/485 RS 232 RJ45 10BT
ADC card
• •
GSS card
• •
NetVision card
•2 •
2
UniVision pro
• •
4
Remote Panel
BMS
1
1
4
Modem
3
LAN (ethernet)
1
Building Management System.
2
Ethernet adapter with Web/SNMP 10/100Mb functions
(E-service via Web required).
3
For T-service via telephone network.
4
By jbus tunnelling on TCP/IP.
9.1-1
34521
8976
Legend pin RS232/485 C1
1 Not connected 2 RX for RS232 3 TX for RS232 4 Data + 5 GND for RS232 6 Data − 7 Reserved 8 Not connected 9 +12 V
Legend pin Modem C2
1 Reserved 2 RX for RS232 3 TX for RS232 4 Reserved 5 GND for RS232 6 Not connected 7 RTS 8 CTS 9 +12 V
ENGLISH
41
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
9.2 STANDARD LAN WEB PAGE.
By connecting the UPS to a standard LAN network, the operating status of the UPS can be monitored from any PC connected to the network through an html page.
9.2.1 Activation.
Comply with the following operations to activate the mo­nitoring system:
• Connect the UPS to the LAN network (connector A in the
picture aside).
A. If the BOOT DHCP protocol is enabled in the local network: verify the IP address shown in the PARAMETERS >
PRESENT CONFIG > LOCAL AREA NETWORK IP menu on the UPS mimic panel (go to point C).
B. If the BOOT DHCP protocol is not enabled in the local network: Foreword: the following is applicable only if the user is in possession of the administrator rights, otherwise the
procedure indicated below is only valid if using a stand-alone PC (i.e. not in a network of computers with admin­istrator privileges) and a network twisted cable.
Deactivate DHCP mode in the COMMAND> EXT.COMMAND> DHCP DISABLE menu on the UPS mimic
panel.
Read the IP address given in the PARAMETERS > PRESENT CONFIG > LOCAL AREA NETWORK IP menu
on the UPS mimic panel (by default 192.168.7.19).
From a PC connected to the network add the address read by means of the following command: Route add
192.168.7.19 210.67.192.147 (assuming 210.67.192.147 to be the IP address of the PC being used).
C. Open an internet browser and key in the address http://XXX.XXX.XXX.XXX and press send (where xxx.xxx.xxx.xxxx
is the IP address read on the mimic panel).
A
ITALIANOENGLISH
42
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
D. A login and a password will be requested ( g. 8.2.1-2),
the default parameters are:
• login: admin
• password: public
Insert data and click OK.
The main web supervisor page will be displayed and
the functions are described in the following para­graph.
9.2.1-2
9.2.2 Description of the functions available.
The main web page shows the general status of the UPS. This page like all the “sub-pages” are dynamic i.e. the data, images or type of messages shown vary in accordance with the UPS status and con guration.
9.2.2-1
A
B
C
Legend.
A Navigation bar. B Menu bar. C system information area.
1
ENGLISH
43
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
9.2.2.2 Menu bar.
The menu bar displays links to html pages that provide detailed information on the unit and describe how to con­ gure special options.
9.2.2.3 List of alarms.
Shows the list of alarms present in table form.
9.2.2.4 Statistics.
The counter folder shows the number of events that have occurred over a given period of time. The average minimum and maximum values of a measurement can be seen by clicking on the measurement folder. A sampling time from one to 10 weeks can be set by clicking on the period folder.
9.2.2.5 UPS management.
The commands folder shows the commands that can be sent to the UPS. The setting folder shows the parameter settings on the UPS.
9.2.2.6 Change language.
Click on the relative  ag to choose a di erent language.
9.2.2.1 Navigation bar.
Consult the on-line guide for details about the various icons. The graphics interface shows a number of icons, each of which is associated to a speci c function:
Connection to the www.socomec.com web site. Regularly check the news that the SOCOMEC group publishes on the site so as to take full advantage of the MASTERYS
TM
unit.
UPS information: Serial number, type, power, etc.
Alarm present: shows the alarms table (this icon appears when the UPS detects an anomaly).
Generator operating mode (this icon appears when the UPS is powered by the generator).
Technical support department e-mail address. This connection opens the e-mail program and automati­cally  lls in the addressee and subject lines.
Information on the network interface: a help page in html is loaded.
1
ITALIANOENGLISH
44
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
9.2.2.7 Local network.
Enable the user to modify the network communication parameters.
Dynamic IP address: if enabled, the IP address is automatically assigned by the network server
Static IP address: the IP address is used if the dynamic IP address is disabled.
Network mask: this is used if the dynamic IP address is disabled.
Gateway: the gateway address used to send TCP/IP data out of the local network.
Password: allows the user to change the password to access the html. To authorise access only to users that have a password. Insert the new password and write it down in case of need.
JBUS TCP/IP Port: used to accept a JBUS frame through LAN tunnelling .
Client JBUS IP address to be authorised: if a speci c IP address is inserted in this box, then only that address/ user will be able to access the html pages. If the address 0.0.0.0 is used, all the PCs on the network will be able to access the supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all users.
Software updating: if on, allows the supervisor to be updated.
Page refresh (sec): the page refresh rate can be set.
Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit connected (this value is inserted in SMS messages or e-mails).
NTP Server: indicates the IP address of the time server to automatically update the date and time on the system.
GMT Correction (minutes): indicates local time and the o set in minutes with respect to the zero meridian of Greenwich
Apply the parameter settings: restarts the monitoring system with the new settings.
9.2.2.8 Con guring e-mail.
This menu lets the user con gure parameters for sending e-mails.
Event that will send an e-mail: as required, the e-mail may be deactivated or activated to send a message in the event of serious alarms or for all alarm conditions.
E-mail server address: insert the IP address (xxx.xxx.xxx.xxx) of the SMTP e-mail server from which you wish to send messages.
e-mail account: Insert the UPS’s dedicated “user account”, which is often the same as the user’s e-mail address.
Addressee: insert the e-mail address to which the alarm messages will be sent.
Periodic connection: set the frequency at which an e-mail is to be sent to verify the connection.
Force an e-mail to be sent now: by selecting “execute” a test e-mail will be sent.
9.2.2.9 Modem con guration.
This menu lets the user con gure the parameters of a modem
Rings before reply: Set the number of rings after which the modem should respond.
Outgoing call
1
: sets the type of outgoing call: SMS or E- service (to activate e-service a contract to the support
centre is required).
Reason for callout: set the reasons for the call (all alarms or for serious faults).
Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit connected (this value is inserted in SMS messages or e-mails).
1
ENGLISH
45
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
Telephone number: insert the number to be called.
Modem initialisation: initial string to be sent to the modem (for special con gurations or certain types of mo­dem).
Connection period: set the number of days between two calls even if no faults occur.
Force an outgoing call: by selecting EXECUTE a test connection is immediately carried out.
1 Activating one con guration excludes the other; therefore if an E-service/T-service contract is subscribed, calls in output cannot be con gured. 2 In the event that the E-service/T-service contains the control code provided by after-sales personnel.
9.2.2.10 Software updating.
This html page is used to update automatically the monitoring software, which could be useful to add new languages or the SNMP function. Once the  le has been acquired (by requesting it from the support service) select it with the browse button. Click on the “start update” button; once the update has been completed, reload the html page.
9.2.2.11 System Information Area.
This area of the screen page shows the measurements and the UPS op­erating mode.
• Click on icon A to display the input measurements.
• Click on icon B to display the bat­tery measurements.
• Click on icon C or D to display the output measurements.
9.2.2.12 How to con gure max-connections-per-server for FIREFOX.
In order to increase the LAN performances:
1. Type about:con g in the address bar and accept dialog box (if necessary).
2. Type server in the  lter  eld box and press return.
3. Set the network.http.max-connections-per-server value to 2 (double click on the item and set 2 in the dialog
box).
A
C
B
D
1
ITALIANOENGLISH
46
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
COMMUNICATION
9
9.3 ACCESSORIES AND SW OPTIONS.
A large number of SW solutions can be adopted on MASTERYS
TM
thanks to its advanced communication facilities.
These solutions have been specially designed for the e cient management of power protection devices.
UNI VISION PRO is the solution for managing a UPS connected to the local server via RS232 interface or via LAN network. It is normally used at departmental level to automatically shutdown the systems and ensure secure control of the UPS that in turn protect servers and workstations. The main functions are:
• Graphic monitoring of the UPS via web browser
• Local shutdown of a server connected via serial interface
• Remote shutdown via proxy agent and optional Java shutdown clients
• Noti cation of anomalies via e-mail to a maximum of 8 addresse.
NET VISION is a solution for managing UPS units connected directly to the local network. It is normally used on medium/large, complex networks and in multi-server environments where the IT manager centrally controls all the network resources. The physical position of the UPS is not signi cant. The main functions are:
• 10/100Mb Ethernet connection (RJ45)
• Graphic monitoring of the UPS via web browser
• Remote shutdown of up to 40 computers
• Noti cation of anomalies via e-mail to a maximum of 8 addresses
• UPS management using SNMP protocol
• Diagnostics via Internet o ered by e-Service.
Java & .NET shutdown Client (JNC) is an optional Java application to be installed on a server for the automatic shutdown of the computers on the network before the UPS stops due critical operating conditions (imminent battery failure, overload, etc.). It is supplied as an option and can be associated to the UNI VISION PRO or NET VISION commu­nication solutions. The main features/functions are:
• Use of the TCP/IP standard network protocol
• Graphics interface for easy con guration
• Minimum use of CPU resources
• Personalisation of shutdown parameters and script
• Continuous monitoring of the e ciency of the connection to the UPS.
T.Service is a cutting edge supervision service ensuring 24/7/365 service. It ensures e ective prevention and con­stant monitoring of the system. Communication between the UPS and the local Socomec Service Centre is via modem (free-air GSM or ANALOG  xed line). The auto-diagnostic system analyses UPS operating conditions, identi­ es faults and monitors environmental conditions such as temperature, overload, avoiding the risk of equipment stoppages. In the event of a failure, the system immediately sends a “diagnostic report” via modem to the Service Centre. Any emergency situation is managed and resolved extremely quickly and remotely by the Service Centre, with immediate intervention on site if needed.
ENGLISH
47
10-40 kVA
MASTERYS IP+
PROBLEM SOLVING
10
The alarm messages displayed enable an immediate diagnosis. Alarms are divided into two categories:
• Alarms related to the UPS external circuits: input mains, output mains, temperature and environment.
• Alarms related to the UPS internal circuits: in this case, the corrective actions will be carried out by the After Sales Department.
10.1 SYSTEM ALARMS.
• A02: output overload.
The power required by the loads is higher than the power available. Check that the load is well balanced on the three phases by checking the measurements on the display. If needed,
disconnect any loads that do not need uninterruptible power.
Important!
The accepted overload time limit is de ned in the technical speci cations. When this time limit is exceeded, the loads will no longer be powered by the inverter.
• A06: auxiliary mains out of tolerance. The auxiliary mains exceeds the acceptable tolerance values. Possible causes are:
• No voltage or frequency present or voltage and frequency out of acceptable values (see the technical speci ca-
tions).
• The frequency is subject to continuous variations (typical with power supplied from an incorrectly sized GE).
• A07: temperature over the limits.
The UPS internal temperature is higher than 50 °C (please refer to Measurements menu on the mimic panel). Check the ventilation or air conditioning system in the UPS room.
• A08: maintenance bypass activated.
The output disconnecting switch Q6 is in position 2 (maintenance bypass). The load is therefore powered directly by mains power supply.
• A17: improper conditions of use.
This alarm does not indicate a malfunction or failure of the UPS, but an incorrect use/sizing of the system. It is activated in the event of:
• Operation for long periods at high temperatures (battery deterioration)
• High number of overloads (wrong sizing)
• Continuous battery discharging (mains not stable)
• High number of switches onto the bypass (high impulsive loads)
• A22: input mains out of tolerance.
The input mains is not present or not su cient (voltage and/or frequency values incorrect with reference to the technical data); if there is no input mains outage, check if no protections upstream of the UPS have tripped. Check that the voltage applied and frequency values are in compliance with the values set on the mimic panel.
• A38, A39, A40, A41: external alarm 1, 2, 3, 4.
One of the ADC PCB inputs has been activated; check the situation of the devices connected to this PCB.
• A56, A57: generator general alarm.
The generator has sent an alarm; check directly on the GE.
ITALIANOENGLISH
48
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
10
PROBLEM SOLVING
• A61: wrong phase cycle direction.
The phase cycle sequence is incorrect. In this case, invert two phases of the input mains. For a UPS with separate auxiliary mains, exchange the two phases of the auxiliary mains only.
10.2 UPS ALARMS.
• A01: battery alarm.
Failure or problem on the battery circuit. Check that the battery switch is closed.
• A18: inverter blocked due to overload.
Reduce the load rate applied to the UPS and reset the alarms.
• A20: wrong con guration.
Error in the con guration parameters; please contact the support service.
• A30: block due to overload.
Reduce the load rate applied to the UPS and reset the alarms.
• A42: T.Service general alarm.
The MASTERYS™ products can be remotely serviced. This alarm indicates that a procedure for analysing the UPS failure has been activated by the support centre (if an e-service contract has been concluded).
• A44: programmed control.
The equipment has to undergo periodic checks by the support service in order to ensure optimum perform­ance and e ciency. If the “Programmed Control” signal appears on the mimic panel, the equipment should be inspected by an adequately trained technician.
• A59: battery circuit open.
Battery switch open.
• A60: fan failure.
Fault in the ventilation system; check that the air inlet at the front and the air outlet at the back of the UPS are not obstructed.
ENGLISH
49
10-40 kVA
MASTERYS IP+
PROBLEM SOLVING
10
10.3 PREVENTIVE MAINTENANCE.
We would like to inform you that specialised periodic maintenance (with yearly frequency) is recommended for the MASTERYS™, in order to o er optimum operating e ciency and avoid downtime of the equipment. It is strongly recommended to give due consideration to any requests for preventive maintenance automatically displayed with alarm message M29. All operations on the equipment must be only carried out by SOCOMEC UPS personnel or by authorised support personnel. Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts subject to wear if necessary (typically batteries, fans and capacitors).
10.3.1 Batteries.
The state of the battery is fundamental to UPS operation. Thanks to the Expert Battery System, the information relating to the state and the conditions of use of the battery are processed in real time and the recharging and discharging procedures are selected automatically in order to optimise battery life expectancy and o er maximum performance. Furthermore, during the operating life of the battery, MASTERYS™ stores statistics on the conditions of use of the battery for analysis. Since the expected life of the batteries is very much dependent on operating conditions (number of charging and discharging cycles, load rate, temperature), a periodic check by authorised personnel is recommended.
When replacing the batteries, use the same type and con guration by placing them in the appro-
priate containers so as to avoid the risk of acid leakage. The replaced batteries must be disposed of at authorised recycling and disposal centres. Do not open the plastic cover of the batteries as they contain harmful substances.
10.3.2 Fans.
The life of the fans used to cool the power parts is dependent on the using and environmental conditions (tem­perature, dust). Preventive replacement by an authorised technician is recommended within four years (in normal operating condi­tions).
When needed, fans should be replaced as per speci cations by SOCOMEC UPS.
10.3.3 Capacitors.
The equipment houses electrolytic capacitors (used in the recti er and inverter section) and  ltering capacitors (used in the output section), whose life is dependent on using and environmental conditions. The average expected life of these components is shown below:
• Electrolytic capacitors: 5 years;
• Filtering capacitors: 7 years.
In any case the e ective state of the components is veri ed during preventive maintenance.
ITALIANOENGLISH
50
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
11
OPTIONS
11.1 KIT GSS (GLOBAL SUPPLY SYSTEM).
To be installed on the slot “L”, this kit optimises generator sizing and control when connected to the UPS input. The generator set can be instructed to start up automatically the moment the mains power is lost, or alternatively, following a user-set time period without the mains power, and/or when the batteries have discharged to their residual capacity.
11.2 ISOLATION CONTROLLER.
Installed on the DIN rail “F”, this device continually checks the transformer isolation, displaying an alarm message on the mimic panel. The management of the option is possible via ADC card without temperature sensor (refer to paragraph 3.9 “ADC card”)
11.3 REMOTE MIMIC PANEL.
This device monitors and interacts with the UPS through a serial link RS 485 (maximum distance of 175 m) 25 m cable supplied standard; 50 m cable available as an option).
Legend.
A LAN RJ45 connector for Ethernet. B Serial RS232 connector for Modem. C Serial RS232/485 connector for after sales. F DIN rail (under the panel) L Slots for communication cards (ADC card
installed as standard, 1 slot available for an additional card).
Masterys IP+ with battery.
Masterys IP+ without battery.
CBA
F
L
F
L
ENGLISH
51
10-40 kVA
MASTERYS IP+
11.4 ACS PCB.
To be installed on the slot “L”, it synchronises UPS output with an external power source (another UPS, even of a di erent brand, generator or transformer).
11.5 ADC CARD WITH TEMPERATURE SENSOR.
This card can be used to manage up to four normally closed or normally open outputs and up to three digital inputs in con gurable mode. If more than one ADC card is used simultaneously, the dip-switch con gurations must be di erent. Secure the card with the appropriate screws.
11.6 EXTERNAL BACK-FEED PROTECTION.
External devices can be installed to protect against the backfeed of dangerous currents, both on the MAINS SUPPLY and on the AUX MAINS SUPPLY. These devices have to be connected to the terminals provided (see picture 11.6-1). Refer to the following paragraphs for details on the electrical connections and on activating the chosen protec­tion.
Attention.
In some failure conditions (earth leakage, signi cant phase dispersion or in case of non-isolated neutral system), high potential can be detected in the neutral. It will therefore be necessary to install either adequate neutral switching or protection system.
11.6-1
Backfeed connection
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
OUT
TRANSFORMER
AUX MAINS
SUPPLY
L11 L21 L31 N1 L14 L24 L34 N4 N3L13 L23 L33 L12 L22 L32 N2L1 L2 L3 N
COM1
COM2
NC1
NC2
11
OPTIONS
ITALIANOENGLISH
52
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
11
OPTIONS
11.6.1 Protection on Mains Supply and on Auxiliary Mains Supply.
Activating UPS protection on the mimic panel: access the Con guration menu on the mimic panel (see the Con-  guration Menu section in the manual) and set the BACKFEED TYPE parameter to 2.BYPASS-INPUT Alone.
Diagram of principle.
Legend.
A Distribution panel B Coil remote switch L1-L2-L3-N Input power source L11-L21-L31-N1 Backup power source M1 Input power terminals M2 Backup power terminals M3 Backfeed terminals T1 Remote switch
1
T2 Remote switch
1
SW1 Input power switch on the distribution SW2 Backup power switch on the distribution
11.6.1-1
A UPS
L11
SW2
L21
L31
N1
T2
B
M2
L11
L21
L31
N1
NC1
COM1
NC2
COM2
M3
L1
SW1
L2
L3
N
T1
B
M1
L1
L2
L3
N
UPS 3/3 with separate auxiliary supply.
11.6.1-2
A UPS
SW2
L11
N1
T2
B
M2
L11
N1
L1
SW1
L2
L3
N
T1
B
M1
L1
L2
L3
N
NC1
COM1
NC2
COM2
M3
UPS 3/1 with separate auxiliary supply.
1
Remote switches - rated current
Model T1 T2
10 3/1 32 A AC1 45 A AC1 15 3/1 32 A AC1 45 A AC1 20 3/1 45 A AC1 60 A AC1 30 3/1 60 A AC1 60 A AC1 10 3/3 32 A AC1 32 A AC1 15 3/3 32 A AC1 32 A AC1 20 3/3 45 A AC1 45 A AC1 30 3/3 60 A AC1 60 A AC1 40 3/3 90 A AC1 90 A AC1
ENGLISH
53
10-40 kVA
MASTERYS IP+
OPTIONS
11
11.7 PROFIBUS.
On request, the UPS can be provided with a Pro bus pro­tocol converter, installation software, con guration software and user manuals (detail P on the picture aside).
11.8 GSM MODEM.
Enables sending of SMS messages regarding the equipment’s operating status.
11.9 SERIAL ISOLATED RS232 DB9 CONNECTION and RS485 PCB.
To be installed on the slot “L”. A serial RS232 DB9 connector and an isolated RS485 connector are available on the card. For parallel system: the option must be installed only in the concentrator UPS.
11.10 COLD START.
The Cold Start option allows the starting up of the UPS on Battery Mode when both Mains and AUX Mains are miss­ing. Be sure that both Mains and AUX Mains are not present (otherwise the UPS will not start using the Cold Start). Perform the following operations to switch on the UPS on Battery Mode:
• close the internal/external battery breaker
• press button P1 (postion P on the drawing above) for about 4 seconds
• wait for the standard start up procedure
In case of battery discharged, the Cold Start could not be able to start up the UPS. When either Mains or AUX Mains return, the Cold Start circuit automatically excludes itself.
P
ITALIANOENGLISH
54
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
TECHNICAL SPECIFICATIONS
11
Models
10 15 20 30 40
Input/Output phases 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3 3/3
Electrical speci cations - Input
10 15 20 30 40
Mains voltage 3P+N 400 V +20% -15% (up to -35% @70% of nominal load) Input frequency 50-60 Hz ±10% Input power factor 0,99 THDI < 2.5%
Electrical speci cations - Output
10 15 20 30 40
Output voltage (three phase + neutral) 230 V single phase (selectable: 208
(1)
/220/230/240 V) ±1%
400 V three phase (selectable 360
(1)
/380/400/415 V) ±1% Frequency 50-60 Hz ±2% (from 1% to 8% if generator is used) Automatic bypass nominal output voltage ±15%
(from 10% to 20% selectable if generator is used) Nominal power (kW) 9 13,5 18 27 36
Overload on automatic bypass @ 25 °C
(2)
20 minutes @ 125%, 4 minutes @ 150%, 2 minutes @ 200%
Crest factor 3:1 Voltage distortion 1% with linear load
(1) @ Pout = 90% Pnom. (2) With transformer on output or bypass.
Environment
10 15 20 30 40
Operating temperature 0÷40 °C (15÷25 °C recommended for longer battery life) Storage temperature -5÷45 °C Relative humidity 0÷95% condensation-free Max. altitude 1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max Acoustic noise (dB) < 52 < 52 < 52 < 55 < 55 Required cooling capacity (m
3
/h) 280 280 280 465 465 Dissipated power max (W) 680 900 1150 1750 2300 Dissipated power (BTU/h) 2300 3050 4070 6050 7900
Standards
10 15 20 30 40
Safety (TÜV SÜD certi ed) EN 62040-1-1, EN 60950-1 Type and performance EN 62040-3 (VFI-SS-111) EMC EN 62040-2 Product certi cation CE, TÜV SÜD Protection level IP31
600
800
1400
Weight: up to 500 kg
WEIGHT
10-40 kVA
MASTERYS IP+
PARALLEL CONFIGURATIONS
ITALIANOENGLISH
56
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
MASTERYS IP+ allows both parallel power and parallel 1+1 redundant con gurations.
WARNING!
Parallel power con guration is possible ONLY with the transformer connected in the input (Mains or Auxiliary Mains).
WARNING!
Parallel with transformer connected to the output is possible only by using the speci c kit including two speci c UPS (one with transformer and one without transformer) for 1+1 redundant con guration.
WARNING!
Parallel con guration must only be activated by SOCOMEC UPS quali ed personnel.
Use the UPS in accordance with the technical speci cations given in this Installation and Operating Manual. The UPS units connected in parallel con guration are identical to a standard UPS, as a result safety, shipping and installation recommendations in chapters 2 and 3 also apply.
INSTALLATION.
• Parallel power con guration: Please check that the transformer is connected on the input side (Mains or Aux Mains - refer to paragraph 3.5).
UPS units operating in parallel are interconnected using control cables and are con gured di erently depending on the position they are assigned. For this reason the units have a position label:
• The “LEFT” label means that the unit must be positioned to the left.
• The “RIGHT” label means that the unit must be positioned to the right.
• The “INTERNAL” label (used only on systems with three UPS) means that this unit must be positioned between
the two other cabinets.
• Parallel 1+1 redundant con guration:
UPS units operating in parallel 1+1 redundant con guration are interconnected using control cables and are con gured di erently depending on the position they are assigned. For this reason the units have a position label:
• The “LEFT” label means that the unit must be positioned to the left (UPS with transformer con gured as concentrator).
• The “RIGHT” label means that the unit must be positioned to the right (UPS without transformer).
The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough room for an external battery cabinet to be inserted beside each UPS.
WARNING!
The UPS must be secured to the  oor (see paragraph 3.3).
POWER CONNECTIONS.
• The power supply to each unit must be protected as indicated in the table in paragraph 3.4.
• The cross section and length of the input and output cables must be identical for all the units.
• The phase rotation must be the same for all units connected in parallel.
PARALLEL CONFIGURATION
ENGLISH
57
10-40 kVA
MASTERYS IP+
• Cables of the same length and cross section must be used for the connection between the general power switch
, the switches ➋ and the respective UPS units.
• If a di erential switch is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel, it must be a selective type and the trigger value must be 0.5 A by the number of UPS
connected in parallel.
CONTROL CONNECTIONS.
In order for units connected in a parallel con guration to operate correctly, control cables are required to exchange data between the various UPS units making up the parallel system, for management of correct load sharing and synchronisation logic. The cables in question are supplied with the UPSs.
PARALLEL CONFIGURATION
ITALIANOENGLISH
58
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
PARALLEL CONFIGURATION
RECOMMENDED PARALLEL POWER CONFIGURATION.
For the connections also refer to chapter 3.
15 m max 25 m max
Legend. 1 Main di erential magneto-thermal
switch.
2 Magneto-thermal switch. 3 “Parallel bus” cable. 4 Output switch. 5 System shutdown switch. 6 Distribution. I Internal UPS. L Left UPS R Right UPS
❶❶
L RI II I
MAINS AUXILIARY MAINS
ENGLISH
59
10-40 kVA
MASTERYS IP+
PARALLEL CONFIGURATION
15 m max 25 m max
❶❶
➋➋
L R
MAINS AUXILIARY MAINS
RECOMMENDED PARALLEL 1+1 REDUNDANT CONFIGURATION
For the electrical connections refer to page 60.
Legend. 1 Main di erentialmagneto-thermal
switch.
2 Magneto-thermal switch. 3 “Parallel bus” cable. 4 Output switch. 5 System shutdown switch. 6 Distribution. 7 Power connections (refer to page 60) L Left UPS R Right UPS
ITALIANOENGLISH
60
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
PARALLEL CONFIGURATION
RIGHT UPS
L13 L23 N3L33
IN
TRANSFORMER
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
OUT
TRANSFORMER
L11 L21 L31 N1N1L14 L24 L34 N4 L12 L22 L32 N2L1
L1
L2 L3 N
AUXILIARY
MAINS
MAINS
SUPPLY
L11 L21 L31L2 L3 N
AUXILIARY
MAINS
EXT. BATTERY
+B2 -B2 -B1 +B1
TA1 TA2 TA 5TA4
TA1 TA2 TA 5TA4
OUTPUT
L14 L24 L34 N4
AUXILIARY
MAINS
AUXILIARY
MAINS
TO
LOAD
LEFT UPS
MAINS
MAINS
cable section: ø 1.5 - 2.5 mm
2
Cables provided
3/3
PARALLEL 1+1 REDUNDANT CONFIGURATION CONNECTIONS.
Output transformer (standard con guration).
WARNING!
Before connecting TA4 and TA5 remove the bridge cable from TA4-TA5 on both UPSs
Cables
Cables
provided
provided
ENGLISH
61
10-40 kVA
MASTERYS IP+
PARALLEL CONFIGURATION
RIGHT UPS
LEFT UPS
EXT. BATTERY
+B2 -B2 -B1 +B1
OUTPUT
MAINS
SUPPLY
IN
TRANSFORMER
L11A L11 N11A N11 L14 N4 N3L13 L12 N2L1 L2 L3 N
AUXILIARY
MAINS
OUT
TRANSFORMER
EXT. BATTERY
+B2 -B2 -B1 +B1
MAINS
SUPPLY
L11A L11 N11A N11 L14 N4L1 L2 L3 N
AUXILIARY
MAINS
OUTPUT
AUXILIARY
MAINS
AUXILIARY
MAINS
TO
LOAD
MAINS
MAINS
Cables provided
3/1
PARALLEL 1+1 REDUNDANT CONFIGURATION CONNECTIONS.
Output transformer (standard con guration).
Cables
Cables
provided
provided
IP52 VERSION
10-30 kVA
MASTERYS IP+
ITALIANOENGLISH
64
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
IMPORTANT.
• This section provides important instructions for the safe use, movement and connection of MASTERYS IP+ IP52 version.
• All the information included in this manual are valid except for the following ones that are speci c for MASTERYS IP+ IP52 version.
• To ensure the IP52 protection, the  oor roughness tolerance must be 3 mm max.
IP52 VERSION
INSTALLATION OF THE UNIT.
MASTERYS IP+
1 2 3
ENGLISH
65
10-40 kVA
MASTERYS IP+
IP52 VERSION
SURFACE ROUGHNESS TOLERANCE.
IDENTIFYING SWITCHING AND CONNECTION ORGANS.
Legend.
A LAN RJ45 connector for Ethernet. B Serial RS232 connector for Modem. C Serial RS232/485 connector for after
sales.
D Cable trunking for control cables. E Fans. F DIN rail (behind the panel). G Fuses. H Power connections (behind the plastic
protection).
I Slots for communication cards (ADC card
installed as standard, 1 slot available for an additional card)..
L Door air  lters. Q2 Input switch (MAINS). Q6 Output switch.
Q2 Q6
E
L
D
I
F
G
H
Masterys IP+ IP52 version without batteries.
CBA
3 mm max
ITALIANOENGLISH
66
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
IP52 VERSION
PREVENTIVE MAINTENANCE.
Please also refer to paragraph 10.3.
The user is allowed ONLY to replace the front door internal air  lter. A spare part kit is avail­able as options. It is strongly recommended to replace the front door internal air  lters at least every 6 months, but their wear can be increased by the environ­mental conditions. Any other maintenace operation on the equip­ment must be only carried out by SOCOMEC UPS personnel or by authorised support per­sonnel.
Air  lters
INSTALLATION PROCEDURES AND INSTRUCTIONS.
Please also refer to paragraph 3.6. To ensure the IP52 protection, lead the power
cables as shown in the picture aside.
Not provided
ENGLISH
67
10-40 kVA
MASTERYS IP+
IP52 VERSION TECHNICAL SPECIFICATIONS
Models
10 15 20 30
Input/Output phases 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3
Electrical speci cations - Input
10 15 20 30
Mains voltage 3P+N 400 V +20% -15% (up to -35% @70% of nominal load) Input frequency 50-60 Hz ±10% Input power factor 0,99 THDI < 2.5%
Electrical speci cations - Output
10 15 20 30
Output voltage (three phase + neutral) 230 V single phase (selectable: 208
(1)
/220/230/240 V) ±1%
400 V three phase (selectable 360
(1)
/380/400/415 V) ±1% Frequency 50-60 Hz ±2% (from 1% to 8% if generator is used) Automatic bypass nominal output voltage ±15%
(from 10% to 20% selectable if generator is used) Nominal power (kW) 8 12 16 24
Overload on automatic bypass @ 25 °C
(2)
20 minutes @ 125%, 4 minutes @ 150%, 2 minutes @ 200%
Crest factor 3:1 Voltage distortion 1% with linear load
(1) @ Pout = 90% Pnom. (2) With transformer on output or bypass
Environment
10 15 20 30
Operating temperature 0÷35 °C Storage temperature -5÷45 °C Relative humidity 0÷95% condensation-free Max. altitude 1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max Acoustic noise (dB) < 52 < 52 < 52 < 55 Required cooling capacity (m
3
/h) 625 625 625 625 Dissipated power max (W) 680 900 1150 1750 Dissipated power (BTU/h) 2300 3050 4070 6050
Standards
10 15 20 30
Safety EN 62040-1-1, EN 60950-1 Type and performance EN 62040-3 (VFI-SS-111) EMC EN 62040-2 Product certi cation CE Protection level IP52
600
800
1400
Weight: up to 500 kg
WEIGHT
www.socomec.com
VALID FOR FRANCE VALID FOR ITALY
ISO 9001 FM 28237
ISO14001
EMS 553476
YOUR DISTRIBUTOR
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 951 300 € R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 admin.ups.fr@socomec.com
SOCOMEC Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY Tel. +39 0444 598611 - Fax +39 0444 598622 hr.ups.it@socomec.com
SALES, MARKETING AND SERVICE MANAGEMENT
SOCOMEC Paris
95, rue Pierre Grange F-94132 Fontenay-sous-Bois Cedex - FRANCE Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12 dcm.ups.fr@socomec.com
Socomec worldwide
IN WESTERN EUROPE
BELGIUM
B - 1190 Bruxelles Tel. +32 (0)2 340 02 34 info.ups.be@socomec.com
FRANCE
F - 94132 Fontenay-sous-Bois Cedex Tel. +33 (0)1 45 14 63 90 dcm.ups.fr@socomec.com
GERMANY
D - 68309 Mannheim Tel. +49 (0) 621 71 68 40 info.ups.de@socomec.com
ITALY
20098 San Giuliano Milanese (MI) Tel. +39 02 98 242 942 info.ups.it@socomec.com
PORTUGAL
2640-486 Mafra Tel. +351 261 812 599 info.ups.pt@socomec.com
SPAIN
E - 08329 Teià (Barcelona) Tel. +34 935 407 575 info.ups.sib@socomec.com
THE NETHERLANDS
NL - 3991 CD Houten Tel. +31 (0)30 760 0911 info.ups.nl@socomec.com
UNITED KINGDOM
Cirencester - GL7 5XL Tel. +44 (0)1285 863300 info.ups.uk@socomec.com
OTHER COUNTRIES
Tel. +34 935 407 575 info.ups.europe@socomec.com
IN EASTERN EUROPE, MIDDLE EAST, AFRICA
UNITED ARAB EMIRATES
371355 Dubai airport free zone Dubai (United Arab Emirates) Tel.: +971 (0) 4 29 98 441 info.ups.ae@socomec.com
POLAND
01-625 Warszawa Tel. +48 22 825 73 60 info.ups.pl@socomec.com
ROMANIA
023383 Bucharest Tel. +40 21 319 36 88 ( 89, 81, 82) info.ups.ro@socomec.com
RUSSIA
125167 - Moscow Tel. +7 495 775 19 85 info.ups.ru@socomec.com
SLOVENIA
SI - 1000 Ljubljana Tel. +386 1 5807 860 info.ups.si@socomec.com
TURKEY
34357 Istanbul Tel. +90 (0) 216 540 71 20 info.ups.tr@socomec.com
OTHER COUNTRIES
Tel. +39 0444 598 611 info.ups.emea@socomec.com
IN ASIA PACIFIC
AUSTRALIA
Macquarie Park NSW 2113 Tel. +61 2 9325 3900 info.ups.au@socomec.com
CHINA
Chaoyang, Beijing 100016 P.R., China Tel. +86 10 59756108 info.ups.cn@socomec.com
INDIA
Guindy, Chennai – 600 032 Tel. +91 44 3921 5400 info.ups.in@socomec.com
MALAYSIA
47301 Petaling Jaya.- Selangor, Malaysia Tel. +603 7804 0850 info.ups.my@socomec.com
SINGAPORE
Singapore 408694 Tel. +65 6506 7600 info.ups.sg@socomec.com
THAILAND
Chatujak Bangkok 10900 Tel. +66 2 941-1644-7 info.ups.th@socomec.com
VIETNAM
Ho Chi Minh City Tel. +84-839734.990 info.ups.vn@socomec.com
ASIA PACIFIC HEAD OFFICE
Tel. +65 6507 9770 info.ups.apac@socomec.com
IN AMERICA
LATIN AMERICAN COUNTRIES
Tel. +34 935 407 575 info.ups.sib@socomec.com
*IOMMASIPXX09-GB 04*
IOMMASIPXX09-GB 04 12.2012
Loading...