MASTERYS GP4
From 60 to 160 kVA
101
4.3 RECOMMENDED PROTECTIONS
RECOMMENDED PROTECTION DEVICES - Rectifier
(1)
Rated power (kVA) 60 80 100 120 160
C curve circuit breaker (A) 125 160 250 315
gG fuse (A) 125 160 250 315
RECOMMENDED PROTECTION DEVICES - General bypass
(2)
Rated power (kVA) 60 80 100 120 160
Max I
2
t supported by the bypass (A2s) 120000 400000 400000
Max Ipk supported by the Bypass(A) 5000 9000 9000
Conditional short circuit current rating (Icc) 10 kA
C curve circuit breaker (A) 160 200 250 400
gG fuse (A) 160 200 250 400
RECOMMENDED PROTECTION DEVICES - Input residual current circuit breaker
(3)
Rated power (kVA) 60 80 100 120 160
Input residual current circuit breaker 0.5 A Selective type B
RECOMMENDED PROTECTION DEVICES - Output
(4)
Rated power (kVA) 60 80 100 120 160
C curve circuit breaker
(3)
(A) ≤ 20 ≤ 25 ≤ 32 ≤ 40 ≤ 50
B curve circuit breaker
(3)
(A) ≤ 40 ≤ 50 ≤ 63 ≤ 80 ≤ 100
CABLES - Maximum cable section
(5)
Rated power (kVA) 60 80 100 120 160
Rectifi er terminals (4x)
bus bar with holes ø 8 mm
70 mm
2
(fl exible cable and rigid
cable)
bus bar with holes ø 10 mm
2x120 mm2 (fl exible cable and
rigid cable)
bus bar with
holes ø 10 mm
2x150 mm2
(fl exible cable
and rigid cable)
Bypass terminals (4x)
Battery terminals (3x)
Output terminals (4x)
1. Rectifier protection should only be considered in the event of separate inputs. Recommended values to avoid unwanted
tripping with UPS at full power. When the bypass and rectifier inputs are combined (common input), the general input
protection rating must be the highest of the two (bypass or rectifier).
2. Recommended values to avoid unwanted tripping with UPS at full power. A current limiting device has to be used in case of
maximum i
2
t and Ipk of the SCR by-pass is exceeded. When the bypass and rectifier inputs are combined (common input),
the general input protection rating must be the highest of the two (bypass or rectifier).
3. RCD is not necessary when the UPS is installed in a TN-S system. RCD is not permitted on TN-C systems. If a RCD is
required a B-type should be used. RCD must be coordinate with residual current circuit breakers downstream of the UPS
connected to the UPS output. If the bypass network is separate from the rectifier circuit, or in the event of parallel UPS, use a
single residual current circuit breaker upstream of the UPS.
4. Protection tripping downstream of the UPS with inverter short circuit current (Worst case = AUX MAINS not present). In the
Normal case, with AUX MAINS present, fault clearing is determined by the Mains short-circuit capability. The rating of the
protection can be increased “n” times downstream of a parallel UPS system, with “n” equal to the number of parallel UPS
units.
5. Use cable with tin-plated eyelets for the connection